CMC Industrial Electronics mAI085MB Interface Technical Manual

Page 1
mAI085MB Actuator
Distributive Intelligence
Document No. 10856 Revision B
July 2007
1997-98-99, 2000 CMC Industrial Electronics Ltd.
Phone: (604) 421-4425 Toll-Free: (888) 421-4425 Fax: (604) 421-7734
CMC INDUSTRIAL ELECTRONICS LTD
[email protected] www.cmciel.com
Page 2
Page 3
mAI085-MB Actuator Interface Technical Manual /i
Table of Contents
1. Overview..............................................................................................................................1
2. Description of the Keypad and Indicators.............................................................................3
3. External Connections...........................................................................................................5
3.1 Power and Communications .........................................................................................6
3.2 Optional Extended Data Network..................................................................................7
4. Using the Interface...............................................................................................................9
4.1 Selecting an Actuator Controller ...................................................................................9
4.2 Changing a Setpoint .....................................................................................................9
4.3 Opening the Actuators ..................................................................................................9
4.4 Closing the Actuators....................................................................................................9
4.5 Clearing the Setpoints.................................................................................................10
5. Configuration .....................................................................................................................11
5.1 Overview of System Configuration..............................................................................11
5.2 Configuration Keyboard Functions..............................................................................14
5.3 Configuration Menus...................................................................................................15
5.3.1 Main Menu...........................................................................................................16
5.3.2 Local Menu ..........................................................................................................18
5.3.3 Actuator Controller Menu .....................................................................................18
5.3.4 Modbus Interface Menu .......................................................................................21
5.3.5 Factory Values Menu...........................................................................................22
5.3.6 Diagnostics Menu ................................................................................................23
6. The Input / Output System .................................................................................................25
7. Controlling Conveying Systems .........................................................................................27
8. Using the Modbus Network Interface .................................................................................29
8.1 The Modbus Serial Interface .......................................................................................29
8.2 Register Assignments .................................................................................................29
8.2.1 Read Only Registers............................................................................................29
8.2.2 Read-Write Registers ..........................................................................................31
8.2.3 mAI085-MB Special Registers .............................................................................31
9. Specifications.....................................................................................................................33
10. Appendix 1 - Editing Controller Setup Tables on a PC ...................................................35
10.1
Setting up HyperTerminal........................................................................................35
10.2
Downloading the Configuration to the PC................................................................37
10.3
Uploading the Configuration to the mAI085MB........................................................40
11. Appendix 2 - Drawings ...................................................................................................43
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 4
mAI085-MB Actuator Interface Technical Manual /ii
Table of Figures
Figure 1 - Keypad and Indicators ................................................................................................3
Figure 2 - Terminal Blocks and Connectors ................................................................................5
Figure 3 - Recommended Network and Power Connections .......................................................6
Figure 4 - Extended Data Network ..............................................................................................7
Figure 5 - Configuration Keypad and Indicators ........................................................................14
Figure 6 - Conveying System Timing Diagram ..........................................................................28
Revision Notes
First Release August 14, 2006
Revision A, July 2, 2007
•
Add output relay contact ratings, update specifications and port descriptions
•
Add the Diagnostics and Upload/Download menu functions
Revision B, July 20, 2007
•
Add setup details for ASCII character delays to the upload/download instructions
•
Add notes describing the controller network expansion port
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 5
mAI085-MB Actuator Interface Technical Manual /1
1. Overview
The mAI085-MB Actuator Interface is an interface between the control room operator and a network of Actuator Controllers. The interface is capable of controlling up to 100 actuators, either on a single network of up to 31 controllers or through a series of network drops utilizing RS485 repeaters. The interface allows for the pre-setting of setpoints for each of the actuators. An open key opens all of the actuators to their preset setpoints. A close key closes all of the actuators. A clear pushbutton sets all of the actuator setpoints to zero (fully closed).
The interface has optional features that allow the control of a conveying system. Timers are provided which can delay the start of the actuator opening to allow a conveying system to start. A second timer allows the conveying system to purge after closing all of the actuators. Individual timers for each actuator allow for the distance between conveying system entry points. The interface will open and close each actuator in sequence to provide superior blending.
The interface communicates to the actuator controllers using the Modbus RS485 RTU protocol.
A Modbus RS232 RTU communications interface is provided for connection to a host computer or PLC. The status information from all 100 actuators is available to the host computer or PLC over this Modbus network. In addition, the interfaces front panel operators and enunciators are mimicked over this network.
To facilitate configuration of the interface and the attached actuators a menu driven setup system is provided. A table of parameters is saved for each actuator. The system allows the retrieval and downloading of actuator parameters individually or for the entire network. A facility is provided to backup the configuration to a TAB delimited file suitable for editing using Excel.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 6
mAI085-MB Actuator Interface Technical Manual /2
This page intentionally left blank
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 7
mAI085-MB Actuator Interface Technical Manual /3
2. Description of the Keypad and Indicators
NDUSTRIAL ELECTRONICS
CMC I
12
11
10
OL
IDL
POS
FLT
MOV
OPN
CLS
EMP
SCAN
1
2
3
9
8
OPEN CLOSE CLEAR SET
PV
SV
A
CTUATOR INTERFACE
67
4
5
Figure 1 - Keypad and Indicators
ID Label Description of Operation
1 Upper Display Displays the name of the selected actuator.
2 Upper UP / DOWN Selects which actuator to view.
3 Lower Display Displays the process value or setpoint of the selected actuator.
4
Setpoint Value
Displaying the actuator setpoint
5 Lower UP /DOWN First press displays the setpoint of the selected actuator and each
subsequent press increases or decreases the setpoint value.
6 Set key
Saves the displayed setpoint only when SV is illuminated
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 8
mAI085-MB Actuator Interface Technical Manual /4
ID Label Description of Operation
7 Clear key and
lamp
8 Open / Close keys
and indicators
9
Process Value
10 Status Indicators
11 Fault Indicators
Clears all actuator setpoints. First press illuminates the lamp, the second press clears the setpoints and turns off the lamp. The lamp will turn off automatically after 10 seconds if the key is not pressed the second time and the setpoints will not be cleared.
If the CLEAR lamp is illuminated continuously and the operator keyboard does not function, the keyboard has been locked by the Modbus interface. Pressing and holding the CLEAR key for 10 seconds will unlock the keyboard. The CLEAR lamp will extinguish when the keyboard is unlocked. The setpoints will not be cleared during this operation.
Opens or closes the actuators to their pre-set values. The indicators display which mode is active.
Displaying the actuator position
MOV - actuator is currently moving to setpoint
OPN – if configured, indicates the actuator is fully open
CLS - if configured, indicates the actuator is fully closed
EMP - if configured, indicates the bin served by the actuator is empty
OL – if configured, the actuator has faulted due to excess running current
IDL - if configured, the actuator has faulted due to excess idle current
POS – the actuator failed to reach the selected position
FLT – the actuator controller is not communicating or has a hardware
fault
12 Scan key Press once to scan through all controllers at 1 second intervals. Press
the SCAN key again to cancel scanning. Pressing the up or down actuator selection keys also cancels scanning.
Table 1 - Description of Keys and Indicators
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 9
3. External Connections
mAI085-MB Actuator Interface Technical Manual /5
1 2 3 4 9
13
V- V+SHD_L D_H
12
V- V+G
7 8
65
10
11
Figure 2 - Terminal Blocks and Connectors
ID Label Description
1 Output 1 Contact will close if in open mode or to start the conveying system.
Maximum load 1A @24VDC, 0.5A@120VAC
2 Output 2 Contact will close if in close mode or to stop the conveying system.
Maximum load 1A @24VDC, 0.5A@120VAC
3 Output 3 Contact will close if all setpoints are at zero.
Maximum load 1A @24VDC, 0.5A@120VAC
4 Output 4 Contact will close if the interface has an internal fault.
Maximum load 1A @24VDC, 0.5A@120VAC
5 Inputs 1 Energizing will select open mode.
6 Inputs 2 Energizing will select close mode.
7 Inputs 3 Energizing will clear all setpoints to zero.
8 Inputs 4 Energizing will force all actuators closed without affecting open/close
mode selection. Blending timers are ignored during a force close.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 10
mAI085-MB Actuator Interface Technical Manual /6
ID Label Description
9 Input Common Common connection for inputs. Inputs accept 8-32VDC of either polarity,
maximum load is 20mA.
10 Modbus Port Modbus network port - see Appendix for connections details, wired DCE
11 Input Power
Terminal
12 Output Power and
Network Connections
13 Controller Network
Expansion
Download / Upload Port
V+ G V-
V+ D_H SH D_L V-
22 -26 VDC @ 2.0A Earth Ground VDC Common
24 VDC fused at 1.75A Data + (non inverted) Shield Data - (inverted) VDC Common
RS232 connection for repeaters or fiber-optic cable drivers for the controller network. Operates in parallel with the RS-485 port.
Port for exporting parameters to a comma delimited file - see Appendix B for port wiring details, wired DTE
Table 2 - Description of Terminals and Connections
3.1 Power and Communications
A 2 or 3 pair shielded power and communication cable is utilized. Low capacitance twisted pair cable is recommended. The cable should be sized to ensure voltage drop on the power conductor does not exceed actuator controller input voltage specifications. The mAI085-MB can accommodate up to a maximum of 31 actuator controllers. See drawing 10284 in the Appendix for complete cabling details.
To force close
dry contact if used
GREEN BLACK
RED
RED
BLACK
BLACK
WHITE
WHITE
BLACK
GREEN
SHIELD
SHIELD
2 Pair
3 Pair
Cables
Cables
WHT/BLU
SHIELD
WHT/ORG
ORG/WHT
24
5
DC Common
4321
Data -
Shield
Data +
24VDC Output
DC Common
D+SD-C
Data -
Shield
Data +
P1C
24VDC
Common
Input P1
X
mGP145-MB
Gate Positioner
BLU/WHT
WHT/BRN
BRN/WHT
WHT/GRN
GRN/WHT
654321
J2
SHIELD
WHT/ORG
X
mGP145-MB
Gate Positioner
WHT/BLU
WHT/BRN
BRN/WHT
WHT/GRN
ORG/WHT
GRN/WHT
654321
120 Ohm 1/
4W
Terminating
Resistor
BLU/WHT
J2
mAI085-MB
Actuator Interface
Figure 3 - Recommended Network and Power Connections
Distributive Intelligence
mAC185-MB
Actuator Controller
Data Cable Pairs 20ga 22ga 2 9402 8723 3 9973 8777 Belden or equiv.
CMC INDUSTRIAL ELECTRONICS LTD
Page 11
mAI085-MB Actuator Interface Technical Manual /7
3.2 Optional Extended Data Network
CMC INDUSTRIAL ELECTRONICS
OL
IDL
POS
FLT
24VDC
1.25A
4 conductor
communications
cable RS-485
MOV
OPN
CLS
EMP
OPEN CLOSE CLEAR SET
PV
SCAN
SV
ACTUATOR INTERFACE
Modbus RTU
Host Computer
or PLC
RS-232
RS-485 repeater Phoenix
Contact
2744429
Controller
91 - 100
Controller
1 - 30
RS-485
repeater
Phoenix Contact
2744429
Controller
31-60
RS-485 repeater Phoenix
Contact 2744429
Controller
61 - 90
Figure 4 - Extended Data Network
The interface can accommodate up to 100 actuator controllers if RS485 repeaters are used. A typical repeater is the Phoenix Contact Part No. 2744429 optical isolated repeater. Up to 30 controllers can be on a single network segment (31 for the end of line). Using repeaters, a linear network as shown above, or various forms of star or tee networks can be deployed as required. The start of a branch on either a star or tee network must always begin with a repeater.
A network expansion RS232 port is also provided. This port can connect directly to repeaters or fiber-optic cable drivers. Controllers can be connected to both the standard RS485 port and the expansion RS232 port. The port is designated J1 and is a female DB9 connector. It is wired DTE.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 12
mAI085-MB Actuator Interface Technical Manual /8
This page intentionally left blank
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 13
mAI085-MB Actuator Interface Technical Manual /9
4. Using the Interface
The controller has an easy to use keyboard for selecting and controlling the connected actuators.
4.1 Selecting an Actuator Controller
Use the upper up or down keys to select the actuator. The right keys move between the actuator one at a time. The left keys skip actuators at a time. The upper display indicates which actuator is selected. The SCAN key allows the viewing of all connected actuators at one second intervals. Pressing the SCAN key or any of the upper up/down keys can cancel scan.
4.2 Changing a Setpoint
The lower up/down keys change the setpoint for the selected actuator. The first press of any of the up or down keys switches the lower display to the setpoint mode and the SV lamp will illuminate. The right keys change the setpoint by 1. The left keys change the setpoint by 10. The setpoint will not be saved and sent to the actuator until the SET key is pressed. If the SET key is not pressed within 10 seconds, the display reverts to PV mode and the new setpoint is discarded.
…Caution…
If it is required that all the actuators respond simultaneously to the
new setpoints, then first insure that the interface is in close mode
before making any changes to the setpoints.
The command to move the actuator is only sent when a setpoint has changed or the operating mode is changed from closed to open. Pressing the SET key with the same setpoint value as the previous move will not start a move operation.
4.3 Opening the Actuators
Pressing the OPEN key opens all actuators with a setpoint above 0. The OPEN indicator light will illuminate. The STATUS display will indicate the status of the current open operation for the selected actuator.
4.4 Closing the Actuators
Pressing the CLOSE key closes all actuators to a setpoint of 0. The CLOSE indicator light will illuminate. The STATUS display will indicate the status of the current close operation for the selected actuator.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 14
mAI085-MB Actuator Interface Technical Manual /10
4.5 Clearing the Setpoints
The CLEAR key allows the clearing of all actuator setpoints. The first press of the CLEAR key illuminates the CLEAR lamp. The second press of the key clears all actuator setpoints to 0. If the key in not pressed a second time within 10 seconds, the lamp will extinguish and the setpoints will not
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 15
mAI085-MB Actuator Interface Technical Manual /11
5. Configuration
The mAI085-MB Actuator Interface is configured using a menu driven interface. The operator keyboard changes function during configuration. This section will describe the configuration of the interface. The description will first define the keyboard functions, then describe the configuration menus used.
5.1 Overview of System Configuration
Each actuator connected to the Interface has parameters that control its operation. These parameters are stored in non-volatile memory at each actuator. These parameters can be modified using the keyboard of the Interface. The Interface can also store in its internal non­volatile memory, a copy of the parameters from each actuator.
The following table defines the steps used to set the actuator parameters and calibrate each actuator controller.
Step Function Action at Interface Action at
Actuator Controller
1 Load Factory Default Values for the
Interface using the Factory Values Menu..
2
Using the Controller Menu, set the iD and adjust the parameters as required for controller 1.
3
Using the Controller Menu, Snd the adjusted parameters to controller 1.
4
From the Controller Menu, calibrate controller 1, using the CAL function.
5 Test the configuration by exercising
controller 1
All internal Interface
no action parameters are overwritten with the factory default values
Parameters for
no action actuator controller 1 are adjusted in the Interface parameter table
no action Parameters at
actuator controller 1
are overwritten with
values from the
Interface
no action Calibration
parameters are
adjusted by the
actuator controller
Open and close the gate to several
Controller will position
the gate positions including fully open and fully closed and verify the limit switch operation if used
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 16
mAI085-MB Actuator Interface Technical Manual /12
Step Function Action at Interface Action at
Actuator Controller
6
From the Controller Menu, use the GEt function to upload the calibrated parameters from controller 1.
7
From the Controller Menu, use the tPL function to set the values from controller 1 as a template
6
Using the Factory Values Menu, propagate the parameters from controller 1 to the remaining controllers within the Interface.
7
From the Main Menu, save the values using the SAv command. Performing the SAv now insures that the Interface’s parameter table will not be lost should power need to be cycled during the remaining steps. You may perform a SAv at any time during system setup.
Parameters for controller 1 in the Interface parameter table are overwritten with values from the actuator controller
Parameters for controller 1 in the Interface parameter table are stored in a temporary template register
Parameters for actuator controllers 1­100 in the Interface’s parameter table are overwritten with the values from the template
Parameters are saved to non-volatile memory in the Interface
no action
no action
no action
no action
8
From the Main Menu, use the Fnd function to locate the remaining controllers on the network. Exit calibration mode and confirm that all of the installed actuator controllers are present on the network. If installed controllers are not present, check field address settings and wiring and Fnd again until all of the controllers are found.
Distributive Intelligence
All active flags are cleared, then set for those actuator controllers located on the network; controller 1 is always set to active
CMC INDUSTRIAL ELECTRONICS LTD
no action
Page 17
mAI085-MB Actuator Interface Technical Manual /13
Step Function Action at Interface Action at
Actuator Controller
9
10.
11
12
13
From the Main Menu perform a Snd function to send the previously saved parameters to the remaining controllers.
From the Controller Menu, set the iD for each of the remaining controllers.
Using the Controller Menu, Calibrate each of the remaining controllers using the CAL function.
From the Main Menu perform a GEt function to retrieve the calibrated parameters from all of the connected actuator controllers.
From the Main Menu, save the parameters using the SAv command
no action Parameters for all
active actuator
controllers on the
network are
overwritten with
values from the
Interface
ID parameter is
no action overwritten for each actuator
no action Calibration
parameters are
adjusted by the
actuator controller
Interface parameters
no action are overwritten with the values from all active actuator controllers
Parameters are saved
no action to non-volatile memory
Once you have completed this sequence, all of the actuator controllers will be calibrated and their parameters saved in the Interface’s non-volatile memory. This allows an actuator controller to be replaced and reconfigured with the parameter values saved in the Interface by using the Snd command from the Controller Menu.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 18
mAI085-MB Actuator Interface Technical Manual /14
5.2 Configuration Keyboard Functions
To enter configuration mode, press and hold the SCAN key for 10 seconds. The upper display will show LoC, indicating entry into configuration mode.
NDUSTRIAL ELECTRONICS
CMC I
12
11
10
OL
IDL
POS
FLT
MOV
OPN
CLS
EMP
SCAN
1
2
3
9
8
OPEN CLOSE CLEAR SET
PV
SV
A
CTUATOR INTERFACE
67
4
5
Figure 5 - Configuration Keypad and Indicators
ID Label Description of Operation
1 Upper Display Displays the configuration menu item.
2 Upper UP / DOWN Selects the configuration menu item.
3 Lower Display Displays the configuration value. The flashing cursor indicates which
digit is being acted on.
4
Setpoint Value
Not used, off.
5 Lower UP /DOWN
Distributive Intelligence
For YES/no menu items the right up arrow key is YES and the right down arrow key is no.
CMC INDUSTRIAL ELECTRONICS LTD
Page 19
For value entries, there is a flashing cursor indicating which digit is being advanced. The left up/down arrow keys move the cursor left and right. The right up/down arrow keys increase and decrease the value.
6 Set key Not used.
7 Clear key and lamp Not used .
mAI085-MB Actuator Interface Technical Manual /15
8 Open / Close keys
Not used.
and indicators
9
Process Value
Not used, off.
10 Status Indicators Not used, all off.
11 Fault Indicators Not used, all off.
12 Scan key Press and hold for 10 seconds to enter configuration mode. Press to
return to last menu or from the main menu, to exit configuration mode.
5.3 Configuration Menus
There are four level of menus within the configuration system. The keyboard operation remains the same for all of the menus. Menu items are selected using the upper right arrow keys. The SCAN key is used to move back one level in the menu tree. To exit configuration the SCAN key is pressed from the Main Menu.
There are 2 typical responses to a menu item. The first is a Yes/No response. The lower right keys select YES (up arrow) and no (down arrow). The second is to modify the value displayed by the menu item. The lower arrow keys serve 2 functions when modifying values. The left arrow keys positions the flashing cursor to the digit to be modified. The right arrow keys increase or decrease the value.
Any changes made to the selected items are immediate. The interface has non-volatile storage for the system parameters. A modification to the parameters using the menus does not update this non-volatile storage directly. Be sure to backup any changes using the SAv function from the Main Menu before removing power from the interface. Each time power is cycled, the interface restores the saved values from non-volatile memory. Any changes made will be lost if power is cycled before a SAv operation has been completed.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 20
mAI085-MB Actuator Interface Technical Manual /16
5.3.1 Main Menu
The Main Menu allows the selection of several sub-menus and selection of the global parameter functions. All Main Menu items require YES/no responses.
Display Function Response
LoC
CtL
bUs
FAC
SAv
rCL
Go to the local interface parameters menu.
Go to the configure actuator controllers menu.
Go to the configure ModBus RS232 interface menu.
Go to the reset factory values Menu
Save the current configuration to non-volatile storage. A YES response will display SUrE in the lower display. A second YES response will save all parameters to non-volatile storage. The lower display will indicate the progress of the operation. When the operation is completed successfully, the lower display will show donE. Should the operation not complete successfully the lower display will show FAiL. If the operation fails, repeat the save. Should repeated attempts to save the parameters fail, the non-volatile storage is damaged and the unit should be replaced.
Recall the last saved configuration from non-volatile storage. This operation is done automatically during normal startup of the interface. The last saved configuration can be recalled by answering YES to this item. A YES response to the SUrE display will restore all interface parameters from non-volatile storage.
***************************** WARNING ********************************
YES/no
YES/no
YES/no
YES/no
YES/no
YES/no
This function will overwrite the current Interface parameter table with the last saved table. All current adjustments to the table will be lost.
***************************************************************************.
Fnd
Find all active controllers on the network. A YES response displays SUrE in the lower display. The second YES response starts the operation. The upper display indicates the actuator controller address and the lower display the result of the query. All 100 addresses are queried (1-100). Each controller, if found, will display YES on the lower display. Unused addresses will show no. Once complete, the lower display shows DonE. The Active flag for each controller is set or cleared during this operation. Each address is tried 5 times.
GEt
Gets the operational parameters from all actuator controllers marked active. A YES response displays SUrE in the lower display. The
Distributive Intelligence
YES/no
YES/no
CMC INDUSTRIAL ELECTRONICS LTD
Page 21
mAI085-MB Actuator Interface Technical Manual /17
Display Function Response
second YES response starts the operation. The upper display indicates the controller address and the lower display the result of the query. All addresses marked active are queried. Once complete, the lower display shows DonE. Should an active actuator controller not be found, the lower display will show FAiL. Each active address is tried 5 times. If you are uncertain that a controller’s parameters have been retreived, use the GEt function within the “Configure Actuator Controllers Menu” to verify the operation.
Snd
dnL
UPL
dGn
Send the operational parameters to all active controllers on the network. A YES response displays SUrE in the lower display. The second YES response starts the operation. The upper display indicates the controller address and the lower display the result of the query. All addresses marked active are queried. Once complete, the lower display shows DonE. Should an active actuator controller not be found, the lower display will show FAiL. Each address is tried 5 times. If you are uncertain that a controller’s parameters have been sent, use the Snd function within the “Configure Actuator Controllers” Menu to verify the operation.
***************************** WARNING ********************************
This function will overwrite all of the actuator controllers locally saved parameters. This may cause unpredictable results in these field devices. Verify the parameters in the mAI085-MB are correct before executing this function.
Download the sensor data table to a PC. See Appendix A – Editing Sensor data tables on a PC.
Upload the sensor data table from a PC. See Appendix A – Editing Sensor data tables on a PC.
Go to the Modbus Slave Interface Menu.
YES/no
YES/no
YES/no
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 22
mAI085-MB Actuator Interface Technical Manual /18
5.3.2 Local Menu
The local menu allows the configuration of parameters specific to the mAI085-MB.
Display Function Response
oPn
oPL
CPL
oDL
CDL
Selects the Open/Close mode at startup. Selecting YES will start the interface with the OPEN lamp on. Selecting no will start the interface with the CLOSE lamp on. The default value is no.
Selects the open relay output pulse timing. See “Controlling Conveying Systems” for details on output pulse timing. A value of 0 disables this function. The default value is 0.
Selects the close relay output pulse timing. See “Controlling Conveying Systems” for details on output pulse timing. A value of 0 disables this function. The default value is 0.
Selects the open delay. This delay allows for a conveying system to start before beginning to open any actuators. The delay starts when the OPEN key is pressed. See “Controlling Conveying Systems” for details. A value of 0 disables this function. The default value is 0.
Selects the close delay. This delay allows for a conveying system to purge after closing all actuators. The delay starts when the last actuator has been commanded to close. See “Controlling Conveying Systems” for details. A value of 0 disables this function. The default value is 0.
YES/no
0-255
seconds
0-255
seconds
0-255
seconds
0-255
seconds
SPd
Selects the baud rate for the controller communications network.
9600, 1920
Changing the baud rate without first setting the baud rates for all of the field devices will result in lost communication to the field devices. The default setting is 19200 baud.
5.3.3 Actuator Controller Menu
The Actuator Controller Menu allows the configuration of the field actuator controller. In addition this menu allows the setup of internal parameters that affect the open/close timing of the actuator controllers. Additional menu items allow the recall and saving of the parameters from the field device on an individual controller basis.
Provision is made to create a template from a specific controller. This template can then be used to preset any additional controllers. Using the template/copy system can help speed up the configuration process.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 23
mAI085-MB Actuator Interface Technical Manual /19
9
Z
A menu selection allows the remote calibration of the field actuator controllers. This function sets the field controller into calibration mode and alerts the operator when the calibration is complete.
Before this menu can be entered, the specific controller to be configured must be selected. When entering this menu the upper display will show C 0, indicating controller address 0. Use the upper arrow keys to select the controller to be configured. Selecting YES with the lower arrow keys enters the configuration menu for the controller shown in the upper display.
Display Function Response
ACt
id
SPt
odL
CdL
Controller is active and present on the network. This flag is set automatically when the Fnd function is executed. The network can be manually configured using this menu item. The default setting is no, not on the network except for address 1, which is YES.
Selects the Identification shown in the upper display for this actuator during normal operation. The numbers 0-9 and all 26 letters of the alphabet are represented in the character table. Some character renditions are compromises due to the nature of the 7 segment display. In addition, the -,_ and blank characters are included. The default setting starts with 1 for address 1.
Sets the default setpoint for this actuator on startup. Values from 0 to full scale are permitted.
Sets the open delay time for this controller. When set, this timer delays the opening of the actuator. The delay starts after the open delay specified in the Local Menu. This timer can be used to insure accurate blending of materials occurs during conveying system startup. A value of 0 disables this function. The default value is 0.
Sets the close delay time for this controller. When set, this timer delays the closing of the actuator. The delay starts when the CLOSE key is pressed. This timer can be used to insure accurate blending of materials occurs during conveying system shutdown. A value of 0 disables this function. The default value is 0.
YES/no
0-
A-
- _ blank
0-FS
0-255
seconds
0-255
seconds
CpY
Copy the template values to this controller. The template can be loaded from any selected controller using the tPL menu item. Selecting YES copies the template values to this controller and the menu display returns to Act. This function will not operate until a template has been set.
tPL
Set the template using this controller. Selecting YES copies this controllers parameters to the template. The menu display returns to
ACt.
Distributive Intelligence
YES/no
YES/no
CMC INDUSTRIAL ELECTRONICS LTD
Page 24
mAI085-MB Actuator Interface Technical Manual /20
Display Function Response
GEt
Snd
Get the operational parameters from this controller. A YES response displays SUrE in the lower display. The second YES response starts the operation. Once complete, the lower display shows DonE. Should the controller not respond, the lower display will show FAiL..
***************************** WARNING ********************************
This function will overwrite the Interface’s saved copy of the parameters. Verify the parameters in the actuator controllers are correct before executing this function.
***************************************************************************
Send the operational parameters to this controller. A YES response displays SUrE in the lower display. The second YES response starts the operation. Once complete, the lower display shows DonE. Should the controller not respond, the lower display will show FAiL.
***************************** WARNING ********************************
This function will overwrite the actuator controllers saved parameters. This may cause unpredictable results in this field device. Verify the parameters in the mAI085-MB are correct before executing this function.
***************************************************************************
YES/no
YES/no
CAL
Place the actuator controller in calibrate mode. The actuator controllers have an automated calibration function. This function sets the primary operational parameters for the controller by exercising the actuator. A YES response displays SUrE in the lower display. The second YES response starts the operation. During the calibration sequence, the lower display shows rUn. Pressing YES will stop the calibration sequence. The lower display will show DonE when the sequence ends. If a calibration does not complete the lower display will show FAiL. It is recommended that the results of the field calibration be uploaded to the mAI085-MB using the GEt command. This will allow the verification of the controller parameters using the parameter functions of this menu. In addition, by saving the parameters in the interface, a replacement field device can be easily reprogrammed to match the replaced device using the Snd command.
***************************** WARNING *******************************
The field actuator will move during this operation. Be sure field personnel are notified and that the device is safe to operate before executing this command.
Distributive Intelligence
YES/no
CMC INDUSTRIAL ELECTRONICS LTD
Page 25
mAI085-MB Actuator Interface Technical Manual /21
Display Function Response
This function will modify the actuator controllers saved parameters. Verify that the calibration sequence completed successfully and that the actuator is operating properly before placing the field device into service. Actuator controllers that do not complete the calibration sequence revert automatically to the pre-calibration parameter table saved in the actuator controller.
***************************************************************************
OFt -
CSP
Allows the adjustment of the field parameters of the actuator controllers. The descriptions of these parameters are listing in the Technical Manual for the mAC/GP1X5-MB actuator controllers and gate positioners. Refer to the mAC/GP1X5-MB Technical Manual for further information.
See
mAC/GP1X5
-MB
Technical
Manual
5.3.4 Modbus Interface Menu
The Actuator Interface allow remote operation and monitoring over a Modbus network. Modbus is an industry standard network protocol for connecting PLC and field devices. The Actuator Controller is a Modbus Slave device and only utilizes the RTU protocol. See “Using the Modbus Network Interface” for further information.
Display Function Response
Adr
SPd
Par
Selects the Modbus slave address. The default address is 1.
Sets the baud rate of the Modbus serial port. The default baud rate is 9600 baud.
Selects whether parity is active on the serial port. The default is no parity.
1-125
300,600, 1200,2400, 4800,9600,
1920
YES/no
Odd
Select the type of parity, even or odd. A YES response selects odd parity, a no response selects even parity. The default is even parity if parity has been enabled.
Prt
Port Reset Timer; should the Modbus port become disabled due to electrical disturbance. This timer will automatically restart the Modbus Slave port; the timer will reset the port at the entered interval (in seconds) if no valid Modbus messages are received. A setting of 0 disables this function.
Distributive Intelligence
YES/no
0-255
CMC INDUSTRIAL ELECTRONICS LTD
Page 26
mAI085-MB Actuator Interface Technical Manual /22
5.3.5 Factory Values Menu
The Interface can be configured to a range of factory preset values. The menu items allow the selection of the actuator controller model, speed of actuator operation and actuator accuracy. When the save function from this menu is executed all of the controller ID’s will be reset to A1 – A100 and all of the controllers except controller 1 will be made inactive.
If no selections are made for tyP, SPd or ACC then the values from controller 1 will be used as defaults. If a SAv is executed without tyP, SPd or ACC being set, the settings for controller 1 will be propagated to all of the remaining controllers, the controller ID’s will be reset to A1 – A100 and all of the controllers except controller 1 will be made inactive.
There are two ways to execute a factory reload. The first is to utilize a preset factory table. This table contains known working values for all of the parameters suitable for most installations. To select the correct tables for the actuator controller you are using, first use tyP, SPd and ACC to select the model of your controller, the running speed of the actuator and the required position accuracy. The required configuration can then be saved using the Sav function.
The second method of saving default values uses a template that can be preset with a modified set of values based on an individual actuator controller. To use this function, first setup and test an individual actuator controller. Once the operation of this controller has been verified use the template function (tPL) in the controller menu (CtL) to load the parameter template buffer. To save this template buffer to all of the remaining controllers, do not select a type, speed or accuracy, instead proceed directly to Sav function. Once select this function will save the template parameter values to the Interface’s parameter table for all100 controllers.
Note these tables are not automatically sent to the actuator controllers. Use the global Snd command to move the Interface’s parameter table to the active controllers.
Display Function Response
tyP
Selects the model of actuator controller connected to the interface
185,165
145,125, nonE
SPd
Sets the full stroke speed of the actuator in seconds. Use the first
10,30,60, none
value that is longer than your actuators full movement speed.
ACC
Select the position accuracy required.
SAv Selecting YES will load the selected values to all 100 controller
0-10
YES/no
parameter storage locations. Note that the new values are not automatically downloaded to the networked actuator controllers. Use the Snd command to send the parameters to the actuator controllers.
***************************** WARNING *******************************
All existing values will be overwritten and are not recoverable ***************************************************************************
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 27
mAI085-MB Actuator Interface Technical Manual /23
5.3.6 Diagnostics Menu
The mTI085 has a built in diagnostics system. This menu allows for the diagnosis of the input ports, communications ports and keyboard. Test connectors are required to test the communications port. Press the SETUP key to exit any of the diagnostic tests.
Display Function Response
io
tP1
tP2
kYb
Tests the supervisory inputs and outputs. Once selected, energizing a supervisory input will close the corresponding supervisory output, i.e. energizing input closes output 1.
Test communications port 1. A loopback test connector that connects pins 2 to 3 and pins 7 to 8 is required. If the test returns a 1 or 2 response, the RTS/CTS signals are not functioning. If the response is 10 – 27 the unit is unable to send or receive characters.
Test communications port 2. A loopback test connector that connects pins 2 to 3 and pins 7 to 8 is required. If the test returns a 1 or 2 response, the RTS/CTS signals are not functioning. If the response is 10 – 27 the unit is unable to send or receive characters.
Once selected, each press of a keyboard key will return a numeric code. Pressing the SETUP key exits the test and does not display a code.
rUn
Error
message,
GOOd or
bAd
Error
message,
GOOd or
bAd
n/a
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 28
mAI085-MB Actuator Interface Technical Manual /24
This page intentionally left blank
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 29
mAI085-MB Actuator Interface Technical Manual /25
6. The Input / Output System
The mAI085-MB Actuator Interface has 4 discrete inputs and 4 discrete outputs. Figure 2 and Table 2 detail the physical connections to the discrete signals. Each of the signals is described below:
Name Description
Input 1 Pin 1
Input 2 Pin 2
Input 3 Pin 3
Input 4 Pin 4
Output 1 Pins 1 & 2
Energizing this input will select Open mode and turn on the OPEN indicator on the front panel. Only the positive edge of the input signal is recognized and the input must be de-energized between operations. Once energized, this input does not affect front panel operator function.
Energizing this input will select Close mode and turn on the CLOSE indicator on the front panel. Only the positive edge of the input signal is recognized and the input must be de-energized between operations. Once energized, this input does not affect front panel operator function.
Energizing this input will clear all of the actuators setpoints. The clear will occur immediately. Only the positive edge of the input signal is recognized and the input must be de-energized between operations. Once energized, this input does not affect front panel operator function.
Energizing this input forces all of the actuators closed immediately. The actuators will remain closed regardless of the controller being in Open mode. Open/Close mode is not affected by this input and the actuators will re-open when this input is de-energized if the interface is in Open mode. Open/Close timers are ignored by this input and the force close will override any timing function in progress.
This output can have 2 functions depending on the setting of the oPL timer. If the oPL timer is set to 0, this output will energize whenever the interface is in Open mode. The output remains energized until the mode is changed to Close. If a value has been entered into the oPL timer, this output will energize for the length of time set by the oPL time, each time the Open mode is selected. This form of operation can be used as a start signal for a conveying system.
Output 2 Pins 3 & 4
This output can have several functions depending on the setting of the cPL and cDL timers. If the cPL timer is set to 0, this output will energize whenever the interface is in Close mode. The output remains energized until the mode is changed to Open. If a value has been entered into the cPL timer, this output will energize for the length of time set by the cPL time, each time the Close mode is selected. This form of operation can be used as a stop signal for a conveying system. The energizing of this output will be delayed if a value other than 0 is set in the oDL timer. The oDL timer can be used to purge a conveying system after all of the actuator gates have been closed using the Close mode.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 30
Name Description
mAI085-MB Actuator Interface Technical Manual /26
Output 3 Pins 5 & 6
Output 4 Pins 7 & 8
This output will be energized any time all of the actuator setpoints are 0. The output de-energizes whenever a non-zero setpoint is entered into any of the actuators.
This output is energized whenever an internal fault is detected in the mAI085-MB Actuator Interface. Possible faults are invalid parameter table (checksum verification failed during startup), corrupted firmware or damaged hardware.
***************************** WARNING ********************************************
Operation of the mAI085-MB Actuator Interface may be unpredictable when this contact is energized.
*****************************************************************************************
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 31
mAI085-MB Actuator Interface Technical Manual /27
7. Controlling Conveying Systems
The mAI085-MB Actuator Interface allows the direct control of simple conveying systems. The interface has several timers that facilitate this control. These timers in conjunction with the discrete output system control the conveying system. The following timers are used:
ID Description Menu
oPL
cPL
odL
cdL
odL
Provides a pulsed output from Output 1 to start a conveying system. If this value is set to 0, Output 1 will remain on continuously whenever the OPEN lamp is on. If a value is set in this timer the output will pulse on for the time selected in seconds each time the OPEN lamp turns on.
Provides a pulsed output from Output 2 to stop a conveying system. If this value is set to 0, Output 2 will remain on continuously whenever the CLOSE lamp is on. If a value is set in this timer the output will pulse on for the time selected in seconds each time the CLOSE lamp turns on. The operation of the output will be delayed if a value is entered into the cdL timer.
Delays the opening of the actuators to allow the conveying system to fully start. Output 1 will energize (or pulse if oPL is set) immediately upon the OPEN lamp illuminating. The actuators will begin to open after this delay in seconds. This timer starts immediately upon entering Open mode.
Delays the stopping of the conveying system until all of the gates are closed and the system has been purged. This timer starts after the CLOSE lamp illuminates and all of the gates have been issued close commands. Once this timer expires, Output 2 will energize (or pulse if cPL is set).
This timer allows for the different location of each actuator along a conveying system. Actuators near the start of the conveying system must open first, with each successive actuator opening a short time latter. This ensures an accurate blend of the material. Each actuator has a timer that delays the opening after the primary delay odL has expired.
LoC
LoC
LoC
LoC
CtL
cdL
This timer allows for the different location of each actuator along a conveying system. Actuators near the start of the conveying system must close first, with each successive actuator closing a short time latter. This ensures an accurate blend of the material. Each actuator has a timer that delays the closing when the interface enters Close mode.
Distributive Intelligence
CtL
CMC INDUSTRIAL ELECTRONICS LTD
Page 32
mAI085-MB Actuator Interface Technical Manual /28
Figure 6 details a typical start/stop sequence for a conveying system.
Open lamp
Close Lamp
Output 1
Output 2
Actuator 1
Actuator 2
Acutator 3
Enters Open mode
oPL Timer expires
oDL Timer expires
Actuator 1 oDL Timer expires
Actuator 2 oDL Timer expires
Actuator 3 oDL Timer expires
Enters Closed mode
Actuator 1 cDL Timer expires
Actuator 2 cDL Timer expires
Actuator 3 cDL Timer expires
cDL Timer expires
cPL Timer expires
Figure 6 - Conveying System Timing Diagram
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 33
mAI085-MB Actuator Interface Technical Manual /29
8. Using the Modbus Network Interface
The mAI085-MB incorporates a RTU Slave Mobus interface. This interface responds to only 3 Modbus slave commands. The commands are 3 - Read Holding Registers, 6 - Write One Holding Register and 16 - Write Multiple Holding Registers. The Modbus protocol allows a maximum of 125 Register Reads and 100 Register Writes in a single transaction. The following tables provide the register assignments for the Modbus interface. The command register within the interface mimics the operation of the front panel keys and discrete inputs.
8.1 The Modbus Serial Interface
The physical connection is by a RS-232 port. The unit has a DB9 female connector, wired as a DCE device. A modem or pin to pin cable can be used to connect the unit to a standard DTE port. The connector pin-out is:
Pin Function at DTE device
1 DCD - always +9VDC 2 TX - data from mAI085-MB 3 RX - data to the mAI085-MB 4 DTR - not used 5 Common 6 DSR - always +9VDC 7 RTS - not used 8 CTS - always +9VDC 9 RI - not used
The unit supports 8 bit, even, odd or no parity in RTU mode. A full range of baud rates from 300 -19200 are supported.
8.2 Register Assignments
8.2.1 Read Only Registers
Two registers are assigned to each addressed controller. The mAI085-MB can address up to 100 controllers, starting from address 1 to address 100. Each addressed controller corresponds to the following register table:
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 34
mAI085-MB Actuator Interface Technical Manual /30
Register Function
40002 Controller 1 Process value 40003 Controller 1 Status 40004 Controller 2 Process value 40005 Controller 2 Status 40006 Controller 3 Process value 40007 Controller 3 Status ~ ~ 40200 Controller 100 Process value 40201 Controller 100 Status
The controller process value is a 12 bit unsigned integer. The process value will occupy bits 0 ­11 of the process value word. The factory set range of the process value will be from 0 - 100, signifying 0 - 100%. The controller status word definition is as follows:
Bit Function
0 Input 1 (Force Close) , 1 = input lamp off 1 Input 2 (Closed Limit) , 1 = input lamp off 2 Input 3 (Open Limit) , 1 = input lamp off 3 Input 4 (not assigned), 1 = input lamp off 4 Seek in progress, 1 = seeking 5 Motor running, 1 = running 6 Motor direction, 1 = close 7 not used, always 0 8 Position fault, 1 = did not reach position 9 Over fault, always 0, not implement in mGP145 10 Idle Load fault, always 0 not implement in mGP145 11 Parameter fault, 1 = parameters corrupted 12 Firmware fault, 1 = controller failed 13 Bad command, 1 = last command invalid 14 Calibration mode, 1 = in calibration mode 15 Communications fault, 1 = no communications
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 35
mAI085-MB Actuator Interface Technical Manual /31
8.2.2 Read-Write Registers
Each controller has one register for the setpoint value. The setpoint value will occupy bits 0 ­11 of the setpoint value word. The factory set range of the setpoint value will be from 0 - 100, signifying 0 - 100%. Writing a setpoint to the setpoint register will cause the actuator controller to immediately position the actuator. The value in the setpoint register must change to initiate a move. If the actuator faulted in the last attempted move, a different setpoint value will have to be written to force a new move. The actuator will only move if the interface OPEN indicator is on. Open mode can be selected by pressing the OPEN key. The interface can be configured to start in open mode from the local menu and open mode can be forced over the Modbus communications system through the interface command register.
Register Function
40301 Controller 1 setpoint 40302 Controller 2 setpoint 40303 Controller 3 setpoint ~ ~ 40400 Controller 100 setpoint
8.2.3 mAI085-MB Special Registers
In addition, two special registers have been assigned. These registers are for controlling the mAI085-MB Actuator Interface. The function of these registers is as follows:
Register R or R/W Function
40001 R mAI085-MB status 40300 R/W mAI085-MB commands
The mAI085-MB status register bit assignments are:
Bit Function
0 mAI085-MB input 1, 0 = input open 1 mAI085-MB input 2, 0 = input open 2 mAI085-MB input 3, 0 = input open 3 mAI085-MB input 4, 0 = input open 4 mAI085-MB output 1, 0 = output off 5 mAI085-MB output 2, 0 = output off 6 mAI085-MB output 3, 0 = output off
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 36
mAI085-MB Actuator Interface Technical Manual /32
7 mAI085-MB output 4, 0 = output off 8 in open mode, 1 = yes 9 setpoints all cleared, 1 = yes 10 local keyboard disabled, 1 = yes 11 always 0 12 RAM fault, 1 = yes 13 mAI085-MB parameter corruption, 1 = yes 14 mAI085-MB firmware fault, 1 = yes 15 mAI085-MB in calibration, 1 = yes
There are 4 command bits to control the interface. These command bits are active only on the 0 to 1 transition. The bit must be returned to 0 before the command will execute again. Each of the bits acts independently. The mAI085-MB command register bit assignments are:
Bit Function 0 mAI085-MB to close mode, 1 = yes 1 mAI085-MB to open mode, 1 = yes 2 mAI085-MB, clear all setpoints, 1 = yes 3 mAI085-MB disable local keyboard, 1 = yes 4 mAI085-MB enable local keyboard, 1 = yes 5 not used, always write 0 6 not used, always write 0 7 not used, always write 0 8 not used, always write 0 9 not used, always write 0 10 not used, always write 0 11 not used, always write 0 12 not used, always write 0 13 not used, always write 0 14 not used, always write 0 15 not used, always write 0
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 37
9. Specifications
Description Characteristic
mAI085-MB Actuator Interface Technical Manual /33
DC Supply
Voltage
Current
Supervisory Inputs
Voltage
Current
Supervisory Contacts
Voltage
Current
Actuator Controller DC Supply
Voltage
Current
Actuator Controller Communications
Standard
Distance
Input Load
Termination
Auxiliary Communications Ports
Modbus RTU Port
Download/Upload and Controller Network Expansion port
20 - 28VDC
2.0 @ 24VDC
24VDC
20mA
32VDC, 120VAC
1.0A @ 24VDC, 0.5A @ 120VAC Resistive
20 - 28VDC
1.5A @ 24VDC
RS485 differential
500m (1640ft.)
12kΩ, standard
120Ω balanced line
RS-232C, DB9S connector, wired DCE
RS-232C, DB9P connector, wired DTE
Environment
Temperature
Relative Humidity
Dimensions
Height
Width
Depth
Distributive Intelligence
-40 to 70°C (-40 to 158°F)
0 to 95% non-condensing
90mm (3.55”)
90mm (3.55”)
127mm (5.0”)
CMC INDUSTRIAL ELECTRONICS LTD
Page 38
mAI085-MB Actuator Interface Technical Manual /34
This page intentionally left blank
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 39
mAI085-MB Actuator Interface Technical Manual /35
10. Appendix 1 - Editing Controller Setup Tables on a PC
The mAI085 can download and upload the field actuator controller setup tables to a PC over a standard serial port. Using software supplied as part of the Windows operating system and spreadsheet software, such as Excel, the configuration tables can be conveniently edited and sorted. The download (dnl) and upload (UPL) functions are accessed from the main menu. See Section 5 – Setup for details on selecting these functions. Before starting these functions you will need the following:
1. A PC running Windows software;
2. A null-modem serial cable with a 9 pin female connector on both ends;
3. A communication software package, such as HyperTerminal that is supplied with most Windows OS distributions.
The following instructions assume you are using HyperTerminal for communications and Excel for editing:
10.1 Setting up HyperTerminal
1. Open HyperTerminal;
2. Enter the name Direct for the connection name as below then click OK;
3. Select the communications port you are using and then click OK;
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 40
mAI085-MB Actuator Interface Technical Manual /36
4. Set the communications port settings as shown and then click OK. The settings are Bits per second - 9600, Data bits - 8, Parity - None, Stop bits -1, Flow control ­None;
5. On some computers it may be necessary to add a short delay to each transmitted character when uploading configurations to the mTI085. From the File menu in HyperTerminal, select Properties. On the next screen select the Settings tab. On the next screen click the ASCII Setup button. Set the Character delay field to 2 milliseconds and then click OK;
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 41
mAI085-MB Actuator Interface Technical Manual /37
6. You will now be at the main HyperTerminal Screen. Select File and then Save and the screen below will appear. Click Save to save this configuration as Direct.ht. You can now open HyperTerminal from the Direct Icon anytime you require this connection.
You are now ready to download the configuration file.
10.2 Downloading the Configuration to the PC
1. Select dnL from the Main Menu;
2. From HyperTerminals menu, click on Transfer and then Capture Text. Enter the path and file name where you want to store the configuration file as shown below. Note HyperTerminal appends data to existing files. You must delete the file each time you do a download or use a different file name. When you have completed entering the name, click Start;
3. On the mTI085 press YES and the YES again to the SurE prompt. The mTI085 will begin dumping the configuration file to HyperTerminal. When the transfer is complete, the mAI085MB will show donE and your PC screen will appear as:
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 42
mAI085-MB Actuator Interface Technical Manual /38
4. From the HyperTerminal menu, select Transfer and then Capture Text, then Stop. You have now created a “.txt” file containing the configuration data.
5. Open Excel and select File and then Open. You will have to change the type of file to open in the highlighted dialog box as shown below. You want to open files of type “.txt”. Once you have selected file type “.txt”, select your data file and then click Open.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 43
mAI085-MB Actuator Interface Technical Manual /39
6. Excel will display a data import dialog. The data from the mAI085MB is pre-formatted to be automatically imported into Excel. Just click Finish to import the data.
7. Adjust the width of the columns A so you can see the headings. Edit the data as required. A sample of an Excel spreadsheet is shown below. The columns correspond directly with the menu prompts from the CtL menu. There are 2 sections to the file. The first is the controller setup parameters. The second is the setting saved under the LoC menu. Do not modify the headings rows. These rows are discarded when uploaded to the mAI085MB.
Note that the mAI085MB does not verify the entries you have made. Do not change the format of the spreadsheet in anyway and do not enter field longer than the maximum allowed lengths. Always download and upload the entire controller range. The mAI085MB can be reset to factory values using the Fac option from the main menu.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 44
mAI085-MB Actuator Interface Technical Manual /40
8. When finished, save the file as a “.txt” file. Excel will prompt you to change the type of file when you save or exit, as it defaults to the “.xls” file format. Always answer to not change format of the file. The screen sample below shows a typical dialog.
Note you must click on Yes at this dialog to save your file as a “.txt” file.
10.3 Uploading the Configuration to the mAI085MB
1. To upload the file to the mTI085, select UPL from the main menu of the mAI085MB. HyperTerminal should be open and the cable connected.
2. Select Transfer and then Send Text File from the HyperTerminal menu. Select the file from the dialog box, but do not double click on the file, or click Open yet.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 45
mAI085-MB Actuator Interface Technical Manual /41
3. On the mTI085 select YES, and then YES again to the SurE prompt. The lower display will show 128. Click on Open on the HyperTerminal dialog to start the transfer. The lower display will count down as the sensor data is received.
4. When the transfer is complete. The lower display will show donE. Select Sav from the Main menu of the mAI085MB to save your uploaded data.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 46
mAI085-MB Actuator Interface Technical Manual /42
This page intentionally left blank
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 47
mAI085-MB Actuator Interface Technical Manual /43
11. Appendix 2 - Drawings
Drawings included in this appendix are:
Drawing Number Description
10283 mAI085-MB Connection details
10284 Gate Positioner Data Cable Wiring Overview
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Page 48
mAI085-MB Actuator Interface Technical Manual /44
A
J2
Modbus
TB3
Inputs
TB4
Outputs
A Change identifiers for com port J1 JULY 2/07 DMF
1
6
1 2 3 4 51 2 3 4
9
5
5
9
6 7 8
5
6
1
TB1
Power
1 2 3
5
1 2 3 4
Supply
Burnaby, BC Canada
CMC Industrial Electronics Ltd.
TB2
Data
mAI085MB Rear View
Network
REF:
D. FORST
DRAWN BY:
mAI085MB Connection Details
DO NOT SCALE
1 OF 1
10283
PAGE:
DRAWING NO: REV:
APPROVED BY:
CHECKED BY:
SEPT 23, 1999
COPYRIGHT 1999
DATE:
J1
Expansion
In Open
1
TB4 - Isolated Relay Outputs
TB1 - Power Supply
2
24VDC Common
Earth Ground
1
2
Distributive Intelligence
In Close
All Setpoints
Cleared
Fault
2 - RX Data In
3 - TX Data Out
5 - Data Common
7 - RTS Out
2 - TX Data Out
3 - RX Data In
5 - Data Common
and Download / Upload Port
3
4
5
6
7
8
24VDC, 2A Input
3
DC Common
Data -
Shield
1
2
TB2 - Data Network
3
J1 - Controller Network Expansion
Data +
24VDC Output
4
5
Set Open
1
TB3 - DC Control Inputs
J2 - Modbus Network
Set Close
Clear Setpoints
Force Closed
Input Common
2
3
4
5
CMC INDUSTRIAL ELECTRONICS LTD
Page 49
mAI085-MB Actuator Interface Technical Manual /45
Terminating
DC Common
mGP145-MB
mGP145-MB
Gate Positioner
DC Common
A
DATE APP.
4W
120 Ohm 1/
BLU/WHT
J2
WHT/BLU
DESCRIPTION
REMOVE mBA085 AND ADD mAC185-MB AUG 14/06 DMF
A
REV
GRN/WHT WHT/GRN BRN/WHT WHT/BRN ORG/WHT WHT/ORG
SHIELD
9402 8723
9973 8777
Data Cable
Pairs 20ga 22ga
Belden or equiv.
Burnaby, BC Canada
CMC Industrial Electronics Ltd.
REF:
D. FORST
Wiring Overview
DRAWN BY:
Gate Positioner Data Cable
DO NOT SCALE
1 OF 1
10284
PAGE:
DRAWING NO: REV:
APPROVED BY:
CHECKED BY:
SEPT 23, 1999
COPYRIGHT 1999
DATE:
J2
SHIELD
Gate Positioner
RED
BLACK
BLACK
GREEN
RED
BLACK
dry contact if used
Distributive Intelligence
P1
Common
24VDC
24
Data +
D+D-
Shield
Data -
3 Pair
WHITE
WHITE
Cables
BLACK
SHIELD
2 Pair
Cables
GREEN
SHIELD
24VDC Output
mAC185-MB
Actuator Controller
Data +
Shield
Data -
mAI085-MB
Actuator Interface
permissive is used.
Notes:
1. Data Wiring 2 or 3 pair shielded cable, up to 32 gates per network segment.
3. Wire colors shown are for Belden multi-pair cabling.
2. Force all closed permissive is a programmable option. Use 3 pair data cable if
CMC INDUSTRIAL ELECTRONICS LTD
Page 50
mAI085-MB Actuator Interface Technical Manual /46
This page intentionally left blank
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Loading...