1.3 - THE KEYPAD
ON/OFF: Switches the status of the unit; if on,
pressing the button places it in Standby; vice-versa,
it is reactivated.
ALARM / Prg: When an alarm is present, mutes the
buzzer; if the clock option is present, in programming
phase sets the time.
UP: In programming phase, scrolls or increases the
value of the parameters. If the clock option is present,
each time the button is pressed the following are
displayed, in sequence: the current time, the date
and the room temperature.
DOWN: Held displays the set point. In programming
phase, scrolls or decreases the value of the
parameters.
ENTER / Sel: Pressed for 5s accesses the
parameters. In programming phase, changes the
value of the selected parameter (see par. 1.4 Modifying the parameters). If the clock option is
present, in programming phase sets the time.
UP + DOWN pressed together for 2s reset the alarms.
1.4 - MODIFYING THE PARAMETERS
− Press the ENTER button for 5s, the value of the first
accessible parameter will be displayed, and in the top
right, the code of the parameter, flashing.
− Scroll the various parameters using the UP and DOWN
buttons.
− Pressing ENTER again displays the value, flashing, of
the selected parameter, while the UP and DOWN
buttons change the value.
− Press ENTER again to temporarily save the new value.
Then, use the UP and DOWN buttons to scroll the menu
of the parameters, repeating the previous operations for
each parameter to be modified.
− Press the ALARM button, on the other hand, to store the
changes made.
Adjusting the contrast of the LCD
The contrast of the display can be adjusted according to
the effective angle of viewing.
Pressing the ENTER and UP buttons together increases
the value, vice-versa, ENTER and DOWN decrease it.
1.5 - CONTROL PARAMETERS
r1 Temperature set point (cooling)
Used to set the temperature set point in cooling (see
diagrams at the end of the paragraph).
Default: 20.0
r2 Cooling differential
Used to set the differential in cooling mode (see
diagrams at the end of the paragraph).
Range: 0.1-11.0°C
Default: 3.0
r3 Heating differential
Used to set the differential in heating mode (see
diagrams at the end of the paragraph).
Range: 0.1-11.0°C
Default: 2.0
r4 Temperature dead zone
Used to set the dead zone (see diagrams at the end of
the paragraph). When the air inlet temperature is inside
the dead zone, all the actuators are off, except for when
the compressor is operating following a dehumidification
request.
Range: 0.1-11.0°C
Default: 1.0
WARNING: THE PARAMETERS FROM r5 TO r8 ARE
PRESENT ONLY TOGETHER WITH THE HUMIDITY
PROBE OPTION
r5 Humidity set point
Sets the humidity set point (see diagrams at the end of
the paragraph).
Default: 50
r6 Humidification differential
Sets the differential for humidification (see diagrams at
the end of the paragraph).
Range: 1-20%rH
Default: 4
r7 Dehumidification differential
Sets the differential for dehumidification (see diagrams at
the end of the paragraph).
Range: 1-20%rH
Default: 3
r8 Humidity control dead zone
Used to set the dead zone (see the diagram at the end of
the paragraph). When the humidity measured by the
humidity probe is inside this zone, the humidifier and the
dehumidification function are not active.
Range: 1-20%rH
Default: 2
r9 Temperature set point (heating)
Heating set point, does not affect the operation of the
machine, its setting is superfluous.
Default: 18.0
rt Time band setting
If the clock option is installed, used to set time band
mode (see chap. 3)
0= time bands disabled
1= temperature monitoring
2= On/Off
Range: 0-2 flags
Default: 0
1.6 - READ ONLY PARAMETERS
rP Humidity probe reading
Percentage of humidity. Only with probe installed.
rr Probe B4 reading
Outlet air temperature. Displayed only with probe
installed.
c9 Hour counter, compressor 1
cA Hour counter, compressor 2
Indicates the number of operating hours for compressor 1
and/or 2. The reading of cA has no meaning, as only one
compressor is used.
FA Hour counter, outlet fan
Indicates the number of operating hours of the fan.
FC Hour counter, filter
Indicates the number of operating hours of the filter.
Hr Software version
Displays the version of the software.