CLIVET WSAN-XIN51, WSAN-XIN21, WSAN-XIN31, WSAN-XIN41, WSAN-XIN71 Installation And Operating Manual

...
AIR COOLED INVERTER HEAT PUMP FOR OUTDOOR INSTALLATION
WSAN-XIN 21-141
Installation and
operating manual
M0R940E13-00 11/06/2013
Dear Customer,
We congratulate you on choosing these product
Clivet is being working for years to oer systems able to assure the maximum comfort for long time with high reliability, eciency, quality and safety.
The target of the company is to oer advanced systems, that assure the best comfort, reduce the energy con-sumption, the installation and maintenance costs for all the life-cycle of the system.
With this manual, we want to give you information that are useful in all the phases: from the reception, to the installation and use until the disposal so that a system so advanced oers the best procedure of installation and use.
Best regards and have a nice reading.
CLIVET Spa
The data contained in this manual is not binding and may be changed by the manufacturer without prior notice.
Reproduction, even is part, is FORBIDDEN © Copyright - CLIVET S.p.A. - Feltre (BL) - Italia
Table of contents
1 Installation quick guide 5
2 General description 6
3 Reception 8
4 Positioning 10
5 Water connections 12
6 Electrical connections 15
7 Start-up 22
8 Control 27
9 Maintenance 41
10 Decommissioning 54
11 Residual risks 55
12 Dimensional drawings 56
13 Technical information 60
14 Accessories 64
15 Alarms - Stata 70
M0R940E13-00 WSAN-XIN 21-141 3
4 WSAN-XIN 21-141 M0R940E13-00
1 Installation quick guide
chapter / page
A Domestic hot water module 14.4 Boiler management→69
B Temperature probe domestic hot water 14.4 Boiler management→69
C Boiler 14.4 Boiler management→69
D 3-way DHW valve 14.4 Boiler management→69
E 3-way valve 14.4 Boiler management→69
F 1° setpoint control 14.4 Boiler management→69
G 2° setpoint control (2 setpoint>1 setpoint) 14.4 Boiler management→69
BUS connection
H
H+H1 = 100mt max
I Control F delay respect to control E 14.4 Boiler management→69
L ON/OFF 6.7 SA1 = ON-OFF remote→20
M summer/winter 6.8 SA2 = Summer - Winter remote→20
N room thermostat 14.1 RCTX - Remote control→65
O Boiler control 6.6 Connections performer by customer→19
P Remote alarm signal 6.6 Connections performer by customer→19
Q Water lter 5.7 Water lter→14
R Bypass 14.4 Boiler management→69
S Power supply 6.4 Power input→15
Weight and dimensions 12 Dimensional drawings→56
M0R940E13-00 WSAN-XIN 21-141 5
14.4 Boiler management→69
2 General description
2.1 Manual
The manual provides correct unit installation, use and maintenance.
Pay particolar attention to:
Warning, identies particularly important operations or information.
Prohibited operations that must not be carried out, that compromise the operating of the unit or may cause damage to persons or things.
It is advisable to read it carefully so you will save time during operations.
•
Follow the written indications so you will not cause damages to things and injuries people.
•
2.2 Preliminaries
Only qualied personnel can operate on the unit, as required by the regulation in force.
2.3 Risk situations
The unit has been designed and created to prevent injures to people.
During designing it is not possible to plane and operate on all risk situation.
Read carefully “Residual risk” section where all situation which may cause damages to things and injuries to people are reported.
Installation, starting, maintenance and repair required specic knowledge; if they are carried out by inexperienced personnel, they may cause damages to things and injuries people.
2.4 Intended use
Use the unit only:
for cooling/heating water or a water and glycol mix for air-conditioning only
•
attenendosi ai limiti previsti dal bollettino tecnico e dal presente manuale
•
Any use other than intended does not involve the manufacturer in any commitment or obligation.
2.5 Installation
The positioning, hydraulic system, refrigerating, electrics and the channelisation of the air must be determined by the system designer in accordance with local regulations in force.
Follow local safety regulations.
Verify that the electrical line characteristics are in compliance with data quotes on the unit serial number label.
2.6 Maintenance
Plan periodic inspection and maintenance in order to avoid or reduce repairing costs.
Turn the machine o before any operation.
2.7 Modication
All unit modications will end the warranty coverage and the manufacturer responsibility.
2.8 Breakdown/Malfuction
Disable the unit immediately in case of breakdown or malfunction.
Contact a constructor certied assistance service.
Use original spares parts only.
Using the unit in case of breakdown or malfunction:
voids the warranty
•
may compromise the safety of the machine
•
may increase time and repair costs
•
6 WSAN-XIN 21-141 M0R940E13-00
2.9 User training
The installer has to train the user on:
Start-up/shutdown
•
Set points change
•
Standby mode
•
Maintenance
•
What to do / what not to do in case of breakdown
•
2.10 Data update
Continual product improvements may imply manual data changes.
Visit manufacturer web site www.clivet.it for updated data.
2.11 Indications for the user
Keep this manual with the wiring diagram in an accessible place for the operator.
Note the unit lable data so you can provide them at the assistance centre in case of intervention (see “Unit identication” section).
provide a machine notebook that allows any interventions carried out on the machine to be noted and tracked making it easier to suitably note the various interventions and aids the search for any breakdowns.
In case of breakdown or malfunction:
Immediately deactivate the unit
•
Contact a assistance service centre authorized by the manifacturer
•
Ask the installer to format on:
Start-up/shutdown
•
Set points change
•
Standby mode
•
Maintenance
•
What to do / what not to do in case of breakdown
•
2.12 Unit indentication
The serial number label is positioned on the unit and allows to indentify all the unit features.
It has not to be removed for any reason.
It reports the regulations indications such as:
unit type
•
serial number (12 characters)
•
year of manufacture
•
wiring diagram number
•
electrical data
•
manufacturer logo and address
•
2.13 Serial number
It identies uniquely each unit.
It identies specic spare parts for the unit.
2.14 Assistance request
Note data from the serial number label and write them in the chart on side, so you will nd them easily when needed.
Series
Size
Serial number
Year of manufacture
Electrical wiringdiagram
M0R940E13-00 WSAN-XIN 21-141 7
3 Reception
You have to check before accepting the delivery:
That the unit hasn’t been damaged during transport
•
That the materials delivered correspond with that indicated on the transport document comparing the data with the identication label
•
positioned on the packaging.
In case of damage or anomaly:
Write down on the transport document the damage you found and quote this sentence: “Conditional acceptance clear evidence of
•
deciencies/damages during transport”
Contest by fax and registered mail with advice of receipt to supplier and the carrier.
•
Any disputes must be made within the 8 days owing the delivery. Complaints after this period are invalid.
3.1 Storage
Observe external packaging instructions.
3.2 Handling
1. Verify unit weight and handling equipment lifting capacity.
2. Identify critical points during handling (disconnected routes, ights, steps, doors).
3. Use protections not to damage the unit.
4. Before starting the handling, make sure that the unit is stable.
5. Start hoisting the unit.
6. Remove screws
8 WSAN-XIN 21-141 M0R940E13-00
3.3 Packaging removing
Be careful not to damage the unit.
Keep packing material out of children’s reach it may be dangerous.
Recycling and disposing the packaging material in conformity with local regulations.
M0R940E13-00 WSAN-XIN 21-141 9
4 Positioning
During positioning consider these elements:
Shafts required by the unit
•
Electrical connections
•
Water connections
•
Spaces for air exhaust and intake
•
4.1 Functional spaces
Functional spaces are designed to:
guarantee good unit operation
•
carry out maintenance operations
•
protect authorized operators and exposed people
•
Respect all functional spaces indicated in the DIMENSIONS section.
Double all functional spaces if two or more unit are aligned.
4.2 Positioning
Units are designed to be installed:
EXTERNAL
•
in xed positions
•
Limit vibration transmission:
use antivibration devices on unit bearing points
•
install exible joints on the hydraulic
•
Choose the installation place according to the following criteria:
Customer approval
•
safe accessible position
•
technical spaces requested by the unit
•
spaces for the air intake/exhaust
•
avoid ood-prone places
•
verify unit weight and bearing point capacity
•
verify that all bearing points are aligned and leveled
•
install the unit raised from the ground
•
max. distance allowed by the electrical connections
•
condensate water draining
•
Prefer places where the unit doesn’t disturb the neighbours.
Avoid installations next to bedrooms or windows.
Avoid snow accumulations on batteries.
A correct circulation of the air is indispensible to guarantee the good working order of the machine.
Avoid therefore:
obstacles to the airow
•
exchange diculties
•
leaves or other foreign bodies that can obstruct the exchange batteries
•
winds that hinder or favour the airow
•
heat or pollution sources close to the unit (chimneys, extractors etc..)
•
stratication (cold air that stagnates at the bottom)
•
recirculation (expelled air that is sucked in again)
•
positioning below the level of the threshold, close to very high walls, attics or in angles that could give rise to stratication or recirculation
•
phenomenons
Ignoring the previous indications could:
energy eciency decrease
•
blocks due to HIGH PRESSURE (in summer) or LOW PRESSURE (in winter)
•
A. Keep the min. distances from the podestrian areas.
B. Provide windbreaks in locations with strong winds.
C. Avoid snow accumulations on batteries.
D. Install the unit lifted from the ground.
E. Provide a protection.
10 WSAN-XIN 21-141 M0R940E13-00
4.3 Condensate water
When a heat pump is running it produces a considerable amount of water due to the defrosting cycles of the external coil.
The condensation must be eliminated in a manner to avoid wetting pedestrian areas.
The unit anti-freeze electric resistance prevents the ice from forming inside the tray.
With extensive very cold outdoor temperatures, condensation could freeze outside the unit blocking the ow and causing a slow build-up of ice; therefore special attention must be paid to eliminating condensation, raising the unit o the ground and evaluating whether antifreeze elements should be installed.
A. Condensation collection basin
B. Unit support
C. Condensate discharge connection Ø 13
M0R940E13-00 WSAN-XIN 21-141 11
5 Water connections
5.1 Water quality
The water quality can be checked by qualied personnel.
Water with inadequate characteristics can cause:
pressure drop increase
•
energy eciency decrease
•
corrosive symptom increase
•
Acceptable water quality values:
Provide a water treatment system if values fall outside the limits.
5.2 Risk of freeze
If the unit or the relative water connections are subject to temperatures close to 0°C:
mix water with glycol, or
•
safeguard the pipes with heating cables placed under the insulation, or
•
empty the system in cases of long non-use
•
5.3 Anti-freeze solution
Consider that the use of anti-freeze solution determines an increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not corrosive) and compatible with the hydraulic circuit components.
Do not use dierent glicol mixture (i.e. ethylic with propylene).
5.4 Water ow-rate
The project water-ow must be:
inside the exchanger operating limits (see the TECHNICAL INFORMATION section)
•
guarantee, also with variable system conditions (for example in systems where some circuits are bypassed in particular situations).
•
5.5 Operation sequence
1. Carefully wash the system with clean water: ll and drain the system several times.
2. Apply additives to prevent corrosion, fouling, formation of mud and algae.
3. Fill the plant
4. Execute leakage test.
5. Isolate the pipes to avoid heat dispersions and formation of condensate.
6. Leave various point of service free (wells, vent-holes etc).
Neglecting the washing will lead to several lter cleaning interventions and at worst cases can cause damages to the exchangers and the other parts.
12 WSAN-XIN 21-141 M0R940E13-00
5.6 Racommended connection
The installer must to dened:
component type
•
position on system
•
1 Pump / circulating pump 9 lling valve 2 vent 10 shut-o valve 3 limit unit 11 Internal storage tank 4 antivibration joints 12 lter 5 piping support 13 Flow Switch 6 expansion vessel 14 safety valve 7 pressure gauge 15 Drain valve 8 thermometer 16 utility side exchanger
(sizes 21÷71)
A. vent B. pump C. input probe D. Safety valve (6 Bar)
E. plate exchanger F. Flow Switch G. input probe H. water outlet
M0R940E13-00 WSAN-XIN 21-141 13
(size 81÷141)
A. vent B. Dierential pressure switch C. input probe D. plate exchanger
E. pump F. input probe G. Safety valve (6 Bar) H. water outlet
5.7 Water lter
If not present on-board the machine, must be installed immediately in the water input of the unit, in a position that is easily accessible for cleaning.
The lter never should be removed, this operation invalidates the guaranty.
14 WSAN-XIN 21-141 M0R940E13-00
6 Electrical connections
The characteristics of the electrical lines must be determined by specialized personnel able to design electrical installations; moreover, the lines must be in conformity with regulations in force.
The protection devices of the unit power line must be able to stop the presumed short circuit current, whose value must be determined in function of system features.
The power cables and the protection cable section must be dened in accordance with the characteristics of the protections adopted.
All electrical operations should be performed by trained personnel having the necessary requirements by the regulations in force and being informed about the risks relevant to these activities.
Operate in compliance with safety regulations in force.
6.1 Electrical data
The serial number label reports the unit specic electrical data, included any electrical accessories.
The electrical data indicated in the technical bulletin and in the manual refer to the standard unit, accessories excluded.
It reports the regulations indications such as:
Voltage
•
F.L.A.: full load ampere, absorbed current at maximum admitted conditions
•
F.L.I.: full load input, full load power input at max. admissible condition
•
Electrical wiringdiagram Nr.
•
If the DHW module is present, consider the electric resistance absorption in the power supply line dimensionino.
6.2 Connections
1. Refer to the unit electrical diagram (the number of the diagram is shown on the serial number label).
2. Verify that the network has characteristics conforming to the data shown on the serial number label.
3. Before starting work, verify that the sectioning device at the start of the unit power line is open, blocked and equipped with cartel warning.
4. Primarily you have to realize the earthing connection.
5. Shelter the cables using adequate measure fairleads.
6. Before power the unit, make sure that all the protections that were removed during the electrical connection work have been restored.
6.3 Signals / data lines
Do not overpass the maximum power allowed, which varies, according to the type of signal.
Lay the cables far from power cables or cables having a dierent tension and that are able to emit electromagnetic disturbances.
Do not lay the cable near devices which can generate electromagnetic interferences.
Do not lay the cables parallel to other cables, cable crossings are possible, only if laid at 90°.
Connect the screen to the ground, only if there aren’t disturbances.
Guarantee the continuity of the screen during the entire extension of the cable.
Respect impendency, capacity and attenuation indications.
M0R940E13-00 WSAN-XIN 21-141 15
6.4 Power input
A, B: Ø 22 mm
C: Ø 34 mm
Install the isolator switch near the unit.
Fix the cables: if vacated may be subject to tearing.
The cable don’t have to touch the compressor and the refrigerant piping (they reach high temparatures).
16 WSAN-XIN 21-141 M0R940E13-00
6.5 Electrical panel
A Signals B RS485 C Power supply
AP1 Main control module FU1 Fuse AP2 Electronic thermostatic management FU2 230V aux. cicuit fuse AP4 Fan control module KA1 Inverter alarm auxiliary relay
AP6 RS 485 module
C1 C2
T1 Transformer XT1 Terminal block of the customer connections
(OPTIONAL) Fan capacitor KA3 Ciculation pump control relay
KA2 Compressor control relay
M0R940E13-00 WSAN-XIN 21-141 17
A Signals B RS485 C Power supply
AP1 Main control module FU1 230V aux. cicuit fuse AP2 Electronic thermostatic management FU2 compressor overload protection and timer AP4 Fan control module QS1 Main isolator switch
AP6 RS 485 module
QM1 Compressor line protection
(OPTIONAL)
C1
Fan capacitor KA1 Inverter alarm auxiliary relay
C2 T1 Transformer KA2 Compressor control relay FU1 compressor overload protection and timer
KA3 Ciculation pump control relay
Size 51-71
FU2 230V aux. cicuit fuse
XT1 Terminal block of the customer connections
Size 51-71
18 WSAN-XIN 21-141 M0R940E13-00
6.6 Connections performer by customer
Electrical panel
(sizes 21÷71)
1 Unit QG Electrical panel 2 Connections perfomer by customer AP7 Room keypad 3 Only for sizes 21-41 SA2 Remote summer/winter
4 Only for sizes 51-71 SA1 Remote ON-OFF
A Fuses
Provided by the customer
B Isolating switch
Provided by the customer
FU1 Fuse
6.8 SA2 = Summer - Winter remote→20
6.7 SA1 = ON-OFF remote→20
M8 Pump use
Provided by the customer
XT1 Terminal block of the customer connections
M0R940E13-00 WSAN-XIN 21-141 19
Electrical panel
(size 81÷141)
1 Unit SA1 Remote ON-OFF 2 Connections perfomer by customer SA2 Remote summer/winter A Fuses
Provided by the customer
QS1 Isolating switch M8 Pump use
QG Electrical panel XT1 Terminal block of the customer connections
AP7 Room keypad
Provided by the customer
6.7 SA1 = ON-OFF remote
Set parameter CL43 as shown in the table
CL43 ON/OFF Standby Time bands only DHW
-2 SA1 = ON-OFF remote from menu YES from menu
-1 ON/OFF only by keypad SA1 = remote standby NO from menu
0
28 from keypad from menu YES
OFF: emergency stop, not active the antifreeze safeties etc.
Standby: assisted stop, are active the antifreeze safeties etc.
ON/OFF only by keypad
(SA1 disabled)
Menu standby (SA1 disabled)
YES from menu
SA1 = only Domestic Hot Water
6.8 SA2 = Summer - Winter remote
Set parameter CL44
CL44 Summer/Winter change
0 from keypad SA2 = disabled
-3
by SA2
SUMMER
WINTER
change from keyboard disabled
remote
6.9 Remote control with room thermostat
For details see: 14.1 RCTX - Remote control65
6.10 Domestic hot water module
For details see: 14.3 AMACSX - Domestic hot water module67
6.11 Serial communication module with RS485 serial converter kit
For details see: 14.2 CMSC2X - Serial communication module with RS485 serial converter kit66
20 WSAN-XIN 21-141 M0R940E13-00
7 Start-up
7.1 General description
The indicated operations should be done by qualied technician with specic training on the product.
Upon request, the service centres performing the start-up.
The electrical, water connections and the other system works are by the installer.
Agree upon in advance the star-up data with the service centre.
Before checking, please verify the following:
the unit should be installed properly and in conformity with this manual
•
the electrical power supply line should be sectioned at the beginning
•
the line sectionalizing device is open, locked and equipped with the suitable warning
•
make sure no tension is present
•
7.2 Preliminary checks
For details refer to the dierent manual sections.
Unit OFF power supply
1. safety access
2. functional spaces
3. air ow: correct return and supply (no bypass, no stratication)
4. structure integrity
5. fans run freely
6. unit on vibration isolators
7. unit input water lter + shut-o valves for cleaning
8. vibration isolators on water connections
9. expansion tank (indicative volume = 5% system content)
10. cleaned system
11. loaded system + possibile glicole solution + corrosion inhibitor
12. under pressure system
13. vented system
14. refrigerant circuit visual check
15. earthing connection
16. power supply features
17. electrical connections provided by the customer
7.3 Start-up sequence
For details refer to the dierent manual sections.
Unit ON power supply
1. compressor carter resistances operating at least since 8 hours
2. o-load voltage measure
3. phase sequence check (unit only 400/3/50)
4. unit ON
5. load voltage measure and absorptions
6. check of all fan operating
7. measure of return and supply water temperature and ow valutation
8. super-heating and sub-cooling measure and discharge temperature
9. check no anomalous vibrations are present
10. climatic curve personalization
11. set date and time
12. personalise scheduling
13. personalise DHW *
14. climatic curve personalization
15. set ambient keypad *
16. complete and available unit documentation
*If present
M0R940E13-00 WSAN-XIN 21-141 21
7.4 Refrigeration circuit
1. Check carefully the refrigerating circuit: the presence of oil stains can mean leakage caused by transportation, movements or other).
2. Verify that the refrigerating circuit is in pressure: Using the unit manometers, if present, or service manometers.
3. Make sure that all the service outlets are closed with proper caps; if caps are not present a leak of refrigerant can be possible.
4. Open the cocks of the refrigerant circuit, if there are any.
7.5 Refrigerant circuit
1. Before realizing the unit connection make sure that the hydraulic system has been cleaned up and the clearing water has been drained.
2. Check that the water circuit has been lled and pressurized.
3. Check that the shut-o valves in the circuit are in the “OPEN” position.
4. Check that there isn’t air in the circuit, if required, evacuate it using the air bleed valve placed in the system high points.
5. When using antifreeze solutions, make sure the glycol percentage is suitable for the type of use envisaged.
Weight of glycol (%) 10 20 30 40
Freezing temperature (°C) -3.9 -8.9 -15.6 -23.4
Safety temperature (°C) -1 -4 -10 -19
7.6 Electric Circuit
Verify that the unit is connected to the ground plant.
Check the conductors tightening: the vibrations caused by handling and transport might cause loosing.
Feed the unit by closing the sectioning device, but leave it on OFF.
Controllare i valori di tensione e frequenza di rete, che devono essere entro i limiti:
400/3/50 +/-10%
•
230/1/50 +/-10%
•
Control the unbalancing of the phases: it must be lower than 2%
Example:
The working out of the limits can cause irreversible damages and voids the warranty.
7.7 Compressor crankcase resistances
Connect the oil resistances on the compressor crankcase at least 8 hours before the compressor is to be starter:
at the rst unit start-up
•
after each prolonged period of inactivity
•
1. Supply the resistances switching o the unit isolator switch.
2. To make sure that hte resistances are working, check the power input.
3. At start-up the compressor crank-case temperature on the lower side must be higher at least of 10°C than the outside temperature.
Do not start the compressor with the crankcase oil below operating temperature.
7.8 Voltages
Check that the air and water temperatures are included in the operating limits.
Start-up the unit.
With operating unit, i.e. in stable conditions and next to the operating ones, check:
Voltage
•
Total absorption of the unit
•
Absorption of the single electric loads
•
22 WSAN-XIN 21-141 M0R940E13-00
7.9 Remote controls
Check that the remote controls (ON-OFF etc) are connected and, if necessary, enabled with the respective parameters as indicated in the “electrical connections” section.
Check that probes and optional components are connected and enabled with the respective parameters (“electrical connections” section and following pages).
7.10 Water set point compensation with external temperature
It is possible to automatically change the set-point according to the outside temperature.
Enable the function:
Par: dS00 set-point compensation of the outside temp.
0 = Disabled
1 = Proportional
2 = Fixed (by step)
Cooling
With low ext. temperature the refrigerant requirements are reduced.
The internal comfort can also be obtained with a set-point higher than standard.
Example:
dS01 = - 6°C
dS03 = 4°C
dS05 = 36°C
setpoint = 10°C
compensated setpoint = 14°C
Parameter modication
Main menuParametersdSdS00
Cool Description dS01 Temperature controller dynamic dierential proportional band in Cool dS03 Maximum temperature controller dynamic dierential in Cool dS05 Temperature controller dynamic dierential setpoint in Cool
M0R940E13-00 WSAN-XIN 21-141 23
Heating
With outside mild temperatures the thermal requirements are reduced.
The internal comfort can also be obtained with a lower setpoint.
Example:
dS02 = 20°C
dS04 = - 7°C
dS06 = -5°C
setpoint = 35°C
compensated setpoint = 28°C
Heat Description dS02 Temperature controller dynamic dierential proportional band in Heat dS04 Maximum temperature controller dynamic dierential in Heat dS06 Set point dynamic dierential of external air
7.11 Water set point compensation with ambient temperature
Only with ambient keyboard option.
Function and parameters are the same of paragraph “Water set point compensation with external temperature”
On the ambient keyboard set parameter Cr 30 = 10
It is possible enable ambient compensation OR external compensation, not ambient AND external compensation.
7.12 Start-up report
Identifying the operating objective conditions is useful to control the unit over time.
With unit at steady state, i.e. in stable and close-to-work conditions, identify the following data:
total voltages and absorptions with unit at full load
•
absorptions of the dierent electric loads (compressors, fans, pumps etc)
•
temperatures and ows of the dierent uids (water, air) both in input and in output from the unit
•
temperature and pressures on the characteristic points of the refrigerating circuit (compressor discharge, liquid, intake)
•
The measurements must be kept and made available during maintenance interventions.
7.13 97/23 CE PED directive
97/23 CE PED DIRECTIVE gives instructions for installers, users and maintenance technicians as well.
Refer to local actuation norms; briey and as an example, see the following:
Compulsory verication of the rst installation:
only for units assembled on the installer’s building site (for ex. Condensing circuit + direct expansion unit)
•
Certication of setting in service:
for all the units
•
Periodical verications:
to be executed with the frequency indicated by the Manufacturer (see the “maintenance inspections” paragraph)
•
24 WSAN-XIN 21-141 M0R940E13-00
8 Control
8.1 Display
Icon Fixed on Flashing Icon
Alarm on progress Silenced alarm Compressor
Heating mode
Remote cooling Remote cooling mode
Standby from keypad Remote standby Primary circuit water pump
Clock Active scheduling
Defrosting Automatic
Not used Boiler activation request
Antifreeze with active heat pump, remote heating mode
Clock setting Scheduling
Manual defrosting activated
Ventilation
At the start-up is performed a board automatic test: all the led ash for some seconds
Heater ON - D.H.W.
ON: Domestic hot water Flashing: D.H.W. mode - standby
8.2 Keys
Symbol Name Action Function (3 sec.)
Up
Down
Esc
Set
Increases the value Next voice
Decreases the value Previous voice
Esc WITHOUT SAVING MODIFICATIONS Previous level
Conrm Esc WITH MODIFICATION SAVING Go to the next level STATA menu
Silenced alarm
On / O *
Heat / cool / stdby / as
Inputs / clock / active alarms / setpoint
Activate / disactivate the time bands
Access to the SETTING menu Parameters / function / password / alarms
* Unit in OFF the antifreeze function is not active.
M0R940E13-00 WSAN-XIN 21-141 25
8.3 Navigation
Press 2 sec.
*Manual defrosting: possible only under certain conditions.
Use for qualied technicians reserved.
OPERATING MODE
STATA
SCHEDULING
Heat Heating Cool Cooling StdBY Standaby - o
AS
Ai, di, AO, dO Inputs, outputs AO Digital inputs of Analogical outputs dO Digital outputs CL Clock AL Active alarms HR Compressor operating hours SP Setpoint
PAR - parameters Conguration
Fnc - functions
PASS - password EU - alarms Alarm log
Domestic hot water The unit switches to ACS mode, only by Heat mode
dEF - manual defrosting* tA - alarm reset St - on / o CC - copy card EUr - alarm log reset
26 WSAN-XIN 21-141 M0R940E13-00
8.4 ON/OFF
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press 3 sec.
OFF
2 OFF Press 3 sec.
ON
8.5 Change the operating mode
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press 2 sec.
2 Cool Select
3 Heat Conrm
* O the unit is immediately stopped without respecting any timing.
Stanby the antifreeze function is active ( pump ON for water temperature < 4°C ).
The circulator anti-blocking function is active ( pump ON at predened intervals).
Cool *
Choose standby, o: STBY cool: COOL heat: HEAT DHW: AS
8.6 Clock setting
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 Ai Select
3 CL Access Hour
Ai
CLOCK menu
Choose
4 Hour Select
5 YEAR Press 3 sec.
6 ! 2012 ! Press
7 ! 2013 ! Conrm 2013
8 Press Back to step 4
hour: HOUR date: DATE year: YEAR
Conrm ! Value ashing !
Set the value
8.7 Water setpoint modication
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 Ai Select
3 SP Access Cool
4 Cool Select
5 AS Conrm
Ai
SP
Choose Cool Heat AS
50
6 50 Press
7 55 Conrm
8 Press
M0R940E13-00 WSAN-XIN 21-141 27
Set the value 55
55
Back to the previous menu
8.8 Display of inputs - outputs
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 Ai Choose menu
3 of Access
4 diL1 Scroll the list
5 diL4 Press to see the value
6 Press
For details see:
15.4 Stata71
Ai
Ai: analogical inputs di: digital inputs AO: analogical outputs dO: digital outputs
diL1
Choose diL4
For digital inputs: 0 = input not active - open 1 = input active - closed
Back to the previous menu
8.9 Silenced alarm
Step Display Ac tion Keys Menu/Variable Notes
1 Er01 The alarm code is ashing 2 13.5°C Alternated to temperature
3
4 Press any button
Fixed ALARM led
5 ALARM led is ashing
For details see:
8.27 Alarms38
8.10 Alarms
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 Ai Select
3 Al Press
4 Er01 Scroll
5 Press Back to the previous menu
Ai
ALARM menu Al
Access 1° active alarm
Other active alarms
8.11 Alarm reset
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 PAr Select FnC
PAr
3 FnC Press dEF
4 dEF Select tA
5 tA Press
6 Press Back to the previous menu
28 WSAN-XIN 21-141 M0R940E13-00
8.12 Alarm log
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 PAr Select EU
3 EU Press
4 EU00 Press
5 Er01 Select
6 20:01 Select
7 27.10 Select
8 --:-- Select
9 --:-- Select
10 AUt o Press
11 Press Back to the previous menu
PAr
Last registered alarm EU00
Access to alarm code info Er01
Hour of the alarm 20:01
Date of the alarm
27.10
Alarm output hour Example: alarm still active
--:--
Alarm output date Example: alarm still active
--:--
Type of alarm: AUto (automatic) MAnu (manual)
8.13 Alarms log reset
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 PAr Select
3 FnC Press dEF
4 dEF Select
5 EUr Press 3 sec. YES
6 Press Back to the previous menu
PAr
FnC
EUr
M0R940E13-00 WSAN-XIN 21-141 29
8.14 Setting menu
SETTING menu - PAR (conguration parameters)
Label Acronym meaning (label) Parameters of:
CL Conguration Local Local I/O Conguration CE Conguration Expansion Expansion I/O Conguration Cr Conguration Remote terminal Remote terminal I/O Conguration CF ConFiguration Conguration Ui User interface User interface tr thermoregulation Thermoregulation St Stati (Operating modes) Operating stata
CP ComPressori Compressor
PI Pump (Internal) Primary circuit water pump FI Fan (Internal) Not used FE Fan (External) Fans (external) of the disposable exchanger
PE Pump (External) Not used
Hi Electric Heaters (Internal) Electric heaters of the primary exchanger
HE Electric Heaters (External) Not used
HA Auxiliary Output Not used
br Boiler Boiler dF deFrost Defrosting dS dynamic Setpoint Dynamic Setpoint Ad Adaptive Adaptive (adaptive function) AF AntiFreeze Anti-ice AS Domestic hot water, Anti-Legionella Domestic hot water, Anti-Legionella
HP Heat Pump Heat pump
PL Power Limitation Not used
tE Time Events Time bands AL ALarm Alarms
8.15 Scheduling management
It is possible to set 3 dierent schedulings.
To each scheduling is possible to associate 4 events.
To each day of the week is possible to associate a scheduling.
In the example the schedulings have been assigned:
Scheduling 1 Monday Tuesday Wednesday
Scheduling 2 Thursday Friday
Scheduling 3 Saturday Sunday
Day Scheduling 1 Scheduling 2 Scheduling 3
Monday tE01 = 1 - -
Tuesday tE02 = 1 - -
Wednesday tE03 = 1 - -
Thursday - tE04 = 2 -
Friday - tE05 = 2 -
Saturday - - tE06 = 3
Sunday - - tE07 = 3
To enable the hour scheduling set the parameters tE00 and CL43:
Par tE00 hour scheduling
0 = disabled, 1 = enabled
Par CL43 = -2
Parameter modication
Main menuParameterstEtE00
30 WSAN-XIN 21-141 M0R940E13-00
In the following example the scheduling 1 schedules:
at 07:00 changes the cooling set-point
at 12:00 changes the cooling set-point
at 16:30 changes the cooling set-point
at 22:00 changes the cooling set-point
Scheduling 1
Description Event 1 Event 2 Event 3 Event 4
Time tE10 = 07 tE17 = 12 tE24 = 16 tE31 = 22
Minutes tE11 = 00 tE18 = 00 tE25 = 30 tE32 = 00
Mode 0= on
1= standby
*Cooling tempera-
ture
*Heating tempera-
ture
tE12 = 0 tE19 = 0 tE26 = 0 tE33 = 0
tE13 = - tE20 = - tE27 = - tE34 = -
tE14 = 20 tE21 = 22 tE28 = 22 tE35 = 18
DHW temperature tE22 = 45 tE22 = 45 tE29 = 55 tE36 = 45
* If the unit is in Cooling is used the cooling temperature. * If the unit is in Heating is used the heating temperature.
Sched. 1 (par.) Sched. 2 (par.) Sched. 3 (par.)
Time tE10 tE38 tE66
Minutes tE11 tE39 tE67
Event 1
Mode 0= on
1= standby
Cooling tem-
perature
Heating tem-
perature
DHW tempera-
ture
tE12 tE40 tE68
tE13 tE41 tE69
tE14 tE42 tE70
tE15 tE43 tE71
Event 2
Event 3
Event 4
Time tE17 tE45 tE73
Minutes tE18 tE50 tE74
Mode 0= on
1= standby
Cooling tem-
perature
Heating tem-
perature
DHW tempera-
ture
tE19 tE47 tE75
tE20 tE48 tE76
tE21 tE49 tE77
tE22 tE50 tE78
Time tE24 tE52 tE80
Minutes tE25 tE53 tE81
Mode 0= on
1= standby
Cooling tem-
perature
Heating tem-
perature
DHW tempera-
ture
tE26 tE54 tE82
tE27 tE55 tE83
tE28 tE56 tE84
tE29 tE57 tE85
Time tE31 tE59 tE87
Minutes tE32 tE60 tE88
Mode 0= on
1= standby
Cooling tem-
perature
Heating tem-
perature
DHW tempera-
ture
tE33 tE61 tE89
tE34 tE62 tE90
tE35 tE63 tE91
tE36 tE64 tE92
M0R940E13-00 WSAN-XIN 21-141 31
8.16 Sanitary water
To enable the DHW function:
Par AS00 DHW operating
1 = Enable the heat pump for DHW + DHW 3-way valve
3 = Enable the heat pump for DHW + electric heater + DHW 3-way valve
Parameters to setting:
CL 90 = 9 CE 50 = 11 AS = 1
CE 00 = 2 CE 60 = 0 AS = 5
CE 30 = 11 AS = 5
Parameter modication
Main menuParameterstEAS00
Parameter:
AS01 DHW setpoint
AS04 DHW hysteresis
DHW scheduling
To enable the hour scheduling:
Par tE00 hour scheduling
0 = disabled, 1 = enabled
Parameter modication
Main menuParameterstEtE00
AS = 20
Antilegionella scheduling
The scheduling can be programmed for each day of the week.
Parameter:
AS20 antilegionella set-point
AS04 DHW hysteresis
Parameter modication
Main menuParameterstEAS20
In the following example the antilegionella cycle is scheduled:
Wednesday duration 1 starting at 23:00
Sunday duration 2 starting at 22:30
Day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Cycle duration (0=
OFF from 1 to 24
hours)
Time Minutes
32 WSAN-XIN 21-141 M0R940E13-00
8.17 Ambient keyboard - option
The keyboard repeats all the built-in control functions.
8.18 Display
Icon Fixed on Flashing Icon
Alarm on progress Silenced alarm Compressor
Heating mode
Remote cooling Remote cooling mode Primary circuit water pump
Standby from keypad Remote standby
Defrosting Manual defrosting activated
Heater ON - D.H.W.
Antifreeze with active heat pump, remote heating mode
Ventilation
At the start-up is performed a board automatic test: all the led ash for some seconds
Display shows Clock (not related to scheduling)
ON: Domestic hot water Flashing: D.H.W. mode - standby
Not used
8.19 Keys
Symbol Name Action Function (3 sec.)
Up
Down
Esc
Increases the value Next voice
Decreases the value Previous voice
Esc WITHOUT SAVING MODIFICATIONS Previous level
Silenced alarm
On / O *
Heat / cool / stdby / as
Conrm
Set
* Unit in OFF the antifreeze function is not active.
M0R940E13-00 WSAN-XIN 21-141 33
Esc WITH MODIFICATION SAVING Go to the next level STATA menu
Activate / disactivate the time bands
Access to the SETTING menu Parameters / function / password / alarms
Inputs / clock / active alarms / setpoint
8.20 Navigation
Press 3 sec.
OPERATING MODE
STATA
SCHEDULING
Heat Heating Cool Cooling StdBY Standaby - o
AS
Ai, di, AO, dO Inputs, outputs AO Digital inputs of Analogical outputs dO Digital outputs CL Clock AL Active alarms SP Setpoint
PAR - parameters Conguration
Fnc - functions
PASS - password EU - alarms Alarm log
Domestic hot water The unit switches to ACS mode, only by Heat mode
dEF - manual defrosting tA - alarm reset St - on / o CC - copy card EUr - alarm log reset
34 WSAN-XIN 21-141 M0R940E13-00
8.21 ON/OFF
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press 3 sec.
2 OFF Press 3 sec. ON
OFF
8.22 Change the operating mode
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press 2 sec.
2 Cool Select
3 Heat Conrm
* O the unit is immediately stopped without respecting any timing.
Stanby the antifreeze function is active ( pump ON for water temperature < 4°C ).
The circulator anti-blocking function is active ( pump ON at predened intervals).
Cool *
Choose standby, o: STBY cool: COOL heat: HEAT DHW: AS
8.23 Clock setting
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
Ai
2 Ai Select
3 CL Access Hour
4 Hour Select
5 YEAR Press 3 sec.
6 ! 2012 ! Press
7 ! 2013 ! Conrm 2013
8 Press
CLOCK menu
Choose hour: HOUR date: DATE year: YEAR
Conrm ! Value ashing !
Set the value
Back to step 4
8.24 Water setpoint modication
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 Ai Select
3 SP Access Cool
4 Cool Select
5 ACS Conrm
Ai
SP
Choose Cool Heat ACS
50
6 50 Press
7 55 Conrm
8 Press
M0R940E13-00 WSAN-XIN 21-141 35
Set the value 55
55
Back to the previous menu
8.25 Display of inputs - outputs
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 Ai Choose menu
3 of Access
Ai
Ai: analogical inputs di: digital inputs AO: analogical outputs dO: digital outputs
diL1
4 diL1 Scroll the list
5 diL4 Press to see the value
6 Press
For details see:
15.4 Stata71
Choose diL4
For digital inputs: 0 = input not active - open 1 = input active - closed
Back to the previous menu
8.26 Silenced alarm
Step Display Ac tion Keys Menu/Variable Notes
1 Er01 The alarm code is ashing 2 13.5°C Alternated to temperature
3
4 Press any button
5 ALARM led is ashing
For details see:
8.27 Alarms38
Fixed ALARM led
8.27 Alarms
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 PAr Select
3 FnC Press dEF
4 dEF Select
5 tA Press
6 Press Back to the previous menu
PAr
FnC
tA
36 WSAN-XIN 21-141 M0R940E13-00
8.28 Alarm reset
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
PAr
2 PAr Select
3 FnC Press dEF
4 dEF Select
5 tA Press
6 Press Back to the previous menu
FnC
tA
8.29 Alarm log
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 PAr Select EU
3 EU Press
4 EU00 Press
5 Er01 Select
6 20:01 Select
7 27.10 Select
8 --:-- Select
9 --:-- Select
10 AUt o Press
PAr
Last registered alarm EU00
Access to alarm code info Er01
Hour of the alarm 20:01
Date of the alarm
27.10
Alarm output hour Example: alarm still active
--:--
Alarm output date Example: alarm still active
--:--
Type of alarm: AUto MAnu (manual)
11 Press Back to the previous menu
8.30 Alarms log reset
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 PAr Select
3 FnC Press dEF
4 dEF Select EUr
5 EUr Press 3 sec. YES
6 Press Back to the previous menu
M0R940E13-00 WSAN-XIN 21-141 37
PAr
FnC
8.31 Ambient temperature display
It is possible to set the keypad to display the ambient temperature.
The probe is not used to perform the ambient thermoregulation.
Follow these steps:
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 PAr Press PAr
3 PAr Select Cr
4 Cr Press Cr..
5 Cr. . Select
6 Cr00 Conrm
7 0 Select
8 2 Conrm 2
9 Press
10 Select
11 Cr30 Conrm
12 0 Select
13 16 Conrm
14 Press Back to the previous menu
PAr
Cr00 Anable ambient probe
0
2
Back to the previous menu
Cr30 Temperature display
0
16
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press
2 PAr Press
3 PAr Select
4 Ui Press Ui..
5 Ui.. Select
6 Ui22 Conrm 0
7 0 Select 1
8 1 Conrm 1
9 Press Back to the previous menu
Step Display Ac tion Keys Menu/Variable Notes
1 Main menu Press 3 sec.
2 Select Air1
3 Air1 Press
PAr
PAr
Ui
Ui22
Is it possible to disable the ambient keyboard:
Cr00 = 0
Cr30 = 0
To enable water setpoint compensation with ambient temperature set:
Cr 30 = 10
38 WSAN-XIN 21-141 M0R940E13-00
9 Maintenance
9.1 General description
Maintenance must be done by authorized centres or by qualied personnel.
The maintenance allows to:
maintain the unit eciency
•
reduce the deterioration speed to whom every equipment is subject over time
•
assemble information and data to understand the state of the unit eciency and avoid possible damages
•
Before checking, please verify the following:
the electrical power supply line should be sectioned at the beginning
•
the line sectionalizing device is open, locked and equipped with the suitable warning
•
make sure no tension is present
•
9.2 Inspections frequency
Perform an inspection every 6 months of unit operating.
The frequency, however, depends on the use.
In the event of frequent use it is recommended to plan inspections at close intervals:
frequent use (continuous or very intermittent use, near the operating limits, etc)
•
critical use (service necessary)
•
9.3 Unit booklet
It’s advisable to create a unit booklet to take notes of the unit interventions.
In this way it will be easier to adequately note the various interventions and aid any troubleshooting.
Report on the booklet:
date
•
type of intervention eected
•
intervention description
•
carried out measures etc.
•
9.4 Standby mode
If a long period of inactivity is foreseen:
turn o the power
•
avoid the risk of frost (empty the system or add glycol)
•
Turn o the power to avoid electrical risks or damages by lightning strikes.
With extremely rigid temperatures keep fed heating resistances of the electrical panel (option).
It’s recommended that the starting-up after the stopping period is performed by a qualied technician, especially after seasonal stops or seasonal switch.
When restarting, refer to what is indicated in the “start-up” section.
Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required.
M0R940E13-00 WSAN-XIN 21-141 39
9.5 Main components
(sizes 21÷71)
A. Coil B. Inverter C. Electrical panel D. Exchanger
A. vent B. pump C. input probe D. Safety valve (6 Bar)
E. pump F. Compressor G. Fan
E. plate exchanger F. Flow Switch G. input probe H. water outlet
40 WSAN-XIN 21-141 M0R940E13-00
(size 81÷141)
A. Coil B. Inverter C. Electrical panel D. Exchanger
A. vent B. Dierential pressure switch C. input probe D. plate exchanger
E. pump F. Compressor G. Fan
E. pump F. input probe G. Safety valve (6 Bar) H. water outlet
M0R940E13-00 WSAN-XIN 21-141 41
9.6 Control check list
intervention frequency (months) 1 6 12
1 presence corrosion X
2 panel xing X
3 fan xing X
4 coil cleaning X
5 water lter cleaning X
6 check the exchanger eciency X
7 circulating pumps X
8 check of the xing and the insulation of the power lead X
9 check of the earthing cable X
10 electric panel cleaning X
11 capacity contactor status X
12 termina closing, cable insulation integrity X
13 voltage and phase unbalancing (no load and on-load) X
14 absorptions of the single electrical loads X
15 test of the compressor carter resistances X
16 leak control* X
17 survey of the refrigerant circuit operating parameters X
18 check of the 4-way change X
19 protective device test: safety valves, pressure switches, thermostats, ow switches etc.. X
20 control system test: setpoint, climatic compensations, capacity stepping, water / air ow-rate variations X
21 control device test: alarm signalling, thermometers, probes, pressure gauges etc.. X
* European regulation 303/2008 Refer to the local actuation regulations; in short and just as an indication the regulation order as follow. Companies and technicians that eect
interventions of installation, maintenance/repairs, leak control and recovery must be CERTIFIED as expected by the local regulations. The leak control must be eected with annual renewal.
9.7 Air coil
Contact with the exchanger ns can cause cuts: wear protective gloves to perform the above described operations.
It is extremely important that the battery gives the maximum thermal exchange; therefore, its surface must be cleaned from dust and deposits.
Remove all impurities from the surface.
Using an air pressure gun, clean the aluminum surface of the battery; be careful to direct the air in the opposite direction of the fan air movement.
Hold the gun parallel to the ns to avoid damages.
As an alternative, an aspirator can be used to suck impurities from the air input side.
Verify that the aluminum ns are not bent or damaged, in the event of damages contact the authorized assistance center and get the battery “ironed out” in order to restore the initial condition for an optimal air ow.
9.8 Water side exchanger
It is very important for the exchanger to be able to provide the maximum thermal exchange, therefore it is essential for the inner surfaces to be clean of dirt and incrustations.
Periodically check the dierence between the temperature of the supply water and the condensation temperature: if the dierence is greater than 8°C–10°C it is advisable to clean the exchanger.
The clearing must be eected:
with circulation opposite to the usual one
•
with a speed at least 1,5 times higher than the nominal one
•
with an appropriate product moderately acid (95% water + 5% phosphoric acid)
•
after the cleaning rince with water to inhibe the detergent rests
•
42 WSAN-XIN 21-141 M0R940E13-00
9.9 Water lter
Check that no impurities prevent the correct passage of water.
9.10 Electric fans
Check:
the fans and the relative protection gridsare well xed
•
the fan bearings (evident by noise and anomalous vibrations)
•
the terminal protection covers are closed and the cable holders are properly positioned
•
9.11 Circulating pumps
Check:
no leaks
•
bearing status (anomalies are highlighted by abnormal noise and vibration)
•
the terminal protection covers are closed and the cable holders are properly positioned
•
9.12 Probe position
A. Fresh air probe
M0R940E13-00 WSAN-XIN 21-141 43
9.13 Spare parts sizes 21-31-41
44 WSAN-XIN 21-141 M0R940E13-00
Ref. Components
1 Mono-phase compressor
2 Reversing cycle valve
Electronic thermostatic valve
3
(Solenoid + Body)
4 Internal plate exchanger
5 External nned exchanger
6 Circulator
EC circulator (High eciency)
7 (*) Mono-phase electrical panel
Mono-phase electrical panel of EC circulator
8 Mono-phase Inverter
9 Water Kit
10 Flow Switch
11 Rear panel
12 Right panel
13 Roof
14 Flow nozzle
15 Fan grid
16 Fan
17 Grid for the coil protection
18 Tray
19 Base
20 Supervisory control for the keypad protection
(*) Components installed inside each electrical panel
SB655/C Control module
XVD420 driver module for electr. valve
230/12+12+24V mono-phase transformer
Control module of the condensing fans
420v 30.000h/Class A condenser
Condensing air temp. probe
Refrigerant circuit gas temp. probe
Water temperature probe
M0R940E13-00 WSAN-XIN 21-141 45
9.14 Spare parts sizes 51-71
46 WSAN-XIN 21-141 M0R940E13-00
Rif Components
1 Three-phase compressor
2 Reversing cycle valve
Thermostatic valve
3
(Solenoid + Body)
4 Internal plate exchanger
5 External nned exchanger
6 Circulator
EC circulator (High eciency)
7 (*) Mono-phase electrical panel
Mono-phase electrical panel of EC circulator
Three-phase electrical panel
Three-phase electrical panel of EC circulator
8 Mono-phase Inverter
Three-phase Inverter
9 Water Kit
10 Flow Switch
11 Rear panel
12 Right panel
13 Roof
14 Flow nozzle
15 Fan grid
16 Fan
17 Grid for the coil protection
18 Tray
19 Base
20 Supervisory control for the keypad protection
(*) Components installed inside each electrical panel
SB655/C Control module
XVD420 driver module for electr. valve
230/12+12+24V mono-phase transformer
Control module of the condensing fans
420v 30.000h/Class A condenser
Condensing air temp. probe
Refrigerant circuit gas temp. probe
Water temperature probe
M0R940E13-00 WSAN-XIN 21-141 47
9.15 Spare parts sizes 81-101
48 WSAN-XIN 21-141 M0R940E13-00
Ref. Components
1 Compressor
2 Reversing cycle valve
Electronic thermostatic valve
3
(Solenoid + Body)
4 Internal plate exchanger
5 External nned exchanger
6 Circulator
EC circulator (High eciency)
7 (*) Three-phase electrical panel
Three-phase electrical panel of EC circulator
8 Three-phase Inverter
9 Dierential pressure switch
10 Rear panel
11 Right panel
12 Left panel
13 Roof
14 Flow nozzle
15 Fan grid
16 Fan
17 Grid for the coil protection
18 Tray
19 Base
20 Supervisory control for the keypad protection
(*) Components installed inside each electrical panel
SB655/C Control module
XVD420 driver module for electr. valve
230/12+12+24V mono-phase transformer
Control module of the condensing fans
420v 30.000h/Class A condenser
Condensing air temp. probe
Refrigerant circuit gas temp. probe
Water temperature probe
M0R940E13-00 WSAN-XIN 21-141 49
9.16 Spare parts sizes 121-141
50 WSAN-XIN 21-141 M0R940E13-00
Ref. Components
1 Compressor
2 Reversing cycle valve
Electronic thermostatic valve
3
(Solenoid + Body)
4 Internal plate exchanger
5 External nned exchanger
6 Circulator
EC circulator (High eciency)
7 (*) Three-phase electrical panel
Three-phase electrical panel of EC circulator
8 Three-phase Inverter
9 Dierential pressure switch
10 Rear panel
11 Right panel
12 Left panel
13 Roof
14 Flow nozzle
15 Fan grid
16 Fan
17 Grid for the coil protection
18 Tray
19 Base
20 Supervisory control for the keypad protection
(*) Components installed inside each electrical panel
SB655/C Control module
XVD420 driver module for electr. valve
230/12+12+24V mono-phase transformer
Control module of the condensing fans
420v 30.000h/Class A condenser
Condensing air temp. probe
Refrigerant circuit gas temp. probe
Water temperature probe
M0R940E13-00 WSAN-XIN 21-141 51
10 Decommissioning
10.1 Disconnecting
Only authorised personnel must disconnect the unit.
Avoid leak or spills into the environment.
Before disconnecting the unit, the following must be recovered, if present:
refrigerant gas
•
anti-freeze solutions in the hydraulic circuit
•
Awaiting dismantling and disposal, the unit can also be stored outdoors, as bad weather and rapid changes in temperature will not cause damage to the environment, if electric, cooling and hydraulic circuits of the unit are integral and closed.
10.2 Dismantling and disposal
The unit must always be sent to authorised centres for dismantling and disposal.
When dismantling the unit, the fan, the motor and the coil, if operating, may be recovered by the specialist centres for reuse.
All the materials must be recovered or disposed of in compliance with the corresponding national standards in force.
For further information on the decommissioning of the unit, contact the manufacturer.
10.3 Directive EC RAEE
The units covered by the legislation in question are marked with the symbol on the side.
With the aim of protecting the environment, all of our units are produced in compliance with Directive EC on waste electrical and electronic equipment (RAEE).
The potential eects on the environment and on human health due to the presence of hazardous substances are shown in the use and maintenance manual in the section on residual risks.
Information in addition to that indicated below, if required, can be obtained from the manufacturer/distributor/importer, who are responsible for the collection/handling of waste originating from equipment covered by EC-RAEE. This information is also available from the retailer who sold this appliance or from the local authorities who handle waste.
Directive EC-RAEE requires disposal and recycling of electrical and electronic equipment as described therein to be handled through appropriate collection, in suitable centres, separate from collection for the disposal of mixed urban waste.
The user must not dispose of the unit at the end of its life cycle as urban waste, it must instead be handed over to appropriate collection centres as set forth by current standards or as instructed by the distributor.
52 WSAN-XIN 21-141 M0R940E13-00
11 Residual risks
General description
In this section the most common situations are signalled,as these cannot be controlled by the manufacturer these could be a source of risk situations for people or things. Danger zone This is an area in which only an authorised operator may work. The danger zone is the area inside the unit which is accessible only with the deliberate removal of protections or parts thereof.
Handling
The handling operations, if implemented without all of the protec­tion necesssary and without due caution, may cause the fall or the tipping of the unit with the consequent damage, even serious, to persons, things or the unit itself. Handle the unit following the instructions provided in the present manual regarding the packaging and in compliance with the local regulations in force. Should the gas refrigerant leak please refer to the refrigerant “Safety sheet”.
Installation
An incorrect installation of the unit could cause water leaks, conden­sate accumulation, leaking of the refrigerant, electric shock, bad functioning or damage to the unit itself. Check that the installation has been implemented by qualied technical personnel only and that the instructions contained in the present manual and the local regulations in force have been adhered to. The installation of the unit in a place where even infrequent leaks of inammable gas and the accumulation of this gas in the area sur­rounding the area occur could cause explosions or res. Carefully check the positioning of the unit. The installation of the unit in a place unsuited to support its weight and/or guarantee adequate anchorage may cause the fall or the tipping of the unit with the consequent damage to things, people or the unit itself. Carefully check the positioning and the anchoring of the unit. Easy access to the unit by children, unauthorised persons or animals may be the source of accidents, some serious. Install the unit in areas which are only accessible to authorised person and/or provide protection against intrusion into the danger zone.
General risks
Smell of burning, smoke or other signals of serious anomalies may indicate a situation which could cause damage to people, things or the unit itself. Electrically isolate the unit (yellow-red isolator). Contact the authorised service centre to identify and resolve the problem at the source of the anomaly. Accidental contact with exchange batteries, compressors, air deliv­ery tubes or other components may cause injuries and/or burns. Always wear suitable clothing including protective gloves to work inside the danger zone. Maintenance and repair operations carried out by non-qualied personnel may cause damge to persons, things or the unit itself. Always contact the qualied assistance centre. Failing to close the unit panels or failure to check the correct tightening of all of the panelling xing screws may cause damage to persons, things or the unit itself. Periodically check that all of the panels are correctly closed and xed. If there is a re the temperature of the refrigerant could reach values that increase the pressure to beyond the safety valve with the consequent possible projection of the refrigerant itself or explosion of the circuit parts that remain isolated by the closure of the tap. Do not remain in the vicinity of the safety valve and never leave the refrigerating system taps closed.
Electric parts
An incomplete attachment line to the electric network or with incor­rectly sized cables and/or unsuitable protective devices can cause electric shocks, intoxication, damage to the unit or res. Carry out all of the work on the electric system referring to the electric layout and the present manual ensuring the use of a system thereto dedicated. An incorrect xing of the electric components cover may favour the entry of dust, water etc inside and may consequently can electric shocks, damage to the unit or res. Always x the unit cover properly. When the metallic mass of the unit is under voltage and is not correctly connected to the earthing system it may be as source of electric shock and electrocution. Always pay particular attention to the implementation of the earth­ing system connections. Contact with parts under voltage accessible inside the unit after the removal of the guards can cause electric shocks, burns and electrocution. Open and padlock the general isolator prior to removing the guards and signal work in progress with the appropriate shield. Contact with parts that could be under voltage due to the start up of the unit may cause electric shocks, burns and electrocution. When voltage is necessary for the circuit open the isolator on the attachment line of the unit itself, padlock it and display the appro­priate warning shield.
Moving parts
Contact with the transmissions or with the fan aspiration can cause injuries. Prior to entering the inside of the unit open the isolater situated on the connection line of the unit itself, padlock and display the suitable sign. Contact with the fans can cause incurie. Prior to removing the protective grill or the fans, open the isolator on the attachment line of the unit itself, padlock it and display the appropriate warning sign.
Refrigerant
The intervention of the safety valve and the consequent expulsion of the gas refrigerant may cause injuries and intoxication. Always wear suitable clothing including protective gloves and eyeglasses for operations inside the danger zone. Should the gas refrigerant leak please refer to the refrigerant “Safety sheet”. Contact between open ames or heat sources with the refrigerant or the heating of the gas circuit under pressure (e.g. during welding operations) may cause explosions or res. Do not place any heat source inside the danger zone. The maintenance or repair interventions which include welding must be carried out with the system o.
Hydraulic parts
Defects in tubing, the attachments or the cut-o parts may cause a leak or water projection with the consequent damages to peopl, things or shortcircuit the unit.
M0R940E13-00 WSAN-XIN 21-141 53
12 Dimensional drawings
12.1 Size 21-31-41
1. Antivibration xing holes
2. (16)drill holes for lifting
3. GENERAL ELECTRICAL PANEL
4. Power line input
5. control keypad
6. GAS F 1” internal exchanger water inlet
7. GAS F 1” internal exchanger water inlet
8. Condensate discharge
9. Clearance access recommended
Size 21 31 41
Length mm 895 895 895
Depth mm 378 378 378
Height mm 992 992 992
W1 kg 37 38 40
W2 kg 17 18 20
W3 kg 39 40 42
W4 kg 19 20 22
Operating weight kg 112 116 124
Shipping weight kg 110 114 122
54 WSAN-XIN 21-141 M0R940E13-00
12.2 Size 51-71
1. Antivibration xing holes
2. (16)drill holes for lifting
3. GENERAL ELECTRICAL PANEL
4. Power line input
5. control keypad
6. GAS F 1” internal exchanger water inlet
7. GAS F 1” internal exchanger water inlet
8. Condensate discharge
9. Clearance access recommended
Size 51 71
Length mm 1038 1038
Depth mm 410 410
Height mm 1234 1234
W1 kg 51 53
W2 kg 32 33
W3 kg 53 55
W4 kg 34 34
Operating weight kg 170 175
Shipping weight kg 168 173
M0R940E13-00 WSAN-XIN 21-141 55
12.3 Sizes 81-91-101
1. Compressor compartment
2. GENERAL ELECTRICAL PANEL
3. control keypad
4. Power line input
5. Clearance access recommended
6. Electric fan
7. GAS F 1” internal exchanger water inlet
8. GAS F 1” internal exchanger water inlet
9. Condensate discharge
10. Antivibration xing holes
11. (16)drill holes for lifting
Size 81 91 101
Length mm 1685 1685 1685
Depth mm 629 629 629
Height mm 1137 1137 1137
W1 kg 65 65 65
W2 kg 35 35 35
W3 kg 85 85 85
W4 kg 55 55 55
Operating weight kg 240 240 240
Shipping weight kg 250 250 250
56 WSAN-XIN 21-141 M0R940E13-00
12.4 Sizes 121-131-141
1. Compressor compartment
2. GENERAL ELECTRICAL PANEL
3. control keypad
4. Power line input
5. Clearance access recommended
6. Electric fan
7. GAS F 1” internal exchanger water inlet
8. GAS F 1” internal exchanger water inlet
9. Condensate discharge
10. Antivibration xing holes
11. (16)drill holes for lifting
Size 121 131 141
Length mm 1685 1685 1685
Depth mm 629 629 629
Height mm 1517 1517 1517
W1 kg 70 70 70
W2 kg 55 55 55
W3 kg 110 110 110
W4 kg 75 75 75
Operating weight kg 310 310 310
Shipping weight kg 320 320 320
M0R940E13-00 WSAN-XIN 21-141 57
13 Technical information
13.1 General technical data
Size 21 31 41 51 71 81 91 101 121 131 141
Radiant panels
Heating
Heating capacity 1 kW 5,41 6,81 8,70 11,9 14,3 16,5 18,4 19,6 23,8 26,4 30,3
Total power input 2 kW 1,35 1,71 2,22 2,98 3,61 4,44 4,99 5,22 6,64 7,19 8,31
COP (EN 14511:2011) 3 4,00 3,98 3,93 3,98 3,96 3,72 3,70 3,76 3,58 3,67 3,65
Cooling
Cooling capacity 6 kW 4,25 6,34 8,07 10,3 13,0 15,9 17,6 19,4 25,4 28,3 32,1
Total power input 2 kW 1,14 1,74 2,16 2,82 3,50 4,53 4,88 5,52 7,41 8,27 9,60
EER (EN 14511:2011) 7 3,73 3,65 3,73 3,67 3,72 3,52 3,62 3,53 3,43 3,43 3,34
ESEER 8 5,14 5,53 5,55 5,28 6,02 5,48 5,73 5,89 5,22 5,24 5,74
Water ow-rate 6 l/s 0,20 0,30 0,38 0,49 0,62 0,75 0,85 0,92 1,20 1,34 1,52
Useful pump discharge head
Heating
Heating capacity 4 kW 5,19 6,54 8,25 11,5 13,8 16,2 18,5 20,4 25,8 28,2 31,5
Total power input 2 kW 1,66 2,09 2,65 3,64 4,42 5,43 6,23 7,17 8,91 9,81 11,4
COP (EN 14511:2011) 3 3,12 3,14 3,11 3,15 3,12 2,98 2,97 2,85 2,89 2,88 2,77
Cooling
Cooling capacity 9 kW 3,88 5,24 6,11 8,84 11,7 15,5 16,8 19,5 24,0 26,6 29,1
Total power input 2 kW 1,52 2,04 2,32 3,35 4,45 5,91 6,37 8,37 10,3 11,5 13,4
EER (EN 14511:2011) 7 2,55 2,57 2,63 2,64 2,63 2,62 2,64 2,33 2,33 2,32 2,18
ESEER 10 3,82 3,71 3,47 4,06 4,43 4,17 4,36 4,3 3,84 4,03 4,23
Water ow-rate 9 l/s 0,18 0,25 0,29 0,42 0,55 0,73 0,82 0,92 1,14 1,26 1,38
Useful pump discharge head
Heating
Heating capacity 5 kW 5,05 6,39 8,03 11,0 13,3 15,2 17,7 19,9 24,0 26,6 29,9
Total power input 2 kW 2,01 2,51 3,25 4,42 5,39 6,56 7,56 8,83 11,1 11,8 13,7
COP (EN 14511:2011) 3 2,52 2,55 2,47 2,50 2,47 2,31 2,34 2,25 2,17 2,25 2,18
Water ow-rate 5 l/s 0,12 0,15 0,19 0,27 0,32 0,36 0,42 0,48 0,57 0,64 0,71
Useful pump discharge head
Compressor
Type of compressors Rotary inverter dc Scroll inverter DC
Refrigerant R-410A
No. of compressors No 1 1 1 1 1 1 1 1 1 1 1
Oil charge l 0,35 0,35 0,87 1,7 1,7 1,9 1,9 1,9 1,9 1,9 1,9
Refrigeration circuits No 1 1 1 1 1 1 1 1 1 1 1
Utility side exchanger
Type of internal ex­changer
No. of exchangers No 1 1 1 1 1 1 1 1 1 1 1
Water content l 0,56 0,64 0,64 1,14 1,8 2,37 2,37 2,37 3,13 3,13 3,13
External Section Fans
Type of fans 12 AX AX AX AX AX AX AX AX AX AX AX
No. of fans No 1 1 1 2 2 1 1 1 2 2 2
Standard air ow l/s 653 1028 1028 2056 1996 2222 2306 2444 2778 3056 3172
Installed unit power kW 0,12 0,15 0,15 0,15 0,15 0,45 0,41 0,4 0,5 0,47 0,44
6 kPa 57 49 56 53 61 79
elforoom and elfospace terminal units
9 kPa 59 54 65 60 71 80 77 73 86 62 56
Radiators
5 kPa 58 54 65 64 94 104 101 99 86 85 82
11 PHE
76 73 84 58 49
58 WSAN-XIN 21-141 M0R940E13-00
Size 21 31 41 51 71 81 91 101 121 131 141
Hydraulic circuit
Maximum water side pressure
kPa 550 550 550 550 550 550 550 550 550 550 550
Safety valve calibration kPa 600 600 600 600 600 600 600 600 600 600 600
Min. installation water contents
l 17 20 25 33 40 50 53 57 63 68 74
Power supply
Standard power supply 230/1/50 400/3/50+N
1. Entering/leaving water temperature user side 30/35°C, external exchanger entering air temperature 7 °C (R.H. = 85%)
2. The overall power absorbed is calculated by adding the power absorbed by the compressor + the power absorbed by the fans + the power absorbed by the auxiliary electrical circuit + the percentage value of the pump to overcome pressure drops inside the unit
3. COP (EN 14511:2008) performance coecient in heating mode. Ratio between heating capacity supplied and absorbed power in accordance with EN 14511:2008. The absorbed power is the sum of the power absorbed by the compressor + electric auxiliary circuit + percentage of power absorbed by the pump to prevent pressure drops inside the unit
4. Entering/leaving water temperature user side 40/45°C, external exchanger entering air temperature 7 °C (R.H. = 85%)
5. Entering/leaving water temperature user side 45/55°C, external exchanger entering air temperature 7°C (R.H. = 85%)
6. User side entering/leaving water temperature 23/18°C, external exchanger entering air 35°C
7. EER (EN 14511:2011) performance coecient in cooling mode. Ratio between cooling capacity provided and power absorbed in compliance with EN 14511:2011. The absorbed power is the sum of the power absorbed by the compressor + power absorbed by the fans + the power absorbed by the electric auxiliary circuit + the percentage value of the pump to overcome pressure drops inside the unit
8. ESEER calculated by Clivet for radiant systems with water produced at 18°C by taking into account the load conditions and source water temperature as dened by EUROVENT for water at 7°C
9. User side entering/leaving water temperature 12/7 °C, external exchanger entering air 35°C
10. ESEER calculated by EUROVENT, for systems featuring terminal units with water produced at 7°C
11. PHE = plate exchanger
12. AX = axial fan
13.2 Operating range
Cooling
Twu [°C] = exchanger water outlet temperature Eat [°C]: external exchanger inlet air temperature
1. Normal operating range
2. Operating range with modulating fans
3. Operating range where the use of ethylene glycol is mandatory in
Heating
Twu [°C] = exchanger water outlet temperature Eat [°C]: external exchanger inlet air temperature
1. Normal operating range
relation to the temperature of the water at the outlet of the user side exchanger
4. Operating range with modulating compressor
2. Operating range with modulating compressor
3. Operating range with modulating fans
M0R940E13-00 WSAN-XIN 21-141 59
13.3 Sound levels
Sound power level
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
21 73 73 70 65 63 59 51 36 49 64 31 76 70 65 60 58 53 46 48 49 64 41 76 71 66 61 59 54 47 49 49 64
51 76 71 69 66 63 58 50 39 53 68 71 77 71 69 67 63 59 50 40 54 69 81 83 77 69 61 63 67 60 61 56 72 91 84 79 70 62 64 67 60 61 56 72
101 86 81 72 62 65 67 60 61 57 73 121 81 73 67 61 63 67 61 61 55 71 131 85 76 70 61 64 67 61 61 56 72 141 86 79 72 63 65
Sound levels refer to units with full load under nominal test conditions. The sound pressure level refers to a distance of 1m from the outer surface of the unit operating in an open eld. Noise levels are determined using the tensiometric method (UNI EN ISO 9614-2) Data referred to the following conditions: utility side exchanger water inlet/outlet 12/7°C source side exchanger water inlet/outlet 30/35℃
Octave band (Hz)
68 61 62 57 73
Sound pres-
sure level
Sound power
level
13.4 Admissible water ow rates
Min. (Qmin) and max. (Qmax) water ow-rates admissibles for the correct unit operation.
Size 21 31 41 51 71 81 91 101 121 131 141 Minimum ow [l/s] 0,15 0,18 0,18 0,23 0,34 0,32 0,32 0,32 0,45 0,45 0,45 Maximum ow-rate [l/s] 0,90 0,90 0,90 1,10 1,50 1,70 1,70 1,70 1,90 1,90 1,90
13.5 Unit without hydronic system
Exchanger pressure drop limit. Warning: don’t use over this limit.
unit without hydronic assembly Dp = pressure drop Q = water ow
Exchamger pressure drop limit. Warning: don’t use below this limit.
60 WSAN-XIN 21-141 M0R940E13-00
13.6 Unit with hydronic system - option
13.7 Unit with EC high eciency circulating group - optional
Available pressure curves with high-eciency circulator
Available pressure curves with hydronic assembly
DP [kPa] = Available pressure Q [l/s] = water ow rate
the heads are intended as available at the unit connections
High-eciency circulator absorption curves
M0R940E13-00 WSAN-XIN 21-141 61
14 Accessories
VERSIONS
H High energy eciency
CONFIGURATIONS
400TN Supply voltage 400/3/50+N
230M Supply voltage 230/1/50
HYDRAULIC CIRCUIT
ACS5SX
ACS300X
ACS500X
ACS3SX
3DHWX
- Hydronic group utility side: not required
KSAX
KTFL2X
KTFL1X
CMACSX
SYSTEM ADMINISTRATORS
CMSC2X
ELECTRIC CIRCUIT
RCTX
INSTALLATION
AMRX
500 litres domestic hot water tank with solar coil Accessory separately supplied
300 litres domestic hot water tank Accessory separately supplied
500 litres domestic hot water tank Accessory separately supplied
300 litres domestic hot water tank with solar coil Accessory separately supplied
Three-way valve for domestic hot water Accessory separately supplied
100 litres hydraulic breaker Accessory separately supplied
Water connection hoses with 1 1/4” connections Accessory separately supplied
Water connection hoses with 1” connections Accessory separately supplied
Domestic hot water module Accessory separately supplied
Serial communication module with RS485 serial converter kit Accessory separately supplied
Remote control Accessory separately supplied
Rubber antivibration mounts Accessory separately supplied
62 WSAN-XIN 21-141 M0R940E13-00
14.1 RCTX - Remote control
QG Electrical panel XT1 Terminal block of the customer connections AP7 Room keypad
A Max. = 100 mt.
Cable section: Min. 0,35 Max.1 mm2
LAN net: A + B = 100 mt. Max AMACSX - Domestic hot water module
M0R940E13-00 WSAN-XIN 21-141 63
14.2 CMSC2X - Serial communication module with RS485 serial converter kit
1 Install the AP6 converter
2 Connect TTL serial
3 Wire as indicated in the wiring diagram.
Supervisory
The unit can be connected to an external supervisory system.
Enable the function:
Par: CF01 protocol selection
0 = Disabled
1 = Modbus
Parameter modication
Main menuParametersCFCF01
Parameter Description Range
CF30
CF31 BaudRate Baud Rate (0=1200 / 1=2400 / 2=4800 / 3=9600 / 4=19200) supervision serial
address
Modbus
1....255
Cable characteristics
Couple of conductors twisted and shielded
Section of conductor 0,22mm2…0,35mm2
Nominal capacity between conductors < 50 pF/m
Nominal impedance 120 Ω
Recommended cable Belden 3105A or others with equal properties
64 WSAN-XIN 21-141 M0R940E13-00
14.3 AMACSX - Domestic hot water module
Domestic hot water module
1
L.300 x P.220 x H.120
Water temperature probe
2
cable length 5 mt
BT7
B Max. = 100 mt.
Cable section: Min. 0,35 Max.1 mm2
C Electric heater provided by the customer D 3-way valve
(accessory 3DHWX)
LAN net: A + B = 100 mt. Max AMACSX - Domestic hot water module
The resistance R can operate simultaneously to the compressor.
For example:
antilegionella scheduling
•
BT7 < (setpoint ACS - 19°C)
•
M0R940E13-00 WSAN-XIN 21-141 65
E CMACSX - 230/1/50 - PER90001 Y VACS DHW valve
(accessory 3DHWX)
F CMACSX - 400/3/50+N - PER90003 BT7 DHW storage probe QG Electrical panel
Heat pump
R6 Electric heaters of the DHW storage
(provided by the Customer)
XT1 Terminal block of the customer connections ST Storange high temperature safety thermostat B LAN serial: L max = 100 mt
Cable section: Min. 0,35 Max.1 mm2
66 WSAN-XIN 21-141 M0R940E13-00
14.4 Boiler management
Indicative diagram - see wiring diagram
A Domestic hot water module L.300 x P.220 x H.120 B Temperature probe domestic hot water cable length 5 mt
C Boiler provided by the Customer
D 3-way DHW valve accessory YVACS
E 3-way valve accessory YVACS
F 1° setpoint control On-o (on = 1°setpoint, o = boiler o) G 2° setpoint control (2 setpoint>1 setpoint) On-o (on = 2° setpoint) H max 100 mt Min. 0,35 Max.1 mm2
I Control F delay respect to control E
Enable boiler:
par br00 = 3
•
Setpoint (C) < heat pump operation range
ON control F = ON control E+ 30 sec.
A Boiler in integration to the heat pump B Boiler replacing the heat pump
Based on the system water temperature / domestic hot water Br02 = 0 (Factory value)
Main menu
Parameters→br Main menu
Based on the outdoor air temperature Enable the function: HP00=1
Parameters
HP
M0R940E13-00 WSAN-XIN 21-141 67
15 Alarms - Stata
15.1 Alarms
Before resetting an alarm identify and remove its cause.
Repeated resets can cause irreversible damage.
Code Description Type E000 General alarm AUTO E001 High pressure (digital) circuit 1 * E003 High pressure (analogical) circuit 1 * E007 Low pressure (analogical) circuit 1 * E010 Inverter alarm * E020 Primary circuit ow switch Time E030 Primary circuit antifreeze AUTO E035 Primary circuit output high temperature AUTO E045 Faulty clock error AUTO E046 Error: Clock to set AUTO
E047
E048 Anti-legionella AUTO E060 Faulty water temperature probe or primary exchanger input AUTO E061 Faulty water temperature probe or primary exchanger output AUTO E062 Faulty exchanger temperature probe AUTO E065 Faulty ambient keyboard temperature probe AUTO E066 Faulty DHW temperature probe AUTO E068 Faulty external temperature probe AUTO E069 Faulty high pressure input circuit 1 AUTO E071 Faulty compressor discharge temperature probe AUTO E080 Conguration error AUTO E081 Signalling of compressor operating hour exceeding Manual E085 Signalling of primary circuit pump operating hour exceeding Manual E090 Signalling of alarm log record exceeding Manual
Error of LAN communication between main module and electronic thermostatic module or ambient keyboard (if pre­sent) or DHW module (if present)
A = AUTOMATIC reset
M = MANUAL reset
* after some interventions is necessary the manual reset
AUTO
15.2 Electronic thermostatic driver alarm
Code Description Type E101 Faulty low pressure trasducer - dAI1 AUTO E102 Faulty low pressure temperature probe - dAI2 AUTO E103 Faulty discharge temperature probe - dAI3 probe AUTO E106 Saturation output error AUTO E107 MOP alarm AUTO E108 Signalling of valve max opening AUTO E110 NO link alarm AUTO E111 Excessive current draw * Manual E112 Winding 1 disconnection * Manual E113 Winding 1 short circuit * Manual E114 Winding 2 disconnection * Manual E115 Winding 2 short circuit * Manual
A = AUTOMATIC reset
* Switch on and o the electronic thermostatic driver
68 WSAN-XIN 21-141 M0R940E13-00
15.3 Led inverter
The access is riserve to the service centres.
Danger of electrocution.
Led:
ON: normal operating
Slow ashing (ON 1sec.,OFF 0.5 sec.): stanby compressor stopped
Fast ashing (ON 0.2 sec.,OFF 0.2 sec.): in alarm.
15.4 Stata
Main menuSETAi, di, AO, dOAi L1
Menu Code Description
AiE1 DHW temperature Ai L1 Primary outlet temperature Ai L2 Primary inlet temperature Ai L3 Coil temperature
Ai
of
AO
dO
E1
Sr Actual Setpoint: setpoint with compensation / operating limit
Hr
Ai L4 High pressure transducer Ai L5 Outside temperature 1Ai 1 Low pressure transducer (thermostatic sensor on the driver) 1Ai 2 Return temperature (thermostatic sensor on the driver) 1Ai 3 Discharge temperature (thermostatic sensor on the driver) di L1 High pressure di L2 Compressor Alarm di L3 Flow utility side di L4 Remote On-O di L5 Remote Heat/Cool
AO L1 Primary pump (it is a digital 0/1) AO L2 Fan signal (standard version) AO L3 Compressor signal AO L4 Primary pump signal (if in variable ow ) AO L5 Fan signal (High-eciency version)
dOE1 DHW heater (if present)
dO L1 DHW valve dO L2 Reversing valve refrigerant circuit dO L3 Frost Heater dO L4 Auxiliary heater dO L5 Compressor start dO L6 Cumulative alarm
1rE1 Superheating temperature
1rE2 Condensing saturate temperature
1rE5 Superheating
1rE6 Gas pressure (=1Ai1)
1rE7 Opening percentage electronic thermostatic valve 1SP4 Superheating Setpoint
CP01 Hours compressor: dozens
PU01 Hours utility pump: dozens
M0R940E13-00 WSAN-XIN 21-141 69
70 WSAN-XIN 21-141 M0R940E13-00
Page intentionally left blank
71
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy Tel. + 39 0439 3131 - Fax + 39 0439 313300 - info@clivet.it
CLIVET ESPAÑA S.A.
Parque Empresarial Villapark, Avda. Quitapesares 50 - 28670, Villaviciosa de Odón, Madrid - España Tel. + 34 91 6658280 - Fax + 34 91 6657806 - info@clivet.es
CLIVET UK LTD
4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - info@clivet-uk.co.uk
CLIVET NEDERLAND B.V.
Siliciumweg 20a, 3812 SX Amersfoort - Netherlands Tel. + 31 (0) 33 7503420 - Fax + 31 (0) 33 7503424 - info@clivet.nl
CLIVET GmbH
Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - info.de@clivet.com
CLIVET RUSSIA
Elektrozavodskaya st. 24, oce 509 - 107023, Moscow, Russia Tel. + 74956462009 - Fax + 74956462009 - info.ru@clivet.com
CLIVET MIDEAST FZCO
Dubai Silicon Oasis (DSO), High Bay Complex, Ind Unit No. 3 - PO Box 28178 - DUBAI, UAE Tel. + 97 14 3208499 - Fax + 97 14 3208216 - info@clivet.ae
CLIVET AIRCONDITIONING SYSTEMS (P) LTD
3C3, Gundecha Onclave, Kherani Road, Saki Naka, Andheri (East), Mumbai 400 072 (INDIA) Tel. + 91 - 22 - 6193 7000 - Fax + 91 - 22 - 6193 7001 - sales.india@clivet.com
www.clivet.com
Loading...