TECHNICAL DATA
CABLE GLAND TYPE : TC
INGRESS PROTECTION : IP66, NEMA 4X
PROCESS CONTROL SYSTEM : BS EN ISO 9001
: ISO/IEC 80079-34:2011
ASSEMBLY FITTING INSTRUCTIONS
FOR INSTALLATION OF CMP CABLE
HAZARDOUS AREA CLASSIFICATION
ATEX CERTIFICATION No : SIRA 09ATEX1092X
ATEX CERTIFICATION CODE : II 2 GD Exd IIC Gb / Ex e IIC Gb / Ex ta IIIC Da
IEC Ex CERTIFICATION No : IEC Ex SIR.09.0042X
IEC Ex CERTIFICATION CODE : Ex d IIC Gb / Ex e IIC Gb / Ex ta IIIC Da
cCSAus CERTIFICATION No : CSA.09.2220601X
cSAus CERTIFICATION CODE : Class I Div 2 Groups A, B, C, D; Class II, Div 2 Groups E, F, G; Class III Div 2; Enclosure type 4X;
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions
before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
• The glands shall only be fitted to enclosures where temperatures, at the point of mounting, is below 110°C.
• The cable shall be effectively clamped as close as possible to the gland.
• When used for Ex e (IP54) or Ex ta (IP6X) applications, the user shall provide a suitable interface seal between the gland and associated enclosure
to maintain the level of ingress protection.
• Under CEC Code Cable Glands with metric entry threads are only suitable for Areas Classified in ZONES unless fitted with an approved Metric to
NPT thread conversion adaptor. Under NEC Code, cable glands with metric threads can be used in divisions with the following restrictions:
• TC Cable Glands will be restricted to Hazardous Location Areas stated under the NEC/CEC Part I, Installation Code under WIRING METHOD.
• Gland Size 20S is for use with UL approved tray cable only.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud *
Ordering Reference
(Std Thread)
Aluminium NP Brass S. Steel NPT Option Min Max Min Max
TC-050A028 TC-050A028 TC-050A028 1/2” - 0.78
TC-075A028 TC-075A028 TC-075A028 - 3/4” 0.80
TC-050A055 TC-050A055 TC-050A055 1/2” - 0.78
TC-075A055 TC-075A055 TC-075A055 - 3/4” 0.80
TC-075A079 TC-075A079 TC-075A079 3/4” - 0.80
TC-100A079 TC-100A079 TC-100A079 - 1” 0.98
TC-100A104 TC-100A104 TC-100A104 1” - 1.98
TC-125A104 TC-125A104 TC-125A104 - 1-1/4” 1.00
TC-125A127 TC-125A127 TC-125A127 1-1/4” - 1.00
TC-150A127 TC-150A127 TC-150A127 - 1-1/2” 1.03
TC-150A150 TC-150A150 TC-150A150 1-1/2” - 1.03
TC-200A150 TC-200A150 TC-200A150 2” 1.06
TC-200A174 TC-200A174 TC-200A174 2” - 1.06
TC-250A174 TC-250A174 TC-250A174 - 2” 1.57
TC-200A197 TC-200A197 TC-200A197 2” - 1.06
TC-250A197 TC-250A197 TC-250A197 - 2-1/2” 1.57
TC-250A220 TC-250A220 TC-250A220 2-1/2” - 1.57
TC-300A220 TC-300A220 TC-300A220 - 2-1/2” 1.63
TC-250A244 TC-250A244 TC-250A244 2-1/2” - 1.57
TC-300A244 TC-300A244 TC-300A244 - 3” 1.63
TC-300A268 TC-300A268 TC-300A268 3” - 1.63
TC-350A268 TC-350A268 TC-350A268 - 3-1/2” 1.68
TC-350A315 TC-350A315 TC-350A315 3-1/2” - 1.68
TC-400A315 TC-400A315 TC-400A315 - 4” 1.73
TC-400A354 TC-400A354 TC-400A354 4” - 1.73 - - 2.99 3.54 5.25 5.67 2.28 38.80
I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the
following standards-
Ex e ; Class I, Zone 1, AEx e
Entry Thread
All dimensions in inches
Thread
Length
Cable Range
Min
Insert
0.13 0.28 - - 1.20 1.30 0.79 1.94
0.26 0.41 0.41 0.55 1.20 1.30 0.79 1.69
0.47 0.61 0.61 0.79 1.48 1.60 0.98 3.17
0.67 0.85 0.85 1.04 1.81 1.95 0.98 3.88
0.92 1.10 1.10 1.27 2.05 2.21 1.18 4.94
1.22 1.37 1.37 1.50 2.36 2.55 1.26 6.00
- - 1.40 1.74 2.95 3.19 1.26 8.64
- - 1.63 1.97 2.95 3.19 1.65 8.29
- - 1.86 2.20 3.54 3.82 1.65 13.58
- - 2.13 2.44 3.54 3.82 1.69 13.58
- - 2.40 2.68 4.33 4.68 1.69 23.63
- - 2.62 3.15 4.84 5.23 2.28 34.22
Cable Range
No Insert
Across
Flats
Across
Corners
Assembled
Length
Approx
Weight
Aluminium
(Ozs)
Cable Connector Selection Table
CONNECTOR TYPE TC
FOR TERMINATION OF TRAY CABLES, FLEXIBLE CORD, UNARMOURED AND WIRE BRAID CABLES FOR
USE IN HAZARDOUS LOCATIONS
INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC
CABLE
CABLE
CONNECTOR
CONNECTOR
TYPE
TYPE
TC
TC
CMP Document No. FI411 Issue 4 01/13
EN60079-0:20079, EN60079-1:2007, EN60079-7:2007, BS 6121:1989, EN50262:1998 (Amd 2001), EN61241-0:2006, EN61241-1:2004
Dr Geof Mood - Technical Director - (Authorised Person)
Registered Office: Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 191 265 0581
0518
Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.
E-Mail: cmp@cmp-products.co.uk • Web: www.cmp-products.com
www.cmp-products.com
Logo’s shown for illustration purposes only. Please check certification for details
DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
www.cmp-products.com
INSTALLATION INSTRUCTIONS FOR TC CABLE CONNECTOR
CABLE CONNECTOR COMPONENTS
1. “O” Ring
2. Entry Component
3. Seal Insert*
4. Nut Insert*
5. Seal Nut
Note*: The Seal and Nut inserts are only used in
connector sizes 40 (1-1/4”) and below to
give two cable size ranges.
PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION
1. If using the smaller cable range there is no need to disassemble the connector. (Size ranges are
marked on the connector).
53 421
3. Secure the complete connector into the equipment.
4. Determine the conductor length to suit the geometry of the equipment and prepare the cable
accordingly, removing part of the outer sheath where required to reveal the insulated conductors.
2. Slacken the seal nut (5) to relax the seal.
Try to pass the cable through the connector. If
this is possible, move to stage 3.
If not dissassemble the connector and remove
the seal insert (3) and the nut insert (4).
This will allow the cable to pass through the
connector.
5. Pass the cable through the gland to the desired position hold the entry component (2) with a
spanner then tighten the seal nut until heavy resistance is felt. This will occur when:-
A) The seal nut (5) has clearly engaged the cable and cannot be further tightened without
the use of excessive force by the installer.
B) The seal nut (5) is metal to metal with the entry component (2). (This should only
happen on minimum cable sizes.)
Seal Insert 3
Nut Insert 4
www.cmp-products.com
DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH