C-more RS-232 User Manual

Page 1
Chapter
Chapter
Chapter
PLC CommuniCations
6
6
6
In This Chapter...
Introduction ............................................................................................................... 6–2
DirectLOGIC PLCs Password Protection ...................................................................6–2
PLC Communication Cables & Wiring Diagrams ......................................................6–5
AutomationDirect PLCs RS-232C Serial: .................................................................... 6–7
AutomationDirect PLCs RS-422A/RS-485A: ............................................................. 6–10
Direct LOGIC Universal Isolated Network Adapter, p/n FA-ISOCON: ...................... 6–16
Direct LOGIC Universal Converter, p/n F2-UNICON: .............................................. 6–17
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples .......................................6–18
Allen-Bradley: .........................................................................................................6–22
GE: ......................................................................................................................... 6–27
GE VersaMax Micro: ............................................................................................... 6–27
Mitsubishi:..............................................................................................................6–27
Omron: .................................................................................................................. 6–29
Modicon ModBus RS-232: ......................................................................................6–30
Modicon Micro Series:............................................................................................6–30
Modicon ModBus with RJ45: .................................................................................. 6–30
Siemens: .................................................................................................................6–31
Page 2
®

Introduction

1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8

DirectLOGIC PLCs Password Protection

9
9
10
10
The C-more family of touch panels is capable of communicating with a wide variety of Programmable Logic Controllers. C-more is capable of communicating over RS232, RS422 and RS485 serial networks as well as Ethernet networks. It communicates with all AutomationDirect PLC’s utilizing various protocols. C-more also communicates with other brands of PLCs by their different protocols. The table on the next page lists all of the various PLCs and protocols that can be configured. The page after the protocol table lists the various serial communication cables that are available to purchase. The rest of this chapter is devoted to show the pin to pin connections of all the available cables plus wiring diagrams that the user can refer to in order to construct their own cables, along with wiring diagrams of cables that are not available for purchase. To simplify RS422/RS485 wiring schemes, we have included wiring diagrams showing connections for available terminal connectors such as our ZIPLink Communication Adapter Module, p/n ZL-CMA15, used for example with our DL-06 and D2-260 PLCs and C-more D-Sub 15-pin to Terminal Block Adapter p/n EA-COMCON-3.
If you have difficulty determining whether the particular PLC and/or protocol you are using will work with the C-more series of touch panels, please contact our technical support group at 770-844-4200
NOTE: Many DirectLogic PLCs support multi-level password protection of the ladder program. This allows password protection while not locking the communication port to an operator interface. The multilevel password can be invoked by creating a password with an upper case “A” followed by seven numeric characters (e.g. A1234567). Please refer to the specific PLC user manual for further details.
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
6-2
C-more
Touch Panel
DL-06 PLC
C-more to
Direct LOGIC
Port 2
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
VGA 15-pin port
serial cable
p/n EA-2CBL-1
Page 3
®
PLC Protocol & Cables
Compatibility Table
Model Protocols
P3000 Serial
P3000 Ethernet
Modbus (CLICK)
K-Sequence
Direct NET
Modbus (Koyo addressing)
Direct LOGIC Ethernet
K-Sequence
Direct NET
K-Sequence
Direct NET
Modbus (Koyo addressing)
Direct NET
Modbus (Koyo addressing)
Direct LOGIC Ethernet
Direct NET
Direct NET
K-Sequence
Direct NET
Modbus (Koyo addressing)
Direct NET
Modbus (Koyo addressing)
K-Sequence
Direct NET
K-Sequence
Direct NET
K-Sequence
Direct NET
Modbus (Koyo addressing)
Direct NET
Modbus (Koyo addressing)
Direct LOGIC Ethernet
GS Drives Serial
GS Drives TCP/IP (GS-EDRV)
AutomationDirect
PLC Compatibility Table continued on the next page.
Productivity3000
CLICK
DL05/DL06
DL105 all K-Sequence
DL205
DL305
DL405
H2-WinPLC (Think & Do) Live V5.2 or later and Studio any version Think & Do Modbus RTU (serial port)
H2-WinPLC (Think & Do) Live V5.5.1 or later and Studio V7.2.1 or later Think & Do Modbus TCP/IP (Ethernet port)
GS Drives
SOLO Temperature Controllers SOLO Temperature Controller
all
H0-ECOM/H0-ECOM100
D2-230 K-Sequence
D2-240
D2-250/D2-250-1/D2-260
D2-240/D2-250-1/D2-260 Using DCM
H2-ECOM/H2-ECOM100
D3-330/330P (Requires the use of a Data Communications Unit)
D3-340
D3-350
D3-350 DCM
D4-430
D4-440
D4-450
All with DCM
H4-ECOM/H4-ECOM100
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
6-3
Page 4
®
PLC Protocol & Cables (cont’d)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
Compatibility Table (cont’d)
Model Protocols
MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5-01/02/03 DH485/AIC/AIC+
MicroLogix 1000, 1100, 1200, 1400 and 1500
DF1 Half Duplex; DF1 Full DuplexSLC 5-03/04/05
ControlLogix™, CompactLogix™, FlexLogix™
Allen-Bradley
GE
Mitsubishi
Modicon
Omron
Siemens
PLC-5 DF1 Full Duplex
ControlLogix, CompactLogix, FlexLogix - Tag Based DF1 Half Duplex; DF1 Full Duplex
ControlLogix, CompactLogix, FlexLogix - Generic I/O Messaging EtherNet/IP Server
ControlLogix, CompactLogix, FlexLogix - Tag Based
EtherNet/IP ClientMicroLogix 1100, 1400 and SLC 5/05, via native Ethernet port
MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5-03/04/05, all via ENI adapter
90/30, 90/70. Micro 90, VersaMax Micro SNPX
FX Series FX Direct
Q02, Q02H, Q06H, Q12H, Q25H Q CPU
Q, QnA Serial QnA Serial
Q, Qna Ethernet QnA Ethernet
984 CPU, Quantum 113 CPU, AEG Modicon Micro Series 110 CPU: 311-xx, 411-xx, 512-xx, 612-xx
Other devices using Modicon Modbus addressing
C200 Adapter, C500 Host Link
CJ1/CS1 Serial
CJ1/CS1 Ethernet
S7-200 CPU, RS-485 Serial PPI
S7-200 CPU, S7-300 CPU, S7-1200 CPU; Ethernet Ethernet ISO over TCP
Modbus RTU
Modbus RTU
Modbus TCP/IP
FINS
14
14
A
a
B
B
C
C
D
D
6-4
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 5
®
81
15 9

PLC Communication Cables & Wiring Diagrams

Purchased Cable
Description
AutomationDirect Productivity Series, CLICK, Direct LOGIC PLC RJ-12 port, DL05, DL06, DL105, DL205, D3-350, D4-450 & H2-WINPLC (RS-232C)
Direct LOGIC (VGA Style) 15-pin port DL06, D2-250 (250-1), D2-260 (RS-232C)
Direct LOGIC PLC RJ-11 port, D3-340 (RS-232C)
Direct LOGIC DL405 PLC 15-pin D-sub port, DL405 (RS-232C)
Direct LOGIC PLC 25-pin D-sub port, DL405, D3-350, DL305 DCU and all DCM’s (RS-232C)
Allen-Bradley MicroLogix 1000, 1100, 1200, 1400, 1500 (RS-232C)
Allen-Bradley SLC 5-03/04/05, ControlLogix, CompactLogix, FlexLogix, MicroLogix DF1 port (RS-232C)
Allen-Bradley PLC-5 DF1 port (RS-232C)
Allen-Bradley MicroLogix, SLC 5-01/02/03, PLC5 DH485 port (RS-232C)
GE 90/30, 90/70, Micro 90, VersaMax Micro 15-pin D-sub port (RS-422A)
MITSUBISHI FX Series 25-pin port (RS-422A)
MITSUBISHI FX Series 8-pin mini-DIN (RS-422A)
OMRON Host Link C200 Adapter, C500 (RS-232C)
Cable
Part Number
EA-2CBL
EA-2CBL-1
EA-3CBL
EA-4CBL-1
EA-4CBL-2
EA-MLOGIX-CBL
EA-SLC-232-CBL
EA-PLC5-232-CBL
EA-DH485-CBL
EA-90-30-CBL
EA-MITSU-CBL
EA-MITSU-CBL-1
EA-OMRON-CBL
Part No. EA-2CBL
Part No. EA-2CBL-1
Part No. EA-3CBL
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
NOTE 1: The above list of pre-made communications cables may be purchased. See further in this chapter for wiring diagrams of additonal user constructed cables. This chapter also includes wiring diagrams for the pre-made cables.
NOTE 2: EZTouch serial PLC communication cables are compatible with C-more touch panels.
C-more PLC Serial
Communications Port
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
D-Sub 15-pin female
on rear of touch panel
6-5
14
14
A
a
B
B
C
C
D
D
Page 6
®
PLC Communication Cables & Wiring Diagrams
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
Part No. EA-4CBL-1
Part No. EA-PLC5-232-CBL
Part No. EA-MLOGIX-CBL
Part No. EA-DH485-CBL
Part No. EA-4CBL-1
Part No. EA-SLC-232-CBL
A
a
B
B
C
C
D
D
6-6
Part No. EA-MITSU-CBL-1
Part No. EA-90-30-CBL
Part No. EA-OMRON-CBL
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Part No. EA-MITSU-CBL
Page 7
®
PLC Communication Cables & Wiring Diagrams (cont’d)
The following series of wiring diagrams show the connectors and wiring details for the communication cables that are used between the C-more touch panels and various PLC controllers. Part numbers are included with the pre-made cables that can be purchased from AutomationDirect. The information presented will allow the user to construct their own cables if so desired.
EA-2CBL
To PLC
RJ12 Port
1 = Sig GND 2 = do not use 3 = RXD 4 = TXD 5 = do not use 6 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
Productivity Series, Do-more, CLICK and Direct Logic PLC RJ12 port:
DL05, DL06, DL105, DL205, DL350, DL450, H2-WINPLC
RJ12 6-pin
Phone Plug
(6P6C)
TXD
RXD
1 2 3 4 5 6
GND
RS-232C (p/n EA-2CBL)
Wiring Diagram
4
3
1
shield
8 = do not use
RXD
TXD
7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
3
2
5
1

AutomationDirect PLCs RS-232C Serial:

To PLC
15-Pin HD Port
Direct Logic PLC (VGA style) 15-pin HD port:
D2-250, D2-250-1, D2-260, DL06
RS-232C (p/n EA-2CBL-1)
To C-more Touch
Panel PLC Port
15-pin D-sub
15 = do not use
(male)
14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use
1
9 = do not use
EA-2CBL-1
To C-more Touch Panel
Serial Port2
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
8 = do not use 7 = Sig GND 6 = do not use 5 = CTS 4 = RTS 3 = RXD 2 = TXD 1 = +5 VDC - N/C
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
15-pin
HD D-sub
(male)
15 = do not use 14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use
1
6
9 = do not use
HD = High Density
TXD
RXD
GND
RTS
CTS
2
3
7
4
5
Wiring Diagram
shield
3
2
5
1
RXD
8 = do not use
TXD
7 = do not use 6 = donot use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
15-pin D-sub (male)
1
15
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
15 = do not use 14 = do not use 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
6-7
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
Page 8
®
AutomationDirect PLCs RS-232C Serial (cont’d):
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
Direct Logic PLC RJ11 port: D3-340
To PLC
RJ11 Port
RJ11 4-pin
Phone Plug
(4P4C)
1 = RXD 2 = TXD 3 = do not use 4 = Sig ground
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
1 2 3 4
TXD
RXD
GND
RS-232C (p/n EA-3CBL)
Wiring Diagram
2
1
4
shield
8 = do not use
RXD
TXD
7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
3
2
5
1
15-pin D-sub (male)
1
15
EA-3CBL
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
12
12
13
13
14
14
A
a
B
B
C
C
D
D
6-8
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 9
®
AutomationDirect PLCs RS-232C Serial (cont’d):
To PLC
15-Pin Port
Direct Logic PLC 15-pin D-sub port: DL405,
RS-232C (p/n EA-4CBL-1)
EA-4CBL-1
To C-more Touch
Panel PLC Port
1
1
2
2
Wiring Diagram
2
15-pin
8 = YOM Sense 7 = CTS 6 = do not use 5 = do not use 4 = Online 3 = RXD (232C) 2 = TXD (232C) 1 = YOP Sense
To PLC
25-Pin Port
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use 8 = do not use 7 = Signal GND 6 = do not use 5 = CTS 4 = RTS 3 = RXD 2 = TXD 1 = do not use
D-sub
15 = Logic GND
(male)
14 = Logic GND
15
13 = Logic GND 12 = do not use 11 = do not use 10 = do not use 9 = do not use
1
See PLC user manual
for pin out details.
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
25-pin D-sub
25 = do not use
(male)
24 = do not use
25
23 = do not use 22 = do not use 21 = do not use 20 = do not use 19 = do not use 18 = do not use 17 = do not use 16 = do not use 15 = do not use
1
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
14 = do not use
TXD
3
RXD
4
online
13
GND
14
GND
15
GND
1
YOP
7
CTS
8
YOM
shield
Direct Logic PLC 25-pin D-sub port:
DL405, D3-350, DL305 DCU, and all DCMs,
RS-232C (p/n EA-4CBL-2)
Wiring Diagram
2
TXD
3
RXD
7
GND
4
RTS
5
CTS
shield
3
2
5
1
3
2
5
1
RXD
TXD
8 = do not used 7 = do not used 6 = do not used 5 = Logic GND 4 = do not used 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
RXD
8 = do not use 7 = do not use
TXD
6 = do not use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
15-pin
D-sub
15 = do not use
(male)
14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
1
EA-4CBL-2
To C-more Touch
Panel PLC Port
15-pin D-sub
15 = do not use
(male)
14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
1
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
6-9
Page 10
®

AutomationDirect PLCs RS-422A/RS-485A:

When using the RS-422A/RS-485A capabilities of the C-more PLC communications port, the
1
1
2
2
termination resistor is placed between the RXD– and RXD+ terminals on the PLC side of the connection between the touch panel and PLC. The Termination Resistor value is based on the characteristic impedance of the cable being used. To enable the built-in 120 Ohm Termination Resistor, jumper pin 13 to pin 9 (RXD+) on the C-more 15-pin PLC communications port.
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
To PLC
15-Pin Port
HD D-sub
8 = do not use 7 = Sig GND 6 = RXD– 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
To PLC
25-Pin Port
Direct LOGIC DL-06, D2-250, D2-250-1, D2-260 (all Port 2)
15-pin
(male)
1
15
6
15 = CTS– 14 = CTS+ 13 = RXD+ 12 = RTS­11 = RTS+ 10 = TXD– 9 = TXD+
TXD+
TXD–
RXD+
RXD–
GND
RTS–
CTS–
RTS+
CTS+
Direct LOGIC D2-DCM*, D3-DCM* & D4-DCM*
9
10
13
6
7
12
15
11
14
RS-422A
Wiring Diagram
shield
RS-422A
User Constructed
13
9
10
11
12
5
1
Term.
RD+
8 = do not use 7 = do not use
RD–
6 = do not use
SD+
5 = Logic GND
SD–
4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
User Constructed
14
15
17
16
7
11
13
10
12
Wiring Diagram
shield
13
Term.
9
RD+
8 = do not use
10
7 = do not use
RD–
6 = do not use
11
SD+
5 = Logic GND
12
SD–
4 = do not use 3 = do not use
5
2 = do not use 1 = Frame GND
* Note: The DCM modules must be set for: Direct NET Slave, HEX mode.
1
25-pin
25 = do not use
D-sub 13 = CTS– 12 = CTS+ 11 = RTS– 10 = RTS+ 9 = do not use 8 = do not use 7 = 0 V 6 = do not use 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
(male)
1
24 = do not use 23 = do not use 22 = do not use
25
21 = do not use 20 = do not use 19 = do not use 18 = do not use 17 = RXD+ (RS422) 16 = RXD– (RS422) 15 = TXD– (RS422) 14 = TXD+ (RS422)
TXD+
TXD–
RXD+
RXD–
0V
RTS–
CTS–
RTS+
CTS+
15-pin D-sub (male)
1
15-pin D-sub (male)
1
15
15
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS422) 11 = SD+ (RS422) 10 = RD– (RS422) 9 = RD+ (RS422)
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS422) 11 = SD+ (RS422) 10 = RD– (RS422) 9 = RD+ (RS422)
C
C
D
D
6-10
NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be connected to a panel.
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 11
®
AutomationDirect PLCs RS-422A/RS-485A (cont’d):
To PLC
25-Pin Port
Direct LOGIC D4-430/D4-440/D4-450 Port 1 and D3-350 Port 2
RS-422A
User Constructed
To C-more Touch
Panel PLC Port
1
1
2
2
14
16
9
10
7
18
23
19
11
12
13
24
25
7
Wiring Diagram
shield
RS-422A
Wiring Diagram
shield
13
9
10
11
12
5
1
13
9
10
11
12
5
1
Term.
RD+
8 = do not use 7 = do not use
RD–
6 = do not use
SD+
5 = Logic GND
SD–
4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
User Constructed
Term.
RD+
8 = do not use 7 = do not use
RD–
6 = do not use
SD+
5 = Logic GND
SD–
4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
25-pin
D-sub 13 = do not use 12 = do not use 11 = CTS+ 10 = RXD– (RS422) 9 = RXD+ (RS422) 8 = do not use 7 = 0 V 6 = do not use 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
To PLC
25-Pin Port
13 = TXD– (RS422) 12 = TXD+ (RS422) 11 = do not use 10 = do not use 9 = do not use 8 = do not use 7 = 0 V 6 = do not use 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
(male)
1
25-pin
D-sub
(male)
1
25 = do not use 24 = do not use
25
23 = CTS– 22 = do not use 21 = do not use 20 = do not use 19 = RTS+ 18 = RTS– 17 = do not use 16 = TXD– (RS422) 15 = do not use 14 = TXD+ (RS422)
25 = RXD– (RS422) 24 = RXD+
25
(RS422) 23 = do not use 22 = do not use 21 = do not use 20 = do not use 19 = do not use 18 = do not use 17 = do not use 16 = do not use 15 = do not use 14 = do not use
TXD+
TXD–
RXD+
RXD–
0V
RTS–
CTS–
RTS+
CTS+
Direct LOGIC D4-450 Port 3
RTS and CTS are not present on this port.
TXD+
TXD–
RXD+
RXD–
0V
15-pin D-sub (male)
1
15-pin
D-sub
(male)
1
15
15
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS422) 11 = SD+ (RS422) 10 = RD– (RS422) 9 = RD+ (RS422)
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS422) 11 = SD+ (RS422) 10 = RD– (RS422) 9 = RD+ (RS422)
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be connected to a panel.
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
6-11
B
C
C
D
D
Page 12
®
AutomationDirect PLCs RS-422A/RS-485A (cont’d):
1
1
2
2
To PLC
15-Pin Port
Direct LOGIC DL-06, D2-260 (both Port 2)
RS-485A
User Constructed
To C-more Touch
Panel PLC Port
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
15-pin
HD D-sub
(male)
8 = do not use 7 = Sig GND 6 = RXD– 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
NOTE: The RS-485 wiring diagram shown above is not for multi-drop networks involving connecting more than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be connected to a panel.
15 = CTS–
15
14 = CTS+ 13 = RXD+ 12 = RTS­11 = RTS+
1
6
10 = TXD– 9 = TXD+
RXD+
TXD+
TXD–
RXD–
GND
RTS–
CTS–
RTS+
CTS+
Wiring Diagram
13
9
10
6
7
12
15
11
14
shield
13
9
11
10
12
5
1
Term.
RD+
8 = do not use 7 = do not use
SD+
6 = do not use
RD–
5 = Logic GND
SD–
4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
15-pin D-sub
(male)
1
15
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS485) 11 = SD+ (RS485) 10 = RD– (RS485) 9 = RD+ (RS485)
14
14
A
a
B
B
C
C
D
D
6-12
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 13
®
AutomationDirect PLCs RS-422A/RS-485A (cont’d):
Direct LOGIC ZIPLink ZL-CMA15L Adapter Module to EA-COMCON-3 Terminal Block Adapter
RS-232 RXD
RS-232 TXD
TERMINATE
232
TXD
RXD
+5V
232
TXD
RXD
+5V
SIGNAL GND
RS-422/485 RX–
RS-422/485 TX–
RS-422/485 RX+
RS-422/485 TX+
RS-232 RXD
RS-232 TXD
SIGNAL GND
RS-422/485 RX–
RS-422/485 RX+
RS-422/485 TX–
RS-422/485 TX+
ZL-CMA15L
RXD
TXD
RS422/485
TX+
TX-
SG
RX-
RX+
ZL-CMA15L
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
Direct LOGIC ZIPLink ZL-CMA15L Adapter Module to EA-COMCON-3 Terminal Block Adapter
TERMINATE
ZL-CMA15L
RXD
TXD
RS422/485
TX+
TX-
SG
RX-
RX+
ZL-CMA15L
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
RS-485A – PLC D2-260 or DL06 only – Port 2
Wiring Diagram
+5V
See ZL-CMA15L specifications on termination resistor jumper.
RS-422A – PLC D2-250 (-1), D2-260 or DL06 – Port 2
+5V
See ZL-CMA15L specifications on termination resistor jumper.
shield
Wiring Diagram
shield
Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
GND
RD–
SD–
SD+
RD+
EA-COMCON-3
TERM
Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
GND
SD–
SD+
RD–
RD+
EA-COMCON-3
TERM
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
NOTE: The RS-422 and RS-485 wiring diagrams shown above are not for multi-drop networks involving connecting more than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more than one PLC will be connected to a panel.
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
14
14
6-13
A
a
B
B
C
C
D
D
Page 14
®
AutomationDirect PLCs RS-422A/RS-485A (cont’d):
1
1
Productivity3000 PAC RS485 Port to EA-COMCON-3 Terminal Block Adapter
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
SIGNAL GND
TXD / RXD –
TXD / RXD +
Productivity3000
PS485 Port
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Removable Connector
included with
Productivity3000 CPU
*
Wiring Diagram
shield
* 120 Ω resistor
AutomationDirect Productivity PAC
RS-485
Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
GND
RD –
SD –
SD +
RD +
TERM
EA-COMCON-3
To C-more Touch Panel Serial Port2
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
6-14
Wiring Diagram
TXD+ / RXD+
TXD- / RXD-
+
-
Ground
G
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
NOTE: The RS-485 wiring diagrams shown above are not for multi-drop networks involving connecting more than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more than one PLC will be connected to a panel.
TXD+ / RXD+
TXD- / RXD-
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
3
Term.
8 10
5
Ground
Use 120 ohm resistors as termination resistors (Term.)
shield
13
11
12
Term.
9
RD+
8 = do not use 7 = do not use
SD+
6 = do not use
RD–
5 = Logic GND
SD–
4 = do not use
5
1
3 = do not use 2 = do not use 1 = Frame GND
15-pin D-sub
(male)
1
15
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS485) 11 = SD+ (RS485) 10 = RD– (RS485) 9 = RD+ (RS485)
Page 15
®
AutomationDirect PLCs RS-422A/RS-485A (cont’d):
CLICK
Com Port 3
RS-485 Signal A
RS-485 Signal B
Logic Ground
+
-
LG
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
AutomationDirect CLICK PLC
RS-485
Signal A
Term.
RS-485
Signal B
Logic
Ground
Use 120 ohm resistors as termination resistors (Term.)
Analog CPU
RS-485
Wiring Diagram
3
8 10
5
shield
13
11
12
9
5
1
Term.
RD+
8 = do not use 7 = do not use
SD+
6 = do not use
RD–
5 = Logic GND
SD–
4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
To C-more Touch Panel Serial Port2
15-pin
D-sub
(male)
15
1
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS485) 11 = SD+ (RS485) 10 = RD– (RS485) 9 = RD+ (RS485)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
NOTE: The RS-422 and RS-485 wiring diagrams shown above are not for multi-drop networks involving connecting more than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more than one PLC will be connected to a panel.
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
6-15
D
D
Page 16
®

Direct LOGIC Universal Isolated Network Adapter, p/n FA-ISOCON:

1
1
RS-422A to RS-232C – PLC DL05 or D2-240 – Port 2 only
2
2
A
3
3
RXD
4
4
5
5
6
6
7
7
8
8
9
9
TXD
TXD EN
B
C
D
FA-ISOCON
FA-ISOCON Universal Isolated Network Adapter
Wiring Diagram
COM B
RX–
RX+
TX–
TXD RXD CTS C-A
+V C-A
TX+ TX– RX– RX+ C-B
TX+
Ground the shield only at the equipment end where the FA-ISOCON is located.
See FA-ISOCON specificaitons to properly configure the adapter.
shield
Port 2
Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
GND
SD–
SD+
RD–
RD+
TERM
EA-COMCON-3
Note: When using multiple PLCs connected to one C-more touch panel, only jumper the Term terminal to the RD+ terminal when the panel is the last device at one end of the network.
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
6-16
DL05 PLC
R
W
Modular cable included with the FA-ISOCON
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
P
N
U
R
U
P
C
1
X
T
1
X
R
2
X
T
2
X
R
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 17
®

Direct LOGIC Universal Converter, p/n F2-UNICON:

RS-422A to RS-232C – PLC DL05 or D2-240 – Port 2 only
F2-UNICON Universal Converter
Wiring Diagram
GND
RXD–
RXD+
TXD–
TXD+
Ground the shield only at the equipment end where the F2-UNICON is located.
shield
Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
GND
SD–
SD+
RD–
RD+
TERM
EA-COMCON-3
1
1
2
2
3
3
4
4
5
5
See F2-UNICON specificaitons to
F2-UNICON
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
properly configure the converter.
Modular cable included with the F2-UNICON
Note: When using multiple PLCs connected to one C-more touch panel, only jumper the Term terminal to the RD+ terminal when the panel is the last device at one end of the network.
D2-240 PLC
PWR
BATT
DL240
CPU
RUN CPU
RUN
TERM
CH 1
CH 2
CH 3
CH 4
PORT 1
PORT 2
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
6-17
Page 18
®
Typical RS-422 Multi-Drop Wiring Diagram (cont-d)
HD = High Density
8 = do not use 7 = Sig GND 6 = RXD– 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples

1
1
DL06 and DL205 used for illustration purposes
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
DirectLOGIC
DL06 PLC
(example device communicating
across RS-422 connection)
Port 2
ZL-CMA15L
RXD
TXD
When connecting to a DirectLogic PLC
232
RXD–
RS422/485
TX+
TX-
TXD
SG
RXD
RX-
RX+
+5V
use connector ZL-CMA15L or ZL-CMA15
Shielded Cable
RTS–
RTS+
CTS+
RXD+
*
RXD+
RXD–
Cable Adapter
(ZL-CMA15L shown)
To DL06 PLC port 2
(example RS-422 connection)
GND
TXD–
TXD+
7
10 9 6 13 11 14 12 15
TXD+
TXD–
Signal GND
* Termination resistors required at both ends of the network receive data signals to match the impedance of the cable (between 100 and 500 ohms).
Typical RS-422 Multi-Drop Wiring Diagram
Port 2
ZL-CMA15L
(Slave)
Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
CTS–
8 = do not use 7 = Sig GND 6 = RXD– 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
HD D-sub
1
HD = High Density
using DirectLogic pin numbers to illustrate
Cable Adapter
(ZL-CMA15L shown)
15-pin
15 = CTS–
(male)
14 = CTS+
15
13 = RXD+ 12 = RTS­11 = RTS+ 10 = TXD– 9 = TXD+
6
RXD
TXD
232
RS422/485
TX+
TX-
TXD
SG
RXD
RX-
RX+
+5V
Shielded Cable
To D2-250-1 PLC port 2
(example RS-422 connection)
GND
TXD–
TXD+
RTS+
RXD–
7
10 9 6 13 11 14 12 15
shield
CTS+
RXD+
(Slave)
DirectLOGIC
DL205 PLC
(example device communicating across RS-422 connection)
CTS–
RTS–
RXD+
RXD–
TXD+
TXD–
Signal GND
6-18
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 19
®
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)
DL06 and DL205 used for illustration purposes
C-more
Touch Panel
Shielded Cable
Date code
Country of Origin
EA-COMCON-3
KOYO ELECTRONICS INDUSTRIES CO., LTD.
SD–
GND
SD+
(Slave)
Port 2
Cable Adapter
(ZL-CMA15L shown)
Shielded Cable
DirectLOGIC
DL06 PLC
(example device communicating
across RS-422 connection)
ZL-CMA15L
RXD
TXD
232
RS422/485
TX-
TXD
TX+
SG
RXD
RX-
RX+
+5V
1
1
2
2
3
3
4
4
5
(Master)
TERM
RD+
RD–
5
6
6
7
7
8
8
9
9
Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
To DL06 PLC port 2
(example RS-422 connection)
GND
8 = do not use 7 = Sig GND 6 = RXD– 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
15-pin
HD D-sub
15 = CTS–
(male)
14 = CTS+
15
13 = RXD+ 12 = RTS­11 = RTS+ 10 = TXD– 9 = TXD+
1
6
HD = High Density
TXD+
TXD–
RXD+
RXD–
Signal GND
TXD–
TXD+
7
10 9 6 13 11 14 12 15
RXD–
shield
RTS+
RXD+
RTS–
CTS+
Signal GND
CTS–
TXD+
TXD–
8 = do not use 7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
RXD+
RXD–
Typical RS-422 Multi-Drop Wiring Diagram (cont-d)
using DirectLogic pin numbers to illustrate
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
To C-more Touch Panel
EA-COMCON-3
15-pin D-sub
15 = do not use
(male)
14 = do not use
15
13 = Termination 12 = SD– (RS422) 11 = SD+ (RS422) 10 = RD– (RS422) 9 = RD+ (RS422)
1
* Termination resistors required at both ends of the network receive data signals to match the impedance of the cable (between 100 and 500 ohms). Jumper pin 13 to 9 on the C-more Touch Panel 15-pin connector to place the 120 internal resistor into the network. If the cable impedance is different, then use an external resistor matched to the cable impedance.
RD–
GND
5
10 9 12 11 13 1
RD+
shield
SD–
SD+
* Term.
10
10
11
11
SHD
12
12
13
13
14
14
6-19
A
a
B
B
C
C
D
D
Page 20
®
Typical RS-485 Multi-Drop Wiring Diagram (cont-d)
8 = do not use 7 = Sig GND 6 = RXD– 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)
1
1
DL06 and DL205 used for illustration purposes
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
(example device communicating
across RS-422 connection)
Port 2
ZL-CMA15L
RXD
TXD
TXD–
RS422/485
TX+
TX-
SG
RX-
RX+
+5V
TXD+
RTS+
CTS+
RXD+
*
Cable Adapter
(ZL-CMA15L shown)
To DL06 PLC port 2
(example RS-485 connection)
GND
RXD–
7
6 10 13 9 11 14 12 15
* Termination resistors required at both ends of the network to match the impedance of the cable (between 100 and 500 ohms).
DirectLOGIC
DL06 PLC
Port 2
ZL-CMA15L
(Slave)
When connecting to a DirectLogic PLC
232
TXD
RXD
use connector ZL-CMA15L or ZL-CMA15
Shielded Cable
Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
CTS–
RTS–
8 = do not use 7 = Sig GND 6 = RXD– 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
HD D-sub
HD = High Density
TXD– / RXD–
TXD+ / RXD+
Signal GND
Cable Adapter
(ZL-CMA15L shown)
15-pin
15 = CTS–
(male)
14 = CTS+
15
13 = RXD+ 12 = RTS­11 = RTS+ 10 = TXD– 9 = TXD+
1
6
RXD
TXD
RS422/485
TX+
TX-
SG
RX-
RX+
To D2-250-1 PLC port 2
(example RS-485 connection)
GND
RXD–
7
6 10 13 9 11 14 12 15
shield
Typical RS-485 Multi-Drop Wiring Diagram
using DirectLogic pin numbers to illustrate
232
TXD
RXD
+5V
TXD–
RXD+
DirectLOGIC
DL205 PLC
(example device communicating across RS-422 connection)
Shielded Cable
CTS–
RTS+
CTS+
RTS–
TXD+
(Slave)
TXD– / RXD–
TXD+ / RXD+
Signal GND
6-20
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 21
®
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)
DL06 and DL205 used for illustration purposes
C-more
Touch Panel
Shielded Cable
Date code
Country of Origin
EA-COMCON-3
KOYO ELECTRONICS INDUSTRIES CO., LTD.
SD–
GND
TERM
RD+
RD–
SD+
(Slave)
Port 2
Cable Adapter
(ZL-CMA15L shown)
Shielded Cable
DirectLOGIC
DL06 PLC
(example device communicating
across RS-422 connection)
ZL-CMA15L
RXD
TXD
232
RS422/485
TX-
TXD
TX+
SG
RXD
RX-
RX+
+5V
(Master)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
To DL06 PLC port 2
(example RS-485 connection)
8 = do not use 7 = Sig GND 6 = RXD– 5 = do not use 4 = do not use 3 = do not use 2 = do not use 1 = do not use
TXD– / RXD–
TXD+ / RXD+
Signal GND
15-pin
HD D-sub
15 = CTS–
(male)
14 = CTS+
15
13 = RXD+ 12 = RTS­11 = RTS+ 10 = TXD– 9 = TXD+
1
6
HD = High Density
GND
TXD–
RXD–
7
6 10 13 9 11 14 12 15
shield
TXD+
RXD+
RTS+
CTS+
CTS–
RTS–
8 = do not use 7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
Typical RS-485 Multi-Drop Wiring Diagram (cont-d)
using DirectLogic pin numbers to illustrate
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
15-pin D-sub
(male)
1
TXD– / RXD–
TXD+ / RXD+
Signal GND
To C-more Touch Panel
SD–
EA-COMCON-3
15 = do not use 14 = do not use
15
13 = Termination 12 = SD– (RS485) 11 = SD+ (RS485) 10 = RD– (RS485) 9 = RD+ (RS485)
* Termination resistors required at both ends of the network receive data signals to match the impedance of the cable (between 100 and 500 ohms). Jumper pin 13 to 9 on the C-more touch panel 15-pin connector to place the 120 internal resistor into the network. If the cable impedance is different, then use an external resistor matched to the cable impedance.
RD–
GND
5
10 12 9 11 13 1
shield
10
10
11
11
SD+
RD+
* Term.
SHD
12
12
13
13
14
14
A
a
B
B
C
C
D
D
6-21
Page 22
®

Allen-Bradley:

1
1
2
2
To AB MicroLogix RS-232
communication channel
Allen-Bradley MicroLogix™ 1000/1100/1200/1400/1500
RS-232C (p/n EA-MLOGIX-CBL)
EA-MLOGIX-CBL
To C-more Touch
Panel PLC Port
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
0.35” DIA.
Mini Din
8-pin Male
8
6 7
3 4 5
1 2
Nonstandard
keying
TXD
RXD
0.290”
GND
7
4
2
Wiring Diagram
shield
8 = do not use
3
2
5
1
7 = do not use 6 = do not use
RXD
5 = Logic GND
TXD
4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
1 = do not use 2 = Sig GND 3 = do not use 4 = RXD 5 = do not use 6 = do not use 7 = TXD 8 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
EA-SLC-232-CBL
To PLC
9-Pin Port
D-sub
(female)
1 = do not use 2 = RXD 3 = TXD 4 = do not use 5 = Signal GND
1
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
Allen-Bradley SLC 5-03/04/05, ControlLogix, CompactLogix,
FlexLogix, MicroLogix, DF1, RS-232C (p/n EA-SLC-232-CBL)
9-pin
Wiring Diagram
6 = do not use 7 = do not use 8 = do not use 9 = do not use
9
TXD
RXD
GND
3
2
5
shield
3
RXD
2
TXD
5
1
8 = do not use 7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
1
EA-PLC5-232-CBL
To PLC
25-Pin Port
Allen-Bradley PLC5 DF1
RS-232C (p/n EA-PLC5-232-CBL)
15-pin D-sub (male)
15
1
To C-more Touch
Panel PLC Port
15-pin D-sub (male)
15 = do not use 14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
15 = do not use 14 = do not use 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
To C-more Touch
Panel PLC Port
14
14
A
a
B
B
C
C
D
D
6-22
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use 8 = do not use 7 = Signal GND 6 = do not use 5 = do not use 4 = do not use 3 = RXD 2 = TXD 1 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
25-pin D-sub (male)
1
25 = do not use 24 = do not use
25
23 = do not use 22 = do not use 21 = do not use 20 = do not use 19 = do not use 18 = do not use 17 = do not use 16 = do not use 15 = do not use 14 = do not use
TXD
RXD
GND
2
3
7
Wiring Diagram
shield
3
2
5
1
RXD
8 = do not use 7 = do not use
TXD
6 = do not use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
15-pin D-sub
(male)
1
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
15 = do not use 14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
Page 23
®
DH-485
Peripheral
CPU
J1
Power
Allen-Bradley
SLC 500 Modular
PLC Controller
DH-485 Link
(See manufacturer’s litature for details.)
AB 1747-AIC
DH485 Link Coupler
AB 1747-C11 A
Cable
J2
DH-485
Peripheral
CPU
J1
Power
J2
C-more
Touch Panel
C-more
Touch Panel
Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network using the AB DH485 Link Coupler, p/n 1747-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.
C-more
EA-DH485-CBL
Cable
C-more
EA-DH485-CBL
Cable
Allen-Bradley SLC500™, 5/01, /02, /03 DH-485/AIC to Multiple C-more Touch Panels
RS-485A (using C-more cable p/n EA-DH485-CBL)
AB 1747-AIC
DH485 Link Coupler
Channel 1 must be set to DH485.
Allen-Bradley (cont’d):
To AB SLC500
DH-485 Port
RJ45 8-pin
Phone Plug 1 = TXD/RXD+ 2 = TXD/RXD– 3 = do not use 4 = Signal GND 5 = LE 6 = do not use 7 = Signal GND 8 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
(8P8C)
Allen-Bradley SLC500™, 5/01, /02, /03 DH-485
RS-485A (p/n EA-DH485-CBL)
TXD/RXD+
TXD/RXD–
1
2
5
LE *
4
GND
7
GND
Point-to-Point
Wiring Diagram
shield
13
Term.
9
10
11
12
8 = do not use
RD+
7 = do not use
RD–
6 = LE 5 = Logic GND
SD+
4 = do not use
SD–
3 = do not use
6
2 = do not use
LE *
1 = Frame GND
5
1
* Note: The LE signal is wired in the cable as shown, but not required for point-to-point communications.
EA-DH485-CBL
15-pin D-sub (male)
15
1
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS485) 11 = SD+ (RS485) 10 = RD– (RS485) 9 = RD+ (RS485)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
14
14
6-23
A
a
B
B
C
C
D
D
Page 24
®
Allen-Bradley (cont’d):
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
Allen-Bradley
SLC 5/03 Modular
PLC Controller
AB 1747-CP3
RS-232 Cable
Allen-Bradley SLC500™ 5/03 DH-485/AIC to Multiple C-more Touch Panels
(using C-more cables p/n EA-MLOGIX-CBL, EA-SLC-232-CBL)
DH-485 Link
C-more
Touch Panel
Channel 0 must be set to DH485.
C-more
Touch Panel
(See manufacturer’s litature for details.)
AB 1761-NET-AIC
AIC + Advanced
Interface Converter
C-more
EA-MLOGIX-CBL
Cable
AB 1761-NET-AIC
AIC + Advanced
Interface Converter
C-more
EA-MLOGIX-CBL
Cable
To additional
Touch Panel
C-more
EA-SLC-232-CBL
Cable
C-more
12
12
13
13
14
14
A
a
B
B
C
C
D
D
6-24
Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network using the AB AIC+ Advanced Interface Converter, p/n 1761-NET-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 25
®
Allen-Bradley (cont’d):
Multiple Allen-Bradley PLCs connected to multiple C-more Touch Panels
(using AB Ethernet Network Interface p/n 761-NET-ENI with EtherNet/IP protocol)
Allen-Bradley
SLC 5/03 Modular
PLC Controller
AB 1761-NET-ENI
C-more
Touch Panel
cable p/n 1761-CBL-AP00
ETHERNET
RS232
FAULT
TX/RX
IP
PWR
CABLE
EXTERNAL
AB mini DIN to D-shell
AB 1761-NET-ENI
ETHERNET
RS232
FAULT
TX/RX
IP
PWR
CABLE
EXTERNAL
Ethernet/IP
Network
Allen-Bradley
MicroLogix 1000
PLC Controller
Ethernet
Hub or Switch
10/100 Base-T
AB mini DIN to mini DIN
cable p/n 1761-CBL-AM00
Allen-Bradley
MicroLogix 1500
PLC Controller
ETHERNET
RS232
FAULT
TX/RX
IP
PWR
CABLE
EXTERNAL
AB 1761-NET-ENI
C-more
Touch Panel
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
6-25
Page 26
®
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
Allen-Bradley (cont’d):
To PLC
25-Pin Port
25-pin
D-sub 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use 8 = do not use 7 = Signal GND 6 = do not use 5 = do not use 4 = do not use 3 = RXD + 2 = TXD + 1 = do not use
Notes:
1. Polarities must be swapped.
2. Handshaking is turned off
3. Use the above wiring diagram if you need to make your own cable. We recommend using 8103 shielded cable or equivalent.
4. Refer to the PLC-5 Programmable Controllers User Manual Switch Setting Reference for details on switch settings to define the controller's serial port electrical interface.
(male)
1
25 = do not use 24 = do not use
25
23 = do not use 22 = do not use 21 = do not use 20 = do not use 19 = do not use 18 = do not use 17 = do not use 16 = RXD – 15 = do not use 14 = TXD –
Allen Bradley PLC5 DF1
Wiring Diagram
2
TXD +
3
RXD +
7
GND
14
TXD –
16
RXD –
RS-422
shield
10
RD –
12
SD –
5
9
RD +
11
SD +
1
User Constructed
15-pin
8 = do not use 7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
D-sub (male)
1
To C-more
PLC Port
15 = do not use 14 = do not use
15
13 = do not use 12 = SD – 11 = SD + 10 = RD – 9 = RD +
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
6-26
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Page 27
®
GE:
To PLC
15-Pin Port
15-pin D-sub
8 = CTS(B’) 7 = Logic GND 6 = do not use 5 = +5V 4 = do not use 3 = do not use 2 = do not use 1 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
(male)
1
15 = CTS(A’) 14 = do not use
15
13 = SD(B) 12 = SD(A) 11 = RD(B’) 10 = RD(A’) 9 = do not use
GE 90/30 and 90/70 15-pin D-sub port,
RS-422A (p/n EA-90-30-CBL)
SD(B)
SD(A)
RD(B’)
RD(A’)
GND
CTS(B’)
CTS(A’)
+5V
Wiring Diagram
13
12
11
10
7
8
15
5
shield
13
9
10
11
12
5
1
Term.
RD+
8 = do not use
RD–
7 = do not use 6 = do not use
SD+
5 = Logic GND
SD–
4 = do not use 3 = do not use 2 = do not use 1 = Frame GND

GE VersaMax Micro:

To PLC
RJ45 Port 1
1 = RTS 2 = CTS 3 = RXD 4 = TXD 5 = DCD 6 = DTR 7 = +5V 8 = GND
RJ45 8-pin
Phone Plug
(8P8C)
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
GE VersaMax Micro Port 1
TXD
RXD
GND
RS-232C
Wiring Diagram
4
3
8
shield
3
2
5
1
8 = do not use
RXD
7 = do not use 6 = donot use
TXD
5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND

Mitsubishi:

To PLC
25-Pin Port
Mitsubishi FX Series 25-pin D-sub port,
RS-422A (p/n EA-MITSU-CBL)
EA-90-30-CBL
To C-more Touch
15-pin D-sub (male)
15 = do not use 14 = do not use
15
13 = Termination 12 = SD– (RS422) 11 = SD+ (RS422) 10 = RD– (RS422)
1
9 = RD+ (RS422)
User Constructed
15-pin D-sub (male)
15
1
EA-MITSU-CBL
Panel PLC Port
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
To C-more Touch
Panel PLC Port
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
25-pin
D-sub 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use 8 = do not use 7 = Signal GND 6 = do not use 5 = do not use 4 = Signal GND 3 = SD+ (RS422) 2 = RD+ (RS422) 1 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
(male)
1
25
25 = do not use 24 = do not use 23 = do not use 22 = do not use 21 = do not use 20 = do not use 19 = do not use 18 = do not use 17 = do not use 16 = SD– (RS422) 15 = RD– (RS422) 14 = do not use
SD+
SD–
RD+
RD–
GND
GND
Wiring Diagram
3
16
2
15
7
4
shield
13
9
10
11
12
5
1
Term.
RD+
8 = do not use
RD–
7 = do not use 6 = do not use
SD+
5 = Logic GND
SD–
4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
15-pin D-sub
(male)
1
15
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS422) 11 = SD+ (RS422) 10 = RD– (RS422) 9 = RD+ (RS422)
6-27
14
14
A
a
B
B
C
C
D
D
Page 28
®
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
Mitsubishi(cont’d):
To PLC
8-Pin Port
Mini Din
1 = RD– (RS-422) 2 = RD+ (RS-422) 3 = Sig GND 4 = SD– (RS-422) 5 = do not use 6 = do not use 7 = SD+ (RS-422) 8 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
8-pin Male
8
67
345
12
Mitsubishi FX Series 8-pin MINI-DIN,
RS-422A (p/n EA-MITSU-CBL-1)
Wiring Diagram
7
SD+
4
SD–
2
RD+
1
RD–
3
GND
shield
13
Term.
9
RD+
10
RD–
11
SD+
12
SD–
5
1
EA-MITSU-CBL-1
15-pin
8 = do not use 7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
D-sub (male)
1
15
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS422) 11 = SD+ (RS422) 10 = RD– (RS422) 9 = RD+ (RS422)
User Constructed
To PLC
6-Pin Port
1 = RXD (232C) 2 = TXD (232C) 3 = Logic GND 4 = do not use 5 = do not use 6 = do not use
Mitsubishi Q02 / Q02H / Q06H / Q12H / Q25H Serial Driver
and QnA Serial Driver with Direct Connection to
the Serial Port on Q00 and Q01 CPU’s
Mini Din
6-pin Male
2
TXD
5 6
34
12
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
RXD
GND
1
3
RS-232C
Wiring Diagram
shield
3
2
5
1
8 = do not use
RXD
7 = do not use 6 = donot use
TXD
5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
To C-more Touch
Panel PLC Port
15-pin D-sub (male)
15 = do not use 14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use
1
9 = do not use
User Constructed
13
13
14
14
A
a
B
B
C
C
D
D
6-28
To PLC
9-Pin Port
9-pin
D-sub
(female)
1 = CD 2 = RXD 3 = TXD 4 = DTR 5 = Signal GND
1
6 = DSR 7 = RS 8 = CS 9 = do not use
9
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
Mitsubishi Q / QnA Serial PLC
1
CD
4
DTR
6
DSR
7
RS
8
CS
3
TXD
2
RXD
5
GND
QJ71C24N
RS-232C
Wiring Diagram
shield
3
2
5
1
8 = do not use 7 = do not use 6 = do not use 5 = Logic GND 4 = do not use
RXD
3 = RXD (232C)
TXD
2 = TXD (232C) 1 = Frame GND
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
To C-more Touch
Panel PLC Port
15-pin D-sub (male)
15
1
15 = do not use 14 = do not use 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
Page 29
®

Omron:

To PLC
25-Pin Port
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use 8 = do not use 7 = Signal GND 6 = do not use 5 = CTS 4 = RTS 3 = RXD 2 = TXD 1 = do not use
To Peripheral
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
To PLC
9-Pin Port
1 = do not use 2 = TXD 3 = RXD 4 = RTS 5 = CTS
Port Cable
EA-OMRON-CBL
Omron Host Link (C200 Adapter, C500),
RS-232C (p/n EA-OMRON-CBL)
2
3
7
4
5
Wiring Diagram
shield
3
2
5
1
RXD
8 = do not use 7 = do not use
TXD
6 = do not use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
15-pin D-sub (male)
1
15
25-pin
D-sub
(male)
1
25 = do not use 24 = do not use
25
23 = do not use 22 = do not use 21 = do not use 20 = do not use 19 = do not use 18 = do not use 17 = do not use 16 = do not use 15 = do not use 14 = do not use
TXD
RXD
GND
RTS
CTS
User Constructed
Omron FINS (CQM1, CPM1, CPM2, C200, CJ1 & CS1)
9-pin D-sub (male)
9
6 = do not use 7 = do not use 8 = do not use 9 = Signal GND
1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
TXD
RXD
RTS
CTS
SG
2
3
9
4
5
RS-232C
Wiring Diagram
shield
3
2
5
1
8 = do not use 7 = do not use 6 = do not use
RXD
5 = Logic GND
TXD
4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
To C-more Touch
15-pin D-sub
(male)
15
1
Panel PLC Port
15 = do not use 14 = do not use 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
User Constructed
Omron Host Link CQM1 using CQM1-CIF02 Peripheral Port Connecting Cable
RS-232C
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
To C-more Touch
Panel PLC Port
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
1 = do not use 2 = RXD 3 = TXD 4 = do not use 5 = Signal GND
9-pin D-sub (male)
9
6 = do not use 7 = do not use 8 = do not use 9 = do not use
1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
TXD
RXD
GND
3
2
5
Wiring Diagram
shield
3
2
5
1
RXD
TXD
8 = do not use 7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
15-pin
D-sub
(male)
1
15
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
15 = do not use 14 = do not use 13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
6-29
B
B
C
C
D
D
Page 30
®
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12

Modicon ModBus RS-232:

To PLC
9-Pin Port
1 = do not use 2 = RXD 3 = TXD 4 = DTR 5 = Signal GND
9-pin
D-sub
(male)
9
1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
Modicon™ ModBus™, 984 CPU, Quanum 113 CPU
6 = DSR 7 = RTS 8 = CTS 9 = do not use

Modicon Micro Series:

To PLC
9-Pin Port
1 = do not use 2 = TXD 3 = RXD 4 = do not use 5 = Signal GND
110 CPU 311-xx, 110 CPU 411-xx, 110 CPU 512-xx, 110 CPU 612-xx
9-pin
D-sub
(female)
1
6 = do not use 7 = do not use 8 = do not use 9 = do not use
9
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
RS-232C
Wiring Diagram
3
TXD
2
RXD
5
GND
4
DTR
6
DSR
7
RTS
8
CTS
AEG Modicon™ Micro Series:
2
TXD
3
RXD
5
GND
shield
RS-232C
Wiring Diagram
shield
3
2
5
1
3
2
5
1
8 = do not use 7 = do not use 6 = do not use
RXD
5 = Logic GND
TXD
4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
8 = do not use 7 = do not use 6 = do not use
RXD
5 = Logic GND
TXD
4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
User Constructed
To C-more Touch
Panel PLC Port
15-pin
D-sub
(male)
15 = do not use 14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
1
User Constructed
To C-more Touch
Panel PLC Port
15-pin
D-sub
15 = do not use
(male)
14 = do not use 13 = do not use
15
12 = do not use 11 = do not use 10 = do not use 9 = do not use
1
13
13
14
14
A
a
B
B
C
C
D
D
6-30

Modicon ModBus with RJ45:

To PLC
RJ45 Port
1 = do not use 2 = do not use 3 = TXD 4 = RXD 5 = Logic GND 6 = RTS 7 = CTS 8 = do not use
RJ45 8-pin Phone Plug
(8P8C)
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Modicon™ ModBus™ with RJ45
TXD
RXD
GND
RTS
CTS
3
4
5
6
7
RS-232C
Wiring Diagram
shield
3
2
5
1
User Constructed
15-pin
RXD
8 = do not use
TXD
7 = do not use 6 = donot use 5 = Logic GND 4 = do not use 3 = RXD (232C) 2 = TXD (232C) 1 = Frame GND
D-sub (male)
1
To C-more Touch
Panel PLC Port
15 = do not use 14 = do not use
15
13 = do not use 12 = do not use 11 = do not use 10 = do not use 9 = do not use
Page 31
®

Siemens:

To PLC
9-Pin Port
9-pin D-sub (male)
1 = Logic Com 2 = Logic Com 3 = RS485 Sig B 4 = do not use 5 = Logic Com
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect L19954 shielded cable or equivalent.
9
1
6 = +5 VDC 7 = +24 VDC 8 = RS485 Sig A 9 = do not use
Siemens S7-200 CPU Port 0 or 1
RS-485 Signal B
RS-485 Signal A
Logic
Common
RS-485A
Wiring Diagram
3
8 10
5
shield
13
11
12
Term.
9
RD+
SD+
RD–
SD–
5
1
User Constructed
To C-more Touch
Panel PLC Port
15-pin D-sub
8 = do not use 7 = do not use 6 = do not use 5 = Logic GND 4 = do not use 3 = do not use 2 = do not use 1 = Frame GND
(male)
15
1
15 = do not use 14 = do not use 13 = Termination 12 = SD– (RS485) 11 = SD+ (RS485) 10 = RD– (RS485) 9 = RD+ (RS485)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
A
a
B
B
C
C
D
D
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
6-31
Loading...