Coleman DGAA User Manual

MAINTENANCE AND
USER'S INFORMATION,
SERVICE
HIGH EFFICIENCY SEALED COMBUSTION For Installation In:
GAS FURNACE 1. Manufactured (Mobile) Homes
_ODELS_ D_AA and _AH 2. Recreational Vehicles & Park Models {S_ngl@ Stag@ _@wnH@w On_y} 3. Modular Homes & Buildings
CONTACT INFORMATION FOR USA ....................... 1 To Turn Off the Appliance: ............................... 4
CONTACT INFORMATION FOR CANADA ................... 1 FURNACE USER MAINTENANCE ......................... 5
SAFETY ................................................ 1 Air Filters ............................................ 5
While you are away .................................... 2 Removing Filters ...................................... 5
SEASONAL SERVICE INFORMATION ...................... 2 Blower Care .......................................... 5
Your Service Technician ................................ 2 Motor Lubrication ...................................... 5
DESCRIPTION ......................................... 2 SERVICE AND MAINTENANCE MANUAL ..................... 6
WARRANTY AND RESPONSIBILITIES ..................... 2 SAFETY SECTION ...................................... 6
GAS SUPPLY .......................................... 3 FURNACE MAINTENANCE SECTION ...................... 6
Natural Gas Operation .................................. 3 FURNACE CLEANING SECTION .......................... 6
Propane Gas Operation ................................. 3 Burner Removal/Cleaning ............................... 6
INSTRUCTIONS FOR EXAMINING THE Cleaning the Heat Exchanger ............................ 6
FURNACE INSTALLATION ............................... 3 THE FURNACE CONTROLS AND THEIR FUNCTION .......... 6
Observing Burner Operation ............................. 3 SEQUENCE OF OPERATION ............................. 7
If Furnace Fails to Operate Properly ....................... 3 Continuous Blower ..................................... 7
HOW YOUR GAS FURNACE WORKS ...................... 4 Heating Cycle ......................................... 7
IF FURNACE FAILS TO OPERATE PROPERLY .............. 4 Hot Surface Ignition System .............................. 7
When You Call For Service Assistance ..................... 4 TROUBLESHOOTING ................................... 7
To Contact Your Serviceman ............................. 4 FURNACE CONTROL DIAGNOSTICS ...................... 8
SAFETY INFORMATION ................................. 4 REPLACEMENT PARTS LIST .............................. 9
Read the Instructions Below Before Trying WIRING DIAGRAM ...................................... 12
to Start the Furnace .................................... 4 LIMITED WARRANTY .................................... 14
START-UP AND SHUTDOWN INSTRUCTIONS ............... 4
Operating Instructions: .................................. 4
Management System
CONTACT INFORMATION FOR USA CONTACT INFORMATION FOR CANADA
Contact us by mail: Go to website at www.york.com click on "contact", then click on
DISTRIBUTED BY: MANUFACTURED BY:
StyleCrest York International Contact us by mail:
801 W. 37th Street 5005 York Drive York International
Building #7 Norman, OK 73069 Consumer Relations
Wichita, Ks 67219 5005 York Drive
"contact form" and follow the instructions.
Norman, OK 73069
The manufacturer recommends that the user read all SECTION I" SAFETY sections of this manual and keep the manual for
future reference.
&WARNING
FIRE OR EXPLOSION HAZARD - Failure to follow safety warnings
exactly could result in serious injury, death, or property damage.
--Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
--WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance. Do not touch any electrical switch; do not use any phone (including
cell phone) in your building.
Leave the building immediately. Immediately call your gas supplier from a neighbor's phone. Fol-
low the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
-- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
1. The furnace area must be kept clear and free of combustible mate- rials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be kept free and clear of insulating materials. The furnace area must
be examined when installed in an insulated space or when insula- tion is added to be sure that the insulation material has been kept
away from the furnace.
3. Follow the instructions exactly as shown on the OPERATING INSTRUCTION LABEL or the Start-up and Shutdown Instructions
on Page 4 of this manual when lighting the furnace or turning the furnace off.
4. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical
supply.
5. Do not use this furnace if any part has been under water. A flood- damaged furnace is extremely dangerous. Attempts to use the fur-
nace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and replace all gas
controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
Johnson Controls Unitary Products 129099-BUM-J-0112
129099-BUM-J-0112
6. NEVER...Store flammable materials of any kind near your fur- nace. Gasoline, solvents, and other volatile liquids should be
stored only in approved containers outside your home. These materials vaporize easily and are extremely dangerous.
7. NEVER...Store cleaning materials near your furnace. Materials such as bleaches, detergents, powdered cleansers, etc., can
cause corrosion of the heat exchangers.
8. NEVER... Use the area around your furnace as a storage area for items which could block the normal flow of air. This flow of air is
required for ventilation of the various furnace components.
AWARNING
FIRE OR EXPLOSION HAZARD
This furnace is designed and approved for use with Natural Gas
and (LP) Propane Gas ONLY. DO NOT BURN ANY LIQUID FUEL
OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the furnace heat exchanger, which could result in Fire, Personal Injury, and/or Property
Damage.
While you are away
Your furnace is equipped with a safety device which will shut off the supply of gas to the burner in case of malfunction. For this reason it is
never practical to assume that the furnace will operate unattended for a long period of time, especially if there is a possibility of damage to your
property because of freezing. So, if you plan to be away from home, arrange for someone to check your house every day.
SEASONAL SERVICE INFORMATION
During extreme cold weather, ice may form on the furnace roof jack crown. Small amounts of ice forming on the roof jack will present no
problem to proper furnace operation. However, excessive ice formation could restrict the combustion air supply to the burner causing inefficient
burner operation. When the temperature is very cold, near zero or below, it is recom-
mended that the roof jack be inspected every day or more frequently if required. If ice has started to collect on the roof jack crown, it should be
carefully broken off.
Your Service Technician
Your furnace's best friend is your qualified service technician. If the unit gives any indication of improper operation, call your service technician.
If the service technician is allowed to perform the normal routine care of your furnace, he can many times detect potential difficulties and make
corrections before trouble develops. Preventative maintenance of this type will allow you to operate the unit with a minimum of concern, and at
the same time will pay for itself in added years of comfort.
DESCRIPTION
This furnace shall be installed in the downflow position. Figure 1 shows a typical model in the downflow position. The furnace is equipped with
an induced-draft vent blower and atmospheric burner. Combustion air is drawn through the roof jack and pushed into the burner box. Flue gas is
forced from the heat exchanger by the vent blower and discharged
through the flue pipe to the outside atmosphere. This is a forced air furnace. The furnace circulating air blower draws
cool air from the house, passes it over the hot furnace heat exchanger and circulates the warmed air through the ductwork to the house.
The furnace is equipped with the controls necessary for proper opera- tion. The various components referred to in this manual and on the fur-
nace rating plate are identified in Figure 1.
-- VENT PIPE
BLOWER MOTOR CAPACITOR --
BLOWER-- MOTOR
PRESSURE SWITCH _,
CONTROL-- BOARD
SILICONE TUBE
GAS VALVE --
GAS BURNER _ ASSEMBLY
FIGURE 1: Component Locations
FLUE COLLAR
-- BLOWER
H--'--- COMBUSTION
AIR PIPE
SAFETY SHUTOFF SWITCH
--BOOSTER DRAFT ASSEMBLY
AIR CONDITIONING COIL PANELS
WARRANTY AND RESPONSIBILITIES
It is the sole responsibility of the home owner to make certain that the gas furnace has been correctly set up and converted to the proper fuel
(Propane or Natural gas) and adjusted to operate properly. The manufacturer warrants the furnace to be free from defects in mate-
rial or workmanship for the stated time in the warranty agreement (see warranty certificate packed with the furnace).
However, the manufacturer will not be responsible for any repair costs to correct problems due to improper set-up, improper installation, fur-
nace adjustments, improper operating procedure by the user, etc. It is also the sole responsibility of the home owner to make sure that the
home if located above 2,000 ft. altitude be derated. Some specific examples of service calls which cannot be included in
warranty payments are:
1. Converting the furnace to use another type of fuel.
2. Correcting faulty duct work in the home.
3. Correcting wiring problems in the electrical circuit to the furnace.
4. Resetting circuit breakers or other switches.
5. Adjusting the burner air shutter or service calls made to correct problems caused by improper air adjustment.
6. Correcting problems caused by improper gas supply pressure to the furnace.
7. Instructional training on how to light and operate furnace.
8. Furnace problems caused by installation of air conditioner, heat pump, or other air quality device.
9. Problems caused by improper installation of the furnace flue assembly (roof jack).
10. Adding a roof jack extension because of unusual wind conditions or snow conditions.
11. Adjusting thermostats.
12. Problems caused by construction debris which has fallen into the flue or combustion air openings.
13. Replacement of fuses.
14. Problems caused by plugged or restricted orifices by any means.
You should establish a firm understanding of these responsibilities with your manufactured housing dealer, service company or gas supplier so
there will be no misunderstanding at a later time.
2 Johnson Controls Unitary Products
129099-BUM-J-0112
GAS SUPPLY
The gas supply to your home will either be Natural Gas or Propane gas. Your furnace will be factory equipped to operate on only one of these two different gases.
A small metal tag secured to the furnace next to the gas valve will spec- ify the type of gas your furnace is equipped to use.
If the gas is different from that specified on the metal tag, the furnace can be converted by following the instructions on the furnace safety label inside lower front panel. Parts for conversion are contained in the small bag attached to the gas valve. Be sure the proper size orifice is used, as specified on the furnace name plate.
[ kCAUTION
The furnace must be converted by a qualified technician. Improper conversion can cause unsafe operation, explosion, and/or fire or
asphyxiation.
Natural Gas Operation The furnace is designed for 7" W.C. inlet pressure. Pressure is reduced
to 3 1/2" W.C. by the pressure regulator in the gas valve. Propane Gas Operation Inlet pressure to the gas valve must be 11" W.C. When properly con-
verted to Propane gas, the pressure is regulated at 10" W.C.
INSTRUCTIONS FOR EXAMINING THE FURNACE INSTALLATION
It is the owner's responsibility to ensure that an annual inspection of the entire heating portion of the unit is made by a qualified service agency. Examine the furnace as outlined below in steps "1 - 6" before each heating season.
1. Examine the heat exchanger, through an access panel located on the supply air plenum. Visually examine the exterior sections of
the vent/combustion air piping and the vent connectors to be sure that they are physically sound without holes or excessive corro-
sion.
2. Examine the vent pipe making sure it is firmly in place, and is physically sound without holes and all of the connections are
secure.
3. Examine return connections for Modular or Manufactured (Mobile) Homes.
4. Examine the return air filter rack connections to make sure they are physically sound, sealed to the furnace door.
5. Examine the furnace casing making sure the physical support is sound without sagging, cracks or gaps. Examine the furnace base
making sure it is physically sound without cracks, gaps or sagging and has a good seal.
6. Examine the furnace casing for obvious signs of deterioration.
7. Examine the burner flames to make sure the burner look like they are operating properly. The burner flames for natural gas should
appear blue with a few yellow tips. The burner flames for propane gas should appear blue with moderate yellow tips. The flame
should appear cylindrical in shape and should extend from the end of the burner into the heat exchanger.
NATURAL GAS
_ LIGHT BLUE
WITH YELLOW TIPS
DARK BLUE
BLUE TIPS JUST
. STARTING TO
BECOME PRONOUNCED
FIGURE 2: Burner Flame Appearance
PROPANE GAS
TO LIGHT YELLOW
LIGHT BLUE
BLUE TIPS JUST
"_ STARTING TO
BECOME PRONOUNCED
Observing Burner Operation
1. Observe burner to make sure it ignites. Observe color of flame. On natural gas the flame will burn blue with appreciably yellow tips.
On Propane gas a yellow flame may be expected. If flame is not the proper color call a qualified service technician for service.
2. Let furnace heat until blower cycles on.
3. Turn thermostat down.
4. Observe burner to make sure it shuts off.
5. Let the furnace cool and blower cycle off.
AWARNING
Should overheating occur, or the gas supply fail to shut off, shut off
the manual gas valve to the furnace and allow blower to run until fur- nace cools down and blower shuts off before shutting off the electrical supply,
If any abnormalities are observed when checking for correct operation, such as burner failing to ignite or to turn off, sooty flame, etc., call your
nearest authorized service technician as shown in the Service Center List included in the home owner envelope with the furnace.
If Furnace Fails to Operate Properly
1. Check setting of thermostat - and position of HEAT/COOL switch if air conditioning is installed. If a set-back type thermostat is
employed be sure that the thermostat is in the correct operating mode.
2. Check to see that electrical power is ON.
3. Check to see that the knob or switch on the gas control valve is in the full ON position.
4. Make sure filters are clean, return grilles are not obstructed, and supply registers are open.
5. Be sure that furnace flue piping is open and unobstructed.
If the cause for the failure to operate is not obvious, do not attempt to service the furnace yourself. Call a qualified service agency or your gas supplier.
1. Examine Vent Pipe
2. Examine FilterDoor_ ................................................................
3. Remove Filter Door to Examine
....::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::.... CombustionAirPipe
................................................................7. Remove Burner
................................................................._ Door to Examine
i...........................................................
4. Examine Burner Door
5. Remove Burner Door to Examine Furnace Base and t_
Air Conditioning
Coil Panels
FIGURE 3: Furnace Examination Checkpoints
Burner Flame
Johnson Controls Unitary Products 3
129099-BUM-J-0112
HOW YOUR GAS FURNACE WORKS
Your furnace is a very easy appliance to take for granted. Season after season, it sits there in your home, keeping you warm and comfortable. For this reason, you may never have given much thought to the way your furnace operates. In order to get the safest and most efficient oper- ation from your furnace, you should understand how your furnace does its job.
When you set your thermostat to provide more heat in your home, you are starting the heating cycle of the furnace. First, the inducer motor starts to purge the heat exchanger of any remaining gases. Next, the hot surface ignitor glows and after a warm-up period the gas valve opens and ignition occurs. A short time later, the blower starts and dis- tributes the warm air throughout the home. When the temperature set- ting on your thermostat is reached, the gas valve closes, the main burner is turned off, and the blower continues to run until the remaining
warm air in the system is distributed. When the blower stops, the heat-
ing cycle has ended.
IF FURNACE FALLS TO OPERATE PROPERLY
1. Check setting of thermostat - and position of heat/cool switch if air conditioning is installed. If a set-back type thermostat is employed
be sure that the thermostat is in the correct operating mode.
2. Check to see that electrical power is "ON".
3. Check to see that the lever or switch on the gas control valve is in the full "ON" position.
4. Make sure filters are clean, return grilles are not obstructed, and supply registers are open.
5. Be sure that furnace flue piping is open and unobstructed.
When You Call For Service Assistance Very often time can be saved if you will give the service agency the
MODEL and SERIAL NUMBER of your furnace. This will enable him to determine the specific components used, and perhaps to better identify the possible problem and be better prepared if a service call is required.
To Contact Your Serviceman (fill in)
COMPANY:
ADDRESS:
TELPHONE:
All appliances need maintenance by serviceman at the beginning of
each heating season. Call your nearest authorized service technician
to:
1.
Replace filters. Clean all lint and dust from around furnace.
2.
Remove fan and clean all dust and lint from unit with stiff bristle brush.
3. Inspect combustion chamber, the transition into the blower com- partment, flue collar, and roof jack.
4. Check the gas valve and line connections for leaks.
5. Make any adjustments necessary for good operation.
NOTICE
The coil panel provides a good removable access for inspecting
inside the furnace casing. Smoke or reflected light inside the casing indicates the presence of leaks in the heat exchanger.
SAFETY INFORMATION Read the Instructions Below Before Trying to Start the
Furnace
&WARNING
If you do not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury, and/or loss of life.
1. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the
burner by hand.
2. BEFORE OPERATING; smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
3. Use only your hand to push the gas control switch to the "on" posi- tion. Never use tools. If the switch will not operate by hand, don't try to repair it, call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
4. Do not use this appliance if any part has been under water. Imme- diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control,
which has been under water.
START-UP AND SHUTDOWN INSTRUCTIONS Operating Instructions:
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove furnace door.
5. Move gas control switch to the "OFF" position. Do not force. See Figure 4.
6. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow Step 2 (refer to Safety Information on Page 4). If you
don't smell gas, go to next step.
7. Move gas control switch to the "ON" position. Do not force. See Figure 4.
8. Replace burner door.
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate fol- low the instructions, "TO TURN OFF THE APPLIANCE" and call
your service technician or gas supplier.
To Turn Off the Appliance:
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be per- formed.
3. Remove burner access panel.
4. Move gas control switch to the "OFF" position. See Figure 4.
5. Replace burner access panel.
&WARNING
Should overheating occur, or the gas valve fail to shut off, turn the external manual gas valve in the gas supply line to the furnace to the "off" position and let the furnace cool off before shutting off the electri- cal power supply. Refer to Figure 5.
4 Johnson Controls Unitary Products
CONNECTIONS (shown in OFF position) OUTLET
FIGURE 4: Gas Valve
FIGURE 5: Gas Piping
FURNACE USER MAINTENANCE
_WARNING
Before proceeding, be sure the area is well ventilated. Turn the ther-
mostat OFF. If the blower is running, wa# until it stops automatically.
Turn OFF the gas and electrical power supplies to the furnace. Check all metal parts and surfaces to be sure they have cooled to room tem- perature before you begin.
Every time the filters are changed the following items should be visually inspected:
Check roof jack assembly for blockage or leakage. Check all components to be sure they are in good condition and
that there are no obvious signs of deterioration.
Check the evaporator coil drain lines to make sure there are no
cracks or leaks.
Check for dirt or lint on any surfaces or on components. Do not try
to clean any of the surfaces or components. Cleaning of the fur-
nace and its components must be done by a qualified service pro-
fessional.
If, during the inspection of your furnace, you find any of the following conditions:
Excessive amounts of dust and lint on components. Damaged or deteriorated components or surfaces.
Leaks or blockage in the vent pipe passages.
Water on any surface inside or outside of the furnace.
129099-BUM-J-0112
Do not operate the furnace, and call a certified dealer / servicing con- tractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the front panels. Follow the operating instructions to place the furnace in operation.
Air Filters Dirty filters greatly restrict the flow of air and may cause damage to the
moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation.
The filters should be checked every 3 months (DO NOT USE PLEATED FILTER in this furnace). On new construction, check the filters every week for the first four weeks and every three weeks after that, espe- cially if the indoor fan is running continuously. When replacing the fil- ter(s) you must use filters that are the same size and type as those in the furnace (2 - 16 x 20 xl ).
Removing Filters Internally Mounted Air Filters
The air filter is in a rack that is attached to the door of the furnace. To remove the filter you must do the following:
1. Before proceeding, be sure the area is well ventilated. Follow instruction "To turn off the appliance". Check all metal parts and
surfaces to be sure they have cooled to room temperature before you begin.
2. Remove the filter door.
3. Remove the air filter by sliding it down the track. The air filter will slide out of the rack.
4. Replace throw away filter(s)) with the same size new filter(s). Throw away filter(s)) may be replaced with cleanable filter(s) at
this time. Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described in these instructions.
To replace the filter after cleaning you must do the following:
1. Slide filter into place. If the filter has been cleaned, make sure it is dry before re-installing it.
2. Replace the door or cover panel.
3. Make sure the door snaps into the retaining clips.
4. Follow the Operating Instructions to place the furnace back in operation.
Blower Care Even with good filters properly in place, blower wheels and motors will
become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vac- uum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then call a qualified service agency. Only a qualified service agency can perform this service.
AWARNING
Make sure you DO NOT move the clip on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not require periodic oiling.
Johnson Controls Unitary Products 5
129099-BUM-J-0112
SECTION I1: SERVICE AND MAINTENANCE MANUAL
SAFETY SECTION
This section has been designed to assist a qualified service agency in performing service and maintenance on this appliance. The homeown- ers and/or end user must never attempt to perform any service or main- tenance on the appliance especially when it involves the removal or adjustment of any parts and/or components.
The following safety rules must be followed when servicing the furnace.
AWARNING
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous
operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury,
and death or property damage.
Before servicing, disconnect all electrical power to the fur- Race.
When servicing controls, label all wires prior to disconnecting.
Reconnect wires correctly.
Verify proper operation after servicing.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every
heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.
1. The roof cap (if applicable).
2. The furnace vent pipe. Should it be necessary to service the vent/ air intake system, the manufacturer recommends this service be
conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air
intake system.
3. The furnace burner, ignitor and flame sensor.
FURNACE CLEANING SECTION
NOTE: The cleaning operations listed below must be performed only by
a qualified service agency. Burner Removal/Cleaning The main burner should be checked periodically for dirt accumulation. If
cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3. Remove the upper access panel.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner assembly to the combus- tion air box and remove the assembly.
6. Remove burner from the burner assembly.
7. Rinsing in hot water may clean burners.
8. Reassemble in the reverse order.
Cleaning the Heat Exchanger
It is recommended that replacement gaskets be available before
removing burner assembly and combustion air box.
Lower Heat Exchanger Access
1. Turn off the electrical power to the unit and turn off gas supply at the shutoff valve.
2. Remove the blower and burner compartment access doors. Dis- connect the gas supply piping at the union to permit removal of the
entire burner and gas control assembly from the vestibule panel. Use the wrench boss on the gas valve when removing or installing this piping.
3. Unplug the igniter from the wire harness. Disconnect sensor wires. Identify and note the location of all leads for ease of reinstallation.
4. Remove the screws holding the burner assembly to the vestibule panel and remove this assembly. Handle the assembly carefully
since it contains the igniter, which is fragile and easily broken. The lower portion of the heat exchanger will now be exposed. Remove
any soot and scale. Vacuum loose soot, scale and dirt from the heat exchanger.
5. After cleaning is complete, replace all components in reverse order. Re-gasket all surfaces which required a gasket. Reconnect
all wiring. Reattach vent pipe and gas supply lines before restoring service to furnace. Restore electrical power, check gas supply pip-
ing for leaks, and then verify furnace operation.
[ CAUTIONI
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
THE FURNACE CONTROLS AND THEIR FUNCTION
1. Limit Control - This furnace is protected by two (2) high tempera- ture limit switches. The lower limit switch is an automatic reset
type.
2. Upper Limit Control - The upper limit switch near left side of blower is a manual reset type limit switch. If burner does not func-
tion, turn system switch to "OFF" and push reset button in center of limit switch.
3. Gas Valve - The gas valve is 100% shut-off type and will fail safe if for some reason the gas is turned off. It is also of the snap opening
type which opens to fire position.
6 Johnson Controls Unitary Products
SEQUENCE OF OPERATION Continuous Blower
On cooling/heating thermostats with fan switch, when the fan switch is set in the ON position, a circuit is completed between terminals R and G of the thermostat. The blower motor is energized through the cool fan terminal on the ignition control module.
Intermittent Blower - Cooling
On cooling/heating thermostats with fan switch, when the fan switch is set in the auto position and the thermostat calls for cooling, a circuit is completed between the R, Y and G terminals. The motor is energized through the cool fan terminal and runs on the selected speed. The fan off setting is fixed at 60 seconds for SEER enhancement.
Heating Cycle When the system switch is set on HEAT and the fan is set on AUTO,
and the room thermostat calls for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of com- bustion air is being provided, a pressure switch activates the ignition
control. The ignition control provides a 30-second warm-up period. The gas
valve then opens for 10 seconds. If the flame is not detected within 2 seconds of the gas valve opening, the gas valve is shut off and a retry operation begins. If the flame is lost for 2 seconds during the 10 second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation the ventor starts a 15 second inter- purge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition, during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one
hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been cor-
rected the furnace will again lockout after three retries. A momentary loss of gas supply, flame blowout, or a faulty flame probe
circuit will result in a disruption in the flame and be sensed within 0.8 seconds. The gas valve will de-energize and the control will begin a recycle operation. A normal ignition sequence will begin after a 15 sec- ond inter-purge. If during the three recycles the gas supply does not return, or the fault condition is not corrected the ignition control will lock-
out for 60 minutes. During burner operation, a momentary loss of power for 50 milliseconds
or longer will de-energize the gas valve. When the power is restored, the gas valve will remain de-energized and the ignition sequence will immediately restart.
As the gas starts to flow and ignition occurs, the flame sensor begins its sensing function. If a flame is detected during the 10 second flame sta- bilization period the circulating blower will energize 30 seconds after the gas valve opens (20 seconds after the flame stabilization period ends). Normal furnace operation will continue until the thermostat circuit between R and W is opened. When the thermostat circuit opens, the ignition control is de-energized. When the ignition control is de-ener- gized, the gas flow stops, and the burner flames are extinguished. The ventor continues to operate for 15 seconds after the gas flow stops.
The blower motor continues to operate for the amount of time set by the fan-off delay "Jumper" located on the ignition control board. Refer to Figure 6. The heating cycle is complete, and the furnace is ready for the start of the next heating cycle.
129099-BUM-J-0112
LINE VOLTAGE BLACK - HIGH SPEED RED -LOW SPEED
FAN OFF
JUMPER
ADJUSTMENT
FANON _
JUMPER _-
M-
FUSE 3A
FIGURE 6: Furnace Control Board
Hot Surface Ignition System
AWARNING
HOT SURFACE IGNITION SYSTEM Do not attempt to light this furnace by hand (with a match or any other
means). There may be a potential shock hazard from the components
of the hot surface ignition system. The furnace can only be lit auto-
matically by its hot surface ignition system.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1. Check to see that the power to the furnace and the ignition control module is ON.
2. The manual shut-off valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system's
response. Then use the troubleshooting section in this manual to check the system's operation.
AWARNING
Never bypass pressure switch to allow furnace operation. To do I
so will allow furnace to operate under potentially hazardous con- I
ditions. [
Do not try to repair controls. Replace defective controls with [ UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
Johnson Controls Unitary Products 7
129099-BUM-J-0112
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self diagnostic capability. If a system problem occurs, a fault code is shown by a blinking green LED. It is located behind a clear view port in the blower compartment door. DO NOT turn off furnace power as this action will clear the control's memory of the
fault.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced as the control is not field repairable.
Flash sequence codes 1 through 6 are as follows: LED will turn "on" for one second and "off" for one second. This pattern will be repeated the number of times equal to the code. For example, six "on" flashes equals
a number 6 fault code.
All flash code sequences are broken by a 2 second "off" period.
IGNITION CONTROL
Normal flame sense current is approximately
3.7 microamps DC (ua)
Low flame signal control lockout point is
0.9 microamps DC (ua)
1 FLASH: Ignition failure. 2 FLASH: Combustion air pressure switch closed, this indicates that the
normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or mis-wiring.
3 FLASH: Combustion air pressure switch failed to close, this indicates the normally open pressure switch contact did not close at the begin- ning of the heat cycle. This could be caused by a number of problems; faulty inducer, blocked vent pipe, broken pressure switch hose or faulty pressure switch.
4 FLASH: Limit Switch Open, this indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.
5 FLASH: Gas flow with no call for heat. Check gas valve and gas valve wiring.
RAPID FLASHES: Reverse Polarity, reverse polarity indicates reverse line voltage polarity. Both heating and cooling will be affected. Check polarity of both.
STEADY ON: Normal Operation. 60 MINUTE AUTOMATIC RESET FROM LOCKOUT: This control
includes a "watchdog" type circuit that will reset from a lockout condition after 60 minutes. Operational faults 1, 3, 4 and Steady On will be reset. This provides protection to an unoccupied structure if a temporary con- dition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the "watchdog" would restart the unit and provide heat for the house.
NOTE: If a flame is detected the control flashes the LED for 1/8 of a
second and then enters a flame stabilization period.
(Seconds) 0 5 32
THERMOSTAT
INDUCER
IGNITOR
MAIN VALVE
CIRCULATING BLOWER
FIGURE 7: Furnace Event Control Schedule
I
OFF_ ION
I
ION
I
o ,
I ION
OFF
OFF
Thermostat Calling for Heat
Fan on Delay
12 Seconds
I I
I I
I I
I I
I OFF
OFF
( Thermostat Satisfied
I I
I I
I I
I I
I !
I R
,IoFF
IPost i v IiPurge I
I
OFF
OFF
lOFFI
ON
I
60, 90, 120, 180 SEC. _OFF Selectable Fan Off Delay
A
/
8 Johnson Controls Unitary Products
129099-BUM-J-0112
SECTION II1: REPLACEMENT PARTS LIST
All components, assemblies, accessories, and replacement parts for this furnace are available through your qualified service installer or refer to the service center list in your booklet. It is not recommended that the homeowner purchase, install, or replace any components of this furnace. Contact your local contactor, dealer, or service provider for additional information.
\_J
o . .o
,[ [] J
1°
*_ IIII ÷
od
CONTROL BOX DETAIL
Johnson Controls Unitary Products 9
129099-BUM-J-0112
DGAA
ITEM DESCRIPTION DGAA056BDTB DGAA070BDTB DGAA077BDTB DGAA090BDTB
Switch, Pressure $1-32435972000 S 1-32435972000 S1-32435972000 S1-32435972000 <
2 Tubing Silicone (2' Req'd) $1-02812499000 $1-02812499000 $1-02812499000 $1-02812499000
Limit Switch, Manual(Upper) $1-02535358000 $1-02535358000 $1-02535358000 $1-02535358000
4 Assembly, Booster (w/Motor) $1-37319801821 $1-37319801821 $1-37319801821 $1-37319801821
Control Board, Integrated $1-03101932002 $1-03101932002 $1-03101932002 $1-03101932002
6 Valve, Gas $1-02543267000 $1-02543267000 S1-02543267000 $1-02543267000 7 Bracket, Mounting (Gas Valve) $1-07319801064 $1-07319801064 $1-07319801064 $1-07319801064 <
8
9 Exchanger, Heat (w/Gaskets) $1-37319804651 $1-37323792001 $1-37323792002 $1-37323792003 10 Sensor, Flame $1-02535354000 $1-02535354000 $1-02535354000 $1-02535354000 _1 _ Switch, System $1-7681-3301 $1-7681-3301 $1-7681-3301 $1-7681-3301
Transformer (115-24V, 40 VA) $1-2940A3541 $1-2940A3541 $1-2940A3541 $1-2940A3541
3 Switch, Limit S1-02535380000 S 1-02535380000 $1-02535381000 $1-02535381000
14 Burner Assembly, Auto Ignition $1-37319801403 $1-37319801403 $1-37319801403 $1-37319801403
(Includes items 10 & 15) 15 Ignitor, Hot Surface $1-02541021000 $1-02541021000 $1-02541021000 $1-02541021000 16 Filter (2 Req'd) (16x20x1) $1-1214-2511 $1-1214-2511 $1-1214-2511 $1-1214-2511
17 Panel, Door (Upper) Accessory (See Page 4) 18 Panel, Door (Lower, Tall) 7900-7611 7900-7611 7900-7611 7900-7611
................................Motor (See Note 2) (old-see note 4) S1-1468-220P S1-1468-220P S1-1468-220P S1-1468-220P
Motor new-seenote4 $1-02435603000$1-02435603000$1-02435603000$1-02435603000
20 Assembly, Motor Mount (See Note 2) $1-37319806100 $1-37319806100 $1-37319806100 $1-37319806100 21 Plug, Connector $1-02521192000 $1-02521192000 $1-02521192000 $1-02521192000
Capacitor, Run (See Note 3)(Old-see note 4) $1-02420063000 $1-02420063000 $1-02420063000 $1-02420063000
Capacitor (New-see note 4) S 1-02435602000 S 1-02435602000 S 1-02435602000 S 1-02435602000
............................................................Capacitor (Units built on/after 8/11/2008) $1-02435813000 $1-02435813000 $1-02435813000 $1-02435813000
23 Wheel, Blower $1-02619654003 $1-02619654003 $1-02619654003 $1-02619654003
24* Top, Casing $1-07319801342 $1-07319801342 $1-07319801342 $1-07319801342 25* Diagram, Wiring 155887 155887 155887 155887
26* Strike, Door S1-02118364000 S 1-02118364000 S 1-02118364000 S1-02118364000 27* Latch, Door $1-02118365000 $1-02118365000 S 1-02118365000 S1-02118365000 28* Housing, Blower $1-37323864001 $1-37323864001 $1-37323864001 $1-37323864001
29* Gasket, Combustion Air Box $1-01006900005 $1-01006900005 $1-01006900005 $1-01006900005 30* Gasket, Burner S1-01006742000 $1-01006742000 $1-01006742000 $1-01006742000 31" Gasket, Booster Assembly $1-01006900015 $1-01006900015 $1-01006900015 $1-01006900015 32* Gasket, Heat Exchanger $1-01006900001 $1-01006900001 $1-01006900001 $1-01006900001
NOTE:
*Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 1/12. Major components and suggested stocking items are shown with shaded item number.
"<" Across from row indicates a change in that row.
--- Not applicable to specified model.
2.
For Serial Numbers lower then 001207164- Replacement DGAA motors also require Motor Mount
Assembly 373-19806-100 if replaced motor has integral, flex-arm motor mount.
3.
DGAA with 5-Ton Blowers are provided as an accessory item and are not standard equipment from
the factory. See Page 4
4.
The "old" motor must use the "old" run capcitor. The "new" motor can use either capacitor. Serial No. WOF6528688 and above were built with the new motor.
10 Johnson Controls Unitary Products
DGAH
ITEM DESCRIPTION DGAH056BBSB DGAH077BBSB
Switch, Pressure $1-32435972000 $1-32435972000 <
2 Tubing Silicone (2' Req'd) $1-02812499000 $1-02812499000
LimitSwitch, Manual (Upper) $1-02535358000 $1-02535358000
4 Assembly, Booster (w/Motor) $1-37319801821 $1-37319801821
Control Board, Integrated $1-03101932002 $1-03101932002
6 Valve, Gas $1-02543267000 $1-02543267000
7 Bracket, Mounting (Gas Valve) $1-07319801064 $1-07319801064 < 8
9 Exchanger, Heat (w/Gaskets) $1-37319804651 $1-37323792002
10 Sensor, Flame $1-02535354000 $1-02535354000
Switch, System $1-7681-3301 $1-7681-3301 Transformer (115-24V, 40 VA) $1-2940A3541 $1-2940A3541 Switch, Limit $1-02535380000 $1-02535381000
14 Burner Assembly, Auto Ignition $1-37319801403 $1-37319801403
(Includes itemss 10 & 15) 15 Ignitor, Hot Surface $1-02541021000 $1-02541021000 16 Filter (2 Req'd) (16x20x1) $1-1214-2511 $1-1214-2511 17 Panel, Door (Upper) Accessory (See Page 4) 18 Panel, Door (Lower, Short) 7900-7671 7900-7671
Motor $1-02431948000 $1-02431948000
20 Assembly, Motor Mount ......
21 Plug, Connector $1-02521192000 $1-02521192000
::22 Capacitor, Run ......
23 Wheel, Blower S1-02619654003 S 1-02619654003
24* Top, Casing $1-07319801342 $1-07319801342 25* Diagram, Wiring 157953 157953
26* Strike, Door S 1-02118364000 S1-02118364000 27* Latch, Door $1-02118365000 $1-02118365000
28* Housing, Blower $1-37323864001 $1-37323864001 29* Gasket, Combustion Air Box $1-01006900005 $1-01006900005
30* Gasket, Burner $1-01006742000 $1-01006742000 31" Gasket, Booster Assembly $1-01006900015 $1-01006900015
32* Gasket, Heat Exchanger $1-01006900001 $1-01006900001
129099-BUM-J-0112
NOTE: *Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 1/12. Major components and suggested stocking items are shown with shaded item number, "<" Across from row indicates a change in that row.
--- Not applicable to specified model.
3. DGAH with 5-Ton Blowers are provided as an accessory item and are not standard equipment from the factory, See page 4.
BURNER ORIFICE CHART (Normal Altitude Only, See Note 5)
MODEL
NATURAL GAS
LP GAS
ACCESSORY DESCRIPTION DGAA DGAH
5-Ton BlowerAss'y Motor $1-02431975000 $1-02431975000
7900-7751 Run Capacitor (20 MFD) $1-02420051000 $1-02420051000
NOTES
5 Contact Customer Service for installations at altitudes over 2000 feet above sea level.
"<" Across from row indicates a change in that row.
--- Not Applicable to specified model.
056 070 077
S1-9951-1361 S1-9951-1541 S1-9951-1611 $1-9951-0821 $1-9951-0931 $1-9951-0981
ACCESSORY PARTS LIST
Door Panel (Upper) 7900-7631 7900-7631
Motor Mount $1-37319802930 $1-37319802930 Blower Wheel $1-1472-2761 $1-1472-2761
O9O
$1-9951-1771 $1-9951-1061
Johnson Controls Unitary Products 11
Y
..-[
8
0
'11
r-
m
GO
-W
5" E]
B
i
E3
6-)
BLOWER SPEED CHART
CHARTE DE VITESSE
DE LA SOUFFLERIE}
INPUT CF# COOL
(ENTREE) (PCM/ HIGH HEAT
(CL[MA) (CHAU_
BLK REO
056 I_OO (NOI_) (ROUG)
BLK REO
O70 1200 (NOIR) (ROgG)
BLK REO
077 1200 (NOIR) (ROU6)
BLK RE8
O9O mOO (NOLO) (ROUS)
WIRE COLOR KEY
(CODE DE COULEUR
DC FILAGE)
BLK BLACK
(NO/R/ (NOIR)
BLU BLUE
BLEU (GLEU)
RED RED
(ROUG_ ROUGE}
YEL YELLOW
{ AUN (AUNE)
_T WHITE
(BLANC) (t_LANC]
BRN BRO'_#_
(BRUN (_Rux)
GRN GREEN
(VERT (VERT)
PRP PURPLE
(POURPRE) (POURPRE)
OR ORAXGE
{ORA) (ORANGE',
CAUTION
OPE ALL DISCONNECTS BEFORE
SERV[CING THIS UNIT
r:RE_CAUTION
OUVREZ LES OISJONCTEURS AVANT
DE _ROCE'DER AVEC LE SERVICE
BOX DOWNFLOW FURNACE
(FOURNAISE 80X
VENTZLEE PAR LE BAS)
LADDER DIAGRAM
DIAGRAMME ELEMENTAIRE
_/_ POWER SUPPLY 115 160 SEE NOTE IOS
/ALIMENTATION 115 160 VOIR NOTE I)
} TOGGLE S?_]TCH.A _(CO_MUTATEUR (MOTEUR OE
LEV]ER)
(RELAIS CHAUF/CLIM) 50UFFLER[E)
....
LL_ .... ( ..... 1 _
_ALi/y,700L =
ij RELA[S
RELA? ' o'I CT} (9'INDUCT
S
MOTEUR)
qT (4OVA)
_N 'q
HEAT/COOL THERMOSTAT
(THERMOSTAT CLIMA/CHAUFJ
--4 I
GN,S (EN TERRE)
GAS VALVE !
RELAY
E TERRE)
(RELAIS _?E SOUPAPES
DE GAZ)
NOTES:
i ALL FIELD WIRING PER; (A) NATIONA
(B) CANA©IA
(C) LOCAL 0
2 IF ANY OF THE ORIGINAL WIRE AS SU
REPLACED, IT MUST BE REPLACED WIT
TEMPERATURE RATING OF AT LEAST 22 51 CONNECTORS SUITABLE FOR COPPER CO 4, ALL REPLACEMENT COMPONENTS MUST B 5 PROVIDE OISCONNECTS FOR ALL POWER 6, MOTORS ARE INHERENTLY PROTECTED 7 SSI 1S IN SERIES WITH LSI AND LS2
L ELEC CODE (NEC) AND/OR/ N ELEC CODE (CEC) AND/OR/ R CITY CODES. PPLIEO WITH THE FURNACE MUST BE H WIRING MATERIAL HAVING A PF (105_C). NDUCTORS ONLY
E PROPERLY GROUNDED.
SUPPLIES
NOTES:
II TOUT FILAGE EN CHANTIER SELON: (A CODE ELEC NATIONAL (CEN') ET/OU/
(B CODE ELEC CANADiEN (CEC) ET/OU/ (c CODES LOCAUX ET MUNICIPAUXI
2 SI LE FILAGE DOlT ETRE REMPLACE E N PATRIE OU EN TOUT, IL DOlT
L'ETRE AVEC UN MATERIAUX POUVANT RESISTER A DES TEMPERATURES O'AU MOINS 22PF (105_C)
5. SEULEMENT DES MARETTES POUR FIL D E CUIVRE. TOUTE COMPOSANTE DE REMPLACEMENT DOlT [ETRE BIEN MISE EN TERRE. 5 FOURNISSEZ LES DISJONCTEURS POUR L*ALIMENTAITON 6 LES MOTEU_S SONT PROTEGES DE PAR LEUR CONCEPTION. 7 SSI OE SE_IE AVEC LSI ET LSZ
CONNECTION DIAGRAM
(DIAGRAMME DE RACCORDEMENT)
BRN
__1 2 _RN
GAS VALVE
I O'_N GR
IGND
(E TERRE)
FLAME SENSOR
YEL YEL
CAPTEUR DE
FLAMME) _R
, P5/S_
HOT _ R_ I NITER
(IGNITION DE _i
SdRFACE CHA _}E
BLK
6LK
GRN
L BRN
!
_RN
6NO = _
[EN TERRE} /'IRC ®
BLU "_
BLU
8RY
FURNAC_ CONTROL
PI/SI ( NTROLE DE LA
WHT FOURNAISE)
WHT RED
RED 2¢v 9EC 5LU _LK _ _
O;_N LSI aLU LS2 o*w
DE SURCHARGE DE TIn/
LEGEND
OS DISCONNECT SWITCH v AS VALVE
IGN HOT SURFACE IGNITER
PI/SI 9 PIN PLG & SOCKET ON FRNA CE CONTROL BOARD
P2/$2 6 PI PLUG & SOCKET ON FURNACE CONTROL BOARD
o3/95 2 DIN PLUG & SO(KET AT HOT SURFACE IGNITOR
: 4/._-4 9 PIN *_L & SO KET LSI,2 AUXILIARY LIMIT SWITCH ON !?LOWER INLET
ILP PRESSURE S_ITCH
IRC R 1,, CAPACITOR
IT TRAN_,FORMER, 4OVA
IDENTIFIED RU_ CAPACITOR 24V CO NECT[O ROOM THERM STAT
O FIELD CON ECT[ON
FACTORY WIRIN AND _}EVICES
FIELD WIRING A O DEVICES
_ RELAY CONTACT! C IGNITION
_L CONTROL _30ARD
LEGENDE
OS COMMUTATEUR DE DISJONCTON
GV SOUPAPE DE GAZ
IGN IGNITION DE SURFACE CHAUOE PI/SI PRISE & RECEPTACLE A 9 PTS S UR LA PLAOUETTE DE CONTROLE D'IGNIT[ ON P2/$2 PRISE & RECEPTACLE A 6 PTS SU R LA PLAQUETTE DE CONTROLE D'IGNIT[O N P5/$3 PRISE ET RECEPTACLE A 2 PTS i} 'IGNITION DE SURFACE CHAUDE P4/S4 PRISE ET RECEPTACLE A 9 PTS LSI,Z COMMUTATEUR AUXILIAIRE DE PRE SSION SUR _OITIER DE SOUFFLERiE
ILP COMMUTATEUR DE PRESS[ON IRC CAPACITEUR DE FONCTIONNEMENT ID ENTIFIE
IT TRANSFORMEUR, _OVA
@ CAPACITEUR DE FONCTIONNEMENT IDENTIF IE
2#v RACCORDEMENT OU THERMOSTAT DE PIECE
0 RACCOROEMENT DE CHANTIER
FILAGE DE L'USINE ET APPARE[LS
FILAGE DE CHANT[ER ET APPAREIL s
Fq
_L _ CONTACTE9 DES RELAIS 9UR LA PLAQUETT E OE CONTROLE ©'IGNiTiON
155887 UWD A 0705
¢o
(.o O (.o
¢__
6
Y
c
o
"11
r-
m
_0
_3
B 3
i
E3
© >
-I-
WIRE COLOR KEY
(CODE DE COULEUR
DU FILAGE)
BLK 8LACK
[NO{R} _NOIR)
BLU BLUE
[BLEU} (BLEU)
RED RED
{ROUG_ (ROUGE)
YEL YELLOW
(JAUN} (JAUNE)
WHT WHITE
{BLANC} (BLANC)
BAN BROWN
{BRUN) {SPUN)
GRN GREEN
(VENT) (VENT)
PRP PURPLE
(POURPRE) (POURPRE)
ORN ORANGE
(ORA) (ORANGE}
CAUTION
OPEN ALL DISCO ECTS BEFORE
SERVIC[ G THiS (NIT
PRE_CAUTION
OVREZ LES DISJONCTE RS AVAT
DE PROCE'DER AVEC LE SERVICE
BOX DOWNFLOW FURNACE
(FOURNAISE 80X
VENTILEE PAR LE BAS)
LADDER DIAGRAM
DIAGRAMME E[EMENTAIRE CONNECTION DIAGRAM
(DIAGRAMME DE RACCORDEMENT)
POWER SUPPLY 115160 SEE NOTE I
OS _/ _ (ALIMENTATION 115 160 VOIR NOTE I)
HEAT/COOL RELAY
lj {RELAIS
RELAY D'I DUCT) (D'INDUCT
MOTEUR)
8
i {RELA[S
°RELAY !}'IG ]TION II'_R _?M
IT (#OVA}
o
I COOL r({) -- _0
HEAT/COOL THERMOSTAT
',THERMOSTAT CL[MA/CHAUFJ
NOTES:
I. ALL FIELD WIRING pER; A) NATIONA
(B CA ADIA
{C) LOCAL O
2. IF ANY OF THE ORIGINAL WIRE AS SU REPLACED, IT MUST BE REPLACED WIT
TEM_ERATURE qATING OF AT LEAST 22
'ONNECTORS SUITABLE FOR COPPER CO
4 ALL REPLACEMENT COMPONENTS MUST
5. PROVIDE DISCONNECTS FOR ALL POWER
6 MOTORS ARE INHERENTLY ROTECTED 7 SSI IS IN SERIES WITH LSI AND LS
NOTES_
I. TOUT FILAGE EN CHANTIER SELON, (A
(B (C
2. SI LE FILAGE DOIT ETRE REMPLACE L'EtRE AVEC UN MATER[AUX POUVANT D'AU _O/NS 22PF (105_C)
3, SEULEMENT DES MARETTES POUR FIL D
4 TOUTE COMPOSANTE OE REMPLACEMENT
5 FOURN[SSEZ LES DISJONCTEURS POUR 8 LES MOTEURS SONT PROTE.GESDE PAR
7 SSI DE SERIE AVEC LSI ET LS2
I
(EN TERRE)
FLAME SENSOR
(CAPTEUR DE
FLAMME]
(EN TERRE)
YEL
GRN
YEL
_RN
_v_ _ Ps/s5
........ __
RELAY
[IGNITION ©E SURFACE CHAUDE)
BE GAZ) BLK
_LK
DE SURCHARGE
DE T]R/
L ELEC CODE (NEC) AND/OR/ N ELEC CODE (CEC) AND/OR/ R CITY CODES
PPLIED WITH THE FURNACE MUST BE H WIRING MATERIAL HAVING A PF (I05"CI NDUCTOR5 ONLY.
E PROPERLY GROUNOED
SUPPLIES.
CODE ELE.C. NATIONAL (CEN) ET/OU/ CODE ELEC CANADIEN [CEC) ET/OU/ CODES LOCAUX ET MUNICIPAUX.
N PATRIE ou EN TOUT, IL OOIT RESISTER A DES TEMPERATURES
E CU]VRE. 30IT [ETRE _]EN MISE EN TERRE. L'ALIMENTAITON
LEUR CONCEPTION
LEGEND
DS DISCONNECT 5_ITCH GV GAS VALVE
IGN HOT SURFACE IGNITER
PI/SI 9 PIN PLUG & SOCKET ON FURNACE CONTROL BOARD
P /S 6 _IN PLUC & _;OCKET ON FURNACE CONTROL OA_D
P3/$3 2 PIN PLUG a SOCKET AT HOT SURFACE IGNIT R
R4/$4 9 PIN PLUG & SOCKET LSh AUXILIARy LIMIT SWITCH ON EiLO WER INLET
ILF' PRESSbRE SW[TH
IRC RN CA_ACITOR
IT TRANSFORMER, 4OVA
@ IDENTIFIED H CA_)AC[TOR
24v CO_,NE{T[O ROOM THERMOSTAT
0 FIELD CONNECTIO
FACTORY WIRIS,G AND 2EV[CES
FIELD WlRIS, O A O DEVICES
RELAY CO TACTS ON IGNITIO
?? ..............
GRN
G_ _RN
(EN TERRE}
BLU I
BLU
GAY
FURNACE CONTROL
PI/SI tCONTROLE nE LA
WHT FOURNAISE)
WHT RED
I
RED 2¢v SEC BLU J
BLK _ ....... WHT
...... I
OR LSI BL LS2 GAY
WHT BLK
SLK
(COMM TATE JR
(IISVCA NEUT.
LEGENDE
DS COMMUTATEUR DE I][SJONCTON
GV SOUPAPE DE GAZ
]GN IGNITION DE SURFACE CHAUDE
RI/SI PRISE & RECEPTACLE A 9 PTS S UR LA PLAOUETTE DE CONTROLE D'IGNIT[ ON P8/$2 PRISE & RECEPTACLE A 6 _TS SU R LA PLAOUETTE OE CONTROLE D']GN[TIO N PS/S5 PRISE ET RECEPTACLE A _ PTS D 'IGNITION DE SURFACE CHAUDE P4/S¢ PRISE ET RECEPTACLE A 9 PTS LSI,2 COM_UTATEUR AUXILIAIRE DE PRE SS[ON SUN BOITIER DE 50UFFLERIE
ILP COMMUTATEUR DE PRESSION IRC CAPACITEUR DE FONCT[ONNEMENT ENT[FiE
IT TRANSFORMEUR, 4OVA
@ CAPACITEUR DE FONCTIONNEMENT I©ENTIF IE z_ Z4V RACCORDEMENT OU THERMOSTAT OE PIECE 0 RACCORDEMENT DE CHANTIER
FILAGE DE L'USINE ET APPARE[LS
FILAGE DE CHANTIER ET APPAREIL S
_ ....................................... OLED' ........
157955 UWD A 0705
¢o
(.o 0 (.o
L
6
LimitedWarranty
For Manufactured Housing Furnace
UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will replace parts that prove to have
such defects according to the terms outlined below.
FURNACE MODELS
Furnace Model Heat Exchanger l Parts Coverage Labor and Trip Coverage*
DGAA, DGAH 10 years / 2 years 1years
The warranty period for any replacement heat exchanger or part provided here under shall not extend beyond the warranty period stated above. The heat exchanger warranty is on a parts only basis: no labor, freight or other service charges are allowed.
The warranty period will begin on the purchase date of the residence when the product is installed as original equipment, or the installation date when installed in a residence previously purchased by the consumer. Return the Warranty Registration Card to UPG promptly after product installation or purchase for your
benefit and protection. The warranty period will begin upon product shipment from UPG in the absence of a recorded Warranty Registration Card. This warranty applies to the original consumer/purchaser and any subsequent purchaser. The warranty does not apply if the furnace is removed from the orig-
inal residence, or if the residence has been moved from the original location where the furnace was placed in service. This warranty applies only to products installed: (1) in the United States of America or Canada; (2) in accordance with UPG recommendations and specifica-
tions outlined in the Installation Manual provided with the product; (3) in accordance with all national, state/provincial, and local codes; and (4) in the original residence.
Exclusions
1. Shipping/freight, or material charges.
2. Damages resulting from transportation, mishandling, improper application, installation or servicing.
3. Damages resulting from accident, abuse, fire, flood, or other acts of nature.
4. Use of the product in a corrosive atmosphere.
5. Alteration, tampering, defacing or removing the product serial number will serve to void the warranty.
6. Damages resulting from inadequacy or interruption of electrical service, improper energy supply, blown fuses, improper wiring external to the unit or other like damages.
7. Damages resulting from the use of components not approved by UPG.
8. This warranty does not cover consequential damages, incidental damages or incidental expenses including damages to property.
9. Damages caused by failure to perform normal or routine maintenance as set out in the operation and service instructions.
10. Cleaning, replacement of filters, or any other routine maintenance as set out in the User's Information, Maintenance and Service Manual.
11. Replacement or cleaning of nozzles or orifices.
12. Fuses either internal or external to the product.
13. Excessive fuel or electricity consumption.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL-
ITY AND FITNESS FOR A PARTICULAR PURPOSE. SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU.
SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES, OR LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE
DURATION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURATION OF THE EXPRESS WARRANTY ON THE FACE HEREOF. IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CON-
TRACT TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTHERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSE- QUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR
PROFITS, COST OF SUBSTITUTE EQUIPMENT. THIS WARRANTY DOES NOT COVER CONSEQUENTIAL DAMAGES. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG SUPPLIERS AND SUBCONTRACTORS. THE ABOVE LIMITATION ON CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, OR FOR STRICT LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU. UPG DOES NOT ASSUME, OR AUTHORIZE
ANY PERSON TO ASSUME FOR UPG ANY LIABILITY FOR THE SALE OF THIS PRODUCT. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
TO OBTAIN WARRANTY SERVICE
Consult the Authorized Service Center list packed with the furnace installed in the manufactured home or contact your installing or servicing dealer. Or, look in the Yellow Pages of the telephone book under Mobile Homes-or Manufactured Housing-Repair and Service for the name and telephone number of
the nearest authorized manufactured housing service center. If local authorized service cannot be obtained, or you are unable to contact your installing dealer, contact the authorized distributor in your area. If there is no distributor in your area, and you cannot obtain proper service under the terms of the warranty,
please write: Unitary Products Group (UPG) Customer Relations Department, PO Box 19014, Wichita, KS 67204-9014.
Subject to change without notice. Published in U.S.A. Copyright _>2012 by Johnson Controls, Inc. All rights reserved.
Johnson Controls Unitary Products
Wichita, KS 67204-9014
P.O. Box 19014
Supersedes:
129099-BUM-J-0112
129099-BUM-I-0711
Loading...