CMC electronic MAI085MB User Manual

mAI085MB Actuator
Document No. 10856 Revision B
July 2007
1997-98-99, 2000 CMC Industrial Electronics Ltd.
Distributive Intelligence
Phone: (604) 421-4425 Toll-Free: (888) 421-4425 Fax: (604) 421-7734
CMC INDUSTRIAL ELECTRONICS LTD
info@cmciel.com www.cmciel.com
mAI085-MB Actuator Interface Technical Manual /i
Table of Contents
1. Overview..............................................................................................................................1
2. Description of the Keypad and Indicators.............................................................................3
3. External Connections...........................................................................................................5
3.1 Power and Communications .........................................................................................6
3.2 Optional Extended Data Network..................................................................................7
4. Using the Interface...............................................................................................................9
4.1 Selecting an Actuator Controller ...................................................................................9
4.2 Changing a Setpoint .....................................................................................................9
4.3 Opening the Actuators ..................................................................................................9
4.4 Closing the Actuators....................................................................................................9
4.5 Clearing the Setpoints.................................................................................................10
5. Configuration .....................................................................................................................11
5.1 Overview of System Configuration..............................................................................11
5.2 Configuration Keyboard Functions..............................................................................14
5.3 Configuration Menus...................................................................................................15
5.3.1 Main Menu...........................................................................................................16
5.3.2 Local Menu ..........................................................................................................18
5.3.3 Actuator Controller Menu .....................................................................................18
5.3.4 Modbus Interface Menu .......................................................................................21
5.3.5 Factory Values Menu...........................................................................................22
5.3.6 Diagnostics Menu ................................................................................................23
6. The Input / Output System .................................................................................................25
7. Controlling Conveying Systems .........................................................................................27
8. Using the Modbus Network Interface .................................................................................29
8.1 The Modbus Serial Interface .......................................................................................29
8.2 Register Assignments .................................................................................................29
8.2.1 Read Only Registers............................................................................................29
8.2.2 Read-Write Registers ..........................................................................................31
8.2.3 mAI085-MB Special Registers .............................................................................31
9. Specifications.....................................................................................................................33
10. Appendix 1 - Editing Controller Setup Tables on a PC ...................................................35
10.1
Setting up HyperTerminal........................................................................................35
10.2
Downloading the Configuration to the PC................................................................37
10.3
Uploading the Configuration to the mAI085MB........................................................40
11. Appendix 2 - Drawings ...................................................................................................43
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /ii
Table of Figures
Figure 1 - Keypad and Indicators ................................................................................................3
Figure 2 - Terminal Blocks and Connectors ................................................................................5
Figure 3 - Recommended Network and Power Connections .......................................................6
Figure 4 - Extended Data Network ..............................................................................................7
Figure 5 - Configuration Keypad and Indicators ........................................................................14
Figure 6 - Conveying System Timing Diagram ..........................................................................28
Revision Notes
First Release August 14, 2006
Revision A, July 2, 2007
Add output relay contact ratings, update specifications and port descriptions
Add the Diagnostics and Upload/Download menu functions
Revision B, July 20, 2007
Add setup details for ASCII character delays to the upload/download instructions
Add notes describing the controller network expansion port
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /1
1. Overview
The mAI085-MB Actuator Interface is an interface between the control room operator and a network of Actuator Controllers. The interface is capable of controlling up to 100 actuators, either on a single network of up to 31 controllers or through a series of network drops utilizing RS485 repeaters. The interface allows for the pre-setting of setpoints for each of the actuators. An open key opens all of the actuators to their preset setpoints. A close key closes all of the actuators. A clear pushbutton sets all of the actuator setpoints to zero (fully closed).
The interface has optional features that allow the control of a conveying system. Timers are provided which can delay the start of the actuator opening to allow a conveying system to start. A second timer allows the conveying system to purge after closing all of the actuators. Individual timers for each actuator allow for the distance between conveying system entry points. The interface will open and close each actuator in sequence to provide superior blending.
The interface communicates to the actuator controllers using the Modbus RS485 RTU protocol.
A Modbus RS232 RTU communications interface is provided for connection to a host computer or PLC. The status information from all 100 actuators is available to the host computer or PLC over this Modbus network. In addition, the interfaces front panel operators and enunciators are mimicked over this network.
To facilitate configuration of the interface and the attached actuators a menu driven setup system is provided. A table of parameters is saved for each actuator. The system allows the retrieval and downloading of actuator parameters individually or for the entire network. A facility is provided to backup the configuration to a TAB delimited file suitable for editing using Excel.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /2
This page intentionally left blank
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /3
2. Description of the Keypad and Indicators
NDUSTRIAL ELECTRONICS
CMC I
12
11
10
OL
IDL
POS
FLT
MOV
OPN
CLS
EMP
SCAN
1
2
3
9
8
OPEN CLOSE CLEAR SET
PV
SV
A
CTUATOR INTERFACE
67
4
5
Figure 1 - Keypad and Indicators
ID Label Description of Operation
1 Upper Display Displays the name of the selected actuator.
2 Upper UP / DOWN Selects which actuator to view.
3 Lower Display Displays the process value or setpoint of the selected actuator.
4
Setpoint Value
Displaying the actuator setpoint
5 Lower UP /DOWN First press displays the setpoint of the selected actuator and each
subsequent press increases or decreases the setpoint value.
6 Set key
Saves the displayed setpoint only when SV is illuminated
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /4
ID Label Description of Operation
7 Clear key and
lamp
8 Open / Close keys
and indicators
9
Process Value
10 Status Indicators
11 Fault Indicators
Clears all actuator setpoints. First press illuminates the lamp, the second press clears the setpoints and turns off the lamp. The lamp will turn off automatically after 10 seconds if the key is not pressed the second time and the setpoints will not be cleared.
If the CLEAR lamp is illuminated continuously and the operator keyboard does not function, the keyboard has been locked by the Modbus interface. Pressing and holding the CLEAR key for 10 seconds will unlock the keyboard. The CLEAR lamp will extinguish when the keyboard is unlocked. The setpoints will not be cleared during this operation.
Opens or closes the actuators to their pre-set values. The indicators display which mode is active.
Displaying the actuator position
MOV - actuator is currently moving to setpoint
OPN – if configured, indicates the actuator is fully open
CLS - if configured, indicates the actuator is fully closed
EMP - if configured, indicates the bin served by the actuator is empty
OL – if configured, the actuator has faulted due to excess running current
IDL - if configured, the actuator has faulted due to excess idle current
POS – the actuator failed to reach the selected position
FLT – the actuator controller is not communicating or has a hardware
fault
12 Scan key Press once to scan through all controllers at 1 second intervals. Press
the SCAN key again to cancel scanning. Pressing the up or down actuator selection keys also cancels scanning.
Table 1 - Description of Keys and Indicators
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
3. External Connections
mAI085-MB Actuator Interface Technical Manual /5
1 2 3 4 9
13
V- V+SHD_L D_H
12
V- V+G
7 8
65
10
11
Figure 2 - Terminal Blocks and Connectors
ID Label Description
1 Output 1 Contact will close if in open mode or to start the conveying system.
Maximum load 1A @24VDC, 0.5A@120VAC
2 Output 2 Contact will close if in close mode or to stop the conveying system.
Maximum load 1A @24VDC, 0.5A@120VAC
3 Output 3 Contact will close if all setpoints are at zero.
Maximum load 1A @24VDC, 0.5A@120VAC
4 Output 4 Contact will close if the interface has an internal fault.
Maximum load 1A @24VDC, 0.5A@120VAC
5 Inputs 1 Energizing will select open mode.
6 Inputs 2 Energizing will select close mode.
7 Inputs 3 Energizing will clear all setpoints to zero.
8 Inputs 4 Energizing will force all actuators closed without affecting open/close
mode selection. Blending timers are ignored during a force close.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /6
ID Label Description
9 Input Common Common connection for inputs. Inputs accept 8-32VDC of either polarity,
maximum load is 20mA.
10 Modbus Port Modbus network port - see Appendix for connections details, wired DCE
11 Input Power
Terminal
12 Output Power and
Network Connections
13 Controller Network
Expansion
Download / Upload Port
V+ G V-
V+ D_H SH D_L V-
22 -26 VDC @ 2.0A Earth Ground VDC Common
24 VDC fused at 1.75A Data + (non inverted) Shield Data - (inverted) VDC Common
RS232 connection for repeaters or fiber-optic cable drivers for the controller network. Operates in parallel with the RS-485 port.
Port for exporting parameters to a comma delimited file - see Appendix B for port wiring details, wired DTE
Table 2 - Description of Terminals and Connections
3.1 Power and Communications
A 2 or 3 pair shielded power and communication cable is utilized. Low capacitance twisted pair cable is recommended. The cable should be sized to ensure voltage drop on the power conductor does not exceed actuator controller input voltage specifications. The mAI085-MB can accommodate up to a maximum of 31 actuator controllers. See drawing 10284 in the Appendix for complete cabling details.
To force close
dry contact if used
GREEN BLACK
RED
RED
BLACK
BLACK
WHITE
WHITE
BLACK
GREEN
SHIELD
SHIELD
2 Pair
3 Pair
Cables
Cables
WHT/BLU
SHIELD
WHT/ORG
ORG/WHT
24
5
DC Common
4321
Data -
Shield
Data +
24VDC Output
DC Common
D+SD-C
Data -
Shield
Data +
P1C
24VDC
Common
Input P1
X
mGP145-MB
Gate Positioner
BLU/WHT
WHT/BRN
BRN/WHT
WHT/GRN
GRN/WHT
654321
J2
SHIELD
WHT/ORG
X
mGP145-MB
Gate Positioner
WHT/BLU
WHT/BRN
BRN/WHT
WHT/GRN
ORG/WHT
GRN/WHT
654321
120 Ohm 1/
4W
Terminating
Resistor
BLU/WHT
J2
Data Cable
mAI085-MB
Actuator Interface
mAC185-MB
Actuator Controller
Pairs 20ga 22ga 2 9402 8723 3 9973 8777 Belden or equiv.
Figure 3 - Recommended Network and Power Connections
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /7
3.2 Optional Extended Data Network
CMC INDUSTRIAL ELECTRONICS
OL
IDL
POS
FLT
24VDC
1.25A
4 conductor
communications
cable RS-485
MOV
OPN
CLS
EMP
OPEN CLOSE CLEAR SET
PV
SCAN
SV
ACTUATOR INTERFACE
Modbus RTU
Host Computer
or PLC
RS-232
RS-485 repeater Phoenix
Contact
2744429
Controller
91 - 100
Controller
1 - 30
RS-485
repeater
Phoenix Contact
2744429
Controller
31-60
RS-485 repeater Phoenix
Contact 2744429
Controller
61 - 90
Figure 4 - Extended Data Network
The interface can accommodate up to 100 actuator controllers if RS485 repeaters are used. A typical repeater is the Phoenix Contact Part No. 2744429 optical isolated repeater. Up to 30 controllers can be on a single network segment (31 for the end of line). Using repeaters, a linear network as shown above, or various forms of star or tee networks can be deployed as required. The start of a branch on either a star or tee network must always begin with a repeater.
A network expansion RS232 port is also provided. This port can connect directly to repeaters or fiber-optic cable drivers. Controllers can be connected to both the standard RS485 port and the expansion RS232 port. The port is designated J1 and is a female DB9 connector. It is wired DTE.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /8
This page intentionally left blank
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /9
4. Using the Interface
The controller has an easy to use keyboard for selecting and controlling the connected actuators.
4.1 Selecting an Actuator Controller
Use the upper up or down keys to select the actuator. The right keys move between the actuator one at a time. The left keys skip actuators at a time. The upper display indicates which actuator is selected. The SCAN key allows the viewing of all connected actuators at one second intervals. Pressing the SCAN key or any of the upper up/down keys can cancel scan.
4.2 Changing a Setpoint
The lower up/down keys change the setpoint for the selected actuator. The first press of any of the up or down keys switches the lower display to the setpoint mode and the SV lamp will illuminate. The right keys change the setpoint by 1. The left keys change the setpoint by 10. The setpoint will not be saved and sent to the actuator until the SET key is pressed. If the SET key is not pressed within 10 seconds, the display reverts to PV mode and the new setpoint is discarded.
…Caution…
If it is required that all the actuators respond simultaneously to the
new setpoints, then first insure that the interface is in close mode
before making any changes to the setpoints.
The command to move the actuator is only sent when a setpoint has changed or the operating mode is changed from closed to open. Pressing the SET key with the same setpoint value as the previous move will not start a move operation.
4.3 Opening the Actuators
Pressing the OPEN key opens all actuators with a setpoint above 0. The OPEN indicator light will illuminate. The STATUS display will indicate the status of the current open operation for the selected actuator.
4.4 Closing the Actuators
Pressing the CLOSE key closes all actuators to a setpoint of 0. The CLOSE indicator light will illuminate. The STATUS display will indicate the status of the current close operation for the selected actuator.
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /10
4.5 Clearing the Setpoints
The CLEAR key allows the clearing of all actuator setpoints. The first press of the CLEAR key illuminates the CLEAR lamp. The second press of the key clears all actuator setpoints to 0. If the key in not pressed a second time within 10 seconds, the lamp will extinguish and the setpoints will not
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /11
5. Configuration
The mAI085-MB Actuator Interface is configured using a menu driven interface. The operator keyboard changes function during configuration. This section will describe the configuration of the interface. The description will first define the keyboard functions, then describe the configuration menus used.
5.1 Overview of System Configuration
Each actuator connected to the Interface has parameters that control its operation. These parameters are stored in non-volatile memory at each actuator. These parameters can be modified using the keyboard of the Interface. The Interface can also store in its internal non­volatile memory, a copy of the parameters from each actuator.
The following table defines the steps used to set the actuator parameters and calibrate each actuator controller.
Step Function Action at Interface Action at
Actuator Controller
1 Load Factory Default Values for the
Interface using the Factory Values Menu..
2
Using the Controller Menu, set the iD and adjust the parameters as required for controller 1.
3
Using the Controller Menu, Snd the adjusted parameters to controller 1.
4
From the Controller Menu, calibrate controller 1, using the CAL function.
5 Test the configuration by exercising
controller 1
All internal Interface
no action parameters are overwritten with the factory default values
Parameters for
no action actuator controller 1 are adjusted in the Interface parameter table
no action Parameters at
actuator controller 1
are overwritten with
values from the
Interface
no action Calibration
parameters are
adjusted by the
actuator controller
Open and close the gate to several
Controller will position
the gate positions including fully open and fully closed and verify the limit switch operation if used
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Loading...
+ 35 hidden pages