The model number and serial number of this heater are on the data badge which is found inside the
rear case on the lower left hand side.
These numbers should be used when ordering replacement parts.
The BRITONY II Tis a balanced flue instantaneous gas fired multipoint water heater. For direct connection to the mains cold
water supply.
The BRITONY II Tdoes not require any purpose provides ventilation unless installed in a compartment. A compartment enclosing the heater requires high and low level openings communicating with outside air or the room in which the compartment is located. The free area of these openings must be :
Air from room252 cm2 (40 in2)252 cm2 (40 in2)
Air from outside126 cm
HHiigghh LLeevveell LLooww LLeevveel
2
(20 in2)126 cm2 (20 in2)
T GC N° 52 980 04
52 980 09
°
l
The installation of the heater must be in accordance with the relevant requirements of the Gas Safety Regulations, Buildings
Regulations and the Bye-laws of the local Water Under
BRITISH GAS and local authority and the relevant recommendations of the following British Standard Codes of Practice.
BS 5440
BS 5546
BS 6891Specification for installation of low pressure gas pipework of up to 28 mm
(R1) in domestic pr
Flues and air supply for gas appliances of rated imput not exceeding 60 kW (1st and 2nd family gases)
Part 1 - Flues
Part 2 - Air Supply
Code of practise for installation of gas hot water supplies for domestic purposes (2nd family gases)
emises (2nd family gas)
taking. It should also be in accordance with any relevant requirements of
Water flow rate - raised 50° C (90° F) ............................................................6 l/m - 1.32 g.p.m.
Water flow rate - raised 30° C (54° F) ............................................................10.05 l/m - 2.21 g.p.m.
Minimum water pressure...............................................................................1 Bar - 15 P.S.I.
Maximum water pressure ..............................................................................10 Bar - 150 P.S.I.
Water inlet - right hand connection.................................................................15 mm copper
Water outlet - left hand connection.................................................................15 mm copper
Gas - centre connection .................................................................................15 mm copper
3
/h - 88.1 ft3/h
Height............................................................................................................655 mm
Width .............................................................................................................395 mm
Depth.............................................................................................................253 mm
Weight............................................................................................................19 kg
Space for fixing - Top .....................................................................................65 mm
Space for fixing - Bottom ...............................................................................178 mm
Space for fixing - Sides ..................................................................................25 mm
Space for fixing - Front ..................................................................................152 mm
HOLE FOR WALL LINER
Width .............................................................................................................305 mm
Height............................................................................................................205 mm
ALL THICKNESS
W
Standar
Optional flue set.............................................................................................75 - 500 mm
The minimum water pressure is for the correct operation of the heater only. An additional allowance must be made for the resisance
of the pipework and fittings par
ft.) head.
d flue set
............................................................................................75 - 355 mm
ticularly wher
e showers and washing machines ar
e used. This should be the equivalent of 2 m (6.5
3
IInnssttaallllaattiioonn
The BRITONY II T is supplied in two cartons, on containing
he heater, the other containing the balanced flue set.
The standard flue set is suitable for walls having a thickness of
5 mm (3 in) to 355 mm (14 in). An optional flue set for wall
7
thicknesses up to 500 mm (20 in) is available to special order.
Detailed recommandations for flueing are given in BS 5440 :
1. The following notes are for general guidance only.
The heater must be installed so that the flue terminal is exposed
to the external air. The heater must not be installed so that the
terminal discharges into another room or space such as an outhouse or lean-to.
Termination should be on a clear expanse of wall, the terminal
referably being not less than 300 mm (1 ft.) away from a cor-
p
nern recess or projection.
T
DDOO NNOOT
a) within 300 mm (1 ft.) measured vertically from the bottom of
b) within 300 mm (1ft.) above adjacent ground level.
c) within 600 mm (1 ft.) of any surface facing the terminal.
d) immediately beneath eaves or a balcony.
Where the lowest part of the terminal is less than 2 m ( 6,5 ft.)
above the level of any ground, balcony, flat roof or place to
which any person has access, and which adjoints the wall in
which the terminal is situated, the terminal must be protected by
a guard of durable material. (A terminal guard is available from
QUINNELL BARRETT & QUINNELL, 071 639 1357.
The air inlet, product outlets duct or terminal of the heater must
not be closer than 50 mm (2 in) to any combustible material.
Detailed recommandations on the protection of combustible
material are given in BS 5440 : 1
PPRREEPPAARRIINNGG TTHHEE WWAALLL
The heater should be installed on a wall of flat non- combustible
material that will not reverberate. Whatever the thickness of the
wall, make a hole 305 mm (12 in) wide by 205 mm
(8 in) high. If the hole is cut accurately there is no need to line it
as the wall liner will seal of
A minimum clearance of 80 mm (3,2 in) should be left above
the top edge of the wall opening. For dimensions and clearance
see page 2 and Technical Data, page 3.
Slide the wall liner through the wall ensuring that is horizontal
and that the flanged end is flush with the face of the inside wall.
Trim to length if necessary, so that the outer end of the duct is
flush with the face of the outside wall. Make good around the
wall liner if necessary (fig. 1).
N.B. : For walls of between 75-100 mm (3-4 in), tur
liner hooks down through 90°.
install the terminal :
an openable window, air vent or any other ventilation opening.
L
f the cavity
E
.
n the wall
FFIITTTTIINNGG TTHHEE FFLLUUEE TTEERRMMIINNAAL
WWaallll LLiinneer
- For walls of 14 ins. (355 mm) or less, use only the flanged wall
liner section, measure and cut to length so that the liner extend
1/4 in. from external wall face. Cut “U” cover section to length.
- Assemble by inserting the tabs on the “U” shaped section into
t
Turn the tabs over in the direction of the lip on the cover, fit
hooks with nuts and bolts provided.
- Refit liner into hole and cement into position for a weather
proof finish.
- Ensure that the wall liner is horizontal.
- For walls of over 14 in. assemble the telescopic extension
piece in the same manner as the flanged section.
- Insert inside the flanged section and extend until it extends 1/4
in. from external wall face, mark around inside of flanged section.
- Remove liner and extension, cut off surplus from extension
leaving a minimum 2 in. overlap making sure extension does
not obscure hooks.
- Re-assemble liner and extension, seal around outside of joint
with tape supplied.
- Re-fit liner into hole.
- Cement in position for a weather-proof finish.
- Ensure that the liner is horizontal.
NN..BB.. :
hooks but fit the chains into the slots in the bend fixing brackets.
FFlluuee DDuucct
For the standard flue set the duct is telescopic and should be
ajusted to length to ensure that is fully engages with the terminal and the flue bend. The joint should be sealed with the tape
supplied.
For walls over 14 in. fit additional telescopic extension piece
(total 3 pieces) ensuring a 2 in. overlap. Seal the joint with the
r
he slots on the cover.
:
For walls 3 in. - 4 in. (75 mm - 100 mm) do not use the
t
L
Fig. 1Fig. 2Fig. 3