CLIVET MR-DX 17, MR-DX 25, MR-DX 31, MR-DX 61, MR-DX 41 Installation, Operation And Maintenance Manual

...
C. Art. M24D40G3-03 G4D2GB-33
DIRECT EXPANSION CLOSE CONTROL UNIT WITH REMOTE CONDENSER
MR-DX 17-25-31-41-61-71-81
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
GENERAL
THIS MANUAL CONTAINS THE FOLLOWING SECTIONS WHICH ARE TO BE CONSIDERED AN INTEGRAL PART
OF THE WHOLE AND ARE THEREFORE NOT TO BE DETACHED
G4D2GB-3 R4D2GB-3 E4D2GB-3 F4D2GB-3 C4D2GB-3
General Information
Reception
Electrical connections
Start-up
Controls
M4D2GB-3 L4D2GB-3 P4D2GB-3 N4D2GB-3 K4D2GB-3
Routine maintenance Water connections Refrigerant pipes Air filters
Residual risks
IMPORTANT
The contents of this manual are designed to assure the correct installation, adjustment and maintenance of the unit; therefore:
- read the instructions with due care and attention;
- the appliance must be installed, tested and serviced by properly qualified personnel (law n.45, 5.3.1990) licensed in accordance with established legislation.
The manufacturer declines all liability, and guarantee coverage is automatically waived, if electrical and/or mechanical modifications are made to the unit. Tampering and unauthorized repairs or modifications to the unit will automatically void the guarantee.
Observe the safety regulations in force at the time of installation.
Make sure that the characteristics of the mains network conform to the data on the serial number plate inside the electrical panel.
Conserve this manual and the circuit diagram with care. Make sure that they are available for consultation by the operator whenever necessary.
Packing materials (plastic wrappings, expanded polystyrene, nails, etc.) are potentially hazardous and must be kept out of reach of children. Recycle packing materials in accordance with local bylaws.
The water chiller must be used only for the purpose for which it is designed. The manufacturer bears no responsibility in the case of applications other than the specified use.
Disconnect the unit in the case of breakdowns or malfunctions.
If repairs are necessary use only Clivet-approved service centres and always insist on original spare parts. The use of non-original parts and/or unauthorized service centres may result in unsafe operation of the unit.
The manufacturer declines all liability for direct or indirect damage to property or injury
to persons resulting from failure to adhere to the instructions in this manual.
ADDITIONAL SAFETY PRECAUTIONS
This unit has been especially designed and manufactured so to prevent any risk to persons and health hazard. For this reason, design solutions fit to eliminate (where possible) any cause of risk and sensibly reduce the probability of danger have been adopted. Please refer to the Residual risks section of this manual and strictly observe the behaviour prescriptions listed there in order to prevent any possible risk that hasn’t been possible to avoid in the design stage.
2
GENERAL SPECIFICATIONS
Sizes 17 25 31 41 61 71 81
Standard voltage 400/3/50 Cooling capacity (1) kW 5.8 8.3 9.4 12.5 17.0 19.1 23.2 Sensible capacity (1) kW 5.3 6.9 8.1 11.2 14.6 15.5 21.4 Compr.input power (1) kW 1.5 2.3 2.9 3.0 4.7 5.6 5.8
Compressor type Scroll N° of compressors 1 Total oil quantity kg 1.00 1.10 1.10 1.85 1.65 1.65 4
Handling zone Frontal surface m
2
0.36 0.44 0.64 0.78
N° of rows 3 4 Fin space mm 1.8
Coonections Gas connection mm 16 18 Liquid connection mm 12 14 16 Condensate drain mm 22
Handling zone fans (Outlet) N° of fans 1 2 Fan diametre mm 252 280 252 280 RPM rpm 600 1100 1300 1400 1300 1400 Standard air flow l/s 472 555 639 944 1150 1888 Single motor input kW 0.35 0.55 0.35 0.55 Max. ext. static press. Pa 50 Max. ext. static press. (2) Pa 100 150 200 190 200 190 200
Standard unit weight Shipping weight (3) kg 166 170 218 265 275 295 Lenght mm 750 925 1250 1500 Depth mm 490 Height mm 1800
Sound levels Sound Pressure Level (4)dB(A) 47 50 51 53 54 56 58
The data refers to the following conditions:
1) Ambient air 24°C BS/ 16,9°C BU Relative humidity 50% External air 35°C Standard static pressure 50Pa
2) With standard ventilating section, upon request. Contact our sales office for further details.
3) Data refers to the version with outlet downwards.
4) Sound pressure level refers to 1 metre from the outside surface of the unit operating in an open field (version with outlet downwards)
3
POSITIONING
The units are designed for indoor installation.
Make sure that the supporting surface is perfectly level and able to bear the full weight of the unit (see general specifications). Interpose a layer of rubber sheeting between the base of the unit and the supporting surface (to reduce noise and vibration).
Observe the specified functional clearances.
ACCESSORIES
The units can be fitted with the following accessories (upon request):
- Electric heating coil Electric heating section made from reinforced aluminium heaters with integral fins, 2 stage operation and safety thermostat.
- Water heating coil Extra heating coil with 3-way balancing control valve supplied by external hot water.
- Hot gas post-heating Used to maintain the desired room temperature in the event of an increase in relative humidity, adding sensible heat to the air which has already been cooled and dehumidified. Operation occurs by advantageously exploiting part of the hot gas taken from the compressor discharge, conveying it to a coil located downstream of the cooling section.
- Steam humidifier Immersed electrode steam humidifier with electronic controller featuring proportional control fitted with humidity probe on the air intake and steam distributor.
- Differential pressure switch for dirty air filters Differential pressure switch suitable for measuring a pressure difference between the air intake and outlet in the filter section. In the event where the differential pressure is greater than the set value, a remote alarm is signalled.
- Soundproofing panels The panels are lined on the inside with micro-perforated metal plate for the maximum sound insulation.
- Serial communication module to PC or BMS Serial connection kit for connecting the unit control module to a centralised control system (PC or BMS).
- Phase monitor Used to check the presence and the correct sequence of the phases of the power supply.
- Flooding sensor Floor water sensor to detect leaks from the water circuit, with remote alarm.
- Adjustable support frame Height adjustable support frame using painted telescopic columns (RAL 7016). Adjustment is possible from 300-500mm or from 500­700mm.
- Adjustable support frame with duct Height adjustable support frame using painted telescopic columns (RAL 7016), fitted with aluminium deflector that deviates the flow of air leaving the unit. Adjustment is possible from 300-500mm or from 500­700mm.
- Front outlet plenum Plenum for front air discharge, outlets with double row of painted "aluzink" adjustable fins (RAL7016).
- Outlet plenum on three sides Plenum for air discharge from three sides, outlets with double row of painted adjustable fins (RAL 7016).
- Clock Programmable clock for automatic starts, set point changes and time band settings.
- Condensate drain pump The condensate drain pump is used to discharge the water present in the pan to the outside, when the outside discharge point is higher than the pan. The pump is controlled automatically by a built-in level sensor.
- Isolating damper The air outlet damper, controlled by an actuator with spring return, isolates the unit when it is not in operation.
- EU5 air filter Filter made up of a galvanised plate frame with galvanised and electric-welded protective mesh, and regenerable filtering media made from polyester fibre sized with synthetic resins. Efficiency F5 according to CEN-EN 779 standard (classification EU5 according to Eurovent 4/5 – average colorimetric efficiency between 40% and 60% ASHRAE 52-76 Atm). Self-extinguishing (resistance to flame class 1
- DIN 53438).
- Liquid line solenoid valve Solenoid valve used to prevent the unwanted migration of refrigerant during inactivity.
4
AIR INTAKE CONFIGURATIONS
1
2
Possible configurations: 1 = outlet downwards with intake from the front (M3 or D)
2 = outlet upwards with intake from the front (M5 or U)
WARNING: When positioning the unit, leave enough space at the front to inspect the air filters and all
the components subject to checks. To the side of the fittings leave enough space for connections and checks.
5
AIR OUTLET DIMENSIONS
CBA
D E F
C BA B D
E F G
A
A
B
B
H
I
SEZ. B-B 61-71/81
SEZ. A-A
17-25-31/41
I = air outlet downwards II = air outlet upwards
Sizes
Dimensions
A B C D E F G H I
17-25-31 170 300 280 195 255 40 --- 630 260
41 260 335 330 173 285 32 --- 805 260
61-71 140 305 335 165 200 250 40 1130 260
81 145 333 489 200 172 285 33 1370 260
6
REMOVAL OF THE PANELS
1
3
9
4
5
6
7
8
2
Legend:
1) outlet grill for the version with outlet upwards
2) to remove the side panels, unscrew the 4 inner screws
3) right side panel
4) service panel (can be drilled for connections)
5) service connection
6) inside bottom panel
7) outside bottom panel
8) outside top panel (single piece with the outside bottom panel for sizes 17-25-31-41)
9) left side panel
7
UNIT WITH ONE FAN, INSIDE VIEW (17-25-31-41)
1
2
3
4
5
6
10
11
9
8
13
14
18
19
20
22
23
15
12
17
16
7
21
Legend:
1) control panel
2) main isolator switch
3) LCD display
4) electrical panel
5) humidity probe (optional)
6) inlet air temperature probe
7) liquid gauge
8) heater section (optional)
9) hot water or hot gas coil (optional)
10) air filter (optional EU5)
11) evaporating coil
12) steam humidifier (optional)
13) flow differential pressure switch
14) filter differential pressure switch (optional)
15) liquid line solenoid valve (optional)
16) dewatering filter
17) bypass cock
18) hot water control valve
19) outlet fan
20) compressor
21) user terminal block (with Isolert3+ option)
22) outlet air temperature probe (optional)
23) power supply input and connections
8
UNIT WITH TWO FANS, INSIDE VIEW (61-71-81)
1
2
3
4
5
6
10
11
9
8
13
14
20
21
23
24
16
12
17
15
7
22
18
19
20
Legend:
1) control panel
2) main isolator switch
3) LCD display
4) electrical panel
5) humidity probe (optional)
6) inlet air temperature probe
7) liquid gauge
8) heater section (optional)
9) hot water or hot gas coil (optional)
10) air filter (optional EU5)
11) evaporating coil
12) steam humidifier (optional)
13) flow differential pressure switch
14) filter differential pressure switch (optional)
15) liquid line solenoid valve (optional)
16) dewatering filter
17) bypass cock
18) hot water control valve
19) outlet fan
20) compressor
21) user terminal block (with Isolert3+ option)
22) outlet air temperature probe (optional)
23) power supply input and connections
For details of the water and gas connections, see the corresponding sections Water connections and Refrigerant pipes.
9
OUTLET PLENUM (optional)
A
B
C
I = air outlet from the front
II = air outlet on 3 sides
Sizes Dimensions A x B x C
17-25-31 750 x 490 x 450
41 925 x 490 x 450
61-71 1250 x 490 x450
81 1500 x 490 x450
The grills are double row (vertical - horizontal) and can be oriented as desired.
10
ASSEMBLY OF THE OUTLET PLENUM
2
1
Assembly phases:
1) unscrew the screws fastening the front grill
2) fasten the plenum to the unit at the points indicated in the figure, using the fastening screws supplied
3) replace the front grill
11
ADJUSTABLE SUPPORT FRAME (optional)
Available in two heights, 300-500 mm and 500-700 mm
I = exploded diagram * = with duct option II = fastening the frame + = with 500-700 height option
Legend:
A) frame B) rear duct support bracket C) duct D) front or rear bracket E) adjustable leg F) duct side bracket G) side bracket
Assembly diagram
X) M6 screws on inserts Y) Screw and bolt Z) Self-tapping screw
A
*B
*C
+D
+G
E
*F
x
x
y
z
z
z
GRANDEZ
ZED
IM ENSI
O
N
I
1
7-25-314161-7181700x490xH875x490x
H1200x490x
H1450x490xH
SIZES
DIMENSIONS
CLIVET S.p.A. - Z. I. 32030 VILLAPAIERA - FELTRE (BL) Italy - Tel 0439 3131 - Fax 0439 313300 - sito web: www.clivet.com
The information presented in this manual is not binding and may be changed by the manufacturer without notice. All rights reserved.
DIMENSIONS
C
A
B
Sizes 17 25 31 41 61 71 81
A mm 750 750 750 925 1250 1250 1500 B mm 490 490 490 490 490 490 490 C mm 1800 1800 1800 1800 1800 1800 1800
R4D2GB-3
DIRECT EXPANSION CLOSE CONTROL UNIT WITH REMOTE CONDENSER
MR-DX 17-25-31-41-61-71-81
RECEPTION
CONTENTS:
1.0 - INSPECTION UPON DELIVERY
2.0 - HANDLING
2.1 - HANDLING using a FORK LIFT TRUCK or SIMILAR
2.2 - HOISTING using a CRANE or SIMILAR
3.0 - STORAGE
4.0 - REMOVING THE PACKING
5.0 - POSITIONING
1.0 - INSPECTION UPON RECEIPT
The units are delivered in special protective packing. When it arrives check the unit has not been damaged during transport and that it has been supplied complete with all the parts specified in the order. If there is any
visible damage make a note of it on the transport document, accompanied by the words: “ ACCEPTED
WITH RESERVATIONS DUE TO OBVIOUS DAMAGE TO PACKING ” since the delivery free at factory includes
cover for damage to be borne by the insurers in compliance with Italian law N° 450 of 22.08.85 “limite di
risarcibilità”.
IMPORTANT
EVERY OPERATION DESCRIBED BELOW MUST BE CARRIED OUT IN COMPLIANCE WITH THE SAFETY
REGULATIONS IN FORCE CONCERNING BOTH THE EQUIPMENT USED AND THE OPERATING PROCEDURES
ADOPTED.
WARNING
ALWAYS MAKE SURE THE LIFTING CAPACITY OF THE EQUIPMENT USED IS SUITABLE FOR THE WEIGHT OF THE
UNIT IN QUESTION BEFORE CARRYING OUT ANY HANDLING OPERATIONS.
Unit weight table
Size 17 25 31 41 61 71 81
Downflow weight Kg 166 170 170 218 265 275 295 Upflow weight Kg 176 180 180 231 280 290 310
2.0 - HANDLING
2.1 - HANDLING using a FORK LIFT TRUCK or SIMILAR
2.1.1 - Insert the forks in the wooden platform supplied with the unit.
2.1.2 - Start lifting the unit, making sure that it is balanced and stable. Bear in mind that the heaviest part is where the compressor is installed.
CLIVET S.p.A. - Z. I. 32030 VILLAPAIERA - FELTRE (BL) Italy - Tel (0439) 3131 - Fax (0439) 313300 – Web site http://www.clivet.com
The information presented in this manual is not binding and may be changed by the manufacturer without notice. All rights reserved.
2.2 - HOISTING using a CRANE or SIMILAR
2.2.1 - Insert the self-balancing fork in the long side of the wooden base supplied with the unit.
2.2.2 - Place boards on the upper edges of the unit to protect against damage.
2.2.3 - Gradually tension the lifting straps, checking that they remain in position.
2.2.4 - Lift the unit, ensure that the unit is perfectly balanced and stable. Bear in mind that the heaviest part is where the compressor is installed.
WARNING
FOLLOWING THE ADVICE ON THE OUTSIDE OF THE CARDBOARD PACKING WILL ENSURE THE UNIT REMAINS IN PERFECT CONDITION AND OPERATES CORRECTLY, TO THE BENEFIT OF THE END USER. THIS ADVICE IS AS FOLLOWS :
- HANDLE WITH CARE
- KEEP DRY
- UNDER NO CIRCUMSTANCES EVER PLACE OTHER OBJECTS ON TOP OF THE UNIT
3.0 - STORAGE
- Store away from: direct sunlight, rain, sand and wind
- Temperature: maximum 60°C, minimum -10°C
- Maximum humidity: 90%
4.0 - REMOVING THE PACKING
4.1 - Remove the packaging, taking care to avoid damaging the unit.
4.2 - Remove the brackets which hold the unit on the wooden platform using a 10 mm spanner.
4.3 - Lift the unit off the platform.
4.4 - Lower the unit to the ground in the installation point desired
4.5 - Check for any visible damage.
4.6 - Dispose of the packing so that it is taken to specialist collection or recycling centres (respect the regulations in force).
5.0 - POSITIONING
5.1 - Check that the area where the unit is to be located is level and can support the weight involved.
5.2 - Prepare the holes in the floor, in the ceiling and in the adjacent walls for all the service connections: air outlet, refrigerant pipes, humidifier water supply, condensate and humidifier drain, electrical cables. When required, position the support frame, adjust the height so that it corresponds to the raised floor, and check that it is level.
5.3 - Make sure there is a suitable condensate discharge near the site where the unit is installed. If gravity draining
is not possible, an electric condensate drain pump must be installed.
5.4 - The doors and panels should be removed and positioned in a safe place to prevent them from being damaged during the various phases of installation.
5.5 – The MR units with outlet upwards have been designed to discharge the air through an upper outlet with adjustable louvers. If an outlet duct is required, this should be fitted before all other connections to refrigerant pipes or the electrical line. All ducts fastened to the unit must be easily removable so as to allow access to the unit from above.
M4D2GB-3
DIRECT EXPANSION CLOSE CONTROL UNIT WITH REMOTE CONDENSER
MR-DX 17-25-31-41-61-71-81
ROUTINE MAINTENANCE
CONTENTS:
1.0 - ROUTINE MAINTENANCE
1.1 - UNIT
1.2 - WATER SYSTEM
1.3 - ELECTRICAL SYSTEM
1.4 - AIR DUCTING
1.5 - FANS
1.6 - HUMIDIFIER
1.7 - HEATERS
IMPORTANT
MAKE SURE THE UNIT IS NOT CONNECTED TO THE POWER SUPPLY BEFORE STARTING ANY MAINTENANCE OR
CLEANING OPERATIONS
1.0 - ROUTINE MAINTENANCE
This section is intended for the end user and contains information that is extremely important to ensure the unit has a long, trouble free service life. Scrupulously carrying out the few simple operations described below at regular intervals can avoid the need for servicing by specialist personnel. The operations which need to be carried out do not require any special technical knowledge, involving the following simple checks on the components of the unit:
- AIR FILTER CLEANING
- EVAPORATOR COIL
- STRUCTURE
1.1 - UNIT
1.1.1 – AIR FILTER CLEANING (SEE AIR FILTER SECTION).
1.1.2 - EVAPORATOR COIL IMPORTANT: accidentally touching the exchanger fins could cause minor cuts. This operation should be carried out using special gloves. It is essential for the evaporator coil to provide the maximum heat exchange. Consequently, the surface must always be kept free of dirt and deposits. Clean the coil, removing all impurities that may remain on the surface. Check that the aluminium fins are not damaged or bent, and if so, "comb" the coil using the special tool so as to restore the initial condition and ensure the optimum flow of air.
1.1.3 - STRUCTURE
- Check the condition of the parts forming the structure, paying particular attention to its steel components.
- Treat any rusted points of the unit with paints designed to eliminate or reduce this problem.
- Make sure that the unit’s casing panels are mounted firmly in place. Poor mounting can cause abnormal vibrations and noise.
1.2 - WATER SYSTEM
1.2.1 - CONDENSING DRAIN CONTROL It is recommended periodical checking of the drain condensing panel of the unit. The dust or calcareous residues could lead to obstructions.
1.3 - ELECTRICAL SYSTEM
- Make sure there are no cuts, cracks or other signs of deterioration indicating a possible loss of insulating capacity in the power cable that connects the unit to the distribution board. Contact an authorised service centre if any maintenance operations are required
1.4 - AIR DUCTING
- Check that the fixing screws of the ducting and corresponding structures have not loosened. Loose screws are the source of vibrations and therefore noise.
- Check any antivibration systems installed in the ducting to avoid vibration transmission
1.5 - FANS Before staring the unit each season, check the status of the fans.
- Before starting the unit each season, check the fastening of the fans to the structure of the unit.
- Also check that the impeller is perfectly aligned and has not become dangerously unbalanced, as highlighted by abnormal noise and vibrations.
2
1.6. - HUMIDIFIER
1.6.1 - Components to be checked or replaced The steam humidifier has only one part that requires periodical replacement: the steam production cylinder. This operation is necessary when the lime scale that forms inside the cylinder prevents the sufficient flow of current. This situation is signalled on the control board by the LEVEL LED, which flashes. The frequency of this operation depends on the supply water: the more salt or impurities in the water, the more frequently the cylinder will need to be replaced.
The following parts need to be checked annually:
• fill/drain solenoid valve: clean away any solid deposits, without using compressed air, and check correct operation.
• water circuit/supply tank: clean away any deposits in the path travelled by the water from the supply valve to the cylinder. Finally, check that there are no leaks or drips.
• steam outlet pipe/condensate drain: check that along the path, from the humidifier to the distributor in the duct or the room, the pipe is not choked, which would prevent the normal release of steam/condensate.
• humidity probes: check the condition of the probes, and if necessary, re-calibrate them. Do not use compressed air or solvents to clean the probe sensor.
Warning: if placing the unit out of service, completely empty the water from the cylinder.
1.6.2 - Replacing the cylinder
To remove the cylinder, proceed as follows.
• Completely drain the water by pressing the “DRAIN” button on the control board.
• Disconnect the power supply to the humidifier using the isolating switch on the unit.
• Remove the steam pipe from the cylinder.
• Disconnect the electrical connections from the electrodes and remove the plugs from the high level electrodes.
• Unscrew the nut to remove the flare coupling and the filter (when the filter is outside the cylinder)
• Lift the cylinder to pull it out.
Before replacing it:
• The filter body does not need to be replaced, consequently, wash it in water and reposition it on the new cylinder using the new gasket supplied with the latter.
• Check the gasket between the cylinder and the drain assembly.
• Replace the cylinder, repeating the same operations in the reverse order.
1 - pipe locking spring 2 - steam pipe 3 - fill pipe 4 - steam cylinder 5 - O-ring 6 - fill valve 7 - valve supports 8 - drain valve 9 - bottom sump 10 - pipe locking spring 11 - fill pipe 12 - overflow pipe
IMPORTANT
AUTHORISED PERSONNEL SHOULD BE PRESENT WHEN STARTING THE UNIT EACH SEASON, SO AS TO CARRY
OUT BOTH THE ABOVE CHECKS AND THE CHECKS ON THE REFRIGERANT CIRCUIT.
CLIVET S.p.A. - Z. I. 32030 VILLAPAIERA - FELTRE (BL) Italy - Tel 0439 3131 - Fax 0439 313300 - Web site: www.clivet.com
The data contained in this manual is not binding and may be changed by the manufacturer without prior notice. All reproduction, even partial, is prohibi ted.
3
1.7 – HEATERS
The unit is supplied with finned convection heaters that require periodical checking of their cleanliness and their fastening to the support.
If requiring replacement, follow the instructions below, with reference to the figure:
1) -Remove the outlet grill A (version with outlet upwards) or the top access panel (outlet downwards).
2) - Remove the side panels B.
3) - Release the springs C that fasten the heaters to the supports.
4) - Remove the heaters D.
1
2
D
C
B
A
B
F4D2GB-3
DIRECT EXPANSION CLOSE CONTROL UNIT WITH REMOTE CONDENSER
MR-DX 17-25-31-41-61-71-81
START-UP
CONTENTS:
1.0 - PRELIMINARY CHECKS
1.1 - ELECTRICAL PANEL
1.2 - COMPRESSORS
2.0 – STARTING THE UNIT
4.0 – SET POINT AND INTERFACE
1.0 - PRELIMINARY CHECKS
- Check that the unit is positioned correctly and that the air and water connections have been performed correctly.
- Check the power supply voltage and frequency:
WHICH MUST BE WITHIN THE FOLLOWING VALUES
400/3/50 ± 10% The phase unbalance must be less than a maximum of 3%
(see calculation example). Calculation example:
L1 - L2 = 388V L2 - L3 = 379V L3 - L1 = 377V
The mean of the values measured is obtained by:
388 379 377
3
++
= 381
The maximum deviation of the mean is obtained by:
388-381=7 V
The unbalance is obtained by:
7
381
x 100 = 1,83% (accettabile)
IMPORTANT: The following operations must only be performed by suitably trained and authorised personnel. Before starting the following operations, ensure that the power supply is disconnected from the unit at the source and that the isolator device is padlocked and marked by a special warning sign.
1.1 - ELECTRICAL PANEL
- Check that the screws fastening the wires to the electrical components in the panel are tight (vibrations during handling and transport may have caused these to loosen).
- Close the control and power circuit breakers.
- Close the door on the electrical panel.
- Connect the power line to the unit.
- Close the main line isolator switch.
1.2 - COMPRESSORS
The scroll compressors used in these units are very noisy if rotating in the wrong direction. If this occurs, reverse two phases of the electrical power line. The power input of the compressor must be lower than the FLA value declared (seen under “electrical connections”).
(acceptable)
CLIVET S.p.A. - Z. I. 32030 VILLAPAIERA - FELTRE (BL) Italy - Tel (0439) 3131 - Fax (0439) 313300 - sito web http://www.clivet.com
The information presented in this manual is not binding and may be changed by the manufacturer without notice. All rights re served.
2.0 – STARTING THE UNIT
When the unit is powered, with the main isolating switch rotated in position I, and in standby, the “line” LED on the interface is on and the display shows:
Clock and weekday, if the optional clock card is installed.
Room temperature and corresponding unit of measure.
Ambient humidity and corresponding unit of measure in % (if the optional humidifier and probe are present).
The OFF status of the remote switch, if present.
Thermometer, indicating that the value displayed is
the temperature.
At this point, turn the remote on/off switch on (on the display, the text OFF will be replaced by ON). If the switch is not present, proceed as follows.
Press the On/Off button on the interface, causing the following actions:
The green “on” LED associated with the On/Off button will light up.
The display will show the symbols corresponding to the actuators that, depending on the set point and the parameters set, should start operating.
The compressor starts after a delay of 20 seconds from the start of the fan, which itself starts immediately if requested to operate. The fan, in all phases (cooling, heating, humidification and dehumidification) always starts first.
The following are the symbols shown on the display when the unit is operating, indicating the operating status of the unit.
3.0 – STOPPING THE UNIT
To stop the unit, press the ON/OFF button; all the actuators will switch off except for the fan, which will stop after a delay of 20 seconds. The two green LEDs go off to signal that the unit is in standby. At this point, the isolating switch on the door of the panel can be turned to position 0.
4.0 – SET POINT AND INTERFACE
To set the set point and use the interface, refer to the section on the control of the unit.
SHORT DISPLAY LEGEND
Fan on
Cooling active, 1 and 2 refer to the cooling actuators
Heating active, 1 and 2 refer to the heating actuators (optional).
Humidification active (optional).
Dehumidification active (optional)
C4D2GB-3
DIRECT EXPANSION CLOSE CONTROL UNIT WITH REMOTE CONDENSER
MR-DX 17-25-31-41-61-71-81
CONTROLS
CONTENTS:
1.0 – DISPLAY AND KEYPAD
1.1 - THE DISPLAY
1.2 - OPERATING SIGNALS
1.3 - THE KEYPAD
1.4 - MODIFYING THE PARAMETERS
1.5 - CONTROL PARAMETERS
1.6 - READ ONLY PARAMETERS
1.7 - DIAGRAMS
2.0 - ALARMS
2.1 - MANUAL, AUTOMATIC ALARMS AND RESET
2.2 - SHUT-DOWN SIGNAL
2.3 - OPTIONAL ALARMS
2.4 - DIAGNOSTICS
3.0 - OPTIONS
1.0 – DISPLAY AND KEYPAD
Table 1
Room temperature in programming mode displays the value of the parameter
Temperature unit of measure: degrees Centigrade/Fahrenheit
Ambient humidity in programming mode displays the no. of the parameter
Relative humidity unit of measure
Buzzer active
Hour counter limit exceeded
Off from time bands
Time bands active
External contact status:
- ON – enable unit
- OFF – unit in standby
Indicates that the value displayed is the temperature
(without this symbol on, the Set Point is displayed)
Time band selected
Dehumidification active
Fan active :% fan speed
Cooling active:
- number (1 or 2) of cooling actuators; % opening of cooling valve, or (in shelter mode) % opening of freecooling damper
Heating active:
- number (1 or 2) of heating actuators
- % opening of valve
Humidification active: % steam production
Programming phase
- set password
- lock parameter modification
(In clock operation) weekday
-
display clock
- setup clock
1.1 - THE DISPLAY The display shows the main values monitored, and the status of the unit and the actuators. Table 1 to the side lists the symbols and the texts shown on the display, with the corresponding meanings.
N.B. Fig. 1 illustrates all the symbols and texts shown on the display when the controller is started.
Fig. 1
1.2 - OPERATING SIGNALS
The main states of the controller (power supply, alarm active and remote On/Off input status) are indicated by 3 LEDs on the front panel.
Meaning of the LEDs: Line LED (yellow): controller powered Alarm LED (red): alarm active on the unit (the siren symbol on
the display is on only when the buzzer is active) On LED (green): unit On. The effective On status of the unit may also depend on the position of the remote On-Off switch, on the active time band (function enabled only if the clock card is fitted), on the standby condition transmitted by the master unit (when a series of units are in rotation), and is indicated by the fan symbol.
The ON-OFF symbols on the display indicate the status of the remote on/off switch. If the switch is not fitted, the display will always show the ON symbol.
2
1.3 - THE KEYPAD
ON/OFF: Switches the status of the unit; if on, pressing the button places it in Standby; vice-versa, it is reactivated.
ALARM / Prg: When an alarm is present, mutes the buzzer; if the clock option is present, in programming phase sets the time.
UP: In programming phase, scrolls or increases the value of the parameters. If the clock option is present,
each time the button is pressed the following are displayed, in sequence: the current time, the date and the room temperature.
DOWN: Held displays the set point. In programming phase, scrolls or decreases the value of the parameters.
ENTER / Sel: Pressed for 5s accesses the parameters. In programming phase, changes the value of the selected parameter (see par. 1.4 ­Modifying the parameters). If the clock option is
present, in programming phase sets the time.
UP + DOWN pressed together for 2s reset the alarms.
1.4 - MODIFYING THE PARAMETERS
Press the ENTER button for 5s, the value of the first accessible parameter will be displayed, and in the top right, the code of the parameter, flashing.
Scroll the various parameters using the UP and DOWN buttons.
Pressing ENTER again displays the value, flashing, of the selected parameter, while the UP and DOWN buttons change the value.
Press ENTER again to temporarily save the new value. Then, use the UP and DOWN buttons to scroll the menu of the parameters, repeating the previous operations for each parameter to be modified.
Press the ALARM button, on the other hand, to store the changes made.
Adjusting the contrast of the LCD
The contrast of the display can be adjusted according to the effective angle of viewing. Pressing the ENTER and UP buttons together increases the value, vice-versa, ENTER and DOWN decrease it.
1.5 - CONTROL PARAMETERS
r1 Temperature set point (cooling)
Used to set the temperature set point in cooling (see diagrams at the end of the paragraph).
Default: 20.0
r2 Cooling differential
Used to set the differential in cooling mode (see diagrams at the end of the paragraph).
Range: 0.1-11.0°C Default: 3.0
r3 Heating differential
Used to set the differential in heating mode (see diagrams at the end of the paragraph).
Range: 0.1-11.0°C Default: 2.0
r4 Temperature dead zone
Used to set the dead zone (see diagrams at the end of the paragraph). When the air inlet temperature is inside the dead zone, all the actuators are off, except for when the compressor is operating following a dehumidification request.
Range: 0.1-11.0°C Default: 1.0
WARNING: THE PARAMETERS FROM r5 TO r8 ARE PRESENT ONLY TOGETHER WITH THE HUMIDITY PROBE OPTION
r5 Humidity set point
Sets the humidity set point (see diagrams at the end of the paragraph).
Default: 50
r6 Humidification differential
Sets the differential for humidification (see diagrams at the end of the paragraph).
Range: 1-20%rH Default: 4
r7 Dehumidification differential
Sets the differential for dehumidification (see diagrams at the end of the paragraph).
Range: 1-20%rH Default: 3
r8 Humidity control dead zone
Used to set the dead zone (see the diagram at the end of the paragraph). When the humidity measured by the humidity probe is inside this zone, the humidifier and the dehumidification function are not active.
Range: 1-20%rH Default: 2
r9 Temperature set point (heating)
Heating set point, does not affect the operation of the machine, its setting is superfluous.
Default: 18.0
rt Time band setting
If the clock option is installed, used to set time band mode (see chap. 3) 0= time bands disabled 1= temperature monitoring 2= On/Off
Range: 0-2 flags Default: 0
1.6 - READ ONLY PARAMETERS
rP Humidity probe reading Percentage of humidity. Only with probe installed. rr Probe B4 reading Outlet air temperature. Displayed only with probe installed. c9 Hour counter, compressor 1 cA Hour counter, compressor 2
Indicates the number of operating hours for compressor 1 and/or 2. The reading of cA has no meaning, as only one compressor is used.
FA Hour counter, outlet fan
Indicates the number of operating hours of the fan.
FC Hour counter, filter
Indicates the number of operating hours of the filter.
Hr Software version
Displays the version of the software.
3
1.7 - DIAGRAMS
Temperature control diagram
Compressor + electric heaters
The diagram to the side highlights the operation of the compressor and the heaters to bring the temperature from outside the limits r2 and r3 to limit r4. In cooling mode, the compressor starts operating at the end of r2, across the entire band, until the temperature returns inside the dead zone r4. In the heating phase, the 2 triads of heaters start respectively at half of the differential (r3/2) and at the actual limit (r3/2+r3/2). When the temperature starts returning the second triad is deactivated at half of the differential (r3/2) and the first triad is deactivated at r4. Ht and Lt are respectively the high and low temperature limits, over which the alarms Ht and Lt are activated. These alarms are reset automatically 1 degree above (Lt) and 1 degree below (Ht) the threshold.
Temperature control diagram
Compressor + 3-pos. valve
The diagram to the side is typical of machines fitted with a water heating coil. The trend highlights the operation of the water valve and the compressor to bring the temperature back from outside the differential limits r2 and r3 to the limit of the dead zone r4. The zone r3 represents the modulation band for the heating actuator, while r2 is the operating band of the compressor. The valve opens further the more the temperature moves away from the set point (r1), and reaches the maximum value outside of the differential limit r3.
Humidity control diagrams
Humidification + dehumidification control
The diagram highlights the operation of the compressor and the humidifier to bring the value of the humidity, when outside of the limits of the differential r6 and r7, back into the dead zone r8. In the dehumidification phase, the compressor operates even if the temperature is below the set point r1, while in humidification phase the humidifier operates along a ramp (0-10Vdc), proportionally to the humidity request. In dehumidification mode, exceeding the LOW LIMIT, equal to 3/2*r3 (see the temperature control diagram above) causes the compressor to stop, ignoring the dehumidification request, while the heating actuators (hot water coil, heaters or hot gas coil), which are activated as soon as the temperature falls below the set point, continue to operate according to the type of control set, until the temperature reaches the SET POINT, above which the compressor starts operating again so as to dehumidify. Exceeding the high (HH) and low (LH) humidity limits produces the corresponding alarms, with reset automatic and an hysteresis of 1% RH.
4
Temperature control diagram
Compressor + post-heating coil
Dehumidification
only
-{}­The post-heating hot gas coil, unlike the other heating actuators, starts when the temperature is below the set point and the machine is operating in dehumidification mode. The two conditions, temperature and humidity, are controlled at the same time. The coil is activated over the lower limit of r3, and operates across the entire band until the lower limit of r4.
2.0 - ALARMS
2.1 - MANUAL, AUTOMATIC ALARMS AND RESET
When an alarm occurs, the unit performs the following actions:
activation of the buzzer and display of a signal (with unit On);
energising of the alarm relay.
display of the alarm code and red LED on.
In this condition, pressing the ALARM button mutes the buzzer. When the alarms with automatic reset are no longer present, if no alarms with manual reset are active, the following occurs:
buzzer off;
deactivation of the alarm relay;
red alarm LED switches off;
reactivation of the actuators stopped due to the
alarm.
Pressing the UP and DOWN buttons together, for 2s, cancels the display of the alarm code. In the event of alarms with manual reset, pressing the UP and DOWN buttons together, for 2s, performs the following actions:
deactivation of the alarm relay;
red alarm LED switches off;
reactivation of the actuators stopped due to the
alarm. The alarm messages are displayed cyclically in the progressive order indicated in Table 2. At the end of the cycle the percentage of humidity is displayed (if featured) for 6 s.
2.2 - SHUT-DOWN SIGNAL
A relay that is de-energised when an alarm occurs is used for the alarm signal. The relay features a 24V, 1A changeover contact, available via the user terminal block. Terminal C6: power supply common. Terminal NC6: NC contact for the remote alarm signal. Terminal NO6: NO contact for the remote “no alarm” signal.
2.3 - OPTIONAL ALARMS
Flooding, fire or smoke sensor.
Optional devices are available to signal flooding or the presence of fire or smoke. The alarm signal, which is also active in standby, stops the unit, and it can only be reset manually once the alarm conditions are no longer present.
Phase monitor.
This measures the exact connection sequence of the phases, activating an alarm if the machine is not powered as shown on the wiring diagram. The alarm is manually reset.
Differential pressure switch for dirty filters
When the air filter is dirty or clogged and the flow-rate of the air intake falls below 40-50%, the filter differential pressure switch is activated. A signal-only alarm is activated, which is reset automatically when the causes are no longer present.
Loading...
+ 51 hidden pages