Coleman 9330F4552, 8330-752, 9330C755, 8530-750, 9530A751 Installation Instructions Manual

...
RV Products Division
INSTALLATION INSTRUCTIONS
FOR
9330F4552 FREE DELIVERY PLENUM KITS
8330-752 CONTROL BOX KIT (12 VDC COOL ONLY)
9330C755 CONTROL BOX KIT (12 VDC HEAT READY)
8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)
9430A751 ZONE CONTROL KIT (12 VDC COOL ONLY)
9430A755 ZONE CONTROL KIT (12 VDC HEAT READY)
9630A751 ZONE CONTROL KIT (12 VDC HEAT PUMP)
Coleman is a registered trademark of The Coleman Company, Inc. used under license. Mach is a registered trademark.
1976N350 (9-14) PP
Airxcel, Inc.
RV Products Division
P.O. Box 4020
Wichita, KS 67204
TABLE OF CONTENTS
1. Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. General Information and Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3. Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4. System Match-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5. Ceiling Plenum Installation Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6. Control Box Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7. Control Box Kits (Zone) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
8. Wall Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
9. Routing Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
10. Routing Thermostat Wiring (Zone) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
11. Routing 115 VAC Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
12. Securing the Upper Unit to the Roof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
13. Installing the Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
14. Installing the Control Box (Zone) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
15. Installing the Heater Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
16. Installing the Ceiling Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1. WARNINGS
IMPORTANT NOTICE
These instructions are for the use of qualified individuals specially trained and experienced in installation of this type equipment and related system components.
Installation and service personnel are required by some states to be licensed. PERSONS NOT QUALIFIED SHALL NOT SERVICE THIS EQUIPMENT.
WARNING
Improper installation may damage equipment, can create a hazard and will void the warranty.
The use of components not tested in combination with these units will void the warranty, may make the equipment in violation of state codes, may create a hazard and may ruin the equipment.
To prevent the possibility of severe personal injury or equipment damage due to electrical shock, always be sure the electrical power to the appliance is disconnected during installation.
CAREFULLY FOLLOW ALL INSTRUCTIONS AND WARNINGS IN THIS BOOKLET TO AVOID DAMAGE TO THE EQUIPMENT, PERSONAL INJURY OR FIRE.
The words “Shall” or “Must” indicate a requirement which is essential to satisfactory and safe product performance.
The words “Should” or May” indicate a recommendation which is not essential and not required, but which may be useful or helpful.
WARNING – SHOCK HAZARD
NOTE
2. GENERAL INFORMATION AND REQUIREMENTS
This mount kit is designed to provide free delivery (no ducting) air distribution. It is applicable to 47000, 48000 and 49000 Series Roof Top Units Only. The control box mounts inside the upper unit return air opening. The minimum recommended roof thickness with this system is 1”. The upper unit and ceiling assembly mount on a square roof opening 14” to 15” on a side. The roof must be capable of supporting 110 pounds of static load. Keep in mind that dynamic loads exist in recreation vehicles.
All manual controls have been removed from the ceiling plenum. They have been replaced with control relays.
The relays are mounted in the electrical box of the ceiling plenum. The relays contain 12 VDC coils (which may be energized by a wall mounted thermostat), with contacts that control the 115 VAC used to power the roof top unit.
A low voltage controller controls all air conditioning functions. The low voltage controller controls a 12 VDC electrical circuit, which is used to energize the relays in the ceiling plenum. The low voltage controller that Airxcel, Inc. provides for the system may be a combination (Heat/Cool).
2
These low voltage controllers are capable of operating both the roof top air conditioner and any furnace with a 12 VDC control circuit of 1 amp or less (continuous current).
All air conditioning equipment is subject to freeze up when evaporator air flow is sufficiently reduced. Ducting of any length creates potential for reduced evaporator air flow and system freeze up. To protect both the installer and Airxcel, Inc. from conditions that promote reduced air flow and system freeze up, Airxcel, Inc. has equipped the ceiling plenum compressor control circuit with a low temperature probe. The low temperature probe monitors
3. PACKAGE CONTENTS
The mounting kit package contains the following:
1) Steel mount frame
2) Ceiling shroud assembly
3) Small parts package consisting of:
4. SYSTEM MATCH-UP
the temperature of the air conditioner evaporator coil. When the temperature of the evaporator coil drops below 28 degrees F, the switch will open, stopping compressor operation. Compressor operation will resume once the evaporator warms to 55 degrees F.
IMPORTANT
The low temperature sensor is part of the ceiling plenum electrical circuit. The probe must be inserted into the evaporator coil of the roof top unit by the installer when bolting the ceiling plenum to the roof top unit.
a) Mounting bolt (x4) b) Mount screws (x3) c) Supply duct assembly d) Shoulder screw/spring (x4)
Ceiling Assembly Control Box Wall Desired Function Kit Thermostat
12 VDC Control 8330-752 7330G335 Cooling Only or 8330-336
12 VDC Control 9330C755 7330G335 Cool/Heat Ready or 8330-336
24 VAC Control 8530-750 7330B344 Cooling Only or 8330B324
12 VDC Control 9530A751 8530A345 Heat Pump
Ceiling Assembly Control Box Wall Desired Function Kit Thermostat
12 VDC Zone Control Cooling 9430A751 9330A335 Only
12 VDC Zone Control 9430A755 9330A335 Cool/Heat Ready
12 VDC Zone Control Heat 9630A751 9330A335 Pump
3
5. CEILING PLENUM INSTALLATION REQUIREMENT
1. The ceiling plenum must be installed under the roof opening.
The ceiling plenum bolts below the roof top unit.
Compression of the framed ceiling cavity between the roof top unit and the ceiling plenum is what holds both components in place.
2. Ceiling cavity depth (the measurement from the ceiling to the roof – maximum 6”).
3. The 115 VAC service for the roof top unit must be routed into the ceiling plenum. To prevent wire pinching and to promote ease of installation, allowances must be made for routing the 115 VAC supply wiring into the front of the roof opening.
4. The wirebox has a 9 pin receptacle extending from the front. This mates with the roof unit 115 volt electrical conduit. When making this connection, verify that the plugs are properly aligned and have snapped together securely.
Standard Control Box
Cool Only
Boxes
Yes B BLUE Completes -12 VDC circuit for all relays Yes Yes Y YELLOW Energizes coil on Compressor Relay Yes Yes GH GREEN Energizes coil on High Fan Relay Yes Yes GL GRAY Energizes coil on Low Fan Relay Yes Yes FREEZE WHITE Evaporator Freeze Sensor Connections Yes Yes FREEZE
No W WHITE Energizes coil on Heat Relay Yes
Plenum Terminal
Designation
Thermostat Wire
Connection
Zone Control Box
Plenum Terminal
Designation
R+ Red Provides +12 VDC to upper unit control box
Cool Shed
(2 Terminals)
Heat Shed
(2 Terminals)
Room (2 Terminals) Any The remote room temperature sensor attaches here*
Freeze (2 Terminals) White Freeze sensor attaches here
Gen Any Allows system to connect to an automatic start generator system
B- Blue Provides -12 VDC to upper unit control box Sig 1 Purple Communication line between upper unit control box and thermostat Sig 2 Black Communication line between upper unit control box and thermostat
* Zone 1 has option of using thermostat as room sensor
Thermostat Wire
Connection
White
Jumper Wire
White
Jumper Wire
5. The wirebox for the heat/cool units will have a two pin receptacle which mates with the umbilical plug from the heater assembly.
6. LOW VOLTAGE CONTROL WIRING (WALL THERMOSTAT)
A. A low voltage terminal strip on the front of the box
connects to the low voltage control wires. The wires attach by 1/4" quick connects.
B. The low voltage control wiring must be run from the
wall thermostat mounting location to the wirebox low voltage terminals. To prevent wire pinching and to promote ease of installation, allowances must be made for routing the low voltage wiring into the front of the opening.
Function of Low Voltage Terminal
Extending From Ceiling Plenum
Function of Low Voltage Terminal Extending From Ceiling
Plenum
Removing jumper wire will allow system to be connected to N.C.
contacts of a load shed system
Removing jumper wire will allow system to be connected to N.C.
contacts of a load shed system
Heat Ready
Boxes
4