CLIVET WBAN Series, WBAN 122, WBAN 162, WBAN 82, WBAN 302 Installation, Use & Maintenance Manual

...
Page 1
WBAN 82 - 302
Installation use and maintenance manual
M0E240G9-10
22-04-2016
Page 2
Dear Customer, We congratulate you on choosing these product. Clivet is being working for years to offer systems able to assure the maximum
comfort for long time with high reliability, efficiency , quality and safety. The target of the company is to offer advanced systems, that assure the best com­fort, reduce the energy con-sumption, the installation and maintenance costs for all the life-cycle of the system.
With this manual, we want to give you information that are useful in all the phases: from the reception, to the installation and use until the disposal so that a system so advanced offers the best procedure of installation and use.
Best regards and have a nice reading ! CLIVET Spa
2
Page 3
INDEX
General
1
Reception
2
Positioning
3
Water connections
4
Electrical connections
5
Start-up
6
Regulation
7
Maintenance
8
Disposal
9
4
6
8
10
12
21
27
33
35
Technical information
10
Residual risks
11
36
44
3
Page 4
1 - GENERAL
1.1 MANUAL
The manual provides correct unit installation, use and maintenance.
Pay particolar attention to: Warning identifies particularly important operations or
information . Prohibited operations that must not be carried out, that
compromise the operating of the equipment or may cause damage to persons or things.
It is advisable to read it carefully so you will save time
during operations.
Follow the written indications so you will not cause
damages to things and injuries people. The preliminary information must be read prior to carrying out any of the following operations.
1.2 GENERAL INSTRUCTIONS Preliminaries
The positioning, hydraulic system, refrigerating, electrics and the channelisation of the air must be determined by the system designer in accordance with local regulations in force.
Only qualified personnel can operate on the unit, as required by the regulation in force.
Using the unit in case of breakdown or malfunction :
voids the warranty may compromise the safety of the machine may increase time and repair costs.
Follow local safety regulations. .
Keep packing material out of children’s reach it may be
dangerous. . Recycle and dispose of packing material in conformity with
local regulations. .
Risk situations
The unit has been designed and created to prevent injures to people.
During designing it is not possible to plane and operate on all risk situation.
Read carefully "Residual risk" section where all situation which may cause damages to things and injuries to people are reported.
Installation, starting, maintenance and repair required specific knowledge; if they are carried out by inexperienced personnel, they may cause damages to things and injuries people.
Intended use
Use the unit for cooling/heating water or a water and glycol mix for air-conditioning only, within limits defined in the technical bulletin and on this manual..
Any use other than intended does not involve the manufacturer in any commitment or obligation. .
Installation
Verify that the electrical line characteristics are in compliance with data quotes on the unit serial number label.
Maitenance
Plan periodic inspection and maintenance in order to avoid or reduce repairing costs.
Turn the machine off before any operation.
Modification
All unit modifications will end the warranty coverage and the manufacturer responsibility. .
Breakdown/Malfuction
Disable the unit immediately in case of breakdown or malfunction. .
Contact a constructor certified assistance service. Use original spares parts only.
User training
The installer has to train the user on :
start-up / shutdown; set points change; standby mode; maintenance; what to do / what not to do in case of breakdown.
Data update
Continual product improvements may imply manual data changes .
Visit manufacturer web site for updated data.
1.3 INDICATIONS FOR THE USER
Keep this manual with the wiring diagram in an accessible place for the operator.
Note the unit lable data so you can provide them at the assi­stance centre in case of intervention (see "Unit identification" section).
Provide a machine notebook that allows any interventions carried out on the machine to be noted and tracked making it easier to suitably note the various interventions and aids the search for any breakdowns.
In case of breakdown or malfunction:
immediately deactivate the unit . contact a assistance service centre authorized by the
manifacturer.
use original spares parts only
Ask the installer to format on:
start-up / shutdown; set points change; standby mode; maintenance; what to do / what not to do in case of breakdown.
4
Page 5
1 - GENERAL
1.4 UNIT INDENTIFICATION
Serial number label The serial number label is positioned on the unit and allows to
indentify all the unit features. It has not to be removed for any reason. It reports the regulations indications such as:
machine type, exmple:
Series WBAN Size 82
serial number
12 characters Axxxxxxxxxxx
year of manufacture wiring diagram number electrical data manufacturer logo and address .
Serial number It identifies uniquely each machine.
It identifies specific spare parts for the machine. Assistance request Note data from the serial number label and write them in the chart on side, so you will find them easily when needed. In case of intervention you have to provide data.
Serie
Size
Serial number
Year of manufacture
Wiring diagram
1.5 UNIT DESCRIPTION
VULCAN Medium is a high temperature heat pump series representing ideal single solution for heating, cooling and sanitary hot water production for centralised systems, such as in blocks of apartments, hotels and for use with collective applications in general.
A CLASS Energy Efficiency according to Eurovent, both
for heating and cooling.
Ideal for all plant types including radiator systems using
hot water produced at a temperature of up to 60°C, and ambient air at -10°C.
A simplified system thanks to the use of a single generator
for heating and cooling that eliminates the risks and obli­gatory maintenance costs associated with traditional com­bustion systems.
The units in the ELFOEnergy VULCAN Medium range can autonomously produce sanitary hot water and are set up for use in combination with solar panel storage tanks, thus ena­bling the direct use of solar energy.
1.6 ACCESSORIES
VERSIONS OPTIONS
D Partial energy recovery B Water low temperature
REFRIGERANT CIRCUIT
CCCA Copper / aluminium condenser coil with acrylic lining EOL Operating limit extension
AIR SIDE FEATURES
ECHP External fans with larger available head
"ECOBREEZE"
HYDRAULIC CIRCUIT
3DHWX Three-way valve for domestic hot water 3DHW Built-in 3-way valve for domestic hot water on the unit
IS4 Compressor insulation
- Hydronic group utility side: not required
1PUS Standard pump 1PUR Single-pump with reduced available head 1PUM Single-pump with larger available head 1PUHE High efficiency single inverter pump for primary circuit.
CACSX Domestic hot water kit control TCDC Condensate collection pan with electric heater
ELECTRIC CIRCUIT
TASRX Compartment for multifunction keyboard PM Phase monitor PMX Phase monitor SFSTR4N Disposal for inrush current reduction, for unit
400/3/50+N
PFCP Power factor correction capacitors (cosfi > 0.9)
INSTALLATION
AMRX Rubber antivibration mounts PGFC Finned coil protection grill PGFCX Finned coil protection grill
X = Accessory separately supplied
5
Page 6
2- RECEPTION
?
2.1 PRELIMINARY INFORMATION
Operate in compliance with safety regulations in force . For detailed information (dimensions, weight, technical cha-
racteristics etc.) please refer to the “Technical information”
section. Use single protection devices : gloves, glasses ecc. .
2.2 DELIVERY CONTROL
Before accepting the delivery you have to check:
That the unit hasn’t been damaged during transport. Check that the materials delivered correspond with that
indicated on the transport document comparing the data
with the identification label ‘A’ positioned on the packa-
ging.
In case of damage or anomaly:
Write down on the transport document the damage
you found and quote this sentence: "Conditional acceptance clear evidence of deficiencies/ damages during transport".
Contact supplier and the carrier by fax and registered
mail with advice of receipt.
Any disputes must be made within the 8 days following the delivery. Complaints after this period are invalid..
2
3
4
2.3 HANDLING
1. Verify unit weight and handling equipment lifting capacity .
2. Identify critical points during handling (disconnected
routes, flights, steps, doors)
3. Use protection to avoid the unit damaging .
4. Lifting pipe
5. Lifting beam with spacers
6. Lifting with spacer bar
7. Align the barycentre to the lifting point
8. Use all the lifting brackets (see "Technical informations -
dimensions)
9. Gradually bring the lifting belts under tension, making sure they are positioned correctly. .
10. Before handling verify that the unit keeps its balance.
1
5
6
6
Page 7
7
2- RECEPTION
2.4 STORING
Observe external packing instructions .
2.5 PACKING REMOVING
Be careful not to damage the unit. Recycle and dispose of packing material in conformity with
local regulations.
7
Page 8
3 - POSITIONING
3.1 PRELIMINARY INFORMATION
Operate in compliance with safety regulations in force. For detailed information (dimensions, weight, technical
characteristics etc.) please refer to the TECHNICAL INFORMATION section.
Use single protection devices : gloves, glasses ecc.
During positioning consider these elements :
technical spaces required for the machine and system place where the machine will be installed electrical connections water connections air / aeraulic ducts
Do not considerer these elements could decrease performances and operational life of the unit.
3.2 FUNCTIONAL SPACES
Functional spaces are designed to:
guarantee good unit operation carry out maintenance operations protect authorized operators and exposed people
Respect all functional spaces indicated in the TECHNICAL INFORMATION section.
Double all functional spaces if two or more unit are aligned.
3.3 POSITIONING
Units are designed to be installed:
EXTERNAL in fixed positions.
Choose the installation place according to the following criteria:
Customer approval safe accessible position technical spaces requested by the unit spaces for the air intake/exhaust max. distance allowed by the electrical connections control points with capacity adequate to the unit weight condensate water draining
Prefer places where the unit doesn't disturb the neighbours. Avoid installations next to bedrooms or windows. Avoid snow accumulations on batteries. Avoid installations in places subject to flooding In case of ground installation provide a raised base to avoid
flood damages. Protect the unit with an appropriate fencing to avoid the
access to a not authorized personnel (babies, vandals etc.)
Limit vibration transmission:
use antivibration devices on unit bearing points; install flexible joints on the hydraulic.
A correct circulation of the air is indispensible to guarantee the good working order of the machine.
Avoid therefore:
obstacles to the airflow; exchange difficulties;
leaves or other foreign bodies that can obstruct the
exchange batteries;
winds that hinder or favour the airflow; heat or pollution sources close to the unit (chimneys,
extractors etc);
stratification (cold air that stagnates at the bottom); recirculation (expelled air that is sucked in again); positioning below the level of the threshold, close to very
high walls, attics or in angles that could give rise to stratification or recirculation phenomenons.
Ignoring the previous indications could:
energy efficiency decrease; blocks due to HIGH PRESSURE (in summer) or LOW
PRESSURE (in winter).
3.4 CONDENSATE WATER
When a heat pump is running it produces a considerable amount of water due to the defrosting cycles of the external coil.
The condensation must be eliminated in a manner to avoid wetting pedestrian areas.
With extensive very cold outdoor temperatures, condensation could freeze and block the flow, causing a slow build-up of ice; therefore special attention must be paid to eliminating condensation, raising the unit off the ground and evaluating whether antifreeze elements should be installed
8
Page 9
3 - POSITIONING
Condensate collection pan with electric heater - option
1
2
4
3
1 2
3
4
9
Page 10
4 - WATER CONNECTIONS
4.1 PRELIMINARY INFORMATION
Selection and installation of system components must be carry out by installer.
Following you will find some indications to integrate with what is provided by the local regulations in force and by the good technical laws.
4.2 COMPONENTS
CUT-OFF VALVES
Installed at inlet and outlet (both on the water technique
circuit as well as that of the hot domestic water) allow maintenance operations without having to empty the system .
THERMOMETERS AND MANOMETERS
Installed at entry and exit of the main elements facilitate
inspection and maintenance.
AIR BLEED VALVE
Installed in all of the highest points of the system allowing
the venting of the circuits air..
DRAINAGE TAPS
Installed in the lowest points of the system to allow
bleeding.
EXPANSION TANK
It keeps a correct system pressure when the water
temperature changes. It must be dimensioned as a function of water plant volume and temperature.
WATER FILTER
If not present on-board the machine, must be installed
immediately in the water input of the unit, in a position that is easily accessible for cleaning.
The filter never should be removed, this operation
invalidates the guaranty
SUPPORTS
The hydraulic pipes weight mustn’t burden on the unit
connections ..
FLOW SWITCH
The flow switch must be present as a component of the
system
4.4 WATER QUALITY
The water quality is determined by the following factors, avoid therefore:
Inorganic salts pH Biological load (seaweeds etc) Suspended solids Dissolved oxygen
Water with inadequate characteristics can cause:
pressure drop increase energy efficiency decrease corrosive symptom increase
4.5 RISK OF FREEZE
If the unit or the relative water connections can be subject to temperatures close to 0°C adopt measures for prevent risk of freeze.
For example:
Mix water with ethylene glycol Safeguard the pipes with heating cables placed under the
insulation
Empty the system in cases of long non-use and check that:
there are no closed taps present that could trap water
even after emptying
there are no low points in which water can stagnate
even after emptying; carry out any blowing required .
4.6 ANTI-FREEZE SOLUTION
Consider that the use of anti-freeze solution determines an increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not corrosive) and compatible with the hydraulic circuit components (pump etc).
Do not use different glicol mixture (i.e. ethylene with propylene)
4.7 RECOMMENDED CONNECTION
4.3 OPERATION SEQUENCE
1. Carefully wash the system with clean water: fill and drain the system several times.
2. Apply additives to prevent corrosion, fouling, formation of mud and algae.
3. Fill the plant
4. Execute leakage test.
5. Isolate the pipes to avoid heat dispersions and formation of
condensate.
6. Leave various point of service free (wells, vent-holes etc).
Neglecting the washing will lead to several filter cleaning interventions and at worst cases can cause damages to the exchangers and the other parts.
A unit without hydronic assembly B unit with hydronic assembly C unit with three-way valve
1. vent
2. filter
3. pump
4. safety valve
5. three-way valve
10
6. antivibration joints
7. supports
8. expansion tank
9. flow switch
10. vent
11. Differential pressure switch
Page 11
4 - WATER CONNECTIONS
4.8 PARTIAL ENERGY RECOVERY
A configuration which enables the production of hot water free
-of-charge while operating in the cooling mode.
The partial recovery device is considered to be operating when it is powered by the water flow which is to be heated.
The customer is responsible for the management of the circulation pump, valves, thermostats, etc.
When the temperature of the water to be heated is particularly low, it is wise to insert a flow control valve into the system hydraulic circuit, in order to maintain the temperature at the recovery output at above 35°C and thus avoid the condensation of the refrigerant into the partial energy recovery device.
Water connections must be performed carefully as for the evaporator (filter, circuit washing, etc).
Perform all necessary interventions to avoid the RISK OF FREEZING (tubes insulation, emptying of circuit, addition of glycol, anti-freeze resistances).
Water temperature can reach high temperatures (up to 100°C) Avoid the RISK OF BURNS by adopting the necessary
precautions (insulation of tubes, temperature detecting station on water if the sanitary use is foreseen, etc.)
Install safety valves and specifically dimensioned expansion tanks in the hydraulic circuit.
D - Partial recovery device
VM - adjustment charged to the customer
11
Page 12
5 - ELECTRICAL CONNECTIONS
5.1 PRELIMINARY INFORMATION
The characteristics of the electrical lines must be determined by specialized personnel able to design electrical installations; moreover, the lines must be in conformity with regulations in force. The protection devices of the unit power line must be able to stop the presumed short circuit current, whose value must be determined in function of system features. The power cables and the protection cable section must be defined in accordance with the characteristics of the protections adopted. All electrical operations should be performed by trained personnel having the necessary requirements by the regulations in force and being informed about the risks relevant to these activities. Operate in compliance with safety regulations in force .
5.2 ELECTRICAL DATA
The serial number label reports the unit specific electrical data, included any electrical accessories .
The electrical data indicated in the technical bulletin and in the manual refer to the standard unit, accessories excluded.
Refer to the electrical data report on the serial number label.
5.4 SIGNALS / DATA LINES
Do not overpass the maximum power allowed, which varies, according to the type of signal.
Lay the cables far from power cables or cables having a different tension and that are able to emit electromagnetic disturbances.
Do not lay the cable near devices which can generate electromagnetic interferences.
Do not lay the cables parallel to other cables; cable crossings are possible, only if laid at 90°.
Connect the screen to the ground, only if there aren’t
disturbances Guarantee the continuity of the screen during the entire
extension of the cable. Respect impendency, capacity and attenuation indications.
5.5 ELECTRIC LINES INLET
serial
number
label
F.L.A. full load ampere Full load current at max admissible conditions
F.L.I. Full load input Full load power input ( at max. admissible condition )
5.3 CONNECTIONS
1. refer to the unit electrical diagram (the number of the diagram is shown on the serial number label)
2. verify that the network has characteristics conforming to the data shown on the serial number label
3. Before starting work, verify that the sectioning device at the start of the unit power line is open, blocked and equip­ped with cartel warning
4. Primarily you have to realize the earthing connection
5. Shelter the cables using adequate measure fairleads
6. Before power the unit, make sure that all the protections
that were removed during the electrical connection work have been restored.
VOLTAGE
FLA (A)
FLI (kW)
Fix the cables: if vacated may be subject to tearing. The cable don't have to touch the compressor and the
refrigerant piping ( they reach high temparatures ).
12
Page 13
5.6 ELECTRICAL PANEL
1 2
4567
2
3
5 - ELECTRICAL CONNECTIONS
AP1 AP4 AP4A-B AP5 AP10-11 XCA
AP1
Main control module Local base for HID-H1 interface Fan Module RS 485 module Soft starter Terminal block of Customer connections
QM1-2 QM3 KM1-2 KM3 FU1 FU2-3 FU6-7
Compressor motor overload cutout Overload cutout switch pump Compressor contactor Pump contactor Control circuit fuse Phase monitor fuse Fan fuse
1 2 3 terminal block XC4 4 terminal block XC5 5 terminal block XC3 6 terminal block XC2 7 terminal block XC1
RS 485 module auxiliary fuse
13
Page 14
5.7 CUSTOMER CONNECTIONS
SA2 summer - winter
The mode switching can occur from keyboard or remote contact Switch for remote selector
(SA2): set par. 21=0 ; In this
case, the keyboard command is not possible
WR 4-20mA water reset BT14 water outlet temperature probe
of hydraulic module SA1 on-off SA4 domestic hot water WR 0-10V water reset BT9 storage tank temperature probe
5 - ELECTRICAL CONNECTIONS
SA3 2nd setpoint SQ2 flow switch DL demand limit HAE% humidity control probe
14
Page 15
5 - ELECTRICAL CONNECTIONS
A boiler valve control B sanitary hot water valve control C boiler control D cumulative fault alarm relay E unit operating signal
HLH HEAT status HLC COOL status
HL3 3-ways valve status HL1-2 compressor status KM1-2 compressor contactor
15
Page 16
5 - ELECTRICAL CONNECTIONS
4
XC2
6 41
XC5
42
SA4
5
33 34
16
7
XC5
BT14
KM4
XC1
ST9
BT9
YVB
YVB
51 52
YVA
YVA
max 230V AC
max 1A AC1
XC5
XC2
2 1
3 10 11
WBAN
11
XC1
2
KMPU
TK
XCA
TK
FRPU
5.8 3-WAY VALVE - CUSTOMER SUPPLIED
SA4 domestic hot water (Customer supplied) XC2 valve command
5.9 SYSTEM PUMP - CUSTOMER SUPPLIED
XC1 main module terminal block XCA electrical panel terminal block KMPU contactor (Customer supplied) FRPU Overload cutout switch pump (Customer supplied)
5.11 AUXILIARY HEATER IN REPLACEMENT
Customer supplied: auxiliary heater YVA heater interception valve YVB unit interception valve
5.10 AUXILIARY HEATER IN INTEGRATION
Customer supplied: auxiliary heater ST9 high temperature safety thermostat BT14 temperature probe outlet heater KM4 heater contactor
CN4-5
CN4-6
16
Page 17
5 - ELECTRICAL CONNECTIONS
5.12 REMOTE KEYPAD
The keypad can be placed in a remote position for 2 different reasons :
1. To directly interface with the unit without moving from the unit installation place
2. To be used as room thermostat, that measures the ambient temperature and manages the thermoregulation controlling the pump on the secondary
See the CONTROL section. The KEYPAD SUPPORT accessory is necessary
Distance: max 80 mt.
Keypad rear view : 2 coils type AA LR6
17
Page 18
5 - ELECTRICAL CONNECTIONS
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
ON-OFF
Heat-Cool
Setpoint
Water Reset
Demand Limit
MASTER
SLAVE SLAVE SLAVE
SC SSC C
C
C
S
37
19
1
38
20
2
37
19
1
38
20
2
37
19
1
38
20
2
UNIT 1
UNIT 2
UNIT ...6
XC5 XC5 XC5
MAX 200 mt
5.13 MINI-NET
C controls S signaling
1. max : 1 master + 5 slave
2. Perform the electrical connections as indicated in the
diagram
3. Set the DIP1 on the master unit
4. Set the DIP1 on the slave units
5. Set the DIP2 - SW4 on the slave units
6. Switch on and off the master unit
7. On the master become visible the mininet parameters
8. Set the parameters on the master unit
Mininet configuration parameters : CONFIGURATION menu > UNIT > MININET
num. Parameter description
343 N. of units connected in Mininet
N. of units in standby for rotation : it allows to keep
344
one or more units in standby (automatic rotation)
Enables the exclusion of the unit in alarm
345
(1=enabled)
346 Offset between the unit SetPoint
Mininet unit addressing through DIP1
num. UNIT' DIP 1
1 master
2 slave
Electrical connections
For the cable characteristics see MODBUS
RS485
3 slave
4 slave
5 slave
6 slave
2 .. 6 slave
18
Page 19
5 - ELECTRICAL CONNECTIONS
EXEMPLE
4 units operate for the installation 2 units operate for the DHW in an independent and dedicated way to its storage
ACS domestic hot water I installation M Master: installation I S1 Slave1: installation I S2 Slave2: installation I + ACS2 accessory 3DHW Three-way valve for domestic hot water accessory CACSX Domestic hot water kit control S3 Slave3: installation I + ACS3
accessory 3DHW Three-way valve for domestic hot water
accessory CACSX Domestic hot water kit control
Indicative plumbing diagram
S3
S2
S1
ACS
3
ACS
2
I
M
19
Page 20
GND
S -
S +
GND
-
+
S+ S-
-
+
5.14 MODBUS
3
J
3S
4S
ON
ON
S1
S2
ON
RS485
LR
LV
J 1
G N D
-
+
5S
5 - ELECTRICAL CONNECTIONS
Perform the RS 485 MODULE addressing by S3, S4 S5 ; allowed and valid addresses from 1 to 127
AP1
S3 it sets the address dozens S4 it sets the address units S5 it sets the address hundreds ON = 100, OFF = 0
S1 485 terminator: ON = termination YES S2 line polarizer:
Inside the 485 net only one card must be polarized, usually is polarized the master, i.e. the PC ; in this case S2 = OFF = polarization NO
if more cards are polarized, faults occur J1 RS 485 serial J3 TTL serial
AP5
LV = GREEN LED : OK LR = RED LED QUICK FLASHING:
wrong address faulty module
NETWORK CABLE FEATURES Couple of conductors twisted and shielded Section of conductor 0.22mm Nominal capacity between conductors < 50 pF/m nominal impedance 120 Ω Recommended cable BELDEN 3105A
2
…0,35mm
2
20
Page 21
6 - START-UP
PRELIMINARY CHECKS
To check before starting-up the unit . For details refer to the different manual sections.
Preliminary checks - Unit OFF power supply
Access in safety
Functional clearances
Air flow : free return and supply (no bypass, no stratification)
Structure integrity
Fans run freely
Unit on vibration isolators
Unit input water filter + shut-off valves for cleaning
Vibration isolators on water connections
Expansion tank (indicative volume = 5% system content)
Cleaned system
Loaded system + possibile glicole solution + corrosion inhibitor
Under pressure system
Vented system
Refrigerant circuit visual check
Earthing connection
Power supply features
Electrical connections provided by the customer
Ext. auxiliary heater connections (if present)
External 3-way valve connection (if present)
External pump connection (if present)
21
Page 22
6 - START-UP
START-UP SEQUENCE
Operations to perform to start-up the unit. For details refer to the different manual sections.
Start-up sequence - Unit ON power supply
Compressor carter resistances operating at least since 8 hours
Off-load voltage measure
Phase sequence check
Pump manual start-up and flow check
Unit ON
Load voltage measure and absorptions
Liquid light check (no bubbles)
Check of all fan operating
Measure of return and supply water temperature
Super-heating and sub-cooling measure
Check no anomalous vibrations are present
Set-point personalization
Climatic curve personalization
Scheduling personalization
Complete and available unit documentation
22
Page 23
6 - START-UP
L1 L2 L3
388 V
379 V
377 V
388 + 379 + 377
3
=
381
388 (max) – 381 = 7
7
381
x 100 = 1,83 OK
1)
2)
3)
6.1 PRELIMINARY INFORMATION
The indicated operations should be done by qualified technician with specific training on the product.
Upon request, the service centres performing the start-up; the electrical, water connections and the other system works are by the installer.
Agree upon in advance the star-up data with the service centre.
6.2 PRELIMINARY CHECKS
Before checking, please verify the following :
the unit should be installed properly and in conformity with
this manual.
the electrical power supply line should be sectioned at the
beginning.
The line sectionalizing device is open, locked and
equipped with the suitable warning
make sure no tension is present
6.3 REFRIGERANT CIRCUIT
6.5 ELECTRICAL CIRCUIT
Verify that the unit is connected to the ground plant Check the conductors tightening: the vibrations caused by
handling and transport might cause loosing Feed the unit by closing the sectioning device, but leave it on
OFF. Check the tension and line frequency values which must be
within the limits : 400/3/50 +/- 10%
Control the unbalancing of the phases: it must be lower than 2% Example:
1. Check carefully the refrigerating circuit: the presence of oil
stains can mean leakage caused by transportation,
movements or other).
2. Verify that the refrigerating circuit is in pressure: Using the
unit manometers , if present, or service manometers.
3. Make sure that all the service outlets are closed with
proper caps; if caps are not present a leak of refrigerant
can be possible.
6.4 HYDRAULIC CIRCUIT
1. Before realizing the unit connection make sure that the
hydraulic system has been cleaned up and the clearing water has been drained
2. Check that the water circuit has been filled and
pressurized
3. Check that the shut-off valves in the circuit are in the
"OPEN" position.
4. Check that there isn’t air in the circuit, if required,
evacuate it using the air bleed valve placed in the system high points.
5. When using antifreeze solutions, make sure the glycol
percentage is suitable for the type of use envisaged.
The working out of the limits can cause irreversible damages and voids the warranty.
6.6 COMPRESSOR CRANKCASE RESISTANCES
Connect the oil resistances on the compressor crankcase at least 8 hours before the compressor is to be starter :
at the first unit start-up after each prolonged period of inactivity
1. Supply the resistances switching off the unit isolator switch.
2. To make sure that hte resistances are working, check the power input .
3. At start-up the compressor crank-case temperature on the lower side must be higher at least of 10°C than the outside temperature.
Do not start the compressor with the crankcase oil below operating temperature.
Weight of glycol (%)
Freezing temperature (°C) Safety temperature (°C)
10 20 30 40
-4 -9 -15 -23
-1 -4 -10 -19
23
Page 24
6 - START-UP
112 113
116
T.Ex
SP
115 114
117
T.Ex
SP
6.6 TENSIONS
Check that the air and water temperatures are included in the working limits
For information on the control system, refer to the paragraph CONTROL.
Start the unit With unit of full load, namely in stable conditions and close to
those of work, check :
Power supply tension Total absorption of the unit Absorption of the single electric loads
6.7 REMOTE CONSENT
Check that the remote commands (ON-OFF, etc.) are
connected and if necessary enabled with the relevant parameters as described in ELECTRICAL CONNECTIONS section
Check that probes or optional components are connect
and enable with the relative parameters( ELECTRICAL CONNECTION section)
6.8 STARTING REPORT
Realize the operating objective conditions is useful for check the unit over time.
With unit of full load, namely in stable conditions and close to those of work, take the following data:
Tension and general absorptions with unit at full load Absorption of varied electrical loads (compressors, fans,
pumps etc)
Temperatures and capacities of different liquid (water, air)
in the inlet and outlet of the unit
Temperatures and pressures on the refrigerant circuit
characteristic points (compressor discharge, liquid, intake)
The remarks should be preserved and available during maintenance .
6.9 CE 97/23 PED DIRECTIVE
97/23 CE PED DIRECTIVE gives instructions for installers,
users and maintenance technicians as well. Refer to local actuation norms; briefly and as an example, see
the following
Compulsory verification of the first installation :
only for units assembled on the installer’s building site (for ex. Condensing circuit + direct expansion unit)
Certification of setting in service :
for all the units
Periodical verifications:
to be executed with the frequency indicated by the
manufacturer (see the maintenance section)
6.10 SETPOINT CORRECTION FOR OUTSIDE
TEMPERATURE
SUMMER With outside low temperatures the refrigerant requirements are reduced. The internal comfort can also be obtained with a set-point higher than standard. The correction is summed to SP set-point : it increases at the outside temperature T.Ex. decreasing
WINTER With outside mild temperatures the thermal requirements are reduced. The internal comfort can also be obtained with a lower se­tpoint. The correction is subtracted to SP set-point : it decreasing at the outside temperature T Ex. increasing
Configuration parameters
4 CompExt
112 CextMaxC Ext. Temp. max. winter correction 113 CextMinC Ext. Temp. min. winter correction 114 CextMaxH Winter correction max. value
115 CextMinH Winter correction min. value 116 MaxCExtC Summer correction max. value 117 MaxCExtH Winter correction max. value 118 HExtMinC Ext. enthalpy min. correction 119 HExtMaxC Ext. enthalpy max. correction
External temp. comp. enabling
0=No, 1=Cool, 2=Heat, 3=Always
24
Page 25
6 - START-UP
118 119
116
U.R.
SP
141 140
139
W.R.
SP
137 138
136
WR
SP
6.11 SETPOINT CORRECTION FOR EXTERNAL
ENTHALPY
SUMMER With low ext. Humidity the refrigerant requirements are redu­ced. The internal comfort can also be obtained with a set-point higher than standard. The correction is summed to SP set-point : it increases at the fresh air humidity RH decreasing.
Configuration parameters
4 CompExt
16 EnUrExt Enable ext. RH% probe 116 MaxCExtC Summer correction max. value 118 HExtMinC Ext. enthalpy min. correction 119 HExtMaxC Ext. enthalpy max. correction
6.12 DISTRIBUTION PUMP
The pump of the secondary circuit can be controlled :
Enable comp. for External Temp.
0=No, 1=Cool, 2=Heat, 3=Always
by remote request at the SA1 input
6.13 WATER RESET
SUMMER When the refrigerant requirements are low the WR signal is high : the setpoint is increased The correction is summed to SP set-point .
WINTER When the thermal requirements are low the WR signal is low : the setpoint is decreased. The correction is subtracted to SP set-point .
Configuration parameters
5 WaterReset
135 TypeWR
Water Reset enabling 0=No 1=Cool
2=Heat 3=Always
Set WR signal 0=0-10V 1=4-20mA
Configuration parameters
20 PumpBord
24 ControlPump
25 RemOnOffMode
Presence of second pump
0=Customer management 1=Single pump on the unit 2=Single pump+reserve 3=Pump at variable capacity
Enable the off control of the utility pump:
0=No 1=according of the ambient set 2=according to the storage
temperature Set SA1 input:
1=On/Off, 0=thermal request by ambience
136 MaxCWRH
137 SWRMAXH
138 SWRMinH
139 MaxCWRC
140 SWRMaxC
141 SWRMinC
6.14 DEMAND LIMIT
It allows to temporarily limit the electrical capacity absorbed by the unit according to an ext. signal 0 - 10V Higher is the signal and lower the number of available compressors, that is the electrical capacity absorbed.
7 DemandLimitEn Demand Limit enabling
175 Treaction demand limit reaction time
176 TypeDL
Max. value of the Winter WR correction Corresponding signal of the winter max.
correction Corresponding signal of the winter min.
correction Summer correction max. value
Signal percentage of Summer MAX correction
Signal percentage of Summer MIN correction
Configuration parameters
Type of signal for the DL 0 = from analogical input , 1 = from serial line
25
Page 26
6 - START-UP
6.15 HEATER IN REPLACEMENT
With fresh air temperature :
Lower than p. 560 the boiler is enabled Higher than p. 560 + p. 561 the heat pump is enabled
With system water temperature :
Lower than p. 558 the heat pump is disabled Higher than p. 558 - p. 559 the heat pump is enabled
Configuration parameters
13 CaldaiaEn
558 SogliaMaxImp
559 IsteresiSMI
560 SogliaExtC
561 IsteresiExt
562 TimeBypassALM
6.16 HEATER IN INTEGRATION
With fresh air temperature :
Enable boiler function + heat pump Water temp: over it the heat pump
is disabled. Closed valves on Heat pump side
Hysteresis for Heat pump enabling. Opened valves on Heat pump side
Outside temperature threshold: under it the boiler is enabled
External temperature hysteresis for heat pump re-activation
Transition time for alarm from heat pump
Lower than p. 647 the compressors are disabile and is activated only the heater Higher than p. 652 only the compressors are enabled Included between p. 647 and p. 652 resistances and heat
pump are enabled
6.17 DOMESTIC HOT WATER
Configuration parameters
12 EnH2OSanitaria
410 SanitariaHeatMode
411 DelayValvS
412 CompExtH2OS
413 MaxCompH2OS
414 PriorCoolH2OSan 415 PriorHeatH2Osan
416 ComandoVSan
417 SetH2OSanitaria
428 TimeAntiLoop
430 DeltaChiller
Enabling of the DHW management
Management for DHW forced production at satisfied system thermoregulation in heat
Opening time of the DHW valve Enabling of compensation for
outside temperature of the DHW setpoint
Max. outside T correction value for DHW setpoint
0=DHW priority ,1=system priority 0=DHW priority ,1=system priority
DHW valve management:
0=Managed according to the logic
fixed by EnH2oSanitaria, 1= In Heat always excited, 2= In Cool always excited
DHW Set Point Max permanence time in DHW
during the Antiloop control Delta for DHW setpoint of the
heat pump compared with DHW setpoint
Configuration parameters
18 EnPaux Aux. heater enabling
646 PotRes Power provided by the integration
647 LimText Ext. temperature limit for compressor
648 Tregime Resistance Timeout 649 MaxInteg Max. analogical output value of the
650 MinInteg Min. analogical output value of the
651 OffsetOnAux Step difference offset for aux
652 TextOnAux Ext. temperature limit for auxiliary
resistances
operation
integration res. when activated at the same time of the compressor
integration res. in modulation
connection
operation
26
Page 27
7 - CONTROL
27
Page 28
7 - CONTROL
28
Page 29
7 - CONTROL
p 431
p 432
SET
p 429
DOMESTIC HOT WATER (DHW)
The unit puts always the DHW at the set-point value p429. During the accumulation phase the temperature falls down to par 432. During the maintenance phase the temperature falls down to par 431. It is opportune to schedule the maintenance phase by night and during periods of lower use of domestic water. The scheduling allows to set the daily time bands and to assign
the desired operating mode :
Maintenance Maintenance + Recirculation Accumulation + Recirculation Accumulation
Par Menu: Configuration - keyboard Value
02 DHW enable 2 10 Enable network management 1
Par Menu: Configuration - unit Value
12 Enable DHW 1 315 Address 2 316 Baud Rate 1 317 Parity 0
7.5 USER PARAMETER
menu CONFIGURATION > UNIT > ALLI > USER PARAMETER
ID Description Extended description
4 CompExt Enable comp. for External Temp. (0=No 1=Cool 2=Heat 3=always)
10 MantCoolEn 11 MantHeatEn 21 RemMode 51 SetCool 52 SetHeat 53 SecondSetC 54 SecondSetH
Enable summer maintenance 1=Yes/0=No Enable winter maintenance 1=Yes/0=No Set remote inputs 0=H/C or H/DHW only or C/Solo sanitariDHW only from ID, 1=digital input no effect Summer Set Point Winter Set Point Secondary summer SetPoint Secondary winter SetPoint
DHW MODULE
Par Parameters DHW module Value
33 Index 1 34 Baud Rate 1 35 Parity 0
Ensolar
I27
only if present solar system
MDS Modbus Slave 1
1
The list includes the parameters accessibile to the user. Depending on the unit configuration of the unit some parameters may not be used.
29
Page 30
7.6 STATUS
7 - CONTROL
ID DESCRIPTION U.M.
1
Current set point Actual temperature difference (including
2
compensation)
3
Timer relative to resource insertion
Dynamic TimeScan relative to resource
4
insertion
5
External T compensation
6
Ambient T Compensation
7
Water Reset compensation
8
Charge compensation
9
Duty Cycle comp
10
Compensation on duration
11
Utility water input temperature
12
Utility water output temperature
13
Auxiliary heater outlet temperature
14
Fresh air temperature
15
Condensing coil temperature
16
Accumulation temperature
17
Utility pump
18
Utility secondary pump
19
Source flow-rate
20
Condensing pressure
21
Evaporating pressure
22
Auxiliary heater control signal (0-10V)
23
Boiler command
24
Boiler valve command
25
Relative humidity
26
Free cooling (On-Off valve) 0=Off 1=On
27
Variable speed compressor (0-10V)
28
Compressor 1 operating hours
29
Comp 1 starts
30
Compressor 2 operating hours
31
Comp 2 starts
32
Defrosting delay (SeTypeDFR = 0)
33
Defrosting count (SeTypeDFR = 0)
34
Ambient dew temperature
35
Mininet
36
Electric power absorbed
°C
°C
seconds
seconds
°C °C °C °C °C °C °C °C °C °C °C °C
0=Off 1=On 0=Off 1=On %
Bar Bar
% 0=Off 1=On 0=Off 1=On % 0=Off 1=On %
hour Number hour Number seconds seconds °C X=node discon-
nected O=Node connected
KW
ID DESCRIPTION U.M.
37
Water input temperature 2
38
Water output temperature 2
39
Condensing coil temperature C2
40
Ventilation (0-10V) C2
41
Condensing pressure C2
42
Evaporating pressure C2
43
Compressor 1 operating hours C2
44
Comp 1 starts C2
45
Compressor 2 operating hours C2
46
Comp 2 starts C2
47
Delay DFR C2 (SeTypeDFR = 0)
48
Count DFR C2 (SeTypeDFR = 0)
49
Return temperature
50
Discharge temperature
51
Condensing temperature
52
Operative SuperHeat
53
Thermostatic valve opening percentage
54
Actual set point in superheating
55
Not used
56
Not used
57
Not used
58
Not used
59
Not used
60
Not used
61
Not used
62
Not used
63
Not used
64
Not used
65
Not used
66
Not used
67
Not used
68
Not used
69
Not used
70
Not used
71
Not used
72
Operative SuperHeat C2
73
Return temperature C2
°C °C °C
%
Bar Bar hours Number hours Number seconds seconds °C °C °C °C
%
°C
°C °C
Depending on the configuration of the unit some status may not be used.
30
Page 31
7.7 ALARMS (page 1)
7 - CONTROL
Here is the complete list of alarms; according to the type of the unit and its configuration some codes indicated may not be used.
Before resetting an alarm identify and remove the cause that generate it. Repeated reset can cause irreversibile damages as malfunctioning of the system itself.
e 00 E 01 E 02 E 03 E 04 E 05 E 06 E 07 E 08 E 09 E 10 E 11 E 12 E 13 E 14 E 15 E 16 E 17 E 18 E 19 E 20
Base keypad Timeout Input temp. probe utility side Supply temp. probe utility side Outside temp. probe Coil/output temp. probe source Return temp. probe source side Temp. probe in accumulation AUX. heater temp. probe utility Pressure 1 probe (HP) Pressure 2 probe (LP_TE) Ext. RH% probe Water Reset input Demand Limit input Phase monitor Capacity reading Timeout Solar temperature / Source temperature circ. 2 High DHW temperature / Output temperature circ.2 utility Low DHW temperature / Utility input temperature 2 Discharge Temp. probe Return temperature probe Driver disconnection
A N A S A S A S A S A S A S A S A S A S A S A S
A S A/M S A/M S
A S
A S
A S
A S
A S
A S
E 21 Disconnection between the driver and the thermostatic motor A S E 22 No power supplì to the thermostatic driver A S E 23 Source fan thermal / Source pump thermal M S E 24 DHW pump thermal M S E 25 Source fan thermal of Circuit 2 / Source pump thermal Circuit 2 M S E 26 Compressor 1 thermal / Circuit 1 thermal M S E 27 Compressor 2 thermal / Circuit 2 thermal M S E 28 Utility pump 1 thermal M S E 29 Utility pump 2 thermal M S E 30 Utility water flow-rate A E 31 Pressure 1 probe of circuit 2 A S
A = AUTOMATIC reset M = MANUAL reset
S = it is memorie in the alarm log N = it is NOT memorie in the alarm log
31
Page 32
7.7 ALARMS (page 2)
7 - CONTROL
F 01 F 02
High pressure (HP) pag 33 Low pressure (LP)
A/M S A/M S
f 03 HP1 Prealarm A S f 04 LP1 Prealarm A S
f/F 05 HP2 Prealarm A/M S f/F 06 LP2 Prealarm A/M S f/F 07 Max pressure rateo A/M S f/F 08 f/F 09
F 10
Defrosting forcing for low pressure Defrosting stop alarm Max. discharge temperature alarm
A/M N/S A/M S
M S
f/F 11 HP1 prealarm Circuit 2 A/M S f/F 12 LP1 prealarm Circuit 2 A/M S f/F 13 HP2 prealarm Circuit 2 A/M S
f/F 14 LP2 prealarm Circuit 2 A/M S f/F 15 Max pressure rateo Circuit 2 A/M S
f/F 16 Defrosting forcing for low pressure circuit 2 A/M N/S f/F 17 Defrosting stop alarm utility 2 A/M S
F 18
High pressure Circuit 2 (HP) pag 33
A/M S
F 19 Low pressure Circuit 2 (LP) M S
I 01
Utility pump flow
A/M S
I 02 Source pump flow A S I 03 Utility freeze alarm M S I 04 Freeze alarm source side M S I 05 AUX heater antifreeze M S I 06 System charged with utility water A/M S I 07 Incongruent T Delta M S I 08 Thermal alarm on al the utility pumps M S i 09 Utility antifreeze prealarm A S i 10 Change of utility pump A N i 11 User input water temperature out of limit of the actual operating mode A S i 12 DHW Incongruent thermostat A N I 13 Ambient antifreeze alarm A S I 14 Not used I 15 Not used I 16 Source pump flow circuit 2 A S I 17 Accumulation frost alarm M S
A = AUTOMATIC reset M = MANUAL reset
S = it is memorie in the alarm log N = it is NOT memorie in the alarm log
32
Page 33
8 - MAINTENANCE
8.1 GENERAL
Maintenance must be done by authorized centres or by qualified personnel The maintenance enables:
maintain the unit efficiency Reduce the deterioration speed to whom every equipment
is subject over time
Assemble information and data to understand the state of
the unit efficiency and avoid possible damages
8.2 INSPECTIONS FREQUENCY
The inspections should be carried out at least every six months The frequency, however, depends on the use .
In the event of frequent use it is recommended to plan inspections at close intervals :
frequent use (continuous or very intermittent use, near the
operating limits, etc)
critical use (service necessary) .
8.3 MACHINE BOOKLET
It’s advisable to create a machine booklet to take notes of the
unit interventions. In this way will be easier marker the various interventions and will be e facilitate any troubleshooting.
Report on the booklet :
data type of intervention effected intervention description Carried out measures etc ..
8.4 PUT A REST
If a long period of inactivity is foreseen
Turn of the power in order to avoid electrical risks or
damages by lightning strike
avoid the risk of frosts (empty or add glycol in the plant
sections subjected to temperatures below zero , power antifreeze resistances if are present )
It’s recommended that the starter after the period of detention
is made by a qualified technician, especially after seasonal stops or seasonal switch. When restarting, refer to the START-UP section . Schedule technical assistance in advance to avoid hitches and be able to use the installation when necessary.
8.6 WATER EXCHANGER
It is very important for the exchanger to be able to provide the maximum thermal exchange. Therefore, it is essential for the inner surfaces to be clean of dirt and incrustations. Periodically check the difference between the temperature of the supply water and the condensation temperature. If the difference is greater than 8 °C – 10 ° C it is advisable to clean the exchanger. The clearing must be effected :
With circulation opposite to the usual one With a speed at least 1,5 times higher than the nominal one With an appropriate product moderately acid (95% water +
5% phosphoric acid
After the cleaning rince with water to inhibe the detergent
rests.
8.7 ELECTRIC FANS
Check :
the fans and the relative protection gridsare well fixed The fan bearings (evident by noise and anomalous
vibrations )
the terminal protection covers are closed and the cable
holders are properly positioned
8.8 AIR COIL
Contact with the exchanger fins can cause cuts. Wear protective gloves to perform the above described operations. It is extremely important that the battery gives the maximum thermal exchange; therefore, its surface must be cleaned from dust and deposits. Remove all impurities from the surface. It is extremely important that the battery gives the maximum thermal exchange; therefore, its surface must be cleaned from dust and deposits. Remove all impurities from the surface. Using an air pressure gun, clean the aluminum surface of the battery. Be careful to direct the air in the opposite direction of the fan air movement. Hold the gun parallel to the fins to avoid damages. As an alternative, an aspirator can be used to suck impurities from the air input side. Verify that the aluminum fins are not bent or damaged. In the event of damages, contact the authorized assistance center
and get the battery “ironed out” in order to restore the initial
condition for an optimal air flow
8.9 CIRCULATION PUMPS
8.5 WATER FILTER
Verify that there are no impurities which hinder the smooth passage of water.
Verify :
no leaks Bearing status (anomalies are highlighted by abnormal
noise and vibration)
The closing of the terminals cover and the correct
positioning of the cable glands.
33
Page 34
8 - MAINTENANCE
8.9 PERIODICAL CHECK LIST
Controls effected on ……………………………..B y ………………………………………………. Of the Company…………………..……………………………….
Presence of corrosions
Panel fixing
Fan fixing
Coil cleaning
Water filter cleaning
Check the exchanger efficiency
Circulating pumps
Check of the fixing and the insulation of the power lead
Check of the earthing cable
Electric panel cleaning
Capacity contactor status
terminal closing, cable insulation integrity
Voltage and phase unbalancing (no load and on-load)
Absorptions of the single electrical loads
Test of the compressor carter resistances
Leak control *
Survey of the refrigerant circuit operating parameters
Check of the 4-way change
Protective device test : safety valves, pressure switches, thermostats, flow switches etc
Control system test: setpoint, climatic compensations, capacity stepping, water / air flow-rate variations etc
Control device test : alarm signalling, thermometers, probes, pressure gauges etc
Frequency of intervention (months)
1 6 12
Notes / interventions recommended to the owner
*European regulation 303/2008
Refer to the local actuation regulations; in short and just as an indication the regulation order as follow. Companies and technicians that effect interventions of installation, maintenance/repairs, leak control and recovery must be CERTIFIED as expected by the local regulations. The leak control must be effected with annual renewal.
34
Page 35
9 - DECOMMISSIONING
HIGH PRESSURE ALARM MANUAL RESET
9 - DECOMMISSIONING
9.1 DISCONNECTING
Only authorised personnel must disconnect the unit.
Avoid leak or spills into the environment . Before disconnecting the unit, the following must be
recovered, if present:
- refrigerant gas
- Anti-freeze solutions in the hydraulic circuit
Awaiting dismantling and disposal, the unit can also be
stored outdoors, as bad weather and rapid changes in temperature will not cause damage to the environment, if electric, cooling and hydraulic circuits of the unit are integral and closed.
9.3 CE RAEE CE DIRECTIVE
The units covered by the legislation in question are marked with the symbol on the side. With the aim of protecting the environment, all of our units are produced in compliance with Directive EC on waste electrical and electronic equipment (WEEE). The potential effects on the environment and on human health due to the presence of hazardous substances are shown in the use and maintenance manual in the section on residual risks. Information in addition to that indicated below, if required, can be obtained from the manufacturer/distributor/importer, who are responsible for the collection/handling of waste originating from equipment covered by EC - WEEE. This information is also available from the retailer who sold this appliance or from the local authorities who handle waste. Directive EC - WEEE requires disposal and recycling of electrical and electronic equipment as described therein to be handled through appropriate collection, in suitable centres, separate from collection for the disposal of mixed urban waste. The user must not dispose of the unit at the end of its life cycle as urban waste. It must instead be handed over to appropriate collection centres as set forth by current standards or as instructed by the distributor. If disposal takes places at the same time as delivery of a new electrical or electronic equipment for the same family, the product may be collected directly by the distributor.
9.2 DISMANTLING AND DISPOSAL
THE UNIT MUST ALWAYS BE SENT TO AUTHORISED CENTRES FOR DISMANTLING AND DISPOSAL.
When dismantling the unit, the fan, the motor and the coil, if operating, may be recovered by the specialist centres for reuse.
All the materials must be recovered or disposed of in compliance with the corresponding national standards in force.
For further information on the decommissioning of the unit, contact the manufacturer.
35
Page 36
DIMENSIONALES AND WEIGHT DISTRIBUTION: WBAN 82-122
36
Page 37
DIMENSIONALS AND WEIGHT DISTRIBUTION: WBAN 162-202
37
Page 38
DIMENSIONALS AND WEIGHT DISTRIBUTION: WBAN 262-302
38
Page 39
39
Page 40
40
Page 41
41
Page 42
42
Page 43
43
Page 44
11 - RESIDUAL RISKS
General In this section the most common situations are signalled. As these
cannot be controlled by the manufacturer these could be a source of risk situations for people or things
Danger zone This is an area in which only an authorised operator may work. The danger zone is the area inside the unit which is accessible only with
the deliberate removal of protections or parts thereof Handling The handling operations, if implemented without all of the protection
necesssary and without due caution, may cause the fall or the tipping of the unit with the consequent damage, even serious, to persons, things or the unit itself.
Handle the unit following the instructions provided in the present manual regarding the packaging and in compliance with the local regulations in force.
Should the gas refrigerant leak please refer to the refrigerant "Safety sheet".
Installation An incorrect installation of the unit could cause water leaks, condensate
accumulation, leaking of the refrigerant, electric shock, bad functioning or damage to the unit itself.
Check that the installation has been implemented by qualified technical personnel only and that the instructions contained in the present manual and the local regulations in force have been adhered to.
The installation of the unit in a place where even infrequent leaks of inflammable gas and the accumulation of this gas in the area surrounding the area occur could cause explosions or fires.
Carefully check the positioning of the unit. The installation of the unit in a place unsuited to support its weight and/
or guarantee adequate anchorage may cause the fall or the tipping of the unit with the consequent damage to things, people or the unit itself.
Carefully check the positioning and the anchoring of the unit. Easy access to the unit by children, unauthorised persons or animals
may be the source of accidents, some serious. Install the unit in areas which are only accessible to authorised person
and/or provide protection against intrusion into the danger zone . General risks Smell of burning, smoke or other signals of serious anomalies may
indicate a situation which could cause damage to people, things or the unit itself.
Electrically isolate the unit (yellow-red isolator). Contact the authorised service centre to identify and resolve the problem
at the source of the anomaly. Accidental contact with exchange batteries, compressors, air delivery
tubes or other components may cause injuries and/or burns. Always wear suitable clothing including protective gloves to work inside
the danger zone. Maintenance and repair operations carried out by non-qualified
personnel may cause damge to persons, things or the unit itself. Always contact the qualified assistance centre. Failing to close the unit panels or failure to check the correct tightening
of all of the panelling fixing screws may cause damage to persons, things or the unit itself.
Periodically check that all of the panels are correctly closed and fixed. If there is a fire the temperature of the refrigerant could reach values that
increase the pressure to beyond the safety valve with the consequent possible projection of the refrigerant itself or explosion of the circuit parts that remain isolated by the closure of the tap.
Do not remain in the vicinity of the safety valve and never leave the refrigerating system taps closed.
Electric parts An incomplete attachment line to the electric network or with incorrectly
sized cables and/or unsuitable protective devices can cause electric shocks, intoxication, damage to the unit or fires.
Carry out all of the work on the electric system referring to the electric layout and the present manual ensuring the use of a system thereto dedicated.
An incorrect fixing of the electric components cover may favour the entry of dust, water etc inside and may consequently can electric shocks, damage to the unit or fires.
Always fix the unit cover properly. When the metallic mass of the unit is under voltage and is not correctly
connected to the earthing system it may be as source of electric shock and electrocution.
Always pay particular attention to the implementation of the earthing system connections.
Contact with parts under voltage accessible inside the unit after the removal of the guards can cause electric shocks, burns and electrocution.
Open and padlock the general isolator prior to removing the guards and signal work in progress with the appropriate shield.
Contact with parts that could be under voltage due to the start up of the unit may cause electric shocks, burns and electrocution.
When voltage is necessary for the circuit open the isolator on the attachment line of the unit itself, padlock it and display the appropriate warning shield.
Moving parts Contact with the transmissions or with the fan aspiration can cause
injuries. Prior to entering the inside of the unit open the isolater situated on the
connection line of the unit itself, padlock and display the suitable sign. Contact with the fans can cause incurie. Prior to removing the protective grill or the fans, open the display the appropriate warning sign. Refrigerant The intervention of the safety valve and the consequent expulsion of the
gas refrigerant may cause injuries and intoxication. Always wear suitable clothing including protective gloves and eyeglasses for operations inside the danger zone.
Should the gas refrigerant leak please refer to the refrigerant "Safety sheet".
Contact between open flames or heat sources with the refrigerant or the heating of the gas circuit under pressure (e.g. during welding operations) may cause explosions or fires.
Do not place any heat source inside the danger zone. The maintenance or repair interventions which include welding must be
carried out with the system off. Hydraulic parts Defects in tubing, the attachments or the cut-off parts may cause a leak
or water projection with the consequent damages to peopl, things or shortcircuit the unit
44
Page 45
Page 46
Page 47
Page 48
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy Tel. + 39 0439 3131 - Fax + 39 0439 313300 - info@clivet.it
CLIVET UK LTD 4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom
Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - info@clivet-uk.co.uk CLIVET AIRCON LTD (Service and Maintenance Division)
Units F5&F6 Railway Triangle Ind Est, Walton Road - Portsmouth, Hampshire - PO6 1TG - United Kingdom Tel. + 44 (0) 2392 381235 - Fax + 44 (0) 2392 381243 - info@clivetaircon.co.uk
CLIVET ESPAÑA COMERCIAL S.L. (Sales)
Calle Gurb, 17 1° 1a - 08500 Vic, Barcelona - España Tel. + 34 93 8606248 - Fax + 34 93 8855392 - info@clivetcomercial.com
CLIVET ESPAÑA S.A.U.(Service and Maintenance Division)
Calle Real de Burgos N° 12 - 28860, Paracuellos del Jarama, Madrid - España Tel. + 34 91 6658280 - Fax + 34 91 6657806 - info@clivet.es
CLIVET GmbH
Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - info.de@clivet.com
CLIVET NEDERLAND B.V.
Siliciumweg 20a, 3812 SX Amersfoort - Netherlands Tel. + 31 (0) 33 7503420 - Fax + 31 (0) 33 7503424 - info@clivet.nl
CLIVET RUSSIA
Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia Tel. + 74956462009 - Fax + 74956462009 - info.ru@clivet.com
CLIVET MIDEAST FZCO
Dubai Silicon Oasis (DSO), High Bay Complex, Ind Unit No. 3, PO BOX 28178 - Dubai, UAE Tel. + 9714 3208499 - Fax + 9714 3208216 - info@clivet.ae
CLIVET AIRCONDITIONING SYSTEMS PRIVATE LIMITED
4BA, Gundecha Onclave - Kherani Road, Saki Naka, Andheri (East) - Mumbai 400 072 - India
Tel. + 91 22 6193 7000 - Fax + 91 22 6193 7001 - info.in@clivet.com
All reproduction, even partial, is prohibited. © Copyright - CLIVET S.p.A. - Feltre (BL) - Italy
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice.
www.clivet.com
Loading...