CLIVET WDH-3 2.250, WDH-3 2.280, WDH-3 2.180, WDH-3 2.220, WDH-3 2.300 Installation And Use Manual

...
WDH-3 2.160-2.180-2.220-2.250-2.280-2.300-
2.320-2.340-2.360-2.420-2.450-2.480-2.540-2.600
WATER COOLED CHILLERS
Installation and Use Manual
M03I40M7-03 15/11/07
UNIT IDENTIFICATION ........................................................................... 4
GENERAL WARNINGS ............................................................................ 5
RESIDUAL RISKS ................................................................................. 6
REFRIGERANT SAFETY CHARTS................................................................................................................................7
RECEPTION......................................................................................... 9
INSPECTION UPON RECEPTION................................................................................................................................. 9
STORAGE ......................................................................................................................................................................9
HANDLING .....................................................................................................................................................................9
POSITIONING .....................................................................................11
GENERAL.....................................................................................................................................................................11
FUNCTIONAL CLEARANCES......................................................................................................................................11
POSITIONING ..............................................................................................................................................................11
WATER CONNECTIONS .........................................................................14
GENERAL.....................................................................................................................................................................14
EXCHANGER USE SIDE .............................................................................................................................................14
DIAGRAM OF RECOMMENDED USE SIDE CONNECTION.......................................................................................15
RECOVERY EXCHANGER ..........................................................................................................................................15
VICTAULIC CONNECTIONS........................................................................................................................................ 15
RECOMMENDED SOURCE SIDE CONNECTION SCHEMA ......................................................................................16
SYSTEM MEASURES ON SOURCE SIDE ..................................................................................................................17
ELECTRICAL CONNECTION ...................................................................18
GENERAL.....................................................................................................................................................................18
STANDARD UNIT ELECTRICAL DATA .......................................................................................................................18
CONNECTION TO THE MAINS ...................................................................................................................................19
CLIVET TALK MODULAR SYSTEM COMPOSITION ..................................................................................................21
MODBUS - CONVERTER CAN to MODBUS via RS 485.............................................................................................23
START-UP..........................................................................................25
PRELIMINARY CHECKS..............................................................................................................................................25
REFRIGERANT SYSTEM ............................................................................................................................................25
WATER SYSTEM .........................................................................................................................................................25
ELECTRICAL SYSTEM ................................................................................................................................................25
VERIFy tensions – absorptions..................................................................................................................................... 25
REMOTE INPUT CONFIGURATIONS .........................................................................................................................25
SETTING THE SET-POINT ..........................................................................................................................................25
EVAPORATOR WATER FLOW RATE .........................................................................................................................26
CONDENSER WATER FLOW RATE ...........................................................................................................................26
REFRIGERANT CIRCUIT PARAMETER CHECK ........................................................................................................26
CONTROL ..........................................................................................27
ROUTINE MAINTENANCE.......................................................................37
MAINTENANCE INSPECTIONS...................................................................................................................................38
97/23 CE PED directive ................................................................................................................................................38
PUT AT REST...............................................................................................................................................................38
REFRIGERANT TABLES .............................................................................................................................................39
TROUBLESHOOTING ............................................................................41
DECOMMISSIONING OF THE UNIT ...........................................................42
DISCONNECTING THE UNIT ......................................................................................................................................42
DISMANTLING AND DISPOSAL ..................................................................................................................................42
TECHNICAL DATA................................................................................43
SOUND LEVELS ..........................................................................................................................................................48
DIMENSIONS ......................................................................................49
M03I40M7-03 15/11/07 page 4
UNIT IDENTIFICATION
SERIAL NUMBER LABEL
The units are identified by the serial number label shown here.
The label lists the type of unit (series and size), serial number, year of manufacture, number of electrical diagram, main technical data, logo and address of the manufacturer.
The label is placed on the unit, generally near the electrical panel and also on the external panelling.
IT MUST NEVER BE REMOVED.
SERIAL NUMBER
This provides unique identification of the machine. It makes it possible to trace the specific features of the unit and to identify the components installed in it.
Without this number, it is not possible to identify with certainty the spare parts that are specific to that unit.
When requesting assistance, always provide the type of machine and the serial number.
Write them in the space below so that they are readily available when needed.
Type of unit : _________________________________
Serial number : _________________________________
Wiring diagram : __________________________
Year of manufacture : ___________________________
M03I40M7-03 15/11/07 page 5
GENERAL WARNINGS
MANUAL PURPOSE
This manual has been designed to enable the unit to be installed, started up and maintained correctly.
MANUAL INSTRUCTIONS
It is essential to observe these instructions. The manufacturer declines all liability for any damage that may be caused whether directly or indirectly to persons or things if these instructions are not heeded.
MANUAL STORAGE
This manual and the unit’s wiring diagram should be carefully stored so that they are readily available to the operator when required.
EXPERT PERSONAL
The unit must be installed, tested and maintained by expert personal who meet the relevant legal requirements (Italian law No. 46 of 5/3/1990).
LOCAL SAFET REGULATION INSTALLATION
The installation must be performed observing the local safety regulations.
POWER SUPPLY
Make sure the power supply conforms to the data on the unit’s rating plate, located inside the door of the main electrical panel.
PACKAGING
The packaging material (plastic bags, polystyrene foam, nails, etc.) is potentially dangerous and should therefore be kept away from children and recycled in compliance with the local regulations in force.
MAINTENANCE
Before performing any service operations, cut off the power. Perform the operations in conformity with the local regulations in force.
PERIODICAL INSPECTIONS
Perform periodical inspections to locate possible loosened or broken parts. If the repairs are not performed, there will be a higher risk for things and peoples to become damaged and injured.
FAULT – POOR OPERATION
Switch off the unit in the event of faults or poor operation.
REPAIR
Only have repairs carried out by a service centre authorised by the manufacturer, and insist on the use of original spare parts only. Failure to comply with the above may compromise the safety of the unit.
MODIFICATIONS
The manufacturer will not accept any responsibility, and the warranty will lapse, in the event of electric and/or mechanical modifications. Any modification which is not formally authorized, and which does not respect the instructions given in this manual, will cause the warranty to lapse.
INTENDED USE
The unit must only be used for the specific purpose it was designed :
The unit is designed to cool/heat water or a water and glycol mix for air-conditioning, within the limits defined in the technical bulletin and this manual.
Any use other than that specified does not imply any commitment or constraint by the manufacturer in any way whatsoever.
ADDITIONAL SAFETY PRECAUTIONS
This unit has been especially designed and manufactured so to prevent any risk to persons and health hazard. For this reason, design solutions fit to eliminate (where possible) any cause of risk and sensibly reduce the probability of danger have been adopted. Please refer to the "Residual Risks" section of this manual and strictly observe the behaviour prescriptions listed there in order to prevent any possible risk that hasn’t been possible to avoid in the design stage.
DATA UPDATING
The manufacturer may be able to modify the data without prior notice as a consequence of constant improvements.
REGULATIONS AND CERTIFICATIONS
UNI EN ISO 9001 CERTIFICATION
Clivet S.p.A., in order to guarantee customer satisfaction, has chosen the ISO 9001 Quality System as the reference for all its business activities. This is demonstrated by the company’s commitment to ongoing improvements in the quality and reliability of its products; its sales, design, purchasing, production and after-sales service activities are the means used to reach such purpose.
CE MARK
Clivet products bear the CE mark, in compliance with the requirements of the following EC directives, including the latest amendments, and with the corresponding national approximated legislation:
- 98/37/CE
- 89/336/CEE as modified by the directives 92/31/CEE
and 93/68/CEE
- 73/23/CEE as modified by the directive 93/68/CEE
- 97/23/CE
EUROVENT CERTIFICATION
Clivet is partecipating in the EUROVENT Certification Programme "Liquid Chilling Packages". Products are listed in the EUROVENT Directory of Certified Products and in the site www.eurovent-certification.com. Eurovent Chillers Certification Programme covers air cooled packaged chillers up to 600 kW and water cooled packaged chillers up to 1500 kW.
M03I40M7-03 15/11/07 page 6
RESIDUAL RISKS
GENERAL
This section lists some of the more common situations which, being beyond the control of the manufacturer, could be a source of risk to persons or property.
DANGER AREA
The figure below highlights the area in which only authorised personnel may operate.
External danger zone, identified by a precise area
around the unit and its vertical projection on the ground in the case of hanging unit.
Internal danger zone, identified by the area that can
be entered only after having intentionally removed the protecting panels or parts of these.
A
B
C
D
A = 2000mm B = 2000mm
C = 2000mm D = 2000mm
HANDLING
If handling operations are undertaken without adopting all the necessary safety procedures and exercising due care, the unit can fall or topple, causing damage — possibly extremely serious — to persons and/or property, and to the unit itself.
Ensure the unit is handled and manoeuvred as directed on the packing and in the present manual, and in accordance with local regulations.
In the event of refrigerant gas escaping, refer to the “Safety datasheet” for the particular refrigerant.
INSTALLATION
Incorrect installation of the unit can result in water leaks, accumulation of condensate, escape of refrigerant, electric shocks, fire, as well as irregular operation or damage to the unit itself. Make certain that the installation is carried out only by a qualified technician, also that the directions contained in this manual are followed and local statutory regulations observed. In the event of the unit being installed in a site where there is even the slightest risk of inflammable gas escapes and consequently the possibility of such gases accumulating in area around the unit, the risk of explosion and fire cannot be discounted. Take every care and precaution when selecting the installation site. Installation on a structure not able to bear the weight and/or afford a secure anchorage of the equipment may cause the unit to fall and/or topple, resulting in damage to persons or property, or to the unit itself. Make certain that every care
and precaution is taken when positioning and securing the unit. If the unit is easily accessible to children, unauthorized persons or animals, this is a situation that can give rise accidents and injuries, perhaps serious. Install the unit in a place where access is allowed only to authorized persons, or install barriers or guards preventing unauthorized entry.
GENERAL RISKS
A smell of burning, smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself. Isolate the unit from the electrical power supply (red-and­yellow) switch.
Contact an authorized service centre so that the source of the problem can be identified and remedied.
Accidental contact with heat exchange coils, compressors, pressure pipelines or other components can result in wounding or burns, or both.
Always wear suitable clothing, including protective gloves, when working in the danger area.
Maintenance or repairs carried out by unskilled operatives can result in harm or damage to persons and property, or to the unit itself. Always contact an authorized service centre.
Failure to close the panels of the unit, or to check that all the fixing screws of the panels are properly tightened, can result in harm or damage to persons or property, or to the unit itself.
Verify periodically that all panels are closed and made properly secure.
In the event of fire, the temperature of the refrigerant can rise to the point that pressure will exceed safety levels and perhaps cause fluid to be projected. It may also happen that parts of the circuit isolated by closed valves will explode.
Do not stand near safety valves, and never leave the valves of the refrigerant circuit closed.
ELECTRICAL SYSTEM
If the power line connecting the unit to the a.c. supply is incomplete, or if the connection is made with cables of incorrect cross section and/or with insufficiently rated protective devices, this can result in electric shock, toxicity hazard, damage to the unit or fire.
All work on the electrical system should be carried out referring to the wiring diagram and to the directions given in this manual, and the system itself must be dedicated.
Failure to secure the cover enclosing electrical components can lead to the infiltration of dust and water, ultimately causing electric shocks, damage to the unit, or fire.
Always fasten the cover securely to the unit. If live metal parts of the unit are not connected properly to
the earth system, they can cause electric shock or even death by electrocution.
Make absolutely certain that the connection to the earth system is made in accordance with correct practice.
Contact with live parts rendered accessible internally of the unit when the guards are removed can result in electric shock, burns or death by electrocution.
Before exposing these parts, make certain the isolating switch on the power line to the unit is set to the OFF position and padlocked, and post a warning sign.
M03I40M7-03 15/11/07 page 7
Contact with parts that could become live when the unit is started up can result in electric shock, burns or death by electrocution.
When there is no need for circuits to be powered up, set the isolating switch on the power line to the OFF position, padlock it and post a warning sign.
MOVING PARTS
Contact with the fan rotors can cause injury. Before removing the protective grilles or the fans
themselves, make certain the isolating switch on the power line to the unit is set to the OFF position and padlocked, and post a warning sign.
Before removing the protective grilles or the fans themselves, make certain the isolating switch on the power line to the unit is set to the OFF position and padlocked, and post a warning sign.
REFRIGERANT
In the event of safety valves coming into operation and releasing refrigerant gas, persons in the vicinity can be
injured or suffer toxic effects. Always wear suitable clothing and protective goggles when working in potential hazard areas.
In the event of refrigerant gas escaping, refer to the “Safety datasheet” for the particular refrigerant.
If an open flame or heat source is brought into contact with the refrigerant, or the pressurized gas circuit should overheat (e.g. during welding operations), this can cause explosion or fire. Do not position any heat source within the hazard area.
Maintenance or repair operations involving welding must be carried out with the system emptied of refrigerant.
WATER SYSTEM
Defects affecting pipelines, connections or valves and other control componentry can result in water being leaked or sprayed from the system, occasioning damage to property or causing short circuits in the unit.
Make certain all hydraulic connections are securely made, following the directions given in the present manual.
REFRIGERANT SAFETY CHARTS
01 Identifying elements for
the substance
Product name: forane 134a N°SDS 00941 Supplier: ELF ATOCHEM ITALIA Via Degli Artigianelli 10, 20159 Milano tel. 02/668111
02 Information concerning
composition of components
Chemical name of the compound 1.1.1.2 - tetrafloroethane General name: halogenated hydrocarbon CAS: 811-97-2 EINECS: 212-377-0
03 Identification of risk Effects on health: practically non-toxic
Greatest physical and chemical dangers: Thermal decomposition in toxic and corrosive products
04 First-aid measures Inhalation: Carry the victim into the open air. Resort to oxygen or artificial respiration if necessary.
Contact with skin: Frostbite must be treated in the same way as burns. Contact with the eyes: Immediate rinsing in abundant water. Instructions for the physician: Do not administer catecolammine (due to the sensitisation provoked by the product)
05 Fire prevention measures Specific dangers: Thermal decomposition into toxic and corrosive products. Hydrofluoric acid. Hydrochloric acid in gaseous form.
Phosgene Carbon monoxides (CO). Specific means of intervention: Cool containers/cisterns with jets of water. Prevent any sparks or flames. Do NOT smoke. Special protection systems for fire-fighting squads: Carry breathing apparatus and wear protective clothing.
06 Measures to take in case
of accidental spillage
Individual precautions: Avoid contact with the skin, eyes and inhalation of vapours. In an enclosed space: ventilate or use breathing apparatus (risk of suffocation). NO SMOKING ALLOWED. Remove all risk of sparks or flames.
07 Manipulation and storage Manipulation:
Technical measures/precautions. Form of storage and manipulation applicable to the products: PRESSURIZED GAS. Ensure adequate ventilation and evacuation for the level of equipment.
Advice for use: Prevent sparks and contact with hot surfaces. DO NOT SMOKE.. Storage: Technical measures/Storage procedures: Store at room temperature in the original container. Keep away from flames, hot surfaces
and sparks. Store in a cool, well-ventilated place. Protect full containers from sources of heat to avoid excessive pressures.
Packing: Recommended: Ordinary steel, Stainless steel. Avoid: Alloy containing more than 2% magnesium.
Plastics.
08 Control of individual
exposure/protection
Precautionary measures to be taken: Ensure a sufficient exchange of air and/or suction in workplaces. Control parameters. Exposure limits: recommended by ELF ATOCHEM: VME = 1000ppm=4420mg/m
3
Individual protective equipment: Respiratory protection: In case of insufficient ventilation, carry suitable breathing apparatus. Protection for the hands: Gloves Protection for the eyes: Protective eyewear. Specific hygiene measures: avoid contact with the skin, eyes and inhalation of the vapours. DO NOT SMOKE.
M03I40M7-03 15/11/07 page 8
09 Physical and chemical
properties
Physical state (20°C): liquid gas Colour: colourless Smell: Slightly similar to ether; pH: not applicable. Boiling point/interval: -26,4°C Melting point/interval: -101°C Flash point: No flare up at test conditions Self-ignition temperature: 743°C (1bar) 215°C (3bar) Vapour pressure: (25°C):0.665MPa (6.65bar) a (50°C):1.32MPa (13.2bar) a (70°C): 2.12MPa (21.2bar) Vapour density: (25°C): 4.26kg/m
3
Density: (25°C): 1206kg/m3 a (50°C): 1102kg/m3 a (70°C): 996kg/m3 Solubility: water: (25°C): 0,9g/l Distribution coefficient: log Pow = 1.06 (n-octanole/water) Other data:
Henry constant: 1.53Pa m
3
/mol Not dissociated in water Solubility of water in the product at 25°C: 0,097% in weight. Critical temperature: Tc=101°C Critical pressure. Pc=4.07MPa (40.7bar)
10 Stability and reactivity Conditions to avoid: Avoid contact with flames and red-hot metal surfaces.
Dangerous decomposition products: Thermal decomposition into toxic and corrosive products: hydrofluoric acid, hydrochloric acid in gaseous form, phosgene, carbon monoxide (CO) Other information: Stable product at ambient temperature. In presence of air the product can mix up into a flammable blend at particular temperature and pressure conditions.
11 Toxicological information Acute toxicity:
Inhalation: Practically non-toxic in experiments conducted on animals. CL50/inhalation/4 hrs/on rats>500000ppm As with other volatile aliphatic halogenated compounds, with the accumulation of vapours and/or the inhalation of large quantities, the product can cause: loss of consciousness and heart problems aggravated by stress and lack of oxygen; risk of death.
Local effects: Contact with skin: Frostbite possible from splashes of liquefied gas.
Practically non-irritating for skin in experiments conducted on animals (rabbits).
Contact with the eyes: practically non-irritating for eyes in experiments conducted on animals (rabbits). Sensibilisation: Contact with skin: Experim,ental for the animal: No skin sensitizer (guinea pig). Chronic toxicity: Studies on animal protracted inhalation do not highlight any chronic toxic effect (rat/ years(s)/ Inhalation: 50000ppm) Specifical effects: Genotoxicity according experimental available data NOT Genotoxic Cancerogenesis: experiments on animals do not highlight carcinogen effect clearly demonstrated (rat /Inhalation – for oral
administration) Toxicity for reproduction: Foetal growth no toxic effect for foetal development (rat/rabbit/inhalation). Fertility, according the available data on animal: no toxic effects on fertility (rats/inhalation)
This document refers to the product as is and which conforms to the specifications supplied by ELF ATOCHEM. If combinations or mixtures are made, check that there are no new dangers resulting from this action. The information provided in this report has been provided in good faith and is based on our latest knowledge of the product in question as of the date of publication of the same. The attention of users is drawn to the potential risks of employing the product for any use other than that for which it is intended. This report must be used and reproduced solely for purposes of prevention and safety. The list of legislative, regulatory or administrative texts must not be considered exhaustive. The product user is under obligation to refer to all the official texts concerning the use, conservation and manipulation of the product for which he is sole responsible. The product user must also provide all those who might come into contact with the product with the information necessary for their safety at work and the protection of their health and that of the environment, giving them a copy of this safety information report.
M03I40M7-03 15/11/07 page 9
RECEPTION
INSPECTION UPON RECEPTION
Check on arrival that the unit has not suffered damage during transit and that it is complete in every part as specified in the order. In the event of visible damage/deficiencies being discovered, make a note immediately on the delivery document with the comment: CONDITIONAL ACCEPTANCE — CLEAR EVIDENCE OF DEFICIENCIES/DAMAGE DURING TRANSIT
Inform both the supplier and the carrier of the details by fax and by registered mail with advice of receipt not later than 8 days after taking consignment. Notifications sent after 8 days have elapsed will be ignored.
STORAGE
Shelter from: direct sunlight, rain, sand and wind Temperature: maximum 60°C minimum -10°C Maximum humidity: 90% The respect of the instructions on the exterior side of the
packaging assures the physical and functional integrity of the unit for the final user’s advantage.
It is recommended to:
Handle carefully
Keep in a dry place
Avoid putting other objects on top of the unit (respect
the limits of levels of superimposition shown in the package)
Avoid placing the unit with thermoretractable protection under the sun since the pressure of the circuits can assume values which activate the safety valves.
HANDLING
The operation of handling the unit must be carried out respecting the instructions of the safety norms in force (Legislative Decree 626/94 and following modifications)
Before starting the handling operations:
Value the critical points during handling (stairs, flights, disconnected routes, doors, etc)
Verify that the lifting capacity of the means used is adequate to the unit weight
Consider that the barycentre could be moved with respect to the center of the unit
Before starting to lift, verify that the unit is at a stable balance
The following examples are indications; the choice of the means and of the handling modes will depend on factors, such as:
The unit weight
Type and overall dimensions of the unit
Place and route for the handling (dirt yard, asphalted
square, etc)
Condition of the place of destination (roof, square, etc)
Handling distance characteristics (distances, flights,
steps, doors)
LABELS / YELLOW BRACKETS SHOW THE LIFTING POINTS
C > D
D
C
BA
A < B
==
Baricentro
barycentre
!
1
2
How to balance the charge
Move the upper hook or the lower hooks,
according to the spring equalizer rocker arm type
use a spacer bar
to avoid damaging the unit
Insert safety pins (1)
and split pins (2)
M03I40M7-03 15/11/07 page 10
HOISTING using a CRANE or SIMILAR.
- Slide the provided lifting pipes into the holes in the base of the unit.
- Position the ends of the pipes that protrude from the unit so that you can insert the provided shear pins into the proper holes.
- Fit the lifting belts over the pipes between the safety rods and the base of the unit (see drawing).
- Gradually bring the lifting belts under tension, making sure they are positioned correctly. Make sure the unit is always in steady equilibrium.
- Start hoisting the unit.
Split pin for belt
REMOVING THE PACKING
For removing the packaging, use specific personal protection for the operator (gloves, glasses, etc.).
While removing the packaging, pay attention not to damage the unit.
Check for any visible damage.
Dispose of the packaging by taking it to specialist collection or recycling centres in accordance with local regulations.
M03I40M7-03 15/11/07 page 11
POSITIONING
GENERAL
For installing air-conditioning systems, it is necessary to consider the following:
the technical spaces necessary for the machine and
system
the place where the machine will be installed
the transport of thermal carrier fluids and relevant
connections to the unit:
o water o air o refrigerant (unit in more sections)
electrical connections
If these aspects are not evaluated carefully, they can affect the performances and the working life of the unit.
FUNCTIONAL CLEARANCES
When placing the unit, please respect the functional clearances indicated in DIMENSIONS section. The functional spaces need to be observed because of the following:
to guarantee the good operation of the unit
to allow the performance of all maintenance operations
to protect the authorized operators and exposed people
If more units are placed close to one another, the functional spaces must be doubled.
POSITIONING
1. The units are designed for INDOOR installations,
performed in fixed positions and in areas accessible only to qualified and authorized personnel
2. SAFETY VALVE (only if present on the unit) : the
installer is responsible for evaluating the opportunity of installing drain tubes, in conformity with the local regulations in force ( EN 378 )
3. Install the unit raised from the ground
4. avoid installations in places subject to flooding
5. Verify that the fixing/supporting points are level and
suitable to support the weight of the unit (see the weight and the weights distribution)
6. It is recommended to put the unit on specific
antivibration devices
Each support point of the unit sustains a different weight. Therefore, each anti-vibration device is sized for a specific support point, and can only be placed there. The anti-vibration devices must therefore be placed in accordance with the instructions provided with them and with the dimensional drawings in which the support points are indicated by W1 , W2 , W3 etc .
On each anti-vibration device (if provided by CLIVET), its identifying code is stamped, for example C6100100
Flexible joints are necessary on all the hydraulic/ aeraulic connections (the joints are not supplied by Clivet)
INSTALLING ANTIVIBRATION MOUNTS
C6100026-28 C6100030-32
M03I40M7-03 15/11/07 page 12
Table point of support / antivibration mount
CLASS A
Size Compressor W1 W2 W3 W4
Ant. mount code
ST C6100026 C6100026 C6100028 C6100028
PE980005
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100026 C6100026 C6100028 C6100028
PE980005
2.160 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
2.180 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
2.220 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
2.250 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100032 C6100028
PE980020
2.280 Bitzer
EN C6100028 C6100028 C6100032 C6100032
PE980007
ST C6100028 C6100028 C6100032 C6100028
PE980020
Refcomp
EN C6100032 C6100028 C6100032 C6100028
PE980007
ST C6100032 C6100028 C6100032 C6100028
PE980007
2.300 Bitzer
EN C6100032 C6100028 C6100032 C6100032
PE980025
ST C6100028 C6100028 C6100032 C6100032
PE980007
Refcomp
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100032 C6100032 C6100032 C6100032
PE960007
2.320 Bitzer
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100028 C6100028 C6100032 C6100032
PE980007
Refcomp
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100032 C6100032 C6100032 C6100032
PE960007
2.340 Bitzer
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100028 C6100028 C6100032 C6100032
PE980007
Refcomp
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100032 C6100032 C6100032 C6100032
PE960007
2.360 Bitzer
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100032 C6100032 C6100032 C6100032
PE960007
Refcomp
EN C6100032 C6100032 C6100032 C6100030
PE980032
ST C6100032 C6100032 C6100030 C6100030
PE960007
2.420 Bitzer
EN C6100032 C6100032 C6100030 C6100030
PE960009
ST C6100032 C6100032 C6100032 C6100030
PE980032
Refcomp
EN C6100032 C6100032 C6100032 C6100030
PE980032
ST C6100032 C6100032 C6100030 C6100030
PE960009
2.450 Bitzer
EN C6100032 C6100030 C6100030 C6100030
PE980029
ST C6100032 C6100032 C6100030 C6100030
PE960009
Refcomp
EN C6100032 C6100030 C6100030 C6100030
PE980029
ST C6100032 C6100032 C6100030 C6100030
PE960009
2.480 Bitzer
EN C6100032 C6100030 C6100030 C6100030
PE980029
ST C6100032 C6100032 C6100030 C6100030
PE960009
2.540 Refcomp
EN C6100030 C6100030 C6100030 C6100030
PE960008
ST C6100032 C6100032 C6100030 C6100030
PE960009
2.600 Refcomp
EN C6100030 C6100030 C6100030 C6100030
PE960008
M03I40M7-03 15/11/07 page 13
CLASS B
Size Compressor W1 W2 W3 W4
Ant. mount code
ST C6100026 C6100026 C6100026 C6100026
PE980003
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100026 C6100026 C6100026 C6100026
PE980003
2.160 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100026 C6100026 C6100026 C6100026
PE980003
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100026 C6100026 C6100026 C6100026
PE980003
2.180 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
2.220 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
2.250 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
Refcomp
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
2.280 Bitzer
EN C6100028 C6100028 C6100028 C6100028
PE980006
ST C6100028 C6100028 C6100028 C6100028
PE980006
Refcomp
EN C6100028 C6100028 C6100028 C6100032
PE980020
ST C6100028 C6100028 C6100028 C6100032
PE980020
2.300 Bitzer
EN C6100028 C6100028 C6100032 C6100032
PE980007
ST C6100028 C6100028 C6100028 C6100032
PE980020
Refcomp
EN C6100028 C6100028 C6100032 C6100032
PE980007
ST C6100028 C6100032 C6100032 C6100032
PE980025
2.320 Bitzer
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100028 C6100028 C6100032 C6100032
PE980007
Refcomp
EN C6100028 C6100028 C6100032 C6100032
PE980007
ST C6100032 C6100032 C6100032 C6100032
PE960007
2.340 Bitzer
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100028 C6100028 C6100032 C6100032
PE980007
Refcomp
EN C6100028 C6100028 C6100032 C6100032
PE980007
ST C6100032 C6100032 C6100032 C6100032
PE960007
2.360 Bitzer
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100028 C6100028 C6100032 C6100032
PE980007
Refcomp
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100032 C6100032 C6100032 C6100032
PE960007
2.420 Bitzer
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100028 C6100028 C6100032 C6100032
PE980007
Refcomp
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100028 C6100028 C6100032 C6100032
PE980007
2.450 Bitzer
EN C6100032 C6100032 C6100032 C6100032
PE960007
ST C6100032 C6100032 C6100032 C6100032
PE960007
Refcomp
EN C6100032 C6100032 C6100030 C6100030
PE960009
ST C6100032 C6100032 C6100032 C6100032
PE960007
2.480 Bitzer
EN C6100032 C6100032 C6100030 C6100030
PE960009
ST C6100032 C6100032 C6100032 C6100032
PE960007
2.540 Refcomp
EN C6100032 C6100032 C6100030 C6100030
PE960009
ST C6100032 C6100032 C6100030 C6100030
PE960009
2.600 Refcomp
EN C6100032 C6100030 C6100030 C6100030
PE980029
M03I40M7-03 15/11/07 page 14
WATER CONNECTIONS
GENERAL
Piping must be designed with the least possible number of bends and head variations. If the pressure chute of the installation is above the useful prevalence of the pump, the water delivery capacity is reduced as well as, as a consequence, the thermal exchange and the yield.
INTERCEPTING VALVES
Install on the input and output of the user parts (exchangers, coils, humidifiers, etc) So that it will be possible to carry out all the service operations and possible substitutions without emptying the installation.
PRESSURE AND TEMPERATURE INDICATOR
Install on the input and output of the user parts (exchangers, coils, humidifiers, etc) So that it will be possible to carry out all the service operations.
AUTOMATIC OR MANUAL ESCAPE VALVES
Install the highest points of tubes in a way that the air can escape form the circuit.
BLEEDING COCK
Install them at the lowest points of the circuit, so as to allow emptying.
LEAKAGE TESTS
Before performing the insulation of the tubes, carry out a leakage test.
TUBE INSULATION
All tubes of water must be insulated so that to avoid the formation of condensation and thermal dispersions along the tubes themselves. Verify that the insulation is the vapour coil type. The connections for the air escape and for the emptying must be out of the insulating thickness to assure the accessibility.
CONNECTIONS SUPPORTS
The weight of the hydraulic connections must be supported in the exterior of the unit so as not to stress the connections of user devices (exchangers, coils, humidifiers, etc ) .
ANTI-VIBRATION DEVICES
In case of units with anti-vibration devices, it is necessary to assemble elastic joints, even on water connections.
RISK OF FREEZE
If the unit and the relevant water connections are subject to temperatures near 0°C:
mix the water of the system with glycol
protect the tubes with heating cables under the tubes
insulation
empty the system by verifying that:
o no taps are closed so they can not trap the water,
even after emptying
o there are no low points where the water can
stagnate even after emptying; blow if necessary
INSTALLATION EMPTYING
The refilling of the water present in the installation increase the oxidation phenomena and lime deposits.
If necessary empty only the interested system section and anyway empty or refill the installation if necessary .
EXPANSION TANK
The installation must be kept at the right pressure by both an expansion tank and a combined valve of pressure reduction and discharge; if the components are present on the unit, they must be installed on the installation. The expansion tank must be dimensioned in function of the water in the installation.
MAX. WORKING PRESSURE
10,5 bar evaporator 16 bar condenser
ARIES EFFECTS AND AIR BUBBLES CAN PRODUCE THE OVERCOMING AND CAUSE WATER DROPS.
EXCHANGER USE SIDE
FILTER
It is very important for the water to be free of impurities. If it is not, the efficiency of thermal exchange is diminished. In worst cases, the exchanger can be irreparably damaged. If the filter is not present on the machine, it must be immediately installed upstream from the unit, in a position which can be easily reached for cleaning.
The filter mesh must be :
< 1 mm unit with 1 compressor
< 1.5 mm multicompressor unit.
FLOW SWITCH
The flow switch must be present as a component of the system, so as to ensure shutdown of the unit if water is not circulating. It must be installed in a straight tract of the tubes, not near the elbows, which can generate harmful turbulence
UNFREEZABLE LIQUIDS
If the unit is used when the water temperature is lower than + 4°C, avoid the formation of ice by using unfreezable liquids (ex. Ethilenic Glycol) in the necessary percentage. The use must also be determined for ambient temperatures near 0°C .
ANTIFREEZE RESISTANCES
If the unit is equipped with antifreeze resistances on the exchanger side (standard or optional according to the models), verify that they are electrically fed during periods that the machine is stopped (night, weekends, long stops)
WASHING THE SYSTEM
Carefully wash the system by using clean water and discharge it before connecting the unit.
M03I40M7-03 15/11/07 page 15
DIAGRAM OF RECOMMENDED USE SIDE CONNECTION
Depending on the type of machine and the selected setup, some components may be integrated into the unit.
P
9
11
14
8
F
2
3
5
12
7
6
4
8
1
10
13
P
7
1. Charged system pressure switch
2. vent
3. circulating pump / pump
4. expansion tank
5. safety valve
6. flow switch
7. pressure switch / thermometer
8. filter
9. filling valve
10. antivibration joints
11. user side exchanger
12. Differential pressure switch
13. Discharge cock
14. inertial storage tank
The accumulation tank is necessary in the event of the following:
the water in the system is very low
the unit will not be used in a private house (in an industrial process or other)
RECOVERY EXCHANGER
OPTIONAL - The unit can be equipped with exchangers to recover the condensation heat.
The recovery can be:
TOTAL
with 100% recovery of the condensation heat
the thermoregulation is performed by CLIVET control
system
PARTIAL
with 20% recovery
The customer is responsible for the management of the
circulation pump, valves, thermostats, etc
The recovery input water must not be below 25°C, in the event that, wrongful operations and breakages of the unit can occur .
Water connections must be performed carefully as for the evaporator (filter, circuit washing, etc) .
Perform all necessary interventions to avoid the RISK OF FREEZING (tubes insulation, emptying of circuit, addition of glycol, anti-freeze resistances) .
Water temperature can reach high temperatures (up to 100°C), therefore:
avoid the RISK OF BURNS by adopting the necessary
precautions (insulation of tubes, temperature detecting station on water if the sanitary use is foreseen, etc)
Install safety valves and specifically dimensioned expansion tanks in the hydraulic circuit.
VICTAULIC CONNECTIONS
1. Take away the supplied connection union by acting on the connection joint Victaulic.
2. Weld the union to the installation pipe.
3. Perform the connection between the installation pipe and the evaporator, using the joint.
Do not weld the system pipe with the Victaulic connection joint attached.
The rubber gasket might be irreparably damaged
M03I40M7-03 15/11/07 page 16
RECOMMENDED SOURCE SIDE CONNECTION SCHEMA
P
8
F
2
3
56
1
P
4
7
8
9
10
1. Antivibration joints
2. Shut-off valve
3. Safety valve
4. Flow switch
5. System min. pressure manostat
6. Pressure switch / thermometer
7. vent
8. Differential pressure switch
9. Pump
10. Filter
EVAPORATIVE COOLING TOWER WELL
M03I40M7-03 15/11/07 page 17
SYSTEM MEASURES ON SOURCE SIDE
FILTER
It is very important for the water to be free of impurities. If it is not, the efficiency of thermal exchange is diminished. In the worst cases, the exchanger can be irreparably damaged. The filter, if not present on-board the machine, must be installed immediately upstream from the unit, in a position that is easily accessible for cleaning
FLOW SWITCH
Since it is a system component, it must always be included, in order to ensure unit shutdown in the event of failure of water circulation. It is to be installed in a straight section of the pipes, and not near curves which generate harmful turbulence.
ANTI-FREEZE SOLUTIONS
For use of the unit with ambient temperatures near 0°C, use antifreeze solutions such as ethylene glycol to prevent the formation of ice. Its use is also required when geothermal probes are used.
SYSTEM WASHING
Before connecting the unit, carefully wash the system by filling it and emptying it several times with clean water.
CONTROL OF FLOW RATE
This makes it possible to limit water consumption, increase energy efficiency and extend the unit's operating limits. It can be modified by using
1. Modulating motorized valve
2. Cut-off valve
3. Pressure switch valve
CUT-OFF VALVE
This allows cut-off of water on the source side whenever the compressor is not running.
It is therefore advisable for systems with disposable water, if there is no modulating valve
8
BY
PR
C1
8
BY
PR
C2
BT3-BT4 TEMPERATURE PROBES OF WDHH UNIT
These probes, with respective connection, are supplied with the unit and they must be fitted as specified in the drawing.
CIRC 1 CONDENS.
CIRC 2 CONDENS.
SLEEVE 1/2” (n ot supplied)
NTC TEMPERATURE PROBE OF IP67 TIN
PROBE FIXATION NUT
Scrolling CONNECTION 6mm 1/2” in brass and sealed O-RING
M03I40M7-03 15/11/07 page 18
ELECTRICAL CONNECTION
GENERAL
The characteristics of the electrical lines and relevant components must be determined by SPECIALIZED PERSONNEL ABLE TO DESIGN ELECTRICAL INSTALLATIONS; moreover, the lines must be in conformity with professional procedures and the regulations in force.
All electrical operations should be performed by trained PERSONNEL HAVING THE NECESSARY REQUISITES UNDER LAW and being informed about the risks relevant to these activities.
Before performing any operation on the electrical system, make sure that the unit supply line is SELECTED AT START.
The earth connection must be made prior to other electrical connections.
For all electrical type operations, REFER TO THE ELECTRICAL DIAGRAM ATTACHED TO THE UNIT; the number of the diagram is shown on the registration plate positioned on the electrical board or next to it.
The electrical diagram should be carefully kept together with this manual and should be AVAILABLE FOR FUTURE INTERVENTION ON THE UNIT.
LINE OF UNIT POWER SUPPLY The ELECTRICAL DATA OF THE UNIT are shown in the
technical chart of this manual and on the unit registration plate. The presence of accessories can vary according to the unit; the electrical data shown in the technical chart
refer to standard units. In the event of differences between the data of the registration plate and the data shown in this manual, as well as in the technical chart, please refer to the DATA SHOWN IN THE REGISTRATION PLATE.
The protection device of the unit power supply line should break off the short circuit power whose value should be determined according to the plant features.
The section of supply cables and protection cable must be seized according to the characteristics of the protections used.
SIGNALS / DATA LINES Do not overpass the maximum power allowed, which
varies, according to the type of signal.
Lay the cables far from power cables or cables having a different tension and that are able to emit electromagnetic disturbances.
Do not lay the cable near devices which can generate electromagnetic interferences.
Do not lay the cables parallel to other cables; cable crossings are possible, only if laid at 90°.
Connect the screen to the ground, only if there are no disturbances
Assure the continuity of the screen during the entire extension of the cable.
Observe, if any, the requirements about impendency, capacity, attenuation
STANDARD UNIT ELECTRICAL DATA
Acoustic configuration: Standard (ST) / extremely low noise (EN) / Energy efficiency: Efficiency class A
Sizes 2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
F.L.A. FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.A. - Total A 263 292 326 392 428 452 476 510 544 650 680 710 823 933
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.I. - Total kW 157 176 200 240 262 279 295 319 342 402 420 438 494 562
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value A 627 641 683 808 879 650 674 703 737 911 975 1005 1474 1529
voltage unbalance: max 2 % power supply: 400/3/50 Hz +/-6%
Acoustic configuration: Standard (ST) / extremely low noise (EN) / Energy efficiency: Efficiency class B
Sizes 2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
F.L.A. FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.A. - Total A 263 292 344 382 431 463 496 527 559 592 642 748 823 933
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.I. - Total kW 157 176 213 236 269 294 318 337 356 377 402 443 494 562
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value A 627 641 490 552 577 590 622 701 733 839 916 1250 1474 1529
voltage unbalance: max 2 % power supply: 400/3/50 Hz +/-6%
M03I40M7-03 15/11/07 page 19
CONNECTION TO THE MAINS
1. Make sure that the sectioning device at the beginning of the unit’s power line is opened, locked and equipped with a signal.
2. Open the general line disconnecting switch (if present)
3. Verify that the net is in conformity with the data shown in the registration plate placed on the electrical board.
4. Check the dimensional drawing for the input of the electrical lines
5. Take away the closing plate placed on the electric board (ONLY IF PRESENT) and drill a hole through it to pass the cables through)
6. Protect the cables, using the fairlead of an adequate size.
7. Using the layout of the electrical diagram, single out the connecting terminals of the electrical supply cables, of the neutral (if foreseen) and the PE protection cable
8. Connect the cables to the relevant terminal boards
9. Before supplying power to the unit, make sure that all the safety devices that were removed during electrical connections are positioned again.
Use voltage-free remote control devices that are suitable to commutate very low loads (12V, 10mA)
F1 F4F3F2
?
ESC
I HOME
ALARMMODE SETUP STATE
ON
C O O L
STEP: 03 / 04
15 / 02 / 03 08:03:51
7.
0
°C SET
9.
3
°C OUT
12.
2
°C IN
Few inputs must be activated by configuration parameters whose access is reserved to authorized assistance centers (in order to avoid unauthorized modifications)
ON / OFF FROM REMOTE CONTROL It allows the remote start and stop, not by keypad. It can be used to disable the unit during the night, the weekend etc., so with ON or OFF periods relatively longs (some hours). It has not to be used with ON or OFF cycles too much shorts: they compromise the operating logic and they can cause malfunctions or faults. In summer operating, for example, ON –OFF cycles lower than one hour can compromise the thermoregulation logic, that implements an integral check. If this function is not used, jump the respective terminals .
SIGNALIZATION OF MALFUNCTIONING/ UNIT FUNCTIONING Remote signalization of the proper function (ex. green light) or signalization of blocks of the machine (ex. red light). Maximum voltage at the terminal ends is 24v ac and maximum power is 1A
SECOND SET-POINT It allows the use of a secondary set-point, such as, for example, for a night operation, which can be activated by a remote contact. When the contact is CLOSED, the secondary set-point is activated .
DEMAND LIMIT It allows one to temporarily limit the electric power absorbed by the unit, according to a 10 vcc or 4-20 mA external signal. The higher the signal is, the lower the number of compressors available to meet the thermal need. The parameters must be configured by the assistance center .
MENU NUM Parameter name meaning
thermoregulation­demandlimit
7 DmandLimitEn
Enables the function :
0= disabled
1=by signal
2=by parameter
parameter-set-sensors 82 TypeDl Type of signal : 0=0-10 V ; 1=4-20mA
MODULATING MOTORIZED VALVE It allows to modulate the water flow-rate source side according to its temperature . 0-10V signal, see wiring diagram .
M03I40M7-03 15/11/07 page 20
EXTERNAL AIR TEMPERATURE PROBE - Optional It allows the automatic correction of the set-point according to the external air temperature. For example, the summertime with low external temperatures, it is possible to have the internal comfort even with set-points higher than the standard. The parameter configuration is necessary.
MENU NUM Parameter name meaning
1 EnCompExt
External compensation enabling 0 = no; 1 = COOL only; 2 = HEAT only; 3 = always
4 MaxCExtC Max. ext. compensation value of cooling
5 MaxCExtH Max. ext. compensation value of heating
93 CextMaxH Max. ext. temp. of heating compensation
94 CextMinH Min. ext. temp. of heating compensation
106 CextMaxC Max. ext. temp. of cooling compensation
parameter control compext
107 CextMinC Min. ext. temp. of cooling compensation
parameter-set-sensors 9 ProbeText It enables ext. temp. probe: 0=yes ; 1=non
SUMMER WINTER
p4
p106 p107 Text °C
set COMPENSATO
p 5
set point COMPENSATO
p 94 p 93 T ext °C
EXTERNAL AIR HUMIDITY PROBE - Optional It allows the automatic correction of the set-point, according to external air enthalpy . Nel funzionamento invernale la correzione avviene sulla sola temperatura. The working process is similar to the above mentioned process . The parameter configuration is necessary.
MENU NUM Parameter name meaning
4 MaxCExtC Max. Summer correction value
110 HexMinC Min. correction ext. enthalpy
parameters thermoregulation compext
111 HexMaxC MAX. correction ext. enthalpy
parameter-set-sensors 23 ProbeURExt Enables external humidity probe: 1=YES / 0=NO
M03I40M7-03 15/11/07 page 21
WATER RESET - Opzionale It allows the automatic correction of the set-point, according to an external signal of 4-20 mA or 0-10 vcc. The working process is similar to the above mentioned process . The parameter configuration is necessary .
MENU NUM Parameter name meaning
11 MaxCWRC WR Summer correction max. value
24 MaxCWRH WR Winter correction max. value
75 WaterReset
Water Reset enabling: 0 = no; 1 = COOL only; 2 = HEAT only; 3 = always
102 SWRMaxH Winter MAX correction signal
104 SWRMinH Winter MIN correction signal
105 SWRMaxC Summer MAX correction signal
parameter control waterreset
108 SWRMinC Summer MIN correction signal
parameter-set-sensors 83 TypeWR Inlet signal type: 0=0-10V; 1=4-20mA
SUMMER WINTER
°C
set point COMPENSATO
par 108 par 105 4 mA 20 mA
par11
set point COMPENSATO
p 24
p 102 p 104 T ext °C
CLIVET TALK MODULAR SYSTEM COMPOSITION
CLIVET TALK system is made up of different modules connected to each other with the CAN OPEN protocol. The system configuration varies according to the typology of the unit and of the accessories: not always the represented electric modules are all presents on the unit .
INTERFACE
code C5110821 The interface module allows for the control of the operations of the whole machine, the programming of the different adjustment parameters and also to display the alarms and the unit status.
CENTRAL MODULE
code C5110694 The central module manages the system configuration, the working mode, the set point, the thermal adjustment, remote inputs.
HL
gnd
J17
10
8 6 4 2
9 7 5 3
1
J4
1 3 5 7 9
2 4 6 8 10
CN1
CN2
11 13 15
12 14 16
J5
1 2 3 4 5 6
7 8 9 10 11
DRIVERALCO VCM
123456
78
910
1
1
1
2
SCREW COMPRESSOR MODULE
code C5110801 It manages the cooling circuit (compressors, fans, valves) and relative safety devices.
HL
gnd
J17
10
8 6 4 2
9 7 5 3
1
J4
1 3 5 7 9
2 4 6 8 10
CN1
CN2
11 13 15
12 14 16
J5
1 2 3 4 5 6
7 8 9 10 11
DRIVERALCO VCM
123456
78
910
1
1
1
2
COMPRESSOR MODULE - TANDEM / TRIO
code C5110804 (tandem) – C5110801 (trio) It manages the cooling circuit (compressors, fans, valves) and relative safety devices.
M03I40M7-03 15/11/07 page 22
21 20 19 18 17
16 15 14 13 12
DRIVER VCM
1 2 3 4 5 6
7 8
9 10 11 12
ELECTRONIC THERMOSTATIC EXPANSION VALVE MODULE
code C5110802 This manages the electronic thermostatic valve and the relative sensors for control of temperature/pressure. It is installed above the compressor module
DRIVER VCM
DRIVER MODULE
code C5110803 The electronic thermostatic valve management firmware is located here. It is mounted on the expansion module.
HL
gnd
J17
J12
CN1
CN2
DIP1
DIP2
JUMP4
STRIP
gnd
OFF
ON
1234
OFF
ON
1234
5678
123456
97531
108426
246810
13579
JUMP1
JUMP2
JUMP3
EVAPORATOR MODULE
code C5110674 It manages components, safety devices, inputs and outputs relative to the water circuit (pumps, differential manostat, temperature probes)
HL
gnd
J17
J12
CN1
CN2
DIP1
DIP2
JUMP4
STRIP
gnd
OFF
ON
1234
OFF
ON
12345678
123456
97531
108426
246810
13579
JUMP1
JUMP2
JUMP3
PUMP MODULE
code C5110701 It manages controls and safety devices relative to the circulation pumps
HL
gnd
8 9 10 11
JUMP4
1234 5 67
DIP1
DIP2
STRIP
OF F
O N
1234
OF
F
O N
12345678
JUMP1
JUMP2
JUMP3
13579
24810 6
CN2
CN1
161412108642
151311
97531
J22
J15
gnd
RECOVERY MODULE
code C5110679 It manages the electrovalves and the pumps relative to the recovery circuit.
REMOTE TERMINAL
cod PE1W0005 The remote keyboard has the same functions of the keyboard on board of the machine. The connection of the remote keyboard to the system on board of the machine is carried out, using the “CAN to CAN” converter, which must be placed in the electric board of the machine
The REMOTE KEYBOARD must be configured with the software address = 27 (only an authorised service centre can perform this operation). If the unit is managed by timetables, they must be activated only on one of the two keyboards of the machine, better if the remote keyboard. CONNECTIONS: refer to the electric diagram and to the SIGNAL/DATA LINES paragraph.
230/1/5
0
1
2
V
A
C
XC
1
2
1
2
A
L H
QE unit 1
G
N
D
C5110675
L
S
H
I
L
D
H
230/1/50
2 X 0.34 mm2
+ sch
CAN to CAN
Can 0
Can 1
M03I40M7-03 15/11/07 page 23
MODBUS - CONVERTER CAN TO MODBUS VIA RS 485
Interfacing via RS 485 is performed using a converter for each unit. The converter must be mounted on the electric board of the unit and connected, following the electric diagram attached to the unit. CONNECTIONS: refer to the electric diagram and to the SIGNAL/DATA LINES paragraph
dip switch for the serial address of the module
LED 1 : signalization of gateway working
LED 2 : signalization of gateway in programming
jumper for activating the firmware rewriting of the gateway
RS 485 serial port
dip switch for the configuration of the CAN OPEN addresses
Connection to the CAN network of the machine
Power supply
terminator NOT activated
LGH
C5110770
18
O
N
1
ON
12 Vac
RS 485
+
-
s
CAN 0
Terminator activated
UNIT NETWORK – MINI NETWORK – MASTER SLAVE
The CLIVET TALK Local Network system allows to connect up to 6 machines in a network which all serve the same installation. To interact with the network which controls the working of the system, it is necessary to have a CAN to CAN converter code C5110692 for each machine. Each single machine is equipped with the standard electronic devices: if necessary, it can function as an independent unit.
SpinChiller SpinChillerSpinChiller
CAN 0
At use
Cavo CAN OPEN
Max. extension 200mt with a twisted and shielded pair
L max. single derivation =20cm
L max. single derivation =20cm
L max. single derivation =20cm
Unit #3Unit #2Unit #1
Water Reset
Temp. Ext
UR% Ext
Mode remoto
PE1W0009
(C5110692)
Master #1
PE1W0009 (C5110692)
Slave #2
PE1W0009
(C5110692)
Slave #3
Unit MASTER
CAN 1
CAN 0
CAN 1
CAN 0
CAN 1
CONNECTION CABLE : Section (nominal) 0.34mm2 Heater 70mΩ/meter Impedance 120mΩ/meter Propagation delay 5nS/metrer Length MAX 200meters
DATALOGGER - cod PE1W0006 CONNECTIONS : make reference to the electrical panel and to SIGNALS/DATA LINES paragraph
C5110676
M03I40M7-03 15/11/07 page 24
KIT LONWORKS Upon request, the unit is equipped with the kit already mounted on the electric board; it can eventually be mounted later. Refer to the electric diagram and to the LONWORKS MANUAL. For information about cables for the Lonworks network, visit the web site www.echelon.com
.
LONWORKS technology is a complete platform to implement the network system control. These networks consist of intelligent control instruments, or nodes, which interact with their environment and communicate to each other by using a common message based on the (LonTalk®) protocol. A LONWORKS network can have up to 32,385 nodes subdivided into 255 sub-networks (127 nodes/sub-network). The Gateway device is already configured, according to the Echelon classification for the type of the unit it is designed for, with a number of managed variables, which is a sub-array of those managed originally by the machine and able to accept the Echelon standard profiles. The supply of this device does not include the activity of configuration and management of the LonWorks network to which it is connected; as usual, they are supplied by the Supervision System supplier.
Signalization led of gateway in programming
Dip switch for setting the module serial address
Signalization led of gateway operation
jumper to activate the gateway firmware rewriting
terminator INSERTED
Dip switch configuration of CAN OPEN addresses
Terminator NOT ACTIVATED
17
18 19 20 21 22
23 24
12
3
4
LiteConnector
LonWorks
Module Status
Serial Status
Service
Net B
Net A
Net B
Net A
SHLD
NC
GND
Vin+
RS485
C5110676
Lon Works SIDE
18
ON
1
O
N
12 Vac
485
+
-
S
L G H
CAN 0
GATEWAY LON-WORKS
CAN TO MODBUS
12 Vac
M03I40M7-03 15/11/07 page 25
START-UP
ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES.
THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF
THE SYSTEM.
ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS.
PRELIMINARY CHECKS
Before checking, please verify the following
1. the unit should be installed properly and in conformity with this manual.
2. the electrical power supply line should be sectioned at the beginning.
3. the sectioning device is locked and the proper warning “not to operate” sign is placed on the handle.
4. make sure no tension is present
REFRIGERANT SYSTEM
Carefully check the refrigerating circuit: the presence of oil stains can mean leakage caused by transportation, movements or other).
Open the cocks of the refrigerator circuit, if there are any.
Using the unit manometers, if present, or service manometers, verify that the refrigerating circuit is in pressure.
Make sure that all the service outlets are closed with proper caps; if caps are not present a leak of refrigerant can be possible.
WATER SYSTEM
Ensure that the plumbing system has been washed. Drain the wash water before connecting the unit to the system.
Check that the water circuit has been filled and pressurised.
Perform a seal check at max. working pressure checking that no leaks are present.
Check that the shut-off valves in the circuit are in the "OPEN" position. Check that there is no air in the circuit. If required, bleed it using the vent valves in the system. Check that there are no ARIES EFFECTS in the transient (pump and / or valve activation/deactivation) When using antifreeze solutions, make sure the glycol percentage is suitable for the type of use envisaged.
% weight of ethylene glycol
10 % 20 % 30 % 40 %
Freezing point
- 4 °C - 9 °C - 15 °C - 23 °C
Safety temperature
- 2 °C - 7 °C - 13 °C - 21 °C
Check that the circulator pumps are not blocked. In fact, their motor shaft may seize up, especially after long shutdowns. Unblocking can be accomplished with a screwdriver using the purge hole.
ELECTRICAL SYSTEM
Check the proper tightening of the screws that fix the conductors to the electrical components in the board (during handling and transportation, the vibrations could have loosened them). Verify that the unit is connected to the ground plant. Control that all panels and protection devices of the unit are repositioned and blocked. Charge the unit by closing the sectioning device, but leave it on OFF. Make sure that the tension and net frequency values are within the limit of: 230 +/- 6% single phase unit; 400/3/50 +/- 6% three-phase unit Control the unbalancing of the phases: it must be lower than 2% . Example: L1 - L2 = 388 V, L2 - L3 = 379 V, L3 - L1 = 377 V average of the measured values = (388 + 379 + 377) / 3 = 381 maximum deviation from the average = 388-381= 7V Unbalancing = (7/381) x 100 = 1.83% = ACCEPTABLE Operating out of the indicated limits causes the loss of the guarantee as well as very serious damages.
IF THE CRANKCASE RESISTANCES ARE FITTED
when the unit is started up for the first time and following all prolonged periods of inactivity is OBLIGATORY to connect the oil resistances on the compressor crankcase at least 8 hours before the compressor is to be starter.
BEFORE POWERING THE RESISTANCES, OPEN THE COMPRESSORS COCKS, IF PRESENT.
To supply the resistances is necessary to switch off the isolator switch on the unit.
To make sure that hte resistances are working, check the power input with amperometic pliers.
At start-up the compressor cranckase temperature on the lower side must be higher at least of 10°C than the outside temperature.
DO NOT START THE COMPRESSOR WITH THE CRANKCASE OIL BELOW OPERATING TEMPERATURE.
VERIFY TENSIONS – ABSORPTIONS
Check that the temperatures of the fluids are included in the WORKING LIMITS.
If the controls of the previous paragraphs are positive, it is possible to restart the unit.
For information on the control panel, refer to the paragraph CONTROL.
While the unit is working (ATTENTION ELECTRIC RISK: WORK SAFETLY) check:
Power supply tension
Phase unbalance
Total absorption of the unit
Absorption of the single electric loads
REMOTE INPUT CONFIGURATIONS
Check used remote inputs are activated (ON-OFF etc.) as given in the instructions in the ELECTRIC WIRING chapter.
SETTING THE SET-POINT
Check if it is necessary to modify the set-points shown in the CONTROL chapter
M03I40M7-03 15/11/07 page 26
EVAPORATOR WATER FLOW RATE
Check that the difference between the temperature of exchanger return and supply water corresponds to power according to this formula:
unit cooling power (kW) x 860 = Dt (°C) x flow rate (L/h).
The cooling power is shown in the TABLE ON GENERAL TECHNICAL DATA included in this manual, referred to specific air/water conditions, or in the tables on cooling PERFORMANCE IN THE TECHNICAL BULLETIN referred to various conditions of use.
Check for water side exchanger pressure drops:
Determine the water flow rate.
Measure the difference in pressure between
exchanger input and output and compare it with the graph on WATER SIDE EXCHANGER PRESSURE DROPS.
The measurement of pressure will be easier if pressure gauges are installed as indicated in the DIAGRAM OF SUGGESTED WATER CONNECTIONS .
CONDENSER WATER FLOW RATE
Check that the difference between the temperature of exchanger return and supply water corresponds to power according to this formula:
unit cooling power + power absorbed by compressors (kW) x 860 = Dt (°C) x flow rate (L/h).
The data is shown in the table on GENERAL TECHNICAL DATA included in this manual, referred to specific air/water conditions, or in the tables on COOLING PERFORMANCE
in the TECHNICAL BULLETIN referred to various conditions of use.
Check for water side exchanger pressure drops:
Determine the water flow rate.
Measure the difference in pressure between
exchanger input and output and compare it with the graph on WATER SIDE EXCHANGER PRESSURE
DROPS. The measurement of pressure will be easier if pressure gauges are installed as indicated in the DIAGRAM OF SUGGESTED WATER CONNECTIONS.
REFRIGERANT CIRCUIT PARAMETER CHECK
Detecting the operational conditions is useful to control the unit along time: the performed records must be kept and be available during maintenance interventions.
When the unit works in stable conditions and according to the operating limits, take note of the following data:
1. compressor diacharge temperature (WARNING – BURN DANGERI)
2. condensing pressure
3. liquid temperature
4. dehydrator filter upstream and downstream temperature
5. return pressure
6. return temperature
7. exchanger input water temperature
8. exchanger output water temperature
M03I40M7-03 15/11/07 page 27
CONTROL
CONTROL INTERFACE
COOL cooling HEAT heating
unit status (ON – ECO – OFF )
Enabled timing bands
INLET temperature
alarm
; OK
OUTLET temperature
inserted steps on total ALARM menu access
Current set point
HEAT / COOL changement
SET POINT, TIMING BANDS, CLOCK access
off = unit OFF
on = unit ON
Stata MENU access
ON / OFF unit
HELP parameter descriptions
Back to previous shield
Back to main menu
UNIT START-UP
To turn the unit on or off, hold the ON/OFF switch down for a few seconds. When the unit is on, the “ON” message is displayed; when the unit is off, the “OFF” message is displayed.
It is also possible to access the different menus when the unit is in the “OFF” mode.
It is possible to check the ON/OFF condition at a distance, using a remote device (see the ELECTRICAL CONNECTIONS chapter).
CHARACTERISTICS
THERMOREGULATION
The thermal regulation is based on the INLET temperature. The unit is set for a specific TOTAL DIFFERENCE between the inlet and outlet water temperatures. Usually the designed difference is 5°C, in the event that a different value is foreseen, the 17 and 18 parameters must be set again by the assistance center. According to the total difference, the system defines the level of difference that each compressor can give : the STEP DIFFERENCE. The regulations tend to gradually insert the compressors when the inlet temperature is over the set-point + the step difference. The compressors are activated one per time at the end of the SCANNING TIME. This time varies according to the gap between the water inlet temperature and the Set-point value. The higher the gap value is (both negative and positive), the shorter the interval among the scanning points will be. The value of the scanning time is displayed at the status 6; when the status 7 has reached the value of the status 6, the request of operation of the compressor is activated. The counting of the scanning time starts together with the activation of the compressor. The compressor to be activated is chosen to make the shut circuits operate in order to minimize the wear of the entire refrigerating circuit, as well as the single compressor. At the end of the counting, if the inlet temperature is higher than the step difference, another compressor is inserted. temp. H2O > set-point + step difference. What above described is referred to the COOLING operating, in HEATING the logici s the same but overturned (compressor insertion for outlet temp. < set-point – step jump).
SET-POINT COMPENSATIONS
The compensations are evolved functions that aim at protecting the compressors and fit as much as possible, the operation of the unit to the characteristics of the system and its use. The compensations make the time of the compressors’ operation longer and limit the number of starts-up, to make them delay the insertion time by adding an offset.
The compensation on the DURATION is useful when the water contained in the system is limited.
The compensation on the CHARGE is useful when a variable charge is present.
Optional components are necessary; the modifications of the parameters performed by the assistance centers have to be performed to enable and configure. In industrial applications, where a precise control of the temperature is necessary, it is possible to deactivate the COMPENSATIONS. The Status menu displays the value of the compensations on ext. temp. (status
9) and WR (status 10).
M03I40M7-03 15/11/07 page 28
SET-POINT CORRECTIONS
The correction aim at optimising the energetic efficiency of the unit. To do this, the corrections dynamically modify the set-point according to some variables. For example, in the summertime with very low external temperatures, therefore with a reduced load, it is possible to obtain the internal comfort even with set-points higher that the standard with a consequent higher energetic efficiency. The static set-point can therefore be modified dynamically with two CORRECTIONS based on two factors external to the unit:
Correction based on the External temp. / enthalpy
Correction based on the Water reset (4-20 mA signal supplied by the Customer)
The correct set-point, to which all corrections have been added or detracted, is called PRESENT set-point and is visible at status 2. For further details, see the ELECTRICAL CONNECTIONS chapter.
MAINTENANCE SET POINT
It can be used to maintain the installation inside the working limits, even if the unit is deactivated. The MAINTENANCE Set Point checks the water temperature when the unit is put on OFF or Stand-by. To do this, it periodically activates the circulation pump, tests the water temperature and even activates one or more compressors. It is necessary to modify the parameters with access reserved to the assistance centres
MENU NUM Parameter name meaning
25 MantCoolEn It enables Summer Maintenance PARAMETER CONTROL MAINTENANCE
114 SetMantCool Summer maintenance set-point
DEMAND LIMIT
The function of the DEMAND LIMIT allows the limit of power so that the electric consumptions can be controlled by a signal external to the unit supplied by the customer. On the STATUS menu, no. 22, the external signal of DEMAND LIMIT is displayed. For further information,see the ELECTRICAL CONNECTIONS chapter.
SECOND SET-POINT
The secondary set point is activated by remote authorization (see the ELECTRICAL CONNECTIONS chapter). It is possible to limit the minimum power which can be delivered during the time in which the secondary set point is activated by configuring the 276 MinPot2Set parameter (access reserved to the assistance centres).
TIME TABLES
The system is factory equipped with a clock function, found on the board. By activating the timetables, it is possible to set up to 6 events for each day of the week. If there is also a remote keyboard, the operations relative to the time and the date must be repeated on both keyboards, so that the two clocks (which are different) are synchronized.
M03I40M7-03 15/11/07 page 29
ACCESSIBLE PARAMETERS
PARAMETER MENU STRUCTURE
PARAMETERS
Set
LIST
Thermoreg.
Antifreeze
LIST
Maintenance
LIST
Set - point
LIST
SCHEDULING
Enscheduling
LIST
Configure
LIST
CLOCK SETUP
Clock
LIST
Data
LIST
menu: PARAMETERS – THERMOREG. – SET POINT
DEFAULT values
90 / CEN SecondSetC Secondary cooling Set Point 12
91 / CEN SecondSetH NOT USED - Secondary heating Set Point 35
118 / CEN SetCool Cooling Set Point 6.5
119 / CEN SetHeat NOT USED - Heating Set Point 45
272 / CEN SetRecovery NOT USED 35
menu: PARAMETERS – THERMOREG. – MAINTENANCE
114 / CEN SetMantCool Summer maintenance setpoint 15
117 / CEN SetMantHeat NOT USED - Winter maintenance setpoint 30
menu: PARAMETERS - THERMOREG.– ANTIFREEZE
115 / CEN AllFreeze Antifreeze alarm set 4
121 / CEN PreAF Antifreeze pre-alarm set 4.5
261 / CEN SetResist Antifreeze heater set 4
menu: PARAMETERS – SET – UNIT - EVAPORATORS
37 / EVAP SetResist Antifreeze heater set 4
39 / EVAP ALLFreeze Antifreeze alarm set 4
41 / EVAP PreAF Antifreeze pre-alarm set 4.5
M03I40M7-03 15/11/07 page 30
KEYPAD USE
To enter in the SETUP menu
?
ESC
I
HOME
button F3 SETUP
To select the submenu
?
ESC
I
HOME
buttons ▲▼ F2 – F3
To access
?
ESC
I
HOME
button F1 ENTER
To scrolling voices
?
ESC
I
HOME
buttons
▲▼ F2 - F3
To go back a level of the menu
?
ESC
I
HOME
button ESC
SET UP menu:
PARAMETERS
set point modification
SCHEDULING
enables/disables timing bands
CLOCK SETUP
Set the clock
ID Tast-Cen
(ATC ONLY)
PASSWORD
(ATC ONLY)
To go back to the main menu
?
ESC
I
HOME
button HOME
To enter in the SETUP menu
?
ESC
I
HOME
button F3 SETUP
To select the submenu
?
ESC
I
HOME
buttons ▲▼ F2 – F3
To access
?
ESC
I
HOME
button F1 ENTER
To access the desired parameter
?
ESC
I
HOME
buttons ▲▼ F1 – F2
To modify the parameter value
?
ESC
I
HOME
buttons
+ - F3 – F4
SETUP – PARAMETERS:
THERMOREG.
Set the setpoint and the operating modes
SET
(ATC ONLY)
To go back to the main menu
?
ESC
I
HOME
button HOME
M03I40M7-03 15/11/07 page 31
To enter in the SETUP menu
?
ESC
I
HOME
button F3 SETUP
To select the CONFIGURE submenu
?
ESC
I
HOME
buttons ▲▼ F2 – F3
To access
?
ESC
I
HOME
button F1 ENTER
To select DAY
?
ESC
I
HOME
buttons ▲▼ F1 – F2
To change week day
?
ESC
I
HOME
button F3
To select one of the 6 available daily events
?
ESC
I
HOME
button F4
To select TIME
?
ESC
I
HOME
buttons ▲▼ F1 – F2
To set the event hour and minutes
?
ESC
I
HOME
buttons
+ + F3 – F4
To select STATE
?
ESC
I
HOME
buttons ▲▼ F1 – F2
Select ON/OFF/ECO mode
?
ESC
I
HOME
button F4
To select Setpoint
?
ESC
I
HOME
buttons ▲▼ F1 – F2
Set the manual setpoint of the event
?
ESC
I
HOME
buttons
+ - F3 – F4
SETUP – SCHEDULING:
EnSCHEDULING
enables/disables timing bands
CONFIGURE
Set the timing bands
To go back to the main menu
?
ESC
I
HOME
button HOME
To enter in the SETUP menu
?
ESC
I
HOME
button F3 SETUP
To select the CLOCK SETUP submenu
?
ESC
I
HOME
buttons ▲▼ F2 – F3
To access to CLOCK
?
ESC
I
HOME
button F1 ENTER
To set HOURS MINUTES SECONDS
?
ESC
I
HOME
buttons F2 F3 F4
To confirm the single setting
?
ESC
I
HOME
button F1 ENTER
SETUP – CLOCK SETUP
CLOCK
Set the clock
DATA
Set the dater
To go back to the main menu
?
ESC
I
HOME
button HOME
M03I40M7-03 15/11/07 page 32
UNIT STATUS
A sub-menu is associated with each electronic module of the unit. It displays the system status. According to the unit configuration, and then with electronic modules and options, some sub-menus and statuses can not be used.
STATA STRUCTURE
Generals
LIST
Unit_1
Mod_comp1
LIST
Mod_comp2
LIST
Mod_comp3
LIST
Mod_Evap
LIST
Unit_2
Mod_comp1
LIST
Mod_comp2
LIST
Mod_comp3
LIST
Mod_Evap
LIST
example
Visualized stata referring to
UNIT 1
COMP 2 MODULE
To enter in the STATA menu
?
ESC
I
HOME
button F4 STATE
To select the module
?
ESC
I
HOME
buttons ▲▼ F2 – F3
To access
?
ESC
I
HOME
button F1 ENTER
To scroll the stata
?
ESC
I
HOME
buttons ▲▼ F2 - F3
To go back a level of the menu
?
ESC
I
HOME
button ESC
submenu:
GENERALS UNIT 1
mod_comp1
mod_comp2
mod_comp3
mod_evap
UNIT 2
mod_comp1
mod_comp2
mod_comp3
mod_evap
To go back to the main menu
?
ESC
I
HOME
button HOME
M03I40M7-03 15/11/07 page 33
Index GENERAL stata UM
0
Machine status
1=ON / 0=OFF
1 Machine mode 0=Cool, 1= Heat 2 Actual set point °C ( tenths ) 3 Inlet temperature °C (tenths) 4 Outlet temperature °C (tenths) 5 Number of steps activated 6 Current step value (compensations) °C (tenths) 7 Step activation timer sec 8 Step activation dynamic TimeScan sec
9 CompExt °C (tenths) 10 CompWR °C (tenths) 11 CompCar °C (tenths) 12 CompSpunti °C (tenths) 13 CompDuty °C (tenths) 14 Ambient temperature °C (tenths) 15 Ambient humidity % 16 Free Cooling valve percentage % 17 Free Cooling flow percentage % 18 Free Cooling valve control 1=ON / 0=OFF 19 Pump 1 status 1=ON / 0=OFF 20 Pump 2 status 1=ON / 0=OFF 21 Water Reset % 22 Demand Limit % 60 Digital input bit map of a byte 68 Water flow analogic out 69 Pump module digital out bit map of a byte 71 BitMap connected nodes MS bit map of a byte 72 Hours pump 1 PMP 73 Hours pump 2 PMP 74 Hours pump 3 PMP
Index UNIT_1 – MOD COMP_1 Stata UM
29 Compressor 1 1=ON / 0=OFF 30 Compressor 2 1=ON / 0=OFF 31 Compressor 3 1=ON / 0=OFF 32 Cp 1 timer status 1=ON / 0=OFF 33 Cp 2 timer status 1=ON / 0=OFF 34 Cp 3 timer status 1=ON / 0=OFF 35 Valve 1 c1 status 1=ON / 0=OFF 36 Valve 2 c1 status 1=ON / 0=OFF 37 Valve 3 c1 status 1=ON / 0=OFF 38 Valve 1 c2 status 1=ON / 0=OFF 39 Valve 2 c2 status 1=ON / 0=OFF 40 Valve 3 c2 status 1=ON / 0=OFF 41 Valve 1 c3 status 1=ON / 0=OFF
Index UNIT_1 – MOD COMP_1 Stata UM
42 Valve 2 c3 status 1=ON / 0=OFF 43 Valve 3 c3 status 1=ON / 0=OFF 44 Liquid solenoid 1=ON / 0=OFF 45 Coil temperature °C ( tenths) 46 Recovery temperature °C ( tenths) 47 Condensation pressure bar 48 Evaporation pressure bar 49 Fan Status bar 50 Defrost Status 1=ON / 0=OFF 51 Defrost count time sec 52 Compressor 1 operating time 53 Comp. 1 starts 54 Compressor 2 operating time 55 Comp. 2 starts
M03I40M7-03 15/11/07 page 34
Index UNIT_1 – MOD COMP_1 Stata UM
56 Compressor 3 operating time 57 Comp. 3 starts 58 Recovery valve 1=ON / 0=OFF 59 Recovery PREHP delay sec 61 Digital input bit map of a byte 75 Daikin calculated power % 76 PEvapOp bar 77 Taspirazione °C(tenths) 78 Tscarico °C(tenths) 79 Valve opening % 80 SuperHeat °C(tenths) 81 SuperHeatSPOperativo °C(tenths) 82 TempSaturaCondensazione °C(tenths)
Index UNIT_1 – MODEVAP_1 Stata UM
23 Tout1 °C (tenths) 24 Tout2 °C (tenths) 25 Tinput °C (tenths) 26 Pump 1 status 1=ON / 0=OFF 27 Pump 2 status 1=ON / 0=OFF 28 Heater status 1=ON / 0=OFF 62 Digital input bit map of a byte
ALARMS
BEFORE RESETTING THE ALARM, IDENTIFY AND ELIMINATE THE CAUSE OF ITS ACTIVATION.
REPEATED RESETS CAN CAUSE IRREVERSIBLE DAMAGES.
The presence of an alarm is signaled by the icon flashing
. The cumulative block relay activates simultaneously, according to the type of alarm. Alarms can be reset once the conditions that caused them to trip have been removed. ALARMS and faults show a potentially dangerous situation for the machine integrity. An immediate analysis is necessary to detect the causes of the block. A repeated reset can provoke irreversible damage. That is why reset is MANUAL.
PRE-ALARMS AND SIGNALIZATIONS show a situation similar to that one described above. The occurrence of an alarm is acceptable if it is occasional and/or in transitory situations (for example, when the plant starts). In uncertain cases, please contact the authorized assistance center.
To enter in the ALARM menu
?
ESC
I
HOME
button F2 ALARM
To select VIEW ALARM
?
ESC
I
HOME
buttons ▲▼ F2 –
F3
To access
?
ESC
I
HOME
button F1 ENTER
To scroll the active alarms
?
ESC
I
HOME
buttons ▲▼ F2 -
F3
To reset the alarm in progress
?
ESC
I
HOME
button F1 ENTER
To go back a level of the menu
?
ESC
I
HOME
button ESC
VIEW ALARM
To visualize the alarm in progress
STORE ALARM
To visualize the historical alarm
DEL STORE
To delete the historical alarm
To go back to the main menu
?
ESC
I
HOME
button HOME
An alarm list is associated with the inputs of each electronic module of the unit. According to the unit configuration, and then with electronic modules and options, some lists and/or ALARMS can not be used.
M03I40M7-03 15/11/07 page 35
ALARM STRUCTURE
CENTRAL
Unit_1
Mod_comp1
Mod_comp2
Mod_comp3
Mod_Evap
Unit_2
Mod_comp1
Mod_comp2
Mod_comp3
Mod_Evap
PUPMS – PMP
RECOVERY – REC1
example
CEN : central module alarm
14 : alarm identificative string
E014 : alarm description
CENTRAL MODULE
Str Name
0 E001 H2O IN temp. probe fault on control module 1 E002 H2O OUT temp. probe fault on control module 2 E003 Outside air temp. probe fault 3 E004 Water Reset input fault 4 E005 Outside RH% probe fault 5 E006 Thermal cut-out alarm pump 1 on control module 6 E007 Thermal cut-out alarm pump 2 on control module 7 E008 Flow switch alarm on control module 8 E009 System pressure alarm
9 E010 Phase monitor alarm 10 E011 Antifreeze alarm on control module 11 E012 Antifreeze pre-alarm on control module 12 E013 Change CENTRAL pump 13 E014 Unit configuration alarm 14 E015 Demand Limit input fault 15 E016 Can net disconnectedness on control module 59 E017 Inhibits control in heating 60 E018 Incongruent deltaT alarm 62 E019 Ext low temperature alarm
M03I40M7-03 15/11/07 page 36
COMPRESSOR MODULE
Str Name
16 E101 Cond./ Evap. temp. probe fault 17 E102 Condensing pressure probe fault 18 E103 Evaporation pressure probe fault 19 E104 Recovery temp. probe fault 20 E105 High pressure alarm 21 E106 Low pressure alarm 22 E107 Fan/Pump thermal cut-out alarm 23 E111 Cond. / Evap. H2O flow alarm 24 E112 High pressure pre-alarm 1 25 E113 High pressure pre-alarm 2 26 E114 Low pressure pre-alarm 27 E115 Force defrost alarm 28 E116 Max Press. diff. alarm 29 E117 Recovery H2O flow alarm 30 E118 Heat recovery HP pre-alarm 31 E108 Compressor 1 thermal cut-out alarm 32 E109 Compressor 2 thermal cut-out alarm 33 E110 Compressor 3 thermal cut-out alarm 47 E213 Module not connected 49 E119 Oil differential pressure alarm 58 E120 Condenser frost alarm 61 E121 BP2 prealarm 63 E123 TA TEE alarm 64 E124 TS TEE alarm 65 E125 max TS TEE prealarm 66 E126 max TS TEE prealarm 67 E127 power fail alarm 68 E128 stepper motor error alarm
PUMP MODULE
Str Name
53 E501 Water flow probe fault 54 E502 Thermal pump 1alarm Pump Module 55 E503 Thermal pump 2alarm Pump Module 56 E504 Thermal pump 3alarm Pump Module 57 E505 Max flow-rate signal Pump Module
RECOVERY EXPANSION MODULE
Str Name
50 E301 Out recovery probe alarm 51 E302 Gas temperature probe alarm
EVAPORATOR MODULE
Str Name
34 E201 Evaporator inlet probe fault 35 E202 Evaporator outlet probe 1 fault 36 E202 Evaporator outlet probe 2 probe fault 37 E203 Programmable evaporator input alarm 38 E204 Thermal cut-out alarm, evaporator pump 1 39 E205 Thermal cut-out alarm, evaporator pump 2 40 E206 Evaporator flow switch alarm 41 E207 Evaporator system fill alarm 42 E208 Change pumps on evaporator 43 E209 Antifreeze alarm on evaporator 44 E210 Tout 1, antifreeze pre-alarm on evaporator 45 E211 Tout 2, antifreeze pre-alarm on evaporator 46 E212 System pump lockout 48 E214 Module not connected
M03I40M7-03 15/11/07 page 37
ROUTINE MAINTENANCE
BEFORE UNDERTAKING ANY SORT OF MAINTENANCE OR CLEANING, DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE UNIT, AND ENSURE THAT OTHER PEOPLE CANNOT RE-CONNECT IT .
All equipment is subjected to wear out.
The maintenance makes :
1. keeps the unit efficiency
2. the components last longer
3. keeps their efficiency and limits breakdowns Therefore, it is fundamental to perform periodical checks: a few controls can be performed by the user (AUTONOMOUS MAINTENANCE) and they are mainly
cleaning activities; otherwise, controls have to be performed by specialized technicians (INSPECTIONS).
The machine should have a log book used to keep track of the performed controls. This will make fixing up breakdowns easier.
Take note of the date, type of control (autonomous maintenance, inspection or fixing up), description of the control, actions taken and so on.
SERVICES
Parts subject to intervention:
WATER EXCHANGER STRUCTURE
WATER EXCHANGER
It is very important for the exchanger to be able to provide the maximum thermal exchange. Therefore, it is essential for the inner surfaces to be clean of dirt and incrustations.
Periodically check the difference between the temperature of the supply water and the condensation temperature. If the difference is greater than 8°C–10°C it is advisable to clean the exchanger.
STRUCTURE
Check the condition of the parts making up the structure. Paint so as to eliminate or reduce oxidation at the points in the unit where this problem may occur. Check that the
panelling is fastened correctly. Poor fastening may give rise to malfunctions and abnormal noise and vibration.
M03I40M7-03 15/11/07 page 38
MAINTENANCE INSPECTIONS
Foresee inspection assistance carried out by authorized centers or by qualified personnel. The inspections should be carried out at least:
- Every year for only the cooling units
- Every six months for the cooling and warming
units The frequency, however, depends on the use: in the event of frequent use (continuous or very intermittent use, near the operating limits, etc) or critical use (service necessary) it is recommended to plan inspections at close intervals. The inspections to be performed are as follows:
verify the power supply tension (when emptied or filled)
inspect the electrical board (status of solenoid starter
contacts, terminal closings, the status of wiring and relevant insulations)
inspect the absorption of the single electrical loads
verify the cleaning and the efficiency of the exchangers
inspect the cleaning of the filters (air/water)
verify the leakage from the refrigerating circuit
Verify the protection devices (safety valves, pressure
switches, thermostats, etc.), the adjustment systems, the control devices (alarm signalizations, probes, manometers, etc)
check the operating parameters of the refrigerating circuit (see the following REFRIGERANT TABLES and the START-UP section)
For units equipped with safety valves, follow the Manufacturer’s instructions. Verify periodically the cleaning of the safety valves and that oxidative / corrosive phenomena are not present, in particular for installations near the sea, in industrial areas or in rooms with a corrosive atmosphere.
97/23 CE PED DIRECTIVE
97/23 CE PED DIRECTIVE gives instructions for installers, users and maintenance technicians as well. Refer to local actuation norms. In Italy, refer to the Ministerial Decree of 1
st
December 2004 no. 329 (and following modifications) which defines the performances to be executed; the units of
1
st
category and those defined by the art. 3.3 97/23/EC are not included in this regulation (see the serial number plate on the unit) .
Briefly and as an example, see the following :
1. COMPULSORY VERIFICATION OF THE FIRST INSTALLATION only for units assembled on the installer’s building site (for ex. Condensing circuit + direct expansion unit)
2. CERTIFICATION OF SETTING IN SERVICE for all the units
3. PERIODICAL VERIFICATIONS to be executed with the frequency indicated by the Manufacturer (see the MAINTENANCE INSPECTIONS paragraph)
PUT AT REST
If a long period of inactivity is foreseen, for example the winter for the cooling unit, the following is recommended:
to turn the power off in order to avoid electrical risks or damages by lightning strike
to avoid the risk of frosts as shown in the HYDRAULIC CONNECTIONS section, and, in particular
- to empty or add glycole in the plant sections subjected to temperatures below zero
- to empty or add glycole in the water heating coils, also in summer
- to power antifreeze resistances if present
If the period of inactivity is particularly long or in the event of extremely low temperatures, the external fans can be blocked temporarily; therefore, it is recommended to switch them on every month in order to avoid seizures or electrical overloads when the unit will be switched on.
The restarting of the unit has to be carried out by qualified personnel, in particular, after the winter break for cooling units or when seasonal switching should be performed.
When restarting, refer to the SWITCHING ON section.
Schedule technical assistance in advance to avoid hitches and be able to use the installation when necessary.
M03I40M7-03 15/11/07 page 39
REFRIGERANT TABLES
THIS SECTION IS DEVOTED ONLY TO QUALIFIED TECHNICIANS THAT KNOW THE FOLLOWING:
THE OPERATIONAL PRINCIPLES OF THE REFRIGERATING CIRCUIT OPERATION
THE MODES OF DETECTING TEMPERATURE AND PRESSURE
THE RISKS RELEVANT TO THESE OPERATIONS
The data of the tables allow the testing of the refrigerating circuit operation by the detection of a few objective parameters. The data are significant if they are detected simultaneously and while the refrigerating circuit is running.
Liquid temperature
Return pressure
Return temperature
Condensing pressure
OVERHEATING = return temperature – Saturation temperature
R22 R407C R410A
Return pressure 3.8 bar 3.8 bar 7.2 bar
Return temperature 7.3 °C 7.3 °C 7.3 °C
overheating
7.3 – ( - 1.13 ) =
8.43 °C
1.3 – 1.18 =
6.12 °C
for calculation consider the Td
(dew point)
7.3 – 0.8 = 6.5 °C
SUBCOOLING = condensing temperature (pressure *) – liquid temperature
R22 R407C R410A
Condensing pressure 18.6 bar 18.6 bar 29.6 bar
Liquid temp. 42.9 °C 42.9 °C 45 °C
subcooling
50.39 – 42.9 =
7.49 °C
44.74 – 42.9 =
1.84 °C
for calculation consider the Tb
(bubble point)
49.91 – 45 = 4.91 °C
* It is important that the condensation pressure is detected as close as possible to the point where the liquid temperature is detected, in the event that the calculation will be effected by the losses of charge (and, therefore, of temperature) caused by the refrigerating circuit components placed between the two measurement points.
For R410A the glide was not considered, since it is close to 0.
The values in the tables refer to a specific refrigerant supplier; slight differences are possible with other suppliers.
Pg = P gauge = relevant pressure (read on the pressure gauge)
Ts : saturation pressure
Td = dew point temperature
Tb = bubble point temperature
M03I40M7-03 15/11/07 page 40
Pg R134a Pg R134a Pg R134a Pg R134a
Ts [°C] Ts [°C] Ts [°C] Ts [°C]
0.0 -26.36 11.0 46.32 22.0 73.74 33.0 92.30
0.2 -22.31 11.2 46.96 22.2 74.14 33.2 92.59
0.4 -18.76 11.4 47.59 22.4 74.53 33.4 92.88
0.6 -15.59 11.6 48.22 22.6 74.92 33.6 93.16
0.8 -12.71 11.8 48.84 22.8 75.31 33.8 93.45
1.0 -10.08 12.0 49.46 23.0 75.69 34.0 93.73
1.2 -7.64 12.2 50.06 23.2 76.07 34.2 94.01
1.4 -5.37 12.4 50.66 23.4 76.45 34.4 94.29
1.6 -3.24 12.6 51.26 23.6 76.83 34.6 94.57
1.8 -1.23 12.8 51.84 23.8 77.21 34.8 94.85
2.0 0.67 13.0 52.42 24.0 77.58 35.0 95.12
2.2 2.48 13.2 53.00 24.2 77.95 35.2 95.40
2.4 4.20 13.4 53.56 24.4 78.32 35.4 95.67
2.6 5.84 13.6 54.13 24.6 78.68 35.6 95.94
2.8 7.42 13.8 54.68 24.8 79.04 35.8 96.21
3.0 8.93 14.0 55.23 25.0 79.41 36.0 96.48
3.2 10.39 14.2 55.78 25.2 79.76 36.2 96.75
3.4 11.79 14.4 56.32 25.4 80.12 36.4 97.01
3.6 13.15 14.6 56.85 25.6 80.48 36.6 97.28
3.8 14.46 14.8 57.38 25.8 80.83 36.8 97.54
4.0 15.74 15.0 57.91 26.0 81.18 37.0 97.80
4.2 16.97 15.2 58.43 26.2 81.53 37.2 98.06
4.4 18.17 15.4 58.94 26.4 81.87 37.4 98.32
4.6 19.33 15.6 59.45 26.6 82.22 37.6 98.58
4.8 20.47 15.8 59.96 26.8 82.56 37.8 98.84
5.0 21.57 16.0 60.46 27.0 82.90 38.0 99.09
5.2 22.65 16.2 60.95 27.2 83.24 38.2 99.34
5.4 23.70 16.4 61.44 27.4 83.58 38.4 99.60
5.6 24.73 16.6 61.93 27.6 83.91 38.6 99.85
5.8 25.73 16.8 62.42 27.8 84.24 38.8 100.09
6.0 26.71 17.0 62.90 28.0 84.58 39.0 100.34
6.2 27.67 17.2 63.37 28.2 84.90 39.2 100.59
6.4 28.62 17.4 63.84 28.4 85.23 39.4 100.83
6.6 29.54 17.6 64.31 28.6 85.56 39.6 -
6.8 30.44 17.8 64.77 28.8 85.88 39.8 -
7.0 31.33 18.0 65.23 29.0 86.20 40.0 -
7.2 32.20 18.2 65.69 29.2 86.52 40.2 -
7.4 33.05 18.4 66.14 29.4 86.84 40.4 -
7.6 33.89 18.6 66.59 29.6 87.16 40.6 -
7.8 34.72 18.8 67.04 29.8 87.47 40.8 -
8.0 35.53 19.0 67.48 30.0 87.79 41.0 -
8.2 36.32 19.2 67.92 30.2 88.10 41.2 -
8.4 37.11 19.4 68.36 30.4 88.41 41.4 -
8.6 37.88 19.6 68.79 30.6 88.72 41.6 -
8.8 38.64 19.8 69.22 30.8 89.03 41.8 -
9.0 39.39 20.0 69.64 31.0 89.33 42.0 -
9.2 40.13 20.2 70.07 31.2 89.64 42.2 -
9.4 40.85 20.4 70.49 31.4 89.94 42.4 -
9.6 41.57 20.6 70.90 31.6 90.24 42.6 -
9.8 42.27 20.8 71.32 31.8 90.54 42.8 -
10.0 42.97 21.0 71.73 32.0 90.83 43.0 -
10.2 43.66 21.2 72.14 32.2 91.13 43.2 -
10.4 44.33 21.4 72.54 32.4 91.43 43.4 -
10.6 45.00 21.6 72.95 32.6 91.72 43.6 -
10.8 45.66
21.8 73.35
32.8 92.01
43.8 -
M03I40M7-03 15/11/07 page 41
TROUBLESHOOTING
THE OPERATIONS MUST BE CARRIED OUT BY TECHNICAL QUALIFIED PERSONNEL HAVING THE REQUISITES UNDER LAW REQUISITES AND IN CONFORMITY WITH THE SAFETY REGULATIONS IN FORCE.
THE INTERVENTIONS WITHIN THE WARRANTY PERIOD WILL BE CARRIED OUT BY AUTHORIZED SERVICE CENTERS.
BEFORE RESETTING AN ALARM, IDENTIFY AND ELIMINATE ITS CAUSE. REPEATED RESETS MAY CAUSE SERIOUS DAMAGES.
In certain machine configurations, some safeties may be placed in series and lead back to a single input on the electronic module.
Therefore, check on the electrical diagram whether the device to which the alarm corresponds has other devices or safeties connected in series.
Below is a list of the possible causes of alarms.
HIGH PRESSURE (in cooling)
1. high water temperature (see operating limits)
2. insufficient water flow to the exchanger (high
thermal difference between input and output)
3. not CONSTANT flow (for example, if the pumps
are turned off, certain areas of the plant are excluded or included, other uses are isolated, etc )
4. Dirt water filter / valves open /air bubbles in the
plant
5. dirty exchanger
6. Manostat/transducer: loose electric
contacts/terminals, wiring cables interrupted
7. condensation gas in the cooling circuit
8. Too much refrigerant
9. Check the trigger point for the manostat and
transducer
10. Check the manostat or transducer pressure
control point (deposits of oil, dirt, pin blocked mechanically)
LOW PRESSURE (in cooling)
1. low water temperature (see operating limits)
2. insufficient water flow to the exchanger (high thermal difference between input and output)
3. not CONSTANT flow (for example, if the pumps are turned off, certain areas of the plant are excluded or included, other uses are isolated, etc )
4. Water filter clean / valves open /air bubbles in the plant
5. dirty exchanger
6. Manostat/transducer: loose electric contacts/terminals, wiring cables interrupted
7. refrigerant circuit empty, visible leaks of refrigerant/oil, insufficient charge
8. Blocked dehydrator filter
9. thermostatic device not operating correctly
10. Check the trigger point for the manostat and transducer
11. Check the manostat or transducer pressure control point (deposits of oil, dirt, pin blocked mechanically)
FAULTY PROBE
1. Identify the part on the wiring diagram.
2. Loose electric contacts/terminals, leads broken
3. Check the correct probe ohmic level (using a tester)
4. Change the probe.
5. Check the electronic module configuration (only an authorised service centre can do this)
6. Change the electronic module
FAULTY PRESSURE TRANSDUCER
1. Identify the part on the wiring diagram
2. Loose electric contacts/terminals, leads broken
3. Check the pressure test points are in working order
4. Change the part
5. Check the electronic module configuration (only an authorised service centre can do this)
6. Change the electronic module
COMPRESSOR PROTECTION
1. Identify the part on the wiring diagram
2. Loose electric contacts/terminals, leads broken
3. electrical windings interrupted
4. Vacuum power voltage below the limits
5. power contactors / contacts defective
6. start-up power voltage lower than the limits
7. electrical absorption high / unbalanced
8. High compressor discharge temperature > thermostatic device needs calibrating, insufficient refrigerant charge
M03I40M7-03 15/11/07 page 42
DECOMMISSIONING OF THE UNIT
DISCONNECTING THE UNIT
The units must be disconnected by authorised personnel, who before proceeding must first read the Residual Risks section in this manual.
Before disconnecting the unit, the following must be recovered, if present:
the refrigerant (if the circuits cannot be isolated): the refrigerant must be removed using suction devices operating in a closed circuit, so as to ensure that none of the compound is released into the atmosphere.
the antifreeze in the circuits: when removing this fluid, make sure that it does not leak and that it is not released into the environment. The antifreeze fluid must be stored in special containers.
When recovering the substances present in the unit, all measures must be taken to avoid damaging persons and things and polluting the surrounding area.
Awaiting dismantling and disposal, the unit can also be stored outdoors, as bad weather and rapid changes in temperature will not cause damage to the environment, if electric, cooling and hydraulic circuits of the unit are integral and closed.
DISMANTLING AND DISPOSAL
THE UNIT MUST ALWAYS BE SENT TO AUTHORISED CENTRES FOR DISMANTLING AND DISPOSAL.
When dismantling the unit, the fan, the motor and the coil, if operating, may be recovered by the specialist centres for reuse.
All the materials must be recovered or disposed of in compliance with the corresponding national standards in force.
For further information on the decommissioning of the unit, contact the manufacturer
.
M03I40M7-03 15/11/07 page 43
TECHNICAL DATA
Acoustic configuration: Standard (ST)/Extremely low noise(EN) / Energy efficiency: Efficiency class A
Size
2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
COOLING
Cooling capacity 1 kW 468 536 610 697 758 831 900 960 1011 1169 1209 1248 1448 1537 Compressor power input
kW 91.6 105 118 136 149 163 176 187 198 229 237 246 285 302
Total power input
kW 92.6 106 119 137 150 164 177 188 199 230 238 247 286 303 Heating capacity total recovery
2 kW 548 627 727 814 892 976 1056 1131 1197 1375 1424 1472 1720 1812
Heating capacity partial recovery
2 kW 83.9 96.1 109 125 136 149 161 172 181 210 217 224 260 276
EER
5.05 5.05 5.14 5.07 5.05 5.08 5.07 5.09 5.07 5.08 5.07 5.06 5.06 5.08
ESEER
5.75 5.75 5.85 5.77 5.75 5.78 5.78 5.8 5.77 5.78 5.77 5.76 5.76 5.78
HEATING
Heat output 3 kW 548 627 727 814 892 976 1056 1131 1197 1375 1424 1472 1720 1812 Compressor power input
kW 110 125 149 167 184 202 220 235 250 284 294 304 345 379 Total power input
kW 111 126 150 168 185 203 221 236 251 285 295 305 346 380 COP
4.92 4.97 4.86 4.85 4.82 4.81 4.78 4.79 4.77 4.83 4.83 4.83 4.97 4.77
COMPRESSOR
Type of compressors
4 SCREW
No. of Compressors
Nr 2
Rated power (C1)
HP 80 90 110 125 140 140 160 160 180 210 210 240 270 300
Nominal Power (C2)
HP 80 90 110 125 140 160 160 180 180 210 240 240 270 300
Std Capacity control steps
Nr STEPLESS
Oil charge (C1)
l 11 11 22 19 19 19 35 35 35 35 35 25 25 25
Oil charge (C2)
l 11 11 22 19 19 35 35 35 35 35 35 25 25 25
Refrigerant circuits
Nr 2
INTERNAL EXCHANGER
Type of internal exchanger
5 S&T
No. of internal exchangers
Nr 1
Water flow
l/s 22.3 25.6 29.1 33.3 36.2 39.7 43 45.9 48.3 55.9 57.7 59.6 69.2 73.4
internal exchanger pressure drop
kPa 40.9 41 43.9 65 49.6 34.4 39.7 79.6 87.3 51 54.1 57.4 105.3 117
Water content
l 277.7 233.3 248.3 233.3 418.6 409.6 409.6 409.6 409.6 451.4 451.4 451.4 493 493
EXTERNAL EXCHANGER
type of external exchanger
6 S&T
Water flow rate
l/s 26.7 30.6 34.8 39.8 43.3 47.5 51.4 54.8 57.8 66.8 69.1 71.4 82.8 87.8
external exchanger pressure drop
kPa 16.5 15.5 27.2 21.7 22.1 23.3 24.2 25.7 26.9 18.9 18.7 18.5 17.8 17.7
Water content
l 59 69 59 75 80 85 90 93 95 136 142 147 169 183
Quantity
Nr 2
CONNECTIONS
Water fittings 7 6" 6" 6" 6" 8" 8" 8" 8" 8" 8" 8" 8" 8" 8" Water fittings 7 5" 5" 5" 5" 5" 5" 5" 5" 5" 6" 6" 6" 6" 6"
POWER SUPPLY
Standard power supply
V 400/3/50
(1) data referred to the following conditions :
internal exchanger water = 12/7°C
external exchanger water = 30/35°C (2) recovery exchanger water=40/45°C (3) data referred to the following conditions :
external exchanger water = 40/45°C
internal exchanger water = 12/7°C
(4) DSW = twin-screw compressor (5) S&T = tube bundle (6) S&T = tube bundle (7) Fittings with flexible joint and solder pipe connection
OPERATING LIMITS (COOLING)
SIZE 2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
EXTERNAL EXCHANGER
Max water inlet temperature
1 °C 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Max water inlet temperature 2
°C 55 55 55 55 55 55 55 55 55 55 55 55 55 55
Max water inlet temperature 3
°C 62 62 62 62 62 62 62 62 62 62 62 62 62 62
Min. water outlet temperature
1 °C 27 27 27 27 27 27 27 27 27 27 27 27 27 27
INTERNAL EXCHANGER
Max water inlet temperature
°C 20,5 20,5 20,5 20,5 20,5 20,5 20,5 20,5 20,5 20,5 20,5 20,5 20,5 20,5
Min. water outlet temperature
4 °C 5 5 5 5 5 5 5 5 5 5 5 5 5 5
Min. water outlet temperature
5 °C -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8
(1) unit at full load: internal exchanger water 12/7°C (2) capacity-controlled unit (automatic capacity control) (3) unit not operating
(4) Standard Version (5) Low temperature version Fluid with ethylene glycol of 40%
M03I40M7-03 15/11/07 page 44
Acoustic configuration: Standard (ST)/Extremely low noise(EN) / Energy efficiency: Efficiency class B
Size 2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
COOLING
Cooling capacity 1 kW 408 455 562 620 698 773 828 903 952 993 1049 1171 1295 1458 Compressor power input
kW 86 96.5 118 130 147 162 177 187 196 208 223 246 271 308
Total power input
kW 87 97.5 119 131 148 163 178 188 197 209 224 247 272 309 Heating capacity total recovery
2 kW 473 528 649 718 809 894 962 1039 1095 1148 1217 1358 1503 1692
Heating capacity partial recovery
2 kW 74.2 82.7 102 112 127 140 151 163 172 180 191 212 235 265
EER
4.69 4.67 4.73 4.72 4.71 4.73 4.66 4.8 4.82 4.74 4.68 4.74 4.75 4.72
ESEER
5.28 5.26 5.33 5.32 5.3 5.33 5.25 5.41 5.43 5.34 5.27 5.34 5.35 5.32
HEATING
Heat output 3 kW 473 528 649 718 809 894 962 1039 1095 1148 1217 1358 1503 1692 Compressor power input
kW 107 119 146 161 184 201 218 231 243 258 275 303 337 381 Total power input
kW 108 120 147 162 185 202 219 232 244 259 276 304 338 382 COP
4.4 4.4 4.42 4.44 4.37 4.42 4.39 4.48 4.48 4.43 4.41 4.47 4.44 4.43
COMPRESSOR
Type of compressors 4 SCREW No. of Compressors Nr 2 Rated power (C1) HP 80 90 110 125 140 140 160 160 180 210 210 240 270 300 Nominal Power (C2) HP 80 90 110 125 140 160 160 180 180 210 240 240 270 300 Std Capacity control steps Nr STEPLESS Oil charge (C1) l 11 11 22 19 19 19 35 35 35 35 35 25 25 25 Oil charge (C2) l 11 11 22 19 19 35 35 35 35 35 35 25 25 25 Refrigerant circuits Nr 2
INTERNAL EXCHANGER
Type of internal exchanger 5 S&T No. of internal exchangers Nr 1 Water flow rate
l/s 19.5 21.7 26.8 29.6 33.3 36.9 39.6 43.1 45.5 47.4 50.1 55.9 61.9 69.7 internal exchanger pressure drop
kPa 61 56.2 51.4 61.1 75.2 66.9 58.9 39.9 43.8 78.6 52.2 66.3 79.3 70.9
Water content
l 164.4 159.3 263.3 263.3 263.3 248.3 241.2 409.6 409.6 418.6 409.6 400.9 400.9 461.8
EXTERNAL EXCHANGER
type of external exchanger 6 S&T Water flow rate
l/s 23.6 26.4 32.5 35.8 40.4 44.7 48 52.1 54.9 57.4 60.8 67.7 74.8 84.4 external exchanger pressure drop
kPa 31.7 29.7 34.5 33.4 34.8 33.4 30.5 33 34 36.9 36.3 35.9 34.9 30.9
Water content
l 38 43 49 54 59 67 75 75 75 80 85 95 101 131
Quantity
Nr 2
CONNECTIONS
Water fittings 7 5" 5" 6" 6" 6" 6" 6" 8" 8" 8" 8" 8" 8" 8" Water fittings 7 5" 5" 5" 5" 5" 5" 5" 5" 5" 5" 5" 5" 5" 6"
POWER SUPPLY
Standard power supply
V 400/3/50
(1) data referred to the following conditions : internal exchanger water = 12/7°C external exchanger water = 30/35°C (2) recovery exchanger water=40/45°C (3) data referred to the following conditions : external exchanger water = 40/45°C internal exchanger water = 12/7°C
(4) DSW = twin-screw compressor (5) S&T = tube bundle (6) S&T = tube bundle (7) Fittings with flexible joint and solder pipe connection
OPERATING LIMITS (COOLING)
Size 2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
EXTERNAL EXCHANGER
Max water inlet temperature
1 °C 51 51 51 51 51 51 51 51 51 51 51 51 51 51
Max water inlet temperature 2
°C 55 55 55 55 55 55 55 55 55 55 55 55 55 55
Max water inlet temperature 3
°C 62 62 62 62 62 62 62 62 62 62 62 62 62 62
Min. water outlet temperature
1 °C 26 26 26 26 26 26 26 26 26 26 26 26 26 26
INTERNAL EXCHANGER
Max water inlet temperature
°C 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5 20.5
Min. water outlet temperature
4 °C 5 5 5 5 5 5 5 5 5 5 5 5 5 5
Min. water outlet temperature
5 °C -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8
(1) unit at full load: internal exchanger water 12/7°C (2) capacity-controlled unit (automatic capacity control) (3) unit not operating
(4) Standard Version (5) Low temperature version Fluid with ethylene glycol of 40%
M03I40M7-03 15/11/07 page 45
CORRECTION FACTOR FOR ANTIFREEZE SOLUTIONS
Internal exchanger (evaporator)
% ethylene glycol by weight 5% 10% 15% 20% 25% 30% 35% 40%
Freezing temperature
°C -2.0 -3.9 -6.5 -8.9 -11.8 -15.6 -19.0 -23.4
Safety temperature
°C 3.0 1.0 -1.0 -4.0 -6.0 -10.0 -14.0 -19.0
Cooling Capacity Factor
Nr 0.995 0.990 0.985 0.981 0.977 0.974 0.971 0.968
Compressor input Factor
Nr 0.997 0.993 0.990 0.988 0.986 0.984 0.982 0.981
Internal exchanger Glycol solution flow Factor
Nr 1.003 1.010 1.020 1.033 1.050 1.072 1.095 1.124
Pressure drop Factor Nr 1.029 1.060 1.090 1.118 1.149 1.182 1.211 1.243
The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.
External exchanger (condenser)
% ethylene glycol by weight 5% 10% 15% 20% 25% 30% 35% 40%
Freezing temperature
°C -2.0 -3.9 -6.5 -8.9 -11.8 -15.6 -19.0 -23.4
Safety temperature *
°C -0.3 -0.6 -0.9 -1.3 -1.8 -2.2 -2.7 -3.3
Cooling Capacity Factor
Nr 1.00 0.99 0.99 0.98 0.97 0.97 0.96 0.95
Compressor input Factor
Nr 1.01 1.01 1.02 1.02 1.03 1.04 1.05 1.06
Internal exchanger Glycol solution flow Factor
Nr 1.01 1.02 1.04 1.05 1.07 1.09 1.11 1.13
Pressure drop Factor
Nr 1.02 1.05 1.08 1.12 1.16 1.21 1.26 1.32
The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.
* MAX. REDUCTION EXTERNAL EXCHANGER INLET WATER TEMPERATURE
FOULING CORRECTION FACTOR
INTERNAL EXCHANGER EXTERNAL EXCHANGER
m² °C/W F1 FK1 F2 FK2
0.44 x 10^(-4) 1.00 1.00 1.00 1.00
0.88 x 10^(-4) 0.97 0.99 0.97 1.08
1.76 x 10^(-4) 0.94 0.98 0.92 1.05
F1 = Cooling capacity correction factors FK1 = Compressor power input correction factor F2 = Cooling capacity correction factors FK2 = Compressors input power correction factors
EXCHANGER OPERATING LIMITS
INTERNAL EXCHANGER EXTERNAL EXCHANGER
DPr (S - B) DPw DPr DPw
kPa kPa kPa kPa
CLIVET (C) 2450 2450 1050 2145 1600 PED (CE) 2450 2450 1050 2145 1600
DPr = Maximum operating pressure on refrigerant side DPw = Maximum operating pressure on water side
OVERLOAD AND CONTROL DEVICE CALIBRATION
OPEN CLOSED VALUE High pressure switch
kPa 1730 1170 -
Low pressure switch
kPa 70.0 170 -
Antifreeze protection
°C 3.0 5.5 -
High pressure safety valve
kPa - - 2000
Low pressure safety valve
kPa - - 1650
Max no. of compressor starts per hour
Nr - - 6
High compressor discharge temperature safety thermostat
°C - - 120
M03I40M7-03 15/11/07 page 46
Acoustic configuration: Standard (ST)/Extremely low noise(EN) / Energy efficiency: Efficiency class A Internal exchanger (evaporator) pressure drop: ST(STANDARD)- EN
15 20 25 30 35 40 45 50 60 70 80 90 100
20
30
40
50
60
70
80
90
100
110
120
130
Q [l/s]
Δ
P [kPa]
2
.
1
6
0
2
.
1
8
0
-
2
.
2
5
0
2
.2
2
0
2
.
2
8
0
-
2
.
3
4
0
-
2
.
3
6
0
2
.
3
0
0
-
2
.
3
2
0
2
.
4
2
0
-
2
.
4
5
0
-
2
.
4
8
0
2
.
5
4
0
-
2
.6
0
0
Qmin
[l/s]
Qmax
[l/s]
2.160 14.9 37.0
2.180 17.0 42.6
2.220 18.7 46.3
2.250 17.0 42.6
2.280 21.3 54.6
2.300 29.4 71.9
2.320 29.4 71.9
2.340 21.2 52.1
2.360 21.2 52.1
2.420 37.8 93.5
2.450 37.8 93.5
2.480 37.8 93.5
2.540 30.7 77.9
2.600 30.7 77.9
External exchanger pressure drop (condenser): ST (STANDARD)- EN
Tower water application
5 10 15 20 25 30 35 40 45 50 80
15
20
25
30
35
40
45
50
60
70
80
90
100
Q [l/s]
Δ
P [kPa]
2
.
1
6
0
-
2
.
2
2
0
2
.
1
8
0
2
.
2
5
0
2
.
2
8
0
2
.
3
0
0
2
.
3
2
0
2
.
3
4
0
-
2
.
3
6
0
2
.
4
2
0
2
.
4
5
0
2
.
4
8
0
2
.
5
4
0
Qmin
[l/s]
Qmax
[l/s]
2.160 8.3 22.9
2.180 10.0 26.9
2.220 8.3 22.9
2.250 10.8 28.8 2 . 2 8 0 11.6 3 0 . 5
2.300 12.4 33.5
2.320 13.1 36.6
2.340 13.5 37.7
2.360 13.9 38.8
2.420 19.6 54.1
2.450 20.4 56.2
2.480 21.3 58.3
2.540 25.2 68.6
2.600 26.9 72.6
20 25 30 35 40 45 50 60 70 80 90 100 120 140 160
10
15
20
25
30
35
40
45
50
Q [l/s]
Δ
P [kPa]
2
.
1
6
0
-
2
.
2
2
0
2
.
1
8
0
2
.
2
5
0
2
.
2
8
0
2
.
3
0
0
2
.
3
2
0
2
.
3
4
0
-
2
.
3
6
0
2
.
4
2
0
2
.
4
5
0
-
2
.
4
8
0
2
.
5
4
0
2
.
6
0
0
Qmin
[l/s]
Qmax
[l/s]
2.160 20.6 45.2
2.180 24.3 53.9
2.220 20.6 45.2
2.250 26.5 58.2
2.280 28.5 63.1
2.300 30.2 67.7
2.320 31.9 72.1
2.340 32.7 74.4
2.360 33.6 76.7
2.420 47.1 107.4 2 . 4 5 0 4 8 . 9 112 . 0 2 . 4 8 0 5 0 . 7 116 . 7
2.540 59.6 140.2
2.600 63.4 149.6
Well water application
M03I40M7-03 15/11/07 page 47
Acoustic configuration: Standard (ST)/Extremely low noise(EN) / Energy efficiency: Efficiency class B Internal exchanger (evaporator) pressure drop: ST(STANDARD)- EN
10 20 25 30 35 40 45 50 60 70 80 90
20
30
40
50
60
70
80
90
100
Q [l/s]
Δ
P [kPa]
2
.
16
0
2.
1
8
0
2.
2
2
0
-
2
.
2
5
0
-
2
.
28
0
2.
3
0
0
2
.
32
0
-
2
.
4
2
0
2.
3
4
0
-
2
.
3
6
0
-
2
.
4
5
0
-
2
.
4
80
-
2.
5
4
0
2.
6
00
Qmin
[l/s]
Qmax
[l/s]
2.160 10.5 25.0
2.180 12.2 30.0
2.220 15.7 36.9
2.250 15.7 36.9
2.280 15.7 36.9
2.300 18.7 46.3
2.320 21.9 52.8
2.340 29.4 71.9
2.360 29.4 71.9
2.420 21.3 54.6
2.450 29.4 71.9
2.480 28.6 70.4
2.540 28.6 70.4
2.600 43.4 84.2
External exchanger pressure drop (condenser): ST (STANDARD)- EN
Tower water application
15 20 25 30 35 40 45 50 60 70 80 90 100 120
10
15
20
25
30
35
40
45
50
Q [l/s]
Δ
P [kPa]
2
.
1
6
0
2
.
1
8
0
2
.
2
2
0
2
.
2
5
0
2
.
2
8
0
2
.
3
0
0
2
.
3
2
0
-
2
.
3
4
0
-
2
.
3
6
0
-
2
.
4
2
0
2
.
4
5
0
2
.
4
8
0
2
.
5
4
0
2
.
6
0
0
5 10 15 20 25 30 35 40 45 50 60
15
20
25
30
35
40
45
50
60
70
80
90
100
Q [l/s]
Δ
P [kPa]
2
.
1
6
0
2
.
1
8
0
2
.
2
2
0
2
.
2
5
0
2
.
2
8
0
2
.
3
0
0
2
.
3
2
0
-
2
.
3
4
0
-
2
.
3
6
0
-
2
.
4
2
0
2
.
4
5
0
2
.
4
8
0
2
.
5
4
0
2
.
6
0
0
Qmin
[l/s]
Qmax
[l/s]
2.160 12.6 28.6
2.180 14.5 33.1
2.220 16.3 37.7
2.250 18.1 42.5
2.280 19.9 46.7
2.300 22.8 52.8
2.320 26.0 59.5
2.340 26.9 61.8
2.360 27.8 64.1
2.420 27.8 64.1
2.450 29.8 68.4
2.480 33.6 76.7
2.540 37.2 86.3
2.600 45.1 104.0
Qmin
[l/s]
Qmax
[l/s]
2 . 16 0 5 . 2 14 . 4 2 . 18 0 6 . 0 16 . 7
2.220 6.8 18.9
2.250 7.6 20.8
2.280 8.3 22.9
2.300 9.4 26.1
2.320 10.7 29.8
2.340 11.2 30.9
2.360 11.6 31.9
2.420 11.6 31.9
2.450 12.4 34.4
2.480 13.9 38.8
2.540 15.6 43.0
2.600 18.6 52.2
Well water application
M03I40M7-03 15/11/07 page 48
SOUND LEVELS
Acoustic configuration: Standard (ST) Energy efficiency: Efficiency class A
Acoustic configuration: Extremely low noise (EN) Energy efficiency: Efficiency class A
Sound Power Level (dB)
Sound
pressure
Sound
power
Sound Power Level (dB)
Sound
pressure
Sound
power
Octave band (Hz) level level Octave band (Hz) level level
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
2.160 93 84 90 96 97 87 79 73 81 99 2.160 91 85 86 88 87 83 78 71 72 91
2.180 94 85 90 97 98 88 79 74 81 100 2.180 92 86 87 89 87 83 79 72 73 91
2.220 75 61 86
101
99 84 63 45 83 102 2.220 73 62 83 93 88 79 62 42 74 92
2.250 85 65 87
97
101 87 64 46 83 102 2.250 83 66 84 89 90 82 63 43 74 92
2.280 90 67 98
100
101 86 61 42 84 103 2.280 89 68 95 92 91 81 61 40 75 94
2.300 88 80 97
99
101 86 69 50 84 103 2.300 87 81 93 91 91 81 68 47 74 94
2.320 85 84 95
98
102 87 72 53 84 90 2.320 83 85 92 91 91 82 72 51 74 94
2.340 83 82 97
99
101 87 71 53 83 102 2.340 81 83 94 91 90 82 71 51 74 93
2.360 80 80 99
100
100 88 71 54 83 102 2.360 78 81 96 92 90 83 70 52 75 94
2.420 84 83 95
98
101 86 72 53 83 103 2.420 83 84 92 90 91 82 71 51 74 93
2.450 84 83 95
98
101 86 72 52 83 102 2.450 82 84 91 90 90 81 71 50 73 93
2.480 84 83 95
98
101 86 72 53 83 103 2.480 83 84 92 90 91 82 71 51 74 93
2.540 95 83 88
104
98 95 85 76 84 103 2.540 93 83 84 96 87 90 84 74 77 96
2.600 95 83 88
104
98 95 85 76 84 104
2.600 93 84 84 96 88 90 84 74 77 96
Measures according to ISO 3744 regulations, with respect to the EUROVENT 8/1 certification. the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field. data referred to the following conditions : internal exchanger water = 12/7°C external exchanger water = 30/35°C
Acoustic configuration: Standard (ST) Energy efficiency: Efficiency class B
Acoustic configuration: Extremely low noise (EN) Energy efficiency: Efficiency class B
Sound Power Level (dB)
Sound
pressure
Sound
power
Sound Power Level (dB)
Sound
pressure
Sound
power
Octave band (Hz) level level Octave band (Hz) level level
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
2.160 93 84 90 96 97 87 79 73 81 99 2.160 91 85 86 88 87 82 78 71 72 91
2.180 93 85 90 96 98 88 79 74 81 100 2.180 92 86 87 89 87 83 79 72 73 91
2.220 94 85 91 97 99 88 80 75 82 100 2.220 92 86 87 89 88 84 79 72 73 92
2.250 94 85 91 97 99 89 80 75 82 100 2.250 93 86 87 89 88 84 79 72 73 92
2.280 95 86 92 98 99 89 81 75 83 101 2.280 93 87 88 90 89 84 80 73 74 93
2.300 95 85 90
101
99 92 83 75 83 102 2.300 93 86 87 93 88 87 82 73 75 94
2.320 94 81 87
103
97 94 84 75 83 88 2.320 92 82 83 95 86 89 83 73 76 95
2.340 94 81 86
103
97 94 83 75 83 102 2.340 92 82 83 95 86 89 83 73 76 95
2.360 94 81 86
102
97 94 83 75 83 102 2.360 92 82 83 95 86 89 83 73 76 95
2.420 93 81 86
102
96 93 83 75 83 102 2.420 92 82 83 95 86 89 83 73 76 95
2.450 93 81 86
102
96 93 83 75 83 102 2.450 92 82 83 95 86 89 83 73 76 95
2.480 94 82 87
103
97 94 84 76 84 103 2.480 93 83 83 95 87 89 83 73 76 95
2.540 95 82 88
104
98 95 85 76 84 103 2.540 93 83 84 96 87 90 84 74 77 96
2.600 95 83 88
104
98 95 85 76 84 104
2.600 93 84 84 96 88 90 84 74 77 96
Measures according to ISO 3744 regulations, with respect to the EUROVENT 8/1 certification. the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field. data referred to the following conditions : internal exchanger water = 12/7°C external exchanger water = 30/35°C
M03I40M7-03 15/11/07 page 49
DIMENSIONS
ACOUSTIC CONFIGURATION: STANDARD (ST) / ENERGY EFFICIENCY: EFFICIENCY CLASS A
1
1
2
3
45
6 OD1
7 OD1
10
OD
OD
11
1
10
3
3
C1
C2
15
15
14
13
11
G
8 8
2
9
9
8 8
15
10
11
W1
W2
W3
W4
12
12
16
16
700
1500
700
M N
Q
I
40 1245 40
280 650 395
1325
W
2200 B
D E
700
1000
1600
PO
A
C
L
H
ST-CLA
Size
2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
A mm 514 514 581 581 581 913 913 913 913 1006 1006 1006 1027 1027 B mm 820 820 820 820 948 948 1248 1248 1248 1451 1451 1451 1451 1451 C mm 408 408 475 475 501 833 833 833 833 652 652 652 522 522 D mm 2412 2412 2412 2412 2360 2360 2360 2360 2360 2910 2910 2910 3210 3210
E mm 714 714 714 714 868 868 1168 1168 1168 1095 1095 1095 946 946 H mm 1711 1711 2018 2018 2018 2018 2018 2018 2018 2146 2146 2146 2146 2146
I mm 781 781 781 781 819 819 819 819 819 883 883 883 883 883
L mm 3534 3534 3601 3601 3729 4061 4361 4361 4361 4657 4657 4657 4678 4678 M mm 1604 1602 1604 1673 1606 1865 2006 2007 2006 2120 2176 2119 2138 2139 N mm 1930 1932 1997 1928 2123 2196 2355 2354 2355 2537 2481 2538 2540 2539 O mm 625 643 696 636 634 631 627 627 628 614 613 613 625 625
P mm 700 682 629 717 719 722 726 726 725 739 740 740 728 728 Q mm 293 293 293 293 293 293 293 293 293 324 324 324 324 324 W mm 1398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425
OD mm 168.3 168.3 168.3 168.3 219.1 219.1 219.1 219.1 219.1 219.1 219.1 219.1 219.1 219.1
OD1 mm 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 169.3 169.3 169.3 169.3 169.3
Length mm 3534 3534 3601 3601 3729 4061 4361 4361 4361 4657 4657 4657 4678 4678
Depth mm 1398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425
Height mm 1711 1711 2018 2018 2018 2018 2018 2018 2018 2146 2146 2146 2146 2146
W1 kg 694 733 1008 898 1050 1239 1204 1207 1215 1350 1299 1381 1423 1430 W2 kg 681 717 876 885 916 945 1189 1194 1199 1385 1475 1415 1452 1461 W3 kg 783 781 905 978 1151 1371 1349 1353 1357 1578 1523 1620 1605 1613 W4 kg 769 764 787 964 1004 1046 1332 1339 1340 1619 1730 1659 1638 1648
Operating weight kg 2926 2995 3577 3726 4122 4602 5074 5093 5112 5931 6028 6075 6118 6152
Shipping weight kg 2610 2689 3269 3416 3623 4107 4574 4590 4606 5344 5436 5478 5153 5475
Particular accessories, executions or versions can bring about a great variation of the mass represented here. Please contact our Technical Department.
(1) COMPRESSOR (2) INTERNAL EXCHANGER
(EVAPORATOR)
(3) EXTERNAL EXCHANGER
(CONDENSER) (4) INTERNAL EXCHANGER WATER INLET (5) INTERNAL EXCHANGER WATER
OUTLET (4 & 5) FITTINGS WITH FLEXIBLE JOINT
AND SOLDER PIPE CONNECTION (6) EXTERNAL EXCHANGER WATER INLET (7) EXTERNAL EXCHANGER WATER
OUTLET (6 & 7) FITTINGS WITH FLEXIBLE JOINT
AND SOLDER PIPE CONNECTION (8) HOLE TO HANG UNIT (9) LIFTING HOLES (10) ELECTRICAL PANEL (11) POWER INPUT (12) LIFTING TUBE (13) MINIMUM DIMENSION ON THE
ELECTRICAL SWITCHBOARD SIDE. (14) MINIMUM DIMENSION FOR A SAFE
PASSAGE WHEN THE DOOR OF THE
ELECTRICAL SWITCHBOARD IS OPEN (15) MINIMUM DIMENSION FOR A SAFE
PASSAGE (16) MINIMUM DIMENSION FOR
MAINTENANCE
M03I40M7-03 15/11/07 page 50
ACOUSTIC CONFIGURATION: STANDARD (EN) / ENERGY EFFICIENCY: EFFICIENCY CLASS A
1
1
2
3
45
6 OD1
10
OD
OD
11
1
12
10
3
3
C1
C2
16
16
15
14
11
G
8 8
2
12
9
9
8 8
16
10
11
W1
W2
W3
W4
13
13
17
17
7 OD1
700
1500
700
M N
Q
I
40 1245 40
280 650 395
1325
W
H
A 2200 B
C D E
L
700
1000
1600
PO
EN-CLA
SIZE 2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
A mm 611 611 611 611 903 988 1098 1098 1098 1098 1098 1098 1098 1098 B mm 1020 1020 1020 1020 1148 1148 1448 1448 1448 1451 1451 1451 1451 1451 C mm 505 505 505 505 823 908 1018 1018 1018 743 743 743 594 594 D mm 2412 2412 2412 2412 2360 2360 2360 2360 2360 2910 2910 2910 3210 3210 E mm 914 914 914 914 1067 1068 1368 1368 1368 1093 1093 1093 942 942 H mm 1891 1891 1891 1891 2182 2182 2182 2182 2182 2245 2245 2245 2245 2245
I mm 781 781 781 781 819 819 819 819 819 883 883 883 883 883
L mm 3831 3831 3831 3831 4250 4336 4746 4746 4746 4746 4746 4746 4746 4746
M mm 1713 1706 1719 1710 1996 1946 2197 2197 2198 2215 2267 2215 2212 2213
N mm 2118 2125 2112 2121 2254 2390 2549 2549 2548 2531 2479 2531 2534 2533
O mm 615 625 625 633 632 626 623 623 623 611 610 610 621 621
P mm 710 700 700 720 721 727 730 730 730 742 743 743 732 732 Q mm 293 293 293 293 293 293 293 293 293 324 324 324 324 324 W mm 1398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425
OD mm 168.3 168.3 168.3 168.3 219.1 219.1 219.1 219.1 219.1 219.1 219.1 219.1 219.1 219.1
OD1 mm 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 169.3 169.3 169.3 169.3 169.3
Length mm 3831 3831 3831 3831 4250 4336 4746 4746 4746 4746 4746 4746 4746 4746
Depth mm 1398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 Height mm 1891 1891 1891 1891 2182 2182 2182 2182 2182 2245 2245 2245 2245 2245
W1 kg 750 784 910 966 1068 1307 1293 1298 1301 1438 1387 1467 1510 1516 W2 kg 753 777 923 964 1054 1008 1291 1295 1301 1487 1577 1518 1553 1562 W3 kg 874 885 1026 1062 1178 1470 1469 1474 1477 1697 1642 1738 1725 1733 W4 kg 877 877 1041 1060 1163 1134 1466 1471 1477 1755 1867 1797 1775 1786
Operating weight kg 3254 3323 3900 4053 4463 4919 5519 5538 5557 6376 6473 6520 6563 6597
Shipping weight kg 2938 3017 3592 3743 3964 4424 5019 5035 5051 5789 5881 5923 5598 5920
Particular accessories, executions or versions can bring about a great variation of the mass represented here. Please contact our Technical Department.
(1) COMPRESSOR (2) INTERNAL EXCHANGER
(EVAPORATOR)
(3) EXTERNAL EXCHANGER
(CONDENSER) (4) INTERNAL EXCHANGER WATER INLET (5) INTERNAL EXCHANGER WATER
OUTLET (4 & 5) FITTINGS WITH FLEXIBLE JOINT
AND SOLDER PIPE CONNECTION (6) EXTERNAL EXCHANGER WATER INLET (7) EXTERNAL EXCHANGER WATER
OUTLET (6 & 7) FITTINGS WITH FLEXIBLE JOINT
AND SOLDER PIPE CONNECTION (8) HOLE TO HANG UNIT (9) LIFTING HOLES (10) ELECTRICAL PANEL (11) POWER INPUT (12) SOUNDPROOFED CABIN (13) LIFTING TUBE (14) MINIMUM DIMENSION ON THE
ELECTRICAL SWITCHBOARD SIDE (15) MINIMUM DIMENSION FOR A SAFE
PASSAGE WHEN THE DOOR OF THE
ELECTRICAL SWITCHBOARD IS OPEN (16) MINIMUM DIMENSION FOR A SAFE
PASSAGE (17) MINIMUM DIMENSION FOR
MAINTENANCE
M03I40M7-03 15/11/07 page 51
ACOUSTIC CONFIGURATION: STANDARD (ST) / ENERGY EFFICIENCY: EFFICIENCY CLASS B
1
1
2
3
45
6 OD1
7 OD1
10
OD
OD
11
1
10
3
3
C1
C2
15
15
14
13
11
G
8 8
2
9
9
8 8
15
10
11
W1
W2
W3
W4
12
12
16
16
700
1500
700
M N
Q
I
40 1245 40
280 650 395
1325
W
2200 B
D E
700
1000
1600
PO
A
C
L
H
ST-CLB
SIZE 2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
A mm 515 515 514 514 514 794 705 705 705 705 705 1027 1027 1027 B mm 811 811 820 820 820 939 989 997 997 997 997 1451 1451 1451 C mm 390 390 408 408 408 688 599 624 624 624 624 672 672 672 D mm 2460 2460 2412 2412 2412 2412 2412 2360 2360 2360 2360 2910 2910 2910 E mm 676 676 714 714 714 833 883 918 918 918 918 1096 1096 1096 H mm 1640 1640 1871 1871 1871 1980 1980 2083 2083 2083 2083 2083 2083 2146
I mm 710 710 781 781 781 781 781 819 819 819 819 819 819 883
L mm 3526 3526 3534 3534 3534 3933 3894 3902 3902 3902 3902 4678 4678 4678
M mm 1606 1605 1605 1611 1606 1924 1879 1788 1788 1789 1788 2127 2127 2145
N mm 1920 1921 1929 1923 1928 2009 2015 2114 2114 2113 2114 2551 2551 2533 O mm 639 638 621 619 631 623 623 620 621 632 620 629 629 626 P mm 686 687 704 734 722 730 730 733 732 721 733 724 724 727 Q mm 293 293 293 293 293 293 293 293 293 293 293 293 293 324
W mm 1398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425
OD mm 139.7 139.7 168.3 168.3 168.3 168.3 168.3 219.1 219.1 219.1 219.1 219.1 219.1 219.1
OD1 mm 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 168.3
Length mm 3526 3526 3534 3534 3534 3933 3894 3902 3902 3902 3902 4678 4678 4678
Depth mm 1398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425
Height mm 1640 1640 1871 1871 1871 1980 1980 2083 2083 2083 2083 2083 2083 2146
W1 kg 625 633 753 761 790 833 871 1033 1037 1064 1074 1274 1276 1361 W2 kg 615 622 741 757 778 879 997 1001 1006 1033 1042 1274 1276 1407 W3 kg 674 685 861 875 874 945 989 1184 1185 1174 1232 1418 1421 1531 W4 kg 663 673 847 871 861 999 1132 1148 1149 1140 1194 1418 1421 1582
Operating weight kg 2576 2612 3201 3264 3304 3656 3988 4367 4377 4411 4542 5384 5393 5881
Shipping weight kg 2368 2405 2884 2947 2981 3333 3654 3871 3881 3902 4036 4795 4800 5283
Particular accessories, executions or versions can bring about a great variation of the mass represented here. Please contact our Technical Department.
(1) COMPRESSOR (2) INTERNAL EXCHANGER
(EVAPORATOR)
(3) EXTERNAL EXCHANGER
(CONDENSER) (4) INTERNAL EXCHANGER WATER INLET (5) INTERNAL EXCHANGER WATER
OUTLET (4 & 5) FITTINGS WITH FLEXIBLE JOINT
AND SOLDER PIPE CONNECTION (6) EXTERNAL EXCHANGER WATER INLET (7) EXTERNAL EXCHANGER WATER
OUTLET (6 & 7) FITTINGS WITH FLEXIBLE JOINT
AND SOLDER PIPE CONNECTION (8) HOLE TO HANG UNIT (9) LIFTING HOLES (10) ELECTRICAL PANEL (11) POWER INPUT (12) LIFTING TUBE (13) MINIMUM DIMENSION ON THE
ELECTRICAL SWITCHBOARD SIDE (14) MINIMUM DIMENSION FOR A SAFE
PASSAGE WHEN THE DOOR OF THE
ELECTRICAL SWITCHBOARD IS OPEN (15) MINIMUM DIMENSION FOR A SAFE
PASSAGE (16) MINIMUM DIMENSION FOR
MAINTENANCE
M03I40M7-03 15/11/07 page 52
ACOUSTIC CONFIGURATION: STANDARD (EN) / ENERGY EFFICIENCY: EFFICIENCY CLASS B
1
1
2
3
45
6 OD1
10
OD
OD
11
1
12
10
3
3
C1
C2
16
16
15
14
11
G
8 8
2
12
9
9
8 8
16
10
11
W1
W2
W3
W4
13
13
17
17
7 OD1
700
1500
700
M N
Q
I
40 1245 40
280 650 395
1325
W
H
A 2200 B
C D E
L
700
1000
1600
PO
EN-CLB
SIZE 2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600
A mm 608 608 611 611 611 894 894 868 868 868 868 1098 1098 1098 B mm 1012 1012 1020 1020 1020 1139 1139 1248 1248 1248 1248 1451 1451 1451 C mm 483 483 505 505 505 788 788 788 788 788 788 743 743 743 D mm 2460 2460 2412 2412 2412 2412 2412 2360 2360 2360 2360 2910 2910 2910 E mm 877 877 914 914 914 1033 1033 1168 1168 1168 1168 1096 1096 1096 H mm 1781 1781 1891 1891 1891 2106 2106 2182 2182 2182 2182 2182 2182 2245
I mm 710 710 781 781 781 781 781 819 819 819 819 819 819 883
L mm 3820 3820 3831 3831 3831 4233 4233 4316 4316 4316 4316 4749 4749 4749
M mm 1716 1717 1716 1718 1716 2031 1990 1965 1964 1989 1969 2204 2204 2219
N mm 2115 2114 2115 2113 2115 2202 2243 2351 2352 2327 2347 2545 2545 2530 O mm 637 645 621 632 631 617 617 618 618 629 618 624 624 622 P mm 688 680 704 721 722 736 736 735 735 724 735 729 729 731 Q mm 293 293 293 293 293 293 293 293 293 293 293 293 293 324
W mm 1398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425
OD mm 139.7 139.7 168.3 168.3 168.3 168.3 168.3 219.1 219.1 219.1 219.1 219.1 219.1 219.1
OD1 mm 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 141.3 168.3
Length mm 3820 3820 3831 3831 3831 4233 4233 4316 4316 4316 4316 4749 4749 4749
Depth mm 1398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425
Height mm 1781 1781 1891 1891 1891 2106 2106 2182 2182 2182 2182 2182 2182 2245
W1 kg 720 738 819 853 858 891 1002 1092 1095 1101 1132 1360 1362 1450 W2 kg 726 746 827 864 866 953 995 1086 1087 1143 1134 1375 1377 1507 W3 kg 781 780 937 941 949 1031 1160 1260 1264 1226 1306 1539 1541 1652 W4 kg 788 789 945 953 958 1103 1152 1253 1255 1273 1309 1556 1558 1717
Operating weight kg 3016 3052 3528 3611 3631 3977 4309 4691 4702 4743 4881 5829 5838 6326
Shipping weight kg 2808 2845 3211 3294 3308 3654 3975 4195 4206 4234 4375 5240 5245 5728
Particular accessories, executions or versions can bring about a great variation of the mass represented here. Please contact our Technical Department.
(1) COMPRESSOR (2) INTERNAL EXCHANGER
(EVAPORATOR)
(3) EXTERNAL EXCHANGER
(CONDENSER)
(4) INTERNAL EXCHANGER WATER INLET (5) INTERNAL EXCHANGER WATER
OUTLET
(4 & 5) FITTINGS WITH FLEXIBLE JOINT
AND SOLDER PIPE CONNECTION
(6) EXTERNAL EXCHANGER WATER INLET (7) EXTERNAL EXCHANGER WATER
OUTLET
(6 & 7) FITTINGS WITH FLEXIBLE JOINT
AND SOLDER PIPE CONNECTION
(8) HOLE TO HANG UNIT (9) LIFTING HOLES (10) ELECTRICAL PANEL (11) POWER INPUT (12) SOUNDPROOFED CABIN (13) LIFTING TUBE (14) MINIMUM DIMENSION ON THE
ELECTRICAL SWITCHBOARD SIDE
(15) MINIMUM DIMENSION FOR A SAFE
PASSAGE WHEN THE DOOR OF THE
ELECTRICAL SWITCHBOARD IS OPEN
(16) MINIMUM DIMENSION FOR A SAFE
PASSAGE
(17) MINIMUM DIMENSION FOR
MAINTENANCE
CLIVET SPA Feltre (BL) ITALY
Tel. + 39 0439 3131 Fax + 39 0439 313300 info@clivet.it
CLIVET ESPAÑA S.A. Madrid - SPAIN
Tel. + 34 91 6658280 Fax + 34 91 6657806 info@clivet.es
CLIVET UK LTD Fareham (Hampshire) U.K.
Tel. + 44 (0) 1489 572238 Fax + 44 (0) 1489 573033 info@clive t-uk.co.uk
CLIVET NEDERLAND B.V. Amersfoort - Netherlands
Tel. + 31 (0) 33 7503420 Fax + 31 (0) 33 7503424 info@clivet.nl
CLIVET TFAIR SYSTEMS (P)LTD. Malur - INDIA
Tel. +91 8151 232683/5 Fax +91-8151-232684 info@cli vettfa.com
CLIVET SPA BUREAU DE LIAISON E N FRANCE Verrierès le Buisson - FRANCE
Tel. + 33 (0)1 69 20 25 75 Fax + 33 (0)1 69 20 60 76 info.fr@clivet.com
CLIVET GmbH Norderstedt - GERMANY
Tel. +49 (0) 40 32 59 57-0 Fax +49 (0) 40 32 59 57-194 info.de@clivet.com
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice. All reproduction, even
partial, is PROHIBITED.
© COPYRIGHT - CLIVET S.P.A. - FELTRE (BL) - ITALIA
Loading...