Clorius Controls AVM 321S, AVM 322S Product Data Sheet

AVM 321S, 322S: Valve actuator
How energy efficiency is improved
Automatic adaptation to valve, optimal operator convenience, precision activation and high energy ef­ficiency with minimal operating noise
Features
For actuation of 2- and 3-way valves
• For controllers with constant output (0...10 V / 4...20 mA) or switching output (2-point or 3-point con­trol)
• BLDC motor (brushless DC) with SUT (Superior Universal Technology) electronic control unit of the third generation and electronic load-dependent cut-off
• Automatic detection of applied control signal (continuous or switching), operating display with bi-col­our LED
• Automatic adaptation to the stroke of the valve, between 10 and 20 mm
• Low operating noise
• With the built-in absolute distance measurement system, the position is always maintained in the case of power failure
• The direction of operation, characteristic (linear/equal percentage), positioning time and control sig­nal (voltage/current) can be adjusted via coding switches
• Integrated forced operation can be set via coding switches (with selectable direction of operation)
• Easy re-initialisation using a coding switch
• Crank handle for external manual adjustment with motor cut-off
• Simple assembly with valve; spindle is automatically connected after control voltage is applied
• Numerous adapters enable the unit to be fitted onto non-Clorius valves
• Electrical parallel operation of five actuators
• Parameterisation option via the BUS interface
• Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54
• Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel
• Patented drive-valve coupling
• Mounting column made of aluminium
• Fixing bracket made of cast light alloy for valve fitting with 20 mm stroke and made of plastic for valve fitting with 10 mm stroke
• Electrical connections (max. 1.5 mm²) with screw terminals
• Two break-out cable inlets for metric cable glands made of plastic M20 × 1.5
• Fitting position vertically upright to horizontal, not suspended
• Nominal thrust 1000 N
2)
Technical data
Power supply
Power supply 24 V~ ±20%, 50...60 Hz
Power supply 24 V= –10...20%
Power supply 230 V~ ±15%
Power consumption < 1.7 W, < 3.5 VA
(at nominal voltage, with movement)
Parameters
Nominal force
3)
1000 N
Operating noise
4)
< 30 dB (A) at nominal force
Response time > 200 ms
1) CSA-certified actuators on request
2) Actuating power 1000 N under nominal conditions (24 V, 25 °C ambient temperature, 50 Hz). With boundary
conditions (19.2 V~ / 28.8 V~ / 21.6 V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and positioning time, the actuating/ ten-sile force is minimised to 800 N
3) Noise level with the slowest positioning time, measuring distance 1m
Product data sheet
99.70.06-C
3.1 1/8
AVM32*S
www.cloriuscontrols.com
Temperature of medium
5)
0...100 °C
Nominal voltage 24 V~/=
Characteristic Linear/equal percentage
Control signal y
6)
0...10 V, Ri ≥ 50 kΩ
4...20 mA, Ri ≤ 50 Ω
Positional feedback y
0
0...10 V, load ≥ 5kΩ
Starting point U
0
0 or 10 V
Starting point I
0
4 or 20 mA
Control span ΔU 10 V
Control span ΔI 16 mA
Hysteresis X
sh
160 mV
0.22 mA
Ambient conditions
Operating temperature -10...55 °C
Storage and transport temperature -40...80 °C
Humidity without condensation 5...85 % rh
Standards and directives
Type of protection IP 54 (EN 60529)
Protection class III (EN 60730-1), EN 60730-2-14
CE conformity according to EMC Directive 2004/108/EC EN 610000-6-1, EN 610000-6-2,
EN 610000-6-3, EN 610000-6-4
Low-voltage directive 2006/95/EC EN 60730-1, EN 60730-2-14
(A
VM32*F110 and F120)
Over-voltage categories III
Degree of contamination II
Max. altitude 2000 m
Machine directive 2006/42/EC (according to appendix IIB)
EN ISO 12100
Overview of types
Type Nominal voltage Positioning time
(s/mm)
Nominal stroke Dimensions W x
H x D
Weight
AVM321S 24 V~/= 12 (4) 10 mm 160 × 187 × 88 1.5
AVM322S 24 V~/= 6 (4) 20 mm 160 × 241 × 88 1.6
5)
At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media tempera­ture < 0 °C appropriate accessory must be used (stuffing box heater)
6)
Positioner: also for 2- or 3-point, depending on type of connection
Product data sheet
99.70.06-C
2/8 3.1
Accessories
Type Description
1-0152285 Temperature adaptor for media temperature > 100 °C … 240 °C
1-0152313
*
4...20 mA feedback module
1-0152315
*
Constant power supply module for 85…265Vac 50/60Hz
1-0152665
Adjustable valve adaptor
for for AVM322 and Clorius Controls valves up to 20 mm stroke
1-0152675 Adjustable valve adaptor for for AVM321 and Clorius Controls valves up to 10mm stroke
Cable glands M20×1.5
www.cloriuscontrols.com
Description of operation
Depending on the type of connection (see connection diagram), the actuator can be used as a contin­uous (0...10 V or 4...20 mA), 2-point (OPEN/CLOSE) or a 3-point actuator (OPEN/STOP/CLOSE). The positioning time of the actuator can be set with the S1 switches according to the respective re­quirements. Using switch S2, the direction of operation can be changed. In the end positions (valve limit stop or when the maximum stroke is reached) or upon overload, the electronic motor cut-off (no limit switch) responds and turns off the motor. The external crank handle enables manual positional setting. After the crank handle is folded back, the actuator moves to the target position again (without initialisation). When the crank handle is folded out, the actuator remains in this position.
Intended use
This product is only suitable for the purpose intended by the manufacturer, as described in the “De­scription of operation” section. All related product regulations must also be adhered to. Changing or converting the product is not ad­missible.
Engineering and fitting notes
The concept of a brushless DC motor/electronics ensures electrical parallel operation of up to five ac­tuators of the same type. The valve is mounted directly on the actuator and fixed with screws (no further adjustments are re­quired). The actuator is connected with the valve spindle automatically. As delivered ex works, the ac­tuator spindle is in the middle position. As delivered ex works, the actuator spindle is in the middle position. Condensate, dripping water, etc. must be prevented from entering the actuator along the valve spin­dle. The housing contains two break-out cable inlets for two metric plastic cable glands M20×1.5, which are broken out automatically when the cable inlet is screwed in. If the cable resistance is > 1.5 Ω, the ground should be separated from the power supply and the sig­nal if possible. The cross-section of the power cable must be selected based on the cable length and the number of
actuators. With five parallel actuators and a cable length of 50 m, a cable cross-section of 1.5 mm
2
and a line resistance of > 1.5 Ω must be used (power consumption of the actuator × 5). According to building installation regulations, the lines must be protected from overload or short cir­cuit.
)
Note for UL and CSA applications: In the United States, the installed lines and cross-sections which are to be connected by the customer must comply with the requirements of NFP
A70 (NEC), and in Canada they must comply with the require-
ments of the standard C22.1-12 (CE Code).
The coding switches and the SLC interface for CASE Drives are accessible via an opening in the con­nection area of the actuator. Conversion and operation is possible while the actuator is energised.
Product data sheet
99.70.06-C
3.1 3/8
www.cloriuscontrols.com