CMP E1FW, E1FX, E2FW, E2FX, E1FU Installation Instructions Manual

...
www.cmp-products.com
FOR TERMINATION OF CABLES WITH WIRE BRAID, TAPE ARMOUR (STA/DSTA), STRIP ARMOUR & SINGLE WIRE ARMOUR (SWA) (WITH LEAD INNER SHEATH ON “E2” VARIANT). FOR USE IN EXPLOSIVE ATMOSPHERES.
INCORPORATING EU DECLARATION OF CONFORMITY TO DIRECTIVE [2014/34/EU]
TECHNICAL DATA
EXPLOSIVE ATMOSPHERES CLASSIFICATION
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing: Locknut, Earth Tag, Serrated Washer, Entry Thread (I.P.) Sealing Washer, Shroud
CABLE GLAND TYPES
E1FW, E2FW, E1FX,
E2FX, E1FU & E2FU
INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPE “E”
Number of turns
to tighten
Outer Seal Tightening Guide
GLAND SIZE
20S16 20S 20 25S 25 32 40 50S 50 63S 63 75S 75
CABLE DIAMETER
0.5 13.2 15.9 20.9 22.0 26.2 33.9
1 12.5 15.3 20.0 21.2 25.4 32.9 40.4 46.7 52.8 59.2 65.9 72.1 78.5
1.5 11.9 14.7 19.0 20.4 24.6 31.9 39.0 45.4 51.4 57.7 64.6 70.6 77.2
2 11.2 14.2 18.1 19.6 23.8 30.8 37.6 44.1 50.0 56.2 63.4 69.2 75.9
2.5 10.5 13.6 17.2 18.8 23.0 29.8 36.2 42.9 48.7 54.7 62.1 67.7 74.6
3 9.8 13.0 16.2 18.0 22.2 28.8 34.8 41.6 47.3 53.2 60.9 66.3 73.3
3.5 9.2 12.4 15.3 17.2 21.4 27.8 33.5 40.3 45.9 51.6 59.6 64.8 71.9
4 8.5 11.8 14.4 16.4 20.6 26.8 32.1 39.0 44.5 50.1 58.4 63.4 70.6
4.5 7.8 11.2 13.4 15.6 19.8 25.7 30.7 37.8 43.2 48.6 57.1 61.9 69.3
5 7.1 10.7 12.5 14.8 19.0 24.7 29.3 36.5 41.8 47.1 55.9 60.5 68.0
5.5 6.5 10.1 12.0 14.0 18.2 23.7 27.9 35.2 40.4 45.6 54.6 59.0 66.7
6 5.8 9.5
Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 1670 715 646
E-Mail: customerservices@cmp-products.co.uk • Web: www.cmp-products.com
0518
CABLE GLAND TYPE : E** Family of Glands INGRESS PROTECTION : IP66, (IP67, IP68 available upon request) PROCESS CONTROL SYSTEM : BS EN ISO 9001
: ISO / IEC 80079-34:2001
Order codes shown are for E1FU glands - For e.g. E1FWD glands substitute E1FWD for E1FU - e.g. 20E1FWD1RA
Stepped cone is for single wire armour and grooved cone is for all other armours
E1FW - SWA AWA E2FW - SWA AWA for lead
sheathed cable
E1FX - Braid, Tape, etc Armour E2FX - Braid, Tape, etc Armour for
lead sheathed cable E1FU - Universal Gland for all Armour Types E2FU - Universal Gland for all Armour Types with lead sheathed cable
CMP Document No. FI407 Rev 19 CSA Issue 11, IEC Issue 11
SCAN FOR INSTALLATION VIDEOS
CMP Products Limited on its sole responsibility declares that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following standards: -
EN60079-0:2012, EN60079-1:2007, EN60079-7:2007, EN60079-15:2010, EN60079-31:2009, BS6121:1989, EN62444:2013
David Willcock – Certification Engineer (Authorised Person) CMP Products Limited. Cramlington, NE23 1WH, UK 24th June 2015
Notified Body: SIRA Certification Service, Unit 6 Hawarden Industrial Park, Hawarden, CH5 3US, UK
Cable Gland
Size
Available E ntry Thread s
(Alternate Metric Thread Lengths Available)
Cable
Bedding
Diameter
Overall
Cable
Diameter
Armour Ra nge †
Across
Flats
Across
Corners
Protrusion
Length
Combined Ordering
Referenc e
(*Brass Metric)
Shroud
Cable Gland
Weight
(Kgs)
Grooved Cone (X)
Stepped Cone (W)
Standard Option
Metric
Thread Length
(Metric)
NPT
Thread Length
(NPT)
NPT Min Max Min Max Min Max Min Max Max Max Size Type
Ordering
Suffix
20S16 M20 15.0 1/2” 19.9 3/4” 3.1 8.6 6 .1 13.1 0.3 1.0 0.8 1.25 24.0 26.4 72.5 20S16 E1FU 1RA PVC04 0.16
20S M20 15.0 1/2” 19.9 3/4” 6.1 11.6 9.5 15.9 0.3 1.0 0.8 1.25 24 .0 26.4 70.0 20S E1F U 1RA P VC04 0.15 20 M20 15. 0 1/2” 19.9 3/4” 6.5 13.9 12.5 20.9 0.4 1.0 0.8 1.25 30.5 33. 6 73.0 20 E1FU 1RA PVC06 0.21 25S M25 15.0 3/4” 20.2 1” 11.1 19.9 14.0 22.0 0.4 1.2 1. 25 1.6 37.5 41.3 89.0 25S E1FU 1R A PVC09 0.33
25 M25 15. 0 3/4” 20.2 1” 11.1 19.9 18.2 26.2 0.4 1.2 1.25 1.6 37. 5 41.3 89.0 25 E1FU 1RA PVC09 0.33
32 M32 15 .0 1” 25.0 1 1/4” 17.0 26.2 23.7 33.9 0.4 1.2 1.6 2.0 46.0 50.6 86.0 32 E1FU 1R A PVC 11 0.43 40 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 32.1 2 7.9 40.4 0.4 1.6 1.6 2.0 55. 0 60.5 90.0 40 E1FU 1RA P VC15 0.62 50S M50 15.0 1 1/2” 2 6.1 2” 29.5 38.1 35.2 46.7 0.4 1.6 2.0 2.5 60.0 66.0 91.0 50S E1 FU 1R A PVC18 0.75 50 M50 15.0 2” 26.9 2 1/2” 35.6 44.0 40.4 53.0 0.6 1.6 2.0 2.5 7 0.1 77.1 95.0 50 E1FU 1RA PV C21 0.95 63S M63 15.0 2” 26.9 2 1/2” 4 0.1 49.9 45.6 59.4 0.6 1.6 2.0 2.5 75.0 82.5 102.0 63S E1 FU 1R A PVC23 1.34 63 M63 15.0 2 1/ 2” 39.9 3” 47.2 55.9 54.6 65. 8 0.6 1.6 2.0 2.5 80.0 88.0 104 .0 63 E1F U 1RA PVC25 1.34 75S M75 15.0 2 1/2” 39.9 3” 52.8 61.9 59.0 72.0 0.6 1.6 2.0 2.5 90.0 99.0 115 .0 75S E1FU 1R A PVC28 2 .11
75 M75 15 .0 3” 41.5 3 1/2” 59.1 67. 9 66.7 78.4 0.6 1. 6 2.5 3.0 100.0 110. 0 117.0 75 E1FU 1RA PVC30 2.42 90 M90 24.0 3 1/2” 42.8 4” 66.6 78.6 76.2 90.3 0.8 1.6 3.15 4.0 11 4.3 125.4 147.0 90 E1FU 1RA PVC32 4.21 100 M100 24.0 3 1/2” 42.8 4” 76.0 90.9 8 6.1 101.4 0.8 1.6 3.15 4.0 123.0 135.3 140.0 100 E1 FU 1R A LSF33 4.45 115 M115 24.0 4” 44.0 5” 86.0 97.9 101.5 11 0.2 0.8 1.6 3.15 4.0 133.4 146.7 162.0 115 E1FU 1RA LSF34 6.19 130 M130 24.0 5” 46.8 - 97.0 11 4.9 11 0.2 123.2 0.8 1.6 3.15 4.0 15 2.4 16 7.6 174.0 130 E1FU 1RA LSF35 8.34
Dimensions are displayed in millimetres unless otherwise stated
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.
CERTIFICATION CONDITIONS
1. The E** Type cable glands shall not be used to terminate on braided cables in group I applications.
2. The glands when used for terminating braided cables are only suitable for fixed installations. Cables must be effectively clamped to prevent pulling or twisting.
ATEX CERTIFICATION No : SIRA13ATEX1071X, SIRA13ATEX4077X ATEX CERTIFICATION CODE : ^ II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da, ^ II 3G Ex nR IIC Gc,
^ IM2, Ex d I Mb, Ex e I Mb
IECEx CERTIFICATION No : IECEx SIR.13.0026X IECEx CERTIFICATION CODE : Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb cCSAus CERTIFICATION No : 1310517X CSA us CERTIFICATION CODE* : Class II Div 2, Groups E,F and G, Class III,
Class I Zone 1 AEx e II, Class I Zone 2 AEx nR II, Enclosure Type 4X c CSA CERTIFICATION CODE : Class I, Div 2, Groups A,B,C and D, Class II Div 2, Groups E,F and G, Class III, Ex d IIC, Ex e II, Ex nR II, Enclosure Type 4X
*E** can be used in Class 1, Division 2 Locations for non-explosionproof applications in accordance with Article 501 of the NEC Code
1. Cable gland connectors material may be of brass, aluminum or stainless steel.
2. Connectors with metric entry threads are only suitable for Areas Classified in ZONES unless fitted with an approved Metric to NPT thread conversion adaptor.
3. According to US (NEC) wiring method for the types of cables that can be used in Class I Zone 1 and 2 Classified Areas, should be in accordance of NFPA-70 installation wiring method restrictions.
1. Cable gland connectors’ material may be of brass, aluminium or stainless steel.
2. These glands are not suitable for use with flameproof enclosures installed in Group IIC atmospheres, which have a volume greater than 2000 cc (2 Litre).
3. These Glands are for use with Certified Marine Shipboard metal braided cables constructed according to CSA Std. 245 and IEEE45/IEC600092-353 Standards, or Certified equivalent), for use on Shipboards and Offshore Rigs/platforms only.
4. “E**” cable gland connectors when installed into Class I, Division 2 Classified Areas, are not suitable to be interfaced with an explosion proof enclosure contain­ing arcing and sparking devices, unless installed in conjunction with an approved explosion proof sealing fitting.
ATEX & IECEx
CSA us
c CSA
Logos shown for illustration purposes only. Please check certification for details
www.cmp-products.comwww.cmp-products.com
INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES “E”
CABLE GLAND COMPONENTS - It is not necessary to dismantled the cable gland any further than illustrated below
1. Entry Component
2. Main Item
3. Detachable Armour Cone
4. AnyWay Clamping Ring
5. Body
6. Outer Seal Nut
PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION
1. If required fit shroud over the cable outer sheath;
Prepare the cable by stripping back the cable outer sheath and armour to suit the equipment geometry. Expose the armour by stripping back the outer sheath further using the table below as a guide. If applicable remove any tapes or wrappings to expose cable inner sheath.
Cable Strip Length “L”
Tape armour should be further prepared by cutting the tape into strips as shown below:
CABLE GLAND SIZE 20S/16, 20S, 20 25S, 25, 32, 40 50S, 50, 63S, 63 75S, 75, 90, 100, 115, 130
CABLE STRIP LENGTH “L” 12mm 15mm 18mm 20mm
2. Separate the gland into two sub-assemblies “A & B”. Ensuring that the Outer Seal Nut (6) is relaxed, pass sub-assembly “B” over the cable outer sheath and armour followed by the “AnyWay” clamping ring (4).
Note: On maximum size cables the clamping ring may only pass over the armour.
3. Ensure that the inner seal is relaxed by slackening the Main Item (2). Secure sub-assembly “A” into the equipment either by screwing the Entry Item (1) into a threaded hole or by securing it in a clearance hole using a locknut as applicable.
4. Locate the Armour Cone (3) into its recess in the Main Item (2). (For E1FU and E2FU variants, make sure the correct side of the cone is outermost - grooved for braid/tape armour and stepped for SWA). Pass the cable through sub-assembly “A” until the armour engaged with the cone. Spread the armour evenly around the cone.
5. While continuing to push the cable forward to maintain contact between the armour and the cone, tighten the Main Item (2) until the inner seal makes contact with the cable inner sheath (heavier resistance is felt at this point). Tighten a further full turn. NOTE: The earthing device on E2* type glands will automatically engage the lead sheath.
6. Hold the Main Item (2) with a spanner and tighten sub-assembly “B” onto sub-assembly “A” using a spanner until all available threads are used.
7. Only using finger pressure, tighten the outer seal nut assembly (6) until light resist­ance to tightening is met.
Then either use the outer seal tightening guide tape or table on the rear of the page to determine how much further to tighten the seal using a spanner (using the outer seal tightening guide is recomended).
Wrap the outer seal tightening guide tape around the cable to show the amount of spanner turns needed (as shown here). Make sure the correct side of the outer seal tightening guide tape is used depending on the cable gland size.
1. 2. 3. 4. 5. 6.
Universal Cone (E1FU, E2FU) use stepped side for SWA and grooved side for all other armours
SUB ASSEMBLY A SUB ASSEMBLY B