DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
TECHNICAL DATA
CABLE GLAND TYPE : E** Family of Glands
INGRESS PROTECTION : IP66, IP67, IP68
PROCESS CONTROL SYSTEM : BS EN ISO 9001
ASSEMBLY FITTING INSTRUCTIONS
FOR INSTALLATION OF CMP CABLE
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud *
Available Entry Threads
able
C
Gland
ize
S
20S/16 M20 1/2” 3/4” 15.0 3.1 8.6 6.1 11.5 0.0 1.0 0.9 1.0 24.0 25.9 58.5 20S16E1W1RA PVC04
20S M20 1/2” 3/4” 15.0 6.1 11.6 9.5 15.9 0.0 1.0 0.9 1.25 24.0 25.9 58.5 20SE1W1RA PVC04
20 M20 1/2” 3/4” 15.0 6.5 13.9 12.5 20.9 0.0 1.0 0.9 1.25 30.5 32.9 60.5 20E1W1RA PVC06
25S M25 3/4” 1” 15.0 11.1 19.9 14.0 22.0 0.0 1.0 1.25 1.6 37.5 40.5 67.5 25SE1W1RA PVC09
25 M25 3/4” 1” 15.0 11.1 19.9 18.2 26.2 0.0 1.0 1.25 1.6 37.5 40.5 67.5 25E1W1RA PVC09
32 M32 1” 1-1/4” 15.0 17.0 26.2 23.7 33.9 0.0 1.0 1.6 2.0 46.0 49.7 69.5 32E1W1RA PVC11
40 M40 1-1/4” 1-1/2” 15.0 22.0 32.1 27.9 40.4 0.0 1.0 1.6 2.0 55.0 59.4 78.0 40E1W1RA PVC15
50S M50 1-1/2” 2” 15.0 29.5 38.1 35.2 46.7 0.0 1.0 2.0 2.5 60.0 64.8 75.5 50SE1W1RA PVC18
50 M50 2” 2-1/2” 15.0 35.6 44.0 40.4 53.1 0.0 1.0 2.0 2.5 70.0 75.6 80.5 50E1W1RA PVC21
63S M63 2” 2-1/2” 15.0 40.1 49.9 45.6 59.4 0.0 1.0 2.0 2.5 75.0 81.0 91.5 63SE1W1RA PVC23
63 M63 2-1/2” 3” 15.0 47.2 55.9 54.6 65.9 0.0 1.0 2.0 2.5 80.0 86.4 92.0 63E1W1RA PVC25
75S M75 2-1/2” 3” 15.0 52.8 61.9 59.0 72.1 0.0 1.0 2.0 2.5 89.0 96.1 99.0 75SE1W1RA PVC28
75 M75 3” 3-1/2” 15.0 59.1 67.9 66.7 78.5 0.0 1.0 2.5 3.0 99.0 106.9 102.0 75E1W1RA PVC30
90 M90 3” 3-1/2” 15.0 66.6 79.9 76.2 90.4 0.0 1.6 3.0 3.5 114.0 123.1 120.0 90E1W1RA PVC32
100 M100 - - 15.0 76.0 90.9 86.1 101.5 0.0 1.6 3.15 4.0 123.0 132.8 148.0 100E1W1RA 150/50HST
115 M115 - - 15.0 86.0 97.9 101.5 110.3 0.0 1.6 3.15 4.0 133.4 144.1 169.0 115E1W1RA 180/60HST
130 M130 - - 15.0 97.0 114.9 114.2 123.3 0.0 1.6 3.15 4.0 146.0 157.8 183.0 130E1W1RA 180/60HST
Standard Option Grooved Cone Stepped Cone
Metric NPT NPT Min Max Min Max Min Max Min Max Max Max
Thread
L
in
M
ength
Cable Beding
Diameter
Dimensions are displayed in millimeters unless otherwise stated
Overall Cable
Diameter
Armour Range
Across
Flats
Across
Corners
rotrusi
P
ength
L
on
rdering
O
Reference
Brass Metric)
(
VC
P
Shroud
eference
R
GLAND TYPE “E”
FOR TERMINATION OF CABLES WITH WIRE BRAID, TAPE ARMOUR (STA/DSTA), STRIP ARMOUR &
SINGLE WIRE ARMOUR (SWA) (WITH LEAD INNER SHEATH ON “E2” VARIANT).
CABLE GLAND TYPES
CABLE GLAND TYPES
E1W, E2W, E1X, E2X,
E1W, E2W, E1X, E2X,
E1U & E2U
E1U & E2U
Cable Gland Selection Table
Order codes shown are for E1W glands
For e.g. E1X glands substitue E1W for E1X - e.g. 20E1X1RA
Please note that the overall maximum cable bedding diameter for “E2” variants should be reduced by 1mm to allow for the inner lead sheath.
Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 191 265 0581
E-Mail: cmp@cmp-products.co.uk • Web: www.cmp-products.com
www.cmp-products.com
E1W - SWA Armour
E2W - SWA Armour for lead
sheathed cable
E1X - Braid, Tape, etc Armour
E2X - Braid, Tape, etc Armour
for lead sheathed cable
E1U - Universal Gland for all
Armour Types
E2U - Universal Gland for all
Armour Types with lead
sheathed cable
CMP Document No. FI417 Issue 2 06/11
CMP PRODUCTS
DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES “E”
CABLE GLAND COMPONENTS - It is not necessary to dismantled the cable gland any further than illustrated below
1. Entry Component
2. Main Item
3. Detachable Armour Cone
4. AnyWay Clamping Ring
5. Body
6. Outer Seal Nut
Sub Assembly A Sub Assembly B
www.cmp-products.com
4. Locate the Armour Cone (3) into its recess in the Main Item (2). (N.B. For E1U and E2U
variants, make sure the correct side of the cone is outermost - grooved for braid/tape armour and
stepped for SWA). Pass the cable through sub-assembly “A” until the armour engaged with the
cone. Spread the armour evenly around the cone.
321
PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION
4
65
1. If required fit shroud over the cable outer sheath.
Prepare the cable by removing the cable outer sheath and the armour to suit the geometry of the
equipment. Remove a further 18mm (maximum) of outer sheath to expose the armour. If applicable
remove any tapes or wrappings to expose cable inner sheath. Tape armour should be further prepared
by cutting the tape into strips as shown below:
2. Separate the gland into two sub-assemblies “A & B”. Ensuring that the Outer Seal Nut (6) is relaxed,
pass sub-assembly “B” over the cable outer sheath and armour followed by the “AnyWay” clamping ring
(4).
Note: On maximum size cables the clamping ring may only pass over the armour.
5. While continuing to push the cable forward to maintain contact between the armour and the
cone, tighten the Main Item (2) by hand until heavy resistance is felt. (This is when the inner seal
makes contact with the cable inner sheath). Tighten a further full turn using a spanner.
NOTE: The earthing device on E2* type glands will automatically engage the lead sheath.
6. Hold the Main Item (2) with a spanner and tighten sub-assembly “B” onto sub-assembly “A”
using a spanner until all available threads are used.
3. Ensure that the inner seal is relaxed by slackening the Main Item (2). Secure sub-assembly “A” into
the equipment either by screwing the Entry Item (1) into a threaded hole or by securing it in a
clearance hole using a locknut as applicable.
www.cmp-products.com
7. Tighten the Outer Seal Nut (6) until it comes to an effective stop. This will occur when:A) The Outer Seal Nut (6) has clearly engaged the cable and cannot be further tightened
without the use of excessive force by the installer.
B) The Outer Seal Nut (6) is metal to metal with the body of the gland (5).
DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH