High efficiency air-cooled water chiller
for outdoor installation
Installation use and maintenance manual
M09H40N12-03
11-01-2017
Page 2
Dear Customer,
We congratulate you on choosing these product.
Clivet is being working for years to offer systems able to assure the maximum
comfort for long time with high reliability, efficiency , quality and safety.
The target of the company is to offer advanced systems, that assure the best
comfort, reduce the energy con-sumption, the installation and maintenance
costs for all the life-cycle of the system.
With this manual, we want to give you information that are useful in all the
phases: from the reception, to the installation and use until the disposal so
that a system so advanced offers the best procedure of installation and use.
Best regards and have a nice reading !
CLIVET Spa
The data contained in this bulletin is not binding and may be changed by the manufacturer
without prior notice. All reproduction, even partial, is prohibited.
2
Page 3
INDEX
General
1
Reception
2
Positioning
3
Water connections
4
Electrical connections
5
Start-up
6
Control
7
Maintenance
8
Disposal
9
4
6
8
9
14
22
27
43
46
Residual risks
10
Technical information
11
47
48
3
Page 4
1 - GENERAL
1.1 MANUAL
The manual provides correct unit installation, use and
maintenance.
Pay particolar attention to:
Warning identifies particularly important operations or
information .
Prohibited operations that must not be carried out, that
compromise the operating of the equipment or may cause
damage to persons or things.
It is advisable to read it carefully so you will save time
during operations.
Follow the written indications so you will not cause
damages to things and injuries people. The preliminary
information must be read prior to carrying out any of the
following operations.
1.2 GENERAL INSTRUCTIONS
Preliminaries
The positioning, hydraulic system, refrigerating, electrics and
the channelisation of the air must be determined by the
system designer in accordance with local regulations in force.
On the unit can operate only qualified personal , as
determined by the regulations in force.
Using the unit in case of breakdown or malfunction :
voids the warranty
may compromise the safety of the machine
may increase time and repair costs.
Follow local safety regulations. .
Keep packing material out of children’s reach it may be
dangerous. .
Recycle and dispose of packing material in conformity with
local regulations. .
Risk situations
The unit has been designed and created to prevent injures to
people.
During designing it is not possible to plane and operate on all
risk situation.
Read carefully "Residual risk" section where all situation
which may cause damages to things and injuries to people
are reported.
Installation, starting, maintenance and repair required specific
knowledge; if they are carried out by inexperienced personnel,
they may cause damages to things and injuries people.
Intended use
Use the unit for cooling water or a water and glycol mix for airconditioning only, within limits defined in the technical bulletin
and on this manual..
Any use other than intended does not involve the
manufacturer in any commitment or obligation. .
Installation
Verify that the electrical line characteristics are in compliance
with data quotes on the unit serial number label.
Maitenance
Plan periodic inspection and maintenance in order to avoid or
reduce repairing costs.
Turn the machine off before any operation.
Modification
All unit modifications will end the warranty coverage and the
manufacturer responsibility. .
Breakdown/Malfuction
Disable the unit immediately in case of breakdown or
malfunction. .
Contact a constructor certified assistance service.
Use original spares parts only.
User training
The installer has to train the user on :
start-up / shutdown;
set points change;
standby mode;
maintenance;
what to do / what not to do in case of breakdown.
1.2.9 Data update
Continual product improvements may imply manual data
changes .
Visit manufacturer web site for updated data.
1.3 INDICATIONS FORTHEUSER
Keep this manual with the wiring diagram in an accessible
place for the operator.
Note the unit lable data so you can provide them at the assistance centre in case of intervention (see "Unit identification"
section).
Provide a machine notebook that allows any interventions
carried out on the machine to be noted and tracked making it
easier to suitably note the various interventions and aids the
search for any breakdowns.
In case of breakdown or malfunction:
immediately deactivate the unit .
contact a constructor certified assistance service.
use original spares parts only
Ask the installer to format on:
start-up / shutdown;
set points change;
standby mode;
maintenance;
what to do / what not to do in case of breakdown.
4
Page 5
1 - GENERAL
1.4 UNIT INDENTIFICATION
Serial number label
The serial number label is positioned on the unit and allows to
indentify all the unit features.
It has not to be removed for any reason.
It reports the regulations indications such as:
machine type, exmple:
Series WSAT XEESize 352…….802
serial number
12 characters Axxxxxxxxxxx
year of manufacture
wiring diagram number
electrical data
manufacturer logo and address .
Serial number
It identifies uniquely each machine.
It identifies specific spare parts for the machine.
Assistance request
Note data from the serial number label and write them in the
chart on side, so you will find them easily when needed.
In case of intervention you have to provide data.
Typology
Size
Serial number
Year of manufacture
Wiring diagram
1.5 ACCESSORIES
VERSIONS OPTIONS
EXC Excellence
PRM Premmium
D Partial energy recovery
R Total energy recovery
B Water low temperature
SC Acoustic configuration with compressor soundproofing
EN Extremely low noise acoustic configuration
FCD FREE-COOLING diretto (disponibile solo con opzioni:EXC)
CONFIGURATIONS
CREFP Device for consumption reduction of the external section at
variable speed (phase-cutting)
CREFB Device for consumption reduction of the external section
ECOBREEZE fans
REFRIGERANT CIRCUIT
CCCA Copper / aluminium condenser coil with acrylic lining
CCCA1 Copper / aluminium condenser coil with Energy Guard DCC
Aluminum
MHP High and low pressure gauges
OHE Limit extension kit in heating up to -10°C (W.B.)
HYDRAULIC CIRCUIT
2PM Hydropack with 2 pumps
1PUS Standard pump
1PU1SB Standard pump with emergency pump
AX00 X00-litre storage tank
AX00RPS X00-litre storage tank with primary circuit onboard
Water connections:
ABU Flush hydraulic connections
IFWX Water steel mesh strainer
SYSTEM ADMINISTRATORS
CMSC10 Serial communication module to LonWorks supervisor
CMSC8 Serial communication module to BACnet supervisor
CMSC9 Serial communication module to MODBUS supervisor
ELECTRIC CIRCUIT
RCMRX Remote control via microprocessor control
CONTA2 Energy meter
ECS ECOSHARE function for the automatic management of a
group of units
PM Phase monitor
MF2 Multi-function phase monitor
SFSTR Disposal for inrush current reduction
PFCP Power factor correction capacitors (cosfi > 0.9)
SPC2 Set point compensation with outside temperature probe
SCP4 Compensation of set point with signal 0-10 V
PSX Mains power supply (available only with options: RCMRX)
Operate in compliance with safety regulations in force .
For detailed information (dimensions, weight, technical
characteristics etc.) please refer to the “Technical information”
section.
Use single protection devices : gloves, glasses ecc. .
2.2 DELIVERY CONTROL
Before accepting the delivery you have to check:
That the unit hasn’t been damaged during transport.
Check that the materials delivered correspond with that
indicated on the transport document comparing the data
with the identification label ‘A’ positioned on the
packaging.
In case of damage or anomaly:
Write down on the transport document the damage
you found and quote this sentence: "Conditional
acceptance — clear evidence of deficiencies/
damages during transport".
Contact supplier and the carrier by fax and registered
mail with advice of receipt.
Any disputes must be made within the 8 days following the
delivery. Complaints after this period are invalid..
2.3 HANDLING
1. Verify unit weight and handling equipment lifting capacity .
2. Identify critical points during handling (disconnected
routes, flights, steps, doors)
3. Use protection to avoid the unit damaging .
4. Lifting brackets
5. Lifting beam with spacers
6. Lifting with spacer bar
7. Align the barycentre to the lifting point
8. Use all the lifting brackets (see "Technical informations -
dimensions)
9. Gradually bring the lifting belts under tension, making sure
they are positioned correctly. .
10. Before handling verify that the unit keeps its balance.
1 2
3
4
6
Page 7
2 - RICEPTION
7
5
6
2.4 STORING
Observe external packing instructions .
2.5 PACKING REMOVING
Be careful not to damage the unit.
Recycle and dispose of packing material in conformity with
local regulations.
7
Page 8
3 - POSITIONING
3.1 PRELIMINARY INFORMATION
Operate in compliance with safety regulations in force.
For detailed information (dimensions, weight, technical
characteristics etc.) please refer to the TECHNICAL
INFORMATION section.
Use single protection devices : gloves, glasses ecc.
During positioning consider these elements :
technical spaces required for the machine and system
place where the machine will be installed
electrical connections
water connections
air / aeraulic ducts
Do not considerer these elements could decrease
performances and operational life of the unit.
3.2 FUNCTIONAL SPACES
Functional spaces are designed to:
guarantee good unit operation
Carry out maintenance operations
protect authorized operators and exposed people
Respect all functional spaces indicated in the TECHNICAL
INFORMATION section.
Double all functional spaces if two or more unit are aligned.
3.3 POSITIONING
Units are designed to be installed:
EXTERNAL
in fixed positions.
Limit vibration transmission:
use antivibration devices on unit bearing/supporting
points;
install flexible joints on the hydraulic.
Installation standards:
Safe accessible position;
avoid flood-prone places;
verify unit weight and bearing point capacity;
verify that all bearing points are aligned and leveled;
install the unit raised from the ground;
consider the maximum possible snow level
A correct circulation of the air is indispensible to guarantee the
good working order of the machine.
Avoid therefore:
obstacles to the airflow;
exchange difficulties;
leaves or other foreign bodies that can obstruct the
exchange batteries;
winds that hinder or favour the airflow;
heat or pollution sources close to the unit (chimneys,
extractors etc);
stratification (cold air that stagnates at the bottom);
recirculation (expelled air that is sucked in again);
positioning below the level of the threshold, close to very
high walls, attics or in angles that could give rise to
stratification or recirculation phenomenons.
Ignoring the previous indications could:
energy efficiency decrease;
blocks due to HIGH PRESSURE (in summer) or LOW
PRESSURE (in winter).
3.4 FRESH AIRPROBE
The external probe allows to automatically change the unit
setpoint according to the external enthalpy (temperature +
humidity).
In this way is not possible to optimize the unit energy
efficiency .
In the winter operating also the defrosting times are optimized.
POSITIONING
The sensor must not be influenced by factors that can cause a
false reading (for example direct sun rays, air expelled by the
fan or other sources, contact with the unit structure or other
heat sources, accumulation of snow/ice).
Example for the positioning of the external probe:
A attic
B Underneath a terrace
C If attached to external wall provide a small roof
framework
8
Page 9
4 - WATER CONNECTIONS
4.1 PRELIMINARY INFORMATION
Selection and installation of system components must be
carry out by installer.
Following you will find some indications to integrate with what
is provided by the local regulations in force and by the good
technical laws.
4.2 COMPONENTS
CUT-OFF VALVES :
installed at inlet and outlet (both on the water technique
circuit as well as that of the hot domestic water) allow
maintenance operations without having to empty the
system .
THERMOMETERS AND MANOMETERS :
installed at entry and exit of the main elements facilitate
inspection and maintenance.
AN AIR BLEED VALVE :
installed in all of the highest points of the system allowing
the venting of the circuits air..
DRAINAGE TAPS :
installed in the lowest points of the system to allow
bleeding.
EXPANSION TANK :
It keeps a correct system pressure when the water
temperature changes. It must be dimensioned as a
function of water content.
WATER FILTER :
if not present on-board the machine, must be installed
immediately in the water input of the unit, in a position that
is easily accessible for cleaning.
The filter never should be removed, this operation
invalidates the guaranty
SUPPORTI :
The hydraulic pipes weight mustn’t burden on the unit
connections ..
FLOW SWITCH
The flow switch must be present as a component of the
system
4.4 WATER QUALITY
The water quality can be checked by qualified personnel.
Water with inadequate characteristics can cause:
pressure drop increase
energy efficiency decrease
corrosive symptom increase
Water quality: acceptable values
4.5 RISK OFFREEZE
If the unit or the relative water connections can be subject to
temperatures close to 0°C adopt measures for prevent risk of
freeze.
For example:
Mix water with ethylene glycol
Safeguard the pipes with heating cables placed under the
insulation
Empty the system in cases of long non-use and check that:
there are no closed taps present that could trap water
even after emptying
there are no low points in which water can stagnate
even after emptying; carry out any blowing required .
4.6 ANTI-FREEZE SOLUTION
4.3 OPERATION SEQUENCE
Before connecting the unit, carefully wash the system by filling
it and emptying it several times with clean water.
Ignoring this operation will lead to several filter cleaning
interventions and at worst cases can cause damages to the
exchangers and the other parts.
Execute leakage test before isolate the pipes.
To avoid heat dispersions and formation of condensate isolate
all the pipes. Leave various point of service free (wells, ventholes etc ).
Consider that the use of anti-freeze solution determines an
increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not
corrosive) and compatible with the hydraulic circuit
components (pump etc).
Keine Gemische aus unterschiedlichen Glykolarten benutzen
(z.B. Ethyl mit Propylenglykol).
9
Page 10
P
9
11
14
8
F
2
3
5
12
7
6
4
8
1
10
13
P
7
4 - WATER CONNECTIONS
4.7 RECOMMENDED CONNECTION
1. Charged system pressure switch
2. vent
3. circulating pump / pump
4. expansion tank
5. safety valve
6. flow switch
7. pressure switch / thermometer
8. filter
9. filling valve
10. antivibration joints
11. user side exchanger
12. Differential pressure switch
13. Discharge cock
14. inertial storage tank
The recovery input water must not be below 25°C, in the
event that, wrongful operations and breakages of the unit can
occur .
Water connections must be performed carefully as for the
evaporator (filter, circuit washing, etc) .
Perform all necessary interventions to avoid the RISK OF
FREEZING (tubes insulation, emptying of circuit, addition of
glycol, anti-freeze resistances) .
Water temperature can reach high temperatures (up to 100°
C), therefore:
avoid the RISK OF BURNS by adopting the
necessaryprecautions (insulation of tubes, temperature
detecting station on water if the sanitary use is foreseen,
etc).
Install safety valves and specifically dimensioned
expansion tanks in the hydraulic circuit.
4.10 OPTION CONNECTIONSFLUSHTHEUNIT
4.8 VICTAULIC CONNECTIONS
Take away the supplied connection union by acting on the
connection joint.
Weld the union to the installation pipe.
Perform the connection between the installation pipe and
the evaporator, using the joint.
Do not weld the system pipe with the connection joint
attached.
The rubber gasket might be irreparably damaged.
A - standard unit
B - Unit with ABU option
4.9 RECOVERY EXCHANGER
OPTIONAL
The unit can be equipped with exchangers to recover the
condensation heat.
The customer is responsible for the management of the
circulation pump, valves, thermostats, etc
10
Page 11
4 - WATER CONNECTIONS
4.11 HYDROPACK
OPTIONAL
PUMPING STATION
Available in the versions:
Single pump
Double pump
in this configuration one pump acts as backup of the other.
The microprocessor automatically balances the operating
hours of both the pumps and, in case of failure, the unit
signals the lockout of the pump out of use.
Hydropack with 2 pumps
the pump operating acts in parallel. Thanks to this modular
structure, the water flow-rate can be automatically reduced
if the temperature increases over the operating limit.
This device is very useful during starts-up, weekend
pauses, and after a long period of inactivity. When the
water temperature of the hydronic circuit is very high,
possible blocks for overcharging are avoided, as well as
the consequent interventions of specialized personnel for
the assisted start-up. In case of failure of one pump, the
unit continues to operate guaranteeing the 60% of the
nominal flow-rate.
INERTIAL STORAGE TANK
It is available in the standard version and in the primary/
secondary version to respond to different types of systems.
Version with one/two pumps with storage tank
Version with one/two pumps
Version with one/two pumps with 1°/2° circuit storage tank
11
Page 12
4 - WATER CONNECTIONS
Ev
Vm
V3
Fa
Bc
Bh
Ve
SL
F
VL
Wi
Wo
Ae 35 °C
15 °C
10 °C
C
100%
Ev
Vm
V3
Fa
Bc
Bh
Ve
SL
F
VL
Wi
Wo
Ae 11 °C
15 °C
10 °C
13 °C
C
50%
Ev
Vm
V3
Fa
Bc
Bh
Ve
SL
F
VL
Wi
Wo
Ae 0 °C
15 °C
10 °C
10 °C
C
0%
4.11 FREE-COOLING - OPTION
When the temperature of the fresh air is lower than the temperature of
the return water of the system, the free-cooling version lets you recover
cold from the external environment, reducing the work of the compressors all the way down to nothing.
USE OF ANTI-FREEZE SOLUTIONS
The heat carrier used in the systems that include a Free-Cooling devi-
ce require a glycol solution (usually an ethylene type). This substance
is required because the Free-Cooling units are intended to be installed
where the temperature can drop to very low levels during certain times
of the year. The percentage of glycol in the solution depends on the
low temperatures that can be expected in the place of installation.
Therefore, this parameter is at the discretion of the system designer.
Summer
cooling of the solution is ensured by the refrigerating cycle with
operation of the compressors (C) as in a traditional chiller ;
the Free-Cooling (Bh) coils are not involved.
SUMMER
Key
Ae fresh air
Bc condensino coil
Bh water coil
C scroll compressor
Ev plate evaporator
F dryer filter
Fa fan
SL liquid light
Intermediate season
The energy savings variable between 0 and 100%, based on the tem-
perature difference between fresh air and the system request.
If the unit detects that the fresh air temperature (Ae) is suitable:
1. it inverts the position of the 3-way valve (V3), forcing the
solution to travel through the Free-Cooling coils (Bh) before
reaching the evaporator (Ev);
2. it sets the fans (Fa) at maximum speed to obtain maximum
cooling of the solution from the fresh air;
3. the solution thus undergoes an initial cooling which is free and
natural;
V3 3-way valve
Ve electronic expansion
valve
VL cock on the liquid line
Vm cock on the supply line
Wi water inlet
Wo water outlet
4. the remaining cooling is provided by the refrigeration cycle,
with compressors in stepped operation (power absorbed
proportional to the degree of stepping);
If the temperature of fresh air increases, the microprocessor will automatically revert operation to summer mode, ensuring the same conditions requested by the user.
INTERMEDIATE SEASON
Winter
The three way valve (V3) is in the same position as in the previous
case;
the temperature of the fresh brings the solution at the outlet of
the Free-Cooling coils (Bh) to the temperature required for
use;
the microprocessor control completely deactivates all com-
pressors (C), providing all cooling power at no cost, as opposed to standard units;
if the difference between the temperature of the fresh air (Ae)
and that required for use is such that the temperature of the
solution at the outlet of the Free-Cooling coils (Bh) drops
below the set point required for use (which does not compromise unit safety, because of the glycol in the solution), the
microprocessor modulates fan speed (Fa), turning them off if
necessary. When the fans are off, if the temperature (Wo)
continues to drop, the 3-way valve (V3) positions itself as in
summer operation, changing to digital and allowing the set
point to be maintained.
WINTER
12
Page 13
4 - WATER CONNECTIONS
Ev
C
Vm
Fa
Bc
D
Ve
SL
F
VL
EWi
EWo
Ae 35 °C
12 °C
7 °C
RWo 45 °C
RWi 40 °C
C
Ev
C
Vm
Fa
Bc
R
Ve
SL
F
VL
EWi
EWo
Ae 35 °C
12 °C
7 °C
RWo 45 °C
RWi 40 °C
Lr
VrVc
Ev
C
Vm
Fa
Bc
R
Ve
SL
F
VL
EWi
EWo
Ae 35 °C
12 °C
7 °C
RWo 45 °C
RWi 45 °C
Lr
VrVc
C
4.12 ENERGY RECOVERY - OPTION
Partial energy recovery
The use of a desuperheater makes it possible to recover, free
of charge, the heat that would otherwise be dispersed in the
environment. The partial heat recovery is composed of shell
and tube heat exchangers suitable for recovery of 25% of the
heat power dispersed by the unit (cooling and electrical power
of the compressors). If the temperature of the water to be
heated is relatively low, it is advisable to insert in the plumbing
circuit an adjustment valve to keep the recovery inlet temperature greater than 35°C to prevent condensation.
3) Cold request 50%, hot request 100% = circuit active in
cold+recovery (in this case the unit can provide only 50% of
the requested heat).
With the recovery active the condensing coil (Bc) is deactivated and condensation takes place in the total recovery (R).
With the recovery setpoint met, the condensing coil (Bc) is
reactivated, to perform condensation, via the solenoid valves
(Vr=off and Vc=on). In this case the recovery (R) acts as a
simple desuperheater.
Key
Ae fresh air
Bc condensing coil
C compressor
D heat partial recovery
Ev evaporator
enabling
Ve electronic expansion valve
VL cock on the liquid line
Vm cock on the supply line
Vr valve for total recovery
enabling
EWi cooled water inlet
EWo cooled water outlet
F dryer filter
Fa fan
RWi partial recovery water inlet
RWo partial recovery water outlet
SL spia del liquido
Vc valve for condensing coil
Recupero energetico totale
The use of total heat recovery may be the optimal solution in
all cases that require the production of hot water for medium
In the plumbing circuit, considering the powers involved, it is
advisable to insert a storage tank with suitable capacity to
prevent constant commutations of the unit.
and large potentials. The production of hot water is always of
lesser priority than the production of chilled water. The total
heat recovery is composed of shell and tube heat exchangers
suitable for recovery of 100% of the heat power dispersed by
the unit (cooling and electrical power of the compressors). The
unit with total recovery is capable of managing the recovery
temperature with thermal adjustment integrated in the microprocessor with two steps. The adjustment of power is managed based on chilled water and may have the following instances:
1) Cold request 100%, hot request 0% = circuit active only
cold,
2) Cold request 100%, hot request 100% = circuit active in
cold + recovery,
13
Page 14
5 - ELECTRICAL CONNECTIONS
5.1 PRELIMINARY INFORMATION
The characteristics of the electrical lines must be determined
by specialized personnel able to design electrical installations;
moreover, the lines must be in conformity with regulations in
force.
The protection devices of the unit power line must be able to
stop the presumed short circuit current, whose value must be
determined in function of system features.
The power cables and the protection cable section must be
defined in accordance with the characteristics of the
protections adopted. All electrical operations should be
performed by trained personnel having the necessary
requirements by the regulations in force and being informed
about the risks relevant to these activities.
Operate in compliance with safety regulations in force .
5.2 ELECTRICAL DATA
The serial number label reports the unit specific electrical
data, included any electrical accessories .
The electrical data indicated in the technical bulletin and in the
manual refer to the standard unit, accessories excluded.
Refer to the electrical data report on the serial number label.
6. Before power the unit, make sure that all the protections
that were removed during the electrical connection work
have been restored.
5.4 SIGNALS / DATA LINES
Do not overpass the maximum power allowed, which varies,
according to the type of signal.
Lay the cables far from power cables or cables having a
different tension and that are able to emit electromagnetic
disturbances.
Do not lay the cable near devices which can generate
electromagnetic interferences.
Do not lay the cables parallel to other cables; cable crossings
are possible, only if laid at 90°.
Connect the screen to the ground, only if there aren’t
disturbances
Guarantee the continuity of the screen during the entire
extension of the cable.
Respect impendency, capacity and attenuation indications.
serial
number
label
F.L.A. full load ampere
Full load current at max admissible conditions
F.L.I. Full load input
Full load power input
( at max. admissible condition )
5.3 CONNECTIONS
1. refer to the unit electrical diagram (the number of the
diagram is shown on the serial number label)
2. verify that the network has characteristics conforming to
the data shown on the serial number label
3. Before starting work, verify that the sectioning device at
the start of the unit power line is open, blocked and equipped with cartel warning
4. Primarily you have to realize the earthing connection
5. Shelter the cables using adequate measure fairleads
VOLTAGE
FLA (A)
FLI (kW)
5.5 ELECTRIC LINESINLET
QS1 Main isolator switch
14
Page 15
5.6 ELECTRICAL PANEL
5 - ELECTRICAL CONNECTIONS
APC main control module
AP1 compressor control module
AP1.1 electronic thermostatic management board
AP6 phase monitor module
APT power player
XC Customer connections
QS1 main isolator
QM1-2 compressor thermal magnetic circuit breaker
KM1-2 compressor contactor
QMA auxiliary circuit thermal magnetic circuit breaker
QMV fan motor overload cutout
QM83-4 pump motor overload cutout
KM83-4 pump contactor
15
Page 16
5 - ELECTRICAL CONNECTIONS
5.7 CUSTOMER CONNECTIONS
SQ1 flow switch
SA1 remote on-off selector
SA5 not used
APV 0….10V analogical output
SA1.1 second setpoint enabling switch
QMP recirculation pump
HLC1-2 compressor status signal lamp
HLHE not used
KMP pump contactor
ALM cumulative fault signal
AP18 demand limit
AP19 water reset
16
Page 17
5 - ELECTRICAL CONNECTIONS
5.7 STANDARD KEYBOARD 5.8 P.C. - not supplied
RJ45 : standard connection
Spostare RJ45 da T-HI a T-IP
17
Page 18
5.9 REMOTE KEYPAD
5 - ELECTRICAL CONNECTIONS
Distance up to 350 mt
Distance up to 700 mt
A remote keypad
B = B1 KNX bus, max 350 mt
twisted pair with shield, Ø 0,8 mm
EIB/KNX cable marking recommended
C power supply unit N125/11 5WG1 125-1AB11
C1 AC 120...230 V, 50...60 Hz
Connections
18
Page 19
5 - ELECTRICAL CONNECTIONS
5.11 Ecoshare
Max 7 units
Maximum length of the bus line: 1000 m.
maximum distance between 2 units: 700 m.
Type of cable: shielded twisted pair cable Ø 0.8 mm
use an EIB/KNX cable
Possible connections:
Tree, star, in/out bus, mixed
It is not possible to use a ring connection
No end-of-line resistor or terminator required
There must be suitable arresters to protect the serial
lines from the effects of atmospheric discharges
The data line must be kept separate from the power
conductors or powered at different voltage values and
away from possible sources of electrical interference
19
Page 20
5 - ELECTRICAL CONNECTIONS
5.12 MODBUS - RS485
LED BSP communication with AP1 module
green communication ok
yellow software ok but communication with AP1 down
red flashing : software error
fixed : hardware error
LED BUS communication with MODBUS
green communication ok
yellow startup / channel not communicating
red communication down
Every RS485 serial line must be set up using the 'In/Out'
bus system. Other types of networks are not allowed,
such as Star or Ring networks
The difference in potential between the earth of the two
RS485 devices that the cable shielding needs to be
connected to must be lower than 7 V
Suitable arresters must be set up to protect the serial lines
from the effects of the atmospheric discharges
A 120 ohm resistance must be located on the end of the
serial line. Alternatively, when the last serial board is
equipped with an internal terminator, it must be enabled
using the specific jumper, dip switch or link
The cable must have insulation features and non-flame
propagation in accordance with applicable regulations
The RS485 serial line must be kept separate from the
power conductors or powered by different voltages
The RS485 serial line must be kept as far away as
possible from sources of electromagnetic interference
MODBUS Cable requirements
Conductors twisted and shielded
Section of conductor 0.22mm2…0,35mm2
Nominal capacity between conductors < 50 pF/m
nominal impedance 120 Ω
Recommended cable BELDEN 3106A
A unit
B metal conduit
C metal septums
D metal-lined sheath
(sleeve)
20
Page 21
5 - ELECTRICAL CONNECTIONS
5.13 BACNET 5.14 LONWORK
LED BSP communication with AP1 module
green communication ok
yellow software ok but communication with AP1 down
red flashing : software error
fixed : hardware error
LED BUS communication with BACNET
green ready for communication
yellow startup
red BACnet server down
restart after 3 sec.
LED BSP communication with AP1 module
green communication ok
yellow software ok but communication with AP1 down
red flashing : software error
fixed : hardware error
LED BUS communication with LONWORK
green communication ok
yellow startup
flashing: communicating not possible
red communication down
LONWORK CABLE TYPES
Echelon allows three cable types for channel type TP/FT-10,
including the
Category 5 network cable used commonly in building
automation and control (TIA
568A Cat-5).
CAT-5 SPECIFICATIONS
Unshielded cable, twisted pair with at least 18 beats per
meter:
Cross-sectional area Min. ∅ 0.5mm, AWG24, 0.22mm²
Impedance 100 Ω +/- 15 % @ f > 1 MHz
Operating capacity between two wires of a pair < 46 nF/km
Capacity pair to ground, asymmetric. < 3.3 nF/km
DC loop resistance < 168 Ω
21
Page 22
6 - START-UP
PRELIMINARY CHECKS
Checks before the unit starting-up.
√
1
2
3
4
5
6
7
Preliminary checks - unit OFF power supply
safe access
functional clearances
air flow: free return and supply
(no bypass, no stratification)
structure integrity
the fans turn freely
unit on antivibrations
unit input water filter + shut-off valves for cleaning
START-UP SEQUENCE
Operations to perform for the unit start-up.
√
1
Start-up sequence - unit ON power supply
Compressor cranckase resistances operating at
least since 8 hours
No-load voltage measure 2
Phase sequence check 3
Pump manual start-up and flow check 4
Unit ON 5
Measure of full load voltages and absorptions 6
Check of liquid light (no bubbles) 7
8
9
10
11
12
13
14
15
16
17
antivibrating joints on water connections
expansion tank
(indicative volume = 5% of system content)
cleaned system
loaded system + possible glycoled + corrosion
inhibitor
system under pressure
vented system
Refrigerant circuit visual check
earthing connection
power supply features
electrical connections by customer
Check of all fan operating 8
Return and supplì water temperature measure 9
Super-heating and sub-cooling measure 10
Check that no anomalous vibrations are present 11
Date- hour setting 12
option settings 13
Set-point personalization 14
Scheduling personalization 15
Complete and available unit documentation 16
22
Page 23
6 - START-UP
6.1 PRELIMINARY INFORMATION
The indicated operations should be done by qualified
technician with specific training on the product.
Upon request, the service centres performing the start-up; the
electrical, water connections and the other system works are
by the installer.
Agree upon in advance the star-up data with the service
centre.
6.2 PRELIMINARY CHECKS
Before checking, please verify the following :
the unit should be installed properly and in conformity with
this manual.
the electrical power supply line should be sectioned at the
beginning.
The line sectionalizing device is open, locked and equip-
ped with the suitable warning
make sure no tension is present
6.3 REFRIGERANT CIRCUIT
6.5 ELECTRICAL CIRCUIT
Verify that the unit is connected to the ground plant
Check the conductors tightening: the vibrations caused by
handling and transport might cause loosing
Feed the unit by closing the sectioning device, but leave it on
OFF.
Check the tension and line frequency values which must be
within the limits :
400/3/50 +/- 10%
Control the unbalancing of the phases:
it must be lower than 2%
Example:
1. Check carefully the refrigerating circuit: the presence of oil
stains can mean leakage caused by transportation, movements or other).
2. Verify that the refrigerating circuit is in pressure: Using the
unit manometers , if present, or service manometers.
3. Make sure that all the service outlets are closed
with proper caps; if caps are not present a leak of
refrigerant can be possible.
6.4 HYDRAULIC CIRCUIT
1. Before realizing the unit connection make sure that the
hydraulic system has been cleaned up and the clearing
water has been drained
2. Check that the water circuit has been filled and
pressurized
3. Check that the shut-off valves in the circuit are in the
"OPEN" position.
4. Check that there isn’t air in the circuit, if required,
evacuate it using the air bleed valve placed in the system
high points.
5. When using antifreeze solutions, make sure the glycol
percentage is suitable for the type of use envisaged.
The working out of the limits can cause irreversible damages
and voids the warranty.
Check with amperometric pliers the operating of the
compressor carter heating. Before proceeding with the startup, leave the unit powered with stopped compressors for
some hours.
Weight of glycol (%)
Freezing temperature (°C)
Safety temperature (°C)
10 20 30 40
-4 -9 -15 -23
-2 -7 -13 -21
23
Page 24
6 - START-UP
6.6 COMPRESSOR CRANKCASE RESISTANCES
Connect the oil resistances on the compressor crankcase at
least 8 hours before the compressor is to be starter :
at the first unit start-up
after each prolonged period of inactivity
1. Supply the resistances switching off the unit isolator
switch.
2. To make sure that hte resistances are working, check the
power input .
3. At start-up the compressor crank-case temperature on the
lower side must be higher at least of 10°C than the outside
temperature.
Do not start the compressor with the crankcase oil below
operating temperature.
6.7 VOLTAGES
Check that the air and water temperatures are included in the
operating limits. Refer to “Control” section for the indications
on the control system.
Start-up the unit.
With operating unit, i.e. in stable conditions and next to the
operating ones, check:
supply voltage
total absorption of the unit
absorption of the single electric loads
6.8 REMOTE CONTROLS
Check that the remote controls (ON-OFF etc) are
connected and, if necessary, enabled with the respective
parameters as indicated in the ELECTRICAL
CONNECTIONS section.
Check that probes and optional components are
connected and enabled with the respective parameters
(ELECTRICAL CONNECTIONS section and following
pages)
6.9 EVAPORATOR WATER FLOW-RATE
Check that the difference between the temperature of
exchanger return and supply water corresponds to power
according to this formula:
unit cooling power (kW) x 860 = Dt (°C) x flow rate (L/h).
The cooling power is shown in the table of the GENERAL
TECHNICAL DATA included in this manual, referred to
specific conditions, or in the tables on COOLING
PERFORMANCE in the TECHNICAL BULLETIN referred to
various conditions of use.
Check for water side exchanger pressure drops:
Determine the water flow rate.
Measure the difference in pressure between exchanger
input and output and compare it with the graph on WATER
SIDE EXCHANGER PRESSURE DROPS
The measurement of pressure will be easier if pressure
gauges are installed as indicated in the DIAGRAM OF
SUGGESTED WATER CONNECTIONS .
6.10 OPERATING AT REDUCED LOAD
The units are equipped with partialization steps and they can,
therefore, operate with reduced loads.
However a constant and long operation with reduced
load with frequent stop and start-up of the compressor/s can
cause serious damages for the lack of oil return.
The above-described operating conditions must be
considered OUT of standards.
In the event of compressor break, due to the operating in the
above-mentioned conditions, the guarantee WILL NOT BE VALID and Clivet spa declines any responsibility.
Check periodically the average operating times and the
frequency of the compressors starts: approximately the
minimum thermal load should be such as to need the
operating of a compressor for at least ten minutes.
If the average times are close to this limit, take the proper
corrective actions.
6.11 START-UP REPORT
Identifying the operating objective conditions is useful to
control the unit over time.
With unit at steady state, i.e. in stable and close-to-work
conditions, identify the following data :
Total voltages and absorptions with unit at full load
Absorptions of the different electric loads (compressors,
fans, pumps etc)
Temperatures and flows of the different fluids (water, air)
both in input and in output from the unit
Temperature and pressures on the characteristic points of
the refrigerating circuit (compressor discharge, liquid,
intake)
The measurements must be kept and made available during
maintenance interventions.
6.12 CE 97/23 PED DIRECTIVE
97/23 CE PED DIRECTIVE gives instructions for installers,
users and maintenance technicians as well. Refer to local
actuation norms :
Briefly and as an example, see the following :
COMPULSORY VERIFICATION OF THE FIRST
INSTALLATION:
only for units assembled on the installer’s
building site (for ex. Condensing circuit + direct
expansion unit)
CERTIFICATION OF SETTING IN SERVICE:
for all the units
PERIODICAL VERIFICATIONS:
to be executed with the frequency indicated by
the Manufacturer (see the MAINTENANCE
INSPECTIONS paragraph
24
Page 25
7 - START-UP
CLIMATICA TExt
Only if P0053: En Climatica ≠ 0
The setpoint defined by the temperature curve is shown at
status S0010: ActualSptTExt
P0265:CSptLow Set Point → AirAtSptLowC
P0266:AirAtSptLowC TEXT → SptLowC
P0267:CSptHigh Set Point → AirAtSptHigC
P0268:AirAtSptHigC TEXT → SptHigC
Eg 1:
DemandLimit
pwd
It is possible to limit the absorbed electric power with an
external signal 0-10 Vcc.
The higher the signal is, the lower the number of compressors
available to meet the thermal need .
Only if P0050:En DemandLimit ≠ 0
P0009:set demand limit
Parameter setting of the value
% of demand limit
Eg 2:
Water Reset
pwd
Only if P0051: En WaterReset ≠ 0
The water reset correction affects the setpoint defined by the
Climate curve TExt (actual setpoint).
The setpoint is shown at status S0011: ActualSptWR
P0281:MaxCWRC
Maximum correction to be applied to the
setpoint
Value of the WR control signal
P0283:SWRMaxC
corresponding to the correction of the
set COOL equal to the parameter P281
Value of the WR control signal
P0285:SWRMinC
corresponding to the correction of the
set COOL equal to 0
25
Page 26
6.13 ECOSHARE
If there are more units connected in a local network set the
mode of operation
MODE A
Every unit manages its own compressors
according to the setpoint.
Every unit optimizes its cooling circuits.
Pumps always active, even with
The master manages the single cooling.
The master optimizes individual refrigerant
circuits.
Pumps always active, even with
compressor stoped.
P0343 = 1
P0344 = 0 °C
setpoint 1 = setpoint 2 = setpoint 3
plus: optimal H2O temperature control
MODE C
The master manages the single cooling.
The master optimizes individual refrigerant
circuits.
Active pumps only with active compressors.
P0343 = 2
P0344 = 0 °C
setpoint 1 = setpoint 2 = setpoint 3
plus: minimum pumps consumption
need balanced system (t1 = t2 = t3)
1 2 3
1 2 3
1 2 3
6 - START-UP
Id Description
P0340: Address unit ProcessBus address unit
P0341: Unit network Number of network-connected units including the master
P0342: Standby unit Number of units kept in standby
P0343: TypeRegMS Operation mode : 0=mode A; 1=mode B; 2=mode C
P0344: Offset Trm MS
Temperature Offset the master sum or subtract, depending on the way you set, in order of priority,
to the set point of the slave.
26
Page 27
1/7
10.02.2012 10:15:30
SetPointAttuale 8.5°C
T.InH2OUtilizzo 10.5°C
T.OutH2OUtilizzo 12.5°C
StatoAttuale ON
ModoAttuale Cool
2 1 0 50 %
7.1 DISPLAY MEANING
7 - CONTROL
Function keys
Main menu
Alarm display
Exit
Previous level
Keyboard settings
Up
Increases value
Down
Decreases value
Confirm
Password
ActualSetPoint temperature setting
T.InH2OUtilitySide water inlet temperature utility side
T.OutH2OUtilitySide water outlet temperature utility side
ActualState On / off / eco / pmp On
ActualMode Cool : water cooling
Heat : water heating - NOT USED
7.2 COMMON OPERATIONS
ON, OFF, ECO
change MODE
change SETPOINT
2 installed compressors
3 1 - 0 Compressors ON
example : circuit 1 = 1 compr. On circuit 2 = 0 compr. On 50% required power
main menu
→ cmd local status
→ scegliere OFF - ECO ON - PUMP ON
main menu
→ cmd local mode
→ select COOL - HEAT (NOT USED)
main menu
→ unit parameters
→ setpoint
27
Page 28
7.3 MAIN MENU
7 - CONTROL
Select
Cmd Local state On
Cmd Local mode Cool
Unit stata
Unit parameters
Scheduler
Select
Confirm
Cmd Local state
Cmd Local mode
Unit Stata
Parameters Unit
Scheduler Scheduler
User settings Date and hour
Cmd Local state On
Cmd Local mode Cool
Unit stata
Unit parameters
Scheduler
OFF
ECO
ON
Pmp ON
Cool
Heat
General
Circuit
Thermostatic
Recovery
Hydronic
Master Slave
SetPoint
Language selection
Main index
Main index
not used
Circuit 1 *
Circuit 1 *
Circuit 1 *
Hydronic stata
Stati Master Slave
Local state
ECO : recurrent pump ON-OFF;
compressors keep water system at setpoint
ECO
Pmp ON : pump ON, compressors OFF
Unit Stata
Input, output functioning variables.
See next pages tables
* Circuits number dipend on unit's series .
The menu is repeated for each refrigerant circuit (circuit:
P0001:SetPoint Cool - Cooling
P0002:SetPoint Heat - heating NOT USED
P0003:2°SetPoint Cool - enable by remote switch
P0004:2°SetPoint Heat NOT USED
P0005:SetPoint ECOCool
P0006:SetPoint ECOHeat NOT USED
P0007:SetPointRec - recovery
Schedule
See next page.
28
Page 29
7 - CONTROL
7.4 SCHEDULER
It is possible to set 6 events (Off, Eco, On, Recirculating) for
each week day.
Scheduler must be enabled:
display : actual value = On
pag xy : unit parameters service-maintenance, P0500=1
Select
Confirm
Select
Confirm
Select
Confirm
Setting
Exit
Cmd Local state On
Main index
Cmd Local mode Cool
Unit stata
Unit parameters
Scheduler
Main index
Actual value On
01 : Monday Off
01 : Tuesday Off
01 : Wednesday Off
01 : Thursday Off
01 : Friday Off
d01 : Monday
Scheduled day Active
Time 1 00:00
Value 1 ECO
Time 2 5:00
Value 2 ON
Time 3 17:00
Value 3 ECO
Time 4 20:00
Value 4 OFF
Select
Confirm
Setting
Exit
Scheduled day Active
d01 : Monday
Time 1 xx:yy
Value 1 Eco
Time 2
Value 2
Time 3
Value 3
29
Page 30
7.5 TO VISUALIZE ALARM IN PROGRESS
7 - CONTROL
Before resetting an alarm identify and remove its cause.
Repeated resets can cause irreversible damage.
Press
Press
Press
Press
+ eE001 : Monitore fase : Fault
1 Critico (A)
14.02.2012 11.30.10
Reset Passive 1
+ eE001 : Monitore fase : Fault
Reset Passivo 10
+ eE001 : Monitore fase : Fault
- EE003 : Guasto P1 Util : Ok
+ EE003 : Guasto P1 Util : Fault
alarm log detail
alarm list
alarm log
eE001 : Monitore fase : Fault = active alarm
- EE003 : Guasto P1 Util : Ok = resetted alarm
Press
Slide
Press 3 sec.
Enter password:
Maintenance
Developer
Confirm
Press
Select
Confirm
Select
Confirm
alarm log
Reset Passivo 10
+ eE001 : Monitore fase : Fault
- EE003 : Guasto P1 Util : Ok
+ EE003 : Guasto P1 Util : Fault
.......................................
Password
Password
0 - - -
alarm list
Reset Passive 1
+ eE001 : Monitore fase : Fault
Passivo
Attivo
RESET ALARM
Press
Press
alarm log detail
+ eE001 : Monitore fase : Fault
1 Critico (A)
14.02.2012 11.30.10
alarm list
Reset Passive 1
+ eE001 : Monitore fase : Fault
Select
Uscita :
Premere 3c.
Select
Confirm
alarm list
Reset Passivo 0
password management
Log off
Cambia PSS user
Cambia PSS service
Cambia PSS manufacturer
30
Page 31
ALARM LOG RESET
7 - CONTROL
Press
Press 3 sec.
Insert password:
Maintenance
Manufacturer
Confirm
Press
alarm log
Reset Passivo 10
+ eE001 : Monitore fase : Fault
- EE003 : Guasto P1 Util : Ok
+ EE003 : Guasto P1 Util : Fault
……...
Password
Password
0 - - -
alarm log
Reset Passivo 10
+ eE001 : Monitore fase : Fault
- EE003 : Guasto P1 Util : Ok
+ EE003 : Guasto P1 Util : Fault
……...
Press 3 sec.
Select
Confirm
10.02.2012 10:15:30
SetPointAttuale 8.5°C
T.InH2OUtilizzo 10.5°C
T.OutH2OUtilizzo 12.5°C
StatoAttuale ON
ModoAttuale Cool
12 1 1 100%
password management
Log off
Cambia PSS utente
Cambia PSS service
Cambia PSS costruttore
Select
Confirm
Select
Confirm
Select
AlarmSnapshot 0
Alarm cnf
Lista allarmi :
Ordinamento 1 Ora
Ordinamento 2 Ora
Ordine descrescente Passive
Storico allarmi :
Reset
Execute
Allarmi cnf
AlarmSnapshot 0
Lista allarmi :
Ordinamento 1 Ora
Ordinamento 2 Ora
Ordine descrescente Passive
Storico allarmi :
Reset
7.6 KEYBOARD SETTINGS
Press 3 sec
Select
Confirm
exit :
To exit :
Select
Confirm
HMI settings
local connection
V9.08 B0024
Backlight color Blue
Backlight turn off time 0
Contrast 60
Brightness 100
Firmware Update No
HMI settings
local connection
HMI settings
31
Page 32
7.7 MAIN MENÙ - MAINTENANCE
7 - CONTROL
Press 3 sec.
insert maintenance password
Cmd Local state On
Cmd Local mode Cool
Unit stata
Unit parameters
Scheduler
Select
Confirm
Cmd Local state On
Cmd Local mode Cool
Unit stata
Unit parameters
Scheduler
Password
Password
0 - - -
Main index
Main index
Cmd local state
Cmd local Mode
Unit Stata
Unit parameters
System objects
SetPoint
Unit setting
circuit setting
unit option
Thermoregulator
electrical panel
Compressors
Source
circuit alarms
central alarms
defrost - not used
Climatica Text
Water reset
Freecooling
Hydronic
MasterSlave
Thermostatic
serial communication
Eco
SuperHeat Correction
Recovery
Reset usure
sensor settings
Communication
Save / load
AlarmSanpshot
Diagnostica
password management
time lightening
HMI
Version
sw. info
Target
DiagobjHandler
Scheduler Scheduler
User settings
date / hour setting
language select
32
Page 33
7 - CONTROL
ALARMS - TAB 1
code description description t.i. module input t.a.
eE001 phase monitor Phase monitor DI 687 central T13 DL1 A/M
EE003 pump 1 faulty Pump 1 faulty DI 687 central T13 DL2 M
EE004 pump 2 faulty Pump 2 faulty DI 687 central T4 D1 M
EE005 pump 3 faulty Pump 3 faulty DI 687 central T13 DL2 M
ee010 master offline Master Offline - Master Slave network enabled A
ee011 unit 2 in alarm Unit 2 in alarm - Master Slave network enabled A
ee012 unit 2 offline Unit 2 OffLine - Master Slave network enabled A
ee013 unit 3 in alarm Unit 3 in alarm - Master Slave network enabled A
ee014 unit 3 offline Unit 3 OffLine - Master Slave network enabled A
ee015 unit 4 in alarm Unit 4 in alarm - Master Slave network enabled A
ee016 unit 4 offline Unit 4 OffLine - Master Slave network enabled A
ee017 unit 5 in alarm Unit 5 in alarm - Master Slave network enabled A
ee018 unit 5 offline Unit 5 OffLine - Master Slave network enabled A
ee019 unit 6 in alarm Unit 6 in alarm - Master Slave network enabled A
ee020 unit 6 offline Unit 6 OffLine - Master Slave network enabled A
ee021 unit 7 in alarm Unit 7 in alarm - Master Slave network enabled A
ee022 unit 7 offline Unit 7 OffLine - Master Slave network enabled A
EE023 Pump 1 overload Pump 1 thermal protection DI 965 hydronic T1 X4 M
EE024 Pump 2 overload Pump 2 thermal protection DI 965 hydronic T1 X5 M
The alarm code identifies the concerned circuit:
Es: ee 1 01 :TimeOutModCirc = circuit 1 ee 2 01 :TimeOutModCirc = circuit 2
The number of refrigerant circuits depends on series and size
of the unit.
t.i. input type:
DI digital input
AI analogic input
module:
687 = main module
985 = circuit module
94U = thermostatic driver module
input:
connector number: T1, T2, T3...
PIN code: X1, X2, Q13, DO1....
t.a. alarm type:
A automatic reset
M manual reset
A/M rautomatic reset , after N alarm → manual reset
33
Page 34
7 - CONTROL
ALARMS - TAB 2
code description description t.i. module input t.a.
EE025 Pump 3 overload Pump 3 thermal protection DI 965 hydronic T1 X6 A
EE026 Inverter overload Inverter overload DI 965 hydronic T5 DL1 A
ee027 water IN temp Water inlet temperature probe faulty AI 687 central T1 B1 A
ee028 Water OUT temp Water outlet temperature probe faulty AI 687 central T1 B2 A
ee029 External air temp External air temperature probe faulty AI 687 central T1 B3 A
ee030 Demand Limit Signal logoff or short circuit AI 687 central T2 X1 A
ee031 WaterReset Signal logoff or short circuit AI 687 central T2 X2 A
ee032: External Humidity probe External Humidity probe faulty AI 687 central T2 X3 A
ee033: Cabinet temperature Cabinet temperature probe faulty AI 687 central T2 X4 A
ee034: Timout hydronic module Logoff Hydronic module periperal bus A
ee101: Timoeout circuit module Logoff circuit 1 module periperal bus A
ee102: Timeout comm. Driver Logoff driver 1 module periperal bus A
ee103:
ee104: EEV blocked Driver 1 blocked 94U driver A
EE106: Comp 1 protections Compressor 1 thermal protection DI 985 circuit 1 T4 D1 M
EE107: Comp 2 protections Compressor 2 thermal protection DI 985 circuit 1 T4 D2 M
EE108: Comp 3 protections Compressor 3 thermal protection DI 985 circuit 1 T4 D3 M
EE118: source side protection Source side protection DI 985 circuit 1 T9 DL2 M
ee122: discharge temp. C1 Faulty probe - discharge temperature compressor 1 AI 985 circuit 1 T1 B1 A
ee123: discharge temp. C2 Faulty probe - discharge temperature compressor 2 AI 985 circuit 1 T1 B2 A
ee124: discharge temp. C3 Faulty probe - discharge temperature compressor 3 AI 985 circuit 1 T2 X2 A
ee125: source1 temp. Faulty probe - source 1 temperature AI 985 circuit 1 T1 B3 A
ee126: source2 temp. Faulty probe - source 2 temperature AI 985 circuit 1 T2 X1 A
ee127: Suction temperature Faulty probe - Suction temperature AI 94U driver T2 X2 A
ee128: discharge pressure Faulty probe - discharge pressure AI 985 circuit 1 T2 X3 A
ee129: suction pressure Faulty probe - suction pressure AI 94U driver T1 X1 A
Timeout comm. Module
rec
Logoff recovery module periperal bus A
ee130: Rec. Gas temperature Faulty probe - Recovery gas temperature AI 965 recovery T1 X1 A
ee131: Rec. Pressure Faulty probe - Recovery gas pressure AI 965 recovery T2 X7 A
ee132: Water In rec. Temp. Faulty probe - Water recovery inlet AI 965 recovery T1 X2 A
ee133: Water out rec. Temp. Faulty probe - Water recovery outlet AI 965 recovery T1 X3 A
ee135: Bsp 985 wrong Bios wrong version 985 circuit 1 A
ff105: min overheating Low overheating C1 A
fF109: Low pressure from DI Low pressure from digital input DI 985 circuit 1 T3 X7 A/M
34
Page 35
7 - CONTROL
ALARMS - TAB 3
code description description t.i. module input t.a.
Inlet water temperature utility side
Outlet water temperature utility side
Unit mode digital output (N.O. open=Cool N.O. closed=Heat):
0=Cool 1=Heat
Pump ON by antifreeze alarm: 0=Off 1=On
36
Page 37
7 - CONTROL
CIRCUIT 1 STATA - TAB1
code description description
AI-94U SuctionTemp_X2 Suction temperature
AI-94U SuctionPressureX1 Suction pressure
AI-985 DischargeTC1_B1 Compressor 1 discharge temperature
AI-985 DischargeTC2_B2 Compressor 2 discharge temperature
AI-985 DischargeTC3_X2 Compressor 3 discharge temperature
AI-985 SourceTemp1_B3 Source temperature (air source unit = Probe on source coil. Water source unit = Probe on source inlet)
AI-985 SourceTemp2_X1 Source temperature 2 (air source unit = Probe 2 on source coil. Water source unit = Probe 2 on source inlet)
AI-985 DischargePressure_X3 High pressure probe
AO-985 %Cmd Cmp_X5 Compressor modulating signal control
AO-985 %Cmd Source_X6 Source modulating signal control
S1211 SetPosSteps Number of control steps that must reach the valve to adjust the superheat
S1212 SetPos% Valve % opening command to adjust the superheat
S1213 Pol94xCommOK Connection Status of the module POL94U : 0=NotOK 1=OK
S1214 ActPos% Actual position valve EEV
S1215 ActPosSteps Actual steps number valve EEV
S1216 ECVMode 0 = Idle 1 = Init 2 = Position 3 = FastClose.
S0720: U12 L1 - L2 voltage
S0721: U23 L2 - L3 voltage
S0722: U31 L1 - L3 voltage
S0723: Freq Frequency
S0724: IL1 L1 current
S0725: IL2 L2 current
S0726: IL3 L3 current
S0727: Ptotale Current active power
S0728: Cosfi Total power factor
S0729: Energy Active energy totalized
S0730: THD-U12 Sum of harmonic components of voltage between L1 e L2
S0731: THD-U23 Sum of harmonic components of voltage between L2 e L3
S0732: THD-U31 Sum of harmonic components of voltage between L3 e L1
41
Page 42
P.C. CONNECTION
1 connect P.C. and main module with LAN cable
2 check in the taskbar that the connection is active
7 - CONTROL
3 Open Control panel and select Network and sharing center
4 Select Modify board setting
5 Select Local area connection (LAN)
6 Select Internet protocol version 4 (TPC) IPV4 and enter Property
7 Set the IP address 192.168.1.100
8 Set Subnet mask as 255.255.255.0
confirm (OK)
9
10 Enter Start (Windows button).
11 Write the command cmd and enter/do it
12 Write and run the command Ping 192.168.1.42
13 if will appear dawn an answer string, the connection is ok
14 enter the browser and the address 192.168.1.42
Userid = ADMIN
15
Password = SBTAdmin!
16
42
Page 43
8 - MAINTENANCE
CONTROL CHECK LIST
Controls effected on ……………………………..B y ………………………………………………. Of the Company…………………..……………………………….
√
Presence of corrosions
□
Panel fixing
□
Fan fixing
□
Coil cleaning
□
Water filter cleaning
□
Check the exchanger efficiency
□
Circulating pumps
□
Check of the fixing and the insulation of the power lead
□
Check of the earthing cable
□
Electric panel cleaning
□
Capacity contactor status
□
Termina closing, cable insulation integrity
□
Voltage and phase unbalancing (no load and on-load)
□
Absorptions of the single electrical loads
□
Test of the compressor carter resistances
□
Leak control *
□
Survey of the refrigerant circuit operating parameters
Control system test: setpoint, climatic compensations, capacity stepping, water / air flow-rate variations etc
□
Control device test : alarm signalling, thermometers, probes, pressure gauges etc
□
1 6 12
Notes / interventions recommended to the owner
* European regulation 303/2008
Refer to the local actuation regulations; in short and just as an indication the regulation order as follow.
Companies and technicians that effect interventions of installation, maintenance/repairs, leak control and recovery must be CERTIFIED as expected by
the local regulations.
The leak control must be effected with annual renewal.
43
Page 44
8 - MAINTENANCE
Maintenance must be done by authorized centres or by
qualified personnel
The maintenance allows to:
maintain the unit efficiency
reduce the deterioration speed to whom every equipment
is subject over time
assemble information and data to understand the state of
the unit efficiency and avoid possible damages
8.2 INSPECTIONS FREQUENCY
The inspections should be carried out at least:
Every year for only the cooling units
Every six months for the cooling and warming units
The frequency, however, depends on the use.
In the event of frequent use it is recommended to plan
inspections at close intervals:
frequent use (continuous or very intermittent use, near
the operating limits, etc)
critical use (service necessary).
8.3 UNIT BOOKLET
8.6 ELECTRIC FANS 8.1 GENERAL
Check :
the fans and the relative protection gridsare well fixed
The fan bearings (evident by noise and anomalous
vibrations )
the terminal protection covers are closed and the cable
holders are properly positioned
8.7 COIL
Contact with the exchanger fins can cause cuts.
Wear protective gloves to perform the above described
operations.
It is extremely important that the battery gives the maximum
thermal exchange; therefore, its surface must be cleaned from
dust and deposits. Remove all impurities from the surface.
Using an air pressure gun, clean the aluminum surface of the
battery. Be careful to direct the air in the opposite direction of
the fan air movement.
Hold the gun parallel to the fins to avoid damages. As an
alternative, an aspirator can be used to suck impurities from
the air input side.
It’s advisable to create a unit booklet to take notes of the unit
interventions.
In this way it will be easier to adequately note the various
interventions and aid any troubleshooting.
Report on the booklet:
data
type of intervention effected
intervention description
carried out measures etc.
TENSIONS
After switching off the power, wait at least 5 minutes before
accessing to the electrical panel or any other electrical
component.
Check with a multimeter that there are no residual tensions
8.4 STRUCTURE
Check the condition of the parts making up the structure.
Paint so as to eliminate or reduce oxidation at the points in the
unit where this problem may occur.
Check that the panelling is fastened correctly.
Poor fastening may give rise to malfunctions and abnormal
noise and vibration.
8.5 WATER FILTER
Check that no impurities prevent the correct passage of water.
Verify that the aluminum fins are not bent or damaged. In the
event of damages, contact the authorized assistance center
and get the battery “ironed out” in order to restore the initial
condition for an optimal air flow
8.8 WATER EXCHANGER
It is very important for the exchanger to be able to provide the
maximum thermal exchange. Therefore, it is essential for the
inner surfaces to be clean of dirt and incrustations.
Periodically check the difference between the temperature of
the supply water and the condensation temperature. If the
difference is greater than 8 °C – 10 ° C it is advisable to clean
the exchanger.
The clearing must be effected :
With circulation opposite to the usual one
With a speed at least 1,5 times higher than the nominal one
With an appropriate product moderately acid (95% water +
5% phosphoric acid
After the cleaning rince with water to inhibe the detergent
rests.
44
Page 45
8 - MAINTENANCE
!
8.9 CIRCULATION PUMPS
Verify :
no leaks
Bearing status (anomalies are highlighted by abnormal
noise and vibration)
The closing of the terminals cover and the correct
positioning of the cable glands.
8.10 PUT A REST
If a long period of inactivity is foreseen:
Turn off the power
to avoid electrical risks or damages by lightning strikes
drain the water
to avoid the risk of frost
Protect from air exchangers and plant
To prevent any oxidation and fouling
1. evacuate the system
2. evacuate the exchanger
Use all the cocks presents
3. Use compressed air to blow the exchanger
4. dry completely the exchanger by an hot air jet
for greater safety fill the exchanger with glycoled
solution
5. protect the exchanger from the air
6. Remove the drain plugs to the pumps
Before starting a washing the plant.
It’s recommended that the starting-up after the stopping
period is performed by a qualified technician, especially after
seasonal stops or seasonal switch.
When restarting, refer to what is indicated in the START-UP
section.
Schedule technical assistance in advance to avoid hitches
and to guarantee that the system can be used when required.
8.11 COMPRESSOR SUPPLY LINE SHUT-OFF VALVE
Only if shut-off valve is present .
Do not remove the seal.
Remove only by qualified technician.
Contac the manufacturer for informations
A shut-off valve
45
Page 46
9 - DECOMMISSIONING
9.1 DISCONNECTING
Only authorised personnel must disconnect the unit.
Avoid leak or spills into the environment .
Before disconnecting the unit, the following must be
recovered, if present:
- refrigerant gas
- Anti-freeze solutions in the hydraulic circuit
Awaiting dismantling and disposal, the unit can also be
stored outdoors, as bad weather and rapid changes in
temperature will not cause damage to the environment, if
electric, cooling and hydraulic circuits of the unit are
integral and closed.
9.2 DISMANTLING AND DISPOSAL
THE UNIT MUST ALWAYS BE SENT TO AUTHORISED
CENTRES FOR DISMANTLING AND DISPOSAL.
When dismantling the unit, the fan, the motor and the coil, if
operating, may be recovered by the specialist centres for
reuse.
All the materials must be recovered or disposed of in
compliance with the corresponding national standards in
force.
For further information on the decommissioning of the unit,
contact the manufacturer.
cycle as urban waste. It must instead be handed over to
appropriate collection centres as set forth by current
standards or as instructed by the distributor.
If disposal takes places at the same time as delivery of a
new electrical or electronic equipment for the same
family, the product may be collected directly by the
distributor.
9.3 CE RAEE CE DIRECTIVE
The units covered by the legislation in question are
marked with the symbol on the side.
With the aim of protecting the environment, all of our
units are produced in compliance with Directive EC on
waste electrical and electronic equipment (WEEE).
The potential effects on the environment and on human
health due to the presence of hazardous substances are
shown in the use and maintenance manual in the section
on residual risks.
Information in addition to that indicated below, if
required, can be obtained from the manufacturer/
distributor/importer, who are responsible for the
collection/handling of waste originating from equipment
covered by EC - WEEE. This information is also
available from the retailer who sold this appliance or
from the local authorities who handle waste.
Directive EC - WEEE requires disposal and recycling of
electrical and electronic equipment as described therein
to be handled through appropriate collection, in suitable
centres, separate from collection for the disposal of
mixed urban waste.
The user must not dispose of the unit at the end of its life
46
Page 47
10 - RESIDUAL RISKS
General
In this section the most common situations are signalled. As these
cannot be controlled by the manufacturer these could be a source of risk
situations for people or things
Danger zone
This is an area in which only an authorised operator may work.
The danger zone is the area inside the unit which is accessible only with
the deliberate removal of protections or parts thereof
Handling
The handling operations, if implemented without all of the protection
necesssary and without due caution, may cause the fall or the tipping of
the unit with the consequent damage, even serious, to persons, things or
the unit itself.
Handle the unit following the instructions provided in the present manual
regarding the packaging and in compliance with the local regulations in
force.
Should the gas refrigerant leak please refer to the refrigerant "Safety
sheet".
Installation
An incorrect installation of the unit could cause water leaks, condensate
accumulation, leaking of the refrigerant, electric shock, bad functioning
or damage to the unit itself.
Check that the installation has been implemented by qualified technical
personnel only and that the instructions contained in the present manual
and the local regulations in force have been adhered to.
The installation of the unit in a place where even infrequent leaks of
inflammable gas and the accumulation of this gas in the area
surrounding the area occur could cause explosions or fires.
Carefully check the positioning of the unit.
The installation of the unit in a place unsuited to support its weight and/
or guarantee adequate anchorage may cause the fall or the tipping of
the unit with the consequent damage to things, people or the unit itself.
Carefully check the positioning and the anchoring of the unit.
Easy access to the unit by children, unauthorised persons or animals
may be the source of accidents, some serious.
Install the unit in areas which are only accessible to authorised person
and/or provide protection against intrusion into the danger zone .
General risks
Smell of burning, smoke or other signals of serious anomalies may
indicate a situation which could cause damage to people, things or the
unit itself.
Electrically isolate the unit (yellow-red isolator).
Contact the authorised service centre to identify and resolve the problem
at the source of the anomaly.
Accidental contact with exchange batteries, compressors, air delivery
tubes or other components may cause injuries and/or burns.
Always wear suitable clothing including protective gloves to work inside
the danger zone.
Maintenance and repair operations carried out by non-qualified
personnel may cause damge to persons, things or the unit itself.
Always contact the qualified assistance centre.
Failing to close the unit panels or failure to check the correct tightening
of all of the panelling fixing screws may cause damage to persons,
things or the unit itself.
Periodically check that all of the panels are correctly closed and fixed.
If there is a fire the temperature of the refrigerant could reach values that
increase the pressure to beyond the safety valve with the consequent
possible projection of the refrigerant itself or explosion of the circuit parts
that remain isolated by the closure of the tap.
Do not remain in the vicinity of the safety valve and never leave the
refrigerating system taps closed.
Electric parts
An incomplete attachment line to the electric network or with incorrectly
sized cables and/or unsuitable protective devices can cause electric
shocks, intoxication, damage to the unit or fires.
Carry out all of the work on the electric system referring to the electric
layout and the present manual ensuring the use of a system thereto
dedicated.
An incorrect fixing of the electric components cover may favour the entry
of dust, water etc inside and may consequently can electric shocks,
damage to the unit or fires.
Always fix the unit cover properly.
When the metallic mass of the unit is under voltage and is not correctly
connected to the earthing system it may be as source of electric shock
and electrocution.
Always pay particular attention to the implementation of the earthing
system connections.
Contact with parts under voltage accessible inside the unit after the
removal of the guards can cause electric shocks, burns and
electrocution.
Open and padlock the general isolator prior to removing the guards and
signal work in progress with the appropriate shield.
Contact with parts that could be under voltage due to the start up of the
unit may cause electric shocks, burns and electrocution.
When voltage is necessary for the circuit open the isolator on the
attachment line of the unit itself, padlock it and display the appropriate
warning shield.
Moving parts
Contact with the transmissions or with the fan aspiration can cause
injuries.
Prior to entering the inside of the unit open the isolater situated on the
connection line of the unit itself, padlock and display the suitable sign.
Contact with the fans can cause incurie.
Prior to removing the protective grill or the fans, open the isolator on the
attachment line of the unit itself, padlock it and display the appropriate
warning sign.
Refrigerant
The intervention of the safety valve and the consequent expulsion of the
gas refrigerant may cause injuries and intoxication. Always wear suitable
clothing including protective gloves and eyeglasses for operations inside
the danger zone.
Should the gas refrigerant leak please refer to the refrigerant "Safety
sheet".
Contact between open flames or heat sources with the refrigerant or the
heating of the gas circuit under pressure (e.g. during welding operations)
may cause explosions or fires.
Do not place any heat source inside the danger zone.
The maintenance or repair interventions which include welding must be
carried out with the system off.
Hydraulic parts
Defects in tubing, the attachments or the cut-off parts may cause a leak
or water projection with the consequent damages to peopl, things or
shortcircuit the unit.
1. Data referred to the following conditions: Internal exchanger water temperature = 12 / 7 °C. External exchanger inlet air
temperature = 35°C
2. The Total Power Input value does not take into account the part related to the pumps and required to overcome the pressure drops
for the circulation of the solution inside the exchangers
3. Option. Recovery exchanger water = 40/45°C
4. Data calculated in compliance with Standard EN 14511:2013 referred to the following conditions: Internal exchanger water
temperature = 12/7°C. External exchanger intake air temperature = 35°C
5. Indicative values for standard units with possible +/-10% variation. The actual data are indicated on the label of the unit.
Min. inlet air temperature3°C-10-10-10-10-10-10-10-10-10
Min. inlet air temperature4°C-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0
Min. inlet air temperature5°C-2,0-2,0-2,0-2,0-2,0-2,0-2,0-2,0--2,0
Min. inlet air temperature6°C111111111111111111
Internal exchanger
Max inlet water temperature°C242424242424242424
Min. outlet water temperature7°C5,05,05,05,05,05,05,05,05,0
Min. outlet water temperature8°C-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0
Data referred to the following conditions:
- internal exchanger water = 12/7°C
- air at rest
Caution: Air conditions which are at rest are dened as the absence of air owing towards the unit. Weak winds can
induce air to ow through the exchanger and air-levels which can cause a reduction in the operating range. In the
presence of predominant winds it is necessary to use suitable windbreak barriers.
N.B. To ensure the correct maintenance (no operation) with outdoor air temperatures less than -10°C, the Standard
unit (no FREE-COOLING conguration) must be equipped with the “Electrical panel anti-freeze protection” option
and continue to be supplied with power. The hydraulic circuit must be lled with an adequate percentage of anti-
freeze. In these conditions, the minimum outdoor air temperature which is permitted depends on the model of the
“Electrical panel anti-freeze protection” option which has been chosen, up to a limit value of -39°C.
The operating mode can also be extended up to an outdoor air temperature of –25°C, but only in the FREE-COOLING
conguration which is complete with an “Electrical panel anti-freeze protection” option of an adequate size.
The operating mode can be further extended to external air temperatures of 39°C. Only in the full FREE-COOLING
conguration of the ‘Device to reduce consumption of external section fans operating at variable speed (phase cut)’
and ‘Electrical panel antifreeze protection’ of an adequate size.
In the Standard unit (no FREE-COOLING conguration) with an empty hydraulic circuit and without a power supply,
correct maintenance (not operating) is possible up to a outdoor air temperature of -20°C.
1. Max. inlet air temperature - Unit at full load
2. Max. inlet air temperature - Unit at part load
3. Min. inlet air temperature - Unit at full load and outdoor air at rest
4. Min. inlet air temperature - Unit at part load and outdoor air at rest
5. Minimum input air temperature - Stepped unit and air speed at 0.5 m/s.
6. Minimum input air temperature - Stepped unit and air speed at 1 m/s
7. Standard unit without Low liquid temperature device and air entering the external exchanger at 35°C
8. Unit with Low liquid temperature device and air entering the external exchanger at 35°C. Fluid treated with 40% ethylene glycol.
Graph referred to size 352
The detail of each size is shown in tabular date.
Ta (°C) = external exchanger inlet air temperature (dry bulb).
To (°C) = internal exchanger outlet water temperature
1. Standard unit:(no “Liquid low temperature” conguration)
2. Unit in “Low liquid temperature” conguration (40% ethylene glycol).
3. capacity-controlled unit (automatic capacity control)
4. Unit at full load: (automatic modulation of the air ow rate)
Sound levels refer to full load units, in test nominal conditions. The sound pressure level refers to 1 m. from the unit outer surface operating in open eld.
Measures according to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certication.
Data referred to the following conditions:
internal exchanger water = 12/7°C
outdoor air temperature 35°C
Internal exchanger pressure drops
The pressure drops on the water side are calculated by
considering an average water temperature at 7°C
Q = Water ow rate (l/s)
DP = Pressure drop [kPa]
Sound
pressure
level
The water ow rate must be calculated with the following
formula
Q [l/s] = kWf / (4,186 x DT)
kWf = Cooling capacity in kW
DT = Temperature dierence between inlet / outlet water
To the internal exchanger pressure drops must be added the pressure drops of the mechanical steel mesh strainer that must be placed on the water input line. It is a
device compulsory for the correct unit operation, and it is available as Clivet option. (See the HYDRONIC ASSEMBLY ACCESSORIES). If the mechanical strainer is selected
and installed by the Customer, it is forbidden the use of lters with the mesh pitch higher than 1,6 mm, because they can cause a bad unit operation and also its serious
damaging.
Admissible water ow rates
Min. (Qmin) and max. (Qmax) water ow-rates admissibles for the correct unit operation.
Size
Qmin[l/s]3,23,63,93,94,44,44,95,56,1
Qmax[l/s]9,010,211,111,112,212,213,515,116,6
352402432452502552602702802
Page 51
Excellence version (EN)
51
General technical data (EN)
Acoustic Treatment: extremely low noise (EN)
Size352402432452502552602702802
Cooling
Cooling capacity1kW91,5104116125134145165185207
Compressor power input1kW28,532,937,137,742,146,153,458,566,2
Total power input2kW30,134,538,739,944,348,355,661,469,1
Total recovery heating capacity3kW119139151161176190215242269
1. Data referred to the following conditions: internal exchanger water = 12/7 °C external exchanger inlet air 35°C
2. The Total Power Input value does not take into account the part related to the pumps and required to overcome the pressure drops
for the circulation of the solution inside the exchangers
3. Option. Recovery exchanger water = 40/45°C
4. Data calculated in compliance with Standard EN 14511:2013 referred to the following conditions: Internal exchanger water
temperature = 12/7°C. External exchanger intake air temperature = 35°C
5. indicative values for standard units with possible +/-10% variation. The actual data are indicated on the label of the unit.
6. PHE = plates
7. AX = axial fan
SCROLLSCROLLSCROLLSCROLLSCROLL
Page 52
Operating range - Cooling (EN)
52
Acoustic Treatment: extremely low noise (EN)
Size352402432452502552602702802
External exchanger
Max inlet air temperature1°C464544464645444645
Max inlet air temperature2°C474646474746464746
Max inlet air temperature3°C505050505050505050
Min. inlet air temperature4°C-10-10-10-10-10-10-10-10-10
Min. inlet air temperature5°C-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0
Min. inlet air temperature6°C-2,0-2,0-2,0-2,0-2,0-2,0-2,0-2,0-2,0
Min. inlet air temperature7°C111111111111111111
Internal exchanger
Max inlet water temperature°C242424242424242424
Min. outlet water temperature8°C5,05,05,05,05,05,05,05,05,0
Min. outlet water temperature9°C-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0
Data referred to the following conditions:
internal exchanger water = 12/7°C
air at rest
Caution: Air conditions which are at rest are dened as the absence of air owing towards the unit. Weak winds can
induce air to ow through the exchanger and air-levels which can cause a reduction in the operating range. In the
presence of predominant winds it is necessary to use suitable windbreak barriers.
N.B. To ensure the correct maintenance (no operation) with outdoor air temperatures less than -10°C, the Standard
unit (no FREE-COOLING conguration) must be equipped with the “Electrical panel anti-freeze protection” option
and continue to be supplied with power. The hydraulic circuit must be lled with an adequate percentage of antifreeze. In these conditions, the minimum outdoor air temperature which is permitted depends on the model of the
“Electrical panel anti-freeze protection” option which has been chosen, up to a limit value of -39°C.
1. Max. inlet air temperature - Unit at full load
2. Input air maximum temperature - Unit operating at full load with fans automatically forced at maximum speed (the sound levels in
this particular operating condition are the same as the standard acoustic conguration SC)
3. Max. inlet air temperature - Unit at part load
4. Min. inlet air temperature - Unit at full load and outdoor air at rest
The operating mode can also be extended up to an outdoor air temperature of –25°C, but only in the FREE-COOLING
conguration which is complete with an “Electrical panel anti-freeze protection” option of an adequate size.
The operating mode can be further extended to external air temperatures of 39°C. Only in the full FREE-COOLING
conguration of the ‘Device to reduce consumption of external section fans operating at variable speed (phase cut)’
and ‘Electrical panel antifreeze protection’ of an adequate size.
In the Standard unit (no FREE-COOLING conguration) with an empty hydraulic circuit and without a power supply,
correct maintenance (not operating) is possible up to a outdoor air temperature of -20°C.
5. Min. inlet air temperature - Unit at part load and outdoor air at rest
6. Minimum input air temperature - Stepped unit and air speed at 0.5 m/s.
7. Minimum input air temperature - Stepped unit and air speed at 1 m/s
8. Standard unit without Low liquid temperature device and air entering the external exchanger at 35°C
9. Unit with Low liquid temperature device and air entering the external exchanger at 35°C. Fluid treated with 40% ethylene glycol.
Graph referred to size 352
The detail of each size is shown in tabular date.
Ta (°C) = external exchanger inlet air temperature (dry bulb).
To (°C) = internal exchanger outlet water temperature
1. Standard unit:(no “Liquid low temperature” conguration)
2. Unit in “Low liquid temperature” conguration (40% ethylene glycol).
3. capacity-controlled unit (automatic capacity control)
4. Unit at full load: (automatic modulation of the air ow rate)
Page 53
Sound levels (EN)
53
Acoustic Treatment: extremely low noise (EN)
Size
Sound power level (dB)S ound
Octave band (Hz)
power
level
Sound
pressure
level
631252505001000200040008000dB(A)dB(A)
35282848480716860558163
40282838480747062578163
43282838682757162578365
45285858683767063588365
50284858783767163578466
55284858783787264598466
60284858784787264588566
70286868885797365598667
80286868985807366608667
Sound levels refer to full load units, in test nominal conditions. The sound pressure level refers to 1 m. from the unit outer surface operating in open eld.
Measures according to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certication.
Data referred to the following conditions:
internal exchanger water = 12/7°C
outdoor air temperature 35°C
The indicated sound levels are only valid within the operating eld of the unit in the “Supersilenced EN” conguration; with fresh air temperatures which are higher and in any case within the operating eld of the “Soundproofed
Compressors SC” conguration bearing in mind the sound levels of the unit in the “Soundproofed Compressors SC” conguration.
Internal exchanger pressure drops
The pressure drops on the water side are calculated by
considering an average water temperature at 7°C
Q = water ow rate (l/s)
DP = pressure drop [kPa]
The water ow rate must be calculated with the following
formula
Q [l/s] = kWf / (4,186 x DT)
kWf = Cooling capacity in kW
DT = Temperature dierence between inlet / outlet water
To the internal exchanger pressure drops must be added the pressure drops of the mechanical steel mesh strainer that must be placed on the water input line. It is a
device compulsory for the correct unit operation, and it is available as Clivet option. (See the HYDRONIC ASSEMBLY ACCESSORIES). If the mechanical strainer is selected
and installed by the Customer, it is forbidden the use of lters with the mesh pitch higher than 1,6 mm, because they can cause a bad unit operation and also its serious
damaging.
Admissible water ow rates
Min. (Qmin) and max. (Qmax) water ow-rates admissibles for the correct unit operation.
Standard power supplyV400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Dimensions
A - Lengthmm271027102710271027102710307540254025
B - Widthmm109710971097109710971097109710971097
C - Heightmm180518051805180518051805180518051805
Standard unit weights
Shipping weightkg773796885917955975107712831310
Operating weightkg778802892924963984108712951324
1. Data referred to the following conditions: internal exchanger water = 12/7 °C external exchanger inlet air 35°C
2. data referred to the following conditions: internal exchanger water = 12/7 °C. external exchanger inlet water 35°C
3. The Total Power Input value does not take into account the part related to the pumps and required to overcome the pressure drops
for the circulation of the solution inside the exchangers
4. Option. Recovery exchanger water = 40/45°C
5. Data calculated in compliance with Standard EN 14511:2013 referred to the following conditions: Internal exchanger water
temperature = 12/7°C. External exchanger intake air temperature = 35°C
6. indicative values for standard units with possible +/-10% variation. The actual data are indicated on the label of the unit.
Min. inlet air temperature3°C-10-10-10-10-10-10-10-10-10
Min. inlet air temperature4°C-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0
Min. inlet air temperature5°C-2,0-2,0-2,0-2,0-2,0-2,0-2,0-2,0-2,0
Min. inlet air temperature6°C111111111111111111
Internal exchanger
Max inlet water temperature°C242424242424242424
Min. outlet water temperature7°C5.05.05.05.05.05.05.05.05.0
Min. outlet water temperature8°C-7.0-7.0-7.0-7.0-7.0-7.0-7.0-7.0-7.0
Data referred to the following conditions:
internal exchanger water = 12/7°C
air at rest
Caution: Air conditions which are at rest are dened as the absence of air owing towards the unit. Weak winds can
induce air to ow through the exchanger and air-levels which can cause a reduction in the operating range. In the
presence of predominant winds it is necessary to use suitable windbreak barriers.
N.B. To ensure the correct maintenance (no operation) with outdoor air temperatures less than -10°C, the Standard
unit (no FREE-COOLING conguration) must be equipped with the “Electrical panel anti-freeze protection” option
and continue to be supplied with power. The hydraulic circuit must be lled with an adequate percentage of antifreeze. In these conditions, the minimum outdoor air temperature which is permitted depends on the model of the
“Electrical panel anti-freeze protection” option which has been chosen, up to a limit value of -39°C.
1. Max. inlet air temperature - Unit at full load
2. Max. inlet air temperature - Unit at part load
3. Min. inlet air temperature - Unit at full load and outdoor air at rest
4. Min. inlet air temperature - Unit at part load and outdoor air at rest
The operating mode can also be extended up to an outdoor air temperature of –25°C, but only in the FREE-COOLING
conguration which is complete with an “Electrical panel anti-freeze protection” option of an adequate size.
The operating mode can also be extended up to an external air temperature of –39°C, but only in the FREE-COOLING
conguration which is complete with the ‘Electrical panel anti-freeze protection‘ option of an adequate size.
In the Standard unit (no FREE-COOLING conguration) with an empty hydraulic circuit and without a power supply,
correct maintenance (not operating) is possible up to a outdoor air temperature of -20°C.
5. Minimum input air temperature - Stepped unit and air speed at 0.5 m/s.
6. Minimum input air temperature - Stepped unit and air speed at 1 m/s
7. Standard unit without Low liquid temperature device and air entering the external exchanger at 35°C
8. Unit with Low liquid temperature device and air entering the external exchanger at 35°C. Fluid treated with 40% ethylene glycol.
Graph referred to size 352
The detail of each size is shown in tabular date.
Ta (°C) = external exchanger inlet air temperature (dry bulb).
To (°C) = internal exchanger outlet water temperature
1. Standard unit:(no “Liquid low temperature” conguration)
2. Unit in “Low liquid temperature” conguration (40% ethylene glycol).
3. capacity-controlled unit (automatic capacity control)
4. Unit at full load: (automatic modulation of the air ow rate)
Sound levels refer to full load units, in test nominal conditions. The sound pressure level refers to 1 m. from the unit outer surface operating in open eld.
Measures according to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certication.
Data referred to the following conditions:
internal exchanger water = 12/7°C
outdoor air temperature 35°C
Internal exchanger pressure drops
The pressure drops on the water side are calculated by considering an average
water temperature at 7°℃
Q = water ow rate (l/s)
DP = pressure drop [kPa]
Sound
pressure
level
The water ow rate must be calculated with the following formula
Q [l/s] = kWf / (4,186 x DT)
kWf = Cooling capacity in kW
DT = Temperature dierence between inlet / outlet water
To the internal exchanger pressure drops must be added the pressure drops of the mechanical steel mesh strainer that must be placed on the water input line. It is a
device compulsory for the correct unit operation, and it is available as Clivet option. (See the HYDRONIC ASSEMBLY ACCESSORIES). If the mechanical strainer is selected
and installed by the Customer, it is forbidden the use of lters with the mesh pitch higher than 1,6 mm, because they can cause a bad unit operation and also its serious
damaging.
Admissible water ow rates
Min. (Qmin) and max. (Qmax) water ow-rates admissibles for the correct unit operation.
Size
Qmin[l/s]2,32,62,93,23,63,94,44,95,5
Qmax[l/s]6,67,48,19,010,211,112,213,515,1
352402432452502552602702802
Page 57
Premium version (EN)
57
General technical data (EN)
Acoustic Treatment: extremely low noise (EN)
Size352402432452502552602702802
Cooling
Cooling capacity1kW87,095,9105115126136153178193
Compressor power input1kW29,935,339,942,145,751,659,864,374,4
Total power input2kW32,437,842,444,648,254,162,367,877,9
Total recovery heating capacity3kW114129144155169186208238263
Standard power supplyV400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Dimensions
A - Lengthmm271027102710271027102710307540254025
B - Widthmm109710971097109710971097109710971097
C - Heightmm180518051805180518051805180518051805
Standard unit weights
Shipping weightkg773796885917955975107712831310
Operating weightkg778802892924963984108712951324
1. Data referred to the following conditions: internal exchanger water = 12/7 °C external exchanger inlet air 35°C
2. The Total Power Input value does not take into account the part related to the pumps and required to overcome the pressure drops
for the circulation of the solution inside the exchangers
3. Option. Recovery exchanger water = 40/45°C
4. Data calculated in compliance with Standard EN 14511:2013 referred to the following conditions: Internal exchanger water
temperature = 12/7°C. External exchanger intake air temperature = 35°C
5. indicative values for standard units with possible +/-10% variation. The actual data are indicated on the label of the unit.
6. PHE = plates
7. AX = axial fan
SCROLLSCROLLSCROLLSCROLLSCROLL
Page 58
Operating range - Cooling (EN)
58
Acoustic Treatment: extremely low noise (EN)
Size352402432452502552602702802
External exchanger
Max inlet air temperature1°C434140414140404140
Max inlet air temperature2°C454443444443424443
Max inlet air temperature3°C505050505050505050
Min. inlet air temperature4°C-10-10-10-10-10-10-10-10-10
Min. inlet air temperature5°C-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0
Min. inlet air temperature6°C-2,0-2,0-2,0-2,0-2,0-2,0-2,0-2,0-2,0
Min. inlet air temperature7°C111111111111111111
Internal exchanger
Max inlet water temperature°C242424242424242424
Min. outlet water temperature8°C5.05.05.05.05.05.05.05.05.0
Min. outlet water temperature9°C-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0-7,0
Data referred to the following conditions:
internal exchanger water = 12/7°C
air at rest
Caution: Air conditions which are at rest are dened as the absence of air owing towards the unit. Weak winds can
induce air to ow through the exchanger and air-levels which can cause a reduction in the operating range. In the
presence of predominant winds it is necessary to use suitable windbreak barriers.
N.B. To ensure the correct maintenance (no operation) with outdoor air temperatures less than -10°C, the Standard
unit (no FREE-COOLING conguration) must be equipped with the “Electrical panel anti-freeze protection” option
and continue to be supplied with power. The hydraulic circuit must be lled with an adequate percentage of antifreeze. In these conditions, the minimum outdoor air temperature which is permitted depends on the model of the
“Electrical panel anti-freeze protection” option which has been chosen, up to a limit value of -39°C.
1. Max. inlet air temperature - Unit at full load
2. Input air maximum temperature - Unit operating at full load with fans automatically forced at maximum speed (the sound levels in
this particular operating condition are the same as the standard acoustic conguration SC)
3. Max. inlet air temperature - Unit at part load
4. Min. inlet air temperature - Unit at full load and outdoor air at rest
The operating mode can also be extended up to an outdoor air temperature of –25°C, but only in the FREE-COOLING
conguration which is complete with an “Electrical panel anti-freeze protection” option of an adequate size.
The operating mode can be further extended to external air temperatures of 39°C. Only in the full FREE-COOLING
conguration of the ‘Device to reduce consumption of external section fans operating at variable speed (phase cut)’
and ‘Electrical panel antifreeze protection’ of an adequate size.
In the Standard unit (no FREE-COOLING conguration) with an empty hydraulic circuit and without a power supply,
correct maintenance (not operating) is possible up to a outdoor air temperature of -20°C.
5. Min. inlet air temperature - Unit at part load and outdoor air at rest
6. Minimum input air temperature - Stepped unit and air speed at 0.5 m/s.
7. Minimum input air temperature - Stepped unit and air speed at 1 m/s
8. Standard unit without Low liquid temperature device and air entering the external exchanger at 35°C
9. Unit with Low liquid temperature device and air entering the external exchanger at 35°C. Fluid treated with 40% ethylene glycol.
Graph referred to size 352
The detail of each size is shown in tabular date.
Ta (°C) = external exchanger inlet air temperature (dry bulb).
To (°C) = internal exchanger outlet water temperature
1. Standard unit:(no “Liquid low temperature” conguration)
2. Unit in “Low liquid temperature” conguration (40% ethylene glycol).
3. capacity-controlled unit (automatic capacity control)
4. Unit at full load: (automatic modulation of the air ow rate)
Page 59
Sound levels (EN)
59
Acoustic Treatment: extremely low noise (EN)
Size
Sound power level (dB)
Octave band (Hz)
Sound
power
level
Sound
pressure
level
631252505001000200040008000dB(A)dB(A)
35283848580726960558163
40282838480747062578163
43282838681757162568265
45283838582767063578365
50281838682757062558365
55282838783777264588466
60282838683787164578466
70285858885797365598667
80284858885797365598667
Sound levels refer to full load units, in test nominal conditions. The sound pressure level refers to 1 m. from the unit outer surface operating in open eld.
Measures according to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certication.
Data referred to the following conditions:
internal exchanger water = 12/7°C
outdoor air temperature 35°C
The indicated sound levels are only valid within the operating eld of the unit in the “Supersilenced EN” conguration; with fresh air temperatures which are higher and in any case within the operating eld of the “Soundproofed
Compressors SC” conguration bearing in mind the sound levels of the unit in the “Soundproofed Compressors SC” conguration.
Internal exchanger pressure drops
The pressure drops on the water side are calculated by
considering an average water temperature at 7°℃
Q = water ow rate (l/s)
DP = pressure drop [kPa]
The water ow rate must be calculated with the following
formula
Q [l/s] = kWf / (4,186 x DT)
kWf = Cooling capacity in kW
DT = Temperature dierence between inlet / outlet water
To the internal exchanger pressure drops must be added the pressure drops of the mechanical steel mesh strainer that must be placed on the water input line. It is a
device compulsory for the correct unit operation, and it is available as Clivet option. (See the HYDRONIC ASSEMBLY ACCESSORIES). If the mechanical strainer is selected
and installed by the Customer, it is forbidden the use of lters with the mesh pitch higher than 1,6 mm, because they can cause a bad unit operation and also its serious
damaging.
Admissible water ow rates
Min. (Qmin) and max. (Qmax) water ow-rates admissibles for the correct unit operation.
Size
352402432452502552602702802
Qmin[l/s]2,32,62,93,23,63,94,44,95,5
Qmax[l/s]6,67,48,19,010,211,112,213,515,1
Page 60
Dimensional drawings: Excellence version
60
WSAT-XEE 352-402-432
1. Internal exchanger (evaporator)
2. External exchanger (condenser)
3. Unit xing holes
4. Lifting brackets (removable, if required, after the unit positioning)
5. Electrical panel
6. Power input
7. Soundproofed cabin
8. Internal exchanger water outlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
9. Internal exchanger water inlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
10. Minimum Safe Clearance
11. Minimum Clearance for a Proper Air ow to the Condenser
12. Minimum Clearance Electrical Panel Side
(G) Centre of gravity
SC-EXCEN-EXC
Size352402432352402432
Mmm193319462011193319462011
Nmm114211291064114211291064
Omm579581590579581590
Pmm518516507518516507
ODmm767676767676
Lengthmm307530753075307530753075
Depthmm109710971097109710971097
Heightmm180518051805180518051805
W1 Supporting Pointkg149153156149153156
W2 Supporting Pointkg325342396325342396
W3 Supporting Pointkg161165168161165168
W4 Supporting Pointkg261272304261272304
Shipping weightkg88992510158899251015
Operating weightkg89693310248969331024
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
Page 61
WSAT-XEE 452-502-552-602
61
1. Internal exchanger (evaporator)
2. External exchanger (condenser)
3. Unit xing holes
4. Lifting brackets (removable, if required, after positioning the unit)
5. Electrical panel
6. Power input
7. Soundproofed cabin
8. Internal exchanger water outlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
9. Internal exchanger water inlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
10. Minimum Safe Clearance
11. Minimum Clearance for a Proper Air ow to the Condenser
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
Page 62
WSAT-XEE 702-802
62
1. Internal exchanger (evaporator)
2. External exchanger (condenser)
3. Unit xing holes
4. Lifting brackets (removable, if required, after positioning the unit)
5. Electrical panel
6. Power input
7. Soundproofed cabin
8. Internal exchanger water outlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
9. Internal exchanger water inlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
10. Minimum Safe Clearance
11. Minimum Clearance for a Proper Air ow to the Condenser
12. Minimum Clearance Electrical Panel Side
(G) Centre of gravity
SC-EXCEN-EXC
Size702802702802
Mmm3216322732163227
Nmm1809179818091798
Omm564565564565
Pmm533532533532
ODmm76767676
Lengthmm5025502550255025
Depthmm1097109710971097
Heightmm1805180518051805
W1 Supporting Pointkg114115114115
W2 Supporting Pointkg284292284292
W3 Supporting Pointkg374389374389
W4 Supporting Pointkg108109108109
W5 Supporting Pointkg306315306315
W6 Supporting Pointkg312323312323
Shipping weightkg1483152714831527
Operating weightkg1497154414971544
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
Page 63
Dimensional drawings: Premium version
63
WSAT-XEE 352-402-432-452-502-552
1. Internal exchanger (evaporator)
2. External exchanger (condenser)
3. Unit xing holes
4. Lifting brackets (removable, if required, after positioning the unit)
5. Electrical panel
6. Power input
7. Soundproofed cabin
8. Internal exchanger water outlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
9. Internal exchanger water inlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
10. Minimum Safe Clearance
11. Minimum Clearance for a Proper Air ow to the Condenser
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
Page 64
WSAT-XEE 602
64
1. Internal exchanger (evaporator)
2. External exchanger (condenser)
3. Unit xing holes
4. Lifting brackets (removable, if required, after positioning the unit)
5. Electrical panel
6. Power input
7. Soundproofed cabin
8. Internal exchanger water outlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
9. Internal exchanger water inlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
10. Minimum Safe Clearance
11. Minimum Clearance for a Proper Air ow to the Condenser
12. Minimum Clearance Electrical Panel Side
(G) Centre of gravity
SC-PRMEN-PRM
Size602602
Mmm20522052
Nmm10231023
Omm595595
Pmm502502
ODmm7676
Lengthmm30753075
Depthmm10971097
Heightmm18051805
W1 Supporting Pointkg157157
W2 Supporting Pointkg434434
W3 Supporting Pointkg169169
W4 Supporting Pointkg326326
W5 Supporting Pointkg0.00.0
W6 Supporting Pointkg0.00.0
Shipping weightkg10771077
Operating weightkg10871087
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
Page 65
WSAT-XEE 702-802
65
1. Internal exchanger (evaporator)
2. External exchanger (condenser)
3. Unit xing holes
4. Lifting brackets (removable, if required, after positioning the unit)
5. Electrical panel
6. Power input
7. Soundproofed cabin
8. Internal exchanger water outlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
9. Internal exchanger water inlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
10. Minimum Safe Clearance
11. Minimum Clearance for a Proper Air ow to the Condenser
12. Minimum Clearance Electrical Panel Side
(G) Centre of gravity
SC-PRMEN-PRM
Size702802702802
Mmm2626264326262643
Nmm1399138213991382
Omm567567567567
Pmm530530530530
ODmm76767676
Lengthmm4025402540254025
Depthmm1097109710971097
Heightmm1805180518051805
W1 Supporting Pointkg79797979
W2 Supporting Pointkg260264260264
W3 Supporting Pointkg332344332344
W4 Supporting Pointkg84848484
W5 Supporting Pointkg258262258262
W6 Supporting Pointkg282292282292
Shipping weightkg1283131012831310
Operating weightkg1295132412951324
The presence of optional accessories may result in a substantial variation of the weights shown in the table.