Clyde CKRS 05, CKRS 06, CKRS Series, CKRS 07, CKRS 09 Datasheet

...
Page 1
November 2014
Engineering Data Sheet 801/3
CKRS
Assembled cast iron boiler
Natural gas
Propane Gas
Class D oil
75 kW
to
145 kW
Contents Page
General information 2 Dimensions & data 3
Installation requirements 4 & 5 Boiler control & wiring 6 & 7
Seasonal efficiency of over 84% gives compliance with ADL2B 2013 for gas
fired boilers without the need for additional heating credits
Compact heat exchanger gives small footprint relative to output
Delivered as a ready-assembled block or can be site assembled for easy
access if preferred
Wide range of 2-stage gas and oil burners available
Page 2
Materials & boiler assembling
The boiler is supplied as standard with the cast iron sections assembled. The boiler blocks can be split and reassembled at site to special order. Each section is tested hydraulically for soundness in accordance with EN303. The insulation and steel jacket is already fitted to the boiler. The boiler control panel and burner are packed separately for fitting on site.
Site assembling should only be undertaken by Carnot or their authorised engineer. All insulating and refractory materials are included, with ceramic sealing ropes for all access doors.
Handling
Offloading, dry storing and placing of equipment in the boiler room is the responsibility of the installer.
Equipment must be dry stored and protected from frost. Cartons must not be crushed or otherwise damaged.
Commissioning
Carnot undertake commissioning of boilers.
General information
Description
CKRS cast iron sectional boilers are designed for use in either open vented or pressurised heating systems up to 6 bar working pressure with gas, oil or dual fuel burners. There are five models in the range 75 kW to 145 kW. The boiler has a pressurised combustion chamber and matched burners offered are all capable of overcoming the boiler resistance without the assistance of the chimney.
These are 3-pass boilers and comply with the efficiency requirements of ADL2: 2013 of The Building Regulations.
Application
CKRS boilers are made from Grade GG20 cast iron and conform with the requirements of EN 303. The boilers are suitable for use in LTHW heating systems with a maximum operating pressure of 6 bar and maximum temperature of 90oC.
CKRS boilers may be fired by Natural gas, LPG, Class D or Class C oil with 1 or 2-stage control.
The boiler is suitable for use in either open vented or pressurised heating systems. It is not suitable for use as a direct water heater. Where potable water is required, a matching calorifier or plate heat exchanger must be provided in the system.
Statutory requirements
CKRS boilers are CE marked and must be fired by a compatible burner certified to EN267 (oil firing) or EN676 (gas firing)
tocomplywiththeBoiler(Efficiency)Directive 1993.
The installation, assembling and commissioning of the boiler must be carried out by a qualified engineer in accordance with the instructions provided.
Gas supplies and gas burners must be installed and commissioned by a qualified person, eg. a Gas Safe registered engineer.
Commissioning charges do not include servicing during the guarantee period. This may be carried out under service contract or to specific order.
Boiler log book
A permanent record of commissioning and servicing data and measurements should be kept in the building log book. It should be kept safe and updated whenever routine or emergency work is performed on the boiler.
Guarantee
Subject to correct handling, installation and operation, all equipment is guaranteed for twelve months from the date of despatch. Boiler sections are guaranteed for a period of five years from the date of despatch.
The guarantee is not valid if the boiler is subjected to thermal stress, becomes blocked with debris and/or carbonate deposits from the system water and/or there is no documented evidence of commissioning by a competent engineer.
Fig 1 3-pass operation of boiler
FLOW
RETURN
Second pass
Third pass
EDS801/3 page2
Page 3
Dimensions and technical data
550
820
690
544
65
280
L
HO
HI
EDS801/3 page3
Dimensions
Boiler model CKRS 05 CKRS 06 CKRS 07 CKRS 08 CKRS 09
Output kW 75 93 110 127 145
No. sections 5 6 7 8 9
Overall length L mm 800 922 1044 1166 1288
Combustion chamber length mm 550 670 790 910 1030
Combustion chamber diameter mm
Boiler door thickness mm
Boiler flow connection HO
Boiler return connection HI
Flue s pigot diameter mm
Technical data
Nominal heat output (full load) ncv kW 75.6 93 110.5 127.9 145.3
Nominal heat input (full load) ncv kW 81.6 100.5 119.3 138.1 157
Ef f iciency at 100% load (ncv) % 92.6 92.5 92.6 92.6 92.5
Ef f iciency at 30% load (ncv) % 95.3 95.4 95.4 95.5 95.6
Boiler seasonal efficiency(1) % 85.4 85.4 85.4 85.5 85.6
Natural gas consumption (gcv ) m³ /h 8.4 10.4 12.4 14.3 16.3
Oil consumption class D (ncv) kg/h 6.9 8.5 10.1 11.6 13.2
Dry w eight (excludes burner) kg 289 334 381 429 474
Water volume litres 55 65 75 85 95
Flue gas mas s f low @3% oxygen m³ /h 8.4 10.4 12.3 14.2 16.2
Chimney draught Pa
Gas side resistance mbar 1.65 1.82 2.05 2.3 2.55
Flue gas temperature rise @3% oxy gen Nat gas (2) °C 166 162 159 157 154
Class D oil °C 188 181 178 176 173
Max imum w orking temperature °C
Max imum hydraulic w orking pressure bar
CE-Regis tration number
Wa ter flow rates and hydraulic resistances
Water flow rate at 11°C temp. rise l/s 1.64 2 2.39 2.77 3.15
Hydraulic res istance at 11°C temp. rise kPa 2.52 3.1 4.45 5.5 7.27
Water flow rate at 20°C temp. rise l/s 0.9 1.11 1.32 1.52 1.73
Hydraulic res istance at 20°C temp. rise kPa 0.76 1 1.56 1.9 2.23
Water flow rate at 30°C temp. rise l/s 0.6 0.74 0.88 1.02 1.15
Hydraulic res istance at 30°C temp. rise kPa 0.38 0.54 0.74 0.9 1.13
Notes: (1) Calculated from the non-domestic heating and cooling compliance guide for conf ormance w ith
ADL2A and ADL2B 2013 using the formula n
se as onal =0.81n
30%
+ 0.19n
100%
(2) BS 7190:1989
336
102
R2
R2
150 180
6
CE 1015BR0260
5
90
Page 4
Installation requirements
Boiler location (Refer Figs 2 & 3)
The location chosen for the boiler(s) must be frost free, provide for a satisfactory flue system and an adequate air supply for combustion and ventilation. Adequate access is necessary for boiler and burner servicing.
Boilers must not be installed in areas where flammable vapours are likely to be present. To avoid damage to the boilers, contamination of the combustion air by high levels of dust or halogenated hydrocarbons (eg. Solvents, spray can propellants, cleaning agents, adhesives, etc) must be avoided.
Boilers should be installed on a plinth which is at least 50mm high and is smooth and level (NB : for some burners with acoustic shrouds the plinth may need to be higher ­refer Sales Office).
An uneven plinth can inhibit freedom for expansion and contraction of the boiler during operation.
Burners
Boilers can be supplied with one or two stage Natural gas, LPG, Class D or Class C oil burners. A choice of burner makes is available.
W3
AA
W2
W1
W4
Boiler
Fig 2 - Wall clearances
Plant room layout (Refer Fig 2)
When planning the layout of the boiler room, allowance must be made for opening the boiler door, boiler assembling, boiler cleaning and maintenance. The boiler door may be hinged from the right (as illustrated) or the left. A ceiling height of at least 2.3m is recommended. Wall clearances are:
W1 - at least 700mm. W2 - burner length A + 100mm. W3 - 1000mm (in front of boiler for cleaning). W4 - 500mm minimum (behind boiler for cleaning).
Plinth dimensions (Refer Fig 3)
Plinth height - at least 50mm, smooth and level.
Fig 3 - Plinth dimensions
Fuel specification
Natural gas (GCV 38.76 MJ/m3) with a minimum gas inlet pressure according to the burner model specified.
BS2869 Class D oil (35 sec). Advice should be sought from the oil supplier regarding the storage of Class D oil.
Fuel supply pipework
Install gas or oil supply pipe(s) and service valve(s) so as to allow free access to the boiler and full opening of the furnace door without removing the burner from the boiler door (see below).
Commissioning of the gas supply pipework and components must be carried out by a qualified person, eg, a Gas Safe registered engineer. The gas meter and supply must be sited in accordance with the requirements of BS6400.
Boiler L1 mm
CKRS-05 880
CKRS-06 915
CKRS-07 1125
CKRS-08 1245
CKRS-09 1370
L1
650 min
EDS801/3 page4
Page 5
Installation requirements
Fig 5 - Electricity supply
Electrical supply (Refer Fig 5)
230Vac 1ph burners are supplied as standard. The fused supply should be taken to the control panel only. The harness and connector supplied will feed the burner.
The electricity supplies to the burner and boiler control panel must be wired in accordance with IEE Regulations. A separate supply and isolating switch is required for each boiler in the plant room.
All isolating switches and fuses must be provided by the installer. Burner start/run currents for fuse specification are available on request. Burner wiring diagrams and technical data are also available on request.
All connections between the boiler control panel and the burner are made through harnesses with matching plugs and sockets, supplied as standard.
Note: Fig 5 is only diagrammatic. Double pole switches with the required minimum separation must always be used.
Air supply
Air for ventilation and combustion must be provided for gas fired boilers in accordance with either BS 6644:2011 or IGE/UP/10. Air supply for oil fired boilers must conform to BS 5410 : Part 2.
Chimney design
The CKRS boiler is designed to operate with a pressurised combustion chamber and the chimney is not required to assist the burner in overcoming the boiler resistance. The chimney must cater for the total internal resistance of the flue system from each boiler outlet and not impose an additional load on the burner.
Water circulation (Refer Fig 4)
The flow water temperature from the boiler must reach 60°C (gas firing) or 50°C (oil firing) within 10 minutes of the boiler being brought into operation. Thereafter, water circulation should be maintained through the boiler such that the boiler flow water temperature is always above 60°C (gas firing) or 50°C (oil firing). A pump overrun facility is necessary to ensure that water circulation is maintained for at least three minutes after the boiler is switched off.
There are several ways of providing boiler protection, eg shunt pumps, primary loops, etc. A typical boiler pump and 3-port valve arrangement is shown in Fig 4a and b.
For multi-boiler systems a ‘reverse return’ pipework configuration is required to ensure equal distribution of water flow through the boilers.
Water treatment
Whenever a new boiler is connected to an existing system, the pipework must be thoroughly cleaned and flushed. Carnot recommend that a permanent means of filtration be fitted into the return pipework, such as a sludge trap, hydrocyclone or full flow duplex filters. The boiler guarantee will be invalid if waterways are blocked by debris or carbonate deposits. Long term water treatment is essential to the economic operation and life of both new and refurbished heating systems.
For full information on cleaning, flushing and protecting hot water systems, refer to BSRIA Application Guide AG 1/2001.
T
T
T
Fig 4a Multiple boilers with individual pumps
Fig 4b Alternative arrangement for boiler protection with a primary loop
Boiler
Burner
loom
Isolator & fuse
L
Control panel
Burner
N E
Single phase motor
EDS801/3 page5
Page 6
Boiler control panel and wiring
Control panel CKCR2 provides 2-stage burner control for high/low operation whilst panel CKCR1 provides 1-stage burner control for on/off, modulating or LFS operation. Thermostat TR is a 1-stage item with CKCR1 and a dual thermostat (1 and 2 stage) with CKCR2.
0/I
L1
L2
Fuse STB
L3 L4
TR
Thermometer
EDS801/3 page6
Fig 6 Boiler control panel
¬
1
2
3
4 5
6
7
8
9
10 11 12
L1
T1
à
à
EC1 (removable link)
T2
T8
T6
STB
TR
TR2
Fuse
L1
L2 L3 L4
L N N
L1
N
T1T2
S3
B4
E
T8T7
B5
T6
CKCR2 only
CKCR2 only
Burner loom stage 1
Burner loom stage 2
Fig 7 Boiler control panel wiring
Page 7
EDS801/3 page7
Boiler control panel and wiring
Key to figs 6 and 7
EC1 External Energy Control 1(eg timeclock) L1 On/off indicator lamp L2 Boiler high limit lock-out lamp (lamp is illuminated when running and goes out in lock-out condition) L3 Stage 1 run lamp L4 Stage 2 run lamp STB High limit thermostat (factory set) TR Boiler thermostat (1-stage for CKCR1 or dual operation [TR and TR2] for CKCR2)
Page 8
5 Burgesshall Drive Maidstone Kent ME17 1SH
t : 01622862746
e : info@carnotconsult.com w : carnotconsult.com
EDS 803/2
November 2014
Carnot Consult Ltd
This publication is issued subject to alteration or withdrawal without notice. The illustrations and specifications are not binding in detail. All offers and sales are subject to the Company's current terms and conditions of sale, a copy of which is available on request.
Loading...