Coleman C36MW, C42MW Installation Instructions Manual

p
r
r
A
I
INSTALLATION INSTRUCTIONS
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement Keep it with your other important papers.
SAVE THIS BOOK
arts or accessory items when needed.
WARNING: Always leave glass doors fully opened or fully closed when operating this fireplace.
This firebox meets the construction and safety standards of H.U.D. fo application in mobile homes when installed according to these instructions.
Includes: Manual Variable Control Fan System, Combustion
Air Kit and Bi-Fold Doors with Brushed Brass Finish
This fireplace is approved for use as a wood burning fireplace or fo use with a vented gas log approved to ANS Z21.60, Z21.84 or RGA 2-72 standards or ANS Z21.11.2 standard. A DESA hood must be installed when using a vent-free gas log heater (see Accessories, p. 12).
C36MW
36” Circulating Firebox
for use with a vent-free gas log heater approved to
LL DIMENSIONS IN THIS MANUAL ARE IN
NCHES UNLESS OTHERWISE SPECIFIED
DESA INTERNATIONAL
2701 INDUSTRIAL DRIVE P/N 108918-01 P.O. BOX 90024 REV D BOWLING GREEN, KY 42101-9004 6/02
www.desatech.com
CONTENTS
1. INTRODUCTION ------------------------------------------------------------- PG. 2
2. SELECTING LOCATION ------------------------------------------------------------- PG. 2
3. MINIMUM CLEARANCES ------------------------------------------------------------- PG. 2
4. FRAMING AND INSTALLING ------------------------------------------------------------- PG. 3
5. HEARTH EXTENSION ------------------------------------------------------------- PG. 3
6. OUTSIDE AIR KIT INSTALLATION ------------------------------------------------------------- PG. 4
7. FAN KIT ASSEMBLY ------------------------------------------------------------- PG. 4
8. CHIMNEY PIPE ------------------------------------------------------------- PG. 4-5
9. FIRESTOP THIMBLE AND SPACERS ------------------------------------------------------------- PG. 5-6
10. FLASHING AND TERMINATION ------------------------------------------------------------- PG. 7
11. FINISHING YOUR FIREPLACE ------------------------------------------------------------- PG. 8
12. MANTEL ------------------------------------------------------------- PG. 8
13. GLASS DOORS ------------------------------------------------------------- PG. 8
14. GAS LINE INSTALLATIONS ------------------------------------------------------------- PG. 9
15. DAMPER OPERATION ------------------------------------------------------------- PG. 10
16. TECHNICAL SERVICE ------------------------------------------------------------- PG. 10
17. ILLUSTRATED PARTS ------------------------------------------------------------- PG.11-11a
18. REPLACEMENT AND TECHNICAL PARTS ------------------------------------------------------------- PG.12
19. PART NUMBER REFERENCE TABLE ------------------------------------------------------------- PG.12a
- 1 - For more information, visit www.desatech.com
r
d
n
N
jury
y
l
b
r
Do not store or use gasoline or any other flammable vapors or liquids in the vicinity of this or any othe appliance.
Due to high temperatures, the appliance should be located out of traffic and away from furniture an draperies.
Do not place clothing or other flammable materials o or near the appliance.
EVER leave children unattended when a fire is
burning in the fireplace.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause in propert for assistance or additional information. Consult a qualified installer or local distributor.
damage, or loss of life. Refer to this manua
CHECK HUD REQUIREMENTS BEFORE INSTALLING THIS FIREPLACE.
FOR YOUR SAFETY
,
INTRODUCTION
BEFORE BEGINNING THE INSTALLATION OF THE FIREPLACE, READ THESE INSTRUCTIONS THROUGH, COMPLETELY.
This DESA fireplace and its components are safe
when installed according to this installation manual. Unless you use DESA components, which has been designed and tested for the fireplace system, you may cause a fire hazard.
The DESA warranty will be voided by and DESA
disclaims any responsibility for the following actions:
a) Modification of the fireplace, components, doors, blower, fans, air inlet system and damper control. b) Use of any component part not manufactured or approved by DESA in combination with a DESA fireplace system.
PROPER INSTALLATION is the most important step in ensuring safe and continuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces. Although grounding may not be required by code the manufacturer recommends it.
This Model fireplace C36MW meets the construction and safety standards of HUD for application in mobile homes when installed according to these instructions.
WARNING: Do not install a fireplace insert in this box unless the manufacturers instructions with the insert specifically state this fireplace has been tested for use with the insert.
USE SOLID WOOD OR PROCESSED SOLID FUEL
FIRELOGS ONLY.
-2 - For more information, visit www.desatech.com
WARNING: When processed wood fuel fire logs
are used, do not poke or stir the logs while they are
urning. Use only fire logs that have been evaluated fo the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use.
This fireplace is not intended to be used as a substitute for a furnace to heat an entire home. Use for supplemental heat only.
This wood burning fireplace complies with UL 127 standard as a FACTORY BUILT FIREPLACE.
CAUTION: The structural integrity of the mobile home floor, and ceiling/roof must be maintained.
SELECTING LOCATION
To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines:
1.) The location must allow for proper clearances (see figures 1 & 2).
2.) Consider a location were the fireplace would not be affected by drafts, air conditioning ducts, windows or doors.
3.) A location that avoids the cutting of joists or roof rafters will make installation easier.
4.) An outside air kit is included with this fireplace. For more details refer to section on outside air kit installation on page 4.
MINIMUM CLEARANCES TO COMBUSTIBLES
Back and side of fireplace -------------- ¾” minimum Note: The ¾” clearance is not required at the nailing flanges
Floor* ------------------------------------- 0” minimum *See step 2 of “Installing the Fireplace” on page 3
Perpendicular Wall to Opening of unit - 14” minimum
Top Spacers ------------------------------ 0” minimum
Mantel Clearances ---------------------- see page 8
“Mantels”
Chimney Outer Pipe Surfaces --------- 1” minimum
insulation or other materials.
MINIMUM / MAXIMUM CHIMNEY HEIGHT
The minimum height of the chimney, measured from the base of the fireplace to the flue gas outlet of the termination, is 11.5 feet for straight flue or a flue with one elbow set. The maximum distance between elbows is 2 feet. For systems with 2 elbow sets, minimum height is 22 feet. The maximum height of any system is 28 feet. This measurement includes the fireplace, chimney sections and the height of the termination assembly at the level of the flue gas outlet (see page 6, figure 15).
WARNING: Do not install in a bedroom.
WARNING: Do not pack required air spaces with
FRAMING AND INSTALLING THE FIREPLACE
y
STEP 1: Frame the opening for the fireplace using the dimensions shown in figures 1 & 2. STEP 2: If the fireplace is to be installed directly on carpeting, tile (other than ceramic), or any combustible material other than wood flooring, the fireplace must be installed upon a metal or wood panel extending the full width and depth of the fireplace. STEP 3: Set the fireplace directly in front of this opening and slide the unit back until the nailing flanges touch the side framing. STEP 4: Check the level of the fireplace and shim with sheet metal if necessary. Make sure the unit is balanced on each side. STEP 5: Before securing fireplace to prepared framing, the ember protector (provided), must be placed between the hearth extension (not supplied), and under the bottom front edge of the fireplace to protect against glowing embers falling through. If the fireplace is to be installed on a raised platform, a Z-type ember protector (not supplied) must be fabricated to fit your required platform height. The ember protector should extend under the fireplace a minimum of 1 - 1/2”. The ember protector should be made of galvanized sheet metal (28-gage minimum) to prevent corrosion. STEP 6: Secure the fireplace to the floor using tie-down straps (see figure 3) to prevent shifting.
Figure 1 FRAMING DIMENSION
Figure 2 CORNER INSTALLATION
Figure 3 TIE-DOWN STRAP
HEARTH EXTENSION
A hearth extension projecting a minimum of 16” in front of and a minimum of 8” beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace. Fabricate a hearth extension using a material which meets the following specifications: a layer of non-combustible, inorganic material having a thermal conductivity of K = 0.84 BTU IN/FT. HR. F (or less) at 1” thick. For example, if the material selected has a K factor of
0.25, such as glass fiber, the following formula would apply:
0.25 x 1.0” = 0.30 thickness required
0.84
Thermal conductivity “K” of materials can be obtained from the manufacturer or supplier of the non-combustible material. If the hearth extension is to be covered, use non-combustible material such as tile, slate, brick, concrete, metal, glass, marble, stone etc. Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a non-combustible material (see figure 4).
Figure 4 HEARTH EXTENSION
WARNING: Hearth extension is to be installed onl
as illustrated.
- 3 - For more information, visit www.desatech.com
OUTSIDE AIR KIT (MODEL AK-6)
The installation of an outside air kit should be performed during the rough framing of the fireplace due to the nature of its location. Outside combustion air is accessed through the mobile home floor (Refer to AK-6 Installation Instructions for details). In some instances, a wall installation is required (see Figure 5). Note: An AK-6WAI Air Kit must be ordered when a sidewall installation is required (see accessories on page 12). This fireplace is equipped with a barometric damper, which allows outside air to flow in the fireplace automatically when needed.
Figure 5 OUTSIDE AIR KIT
FAN KIT ASSEMBLY (BK3)
A fan kit assembly is preinstalled in this fireplace. Use of blowers or fans other than manufactured by DESA voids the warranty. The fan is operated by pressing the rocker switch located at the lower right hand corner of the fireplace face. Fan kit electrical connections are made through the electrical cover plate located on the side of the fireplace as shown in figure 6a.
Figure 6a FAN SWITCH AND STRAIN RELIEF
FAN KIT WIRING INSTRUCTIONS
i. Loosen the strain relief by turning the plastic screw
counterclockwise.
ii. Remove electrical cover plate (with strain relief)
from the fireplace by removing the two sheet metal screws as shown in figure 6a.
iii. Slide power source wiring through the strain relief
opening and electrical cover plate and make all the necessary connections.
iv. Slide all wiring connections in the electrical housing
as shown in figure 6b.
v. Secure the electrical cover plate with screws
previously removed.
vi. Tighten strain relief plastic screw. NOTE: Electrical housing and cover plate have sharp edges, wear protective gloves.
Figure 6b ELECTRICAL HOUSING
CHIMNEY PIPE
The DESA chimney system consists of 12, 18, 24, 36 and 48 inch, snap-lock double-wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consideration (lineal gain) and are given in the lineal gain chart (see figure 7). There are two vent kits available, which have been specially designed for common installations in manufactured (mobile homes): MW8K (8’ Vent Kit) and MW9K (9’ Vent Kit). The contents of these kits are listed under accessories on page 12. Most chimney systems for manufactured houses require a standard straight installation as described in this section. If an uncommon offset installation is required, see page 10.
Figure 7 LINEAL GAIN
Important: If the height of the chimney assembly exceeds requirements for transportation of the home, the chimney installation may be completed after the home is sited. Note: the termination must always be installed after the home is sited.
- 4 - For more information, visit www.desatech.com
ASSEMBLY AND INSTALLATION OF THE DOUBLE
y
WALL CHIMNEY SYSTEM
Each double wall chimney section is consist of a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. The pipe sections must be assembled independently as the chimney is installed. When connecting chimney directly to the fireplace, the inner flue pipe section must be installed first with the lanced side up. The outer pipe section can then be installed over the flue pipe section with the hemmed end up. Press down on each pipe section until the lances securely engage the hem on the fireplace starter. The wire will assure the proper spacing between the inner and outer pipe sections.
WARNING: The opening in the collar around the chimne obstructed. Never use blown insulation to fill the chimney enclosure.
at the top of the fireplace must not be
Continue to assemble chimney sections as outlined above, making sure that both the inner and outer pipe sections are locked together. When installing double wall “snap lock” chimney together, it is important to assure the joint between the chimney sections is locked. Check by pulling chimney upward after locking. The chimney will not come apart if properly locked. It is not necessary to add screws to keep the chimney together (exception – see page 6 figure 12).
ADJUSTABLE FIRESTOP THIMBLE (FST-A):
The Adjustable Firestop Thimble Assembly (FST-A) is used to provide the necessary air space and clearance between the chimney pipe and the insulation in the attic space of a manufactured home.
To install the thimble assembly, determine the distance between the ceiling joist and the roof framing. Attach the adjustable thimble to the firestop spacer so that the assembly will cover the distance. The adjustable thimble should be even with or above the roofline (see thimble extensions on page 12 if a longer thimble is needed). Sheet metal screws or staples may be used to attach the thimble to the firestop spacer.
Figure 8 FIRESTOP THIMBLE
An opening large enough to allow the insertion of the firestop thimble assembly will be required in the ceiling. Attach the firestop/thimble assembly to the ceiling/ceiling joist using screws or staples as shown in figure 8. A minimum of 8 screws or staples should be used.
Figure 9 FIRESTOP THIMBLE ASSEMBLY
The firestop thimble assembly should also be used where there is a cathedral ceiling, insulation barrier and roof, all in one assembly in a manufactured home. The FST-A Thimble can be used in any one of three common ceiling pitches: flat, 12”/96”, and 30”/144”.
An opening big enough to allow the insertion of the firestop thimble assembly will be required. This opening depends on the pitch of your ceiling. If your ceiling is a flat or 12”/96” pitch, you must use the adapter plate provided to seal unwanted openings since the opening in the firestop is an ellipse. For 30”/144” pitch, discard the adapter.
Figure 10 FIRESTOP THIMBLE
-5 - For more information, visit www.desatech.com
If the adapter is needed, secure it onto the firestop using holes
j
r
p
provided (see figure 10). The row of holes on the sides of the thimble is provided to allow for pitch variances. Position the firestop assembly and thimble to desired angle and secure with screws provided. Insert the thimble and firestop into the prepared opening and secure to the ceiling by nailing through the firestop flanges. The thimble should be even with or above the roofline. Thimble extensions are available (as an option) when required. See “accessories” on page 12.
NOTE: If there is a second story in the home, firestop spacer V3600FS-8DM will be required. See “Firestop Spacer”.
INSTRUCTIONS WHEN ELBOW OFFSET (30E-8DM)
OF CHIMNEY IS NEEDED
TO INSTALL ELBOWS
1. To achieve desired offset, you may install combinations of 12”, 18”, 24”, 36” and 48” length of double wall pipe (SEE SINGLE OFFSET CHARTAND FIGURE 12).
OFFSET CHART
OFFSET RISE
A B 48" 36" 24" 18" 12"
4 - 3/8 16 -3/8 9 - 3/4 25 - 1/2 1
12 - 3/4 30 - 3/4 1
15 34 - 3/4 1
18 40 1 1
21 - 1/4 46 - 1/4 1 23 - 3/4 49 - 1/4 1 1 27 - 3/4 56 - 3/4 1
30 60 - 3/4 1 1
33 66 1 1
36 71 1 1
38 - 1/4 75 2 41 - 1/4 80 - 1/4 1 1 1
45 86 - 3/4 2
46 - 3/4 89 - 1/2 1 1 1
51 97 1 1
53 - 1/4 101 2 1 56 - 1/4 106 - 1/4 2 59 - 1/4 111 - 1/2 1 1 1 61 - 3/4 115 - 1/2 2 1 64 - 3/4 120 - 3/4 2 1 68 - 1/4 127 1 2
70 130 2 1 1
74 - 1/4 137 - 1/2 1 2 1 76 - 3/4 141 - 1/2 1 2 1 79 - 3/4 146 - 3/4 4
CHIMNEY LENGTH
ELBOW SET ONLY
2. Chimney weight above offset rests on return elbow. Straps must be securely nailed to rafters or joists (see figure 12, details a & b).
3. Maximum length of pipe between supports (return elbow or 12S-8DM) is 2’ of angle run.
- 6 - For more information, visit www.desatech.com
Figure 11 CEILING SUPPORT PIPE
All joints (where two pipes are
oined) should be secured with
two screws, only on the oute
ipe, and shall not penetrate
the inner stainless.
Figure 12 ELBOW OFFSET
FIRESTOP SPACERS (V3600FS-8DM)
Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto the ceiling from below as shown in figure 13.
Figure 13 FIRESTOP SPACER
PENETRATING THE ROOF
To maintain a 1-inch clearance to the pipe on a roof with a pitch, a rectangular opening must be cut. STEP 1: Determine the center point through which the pipe will penetrate the roof. STEP 2: Determine the center point of the roof. Pitch is the distance the roof drops over a given span, usually 12 inches. A 6/12 pitch means that the roof drops 6 inches for each 12 inches one measure horizontally down from the roof rafters. STEP 3: Use the roof opening chart (figure 14) to determine the correct opening length and flashing required. STEP 4: Remove the shingles around the opening measured and cut out this section. STEP 5: Add the next sections of the pipe until the end penetrates the roofline. Check to see that the proper clearances are maintained. Extend chimney by adding sections of double wall pipe until pipe is a minimum of 30 inches above the highest point of the roof cutout. Termination and chimney must extend a minimum of 36 inches above the highest point where it passes through roof.
g
PITCH SLOPE OPENING "A" MAX USE FLASHING
FLAT 0 15 V6F-8DM
0 - 6/12 26.6 16 - 1/8 V6F-8DM
6/12 - 12/12 45.0 20 - 3/8 V12F-8DM
(degrees) (inches) MODEL NO.
Figure 14 ROOF OPENING CHART
FLASHING INSTALLATION (V6F-8DM or V12F-8DM)
Determine the flashing to be used with the roof opening chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nailing through shingles (see figure 15). DO NOT NAIL THROUGH FLASHING CONE.
Figure 15 FLASHING INSTALLATION
INSTALLING FLASHING ON A METAL ROOF
When installing the flashing on a metal roof, it is required that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x ¾” screws and then sealed with roof coating to prevent leakage through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.
STORM COLLAR INSTALLATION (SC1)
Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see figure 16). Apply waterproof caulk around the perimeter of the collar to provide a proper seal.
Note: Storm collar is required but can be installed after the home is sited.
Figure 16 STORM COLLAR
TERMINATIONS / SPARK ARRESTOR
The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination. The terminations approved for this fireplace are the RTL-8DM, which can be use for flashing or chase and the ETL-8DM, for chase style termination only. Figure 17 shows an RTL-8DM round top termination.
Figure 17 TERMINATION
CAUTION: Do not seal openings on the rooftop flashing.
Follow the installation instructions provided with the termination bein
used.
. NOTE: In the rare instance there is a problem with the side driven rain or wind or the chimney is not drafting properly, an ADS-8DM Anti Draft Shield can be used with round terminations.
- 7 - For more information, visit www.desatech.com
CHASE INSTALLATIONS
Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. We suggest that terminations be separated at least 24 inches, center to center and stacked at vertical height difference of 18 inches (see figure 18).
Figure 18 MULTIPLE CHASE INSTALLATION
10-FOOT RULE
All flue gas outlet of chimney termination must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the highest point of the roof that is within a horizontal distance of 10 feet (see figure 19).
Figure 19 10-FOOT RULE
FINISHING THE FIREPLACE
Combustible materials, such as wallboard, gypsum board, sheet rock, drywall, plywood, etc. may make direct contact with sides and top periphery of the fireplace face. It is important that combustible materials do not overlap the face itself. Brick, glass, tile or other non-combustible materials may overlap the front face provided they do not obstruct essential openings like louvered slots or any other opening. When overlapping with a non-combustible facing material, use only non-combustible mortar or adhesive.
MANTEL
A mantel may be installed if desired (see figure 20), Woodwork such as wood trims, mantels, or any other combustible material projecting from the front face must not be placed within 9 inches of the fireplace opening (and within 6 inches of the top louver opening). Combustible materials above 9 inches and projecting more than 1-1/2 inches from the fireplace must not be placed less than 12 inches from the top opening of the fireplace (NFPA STD 211, Sec. 7-3.3.3).
Figure 20 MANTEL CLEARANCE
NOTE: HUD requirements may supersede these minimum dimensions.
OPERATING GUIDELINES AND MAINTENANCE
INSTRUCTIONS
GLASS DOORS
Glass doors are standard with the C36MW fireplace. When the fireplace is in operation, doors must in FULLY OPENED or FULLY CLOSED position only or a fire hazard may be created (see figure 21). A fireplace equipped with glass doors operates much differently than a fireplace with an open front. A fireplace with glass doors has a limited amount of air for combustion. Excessive heat within the fireplace can result if too large a fire is built or if the combustion air gate is not completely open. The following tips should be followed to assure that both the fireplace and the glass door retain their beauty and function properly. Both the flue damper and the glass doors must be fully opened before starting the fire. This will provide sufficient combustion air and maintain safe temperatures in the firebox.
-8 - For more information, visit www.desatech.com
y
y
w
g
g
d
n
Q
Figure 21 GLASS DOORS
IMPORTANT: The glass must be allowed to warm slowly
and evenly. The tempered glass will withstand a gradual temperature rise to 550 degrees Fahrenheit, which is more than a normal fire will generate. Such materials as pitch/wax laden logs, very dry mill end lumber, and large amounts of paper or cardboard boxes can create an excessively hot fire and should not be burned in this fireplace. Always keep the fire well back from the doors and never allow flames to contact the glass.
WARNING: Fireplaces equipped with glass doors should be operated onl doors full
as and flame out of the fireplace opening creatin
risks of both fire and smoke.
closed. Doors, if left partly open, may dra
with doors fully opened or
CLEANING THE GLASS
Clean the glass with any commercial glass cleaner or soap and water. Do not use any abrasive material to clean the glass. Do not clean the glass with any cool water if the glass is still hot from the fire and smoke.
OPTIONAL GAS LINE INSTALLATION
Gas line hook up should be done by your supplier or a qualified service person.
NOTE: Before you proceed, make sure your gas supply is turned off.
A gas line may be installed for the purpose of installing a vented or vent-free gas appliance available through your local distributor. Use only a ½ inch black iron pipe and appropriate fittings. When installing a gas line, a shut-off valve designed for installation outside the appliance is recommended.
STEP 1: To install, remove the knockout indentation on the refractory, (or firebrick), wall located above the refractory hearth floor. The knockout indentation must be firmly tapped with any solid object until it is released. Remove fragmented portions of refractory (see figure 22).
Figure 22 GAS LINE KNOCKOUT
STEP 2: Remove gas line cover plate on either side of fireplace and pull out insulation (if any) from gas line conduit sleeve. Save insulation for reuse.
STEP 3: Run a ½ inch black iron gas line into the fireplace through the rear at gas line conduit sleeve (if using a raised platform, add height). Provide sufficient gas line into fireplace chamber for fitting connection (see figure 23).
NOTE: Secure incoming gas line to wood framing to provide rigidity for threaded end.
Figure 23 GAS LINE INSTALLATION
STEP 4: Repack insulation around gas line and into sleeve opening. Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement. Install the gas appliance or cap-off gas line if desired.
CAUTION: All gas piping and connections must be teste for leaks after the installation is completed. After ensuring that the gas valve is on, apply a commercial leak detectio solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK IS DETECTED. LEAK TESTING SHOULD BE DONE BY A
UALIFIED SERVICE PERSON.
- 9 - For more information, visit www.desatech.com
g
f
g
y
g
g
IF YOU WISH TO INSTALL AN UNVENTED (VENT­FREE) GAS LOG SET, ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS, ANSI Z21.11.2, ARE TO BE INSTALLED IN THIS FIREPLACE.
NOTE: A DESA hood must be installed when using an unvented gas log set (see accessories on page 12).
WARNING: Do not operate an unvented gas log set
in this fireplace with the chimney removed.
If you install a decorative gas appliance (vented gas log), the decorative gas appliance must comply with the Standard for
Decorative Gas Appliance for Installation in Solid Fuel burning Fireplaces, ANS Z21.60, Z21.84 or RGA 2-72, and shall also be installed in accordance with the National Fuel Gas Code, ANS Z223.1-NFPA 54 latest edition.
WARNING: If the fireplace has been used for wood burnin soot, creosote and ashes by a qualified chimney cleaner. Creosote will ignite if highly heated.
lo locked in the fully open position and the glass doors must be in the fully open position.
DAMPER OPERATION
The damper handle, which opens and closes the damper blade, is located inside the firebox, at the center towards the back wall (see figure 24). Pushing the handle back in the keyway slot will free the damper blade to automatically open. To close, reach in and push the handle back into the keyhole slot then pull down and forward to lock it in place (see figure 25).
model 107001-01 desi and efficient.
, the firebox and chimney must be cleaned o
WARNING: When using a decorative vented gas
, the damper must be removed or permanentl
WARNING: Risk of fire! Replace grate with DESA
rate only. This grate has been
ned to keep the operation of your fireplace safe
Figure 24 DAMPER HANDLE LOCATION
Figure 25 DAMPER OPERATION
FOR FURTHER OPERATING GUIDELINES, INSTRUCTIONS AND WARRANTY INFORMATION, PLEASE REFER TO YOUR HOMEOWNERS GUIDE OR CONTACT YOUR AUTHORIZED DEALER.
TECHNICAL SERVICE
You may have questions about installation, operations, or troubleshooting. If so, contact the Technical Service Department at 1-866-672-6040. When calling, have the model number of the fireplace ready.
- 10 - For more information, visit www.desatech.com
ILLUSTRATED PARTS
- 11 - For more information, visit www.desatech.com
ILLUSTRATED PARTS
ITEM # PART # DESCRIPTION QTY. ITEM # PART # DESCRIPTION QTY.
1 54002 WARRANTY, HOME OWNERS BOOK 1 *33 106251-01 DOOR ASSEMBLY-RT 1 2 106943-01 WRAPPER, FIREBOX 1 *34 106574-01 INSTALL INSTRUCTION AK-6 1 3 106968-01 TOP, WRAPPER 1 *35 106586-01 LABEL, CERT. WARNOCK-HERSEY 1 4 107131-01 ASM, OUTER WRAPPER/INSULATION 1 *36 107778-28 LABEL, CARTON 1 5 106944-01 FLOOR, FIREBOX 1 *37 109913-01 CARTON, WRAP 1 6 106949-01 SEPARATOR, AIR 1 *38 107143-01 LABEL, "CAUTION MOVING PARTS…" 1 7 106971-01 LINER, LEFT SIDE BRICK 1 *39 107264-01 BRACKET, SHIPPING 1 8 106970-01 LINER, RIGHT SIDE BRICK 1 *40 107277-10 PLATE, RATING 1
9 106969-01 LINER, REAR BRICK 1 *41 11105 SCREW 10 x 1/2 HWH LGM AB 96 10 106972-01 LINER, BOTTOM BRICK 1 *42 11164 SCREW #8 x 1/2 PH TR HD LGM 2 11 106973-01 LINER, FRONT BOTTOM BRICK 1 *43 11165 SCREW #18 x 5/8 MD TR BLACK OX 8 12 20046 TIEDOWN, GRATE 1 *44 11301 RIVET POP SD42BS STEEL 11 13 106947-01 TOP, FIREBOX 1 *45 11308 RIVET, ALUMINUM 4 14 106967-01 WELDMENT, SIDE DAMPER 1 *46 11412 COTTER PIN 1-1/2 x 1/16 2 15 108872-01 WELDMENT, FRONT FACE 1 *47 14607 SWITCH, ROCKER 1 16 106948-01 DEFLECTOR, AIR 1 *48 14608 PLUG, MALE POLARIZED 1/4" 1 17 21198 PLATE, BLOWER ACCESS 1 *49 15214 LABEL, OUTSIDE AIR 1 18 108918-01 MANUAL, OWNERS 1 *50 15244 LABEL-WARNING DO NOT BLOCK 1 19 107001-01 GRATE, WOOD BURNING 1 *51 15246 LABEL-WARNING 3/4" AIRSPACE 2 20 107126-01 ASSEMBLY, SCREEN 1 *52 15303 LABEL-PRODUCT ID/ACCESSORIES 1 21 109870-01 RETAINER, INSULATION 1 *53 15310 LABEL-PRODUCT ID/CBKIII 1 22 20023 COLLAR, CHIMNEY STARTER 1 *54 16402 INSULATION RA-24 FOIL 4 23 20027 RETAINER, REFRACTORY 2 *55 16405 INSWOOL, BOX 1 x 3 X 33.5 1 24 20088 STOP, DOOR 1 *56 16408 INSULATION HT-23 1-1/2 x 44 1 25 20089 CLIP, PIVOT 2 *57 16901 STRAPPING 7/16 1 COIL = 900 20.75 26 20090 CLIP, SPRING 2 *58 17207 DUCT, FLEX 6" x 37-1/2 TYPE 1 27 106959-01 STANDOFF, TOP 4 *59 27251 LABEL ASSEMBLY, WARNING ALL 1 28 107128-01 CONDUIT, GAS 4 *60 27253 NOTICE: INDENTATION 1 29 106953-01 BOTTOM, WRAPPER 1 *61 109989-01 ELECTRICAL DUCT ASSEMBLY 1 30 106943-01 WRAPPER, FIREBOX 1 *62 54199 LABEL-REMOVE GAS KNOCKOUT 2 31 20046 TIEDOWN, GRATE 2 *63 56090 DECAL, COLEMAN 1
*32 106250-01 DOOR ASSEMBLY-LT 1
* ITEMS NOT SHOWN FOR CLARITY
- 11a - For more information, visit www.desatech.com
REPLACEMENT PARTS
ACCESSORY PARTS
VENT KIT
PART NUMBER
SEE BELOW
VENT KITS - USE FOR MOST COMMON MANUFACTURED (MOBILE) HOME INSTALLATIONS
CONTENTS MW8K MW9K
8' vent kit 9' vent kit
36-8DM 36" Double Wall Pipe
24-8DM 24" Double Wall Pipe
18-8DM
FST-A
18" Double Wall Pipe
Adjustable Firestop Thimble
V6F-8DM Roof Flashing
VSC1-8DM
Storm Collar
RTL-8DM Round Cap Termination
22
10
02
11
11
11
11
- 12- For more information, visit www.desatech.com
PART NUMBER REFERENCE TABLE*
MODEL DESCRIPTION COLEMAN PART # DESA PART #
BK3 TRIPLE FAN BLOWER KIT ----- BK3
EP-36 EMBER PROTECTOR 9736-5601 20093
AK-6 OUTSIDE AIR KIT FLOOR INSTALLATION 9736A-2206 90153
AK-6WAI OUTSIDE AIR KIT WALL INSTALLATION 9736-2306 90156
12-8DM DOUBLE WALL PIPE, 12" SECTION 9736A1212 12-8DM 18-8DM DOUBLE WALL PIPE, 18" SECTION 9736A1218 18-8DM 24-8DM DOUBLE WALL PIPE, 24" SECTION 9736A1224 24-8DM 36-8DM DOUBLE WALL PIPE, 36" SECTION 9736A1236 36-8DM 48-8DM DOUBLE WALL PIPE, 48" SECTION 9736A1248 48-8DM
V6F-8DM ROOF FLASHING, 0 - 6/12 PITCH 9736-5241 V6F-8DM
V12F-8DM ROOF FLASHING, 6/12 - 12/12 PITCH 9736-5281 V12F-8DM
ADS-8DM ANTI-DRAFT SHIELD 9436-2400 ADS-8DM
30E-8DM 30 DEG. ELBOW 9736A1238 30E-8DM
GA6053 HOOD, ANTIQUE BRASS FINISH ----- GA6053 GA6052 HOOD, POLISHED BRASS FINISH ----- GA6052 GA6050 HOOD, BLACK PAINTED FINISH ----- GA6050
HE-36 HEARTH EXTENSION - 36" 9736-2136 90192
SC1-8DM STORM COLLAR (FOR TERMINATION MODEL RTL-8DM) 9736-2241 SC1-1
V3600FS-8DM FIRESTOP SPACER, 1" CLEARANCE ----- V3600FS-8DM
FST-A FIRESTOP THIMBLE 9736A1230 00736 RTL-8DM 8" ROUND TOP TERMINATION 9736-5251 RTL-8DM ETL-8DM 8" SQUARE TOP TERMINATION ----- ETL-8DM
FE3602 FACE EXTENSION ----- FE3602
20745 43" THIMBLE EXTENSION ----- 20745
20746 26" THIMBLE EXTENSION ----- 20746
MW8K 8' VENT KIT CPMH-A/AC MW8K MW9K 9' VENT KIT CPMH-A/ACB MW9K
*Part numbers listed on this chart on the same line and identified by the same description are interchangeable and listed as “same as”. Each part so listed may be substituted for the other part numbers under that listing.
- 12a- For more information, visit www.desatech.com
Loading...