These Category IV, highly efficient, compact, condensing
type furnaces are designed for residential and commercial
installations in a basement, closet, alcove, recreation room
or garage where the ambient temperature is above 32°F, or
higher. They may be either side wall or thru-roof vented
using approved plastic type combustion air and vent piping.
All units are factory assembled, wired and tested to assure
dependable and economical installation and operation.
TECHNICAL GUIDE
Echelon
MODELS: FC9T-UP
GAS-FIRED
CONDENSING / HIGH EFFICIENCY
UPFLOW TWO STAGE FURNACES
UP TO 94% AFUE
NATURAL GAS
40 - 120 MBH INPUT
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.gamanet.org.
WARRANTY
Lifetime limited warranty on both heat exchangers to the
original purchaser; a 20-year limited warranty from original
installation date to subsequent purchaser.
10-year warranty on the heat exchanger in commercial applications.
5-year limited parts warranty.
FEATURES
• Two stage heating operation includes:
- Two stage gas valve
- Two stage inducer operation
• Provides increased comfort level & very quiet unit operation
• Adjustable delay timer allows two stage operation with
single stage thermostat
• Compact, easy to install, ideal height 40" cabinet
• Blower-off delay for cooling SEER improvement.
• Easy to connect power/control wiring.
• Built-in, high level self diagnostics with fault code display.
• Low unit amp requirement for easy replacement application.
• Integrated control module for reliable, economical operation.
• May be installed as either two-pipe (sealed combustion)
or single pipe vent (using indoor combustion air)
• Top intake & vent connection allows installation in narrow
locations.
• Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
• Induced combustion system with inshot main burners for
quiet, efficient operation.
• No special vent termination kit required.
• 100% shut off main gas valve for extra safety.
• PSC -four speed, direct drive motor with large, quiet
blower.
• 24V, 40 VA control transformer and blower relay supplied
for add-on cooling.
FC9T040A12UP1140/261651/27.711 x 82014121
FC9T060B12UP1160/391701/27.711 x 82014135
FC9T080B12UP1180/521751/27.711 x 82014142
FC9T080C16UP1180/521753/410.211 x 102014157
FC9T100C16UP11100/651753/410.211 x 102014162
FC9T100C20UP11100/65175112.811 x 112012164
FC9T120D20UP11120/78170112.811 x 112012180
* ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
NOTES:
1. For altitudes above 2000 ft. reduce capacit y 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.
5. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
Rise
Weight
Unitary Products Group3
Page 4
246739-CTG-C-0407
BLOWER PERFORMANCE CFM
Airflow with Bottom or One Side Retrun - without Filters (CFM)
Models
Speed
Tap
0.10.20.30.40.50.60.70.80.91.0
High139513301265120011201030940820NRNR
FC9T040A12UP11
Med-High1025990960925885825750660NRNR
Med-Low785765745715670625545NRNRNR
Low640605590565530465405NRNRNR
High1650160515701525146514101350127511701060
FC9T060B12UP11
FC9T080B12UP11
Med-High11651185117511651150114011001050970875
Med-Low895915935940940920905860815750
Low710725725725720700685660625560
High1960195519251890183017651695161516001485
FC9T080C16UP11
FC9T100C16UP11
Med-High1565156015601575154515301475142513651260
Med-Low1230127512851300131013001280124511901070
Low930945965975975975975950910850
High2300221021202020193018301715159514801350
FC9T100C20UP11
Med-High1950190018301755168015951500139012701155
Med-Low161015451490144013901315123011551050920
Low132512701225117511051045990905890790
High2560248524102320222021352035192017851650
FC9T120D20UP11
Med-High2090205019901970188518201760167515451405
Med-Low1695167516651615156515101460138512851140
Low1175115011351110108510551005980970845
Airflow with Two Side Returns or with Bottom and One Side Return - without Filters
Models
Speed
Tap
0.10.20.30.40.50.60.70.80.91.0
High2465238022952195209519951875176016201470
FC9T100C20UP11
Med-High2085203519601880180017051605148513601235
Med-Low172516251595154014851405131512351125995
Low1420136013101255118011201070970950845
High2615253524502385228521752075194518251670
FC9T120D20UP11
Med-High2055204520151985193218551785173016051470
Med-Low1690165016201600157015251470139513001200
Low134513351335128512501230118011151010850
NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM).
2. Return air is through side opposite motor (left side).
3. In order to stay within the velocity rating of the filters, airflows above 1800 CFM require either return from two sides or one side plus bottom.
4. Motor voltage at 115 V.
5. NR = Operation at this static pressure is not recommended.
External Static Pressure, Inches W.C.
External Static Pressure, Inches W.C.
4Unitary Products Group
Page 5
246739-CTG-C-0407
FILTER PERFORMANCE
RECOMMENDED FILTER SIZES
The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower performance of the system, apply the filter drop value for the filter being used or select an appropriate value from the “Filter
Performance” table shown below.
NOTE: The filter pressure drop values in the “Filter Performance” table shown below are typical values for the type of
filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter
manufacturer.
Input/Output
BTU/H
40/381200A16 x 2514 x 25
60/561200B16 x 2516 x 25
80/751200B16 x 2516 x 25
80/751600C16 x 2520 x 25
100/931600C16 x 2520 x 25
100/932000C16 x 2520 x 25
120/1122000D(2) 16 x 2522 x 25
NOTES:
1. Air velocity through throwaway type filters may not exceed 300
feet per minute. All velocities over this require the use of high
velocity filters.
2. Air flows above 1800 CFM require e ither return from two sides or
one side plus bottom.
CFM
Cabinet
Size
FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)
For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com
in the Product Catalog Section.
- O/B Terminal Energized in Cooling
Thermostat Installer Setup Number 0200
Thermostat Installer Setup Number 0190 -
Reversing Valve (O/B) Operation - must be set to 0
Pump Backup Heat Source is Fossil Fuel
Thermostat Installer Setup Number 0210 -
External Fossil Fuel Kit - must be set to 0 -
- Backup Heat Source - must be set to 1 - Heat
Heat Pump Backup Heat
External Fossil Fuel Kit is Controlling
Page 8
APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1.Select the filter type.
2.Select the number of return air openings or calculate the
return opening size in square inches to determine the
proper filter pressure drop.
3.Determine the External System Static Pressure (ESP)
without the filter.
4.Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 3 to determine the
total system static.
5.If total system static matches a ESP value in the airflow
table (i.e. 0.20, 0.60, etc,) the system airflow corresponds to the intersection of the ESP column and Model/
Blower Speed row .
6.If the total system static falls between ESP values in the
table (i.e. 0.58, 0.75, etc.), the static pressure may be
rounded to the nearest value in the table determining the
airflow using Step 5 or calculate the airflow by using the
following example.
Example: For a 120,000 Btuh furnace with 2 return openings
and operating on high speed blower, it is found that total system static is 0.58" w.c. To determine the system airflow, complete the following steps:
1.Obtain the airflow values at 0.50" & 0.60" ESP.
Airflow @ 0.50": 2285 CFM
Airflow @ 0.60": 2175 CFM
2.Subtract the airflow @ 0.50" from the airflow @ 0.60" to
obtain airflow difference.
2175 - 2285 = -110 CFM
3.Subtract the total system static from 0.50" and divide this
difference by the difference in ESP values in the table,
0.60" - 0.50", to obtain a percentage.
(0.58 - 0.50) / (0.60 - 0.50) = 0.8
4.Multiply percentage by airflow difference to obtain airflow
reduction.
(0.8) x (-110) = -88
5.Subtract airflow reduction value to airflow @ 0.50" to
obtain actual airflow @ 0.58" ESP.
2288 - 88 = 2197
ACCESSORIES
CONCENTRIC VENT TERMINATION -
1CT0302 (2")
1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole.
PROPANE (LP) CONVERSION KIT 1NP0347 - All units
This accessory conversion kit may be used to convert natural
gas units for propane (LP) operation. Conversions must be
made by qualified distributor or dealer personnel.
CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartidge has a 1/2" plastic tube fittings for installation in the drain line. Calcium carbonate refill media is also
available from the Source 1 Parts (p/n 026-30228-000).
SIDEWALL VENT TERMINATION KIT -
1HT0901 (3")
1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.
EXTERNAL SIDE RETURN FILTER RACK -
1SF0101 - Fits all cabinet sizes
Attaches to side of furnace cabinet in side return applications.
Holds any 16x25x1 permanent or disposable filter.
SIDE RETURN FILTER RACK-
1SR0302 - All Models
1SR0200 - All Models
BOTTOM RETURN FILTER RACK-
1BR0114 or 1BR0214 - For 14-1/2” cabinets
1BR0117 or 1BR0217 - For 17-1/2” cabinets
1BR0121 or 1BR0221 - For 21” cabinets
1BR0124 or 1BR0224 - For 24-1/2” cabinets
HIGH ALTITUDE PRESSURE SWITCHES -
For installation where the altitude is less than 8,000 feet it is
not required that the pressure switch be changed. For altitudes above 8,000 feet see kits below. Conversion must be
made by qualified distributor or dealer personnel.