CLIVET WSAN-XEE Series, WSAN-XEE 82, WSAN-XEE 182, WSAN-XEE 102, WSAN-XEE 222 Installation, Use And Maintenance Manual

...
Page 1
WSAN-XEE 82 - 302
Installation use and maintenance manual
M6G240F7-05
17-12-2013
Page 2
Dear Customer, We congratulate you on choosing these product. Clivet is being working for years to offer systems able to assure the maximum
comfort for long time with high reliability, efficiency , quality and safety. The target of the company is to offer advanced systems, that assure the best com­fort, reduce the energy con-sumption, the installation and maintenance costs for all the life-cycle of the system.
With this manual, we want to give you information that are useful in all the phases: from the reception, to the installation and use until the disposal so that a system so advanced offers the best procedure of installation and use.
Best regards and have a nice reading ! CLIVET Spa
2
Page 3
INDEX
General
1
Reception
2
Positioning
3
Water connections
4
Electrical connections
5
Start-up
6
Regulation
7
Maintenance
8
Technical information
9
4
7
8
9
11
16
20
27
29
10
11
Disposal
Residual risks
36
37
The data contained in this bulletin is not binding and may be changed by the
manufacturer without prior notice. Reference technical bulletin : BT07F009GB-10
3
Page 4
1 - GENERAL
1.1 MANUAL
The manual provides correct unit installation, use and maintenance.
Pay particolar attention to:
Warning identifies particularly important operations or information .
Prohibited operations that must not be carried out, that compromise the operating of the equipment or may cause damage to persons or things.
It is advisable to read it carefully so you will save time
during operations.
Follow the written indications so you will not cause
damages to things and injuries people. The preliminary information must be read prior to carrying out any of the following operations.
1.2 GENERAL INSTRUCTIONS Preliminaries
The positioning, hydraulic system, refrigerating, electrics and the channelisation of the air must be determined by the system designer in accordance with local regulations in force.
Only qualified personnel can operate on the unit, as required by the regulation in force.
Using the unit in case of breakdown or malfunction :
voids the warranty
may compromise the safety of the machine
may increase time and repair costs.
Follow local safety regulations. .
Keep packing material out of children’s reach it may be dangerous. .
Recycle and dispose of packing material in conformity with local regulations. .
Risk situations
The unit has been designed and created to prevent injures to people.
During designing it is not possible to plane and operate on all risk situation.
Read carefully "Residual risk" section where all situation which may cause damages to things and injuries to people are reported.
Installation, starting, maintenance and repair required specific knowledge; if they are carried out by inexperienced personnel, they may cause damages to things and injuries people.
Intended use
Use the unit for cooling/heating water or a water and glycol mix for air-conditioning only, within limits defined in the technical bulletin and on this manual..
Any use other than intended does not involve the manufacturer in any commitment or obligation. .
Installation
Verify that the electrical line characteristics are in compliance with data quotes on the unit serial number label.
Maitenance
Plan periodic inspection and maintenance in order to avoid or reduce repairing costs.
Turn the machine off before any operation.
Modification
All unit modifications will end the warranty coverage and the manufacturer responsibility. .
Breakdown/Malfuction
Disable the unit immediately in case of breakdown or malfunction. .
Contact a constructor certified assistance service.
Use original spares parts only.
User training
The installer has to train the user on :
start-up / shutdown;
set points change;
standby mode;
maintenance;
what to do / what not to do in case of breakdown.
Data update
Continual product improvements may imply manual data changes .
Visit manufacturer web site for updated data
1.3 INDICATIONS FOR THE USER
Keep this manual with the wiring diagram in an accessible place for the operator.
Note the unit lable data so you can provide them at the assi­stance centre in case of intervention (see "Unit identification" section).
Provide a machine notebook that allows any interventions carried out on the machine to be noted and tracked making it easier to suitably note the various interventions and aids the search for any breakdowns.
In case of breakdown or malfunction:
.
immediately deactivate the unit .
contact a assistance service centre authorized by the
manifacturer.
use original spares parts only
Ask the installer to format on:
start-up / shutdown;
set points change;
standby mode;
maintenance;
what to do / what not to do in case of breakdown.
4
Page 5
1.4 UNIT INDENTIFICATION
1 - GENERAL
Serial number label
The serial number label is positioned on the unit and allows to indentify all the unit features.
It has not to be removed for any reason.
It reports the regulations indications such as:
machine type, exmple:
Series WSAN-XEE Size 82
serial number
12 characters Axxxxxxxxxxx
year of manufacture
wiring diagram number
electrical data
manufacturer logo and address .
Serial number It identifies uniquely each machine.
It identifies specific spare parts for the machine. Assistance request
Note data from the serial number label and write them in the
chart on side, so you will find them easily when needed.
In case of intervention you have to provide data.
Serie
2
5
WINTER : the cooling cycle makes it possible to absorb energy (heat at low temperature) from the external environment and to transfer it to the area to be heated.
1. The compressor compresses the refrigerant fluid, placing it at high pressure and high temperature.
2. The 4-way valve reverses the flow with respect to respect to SUMMER operation.
3. In the plate exchanger, the water that returns to the system absorbs heat from the refrigerant.
4. As it cools, the refrigerant condenses and becomes liquid.
5. The expansion valve causes a sudden drop in the pressure of the refrigerant, which becomes very cold as its volume increases.
6. In the external coil, the cold refrigerant evaporates and ab­sorbs heat from the external air. In this phase, as the coil cools, it may freeze. This is why the cycle is automatically reversed periodically for a short time so as to defrost it
1a
6
1b
4
3
Size
Serial number
Year of manufacture
Wiring diagram
1.5 PRINCIPLE OF OPERATION
SUMMER: the cooling cycle allows the transfer of excess indoor heat to the external environment.
1. The compressor compresses the refrigerant gas, placing it at high pressure and high temperature.
2. In the external coil, the refrigerant is cooled, and the heat is released into the environment by means of the fan. This is why the coil needs to be kept clean and free of obsta­cles.
3. When it cools, the refrigerant becomes liquid.
4. The expansion valve causes a sudden drop in the pres­sure of the refrigerant, which becomes very cold as its volume increases.
5. In the exchanger, the refrigerant evaporates and absorbs the heat from the water that returns to the system, cooling it.
2
3
1a
7
1b
4
5
6
5
Page 6
1 - GENERAL
1.6 ACCESSORIES
VERSIONS OPTIONS D Partial energy recovery B Water low temperature CONFIGURATIONS DSPB Double set point for water low temperature REFRIGERANT CIRCUIT CCCA Copper / aluminium condenser coil with acrylic lining CCCA1 Copper / aluminium condenser coil with Fin Guard
treatment (Silver)
MHP High and low pressure gauges MHPX High and low pressure gauges OHP Operation in heat pump OHO Heat-only function HYDRAULIC CIRCUIT
- Hydronic group utility side: not required
1PUS Standard pump 1PUR Single-pump with reduced available head 1PUM Single-pump with larger available head 2PUS Standard double pump 2PUR Double pump with reduced available head 2PUM Double pump with larger available head IFWX Water steel mesh strainer ACC1 Teflon steel storage device SYSTEM ADMINISTRATORS CMMBX Serial communication module to supervisor
(MODBUS)
CMSC9 Serial communication module to Modbus supervisor CMSC7 Modbus/LON WORKS serial converter kit ELECTRIC CIRCUIT RCMRX Remote control via microprocessor control PCDWX Daily and weekly programming clock PM Phase monitor PMX Phase monitor SFSTR4N Disposal for inrush current reduction, for unit
400/3/50+N
PFCP Power factor correction capacitors (cosfi > 0.9) CLSE Free contacts for alarm SCP3X Set point compensation according to the outside en
thalpy
INSTALLATION AMRX Rubber antivibration mounts PGCEX Coil protection grilles external air side
X= Accessory separately supplied
6
Page 7
2- RECEPTION
2.1 PRELIMINARY INFORMATION
Operate in compliance with safety regulations in force .
For detailed information (dimensions, weight, technical cha­racteristics etc.) please refer to the “Technical information” section.
Use single protection devices : gloves, glasses ecc. .
2.2 DELIVERY CONTROL
Before accepting the delivery you have to check:
That the unit hasn’t been damaged during transport.
Check that the materials delivered correspond with that
indicated on the transport document comparing the data with the identification label ‘A’ positioned on the packa­ging.
In case of damage or anomaly:
Write down on the transport document the damage
you found and quote this sentence: "Conditional acceptance — clear evidence of deficiencies/ damages during transport".
Contact supplier and the carrier by fax and registered
mail with advice of receipt.
Any disputes must be made within the 8 days following the delivery. Complaints after this period are invalid..
A
2
1
1 safety rods 2 pins
B
2.3 STORING
Observe external packing instructions .
2.4 HANDLING
Verify unit weight and handling equipment lifting capacity .
Identify critical points during handling (disconnected routes, flights, steps, doors).
Before handling verify that the unit keeps its balance.
Use protection to avoid the unit damaging .
2.5 PACKING REMOVING
Be careful not to damage the unit.
Recycle and dispose of packing material in conformity with
local regulations.
7
Page 8
3 - POSITIONING
3.1 PRELIMINARY INFORMATION
Operate in compliance with safety regulations in force.
For detailed information (dimensions, weight, technical characteristics etc.) please refer to the TECHNICAL INFORMATION section.
Use single protection devices : gloves, glasses ecc.
During positioning consider these elements :
technical spaces required for the machine and system
place where the machine will be installed
electrical connections
water connections
air / aeraulic ducts
Do not considerer these elements could decrease performances and operational life of the unit.
3.2 FUNCTIONAL SPACES
Functional spaces are designed to:
guarantee good unit operation
carry out maintenance operations
protect authorized operators and exposed people
Respect all functional spaces indicated in the TECHNICAL INFORMATION section.
Double all functional spaces if two or more unit are aligned.
3.3 POSITIONING
Units are designed to be installed:
EXTERNAL
in fixed positions
Limit vibration transmission:
use antivibration devices on unit bearing points
install flexible joints on the hydraulic connections
Choose the installation place according to the following criteria:
Customer approval
safe accessible position
technical spaces requested by the unit
spaces for the air intake/exhaust
avoid flood-prone places
verify unit weight and bearing point capacity
verify that all bearing points are aligned and leveled
install the unit raised from the ground
max. distance allowed by the electrical connections
Prefer places where the unit doesn’t disturb the neighbours. Avoid installations next to bedrooms or windows. Avoid snow accumulations on batteries.
Protect the unit with an appropriate fencing to avoid the access to a not authorized personnel (babies, vandals etc.) A correct circulation of the air is indispensible to guarantee the good working order of the machine. Avoid therefore:
obstacles to the airflow;
exchange difficulties;
leaves or other foreign bodies that can obstruct the
exchange batteries;
winds that hinder or favour the airflow;
heat or pollution sources close to the unit (chimneys,
extractors etc);
stratification (cold air that stagnates at the bottom);
recirculation (expelled air that is sucked in again);
positioning below the level of the threshold, close to very
high walls, attics or in angles that could give rise to stratification or recirculation phenomenons.
Ignoring the previous indications could:
energy efficiency decrease;
blocks due to HIGH PRESSURE (in summer) or LOW
PRESSURE (in winter).
3.4 CONDENSATE WATER
When a heat pump is running it produces a considerable amount of water due to the defrosting cycles of the external coil.
The condensation must be eliminated in a manner to avoid wetting pedestrian areas.
With extensive very cold outdoor temperatures, condensation could freeze and block the flow, causing a slow build-up of ice; therefore special attention must be paid to eliminating condensation, raising the unit off the ground and evaluating whether antifreeze elements should be installed
3.5 FRESH AIR PROBE - OPTIONAL
The external probe allows to automatically change the unit set point according to the external enthalpy (temperature + humidity).
It is then possible to optimize the unit energy efficiency.
POSITIONING
The sensor should not be influenced by factors that can distort the reading (eg direct sunlight, air exhausted from the fan or other sources, contact with the unit structure or other heat sources, accumulations of snow / ice).
Examples to position the external probe :
A roof
B under a terrace
C if at free wall provide a
small roofing
NORD
A
B
C
8
Page 9
4 - WATER CONNECTIONS
4.1 PRELIMINARY INFORMATION
Selection and installation of system components must be carry out by installer.
Following you will find some indications to integrate with what is provided by the local regulations in force and by the good technical laws.
4.2 COMPONENTS
CUT-OFF VALVES
Installed at inlet and outlet (both on the water technique
circuit as well as that of the hot domestic water) allow maintenance operations without having to empty the system .
THERMOMETERS AND MANOMETERS
Installed at entry and exit of the main elements facilitate
inspection and maintenance.
AIR BLEED VALVE
Installed in all of the highest points of the system allowing
the venting of the circuits air..
DRAINAGE TAPS
Installed in the lowest points of the system to allow
bleeding.
EXPANSION TANK
It keeps a correct system pressure when the water
temperature changes. It must be dimensioned as a function of water plant volume and temperature.
WATER FILTER
If not present on-board the machine, must be installed
immediately in the water input of the unit, in a position that is easily accessible for cleaning.
The filter never should be removed, this operation
invalidates the guaranty
SUPPORTS
The hydraulic pipes weight mustn’t burden on the unit
connections ..
FLOW SWITCH
The flow switch must be present as a component of the
system
4.3 OPERATION SEQUENCE
1. Carefully wash the system with clean water: fill and drain
the system several times.
2. Apply additives to prevent corrosion, fouling, formation of
mud and algae.
3. Fill the plant
4. Execute leakage test.
5. Isolate the pipes to avoid heat dispersions and formation
of condensate.
6. Leave various point of service free (wells, vent-holes etc).
Neglecting the washing will lead to several filter cleaning interventions and at worst cases can cause damages to the exchangers and the other parts.
4.4 WATER QUALITY
The water quality is determined by the following factors, avoid therefore:
Inorganic salts
pH
Biological load (seaweeds etc)
Suspended solids
Dissolved oxygen
Water with inadequate characteristics can cause:
pressure drop increase
energy efficiency decrease
corrosive symptom increase
4.5 RISK OF FREEZE
If the unit or the relative water connections can be subject to temperatures close to 0°C adopt measures for prevent risk of freeze.
For example:
Mix water with ethylene glycol
Safeguard the pipes with heating cables placed under the
insulation
Empty the system in cases of long non-use and check that:
there are no closed taps present that could trap water
even after emptying
there are no low points in which water can stagnate
even after emptying; carry out any blowing required .
4.6 ANTI-FREEZE SOLUTION
Consider that the use of anti-freeze solution determines an increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not corrosive) and compatible with the hydraulic circuit components (pump etc).
Do not use different glicol mixture (i.e. ethylene with propylene)
4.7 WATER CONNECTIONS
Take away the supplied connection union by acting on the
connection joint.
Weld the union to the installation pipe.
Perform the connection between the installation pipe and
the evaporator, using the joint. Do not weld the system pipe with the connection joint atta­ched.
The rubber gasket might be irreparably damaged.
9
Page 10
4 - WATER CONNECTIONS
4.7 RECOMMENDED CONNECTION
5
1
P
4
2
3
7
6
9
8
F
10
8
P
12
11
1. Charged system pressure switch
2. vent
3. pump
4. expansion tank
5. safety valve
6. flow switch
7. pressure switch/thermometer
STANDARD HYDRAULIC CIRCUIT
13
7
14
8. filter
9. filling valve
10. antivibration joints
11. user side exchanger
12. Differential pressure switch
13. Discharge cock
14. inertial storage tank
water side safety valve
impurity trap with filter
centrifugal pump
antifreeze heater protection to pumping station
drain valve
4.8 WATER CIRCUIT EMPTYING
The unit is equipped with outlets for the pump emptying and storage.
Outlets are accessible from the rear side (left side in the fig­ure).
Storage content : size 82¸122 80 litres size 162¸302 130litres (optional)
4.9 RECOVERY EXCHANGER
OPTIONAL - The unit can be equipped with exchangers to recover the partial condensation heat.
The customer is responsible for the management of the circulation pump, valves, thermostats, etc
The recovery input water must not be below 25°C, in the event that, wrongful operations and breakages of the unit can occur .
Water connections must be performed carefully as for the evaporator (filter, circuit washing, etc) .
Perform all necessary interventions to avoid the RISK OF FREEZING (tubes insulation, emptying of circuit, addition of glycol, anti-freeze heaters) .
Water temperature can reach high temperatures (up to 100° C), therefore:
avoid the RISK OF BURNS by adopting the necessary
precautions (insulation of tubes, temperature detecting station on water if the sanitary use is foreseen, etc)
Install safety valves and specifically dimensioned
expansion tanks in the hydraulic circuit.
10
Page 11
5 - ELECTRICAL CONNECTIONS
5.1 PRELIMINARY INFORMATION
The characteristics of the electrical lines must be determined by specialized personnel able to design electrical installations; moreover, the lines must be in conformity with regulations in force. The protection devices of the unit power line must be able to stop the presumed short circuit current, whose value must be determined in function of system features. The power cables and the protection cable section must be defined in accordance with the characteristics of the protections adopted. All electrical operations should be performed by trained personnel having the necessary requirements by the regulations in force and being informed about the risks relevant to these activities. Operate in compliance with safety regulations in force .
5.2 ELECTRICAL DATA
The serial number label reports the unit specific electrical data, included any electrical accessories .
The electrical data indicated in the technical bulletin and in the manual refer to the standard unit, accessories excluded.
Refer to the electrical data report on the serial number label.
5.4 SIGNALS / DATA LINES
Do not overpass the maximum power allowed, which varies, according to the type of signal.
Lay the cables far from power cables or cables having a different tension and that are able to emit electromagnetic disturbances.
Do not lay the cable near devices which can generate electromagnetic interferences.
Do not lay the cables parallel to other cables; cable crossings are possible, only if laid at 90°.
Connect the screen to the ground, only if there aren’t disturbances
Guarantee the continuity of the screen during the entire extension of the cable.
Respect impendency, capacity and attenuation indications.
5.5 ELECTRIC LINES INLET
serial
number
label
F.L.A. full load ampere Full load current at max admissible conditions
F.L.I. Full load input Full load power input ( at max. admissible condition )
5.3 CONNECTIONS
1. refer to the unit electrical diagram (the number of the
diagram is shown on the serial number label)
2. verify that the network has characteristics conforming to
the data shown on the serial number label
3. Before starting work, verify that the sectioning device at
the start of the unit power line is open, blocked and equip­ped with cartel warning
4. Primarily you have to realize the earthing connection
5. Shelter the cables using adequate measure fairleads
6. Before power the unit, make sure that all the protections
that were removed during the electrical connection work have been restored.
VOLTAGE
FLA (A)
FLI (kW)
Fix the cables: if vacated may be subject to tearing.
The cable don't have to touch the compressor and the refrigerant piping ( they reach high temparatures ).
11
Page 12
5.6 ELECTRICAL PANEL
82 - 122
5 - ELECTRICAL CONNECTIONS
AP1 Main control module AP2 Local keyboard AP3 Expansion module AP5 RS 485 module AP11-12
162 - 302
Soft starter
QM1-2 Compressor motor overload cutout QM3-4 Overload cutout switch pump KM1-2 Compressor contactor KM3-4 Pump contactor QS1 main isolator switch
12
Page 13
5.7 CUSTOMER CONNECTIONS
5 - ELECTRICAL CONNECTIONS
BT6 outside air temperature probe
SQ1 flow switch
SA1 remote ON-OFF selector
SA2 remote summer-winter selector
SA3 remote 2nd setpoint selector
HL1 shut-down unit signal
HL2 operating unit signal
H% humodity control probe
AP7 remote keyboard
13
Page 14
5 - ELECTRICAL CONNECTIONS
A
A
5.8 SET POINT COMPENSATION WITH 4-20 MA SIGNAL (WATER RESET)
It optimizes the energetic efficiency of the unit by automatically changing the set-point according to an external signal of 4-20 ma type. It requests the expansion plug-in module option that must be fitted by the client (refer to the kit instructions) and enabled by parameter 140 = 1. This function must be enabled with parameter18 (=0 not enabled, =1 only summer, = 2 only winter, = 3 summer and winter)
par
18
19
20
21
22
23
24
140
description
WaterReset
MaxCWRH
SWRMAXH
SWRMinH
MaxCWRC
SWRMaxC
SWRMinC
PlugInEn
meaning value
Water Reset enabling 0=No 1=Cool 2=Heat 3=Always 0
Max. value of the Winter WR correction 10
Corresponding signal of the winter MAX. correction 4
Corresponding signal of the winter MIN. correction 20
Summer correction max. value 8
Corresponding signal of the summer MAX. correction 20
Corresponding signal of the summer MIN. correction 4
Enables PLUG-IN presence . 1=YES / 0=NO
SET POINT CURVE IN COOLING SET POINT CURVE IN HEATING
SET POINT
COMP.
=0
P 24
P 23
COMP.
MAX
= P22
m
SET POINT
COMP.
MAX
= P19
P 20
P 21
m
COMP.
= 0
5.9 SET POINT COMPENSATION ON THE TEMPERATURE OR EXTERNAL ENTHALPY
Optimises unit energy efficiency by automatically adjusting the set-point according to enthalpy or the external temperature. Requires the external humidity probe or the external temperature probe, which are optional for certain types of units and must be installed by the customer and enabled by parameters 152=1 and 156=1.
par
description
9 CompExt
10 CextMaxC
11 CextMinC
12 CextMaxH
13 CextMinH
14 MaxCExtC
15 MaxCExtH
16 HExtMinC
17 HExtMaxC
152 TextEn
156 URProbeExt
SET POINT CURVE IN COOLING SET POINT CURVE IN HEATING
COMP.
MAX
= P14
SET POINT
P 10 P 17
meaning value
COMP.
MAX
= P15
T EXT
0
15
30
15
0
8
10
10,5
13,5
External temp. comp. enabling 0=No 1=Cool 2=Heat 3=Always
Ext. Temp. max. summer correction
Ext. Temp. min. summer correction
Ext. Temp. max. winter correction
Ext. Temp. min. winter correction
Summer correction max. value
Winter correction max. value
Ext. enthalpy min. correction
Ext. enthalpy max. correction
EXT. Air probe presence 1=YES, 0=NO
Enables external UR% probe. 1=YES, 0=NO
P 13
SET POINT
P 12
P 11 P 16
COMP.=0
T EXT
COMP.
= 0
14
Page 15
5.10 RS485
CN1 CN1
TTL /
RS485
TTL /
RS485
gnd
gnd
5 - ELECTRICAL CONNECTIONS
TYPE OF NETWORK
The serial lines must be connected in bus typology, i.e. nodes to more points are not admitted
Supervisore
12 V AC
­+
12 V AC
­+
RS-232
­+
gnd
RS-485
OK
1918 20 21 2018 19 21
ALLE ALTRE
UNITA’
SHIELD
It must be connected to a ground without disturbances
Connected to round in only one point
Provide to the shield continuity during all the serial cable
extension.
Sistema di superv isione
NETWORK CABLE FEATURES
Couple of conductors twisted and shielded
Section of conductor 0.22mm
Nominal capacity between conductors < 50 pF/m
nominal impedance 120
Recommended cable BELDEN 3105A
2
…0,35mm2
NO !
Make the termination if the unit is the last of the network .
termination yes = dip ON
15
Page 16
6 - START-UP
PRELIMINARY CHECKS
To check before starting-up the unit .
For details refer to the different manual sections.
Preliminary checks - Unit OFF power supply
Access in safety
Functional clearances
Air flow : free return and supply (no bypass, no stratification)
Structure integrity
Fans run freely
Unit on vibration isolators
Unit input water filter + shut-off valves for cleaning
Vibration isolators on water connections
Expansion tank (indicative volume = 5% system content)
Cleaned system
Loaded system + possibile glicole solution + corrosion inhibitor
Under pressure system
Vented system
Refrigerant circuit visual check
Earthing connection
Power supply features
Electrical connections provided by the customer
Outside air temperature probe
16
Page 17
6 - START-UP
START-UP SEQUENCE
Operations to perform to start-up the unit.
For details refer to the different manual sections.
Start-up sequence - Unit ON power supply
Compressor carter resistances operating at least since 8 hours
Off-load voltage measure
Phase sequence check
Pump manual start-up and flow check
Unit ON
Load voltage measure and absorptions
Liquid light check (no bubbles)
Check of all fan operating
Measure of return and supply water temperature
Super-heating and sub-cooling measure
Check no anomalous vibrations are present
Set-point personalization
Climatic curve personalization
Complete and available unit documentation
17
Page 18
6 - START-UP
6.1 PRELIMINARY INFORMATION
The indicated operations should be done by qualified technician with specific training on the product.
Upon request, the service centres performing the start-up; the electrical, water connections and the other system works are by the installer.
Agree upon in advance the star-up data with the service centre.
6.2 PRELIMINARY CHECKS
Before checking, please verify the following :
the unit should be installed properly and in conformity with
this manual.
the electrical power supply line should be sectioned at the
beginning.
The line sectionalizing device is open, locked and
equipped with the suitable warning
make sure no tension is present
6.3 REFRIGERANT CIRCUIT
1. Check carefully the refrigerating circuit: the presence of oil stains can mean leakage caused by transportation, movements or other).
2. Verify that the refrigerating circuit is in pressure: Using the unit manometers , if present, or service manometers.
3. Make sure that all the service outlets are closed with proper caps; if caps are not present a leak of refrigerant can be possible.
6.5 ELECTRICAL CIRCUIT
Verify that the unit is connected to the ground plant
Check the conductors tightening: the vibrations caused by handling and transport might cause loosing
Feed the unit by closing the sectioning device, but leave it on OFF.
Check the tension and line frequency values which must be within the limits :
400/3/50 +/- 10% Control the unbalancing of the phases:
it must be lower than 2%
Example:
L1 L2 L3
388 V
379 V
377 V
388 + 379 + 377
1)
2)
3)
The working out of the limits can cause irreversible damages and voids the warranty.
3
388 (max)381 = 7
7
x 100 = 1,83 OK
381
381
=
6.4 HYDRAULIC CIRCUIT
1. Before realizing the unit connection make sure that the
hydraulic system has been cleaned up and the clearing water has been drained
2. Check that the water circuit has been filled and
pressurized
3. Check that the shut-off valves in the circuit are in the
"OPEN" position.
4. Check that there isn’t air in the circuit, if required,
evacuate it using the air bleed valve placed in the system high points.
5. When using antifreeze solutions, make sure the glycol
percentage is suitable for the type of use envisaged.
Weight of glycol (%)
Freezing temperature (°C)
Safety temperature (°C)
10 20 30 40
-4 -9 -15 -23
-1 -4 -10 -19
6.6 COMPRESSOR CRANKCASE RESISTANCES
Connect the oil resistances on the compressor crankcase at least 8 hours before the compressor is to be starter :
at the first unit start-up
after each prolonged period of inactivity
1. Supply the resistances switching off the unit isolator switch.
2. To make sure that hte resistances are working, check the power input .
3. At start-up the compressor crank-case temperature on the lower side must be higher at least of 10°C than the outside temperature.
Do not start the compressor with the crankcase oil below operating temperature.
18
Page 19
6 - START-UP
6.6 TENSIONS
Check that the air and water temperatures are included in the working limits
For information on the control system, refer to the paragraph CONTROL.
Start the unit With unit of full load, namely in stable conditions and close to
those of work, check :
Power supply tension
Total absorption of the unit
Absorption of the single electric loads
6.7 REMOTE CONSENT
Check that the remote commands (ON-OFF, etc.) are
connected and if necessary enabled with the relevant parameters as described in ELECTRICAL CONNECTIONS section
Check that probes or optional components are connect
and enable with the relative parameters( ELECTRICAL CONNECTION section)
6.8 STARTING REPORT
Realize the operating objective conditions is useful for check the unit over time.
With unit of full load, namely in stable conditions and close to those of work, take the following data:
Tension and general absorptions with unit at full load
Absorption of varied electrical loads (compressors, fans,
pumps etc)
Temperatures and capacities of different liquid (water, air)
in the inlet and outlet of the unit
Temperatures and pressures on the refrigerant circuit
characteristic points (compressor discharge, liquid, intake)
The remarks should be preserved and available during maintenance .
6.9 CE 97/23 PED DIRECTIVE
97/23 CE PED DIRECTIVE gives instructions for installers, users and maintenance technicians as well.
Refer to local actuation norms; briefly and as an example, see the following
Compulsory verification of the first installation :
only for units assembled on the installer’s building site (for ex. Condensing circuit + direct expansion unit)
Certification of setting in service :
for all the units
Periodical verifications:
to be executed with the frequency indicated by the
manufacturer (see the maintenance section)
19
Page 20
7 - CONTROL
7.1 MULTI-FUNCTION KEYPAD
The HEATING mode functions are active only on HEAT PUMP unit version . In ONLY COOL units, the relative parameters are VISIBLE but NOT ACTIVE , for example the winter setpoint.
OPERING MODES
Unit can be switched on and off by:
ON – OFF
COOLING The compressor is activated with outlet temperature higher than set point
remote or service keypad
remote switch (see ELECTRICAL CONNECTIONS paragraph)
Supervisor
To switch from cooling to heating and vice versa, proceed as follows:
Turn the unit OFF
Wait until the plant water temperature (and external air) fall within the operating limits.
They can be switched over from the remote controls (refer to the ELECTRIC WIRING paragraph).
M
ATUS
AR
AL
ST
ET
S
HEATING The compressor is activated with outlet temperature lower than set point
ECO
A secondary set-point can be used, with respect to the comfort setting. In heating the ECO-set is lower than the standard set , in cooling the ECO-set is higher than the standard set.
MAINTENANCE the plant can be kept within the operating limits even when the unit is OFF or on STANDBY
DEFROSTING The external coil is free from ice stopping the fans and forcing for a short period the unit in cooling
THERMOREGULATION
The thermoregulation is based on the OUTLET temperature.
The unit is dimensioned for a determined TOTAL HEAD between input and output water temperature.
Usually the project step is 5°C; if the value is different, it is necessary reset parameters 37 and 38 (accessible to the service centre).
In function of the total head, the installation determines the head quote that every resource (compressor, heating elements) is able to provide: the STEP HEAD.
The control logic insert gradually the resources when the outlet temperature is higher than the set point + the head step.
The resources are activated one at a time and only at the SCAN TIME expiring.
The scan time is not fixed but it changes in function of the margin between the water outlet temperature and the Set point value. Hi­gher is the margin value (both in positive and in negative) shorter will be the space among the scan points.
The scan time value is visualized at status 4; when the status 3 has reached the status 4 value, the compressor operating request is activated.
What above described, refer to the COOLING operating; in HEATING le logic is the same but “overturned” ( insertion of the compres­sor for outlet temperature< set-point –step jump )
OUTLET temperature
head step
ACTUAL set point
VARIABLE scan time
20
OUTLET temperature SURVEY, at SCAN TIME expiring
time
Page 21
7 - CONTROL
s
SET-POINT COMPENSATIONS
The compensations are evolved functions to protect the compressors and to adapt, as far as possible, the unit operating to the instal­lation and use characteristics.
The compensations prolong the compressor operating time and limit the start number; to do this they delay the compressor insertion point adding an offset.
COMPENSATED compressor activation point
non compensated compressor activation point
The compensation on the DURATION is useful when the installation water content is limited.
The compensation on the CHARGE is useful if the variable charge is present.
For the enabling and the configuration is necessary the parameter modification with reserved access to the service centres.
In industrial applications where is requested a temperature check is possible to disable the COMPENSATIONS.
SET-POINT CORRECTIONS
The correction aim is to optimize the unit energetic efficiency.
To do this the corrections modify the set point in a dynamic way in function of determined variables: for example in summer operating with low external temperatures, so with a reduced charge, is possible to obtain the internal comfort also with set point higher than stan­dard, obtaining an higher energetic efficiency.
CORRECTION
The static set point can so be modified in a dynamic way by two CORRECTIONS based on as many unit external factors:
correction based on the ext. temp. / enthalpy
correction based on the Water reset (4-20 mA signal provided by the Client)
The correct set point, to whom have been summed or removed the corrections, is named ACTUAL set-point and it is visible at status n°1. The STATA menu visualizes the compensation value on the ext. temperature (status 5) and WR (status 6) For further details see the ELECTRICAL CONNECTIONS section
ACTUAL or correct set point (visible at status 1)
static set point
offset by compensation
ACTUAL set point
SET POINT CORRECTION FOR COMPRESSOR OPERATING LIMIT
The function is active only in HEATING; it allows extending the operating limits decreasing gradually the set point when the external temperature descends more than determined limits.
In the graph, the correction action is indicated by the curve left side (B). The curve right side (A) represents the correction state on the external temperature (optional, see the ELECTRICAL CONNECTIONS section). The following data are indicatives .
0 °C
SET POINT
A
B
7 °C 5 °C
-2 °C-15 °C
7 °C
15°C
T EXT
21
Page 22
7 - CONTROL
DEFROSTING
The defrosting aim is to maintain the external coil free from ice during the winter mode : to do that the unit is periodically commuted in “summer” mode for few minutes and the fans are stopped. The defrosting phase is started when the evaporating pressure falls below a fixed value . A count starts and at its end, if the tempera­ture on the coil is lower than the threshold, the defrosting starts . The count changes according to the external temperature and to the ice quantity on the coil ( by some indirect variables ) . When defrosting is complete, the unit returns automatically to the Winter mode. Defrosting is managed according to the external temperature and humidity in the air:
more humidity = frequent defrosting
external temperature next to 0°C = frequent defrosting
By the EXTERNAL HUIDITY PROBE option the defrosting is optimised according to the external temperature and humidity .
CIRCULATION PUMP
The pump is always activated with the units ON. The delivery capacity is variable to soften the thermal shock to the compressors when the plant temperature is close to the threshold limits. Delivery capacity depends on the intake temperature:
SUMMER: high water temperature reduces delivery
WINTER: low water temperature reduces delivery
VENTILATION
Fans are controlled with a variable speed:
in SUMMER, the speed increases according to the increase of external air temperature
in WINTER the speed increases according to the decrease of the external tempe
SET POINT
SUMMER - WINTER
The thermoregulator manages two set points:
SUMMER set-point for cooling (parameter 32)
WINTER set-point for heating (parameter 33)
The control is performed on the OUTLET TEMPERATURE, comparing it with the actual set-point value (visible at status 1).
SET-POINT CALCULATION:
desired medium outlet water temperature = 7°C
Project temperature differential = 5°C (that is inlet water = 12°C)
¼ of the project temperature differential = 5 / 4 = 1.25°C
set-point to be set = 7 – 1.25 = 5.7°C
SECONDARY SET POINT – ECO
A secondary set point can be used with different levels to the “normal” set point. It is normally set to give lower energy consumption with respect to the comfort setting:
The SECONDARY SUMMER set point is higher than the SUMMER setting.
The SECONDARY WINTER set point is lower than the WINTER setting.
It can be set according to individual requirements.
Secondary summer set-point parameter 29
Secondary winter set-point parameter 30
It can be activated from the keyboard, supervisor unit or the remote control. To change it using the remote control refer to the ELECTRIC WIRING paragraph.
22
Page 23
7 - CONTROL
MAINTENANCE
This way, the plant can be kept within the operating limits even when the unit is OFF or on STANDBY, for example during the weekend or the nighttime. Periodically the system activates the circulation pump, measures the water temperature and acti­vates the compressor, if required, to take the water temperature to the set-point level.
Summer maintenance set-point par 42
Winter maintenance set-point par 43
This function is activated by parameters 44 (activate summer maintenance level) and 45 (activate winter maintenance level). With unit in maintenance mode, the display visualizes STB .
FUNCTIONING WITH ETHYLENE GLYCOL
The units foreseen to function with glycoled water come out from the premise with standard parameters. After having added glycol ethylene to water, the technician will properly set the plant.
Parameter to modify: 32 Summer set point 77 Antifreeze heater set 80 Antifreeze alarm 84 Antifreeze pre-alarm threshold
STB
AR
AL
ET
S
M
US
AT
ST
KEYPAD
Menu and “historical log “of
alarms flashes during an
alarm
Led signalling the necessity
to multiply by 100 the value
INDEX display.
COOLING
open in COOL
HEATING
open in HEAT
Increases decreases the
VALUE
Index scrolling
OFF
1
11.6
3
VALUE display
Opened active defrost
Opened active compressor
M
R
A
AL
STATUS
STATUS menu
Opened ACTIV PUMP
T
E
S
ON –OFF
PARAMETER MODIFY
unit in OFF.
S
M
U
AR
STAT
AL
ET S
by keypad by supervisor
2
ALARM
ET
S
switching: long ON - OFF
STATUS
pressure
OUTLET temperature visuali-
S TU A
ARM
AL
ST
SET
zation
23
Page 24
7 - CONTROL
ACCESSIBLE PARAMETERS FROM REMOTE OR SERVICE KEYBOARD
num. Par. description Value UM
29
Summer secondary Set Point
30 Winter secondary Set Point 35 °C 32 Summer Set Point 5.7 °C 33 Winter Set Point 41.2 °C 42 Summer Set Point Maintenance 20 °C 43 Winter Set Point Maintenance 30 °C 44 Enables Summer Maintenance 0 num 45 Enables Winter Maintenance 0 num 77 Antifreeze heater set point 4 °C 80 Antifreeze alarm 4 °C
84 Limit of deactivation before reaching the antifreeze steps 4.5 °C 163 Configures remote inputs: 1 = H/C by keypad or supervisor 192 Keypad address
PARAMETER MODIFICATION
10 °C
1
S
M
U T
LAR
A
STA
T
E
S
3
S
M
U T
A
AR
T
AL
S
ET
S
Push SET button 2
Modify the value 4
M
U T
A
AR
T
AL
S
ET
S
RM A
L
STATUS
A
SET
Select the parameter
S
Select another parameter
5
S
M
U T
A
AR
T
AL
S
ET
S
SET to esc
VISIBLE STATUS FROM REMOTE KEYBOARD OR SERVICE KEYBOARD
Visible status from remote keyboard or service keyboard
INDEX DESCRIPTION VALUE
1
Current Set Point
2 Temperature drop in degrees centigrade given by the compressor including compensations, if any °C
Resource activation timer When this value reaches the value fixed at the 4 status, the thermal regulator will compare the input tem-
3
perature with the set point and will activate the resources, if necessary
4 Dynamic TimeScan relating to source activation Seconds 5 Value in degrees of the external air compensation °C 6 Value in degrees of the water reset signal compensation °C 7 Value in degrees of the charge compensation °C
9 Inlet temperature °C 10 Outlet temperature 1 °C 11 Outlet temperature 2 °C 12 Coil temperature 1 °C 13 Condensing pressure 1 Bar 14 Fan/Coil percentage 1 0-100% 15 Coil temperature 2 °C 16 Condensing pressure 2 Bar 17 Condensing pressure 2 Bar 18 Water Reset signal value 4-20 mA
°C
Seconds
24
Page 25
7 - CONTROL
INDEX DESCRIPTION VALUE
19 Outdoor temperature °C 20 Outdoor Humidity 0-100% 21 Machine Clock - fed unit hours Num 22 Working hours C1 Num 23 Pickups C1 Num 24 Working hours C2 Num 25 Pickups C2 Num 30 Keypad software AS – t 31 Year of certification of the keyboard SW 2007 32 Month of certification of the keyboard SW 03 33 Day of certification of the keyboard SW 04 34 Base Software AS – b 35 Year of certification of the keyboard SW 2007 36 Month of certification of the keyboard SW 1 37 Day of certification of the keyboard SW 11
STATUS DISPLAY
1
S U
ALARM
STAT
SET
push STATUS button
2
Select status
S
M
U
T
A
AR
T
AL
S
ET S
3
M
AR L A
STATUS
T SE
STATUS to esc
ALARMS
BEFORE RESETTING THE ALARM, IDENTIFY AND ELIMINATE THE CAUSE OF ITS ACTIVATION.
REPEATED RESETS CAN CAUSE IRREVERSIBLE DAMAGES.
The ALARMS show a potentially dangerous situation for machine safety. Before resetting the alarm, discover and remove the cause: repeated resetting could cause irreversible damage. To avoid this, the unit can only be reset MANUALLY from the keyboard (only when the cause for the alarm has been removed).
PRE-ALARMS and SIGNALS warn of a risky situation. These could be acceptable only if they happen occasionally or in transitory situations (for example when the plant is being started up). They are reset AUTOMATICALLY, as soon as the cause has been removed, without any input from the keyboard. The pre-alarms are signalled by the fixed C code (not flashing) and on the right the control temperature.
The FAULTS warn of problems with the probes and transducers, and are reset AUTOMATICALLY to allow the unit to continue run­ning, perhaps with fewer functions.
In case of doubt, always contact an authorised service centre.
The presence of an alarm is signalled by the ALARM CODE flashing and the time at which the alarm/alarms occurred.
The cumulative block relay activates simultaneously to the alarm code visualization. Certain alarms, in particular PRE-ALARMS, do not activate the relays.
25
Page 26
ALARM VISUALIZATION
1
3
E 11 2
ALARM
SET
RM A L
A
SET
S
U
STAT
STATUS
flashing Alarm code Alarm unit hours
The most recent alarm is visual­ized Use the arrow keys to visualize other alarms
2
4
opened alarm log
M
US
T
AR
TA
AL
S
ET
S
short pressure ALARM
To esc
M
US
T
AR
TA
AL
S
ET
S
Short pressure ALARM
To RESET
5
S
M R
ATU
A L A
ST
SET
According to the unit configuration and to the current options, some status can not be used.
INDEX ALARM RESET
E 1 Faulty or disconnected water inlet probe Auto. E 2 Faulty or disconnected water outlet probe 1 Auto.
E 3 Faulty or disconnected water outlet probe 2 Auto. E 4 Faulty or disconnected coil probe 1 Auto. E 5 Faulty or disconnected coil probe 2 Auto. E 6 Faulty or disconnected external probe Auto. E 7 Faulty or disconnected pressure transducer 1 Auto.
E 8 Faulty or disconnected pressure transducer 2 Auto. C 9 Water Reset inlet in short circuit or out of range Auto. E 10 Faulty or disconnected external RH% probe Auto. E 11 High pressure 1 MANUAL E 12 Low pressure 1 Auto. E 13 Condensing fan and/or compressor thermal 1 switch MANUAL E 14 High pressure 2 MANUAL E 15 Low pressure 2 Auto. E 16 Condensing fan and/or compressor thermal 2 switch MANUAL E 17 Pump flow Auto. E 18 System charged with water MANUAL E 19 Phase monitor Auto. E 20 Antifreeze alarm MANUAL C 21 Antifreeze PREAlarm Auto. C
22 High pressure PreAlarm 1 Auto. C 23 High pressure PreAlarm 2 Auto. C 24 Pump change Auto. E 25 C1 flow alarm Auto. E 26 C2 flow alarm Auto. C 27 C1 low temperarue alarm C 28 C2 low temperarue alarm E 33 Condenser frost alarm MANUAL E 34 Evaporator input temp. alarm Auto. E 35 Incongruent DeltaT alarm MANUAL
C/E 36 BP1 Low pressure pre-alarm C1 Auto. C/E 37
S = anomalous situation signalisation that doesn’t compromise the unit functionality
BP1 Low pressure pre-alarm C2 Auto.
E = ALARM, situation that compromises the unit functionality
LONG pressure ALARM
Auto. Auto.
26
Page 27
8 - MAINTENANCE
8.1 GENERAL
Maintenance must be done by authorized centres or by qualified personnel
The maintenance enables:
maintain the unit efficiency
Reduce the deterioration speed to whom every equipment
is subject over time
Assemble information and data to understand the state of
the unit efficiency and avoid possible damages
8.2 INSPECTIONS FREQUENCY
The inspections should be carried out at least every six months
The frequency, however, depends on the use .
In the event of frequent use it is recommended to plan inspections at close intervals :
frequent use (continuous or very intermittent use, near the
operating limits, etc)
critical use (service necessary) .
8.3 MACHINE BOOKLET
It’s advisable to create a machine booklet to take notes of the
unit interventions.
In this way will be easier marker the various interventions and
will be e facilitate any troubleshooting.
Report on the booklet :
data
type of intervention effected
intervention description
Carried out measures etc ..
8.4 PUT A REST
If a long period of inactivity is foreseen
Turn of the power in order to avoid electrical risks or
damages by lightning strike
avoid the risk of frosts (empty or add glycol in the plant
sections subjected to temperatures below zero , power
antifreeze resistances if are present )
It’s recommended that the starter after the period of detention
is made by a qualified technician, especially after seasonal
stops or seasonal switch.
When restarting, refer to the START-UP section .
Schedule technical assistance in advance to avoid hitches and
be able to use the installation when necessary.
8.5 WATER FILTER
8.7 WATER EXCHANGER
It is very important for the exchanger to be able to provide the
maximum thermal exchange. Therefore, it is essential for the
inner surfaces to be clean of dirt and incrustations.
Periodically check the difference between the temperature of
the supply water and the condensation temperature. If the
difference is greater than 8 °C – 10 ° C it is advisable to clean
the exchanger.
The clearing must be effected :
With circulation opposite to the usual one
With a speed at least 1,5 times higher than the nominal one
With an appropriate product moderately acid (95% water +
5% phosphoric acid
After the cleaning rince with water to inhibe the detergent
rests.
8.8 ELECTRIC FANS
Check :
the fans and the relative protection gridsare well fixed
The fan bearings (evident by noise and anomalous
vibrations )
the terminal protection covers are closed and the cable
holders are properly positioned
8.9 AIR COIL
Contact with the exchanger fins can cause cuts. Wear
protective gloves to perform the above described operations.
It is extremely important that the battery gives the maximum
thermal exchange; therefore, its surface must be cleaned from
dust and deposits. Remove all impurities from the surface.
It is extremely important that the battery gives the maximum
thermal exchange; therefore, its surface must be cleaned from
dust and deposits. Remove all impurities from the surface.
Using an air pressure gun, clean the aluminum surface of the
battery. Be careful to direct the air in the opposite direction of
the fan air movement.
Hold the gun parallel to the fins to avoid damages. As an
alternative, an aspirator can be used to suck impurities from
the air input side.
Verify that the aluminum fins are not bent or damaged. In the
event of damages, contact the authorized assistance center
and get the battery “ironed out” in order to restore the initial
condition for an optimal air flow
Verify that there are no impurities which hinder the smooth passage of water.
8.6 CIRCULATION PUMPS
Verify :
no leaks
Bearing status (anomalies are highlighted by abnormal
noise and vibration)
The closing of the terminals cover and the correct
positioning of the cable glands.
27
Page 28
8 - MAINTENANCE
CONTROL CHECK LIST
Controls effected on ……………………………..By ………………………………………………. Of the Company…………………..……………………………….
Presence of corrosions
Panel fixing
Fan fixing
Coil cleaning
Water filter cleaning
Check the exchanger efficiency
Circulating pumps
Check of the fixing and the insulation of the power lead
Check of the earthing cable
Electric panel cleaning
Capacity contactor status
Termina closing, cable insulation integrity
Voltage and phase unbalancing (no load and on-load)
Absorptions of the single electrical loads
Test of the compressor carter resistances
Leak control *
Survey of the refrigerant circuit operating parameters
Protective device test : safety valves, pressure switches, thermostats, flow switches etc
Control system test: setpoint, climatic compensations, capacity stepping, water / air flow-rate variations etc
Control device test : alarm signalling, thermometers, probes, pressure gauges etc
1 6
12
Notes / interventions recommended to the owner
* European regulation 303/2008
Refer to the local actuation regulations; in short and just as an indication the regulation order as follow.
Companies and technicians that effect interventions of installation, maintenance/repairs, leak control and recovery must be CERTIFIED as expected by
the local regulations.
The leak control must be effected with annual renewal.
28
Page 29
9 - TECHINICAL INFORMATION
DIMENSIONALES AND WEIGHT DISTRIBUTION WSAN-XEE 82-102-122
Size 82 102 122
M N O P
Length
Depth
Height
W1 W2 W3 W4
Operating weight
Shipping weight
mm 705 700 699 mm 998 1003 1004 mm 345 345 345 mm 330 330 330 mm 1771 1771 1771 mm 680 680 680 mm 1287 1287 1287
kg 101 102 118 kg 60 61 70 kg 88 90 104 kg 66 67 78 kg 315 320 370 kg 325 330 380
(1) COMPRESSOR COMPARTMENT (2) ELECTRICAL PANEL (3) KEYBOARD CONTROL UNIT (4) POWER INPUT (5) FUNCTIONAL SPACE (6) AIR SUPPLY (7) WATER INLET 1 1/4" VICTAULIC (8) WATER OUTLET 1 1/4" VICTAULIC (9) DESUPERHEATER WATER INLET 1" 1/4 VICTAULIC (OPTIONAL) (10) DESUPERHEATER WATER OUTLET 1" 1/4 VICTAULIC (OPTIONAL) (11) MAIN ISOLATOR SWITCH (12) VIBRATION MOUNTS POSITION (13) LIFTING HOLES POSITION
29
Page 30
9 - TECHINICAL INFORMATION
DIMENSIONALS AND WEIGHT DISTRIBUTION WSAN-XEE 162-182-222
Size 162 182 222
M
N O P
Length
Depth
Height
W1 W2 W3 W4
Operating weight
Shipping weight
mm 892 888 889 mm 1040 1044 1043 mm 520 515 517 mm 580 585 583 mm 2012 2012 2012 mm 1100 1100 1100 mm 1599 1599 1599
kg 148 154 162 kg 101 105 110 kg 170 176 186 kg 111 116 122 kg 530 550 580 kg 545 565 595
(1) COMPRESSOR COMPARTMENT (2) ELECTRICAL PANEL (3) KEYBOARD CONTROL UNIT (4) POWER INPUT (5) FUNCTIONAL SPACE (6) AIR SUPPLY (7) WATER INLET 2" VICTAULIC (8) WATER OUTLET 2" VICTAULIC (9) DESUPERHEATER WATER INLET 1" 1/4 VICTAULIC (OPTIONAL) (10) DESUPERHEATER WATER OUTLET 1" 1/4 VICTAULIC (OPTIONAL) (11) MAIN ISOLATOR SWITCH (12) VIBRATION MOUNTS POSITION (13) LIFTING HOLES POSITION
30
Page 31
9 - TECHINICAL INFORMATION
DIMENSIONALS AND WEIGHT DISTRIBUTION WSAN-XEE 262-302
Size 262 302
M
N
O
P
Length
Depth
Height
W1 W2 W3 W4
Operating weight
Shipping weight
mm 1105 1100 mm 1227 1232 mm 515 513 mm 585 587 mm 2406 2406 mm 1100 1100 mm 1593 1593
kg 189 193 kg 128 131 kg 216 221 kg 142 145 kg 675 690 kg 690 705
(1) COMPRESSOR COMPARTMENT (2) ELECTRICAL PANEL (3) KEYBOARD CONTROL UNIT (4) POWER INPUT (5) FUNCTIONAL SPACE (6) AIR SUPPLY (7) WATER INLET 2" VICTAULIC (8) WATER OUTLET 2" VICTAULIC (9) DESUPERHEATER WATER INLET 1" 1/4 VICTAULIC (OPTIONAL) (10) DESUPERHEATER WATER OUTLET 1" 1/4 VICTAULIC (OPTIONAL) (11) MAIN ISOLATOR SWITCH (12) VIBRATION MOUNTS POSITION (13) LIFTING HOLES POSITION
31
Page 32
GENERAL TECHNICAL SPECIFICATIONS
9 - TECHINICAL INFORMATION
Application: Terminal units
Size
COOLING
Cooling capacity 1 kW 23.6 27.5 32.7 39.4 45.6 52.9 63.0 71.9 Compressor power input 1 kW 9.00 10.5 12.7 14.6 17.1 20.3 23.9 27.3 Total power input 2 kW 9.52 11.0 13.2 16.4 18.8 22.0 25.7 29.1 EER 3 2.48 2.49 2.48 2.41 2.42 2.40 2.45 2.47
HEATING
Heat output 4 kW 28.8 32.9 37.5 45.6 53.0 61.9 72.4 83.7 Compressor power input 4 kW 8.66 9.93 11.4 13.4 15.8 18.3 21.1 24.5 Total power input 2 kW 9.16 10.4 11.9 15.1 17.5 20.0 22.9 26.3 COP 4 3.14 3.15 3.16 3.02 3.03 3.09 3.16 3.18
COMPRESSOR
Type of compressors No. of Compressors Std Capacity control steps Oil charge (C1) Refrigerant charge (C1) Refrigerant circuits
INTERNAL EXCHANGER
Type of internal exchanger 5 PHE PHE PHE PHE PHE PHE PHE PHE No. of internal exchangers Water flow rate (Internal Exchanger) 1 l/s 1.1 1.3 1.6 1.9 2.2 2.5 3 3.4 Max water flow-rate internal exchanger pressure drop Useful pump discharge head 1 kPa 136 129 125 107 89 150 141 131
EXTERNAL SECTION FANS
Type of fans 6 AX AX AX AX AX AX AX AX Number of fans Standard air flow Installed unit power
CONNECTIONS
Water fittings
HYDRAULIC CIRCUIT
Max water side pressure Safety valve calibration
POWER SUPPLY
Standard power supply
NOISE LEVELS
Sound pressure level (1 m)
DIMENSIONS
Length Depth Height Packing volume
STANDARD UNIT WEIGHTS
Shipping weight Operating weight
(1) data referred to the following conditions : internal exchanger water = 12/7°C external exchanger air intake 35°C (2) Total absorbed power is given by the compressor absorbed power + fan absorbed power + auxiliary circuit absorbed power. (3) 100% EER internal exchanger water outlet temperature = 7°C outdoor air temperature = 35°C
kPa 48.1 47.6 41.6 42.7 43.1 37.5 39.4 41.9
kPa 550 550 550 550 550 550 550 550 kPa 600 600 600 600 600 600 600 600
dB(A) 60 60 60 64 64 65 65 65
mm 1771 1771 1771 2012 2012 2012 2406 2406 mm 680 680 680 1100 1100 1100 1100 1100 mm 1287 1287 1287 1599 1599 1599 1593 1593
82 102 122 162 182 222 262 302
SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL Nr 2 2 2 2 2 2 2 2 Nr 3 3 2 3 3 3 3 2
l 3.61 3.72 3.54 5.76 5.76 6.65 7.39 8.28 kg 12,5 11,8 14,0 18,0 18,5 23,5 21,5 27,0 Nr 1 1 1 1 1 1 1 1
Nr 1 1 1 1 1 1 1 1
l/s 1.5 1.8 2.3 2.7 3.1 4 4.6 5.4
Nr 2 2 2 1 1 1 2 2
l/s 2553 2545 2514 4965 4902 4778 7196 6971
kW 0.25 0.25 0.25 1.72 1.72 1.72 0.90 0.90
1" 1/4 1" 1/4 1" 1/4 2" 2" 2" 2" 2"
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
V
m3 1.8 1.8 1.8 4 4 4 4.5 4.5
kg 325 330 380 545 565 595 690 705 kg 315 320 370 530 550 580 675 690
(4) data referred to the following conditions : outlet water internal exchanger 45°C outdoor air temperature = 7°C (RH = 85%) (5) PHE = plates (6) AX = axial-flow fan
32
Page 33
GENERAL TECHNICAL SPECIFICATIONS
9 - TECHINICAL INFORMATION
Application: Unit for underfloor heating
Size
COOLING
Cooling capacity 1 kW 31,5 36,7 43,8 52,6 60,2 72,3 83,1 97,2 Compressor power input 1 kW 9,59 11,5 14.0 16,1 18,2 22.0 25,5 29,4 Total power input 2 kW 10.11 12.0 14,5 17.8 19.9 23.7 27.3 31.2 EER
HEATING
Heat output 3 kW 29.2 33.6 38.0 46.9 54.1 63.3 74.0 85.4 Compressor power input 3 kW 6.73 7.63 8.8 10.5 12.6 14.9 17.1 20.0 Total power input COP
COMPRESSOR
Type of compressors No. of Compressors Std Capacity control steps Oil charge (C1) Refrigerant charge (C1) Refrigerant circuits
INTERNAL EXCHANGER
Type of internal exchanger 4 PHE PHE PHE PHE PHE PHE PHE PHE No. of internal exchangers Water flow rate (Internal Exchanger) Max water flow-rate internal exchanger pressure drop 1 kPa 48.1 47.6 41.6 42.7 43.1 37.5 39.4 41.9 Useful pump discharge head 1 kPa 91.8 80.4 72.7 42.9 17.2 111.2 102.3 82.9
EXTERNAL SECTION FANS
Type of fans 5 AX AX AX AX AX AX AX AX Number of fans Standard air flow Installed unit power
CONNECTIONS
Water fittings
HYDRAULIC CIRCUIT
Max water side pressure Safety valve calibration
POWER SUPPLY
Standard power supply
NOISE LEVELS
Sound pressure level (1 m)
DIMENSIONS
Length Depth Height Packing volume
STANDARD UNIT WEIGHTS
Shipping weight Operating weight
(1) data referred to the following conditions : internal exchanger water = 23/18°C external exchanger air intake 35°C (2) Total absorbed power is given by the compressor absorbed power + fan absorbed power + auxiliary circuit absorbed power. (3) data referred to the following conditions : water to internal exchanger 30/35°C outdoor air temperature 7°C DB - 6°C WB
Nr 1 1 1 1 1 1 1 1
kPa 550 550 550 550 550 550 550 550 kPa 600 600 600 600 600 600 600 600
dB(A) 60 60 60 64 64 65 65 65
mm 1771 1771 1771 2012 2012 2012 2406 2406 mm 680 680 680 1100 1100 1100 1100 1100 mm 1287 1287 1287 1599 1599 1599 1593 1593
82 102 122 162 182 222 262 302
3,12 3,05 3,02 2.95 3,02 3,05 3,04 3,11
kW 7.23 8.1 9.3 12.2 14.3 16.6 18.9 21.8
4.04 4.13 4.09 3.84 3.78 3.81 3.92 3.92
SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL Nr 2 2 2 2 2 2 2 2 Nr 3 3 2 3 3 3 3 2
l 3,61 3,72 3,54 5,76 5,76 6,65 7,39 8,28 kg 12,5 11,8 14,0 18,0 18,5 23,5 21,5 27,0 Nr 1 1 1 1 1 1 1 1
l/s 1.5 1.8 2.1 2.5 2.9 3.5 4 4.6 l/s 1.5 1.8 2.3 2.7 3.1 4 4.6 5.4
Nr 2 2 2 1 1 1 2 2 l/s 2553 2545 2514 4965 4902 4778 7196 6971
kW 0,25 0,25 0,25 1.72 1.72 1.72 0.90 0.90
1" 1/4 1" 1/4 1" 1/4 2" 2" 2" 2" 2"
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
V
m3 1.8 1.8 1.8 4 4 4 4.5 4.5
kg 325 330 380 545 565 595 690 705 kg 315 320 370 530 550 580 675 690
(4) PHE = plates (5) AX = axial-flow fan
33
Page 34
9 - TECHINICAL INFORMATION
Application: Terminal units
OPERATING LIMITS (COOLING)
Size
EXTERNAL EXCHANGER
Max air intake temperature 1 °C 47 47 46 47 48 47 47 47 Max air intake temperature 2 °C 49 49 48 49 48 49 49 49 Min. air intake temperature 3 °C -10 -10 -10 -10 -10 -10 -10 -10
INTERNAL EXCHANGER
Max water inlet temperature 4 °C 22 22 22 22 22 22 22 22 Min. water outlet temperature 5 °C 5 5 5 5 5 5 5 5 Min. water outlet temperature 6 °C -8 -8 -8 -8 -8 -8 -8 -8
OPERATING LIMITS (HEATING)
EXTERNAL EXCHANGER
Max air temperature inlet (WB) 7 °C 22 22 24 24 24 22 24 22 Min air inlet temperature (W.B.) 8 °C -7 -7 -7 -7 -7 -7 -7 -7
INTERNAL EXCHANGER
Min. water outlet temperature Max water outlet temperature 9 °C 55 55 53 55 55 55 55 55
Warning: the still air condition is meant as absence of air flow to the unit. Any wind condition can let air pass through the condenser coil thus worsening the operating limits of the unit (see limits with air speed at 0,5 m/s & 1 m/s).
ATTENTION: IN CASE OF PREDOMINANT WINDS, WINDBREAK BARRIERS ARE NECESSARY.
Water thermal head (min / max) are indicated in the section INTERNAL EXCHANGER PRESSURE DROP (1) unit at full load: internal exchanger water 12/7°C (2) internal exchanger water = 12/7°C capacity-controlled unit (automatic capacity control) (3) external exchanger air in quiet
82 102 122 162 182 222 262 302
°C 28 28 28 28 28 28 28 28
(4) this limit can be exceeded for brief and transitory periods with automatic capacity control of the unit: the maximum limit is 30°C. (5) standard unit outdoor air temperature 35°C (6) B = Low Temperature outdoor air temperature 35°C Fluid with ethylene glycol of 40% (7) unit at full load outlet water internal exchanger 45°C (8) outlet water internal exchanger 45°C (9) outdoor air temperature = 7°C (RH = 85%)
Application: Unit for underfloor heating
OPERATING LIMITS (COOLING)
Size
EXTERNAL EXCHANGER
Max air intake temperature 1 °C 44 44 42 43 43 42 41.5 43 Max air intake temperature 2 °C 46 46 45 45 45 45 44 45 Min. air intake temperature 3 °C -10 -10 -10 -10 -10 -10 -10 -10
INTERNAL EXCHANGER
Max water inlet temperature 4 °C 22 22 22 22 22 22 22 22 Min. water outlet temperature 5 °C 5 5 5 5 5 5 5 5 Min. water outlet temperature 6 °C -8 -8 -8 -8 -8 -8 -8 -8
OPERATING LIMITS (HEATING)
EXTERNAL EXCHANGER
Max air temperature inlet (WB) 7 °C 22 22 24 24 24 22 24 22 Min air inlet temperature (W.B.) 8 °C -10 -10 -10 -10 -10 -10 -10 -10
INTERNAL EXCHANGER
Min. water outlet temperature Max water outlet temperature
(1) unit at full load internal exchanger water = 23/18°C (2) internal exchanger water = 23/18°C capacity-controlled unit (automatic capacity control) (3) external exchanger air in quiet (4) this limit can be exceeded for brief and transitory periods with automatic capacity control of the unit: the maximum limit is 30°C. (5) standard unit outdoor air temperature 35°C
82 102 122 162 182 222 262 302
°C 28 28 28 28 28 28 28 28 °C 55 55 53 55 55 55 55 55
(6) B = Low Temperature outdoor air temperature 35°C Fluid with ethylene glycol of 40% (7) unit at full load exchanger water outlet 35°C (8) exchanger water outlet 35°C
34
Page 35
SOUND LEVELS
9 - TECHINICAL INFORMATION
Size
Sound Power Level (dB)
Octave band (Hz)
Sound
pressure
level
Sound
power level
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
82 80 75 78 73 70 66 58 52 60 75 102 79 74 77 73 70 66 60 51 60 75 122 79 74 77 72 70 67 61 52 60 75 162 89 82 78 80 77 69 64 59 64 81 182 89 82 77 79 77 71 66 60 64 81 222 89 82 80 81 77 72 64 59 65 82 262 89 82 79 80 78 73 67 59 65 82 302 89 82 80 81 78 73 64 57 65 82
INTERNAL EXCHANGER PRESSURE DROP
80
70
60
50
DP (kPa)
40
82
122102
182162
Measures according to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certification.
The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field.
Data referred to the following conditions :
- internal exchanger water = 12/7°C
EXCHANGER PRESSURE DROP LIMIT. WARNING: DON'T USE OVER THIS LIMIT
222
262
UNIT WITHOUT HYDRAULIC
302
CIRCUIT COMPONENTS
Q[L/S]= WATER-FLOW RATE DP = PRESSURE DROP
30
20
1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0
82 102 122 162 182 222 262 302
Size
0.70 0.80 0.85 1.00 1.11 1.51 1.74 1.95
Minimum flow [l/s] Maximum flow [l/s]
1.52 1.80 2.85 2.71 3.05 4.05 4.65 5.00
Q (l/s)
EXCHAMGER PRESSURE DROP LIMIT. WARNING: DON'T USE BELOW THIS LIMIT.
CORRECTION FACTOR FOR ANTIFREEZE SOLUTIONS
% ethylene glycol by weight
Freezing temperature Safety temperature Cooling Capacity Factor Compressor input Factor Internal exchanger Glycol solution flow Factor Pressure drop Factor
The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.
5% 10% 15% 20% 25% 30% 35% 40%
°C -2.0 -3.9 -6.5 -8.9 -11.8 -15.6 -19.0 -23.4 °C 3.0 1.0 -1.0 -4.0 -6.0 -10.0 -14.0 -19.0 Nr 0.995 0.990 0.985 0.981 0.977 0.974 0.971 0.968 Nr 0.997 0.993 0.990 0.988 0.986 0.984 0.982 0.981 Nr 1.003 1.010 1.020 1.033 1.050 1.072 1.095 1.124 Nr 1.029 1.060 1.090 1.118 1.149 1.182 1.211 1.243
35
Page 36
10 - DECOMMISSIONING
9.1 DISCONNECTING
Only authorised personnel must disconnect the unit.
Avoid leak or spills into the environment .
Before disconnecting the unit, the following must be
recovered, if present:
- refrigerant gas
- Anti-freeze solutions in the hydraulic circuit
Awaiting dismantling and disposal, the unit can also be
stored outdoors, as bad weather and rapid changes in
temperature will not cause damage to the environment, if
electric, cooling and hydraulic circuits of the unit are
integral and closed.
9.2 DISMANTLING AND DISPOSAL
THE UNIT MUST ALWAYS BE SENT TO AUTHORISED CENTRES FOR DISMANTLING AND DISPOSAL.
When dismantling the unit, the fan, the motor and the coil, if operating, may be recovered by the specialist centres for reuse.
All the materials must be recovered or disposed of in compliance with the corresponding national standards in force.
For further information on the decommissioning of the unit, contact the manufacturer.
9.3 CE RAEE CE DIRECTIVE
The units covered by the legislation in question are marked
with the symbol on the side.
With the aim of protecting the environment, all of our units are
produced in compliance with Directive EC on waste electrical
and electronic equipment (WEEE).
The potential effects on the environment and on human health
due to the presence of hazardous substances are shown in the
use and maintenance manual in the section on residual risks.
Information in addition to that indicated below, if required, can
be obtained from the manufacturer/distributor/importer, who
are responsible for the collection/handling of waste originating
from equipment covered by EC - WEEE. This information is
also available from the retailer who sold this appliance or from
the local authorities who handle waste.
Directive EC - WEEE requires disposal and recycling of
electrical and electronic equipment as described therein to be
handled through appropriate collection, in suitable centres,
separate from collection for the disposal of mixed urban waste.
The user must not dispose of the unit at the end of its life cycle
as urban waste. It must instead be handed over to appropriate
collection centres as set forth by current standards or as
instructed by the distributor.
If disposal takes places at the same time as delivery of a new
electrical or electronic equipment for the same family, the
product may be collected directly by the distributor.
36
Page 37
11 - RESIDUAL RISKS
11.1 GENERAL
In this section the most common situations are signalled. As these cannot be controlled by the manufacturer these could be a source of risk situations for people or things
11.2 DANGER ZONE
This is an area in which only an authorised operator may work.
The danger zone is the area inside the unit which is accessible only with the deliberate removal of protections or parts thereof
11.3 HANDLING
The handling operations, if implemented without all of the protection necesssary and without due caution, may cause the fall or the tipping of the unit with the consequent damage, even serious, to persons, things or the unit itself.
Handle the unit following the instructions provided in the pre­sent manual regarding the packaging and in compliance with the local regulations in force.
Should the gas refrigerant leak please refer to the refrigerant "Safety sheet".
11.4 INSTALLATION
An incorrect installation of the unit could cause water leaks, condensate accumulation, leaking of the refrigerant, electric shock, bad functioning or damage to the unit itself.
Check that the installation has been implemented by qualified technical personnel only and that the instructions contained in the present manual and the local regulations in force have been adhered to.
The installation of the unit in a place where even infrequent leaks of inflammable gas and the accumulation of this gas in the area surrounding the area occur could cause explosions or fires.
Carefully check the positioning of the unit.
The installation of the unit in a place unsuited to support its weight and/or guarantee adequate anchorage may cause the fall or the tipping of the unit with the consequent damage to things, people or the unit itself.
Carefully check the positioning and the anchoring of the unit.
Easy access to the unit by children, unauthorised persons or animals may be the source of accidents, some serious.
Install the unit in areas which are only accessible to authori­sed person and/or provide protection against intrusion into the danger zone .
11.5 GENERAL RISKS
Smell of burning, smoke or other signals of serious anomalies may indicate a situation which could cause damage to people, things or the unit itself. Electrically isolate the unit (yellow-red isolator).
Contact the authorised service centre to identify and resolve the problem at the source of the anomaly.
Accidental contact with exchange batteries, compressors, air
delivery tubes or other components may cause injuries and/or burns.
Always wear suitable clothing including protective gloves to work inside the danger zone.
Maintenance and repair operations carried out by non­qualified personnel may cause damge to persons, things or the unit itself.
Always contact the qualified assistance centre.
Failing to close the unit panels or failure to check the correct tightening of all of the panelling fixing screws may cause damage to persons, things or the unit itself.
Periodically check that all of the panels are correctly closed and fixed.
If there is a fire the temperature of the refrigerant could reach values that increase the pressure to beyond the safety valve with the consequent possible projection of the refrigerant itself or explosion of the circuit parts that remain isolated by the closure of the tap. Do not remain in the vicinity of the safety valve and never leave the refrigerating system taps closed.
11.6 ELECTRICS PARTS
An incomplete attachment line to the electric network or with incorrectly sized cables and/or unsuitable protective devices can cause electric shocks, intoxication, damage to the unit or fires.
Carry out all of the work on the electric system referring to the electric layout and the present manual ensuring the use of a system thereto dedicated.
An incorrect fixing of the electric components cover may favour the entry of dust, water etc inside and may consequently can electric shocks, damage to the unit or fires.
Always fix the unit cover properly.
When the metallic mass of the unit is under voltage and is not correctly connected to the earthing system it may be as source of electric shock and electrocution.
Always pay particular attention to the implementation of the earthing system connections.
Contact with parts under voltage accessible inside the unit after the removal of the guards can cause electric shocks, burns and electrocution.
Open and padlock the general isolator prior to removing the guards and signal work in progress with the appropriate shield.
Contact with parts that could be under voltage due to the start up of the unit may cause electric shocks, burns and electrocution.
When voltage is necessary for the circuit open the isolator on the attachment line of the unit itself, padlock it and display the appropriate warning shield.
37
Page 38
11 - RESIDUAL RISKS
11.7 MOVING PARTS
Contact with the transmissions or with the fan aspiration can cause injuries.
Prior to entering the inside of the unit open the isolater situated on the connection line of the unit itself, padlock and display the suitable sign.
Contact with the fans can cause incurie.
Prior to removing the protective grill or the fans, open the isolator on the attachment line of the unit itself, padlock it and display the appropriate warning sign.
11.8 REFRIGERANT
The intervention of the safety valve and the consequent expulsion of the gas refrigerant may cause injuries and intoxication. Always wear suitable clothing including protective gloves and eyeglasses for operations inside the danger zone.
Should the gas refrigerant leak please refer to the refrigerant "Safety sheet".
Contact between open flames or heat sources with the refrigerant or the heating of the gas circuit under pressure (e.g. during welding operations) may cause explosions or fires.
Do not place any heat source inside the danger zone.
The maintenance or repair interventions which include welding must be carried out with the system off.
11.9 HYDRAULIC PARTS
Defects in tubing, the attachments or the cut-off parts may cause a leak or water projection with the consequent damages to peopl, things or shortcircuit the unit.
38
Page 39
NOTE
39
Page 40
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy Tel. + 39 0439 3131 - Fax + 39 0439 313300 - info@clivet.it
CLIVET ESPAÑA S.A.
Calle Real de Burgos 12 - 28860, Paracuellos de Jarama, Madrid - España Tel. + 34 91 6658280 - Fax + 34 91 6657806 - info@clivet.es
CLIVET UK LTD 4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - info@clivet-uk.co.uk
CLIVET NEDERLAND B.V.
Siliciumweg 20a, 3812 SX Amersfoort - Netherlands Tel. + 31 (0) 33 7503420 - Fax + 31 (0) 33 7503424 - info@clivet.nl
CLIVET GmbH
Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - info.de@clivet.com
CLIVET RUSSIA
Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia Tel. + 74956462009 - Fax + 74956462009 - info.ru@clivet.com
CLIVET MIDEAST FZCO
Dubai Silicon Oasis (DSO), High Bay Complex, Ind Unit No. 3 - PO Box 28178 - DUBAI, UAE Tel. + 97 14 3208499 - Fax + 97 14 3208216 - info@clivet.ae
CLIVET AIRCONDITIONING SYSTEMS (P) LTD 3C3, Gundecha Onclave, Kherani Road, Saki Naka, Andheri (East), Mumbai 400 072 (INDIA) Tel. + 91 - 22 - 6193 7000 - Fax + 91 - 22 - 6193 7001 - sales.india@clivet.com
All reproduction, even partial, is prohibited. © Copyright - CLIVET S.p.A. - Feltre (BL) - Italy
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice.
www.clivet.com
Loading...