![](/html/26/26f9/26f949565c2e270fddaa4ac75da511f419bb46791a8a932769f2aefe5a7cf561/bg1.png)
CMR Electrical Ltd
BoltonHouse
Five Chimneys Lane
Hadlow Down
East Sussex
TN22 4DX
Tel: 01825 733600
Water Leak and Room Over
Temperature Alarm
Installation and Operation
Manual
![](/html/26/26f9/26f949565c2e270fddaa4ac75da511f419bb46791a8a932769f2aefe5a7cf561/bg2.png)
Contents
1) Display and Control
2) Operation
3) Display Screens
4) Water detection Sensor wiring
5) Temperature Sensor wiring
6) Setting the alarm trip set point
7) Positioning the temperature sensor
8) Power, BMS, beacon and SMS connections
9) Beacon and beacon sounder
10) Fitting an SMS / Email messaging system
11) Commissioning
12) Fault Diagnoses
13) Installation Drawings
![](/html/26/26f9/26f949565c2e270fddaa4ac75da511f419bb46791a8a932769f2aefe5a7cf561/bg3.png)
1) Display and Control
2) Operation
In normal operation with no alarms or faults, the audible warning device will be OFF and the display will
be showing screen 2 below. The Temperature alarm trip point (setpoint) can be adjusted using the three
red buttons on the top board, see “Setting the alarm Trip Setpoint”. When the ambient temperature
exceeds the alarm setpoint, the audible warning will start pulsing, the display will show the alarm, see
screen 3, the common alarm BMS contact will operate, and if fitted, zone 2 BMS relay will operate, the
remote beacon/beacon sounder will operate and the SMS will send an Alarm message. The unit will
remain in this mode until the “Mute” button has been pressed when the display will change to show the
status of both temperature and water detection alarms, see screen 5, the audible warning will stop and if
fitted the remote sounder will stop. Once the temperature drops below the setpoint by 2ºC, the system will
automatically reset to normal operation provided the “mute” button has been operated. If the temperature
falls below 0ºC or above 50ºC, the audible warning device will sound, and the display will change to
screen 7. The water detection alarm will operate in the same way as described above but screen 4 will be
displayed when a leak has been detected, again this will stay in this mode until the “Mute” button has
been operated to acknowledge the alarm. If a temperature sensor becomes disconnected or damaged, the
audible warning will sound and the display will show the faulty sensor, see screen 6. Again unit will
remain in this mode until the “Mute” button is pressed. Once the sensor fault has been rectified, the
system will automatically revert to normal running. If the water leak detection sensor becomes
disconnected, the unit will go into “Leak Detected” alarm as described above. If the sensor power fuse
blows or is removed, the audible warning will sound and the display will show screen 8. The unit will
remain in this mode until the “Mute” button is pressed. Once the fuse has been replaced, the system will
automatically revert to normal running provided the “mute” button has been operated.
Water & Temperature
Status Display
Mute Alarm Push
Button
Temperature
Alarm Set Point
Buttons see item
5 below
“ZONE 1”
Removable Terminal
Block for Leak Detection
Sensor
Sensor power
“ZONE 2”
Removable Terminal
Block for Temperature
Sensor