Air-water ductable liquid chiller for indoor installation
Installation and
operating manual
M02S40N16-0014-11-16
Page 2
Dear Customer,
We congratulate you on choosing this product
For many years Clivet has been oering systems that provide maximum comfort, together with high
reliability, eciency, quality and safety.
The aim of the company is to oer advanced systems, that assure the best comfort, reduce energy
consumption and the installation and maintenance cost for the life cycle of the system.
The purpose of this manual is to provide you with information that is useful from reception of
the equipment, through installation, operational usage and nally disposal so that this advanced
system oers the beat solution.
Yours faithfully.
CLIVET Spa
The data contained in this manual is not binding and may be changed by the manufacturer without
prior notice.
The manual provides correct unit installation, use and maintenance.
Pay particular attention to:
Warning, identies particularly important operations or information.
Prohibited operations that must not be carried out, that compromise the operating of the unit or may cause damage to persons or things.
It is advisable to read it carefully so you will save time during operations.
•
Follow the written indications so you will not cause damages to things and injuries people.
•
1.2 Preliminaries
Only qualied personnel can operate on the unit, as required by the regulation in force.
1.3 Risk situations
The unit has been designed and created to prevent injures to people.
During designing it is not possible to plane and operate on all risk situation.
Read carefully “Residual risk” section where all situation which may cause damages to things and injuries to people are reported.
Installation, starting, maintenance and repair required specic knowledge; if they are carried out by inexperienced personnel, they may cause
damages to things and injuries people.
1.4 Intended use
Use the unit only:
for cooling/heating water or a water and glycol mix for air-conditioning only
•
keep to the limits foreseen in the technical schedule and in this manual
•
The manufacturer accepts no responsibility if the equipment is used for any purpose other than the intended use.
1.5 Installation
Indoor installation
The positioning, hydraulic system, refrigerating, electrics and the ducting of the air must be determined by the system designer in accordance
with local regulations in force.
Follow local safety regulations.
Verify that the electrical line characteristics are in compliance with data quotes on the unit serial number label.
1.6 Maintenance
Plan periodic inspection and maintenance in order to avoid or reduce repairing costs.
Turn the unit o before any operation.
1.7 Modication
All unit modications will end the warranty coverage and the manufacturer responsibility.
1.8 Breakdown/Malfuction
Disable the unit immediately in case of breakdown or malfunction.
Contact a certied service agent.
Use original spares parts only.
Using the unit in case of breakdown or malfunction:
voids the warranty
•
it may compromise the safety of the unit
•
may increase time and repair costs
•
4 WSA-XEE 122-402
M02S40N16-00
Page 5
1.9 User training
The installer has to train the user on:
Start-up/shutdown
•
Set points change
•
Standby mode
•
Maintenance
•
What to do / what not to do in case of breakdown
•
1.10 Data update
Continual product improvements may imply manual data changes.
Visit manufacturer web site for updated data.
1.11 Indications for the User
Keep this manual with the wiring diagram in an accessible place for the operator.
Note the unit data label so you can provide them to the assistance centre in case of intervention (see “Unit identication” section).
Provide a unit notebook that allows any interventions carried out on the unit to be noted and tracked making it easier to suitably note the
various interventions and aids the search for any breakdowns.
In case of breakdown or malfunction:
Immediately deactivate the unit
•
Contact a service centre authorized by the manufacturer
•
The installer must train the user, particularly on:
Start-up/shutdown
•
Set points change
•
Standby mode
•
Maintenance
•
What to do / what not to do in case of breakdown
•
1.12 Unit indentication
The serial number label is positioned on the unit and allows to indentify all the unit features.
The matriculation plate must never be removed.
The matriculation plate shows the indications foreseen by the standards, in particular:
unit type
•
serial number (12 characters)
•
year of manufacture
•
wiring diagram number
•
electrical data
•
manufacturer logo and address
•
1.13 Serial number
It identies uniquely each unit.
Must be quoted when ordering spare parts.
1.14 Assistance request
Note data from the serial number label and write them in the chart on side, so you will nd them easily when needed.
Series
Size
Serial number
Year of manufacture
Electrical wiringdiagram
M02S40N16-00 WSA-XEE 122-402 5
Page 6
2 Reception
You have to check before accepting the delivery:
That the unit hasn’t been damaged during transport
•
That the materials delivered correspond with that indicated on the transport document comparing the data with the identication label
•
positioned on the packaging.
In case of damage or anomaly:
Write down on the transport document the damage you found and quote this sentence: “Conditional acceptance clear evidence of
•
deciencies/damages during transport”
Contact by fax and registered mail with advice of receipt to supplier and the carrier.
•
Any disputes must be made within 8 days from the date of the delivery. Complaints after this period are invalid.
2.1 Storage
Observe external packaging instructions.
2.2 Handling
Verify unit weight and handling equipment lifting capacity.
•
Identify critical points during handling (disconnected routes, ights, steps, doors).
•
Suitably protect the unit to prevent damage.
•
Align the barycenter to the lifting point
•
Use all the lifting brackets (see the dimensional section)
•
Gradually bring the lifting belts under tension, making sure they are positioned correctly.
•
Before starting the handling, make sure that the unit is stable.
•
ASupports for handling: remove after the handling.
BProtections
CAdditional lifting brackets
6 WSA-XEE 122-402
M02S40N16-00
Page 7
2.3 Packaging removing
Be careful not to damage the unit.
Keep packing material out of children’s reach it may be dangerous.
Recycle and dispose of the packaging material in conformity with local regulations.
M02S40N16-00 WSA-XEE 122-402 7
Page 8
2.4 Removable fan section for shipping
8 WSA-XEE 122-402
M02S40N16-00
Page 9
3 Positioning
During positioning consider these elements:
Technical spaces requested by the unit
•
Electrical connections
•
Water connections
•
Spaces for air exhaust and intake
•
3.1 Functional spaces
Functional spaces are designed to:
guarantee good unit operation
•
carry out maintenance operations
•
protect authorized operators and exposed people
•
Respect all functional spaces indicated in the DIMENSIONS section.
Double all functional spaces if two or more unit are aligned.
3.2 Positioning
Units are designed to be installed:
INTERNAL
•
in xed positions
•
Limit vibration transmission:
use antivibration devices on unit bearing points
•
install exible joints on the hydraulic connections
•
Choose the installation place according to the following criteria:
Customer approval
•
safe accessible position
•
technical spaces requested by the unit
•
spaces for the air intake/exhaust
•
max. distance allowed by the electrical connections
•
Avoid installations in places subject to ooding
•
verify unit weight and bearing point capacity
•
verify that all bearing points are aligned and leveled
•
install the unit raised from the ground
•
A correct circulation of the air is mandatory to guarantee the good unit operating.
Avoid therefore:
obstacles to the airow
•
diculty of exchange
•
leaves or other foreign bodies that can obstruct the air coil
•
winds that hinder or favour the airow
•
heat or pollution sources close to the unit (chimneys, extractors etc..)
•
stratication (cold air that stagnates at the bottom)
•
recirculation (expelled air that is sucked in again)
•
Ignoring the previous indications could:
reduce energy eciency
•
alarm lockout due to HIGH PRESSURE (in summer) or LOW PRESSURE (in winter)
•
3.3 Saftey valve gas side
The installer is responsible for evaluating the opportunity of installing drain tubes, in conformity with the local regulations in force (EN 378).
3.4 Fresh air probe
For details see:
p.
M02S40N16-00 WSA-XEE 122-402 9
Page 10
3.5 Air channelling
When designing and manufacturing the ducting, consider LOAD LOSSES, AIR FLOW AND SPEED that must be consistent with the unit features.
Limit the load losses by optimising the path, the type and number of bends and junctions.
Consider that excessive external static pressure will lead to a reduction in ow rate, with consequent alarm lockout.
Ensure ducts are thermally insulated.
The weight of the ducting must not burden the connection anges.
Place anti-vibration joints between channels and unit.
Connection to the anges and between the various sections of the channels must guarantee air seal, avoiding dispersions penalising the
overall eciency of the system.
Vertical outlet standard (1)
Rear outlet option (2)
Provide:
water discharge (3-A)
•
grilles to restrict access to small animals (3-B)
•
deectors (3-C) to avoid the by-pass between the two air ows
•
safety grille (4-D)
•
Avoid therefore:
angle curves and narrowings (5)
•
direct air ow on people (6-7), windows, doors, plants, obstacles in general
•
obstacles that prevents the air inow to the coil (8-9)
•
installations next to silent rooms
•
10 WSA-XEE 122-402
M02S40N16-00
Page 11
4 Water connections
4.1 Water quality
Water features
conrming to local regulations
•
total hardness < 14°fr
•
within the limits indicated by table
•
The water quality must be checked by qualied personnel.
Water with inadequate characteristics can cause:
pressure drop increase
•
reduces energy eciency
•
increased corrosion potential
•
Acceptable water quality values:
PH7,5 ÷9,0
2-
SO
4
-
HCO
Total Hardness
Cl
PO
NH3< 0,5
2-
/SO
3
4
-
3-
4
< 100
> 1
4,5 ÷8,5
< 50
< 2,0
ppm
dH
ppm
ppm
ppm
Free Chlorine< 0,5
+
Fe
3
++
Mn
CO
2
H2S
Temperature
Oxygen content< 0,1
< 0,5
< 0,05
< 50
< 50
< 65
ppm
ppm
ppm
ppm
ppb
°C
ppm
Provide a water treatment system if values fall outside the limits.
The warranty does not cover damages caused by limestone formations, deposits and impurities from the water supply and / or failure from
failed system clearing to clean system.
4.2 Risk of freezing
If the unit or the relative water connections are subject to temperatures close to 0°C:
mix water with glycol, or
•
safeguard the pipes with heating cables placed under the insulation, or
•
empty the system in cases of long non-use
•
4.3 Anti-freeze solution
The use of an anti-freeze solution results in an increase in pressure drop.
Make sure that the glycol type utilized is inhibited (not corrosive) and compatible with the water circuit components.
Do not use dierent glicol mixture (i.e. ethylene with propylene).
4.4 Water ow-rate
The project water-ow must be:
inside the exchanger operating limits (see the TECHNICAL INFORMATION section)
•
guarantee, also with variable system conditions (for example in systems where some circuits are bypassed in particular situations).
•
M02S40N16-00 WSA-XEE 122-402 11
Page 12
4.5 Operation sequence
Close all vent valves in the high points of the unit hydraulic circuit
Close all drain valves in the low points of the unit hydraulic circuit:
Heat exchangers
•
Pumps
•
collectors
•
storage tank
•
free-cooling coil
•
1. Carefully wash the system with clean water: ll and drain the system several times.
2. Apply additives to prevent corrosion, fouling, formation of mud and algae.
3. Fill the plant
4. Execute leakage test.
5. Isolate the pipes to avoid heat dispersions and formation of condensate.
6. Leave various point of service free (wells, vent-holes etc).
Neglecting the washing will lead to several lter cleaning interventions and at worst cases can cause damages to the exchangers and the
other parts.
take away the supplied connection union by acting on the connection joint
•
weld the union to the installation pipe
•
perform the connection between the installation pipe and the evaporator, using the joint
•
Retirer le joint de connexion avant de souder le tuyau de l’installation.
The rubber gasket might be irreparably damaged.
4.8 Water lter
Use lter with mesh pitch of 1,6 mm
It must be installed immediately in the water input of the unit, in a position that is easily accessible for cleaning.
The lter never should be removed, this operation invalidates the guaranty.
12 WSA-XEE 122-402
M02S40N16-00
Page 13
4.9 Flow Switch
The ow switch must be present to ensure shutdown of the unit if water is not circulating.
It has to be installed in a duct rectilinear part, not in proximity of curves that cause turbulences.
A. minimum distance
4.10 Partial energy recovery
For details see:
9.1 Partial energy recoveryp.42
4.11 Single pump
For details see:
p.3
4.12 Couple of manually operated shut-o valves
For details see:
9.3 CSVX - Couple of manually opeated shut-o valvesp.43
M02S40N16-00 WSA-XEE 122-402 13
Page 14
5 Electrical connections
The characteristics of the electrical lines must be determined by qualied electrica personnel able to design electrical installations; moreover,
the lines must be in conformity with regulations in force.
The protection devices of the unit power line must be able to stop all short circuit current, the value must be determined in accordance with
system features.
The power cables and the protection cable section must be dened in accordance with the characteristics of the protections adopted.
All electrical operations should be performed by trained personnel having the necessary qualications required by the regulations in force
and being informed about the risks relevant to these activities.
Operate in compliance with safety regulations in force.
5.1 Electrical data
The serial number label reports the unit specic electrical data, included any electrical accessories.
The electrical data indicated in the technical bulletin and in the manual refer to the standard unit, accessories excluded.
The matriculation plate shows the indications foreseen by the standards, in particular:
Voltage
•
F.L.A.: full load ampere, absorbed current at maximum admitted conditions
•
F.L.I.: full load input, full load power input at max. admissible condition
•
Electrical wiringdiagram Nr.
•
5.2 Connections
1. Refer to the unit electrical diagram (the number of the diagram is shown on the serial number label).
2. Verify that the electrical supply has characteristics conforming to the data shown on the serial number label.
3. Before starting work, ensure the unit is isolated, unable to be turned on and a safety sign used.
4. Ensure correct earth connection.
5. Ensure cables are suitably protected.
6. Before powering up the unit, make sure that all the protections that were removed during the electrical connection work have been
restored.
5.3 Signals / data lines
Do not exceed the maximum power allowed, which varies, according to the type of signal.
Lay the cables far from power cables or cables having a dierent tension and that are able to emit electromagnetic disturbances.
Do not lay the cable near devices which can generate electromagnetic interferences.
Do not lay the cables parallel to other cables, cable crossings are possible, only if laid at 90°.
Connect the screen to the ground, only if there aren’t disturbances.
Guarantee the continuity of the screen during the entire extension of the cable.
Respect impendency, capacity and attenuation indications.
5.4 Power input
Fix the cables: if vacated may be subject to tearing.
The cable must not touch the compressor and the refrigerant piping (they reach high temparatures).
QS1: main isolator switch
XC: Customer connections
5.5 Remote ON-OFF
Do not perform short On O cycles
Do not use the remote On O with thermoregulation function.
YESNO !
A
B
A
A B
A
B
B
14 WSA-XEE 122-402
M02S40N16-00
Page 15
5.6 Connections performer by customer
':*Q6
M02S40N16-00 WSA-XEE 122-402 15
Page 16
5.7 Computer connection
1. Service keypad
2. RJ45: standard connection
3. P.C.-not supplied
4. P.C. connection, shift RJ45 from T-HI to T-IP
Congure P.C.
1. connect P.C. and main module with LAN cable
2. check in the taskbar that the connection is active
3. open Control Panel and select Network and sharing center
4. select Modify board setting
5. select Local area connection (LAN)
6. select Internet protocol version 4 (TPC) IPV4 and enter Property
7. set the IP address 192.168.1.100
8. set Subnet mask as 255.255.255.0
9. conrm (OK)
10. enter Start (Windows button)
11. write the command cmd and enter/do it
12. write and run the command Ping 192.168.1.42
13. the message, connection is OK, will appear when successful
14. enter the browser (Crhome, Firefox ecc)
15. write and run the command http:/192.168.1.42
16. Userid = WEB
17. Password = SBTAdmin!
16 WSA-XEE 122-402
M02S40N16-00
Page 17
5.8 Remote control
1Distance up to 350 mtAUser interface
2Distance up to 700 mtB = B1KNX bus, max 350 mt
CPSX - Mains power supply unit
C1AC 120...230V, 50...60Hz
DKNX bus, max 350 mt
twisted pair with shield, ø 0,8 mm
EIB/KNX cable marking recommende
pwer supply unit N125/11 5WG1 125-1AB11
5.9 PSX - Mains power supply unit
pwer supply unit N125/11 5WG1 125-1AB11
M02S40N16-00 WSA-XEE 122-402 17
Page 18
5.10 Modbus - RS485
LED BSPcommunication with AP1 moduleLED BUScommunication with Modbus
greencommunication okgreencommunication ok
yellowsoftware ok but communication with AP1
redashing: software errorredcommunication down
Path
Main menu
down
xed: hardware error
Unit ParametersModbus
yellowstartup / channel not communicating
ParametersShort descriptionDescription
P0445:T1 bus terminationTermination resistor activation on T1 POL902 [0] port = Passive [1] = Active
P0446:T2 bus terminationTermination resistor activation on T2 POL902 [0] port = Passive [1] = Active
A. Unit
B. Metal conduit
C. Metal septums
D. Metal-lined sheath (sleeve)
Modbus / LonWorks / Cable requirements
Couple of conductors twisted and shielded
Section of conductor 0,22mm2…0,35mm2
Rated power between conductors < 50 pF/m
Nominal impedance 120 Ω
Recommended cable BELDEN 3106A
Every RS485 serial line must be set up using the ‘In/Out’ bus system.
•
Other types of networks are not allowed, such as Star or Ring networks.
•
The dierence in potential between the earth of the two RS485 devices that the cable shielding needs to be connected to must be lower
•
than 7 V
There must be suitable arresters to protect the serial lines from the eects of atmospheric discharges
•
A 120 ohm resistance must be located on the end of the serial line. Alternatively, when the last serial board is equipped with an internal
•
terminator, it must be enabled using the specic jumper, dip switch or link.
The cable must have insulation features and non-ame propagation in accordance with applicable regulations.
•
The RS485 serial line must be kept as far away as possible from sources of electromagnetic interference.
•
18 WSA-XEE 122-402
M02S40N16-00
Page 19
5.11 LonWorks
LED BSPcommunication with AP1 moduleLED BUScommunication with LonWorks
greencommunication okgreenready for communication
yellowsoftware ok but communication with AP1
down
redashing: software errorredashing: communicating not possible
xed: hardware errorcommunication down
yellowstartup
5.12 BACnet IP
LED BSPcommunication with AP1 moduleLED BUScommunication with BACnet
greencommunication okgreenready for communication
yellowsoftware ok but communication with AP1
down
redashing: software errorredBACnet server down
xed: hardware errorrestart after 3 sec
yellowstartup
M02S40N16-00 WSA-XEE 122-402 19
Page 20
6 Start-up
6.1 General description
The indicated operations should be done by qualied technician with specic training on the product.
Upon request, the service centres performing the start-up.
The electrical, water connections and the other system works are by the installer.
Agree upon in advance the star-up data with the service centre.
Before checking, please verify the following:
the unit should be installed properly and in conformity with this manual
•
the electrical power supply line should be isolated at the beginning
•
the unit isolator is open, locked and equipped with the suitable warning
•
make sure no tension is present
•
After turning o the power, wait at least 5 minutes before accessing to the electrical panel or any other electrical component.
Before accessing check with a multimeter that there are no residual stresses.
6.2 Preliminary checks
For details refer to the dierent manual sections.
Unit OFF power supply
1. safety access
2. functional spaces
3. air ow: correct return and supply (no bypass, no stratication)
4. structure integrity
5. fans run freely
6. unit on vibration isolators
7. unit input water lter + shut-o valves for cleaning
8. vibration isolators on water connections
9. expansion tank (indicative volume = 5% system content)
10. Close all drain valves in the low points of the unit hydraulic circuit:
11. cleaned system
12. loaded system + possible glycol solution + corrosion inhibitor
13. system under pressure
14. vented system
15. fresh air probe
16. refrigerant circuit visual check
17. earthing connection
18. power supply features
19. electrical connections provided by the customer
6.3 Start-up sequence
For details refer to the dierent manual sections.
Unit ON power supply
1. compressor crankcase heaters operating at least since 8 hours
2. o-load voltage measure
3. phase sequence check
4. pump manual start-up and ow check
5. shut-o valve refrigerant circuit open
6. unit ON
7. load voltage measure and absorptions
8. liquid sight glass check (no bubbles)
9. check all fan operating
10. measure return and supply water temperature
11. measure super-heating and sub-cooling
12. check no anomalous vibrations are present
13. climatic curve personalization
14. climatic curve personalization
15. scheduling personalization
16. complete and available unit documentation
20 WSA-XEE 122-402
M02S40N16-00
Page 21
6.4 Refrigeration circuit
1. Check carefully the refrigerating circuit: the presence of oil stains can mean leakage caused by transportation, movements or other).
2. Verify that the refrigerating circuit is in pressure: Using the unit manometers, if present, or service manometers.
3. Make sure that all the service outlets are closed with proper caps; if caps are not present a leak of refrigerant can be possible.
4. Open the valves of the refrigerant circuit, if there are any.
6.5 Water circuit
1. Before realizing the unit connection make sure that the hydraulic system has been cleaned up and the cleaning water has been drained.
2. Check that the water circuit has been lled and pressurized.
3. Check that the shut-o valves in the circuit are in the “OPEN” position.
4. Check that there isn’t air in the circuit, if required, evacuate it using the air bleed valve placed in the system high points.
5. When using antifreeze solutions, make sure the glycol percentage is suitable for the type of use envisaged.
Neglecting the washing will lead to several lter cleaning interventions and at worst cases can cause damages to the exchangers and the
other parts.
Weight of glycol (%)10203040
Freezing temperature (°C)-3.9-8.9-15.6-23.4
Safety temperature (°C)-1-4-10-19
6.6 Electric Circuit
Verify that the unit is connected to the ground plant.
Check the conductors are tightened as: the vibrations caused by handling and transport might cause these to come loose.
Connect the unit by closing the sectioning device, but leave it on OFF.
Check the voltage and line frequency values which must be within the limits: 400/3/50 +/- 10%
Check and adjust the phase balance as necessary: it must be lower than 2%
Example
Working outside of these limits can cause irreversible damages and voids the warranty.
6.7 Compressor crankcase heaters
Connect the oil resistances on the compressor crankcase at least 8 hours before the compressor is to be starter:
at the rst unit start-up
•
after each prolonged period of inactivity
•
1. Supply the resistances switching o the unit isolator switch.
2. To make sure that heaters are working, check the power input.
3. At start-up the compressor crank-case temperature on the lower side must be higher at least of 10°C than the outside temperature.
Do not start the compressor with the crankcase oil below operating temperature.
6.8 Voltages
Check that the air and water temperatures are within in the operating limits.
Start-up the unit.
With unit operating in stable conditions, check:
Voltage
•
Total absorption of the unit
•
Absorption of the single electric loads
•
M02S40N16-00 WSA-XEE 122-402 21
Page 22
6.9 Remote controls
Check that the remote controls (ON-OFF etc) are connected and, if necessary, enabled with the respective parameters as indicated in the
“electrical connections” section.
Check that probes and optional components are connected and enabled with the respective parameters (“electrical connections” section and
following pages).
6.10 Demand limit
Menu accessible only after having entered the password.
Access reserved only to specically trained personnel.
The parameter modication can cause irreversible damages.
It is possible to limit the absorbed electric power with an external signal 0-10 Vcc or 4-20mA.
The higher the signal is, the lower the number of compressors available to meet the thermal need.
Only if P0050:En DemandLimit ≠ 0
Path: Main Menu / Unit parameters / Demand limit
Step DisplayActionMenu/VariableKeysNotes
1Press 3 sec.
2PasswordSetPassword
3Press
4Main menuSelectUnit parameters
5Unit parametersSelectSet Point
6Set PointSelectDemand limit
7SetDemand limit
8Conrm
9Press 3 sec.
10SelectLocal connections
Path: Main Menu / Unit parameters / Demand limit
ParametersShort descriptionDescription
P0009:set demand limitParameter setting of the value % of demand limit
P0062TypeDLInlet signal type: 0=0-10V; 1=4-20mA
22 WSA-XEE 122-402
M02S40N16-00
Page 23
6.11 Climatic TExt
Menu accessible only after having entered the password.
Access reserved only to specically trained personnel.
The parameter modication can cause irreversible damages.
The setpoint dened by the temperature curve is shown at status S0010: ActualSptTExt
Only if P0053: En Climatica ≠ 0
Path: Main Menu / Unit parameters / Climatica TExt
Example
Step DisplayActionMenu/VariableKeysNotes
1Press 3 sec.
2PasswordSetPassword
3Press
4Main menuSelectUnit parameters
5Unit parametersSelectClimatic TExt
6Climatic TExt (pwd)SelectParameter
7Set
8Conrm
9Press 3 sec.
10SelectLocal connections
Path: Main Menu / Unit parameters / Climatica TExt
ParametersShort descriptionDescription
P0265:CSptLowsetpoint temperature value when the air temperature value is AirAtSptLowC
P0266:AirAtSptLowCexternal air temperature value where the calculated setpoint takes on the value given by SptLowC
P0267:CSptHighsetpoint temperature value when the air temperature value is AirAtSptHigC
P0268:AirAtSptHigCexternal air temperature value where the calculated setpoint takes on the value given by SptHigC
M02S40N16-00 WSA-XEE 122-402 23
Page 24
6.12 Water reset
Menu accessible only after having entered the password.
Access reserved only to specically trained personnel.
The parameter modication can cause irreversible damages.
It is possible to limit the absorbed electric power with an external signal 0-10 Vcc or 4-20mA.
The water reset correction aects the setpoint dened by the Climate curve TExt (actual setpoint).
The setpoint is shown at status S0011: ActualSptWR
Only if P0051: En WaterReset ≠ 0
Path: Main Menu / Unit parameters / Water reset
Step DisplayActionMenu/VariableKeysNotes
1Press 3 sec.
2PasswordSetPassword
3Press
4Main menuSelectUnit parameters
5Unit parametersSelectWater reset
6Water resetSelectParameter
7Set
8Conrm
9Press 3 sec.
10SelectLocal connections
Path: Main Menu / Unit parameters / Water reset
ParametersShort descriptionDescription
P0063TypeWRInlet signal type: 0=0-10V; 1=4-20mA
P0281:MaxCWRCMaximum correction to be applied to the setpoint
P0283:SWRMaxCValue of the WR control signal corresponding to the correction of the set COOL equal to the parameter P0281
P0285SWRMinCValue of the WR control signal corresponding to the correction of the set COOL equal to 0
24 WSA-XEE 122-402
M02S40N16-00
Page 25
6.13 ECOSHARE function for the automatic management of a group of units
Max 7 units
•
Maximum length of the bus line: 1000 m.
•
Maximum distance between 2 units: 700 m.
•
Type of cable: shielded twisted pair cable Ø 0,8 mm. use an EIB/KNX cable
•
Possible connections: Tree, star, in/out bus, mixed
•
It is not possible to use a ring connection
•
No end-of-line resistor or terminator required
•
There must be suitable arresters to protect the serial lines from the eects of atmospheric discharges
•
The data line must be kept separate from the power conductors or powered at dierent voltage values and away from possible sources
•
of electrical interference
M02S40N16-00 WSA-XEE 122-402 25
Page 26
If there are more units connected in a local network set the mode of operation.
MODE A
Every unit manages its own compressors according to the
setpoint.
Every unit optimizes its refrigeration circuits.
Pumps always active, even with compressor stoped.
P0343 = 0
P0344 > 0 °C
setpoint1 > setpoint2 > setpoint3
or
setpoint1 < setpoint2 < setpoint3
MODE B
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Pumps always active, even with compressor stoped.
P0343 = 1
P0344 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: optimal H2O temperature control
MODE C
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Active pumps only with active compressors.
P0343 = 2
P0344 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: minimum pumps consumption need balanced system (t1 = t2 = t3)
Path: Main Menu / Unit parameters / Master Slave
ParametersShort descriptionDescription
P0340:Address unitProcessBus address unit
P0341:Unit networkNumber of network-connected units including the master
P0342:Standby unitNumber of units kept in standby
P0343:TypeRegMSOperation mode: 0=mode A; 1=mode B; 2=mode C
P0344:Oset Trm MS
Temperature Oset the master sum or subtract, depending on the way you set, in order of priority, to the set point of
the slave
26 WSA-XEE 122-402
M02S40N16-00
Page 27
6.14 Evaporator water ow-rate
Check that the dierence between the temperature of exchanger return and supply water corresponds to power according to this formula:
unit cooling power (kW) x 860 = Dt (°C) x ow rate (L/h)
The cooling power is shown in the table of the GENERAL TECHNICAL DATA included in this manual, referred to specic conditions, or in the
tables on COOLING PERFORMANCE in the TECHNICAL BULLETIN referred to various conditions of use.
Check for water side exchanger pressure drops:
determine the water ow rate
measure the dierence in pressure between exchanger input and output and compare it with the graph on WATER SIDE EXCHANGER
PRESSURE DROPS
The measurement of pressure will be easier if pressure gauges are installed as indicated in the DIAGRAM OF SUGGESTED WATER CONNECTIONS.
6.15 Operating at reduced load
The units are equipped with partialization steps and they can, therefore, operate with reduced loads.
However a constant and long operation with reduced load with frequent stop and start-up of the compressor/s can cause serious damages
for the lack of oil return.
The above-described operating conditions must be considered outside the operating limits.
In the event of compressor breakdown, due to operating in the above-mentioned conditions, the guarantee will not be valid and Clivet spa
declines any responsibility.
Check periodically the average operating times and the frequency of the compressors starts: approximately the minimum thermal load
should be such as to need the operating of a compressor for at least ten minutes.
If the average times are close to this limit, take the proper corrective actions.
6.16 Scroll compressor
The Scroll compressors have only one rotation direction.
In the event it is reversed, the compressor is not immediately damaged, but increases its noise and jeopardises pumping.
After a few minutes, the compressor blocks due to intervention of the thermal protection.
In this case, disconnect power supply and invert 2 phases on the machine power supply.
Avoid the compressor working for a long time with contrary rotation: more than 2-3 of these anomalous start-ups can damage it.
To ensure the rotation direction is correct, measure the condensation and suction pressure.
The pressures must signicantly dier: upon start-up, the suction pressure decreases whereas the condensation one, increases.
6.17 Start-up report
Identifying the operating objective conditions is useful to control the unit over time.
With unit at steady state, i.e. in stable and close-to-work conditions, identify the following data:
total voltages and absorptions with unit at full load
•
absorptions of the dierent electric loads (compressors, fans, pumps etc)
•
temperatures and ows of the dierent uids (water, air) both in input and in output from the unit
•
temperature and pressures on the characteristic points of the refrigerating circuit (compressor discharge, liquid, intake)
•
The measurements must be kept and made available during maintenance interventions.
6.18 97/23 CE PED directive
97/23 CE PED DIRECTIVE gives instructions for installers, users and maintenance technicians as well.
Refer to local regulations; briey and as an example, see the following:
Compulsory verication of the rst installation:
only for units assembled on the installer’s building site (for ex. Condensing circuit + direct expansion unit)
•
Certication of setting in service:
for all the units
•
Periodical verications:
to be executed with the frequency indicated by the Manufacturer (see the “maintenance inspections” paragraph)
•
M02S40N16-00 WSA-XEE 122-402 27
Page 28
7 Control
7.1 Led
INFONot used
ALARMBlink / xed = alarm present
CANCELnot used currently
7.2 Display
Ref.VariableDescription
ADate - Time
BActualSetPointTemperature setting
CT.InH2OUtilitySideWater inlet temperature utility side
DT.OutH2OUtilitySideWater outlet temperature utility side
EActualStateOn / o / eco / pmp On
FActualMode
2Installed compressors
1 - 0
50%Heating capacity
Cool: water cooling
Heat: Heating (not used)
Compressors ON
example: circuit 1 = 1 compr. On
circuit 2 = 0 compr. On
7.3 Keys
SymbolNameDescription
InfoMain menu
AlarmAlarm display
Cancel
Exit
Previous level
Keyboard settings
UpIncreases value
DownDecreases value
Enter
28 WSA-XEE 122-402
Conrm
Password
M02S40N16-00
Page 29
7.4 Change unit state
Step DisplayActionMenu/VariableKeysNotes
1Press
2Main menuSelectCmd Local state
3SetOFF - ECO - ON - Pump On*
4Conrm
6Exit
* Local state
ECO: recurrent pump ON-OFF; compressors keep water system at setpoint ECO
Pmp ON: pump ON, compressor OFF
7.5 Change the mode
Step DisplayActionMenu/VariableKeysNotes
1Press
2Main menuSelectCmd Local mode
3Set
4Conrm
5Exit
Cool: water cooling
Heat: water heating (option)
7.6 Modify setpoint
Step DisplayActionMenu/VariableKeysNotes
1Press
2Main menuSelectUnit parameters
3Unit parametersConrmSet Point
4SelectSet Point
5SetSet Point
6Conrm
7Exit
Parameters Short descriptionDescription
P0001SetPoint CoolSetpoint Cool
P0002SetPoint HeatSetpoint HeatNot used
P00032°SetPoint Cool2° Setpoint CoolEnable by remote switch
P00042°SetPoint Heat2° Setpoint Heatnot used currently
P0005SetPoint ECOCoolEconomic summer SetPoint
P0006SetPoint ECOHeatEconomic winter SetPointNot used
P0007SetPointRecRecovery Set Point
M02S40N16-00 WSA-XEE 122-402 29
Page 30
7.7 Scheduler
It is possible to set 6 events (O, Eco, On, Recirculating) for each week day.
Step DisplayActionMenu/VariableKeysNotes
1Press
2Main menuSelectScheduler
3SchedulerSelectDay
4SelectTime
5SetEvent time
6Conrm
7SelectValue
8SetOn/Eco..
9Conrm
10Exit
Enable Scheduler
Step DisplayActionMenu/VariableKeysNotes
1Press 3 sec.
2PasswordSetPassword
3Press*
4Main menuSelectUnit Parameters
5SelectOption cong
6SetP0061=1
7Press 3 sec.
SelectLocal connections
* Unit Parameters menu is displayed
7.8 Keyboard settings
Step DisplayActionMenu/VariableKeysNotes
1Press 3 sec.
2Press
3HMI SettingsSelect
4Press
5Press
6SelectLocal connections
30 WSA-XEE 122-402
M02S40N16-00
Page 31
7.9 Alarms
Before resetting an alarm identify and remove its cause.
Repeated resets can cause irreversible damage.
Example:
+ eE001: Monitore fase: Fault = active alarm
- EE003: Guasto P1 Util: Ok = resetted alarm
Display of alarm: step 1-3
Reset allarm: step 4-10
Step DisplayActionMenu/VariableKeysNotes
1Press
2Alarm list detailPress
3Alarm listSelectAlarm
4Alarm list detailPress 3 sec.
5PasswordSetEnter password
6Alarm list detailPress
7Alarm listSelectAlarm
8Select
9Press 3 sec.
10Password managementSelectLog o
The alarm code identies the concerned circuit:
Example:
ee 1 01:TimeOutModCirc = circuit 1
ee 2 01:TimeOutModCirc = circuit 2
The number of refrigerant circuits depends on series and size of the unit.
Reset
Executed
t.i. input type:
DI = digital input
AI = analogic input
Module:
687 = main module
985 = circuit module
94U = thermostatic driver module
Input:
Connector number:
T1, T2, T3.....
PIN code:
X1, X2, Q13, DO1.....
t.a. alarm type:
A automatic reset
M manual reset
A/M automatic reset, (after N alarm interventions becomes manual reset)
M02S40N16-00 WSA-XEE 122-402 31
Page 32
codedetailed descriptiont.i.moduleinputt.a.
eE001Phase monitorDI687 centralT13 DL1A/M
EE003Pump 1 overloadDI687 centralT13 DL2M
EE004Pump 2 overloadDI687 centralT4 D1M
EE005Pump 3 overloadDI687 centralT13 DL2M
ee010Master Oine - Master Slave network enabledA
ee011Unit 2 in alarm - Master Slave network enabledA
Source 1 temperature (for machines with air-based sources and reversible on gas = Probe 1 on source battery.
For machines with water-based source = Source input probe)
Source 2 temperature (for machines with air-based sources and reversible on gas = Probe 2 on source battery.
For machines with water-based source = Source outlet probe)
Status of the oil dierential pressure switch contact (Active if compressor = Screw): 0=Fault 1=OK
Status of the cycle inversion valve control: 0=O 1=On
Status of the control of the motor’s 1st winding (with PartWiding start-up) / Status of the star contactor control (with delta
start-up)(Active if compressor = Screw): 0=O 1=On
Status of the control of the motor’s 2nd winding (with PartWiding start-up) / Status of the control of the triangle contactor
(with delta start-up)(Active if compressor = Screw): 0=O 1=On
S1114Current cap.Capacity currently used up on the circuit
S1115Requested cap.Capacity required on the circuit
S1116Pressure ratioCompression ratio status (1+HP/1+LP)
S1117FANPreAlarmStatus of the current maximum ventilation pre-alarm 0=O 1=On
S1118Defrost delay
S1119Defrosting status
S1120HWErr
S1121BlckingHWErr
S1122FailSafeStaActive block status: 0=O 1=On
S1123UPSNotAvalUPS failure: 0=O 1=On
S1124CircWarningStatus associated with circuit block alarm
S1125CircBlockLock alarm circuit
S1126ThTDischargeTheoretical discharge temperature
Current value of the countdown towards the cycle inversion due to defrosting. (defrosting starts when the value reaches
zero)
Indicates the defrosting status 0=DfrO (Cycle inversion phase for defrosting phase NOT active) 1=DfrON (Cycle inversion
phase for defrosting phase ACTIVE)
Hardware error of the POL94U module that does not preclude the possibility of moving the valve or closing it.
Possible causes: anomalous voltage values in the valve motor 0=O 1=On
Hardware error of the POL94U module that prevents the electronic valve from moving.
Possible causes: UPS not available, wrong POL94U Bios, HW POL94U Error, Disconnected EEV Motor, calibration error associated with conguration parameters. 0=O 1=On
7.13 Thermostatic C1 status
codedescriptiondetailed description
S1200SHSpOpOperating overheating setpoint net with SH and MET adjustments
0=Idle (motor o) 1=Init (valve initialised when completely closed) 2=Manual (valve controlled in manual mode) 3=Control
(the valve conducts adjustments to control SH)
* European regulation 303/2008
Refer to the local regulations; and ensure correct adherance. Companies and technicians that eect interventions of installation, maintenance/
repairs, leak control and recovery must be CERTIFIED as expected by the local regulations. The leak control must be eected with annual
renewal.
8.3 Unit booklet
It’s advisable to create a unit booklet to take notes of the unit interventions.
In this way it will be easier to adequately note the various interventions and aid any troubleshooting.
Report on the booklet:
date
•
type of intervention eected
•
intervention description
•
carried out measures etc.
•
M02S40N16-00 WSA-XEE 122-402 39
Page 40
8.4 Standby mode
If a long period of inactivity is foreseen:
turn o the power
•
avoid the risk of frost (empty the system or add glycol)
•
Turn o the power to avoid electrical risks or damages by lightning strikes.
With lower temperatures keep heaters turned on in of the electrical panel (option).
It’s recommended that the re-start after the stopping period is performed by a qualied technician, especially after seasonal stops or seasonal
switching.
When restarting, refer to what is indicated in the “start-up” section.
Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required.
8.5 Water side exchanger
It is very important for the exchanger to be able to provide the maximum thermal exchange, therefore it is essential for the inner surfaces to
be clean of dirt and incrustations.
Periodically check the dierence between the temperature of the supply water and the condensation temperature: if the dierence is greater
than 8°C–10°C it is advisable to clean the exchanger.
The clearing must be eected:
with circulation opposite to the usual one
•
with a speed at least 1,5 times higher than the nominal one
•
with an appropriate product moderately acid (95% water + 5% phosphoric acid)
•
after the cleaning rinse with water to inhibit the action of any residual product
•
8.6 Water lter
Check that no impurities prevent the correct passage of water.
8.7 Circulating pumps
Check:
no leaks
•
bearing status (anomalies are highlighted by abnormal noise and vibration)
•
the terminal protection covers are closed and the cable holders are properly positioned
•
8.8 Flow Switch
controls the operations
•
remove incrustations from the palette
•
8.9 Electric fans
Check:
the fans and the relative protection gridsare well xed
•
the fan bearings (evident by noise and anomalous vibrations)
•
the terminal protection covers are closed and the cable holders are properly positioned
•
8.10 Air coil
Contact with the exchanger ns can cause cuts: wear protective gloves to perform the above described operations.
It is extremely important that the battery gives the maximum thermal exchange; therefore, its surface must be cleaned from dust and deposits.
Remove all impurities from the surface.
Using an air pressure gun, clean the aluminum surface of the battery; be careful to direct the air in the opposite direction of the fan air
movement.
Hold the gun parallel to the ns to avoid damages.
As an alternative, vacumn cleaner can be used to suck impurities from the air input side.
Verify that the aluminum ns are not bent or damaged, in the event of damages contact the authorized assistance center and get the ns
straightened in order to restore the initial condition for an optimal air ow.
40 WSA-XEE 122-402
M02S40N16-00
Page 41
8.11 Compressor supply line shut-o valve
A. Supply line shut-o valve
Do not remove the seal
Remove only if authorized by the manufacturer.
Please contact the maker for informations.
8.12 crankcase heather
Check:
closure
•
Operation
•
8.13 System discharge
1. evacuate the system
2. evacuate the exchanger, use all the cocks presents
3. use compressed air to blow the exchanger
4. dry completely the exchanger by an hot air jet; for greater safety ll the exchanger with glycoled solution
5. protect the exchanger from the air
6. remove the drain plugs to the pumps
Any anti-freeze liquid contained in the system should not be discharged freely as it is a pollutant.
It must be collected and reused.
Before starting a washing the plant.
Example
emptying pump
•
It’s recommended that the re-start after the stopping period is performed by a qualied technician, especially after seasonal stops or seasonal
switching.
When restarting, refer to what is indicated in the “start-up” section.
Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required.
M02S40N16-00 WSA-XEE 122-402 41
Page 42
9 Accessories
9.1 Partial energy recovery
A conguration which enables the production of hot water free-of-charge while operating in the cooling mode, thanks to the partial recovery
of condensation heat that would otherwise be rejected to the external heat source.
The maximum capacity available from the partial recovery is equal to the 15% of the rejected heating capacity (cooling capacity + compressor
power input)
The recovery exchanger must be always maintained full of water
The lack of water amplies the noise generated by the operation
When the temperature of the water to be heated is particularly low, it is wise to insert a ow-rate control valve into the system water circuit,
in order to maintain the temperature at the recovery output at above 35°C and thus avoid the condensation of the refrigerant into the partial
energy recovery device.
QAB
V
M
QB
UNIT
QA
QAB
QB
42 WSA-XEE 122-402
M02S40N16-00
Page 43
9.2 Single pump
1Internal exchanger8Pressure gauge
3Purge valve9Safety valve
5drain valve12System load safety pressure switch
6shut-o valve13Anti-ice electric heater
7lter15Circulation pump with inverter
9.3 CSVX - Couple of manually opeated shut-o valves
Il kit allows to isolate the water circuit at the inlet and outlet.
It includes:
no. 2 cast-iron shut-o buttery valves with fast ttings and activation lever with a mechanical calibration lock
•
no. 2 of quick connections
•
9.4 Fresh air probe
The external probe allows to automatically change the unit set point according to the external enthalpy (temperature + humidity).
It is then possible to optimize the unit energy eciency.
Positioning
The sensor has not to be inuenced by factors that can false the reading (for ex. direct solar irradiation, exhaust air by fan or other sources,
contact with the unit structure or other sources of heat, accumulations of snow/ice), it has therefore to be placed in a protected place (possibly
to the north), for example in an attic, under a terrace and if it is on a free wall, provide a small roong.
M02S40N16-00 WSA-XEE 122-402 43
Page 44
9.5 Antivibration
ISTRUZIONI - GUIDE INSTRUCTIONS
PER L’INSTALLAZIONE DEI SUPPORTI ANTIVIBRANTI
INSTALLATION OF THE ANTI-VIBRATION MOUNTS
SUPPORTI ANTIVIBRANTI IN ELASTOMERO serie BBS... FORNITI IN KIT
ELASTOMER ANTI-VIBRATION MOUNTS BBS... line SUPPLIED WITH “KIT”
Il kit è formato da antivibranti serie BBS... per isolare le
macchine citate nella selezione con martinetti M12 e istruzioni di montaggio.
The kit consists of anti-vibration mounts BBS... line to isolate the machines listed in the selection, M12 jacks and instructions for the installation.
anti-vibrations “kit” package dimensions 21x17x12 cm
sizes from 122 to 402
peso netto
net weight (Kg)
peso lordo
gross weight (Kg)
21 cm
44 WSA-XEE 122-402
M02S40N16-00
Page 45
ATTENZIONE:
Prima di procedere all’installazione degli antivibranti accertarsi che il codice identificativo del kit, evidenziato
sulla scatola, sia rispondente al modello di macchina sulla quale deve essere installato.
Il supporto antivibrante è formato da:
x INVOLUCRO “X” involucro d i contenimento in Polyamide 6 (PA6) con elevata resistenza allo
shock, protegge i corpi elastici all’interno.
x ANELLO SUPERIORE “Y”anelli in elastomero termoplastico con elevato grado di isolamento termico
x ANELLO INFERIORE “Z”ed elettrico, ottima resistenza alla fatica, ai raggi UV, all’invecchiamento
atmosferico, a vari agenti chimici quali basi, acidi, alcoli, detergenti,
soluzioni acquose e solventi polari, buona resistenza all’abrasione, elevato
ritorno elastico in ampio intervallo di temperature, resistenza alle
temperature da –50 a +120 °C.
xMARTINETTO “W” in acciaio zincato per registrare il livello della macchina sospesa.
CAUTION:
Make sure the code of the “anti-vibration support kit”, shown on the box corresponds to the machine model on
which it has to be installed.
The anti-vibration support is composed by:
xENCLOSURE “X” containment enclosure in Polyamide 6 (PA6) with high resistance to
shock, protects the inside elastic bodies.
xUPPER RING “Y” rings in thermoplastic elastomer with a high degree of thermic and electric.
xLOWER RING “Z” insulation, excellent fatigue resistance, UV, aging pollution, to various
chemicals such as bases, acids, alcohols, detergents, aqueous
solutions and polar solvents, good abrasion resistance, high
elastic return in wide range of temperatures, resistance to
temperatures from -50 to +120 ° C.
xJACK “W” in galvanized steel to register the level of the suspended machine.
W
X
Y
Z
M02S40N16-00 WSA-XEE 122-402 45
Page 46
COMPONENTI DEL MARTINETTO fig.1
JACK’S COMPOSITION fig.1
fig.1
E2
E
E3
E1 Grano M12 con sede per chiave a brugola del 6.
M12 grain with lodging for Allen Key of the 6
E2 - E6
Dado basso UNI 5589.
TH
.
Low nut UNI 5589.
E3
Rondella elastica spaccata UNI 1751.
Broken elastic washer UNI 1751.
E4
Disco in acciaio Ø esterno 65 foro 13 e sp. 4 mm
per grano M12.
Steel-Disc Ø 65 sp.4 for M12 jack.
E5
Dado alto UNI 5587.
High nut UNI 5587.
PROCEDURA PER L’INSERIMENTO DEL
MARTINETTO SULL’ANTIVIBRANTE.
ROCEDURE TO INSERT THA JACK ON
THE ANTI-VIBRATING.
Configurazione del martinetto
prima dell’inserimento
sull’antivibrante
Configuration of the jack
before the insertion of the
anti-vibrators.
Chiave a brugola del 6
“Allen key” of the 6
TH
E1
E4
E5
E6
Chiave del 19
“simple key” of the 19
E1
TH
fig.2 Utilizzando la chiave a brugola del 6 avvitare il grano M12 (E1)
nell’attacco filettato dell’antivibrante (A1).
Fit the M12 grain (E1) in the threaded housing on the upper plate
of the anti-vibration mount with allen key of the 6
TH
(A1).
fig.3 Utilizzando la chiave del 19, bloccare con il dado basso (E6) il
grano M12 (E1), sulla bussola. L’antivibrante così configurato è
pronto per essere installato come indicato nella pagina seguente.
Using the simple key of the 19
TH
, fit the M12 grain (E1) mounted
on the anti-vibration mount in the hole of the machines base, with
steel nut (E6). In this way, the anti-vibration is ready to be
installed as shown in the next page.
A1
fig.2
E6
fig.3
46 WSA-XEE 122-402
M02S40N16-00
Page 47
ATTENZIONE:
Gli antivibranti devono essere collocati sotto la macchina, secondo l o
schema indicato nell’impronta a terra indicata nella pagine seguenti.
INSTALLAZIONE
A. Posizionare la macchina ad un’altezza che consenta all’operatore di
inserire nel foro (A1), predisposti sul basamento, i martinetti con gli
antivibranti.
B. Attraverso il foro (B1) fe
interponendo la rondella elastica spaccata (E3).
C. Calare in piano la macchina sulla superficie di appoggio, in modo che
gli antivibranti siano caricati simultaneamente. Regolare il livello della
macchina agendo sui dadi alti (E5). Ottenuta la messa in piano della
macchina, bloccare i dadi (E2).
D.Al termine delle operazioni la macchina deve risultare elastica sugli
antivibranti.
BE CAREFUL:
The antivibratings have to be positioned under the machine, according to the
scheme on next pages “foot print”.
INSTALLATION
A. The machine has to be reached by the operator who has to put in the
holes (A1) done on the basement, the jack with the anti-vibrating.
B. Through the hole (B1) fix the anti-vibrating using the low nut (E2) in
opposition with broken elastic washer (E3).
C. Put the machine on the floor on the same time so as to charge
sim
the high nuts (E5). When the machine has reached its right position fix
the before-said nuts (E2).
D.At the end of the
ultaneously the anti-vibrators. Fix the machines’ level working on
elastic on the anti vibratings.
rmare i martinetti con il dado basso (E2),
se operation the machine has to be
A
A1
E3
B
C
E5
B1
E2
E2
M02S40N16-00 WSA-XEE 122-402 47
Page 48
serie BBS...
Impronta a terra / Foot print
Dimensioni / Dimensions
(9)
Codice kit
Kit code
PE2S00002
PE2S00003
(9)
W1
W3W4
1450100
W2
(9)
(9)
500
0
0
3
1
6
(9)
1000
100
(9)
W1
W3
1875
(9)
W2
W4
6
(9)
500
serie WSA-XEE / WSA-XEE line
Macchine / MachinesPunti di appoggio antivibranti / Antivibratings supporting points
Modelli / ModelsW1W2W3W4
WSA-XEE 122
WSA-XEE 162
BBS100 45 sh BBS100 45 sh BBS100 45 sh BBS100 45 sh
BBS100 45 sh BBS100 60 sh BBS100 45 sh BBS100 60 sh
(9)
1300
(9)
1000
Codice kit
Kit code
PE2S00003
PE2S00003
48 WSA-XEE 122-402
Macchine / MachinesPunti di appoggio antivibranti / Antivibratings supporting points
Modelli / ModelsW1W2W3W4
WSA-XEE 182
WSA-XEE 222
BBS100 45 sh BBS100 60 sh BBS100 45 sh BBS100 60 sh
BBS100 45 sh BBS100 60 sh BBS100 45 sh BBS100 60 sh
M02S40N16-00
Page 49
serie BBS...
Impronta a terra / Foot print
Dimensioni / Dimensions
Codice kit
Kit code
PE2S00004
PE2S00004
PE2S00001
PE2S00001
(9)
1300
6
100
(9)
W1
W3
W2
W4
(9)
1000
(9)
2650
500
(9)
serie WSA-XEE / WSA-XEE line
Macchine / MachinesPunti di appoggio antivibranti / Antivibratings supporting points
Modelli / ModelsW1W2W3W4
WSA-XEE 262
WSA-XEE 302
WSA-XEE 352
WSA-XEE 402
BBS100 45 sh BBS100 60 sh BBS100 60 sh BBS100 60 sh
BBS100 45 sh BBS100 60 sh BBS100 60 sh BBS100 60 sh
BBS100 60 sh BBS100 60 sh BBS100 60 sh BBS100 60 sh
BBS100 60 sh BBS100 60 sh BBS100 60 sh BBS100 60 sh
M02S40N16-00 WSA-XEE 122-402 49
Page 50
10 Decommissioning
10.1 Disconnecting
Only authorised personnel must disconnect the unit.
Avoid leak or spills into the environment.
Before disconnecting the unit, the following must be recovered, if present:
refrigerant gas
•
anti-freeze solutions in the water circuit
•
Awaiting dismantling and disposal, the unit can also be stored outdoors, if the electrical, cooling and water circuits of the unit have 100%
integrity and are isolated, bad weather and rapid change in temperature will not result in any environmental impact.
10.2 Dismantling and disposal
The unit must always be sent to authorised centres for dismantling and disposal.
When dismantling the unit, the fan, the motor and the coil, if operating, may be recovered by the specialist centres for reuse.
All the materials must be recovered or disposed of in compliance with the corresponding national standards in force.
For further information on the decommissioning of the unit, contact the manufacturer.
10.3 Directive EC RAEE
The units covered by the legislation in question are marked with the symbol on the side.
With the aim of protecting the environment, all of our units are produced in compliance with Directive EC on waste electrical and electronic
equipment (RAEE).
The potential eects on the environment and on human health due to the presence of hazardous substances are shown in the use and
maintenance manual in the section on residual risks.
Information in addition to that indicated below, if required, can be obtained from the manufacturer/distributor/importer, who are responsible
for the collection/handling of waste originating from equipment covered by EC-RAEE. This information is also available from the retailer who
sold this appliance or from the local authorities who handle waste.
Directive EC-RAEE requires disposal and recycling of electrical and electronic equipment as described therein to be handled through
appropriate collection, in suitable centres, separate from collection for the disposal of mixed urban waste.
The user must not dispose of the unit at the end of its life cycle as urban waste, it must instead be handed over to appropriate collection
centres as set forth by current standards or as instructed by the distributor.
50 WSA-XEE 122-402
M02S40N16-00
Page 51
11 Residual risks
General description
In this section the most common situations are indicated,as these
cannot be controlled by the manufacturer and could be a source of
risk situations for people or things.
Danger zone
This is an area in which only an authorised operator may work.
The danger zone is the area inside the unit which is accessible only
with the deliberate removal of protections or parts thereof.
Handling
The handling operations, if implemented without all of the protection necesssary and without due caution, may cause the drop or the
tipping of the unit with the consequent damage, even serious, to
persons, things or the unit itself.
Handle the unit following the instructions provided in the present
manual regarding the packaging and in compliance with the local
regulations in force.
Should the refrigerant leak please refer to the refrigerant “Safety
sheet”.
Installation
The incorrect installation of the unit could cause water leaks,
condensate accumulation, leaking of the refrigerant, electric shock,
poor operation or damage to the unit itself.
Check that the installation has been implemented by qualied
technical personnel only and that the instructions contained in
the present manual and the local regulations in force have been
adhered to.
The installation of the unit in a place where even infrequent leaks
of inammable gas and the accumulation of this gas in the area
surrounding the area occur could cause explosions or res.
Carefully check the positioning of the unit.
The installation of the unit in a place unsuited to support its weight
and/or guarantee adequate anchorage may result in consequent
damage to things, people or the unit itself.
Carefully check the positioning and the anchoring of the unit.
Easy access to the unit by children, unauthorised persons or animals
may be the source of accidents, some serious.
Install the unit in areas which are only accessible to authorised
person and/or provide protection against intrusion into the danger
zone.
General risks
Smell of burning, smoke or other signals of serious anomalies may
indicate a situation which could cause damage to people, things or
the unit itself.
Electrically isolate the unit (yellow-red isolator).
Contact the authorised service centre to identify and resolve the
problem at the source of the anomaly.
Accidental contact with exchange batteries, compressors, air delivery tubes or other components may cause injuries and/or burns.
Always wear suitable clothing including protective gloves to work
inside the danger zone.
Maintenance and repair operations carried out by non-qualied
personnel may cause damage to persons, things or the unit itself.
Always contact the qualied assistance centre.
Failing to close the unit panels or failure to check the correct
tightening of all of the panelling xing screws may cause damage to
persons, things or the unit itself.
Periodically check that all of the panels are correctly closed and
xed.
If there is a re the temperature of the refrigerant could reach values
that increase the pressure to beyond the safety valve with the
consequent possible projection of the refrigerant itself or explosion
of the circuit parts that remain isolated by the closure of the tap.
Do not remain in the vicinity of the safety valve and never leave the
refrigerating system taps closed.
Electric parts
An incomplete attachment line to the electric network or with incorrectly sized cables and/or unsuitable protective devices can cause
electric shocks, intoxication, damage to the unit or res.
Carry out all of the work on the electric system referring to the
electric layout and the present manual ensuring the use of a system
thereto dedicated.
An incorrect xing of the electric components cover may lead to
the entry of dust, water etc inside and may consequently electric
shocks, damage to the unit or res.
Always x the unit cover properly.
When the metallic mass of the unit is under voltage and is not
correctly connected to the earthing system it may be as source of
electric shock and electrocution.
Always pay particular attention to the implementation of the earthing system connections.
Contact with parts under voltage accessible inside the unit after
the removal of the guards can cause electric shocks, burns and
electrocution.
Open and padlock the general isolator prior to removing the guards
and signal work in progress with the appropriate sign.
Contact with parts that could be under voltage due to the start up
of the unit may cause electric shocks, burns and electrocution.
When voltage is necessary for the circuit open the isolator on the
attachment line of the unit itself, padlock it and display the appropriate warning sign.
Moving parts
Contact with the transmissions or with the fan aspiration can cause
injuries.
Prior to entering the inside of the unit open the isolater situated
on the connection line of the unit itself, padlock and display the
appropriate warning sign.
Contact with the fans can cause injury.
Prior to removing the protective grill or the fans, open the isolator
on the attachment line of the unit itself, padlock it and display the
appropriate warning sign.
Refrigerant
The intervention of the safety valve and the consequent expulsion
of the gas refrigerant may cause injuries and intoxication.
Always wear suitable clothing including protective gloves and
eyeglasses for operations inside the danger zone.
Should the refrigerant leak please refer to the refrigerant “Safety
sheet”.
Contact between open ames or heat sources with the refrigerant
or the heating of the gas circuit under pressure (e.g. during welding
operations) may cause explosions or res.
Do not place any heat source inside the danger zone.
The maintenance or repair interventions which include welding
must be carried out with the system o.
Hydraulic parts
Defects in tubing, the attachments or the removal parts may cause
a leak or water projection with the consequent damages to people,
things or shortcircuit the unit.
Standard airowl/s44444444500050006667750075008333
Installed unit powerkW2.702.702.702.702.702.702.702.70
Max external static pressurePa570570450450570450420240
Connections
Water ttings1 1/2”1 1/2”1 1/2”1 1/2”1 1/2”2”2”2”
Power supply
Standard power supplyV400/3~/50400/3~/50400/3~/50400/3~/50400/3~/50400/3~/50400/3~/50400/3~/50
Dimensions
Lengthmm14501450187518752650265026502650
Depthmm780780780780780780780780
Heightmm19951995199519951995199519951995
1. Data refer to the following conditions: internal water exchanger = 12/7 °C; outdoor air temperature 35°C
2. Exchanger water temperature - Partial recovery = 40/45°C
3. Data calculated in compliance with Standard EN 14511:2011referred to the following conditions : Internal exchanger water temperature = 12/7 °C. Input air temperature to the external exchanger = 35°C Static pressure of the ducted
external section = 120 Pa
Sound levels refer to units at full load.
The sound pressure is measured at 1 m from the external surface of the ducted unit operating in an open eld. (standard UNI EN ISO 9614-2)
Data referred to the following conditions:
- Internal exchanger water temperature = 12/7°C
- outdoor air temperature 35°C
- Static available pressure 120 Pa
Please note that when the unit is installed in conditions dierent from nominal test conditions (e.g. near walls or obstacles in general), the sound levels may undergo substantial variations.
Operating range
Size122162182222262302352402
External exchanger
Max entering air temperature1°C4545454545454544
Max entering air temperature2°C4848484848484847
Min. entering air temperature3°C-10-10-10-10-10-10-10-10
Min. entering air temperature4°C-7.0-7.0-7.0-7.0-7.0-7.0-7.0-7.0
Internal exchanger
Max inlet water temperature°C2127272727272424
Min. leaving water temperature5°C5.05.05.05.05.05.05.05.0
Min. leaving water temperature6°C-7.0-7.0-7.0-7.0-7.0-7.0-7.0-7.0
Data referred to the following conditions:
Internal exchanger water temperature = 12/7°C
Entering eExternal exchanger air temperature = 35°C
1. unit at full load
2. Unit with automatic staging of the compressor capacity.
3. unit at full load
4. Part-load unit
5. Standard unit and external exchanger entering air 35 °C (no ‘Low water temperature (Brine)’ conguration).
6. Unit in ‘Low water temperature (Brine)’ conguration. Fluid processed with 40% ethylene glycol
Graph referred to size 352
The detail of each size is shown in tabular date.
Ta (°C) = entering external exchanger air temperature (dry bulb).
To (°C)= leaving internal exchanger water temperature
1. Standard unit:(no “Liquid low temperature” conguration)
2. Operation eld extension for unit in ‘Low water temperature
(Brine)’ conguration (40% ethylene glycol).
3. Unit with automatic staging of the compressor capacity.
4. Unit at full-load with air ow automatic modulation
M02S40N16-00 WSA-XEE 122-402 53
Page 54
Admissible water ow rates
Min. (Qmin) and max. (Qmax) water ow-rates admissibles for the correct unit operation
Size122162182222262302352402
Qmin[l/s]1.01.11.31.51.72.93.23.6
Qmax[l/s]2.83.23.64.24.78.19.010.2
Exchanger operating range
Internal exchanger
TYPE OF TEST
CLIVET C45001000
PED (CE)45001000
DPr = Max. operating pressure referigerant gas side
DPw = Max. operating pressure water side (utility)
DPrDPw
[kPa][kPa]
Overload and control device calibrations
Setting instruments
High pressure safety pressure switch[kPa]40503300-
Low pressure safety switch[kPa]450600-
low pressure switch (Brine)[kPa]200350-
antifreeze protection[°C]35.5-
high pressure safety valve[kPa]--4500
low pressure safety valve[kPa]--3000
Max no. of compressor starts per hour[n°]--10
high compressor discharge temperature safety thermostat[°C]--120
aprechiudevalore
54 WSA-XEE 122-402
M02S40N16-00
Page 55
Dimensional drawings
Sizes 122-162
DAB2S122_162_0 REV00
DATA 23/06/2016
(1) Compressor compartment
(2) General electrical panel
(3) Exhaust radial electric fans
(4) External exchanger
(5) Internal exchanger
(6) Electric line input
(7) Hydraulic ttings ush with unit (optional)
(8) Partial recovery water ttings (optional)
Size122162
A - Lengthmm14501450
B - Widthmm780780
C - Heightmm19961996
W1 Supporting Pointkg8883
W2 Supporting Pointkg124151
W3 Supporting Pointkg107105
W4 Supporting Pointkg144173
Shipping weightkg456506
Operating weightkg463513
La presenza di accessori opzionali può comportare una variazione signicativa dei pesi indicati in tabella.
M02S40N16-00 WSA-XEE 122-402 55
(9) Functional clearances
(10) Separation line
(R) Outdoor air return
(EV) Vertical air exhaust (standard)
(EO) Horizontal air exhaust (optional)
Page 56
Sizes 182-222
DAB2S182_222_0 REV00
DATA 23/06/2016
(1) Compressor compartment
(2) General electrical panel
(3) Exhaust radial electric fans
(4) External exchanger
(5) Internal exchanger
(6) Electric line input
(7) Hydraulic ttings ush with unit (optional)
(8) Partial recovery water ttings (optional)
Size182222
A - Lengthmm18741874
B - Widthmm780780
C - Heightmm19961996
W1 Supporting Pointkg9898
W2 Supporting Pointkg169171
W3 Supporting Pointkg117118
W4 Supporting Pointkg188191
Shipping weightkg565572
Operating weightkg572578
La presenza di accessori opzionali può comportare una variazione signicativa dei pesi indicati in tabella.
56 WSA-XEE 122-402
(9) Functional clearances
(10) Separation line
(R) Outdoor air return
(EV) Vertical air exhaust (standard)
(EO) Horizontal air exhaust (optional)
M02S40N16-00
Page 57
Sizes 262-302-352-402
DAB2S262_402_0 REV00
DATA 23/06/2016
(1) Compressor compartment
(2) General electrical panel
(3) Exhaust radial electric fans
(4) External exchanger
(5) Internal exchanger
(6) Electric line input
(7) Hydraulic ttings ush with unit (optional)
(8) Partial recovery water ttings (optional)
Size262302352402
A - Lengthmm2650265026502650
B - Widthmm780780780780
C - Heightmm1996199619961996
W1 Supporting Pointkg128138150153
W2 Supporting Pointkg192202242250
W3 Supporting Pointkg146154164168
W4 Supporting Pointkg210217255265
Shipping weightkg667704804829
Operating weightkg676711810836
La presenza di accessori opzionali può comportare una variazione signicativa dei pesi indicati in tabella.
(9) Functional clearances
(10) Separation line
(R) Outdoor air return
(EV) Vertical air exhaust (standard)
(EO) Horizontal air exhaust (optional)