TECHNICAL DATA
CABLE GLAND TYPE : A2FRC
INGRESS PROTECTION : IP66, NEMA 4X
PROCESS CONTROL SYSTEM : BS EN ISO 9001
: ISO/IEC 80079-34:2011
INSTALLATION INSTRUCTIONS FOR
A2FRC CABLE GLAND WITH
HAZARDOUS AREA CLASSIFICATION
ATEX CERTIFICATION No : SIRA06ATEX1097X, SIRA07ATEX4326X
ATEX CERTIFICATION CODE : II 2 GD Ex d IIC, Ex e II, Ex nR II, Ex tD A21 IP66
IEC Ex CERTIFICATION No : IEC Ex SIR.06.0040X
IEC Ex CERTIFICATION CODE : Ex d IIC / Ex e II / Ex nR II, Ex tD A21 IP66
CSA CERTIFICATION No : 1211841
CSA CERTIFICATION CODE : Ex d IIC & Ex e II, CSA Enclosure Type 4X
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions
before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
1. The A2FRC shall only be used where the temperature, at the point of entry, is between -60°C and +130°C.
2. The entry component threads may need additional sealing to maintain the ingress protection rating as applicable to the associated
3. If used to connect to flexible conduit, the conduit must be clamped to prevent pulling or twisting of the cable.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
NOTE: Other thread forms, materials and finishes are available. IEC Ex, ATEX & CSA hazardous area certification marking included as standard. Please consult CMP for any other
requirements.
equipment to which it will be attached.
Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud*
Cable Gland
Size
20S/16 M20 1/2” 3/4” 15.0 1/2” 3.2 8.7 24.0 25.9 37.0 20S16A2FRC1RA031 0.054
20S M20 1/2” 3/4” 15.0 1/2” 6.1 11.7 24.0 25.9 37.0 20SA2FRC1RA031 0.054
20 M20 1/2” 3/4” 15.0 1/2” 6.5 14.0 27.0 29.2 37.0 20A2FRC1RA031 0.059
25 M25 3/4” 1” 15.0 3/4” 11.1 20.0 36.0 38.9 39.0 25A2FRC1RA032 0.112
32 M32 1” 1-1/4” 15.0 1” 17.0 26.3 36.0 38.9 41.0 32A2FRC1RA033 0.128
40 M40 1-1/4” 1-1/2” 15.0 1-1/4” 23.5 32.2 46.0 49.7 42.0 40A2FRC1RA034 0.168
50S M50 1-1/2” 2” 15.0 1-1/2” 31.0 38.2 50.0 54.0 48.0 50SA2FRC1RA035 0.224
50 M50 2” 2-1/2” 15.0 2” 35.6 44.1 65.0 70.2 51.0 50A2FRC1RA036 0.231
63S M63 2” 2-1/2” 15.0 2” 41.5 50.0 65.0 70.2 50.0 63SA2FRC1RA036 0.360
63 M63 2-1/2” 3” 15.0 2-1/2” 47.2 56.0 80.0 86.4 50.0 63A2FRC1RA037 0.344
75S M75 2-1/2” 3” 15.0 2-1/2” 54.0 62.0 80.0 86.4 60.0 75SA2FRC1RA037 0.466
75 M75 3” 3-1/2” 15.0 3” 61.1 68.0 100.0 108.0 60.0 75A2FRC1RA038 0.395
90 M90 3” 3-1/2” 15.0 3” 61.6 80.0 100.0 108.0 79.0 90A2FRC1RA038 1.346
Metric NPT NPT Min Max Max Max
Entry Threads
Standard Option
Min
Thread
Length
Standard
Female
Connection
Thread
All dimensions in millimeters
Overall Cablle
Diameter
Across
Flats
Across
Corners
Nominal
Protrusion
Length
Ordering Reference
(Brass Metric Male x NPT
Female)
Cable Gland
Weight (Kgs)
CONDUIT CONNECTOR
CABLE GLAND FOR USE WITH UNARMOURED AND BRAID ARMOURED CABLES HOUSED IN CONDUITS
IN HAZARDOUS AREAS.
INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC
CABLE
CABLE
GLAND
GLAND
TYPE
TYPE
A2FRC
A2FRC
Cable Gland Selection Table
I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the
following standards:-
EN 60079-0:2006, EN 60079-1:2007, EN 60079-7:2007, BS 6121:1989, EN 50262:19989 (Amd 2001), EN 61241-0:2004, EN 61241-1:2004,
EN 60079-15:2005.
Dr Geof Mood - Technical Director - (Authorised Person)
Registered Office: Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 191 265 0581
0518
Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.
E-Mail: cmp@cmp-products.co.uk • Web: www.cmp-products.com
Company Number:
www.cmp-products.com
CMP Document No. FI448 Issue 2 0113
Logo’s shown for illustration purposes only. Please check certification for details
DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
www.cmp-products.com
INSTALLATION INSTRUCTIONS FOR CMP GLAND TYPE A2FRC
CABLE GLAND COMPONENTS
1. Entry Item
2. Seal
3. Skid Washer
4. Seal Nut
5. Conduit Coupling
PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION
3 4
1. The A2FRC cable gland is suitable for all types of unarmoured cables, providing a flameproof
seal on the outer sheath of the cable. It also has a rotating female-threaded coupling at the
rear of the gland to allow the attachment of conduit.
This gland can also be used with braided cables where sealing is made on the cable outer
sheath and the braid is earthed inside the equipment when this arrangement is allowed by
the prevailing installation code of practice.
521
4. Determine the conductor length required to suit the installation and prepare the cable
accordingly, removing part of the outer sheath where required to reveal the insulated
conductors.
5. Pass the cable through the gland to the desired position, then tighten the seal nut by hand
until resistance is felt (when the seal contacts the cable). Tighten with a spanner one
further turn.
2. There is no need to dismantle the cable gland prior to installation. Simply slacken the Seal
Nut (4) to relax the seal (2).
3. Fit the gland into the equipment and fully tighten the Entry Item (1).
6. Attach the conduit to the Conduit Coupler (5) and fully tighten. Ensure that the Seal Nut
(4) does not come loose during this process by holding it with a spanner.
Conduit
www.cmp-products.com
DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH