Coleman Echelon FC9V User Manual

TECHNICAL GUIDE
Echelon MODELS: FC9V
GAS-FIRED CONDENSING / HIGH EFFICIENCY DOWNFLOW/HORIZONTAL TWO STAGE VARIABLE SPEED FURNACES
NATURAL GAS 60 - 120 MBH INPUT
EFFICIENCY RATING CERTIFIED
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at www.york.com for the most up-to-date technical information.
Additional rating information can be found at www.gamanet.org.
246786-CTG-B-0407
DESCRIPTION
These Category IV, highly efficient, compact, condensing type furnaces are designed for residential and commercial installations in a basement, closet, alcove, recreation room or garage where the ambient temperature is above 32°F, or higher. They may be either side wall or thru-roof vented using approved plastic type combustion air and vent piping. All units are factory assembled, wired and tested to assure dependable and economical installation and operation.
WARRANTY
Lifetime limited warranty on both heat exchangers to the orig­inal purchaser; a 20-year limited warranty from original instal­lation date to subsequent purchaser.
10-year warranty on the heat exchanger in commercial appli­cations.
5-year limited parts warranty.
FEATURES
• Two stage heating operation includes:
- Two stage gas valve
- Two stage inducer operation
• Provides increased comfort level & very quiet unit opera­tion
• Adjustable delay timer allows two stage operation with sin­gle stage thermostat
• Compact, easy to install, ideal height 40" cabinet
• Blower-off delay for cooling SEER improvement.
• Easy to connect power/control wiring.
• Built-in, high level self diagnostics with fault code display.
• Low unit amp requirement for easy replacement application.
• Integrated control module for reliable, economical operation.
• May be installed as either two-pipe (sealed combustion) or single pipe vent (using indoor combustion air)
• Top intake & vent connection allows installation in narrow locations.
• Electronic Hot Surface Ignition saves fuel cost with increased dependability and reliability.
• Induced combustion system with inshot main burners for quiet, efficient operation.
• No special vent termination kit required.
• 100% shut off main gas valve for extra safety.
• 24V, 40 VA control transformer and blower relay supplied for add-on cooling.
• Hi-tech tubular aluminized steel primary heat exchanger.
• Secondary (condensing) heat exchanger of 29-4C high-grade stainless steel.
• Timed on, adjustable off blower capability for maximum com­fort.
• Independent door removal for greater durabilty and ease of access.
• Easy access from front of unit for cleaning, maintenance or service.
• Protection from intake, exhaust or condensate blockage.
• Insulated blower compartment for quiet operation.
• 3-way transition facilitates fresh air piping.
EcoTrak comfort system allows dealer to customize comfort
• settings based on regional location.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246786-CTG-B-0407
7/8
13-7/8
22-3/4
7/8
HORIZONTAL CONDENSATE DRAIN OPENING 2”
JUNCTION BOX HOLE 7/8”
GAS PIPE ENTRY 1-1/2”
CONDENSATE DRAIN HOLE 7/8”
SIDE PIPING HOLE 3-3/8”
22-1/4
25-3/8 26-1/2
27-1/8
30-1/8
LEFT SIDE
T-STAT WIRING 7/8” K.O.
HORIZONTAL CONDENSATE DRAIN OPENING 1-3/4”
18-1/2
11-3/4
7-1/2
2-1/4
1-1/4
BOTTOM IMAGE
29
22-3/4
21-5/8
23-11/16
19-1/4
C
SUPPLY END
1-1/4
A
FRONT
E
2-1/4
T-STAT WIRING 7/8” K.O.
HORIZONTAL CONDENSATE DRAIN OPENING 1-3/4”
40
29
22-3/4
21-1/4
18-1/2
9-1/8
8-1/2
23-5/8
5/8
D
B
20
23-1/4
TOP IMAGE
RETURN END
5/8
HORIZONTAL CONDENSATE DRAIN OPENING 1-3/4”
JUNCTION BOX HOLE 7/8”
GAS PIPE ENTRY 1-1/2”
CONDENSATE DRAIN HOLE 7/8”
RIGHT SIDE
DIMENSIONS
Models
Nominal
CFM
Cabinet
Size
A (in.) B (in.) C (in.) D (in.) E (IN.)
FC9V060B12DH11 1200 B 17-1/2 16-1/4 15 1-3/4 2-3/8 FC9V080B12DH11 1200 B 17-1/2 16-1/4 15 1-3/4 2-3/8 FC9V080C16DH11 1600 C 21 19-3/4 18-1/2 2-1/8 2-3/4 FC9V100C20DH11 2000 C 21 19-3/4 18-1/2 2-1/8 2-3/4 FC9V120D20DH11 2000 D 24-1/2 23-1/4 22 2-1/2 3
Cabinet Dimension
ELECTRICAL AND PERFORMANCE DATA
Air Temp.
Rise
Operating
Weight
Models
Input
(High/Low)
Output
(High/Low)
Nominal
Airflow
Cabinet
Width
Total Unit AFUE
MBH MBH CFM In. Amps % °F FC9V060B12DH11 60 / 39 56 / 36 1200 17-1/2 9 92 35 - 65 FC9V080B12DH11 80 / 52 75 / 49 1200 17-1/2 9 92 35 - 65 FC9V080C16DH11 80 / 52 75 / 49 1600 21 12 92 35 - 65 FC9V100C20DH11 100 / 65 93 / 61 2000 21 14 92 35 - 65 FC9V120D20DH11 120 / 78 112 / 74 2000 24-1/2 14 92 35 - 65
Blower
Size
Max.
Over-current
Protect
Min. Wire Size *
(awg) @ 75 ft.
One Way
Models
Input
(High/Low)
Max. Outlet
Air Temp.
Blower
MBH °F HP Amps In. Lbs. FC9V060B12DH11 60 / 39 165 1/2 7.0 11 x 8 20 14 136 FC9V080B12DH11 80 / 52 165 1/2 7.0 11 x 8 20 14 143 FC9V080C16DH11 80 / 52 165 3/4 10.2 11 x 10 20 14 159 FC9V100C20DH11 100 / 65 165 1 12.7 11 x 11 20 12 164 FC9V120D20DH11 120 / 78 165 1 12.7 11 x 11 20 12 182
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures. Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes. The furnace shall be installed so that the electrical components are protected from water. * Wire size and overcurrent protection must comply with the National Electric Code.
NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.
2 Unitary Products Group
246786-CTG-B-0407
AIR FLOW DATA
FC9V060B12DH11 FC9V080B12DH11 Jumper Settings High Low High Low COOL Tap ADJ Tap 1329 898 1312 878 A B 1133 774 1117 741 B B 1226 842 1202 810 A A 1039 708 996 683 B A 1110 755 1084 725 A C
915 637 892 618 C B 930 646 898 619 B C 719 529 700 511 D B 856 603 827 580 C A 657 526 642 500 D A 762 566 746 532 C C 612 523 596 500 D C
FC9V080C16DH11 FC9V100C20DH11 Jumper Settings High Low High Low COOL Tap ADJ Tap* 1758 1183 2196 1498 A B 1646 1106 1858 1167 B B 1699 1140 2045 1363 A A 1531 1033 1661 1054 B A 1527 1047 1884 1201 A C 1449 969 1597 1022 C B 1368 930 1506 947 B C 1213 832 1395 891 D B 1309 897 1477 922 C A 1116 762 1254 761 D A 1170 808 1304 801 C C 1031 703 1114 657 D C
FC9V120D20DH11 High Low 2342 1528 1904 1229 2140 1404 1700 1096 1918 1247 1643 1044 1522 967 1418 852 1494 945 1287 772 1337 802 1132 668
FC9V060B12DH11 FC9V080B12DH11 Jumper Settings High Low High Low HEAT Tap ADJ Tap* 1137 720 1386 962 A Any
974 625 1322 892 B Any 883 593 1250 849 C Any 825 561 1159 768 D Any
FC9V080C16DH11 FC9V100C20DH11 Jumper Settings High Low High Low HEAT Tap ADJ Tap* 1732 1173 1912 1237 A Any 1631 1110 1688 1079 B Any 1493 1008 1545 967 C Any 1359 931 1422 899 D Any
FC9V120D20DH11 High Low 2238 1465 2014 1313 1863 1211 1686 1075
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automat ically adjust t o provid e constant CFM from 0.0” to
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended. NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details. * The ADJ “D” tap should not be used.
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM - WITHOUT FILTERS
Jumper Settings
COOL Tap ADJ Tap*
AB BB AA BA AC CB BC DB CA DA CC DC
HIGH / LOW HEAT CFM - WITHOUT FILTERS
Jumper Settings
HEAT Tap ADJ Tap*
AAny BAny CAny DAny
Unitary Products Group 3
246786-CTG-B-0407
FILTER PERFORMANCE
The airflow capacity data published in the “Blower Perfor­mance” table listed above represents blower performance WITHOUT filters. To determine the approximate blower per­formance of the system, apply the filter drop value for the fil­ter being used or select an appropriate value from the “Filter Performance” table shown.
NOTE: The filter pressure drop values in the “Filter Perfor­mance” table shown are typical values for the type of filter listed and should only be used as a guideline. Actual pres­sure drop ratings for each filter type vary between filter manu­facturer.
FILTER SIZES
APPLYING FILTER PRESSURE DROP TO DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in place, follow the steps below:
1. Select the filter type.
2. Determine the External System Static Pressure (ESP) without the filter.
3. Select a filter pressure drop from the table based upon the number of return air openings or return air opening size and add to the ESP from Step 2 to determine the total system static.
If total system static matches a ESP value in the airflow table (i.e. 0.20, 0.60, etc,) the system airflow corresponds to the intersection of the ESP column and Model/Blower Speed row
Input / Output
BTU/H
60/56 1200 B (2) 14 x 20 80/75 1200 B (2) 14 x 20 80/75 1600 C (2) 14 x 20
100/95 2000 C (2) 14 x 20
120/112 2000 D (2) 14 x 20
CFM
Cabinet
Size
Top Return
Filter in
FILTER PERFORMANCE - PRESSURE DROP INCHES W.C.
Airflow Range
CFM
0 - 750 230 0.01 0.01 0.15
751 - 1000 330 0.05 0.05 0.20 1001 - 1250 330 0.10 0.10 0.20 1251 - 1500 330 0.10 0.10 0.25 1501 - 1750 380 0.15 0.14 0.30 1751 - 2000 380 0.19 0.18 0.30
2001 & Above 463 0.19 0.18 0.30
Minimum
Opening Size
2
in
Disposable Washable Fibers Pleated
In W.C. In W.C. In W.C.
Filter Type
.
UNIT CLEARANCES TO COMBUSTIBLES
Application
Downflow 130 0 0 0 Horizontal 0 3 0 1 1 0 0 Yes Yes Yes
* Combustible floor base or air conditioning coil required for use on combustible floor.
Top Front Rear Left Side Right Side Flue Floor/Bottom
In. In. In. In. In. In. In.
*
1
Closet Alcove Attic Line Contact
Yes Yes Yes NA
Yes
4 Unitary Products Group
246786-CTG-B-0407
For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section.
(Optional)
Interface
Comfort Alert
24V HUMIDIFIER
C
TWO STAGE
24-Volt Common
AIR CONDITIONING
Y1
Y2
First Stage Cool
Second Stage Cool
R
24-Volt Hot
C
Y1
VARIABLE SPEED
THERMOSTAT
THERMOSTAT
THERMOSTAT
24-Volt Common
FURNACE CONTROL
C
Y1
*PP32U72124
*PP32U71124
24-Volt Common
C
Y1
*DP22U70124
24-Volt Common
Y
C
*DN22C00124
24-Volt Common
R
Y/Y2
First Stage Cool
24-Volt Hot
Single/Second Stage Cool
R
Y2
First Stage Cool
First Stage Cool
First Stage Cool
24-Volt Hot
Second Stage Cool
R
Y2
24-Volt Hot
Second Stage Cool
R
Y2
24-Volt Hot
Second Stage Cool
G
W2
W/W1
Single/First Stage Heat
E/W1
First Stage Heat
E/W1
First Stage Heat
W
First Stage Heat
Fan
Second Stage Heat
G
W2
Fan
Second Stage Heat
G
W2
Fan
Second Stage Heat
G
W2
Fan
Second Stage Heat
(O)
HUM
CFM CONTROL
DHM
(X/L)
Malfunction Light
Reversing Valve– Energized in Cool
Dehumidification - Open on Humidity Rise
L
HM
Dehumidistat
Humidistat
Malfunction Light
( ) CONVENIENCE TERMINAL
NO FUNCTION IN THIS APPLICATION.
set to MLTI STG
Step 16 of Thermostat
Comfort Alert Features
User Configuration Menu
Step 1 of Thermostat User
Configuration Menu must be
24-Volt
Common, is optional
Connection of the "C" Termainal,
is optional
Connection of the "C"
Termainal, 24-Volt Common,
must be set to ON to use
Configuration Menu
when used with batteries
when used with batteries
must be set to MS 2
Step 1 of Thermostat User
in the 'YES' position
for Dehumidification
CFM Control must be
Humidistat Jumper on
the E2 position and the
E2/P Switch must be in
C
*PP32U70124
THERMOSTAT
C
*DN22U00124
THERMOSTAT
Y
24-Volt Common
Y
24-Volt Common
R
Y2
First Stage Cool
Second Stage Cool
R
Y2
First Stage Cool
Second Stage Cool
RC
24-Volt Hot (Heat XFMR)
RC
24-Volt Hot (Heat XFMR)
W2
E/W1
First Stage Heat
24-Volt Hot (Cool XFMR)
24-Volt Hot (Cool XFMR)
Second Stage Heat
W2
E/W1
First Stage Heat
Second Stage Heat
G
Fan
Termainal, 24-Volt
Thermostat Installer
Common, is optional
Connection of the "C"
G
Fan
Termainal, 24-Volt
Connection of the "C"
Setup Number 0170 -
System Type - must be
when used with batteries
Common, is optional
when used with batteries
set to 8 - 2 Heat/2 Cool
must be set to 6 - 2
Heat/2 Cool Conventional
Number 1 - System Type -
Thermostat Installer Setup
Multistage Conventional
Number 15 - Compressor
Thermostat Installer Setup
Protection - must be set to 5
AC10 2 Stage Scroll A/C w/ Variable Speed Furnace - PV8/9; (F,L)*8/9V, (G,L)*8/9V, XYG8V-*, XYF8V-*, XYG9V-*, XYF9V-*
Thermostat Chart - AC
Unitary Products Group 5
246786-CTG-B-0407
C
Y1
HEAT PUMP
TWO STAGE
VARIABLE SPEED
24-Volt Common
C
Y1
24-Volt Common
FURNACE CONTROL
C
Y1
*PP32U71124
24-Volt Common
R
Y2 OUT
First Stage Heat/Cool
Y/Y2
First Stage Cool
W1 OUT
24-Volt Hot
Second Stage Cool Output
R
W/W1
24-Volt Hot
Single/Second Stage Cool
R
24-Volt Hot
First Stage Heat/Cool
W2 OUT
O
First Stage Auxiliary Heat Output
Second Stage Auxiliary Heat Output
G
W2
Fan
Second Stage Heat
Single/First Stage Heat
Reversing Valve–Energized in Cool
(O)
CFM CONTROL
Reversing Valve–Energized in Cool
Fan
O
W2
G
Second Stage Auxiliary Heat
Reversing Valve–Energized in Cool
Y2
X/L
Malfunction Light
Second Stage Heat/Cool
(Y 2)
(X/L)
Malfunction Light
L
Y2
Malfunction Light
Second Stage Heat/Cool
W
BSG
Auxiliary Heat
Bonnet Sensor
BS
Bonnet Sensor
Bonnet Sensor (Optional)
HUM
Dehumidification - Open on Humidity Rise
(Optional)
24V HUMIDIFIER
E/W1
Dehumidistat
HM
Humidistat
DHM
First Stage Auxiliary Heat
Heat Pump to ON
Change FFuel Jumper on
Set W2 Delay on furnace to OFF
( ) CONVENIENCE TERMINAL. NO
FUNCTION IN THIS APPLICATION.
Dehumidification
Menu must be set to Heat Pump 2
and the Humidistat Jumper on CFM
E2/P Switch must be in the E2 position
Step 1 of Thermostat User Configuration
Control must be in the 'YES' position for
C
Y1
*DP22U70124 *PP32U72124
24-Volt Common
R
24-Volt Hot
First Stage Heat/Cool
G
W2
Fan
Second Stage Auxiliary Heat
O
L
Y2
Malfunction Light
Second Stage Heat/Cool
E/W1
First Stage Auxiliary Heat
set to Heat Pump 2
Step 1 of Thermostat User
Configuration Menu must be
on thermostat not necessary
Selection of GAS/ELEC switch
Reversing Valve–Energized in Cool
C
*PP32U70124 *DN22H00124
THERMOSTAT THERMOSTAT THERMOSTAT
Y
RC
24-Volt Common
First Stage Heat/Cool
E
R
Emergency Heat
24-Volt Hot (Cool XFMR)
24-Volt Hot (Heat XFMR)
G
Fan
L
O/B
Reversing Valve
Malfunction Light
Y2
AUX
Auxiliary Heat
Second Stage Heat/Cool
System Type - must be set to
12 - 3 Heat/2 Cool Heat Pump
Pump Backup Heat Source is Fossil Fuel
Thermostat Installer Setup Number 0170 -
Thermostat Installer Setup Number 0200 -
Thermostat Installer Setup Number 0190 -
Reversing Valve (O/B) Operation - must be
set to 0 - O/B Terminal Energized in Cooling
Thermostat Installer Setup Number 0210 -
External Fossil Fuel Kit - must be set to 0 -
Backup Heat Source - must be set to 1 - Heat
Pump Backup Heat
External Fossil Fuel Kit is Controlling Heat
W/031-01996- Series Demand Control; Hot Heat Pump Mode OR Conventional
HP24 Two Stage H/P - H*5B, YZE - w/Variable 2 Stage Furnace, 2 Stage Cooling Ready - PV8/9, (F,L)*8/9V, (G,L)*8/9V, XYG8V-*, XYF8V-*, XYG9V-*, XYF9V-*
Thermostat Chart - HP
6 Unitary Products Group
246786-CTG-B-0407
ACCESSORIES
PROPANE (LP) CONVERSION KIT -
1NP0347 - All units This accessory conversion kit may be used to convert natural
gas (N) units for propane (LP) operation. Conversions must be made by qualified distributor or dealer personnel.
CONCENTRIC VENT TERMINATION - 1CT0302 (2") 1CT0303 (3") For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole. Elimi­nates unslightly elbows for a cleaner installation.
SIDEWALL VENT TERMINATION KIT -
1HT0901 (3") 1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a more attractive termination for locations where the terminal is visable on the side of the home.
COMBUSTIBLE FLOOR BASE -
1CB0317 - 17 1/2” Cabinet 1CB0321 - 21” Cabinet 1CB0324 - 24-1/2” Cabinet
COIL TRANSITION KIT -
1TK0917 - 17-1/2” Furnace 1TK0921 - 21” Furnace 1TK0924 - 24-1/2” Furnace These kits are required in downflow application when using
G*F* series coils. These kits are not required with MC/FC series coils, but please ensure that the coil and furn ace are secured and that there are no air leaks.
CONDENSATE NEUTRALIZER KIT - 1NK0301 Neutralizer cartidge has a 1/2" plastic tube fittings for installa­tion in the drain line. Calcium carbonate refill media is also avaiable from the Source 1 Parts (p/n 026-30228-000).
HIGH ALTITUDE PRESSURE SWITCHES -
For installation where the altitude is less than 8,000 feet it is not required that the pressure switch be changed. For alti­tudes above 8,000 feet see kits below. Conversion must be made by qualified distributor or dealer personnel.
1PS0507 - 060 MBH 1PS0508 - 080/1200 MBH 1PS0509 - 080/1600 MBH 1PS0510 - 100 MBH 1PS0511 - 120 MBH
ROOM THERMOSTATS - A wide selection of compatible thermosets are available to provide optimum performance and features for any installation.
1H/1C, manual change-over electronic non-programmable thermostat.
1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable. * For the most current accessory information, refer to the
price book or consult factory.
Unitary Products Group 7
Subject to change without notice. Printed in U.S.A. 246786-CTG-B-0407 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 246786/036-21637-002 Rev. A (1205)
Unitary 5005 Norman Products York OK Group Drive 73069