CLIVET EVH Space 21, EVH Space 25, EVH Space 41, EVH Space 51, EVH Space 31 Installation And Maintenance Manual

...
EVH SPACE 21-101
INSTALLATION AND MAINTENANCE MANUAL
M27B40A6-05(EC1)
30-10-13
Dear Customer, We congratulate you on choosing an ELFOSystem product, the air conditio-
ning system at annual cycle that offers the possibility in a sole system of meeting all the heating, conditioning and domestic hot water needs.
Clivet is being working for years to offer systems able to assure the maxi­mum comfort for long time with high reliability, efficiency , quality and safety. The target of the company is to offer advanced systems, that assure the best comfort, reduce the energy consumption, the installation and main­tenance costs for all the life-cycle of the system.
With this manual, we want to give you information that are useful in all the phases: from the reception, to the installation and use until the disposal so that a system so advanced offers the best procedure of installation and use.
Best regards and have a nice reading !
CLIVET Spa
The data contained in this manual is not binding and may be changed by the manufacturer without prior notice. All reproduction, even partial, is prohibited.
2
INDEX
General
1
Riception
2
Positioning
3
Water connections
4
5
Aeraulic connections
6
Electrical connections
7
Start-up
8
Control
9
Maintenance
4
6
7
9
11
12
5
18
21
10
Residual risks
Decommissioning
11
12
Technical information
24
25
26
3
1 - GENERAL
1.1 MANUAL
The manual provides correct unit installation, use and maintenance.
Fare particolare attenzione ad : WARNING indicate particularly important operations or
information. PROHIBITED indicate operations that must not be carried out,
that compromise the operating of the equipment or may cause damage to persons or things.
It is advisable to read it carefully so you will save time
during operations.
Follow the written indications so you will not cause
damages to things and injuries people. The preliminary information must be read prior to carrying out any of the following operations.
1.2 GENERAL INSTRUCTIONS Preliminaries
The positioning, hydraulic system, refrigerating, electrics and the channelization of the air must be determined by the system designer in accordance with the local regulations.
Only qualified personnel can operate on the unit, as required by the regulation in force.
Using the unit in case of breakdown or malfunction
voids the warranty
may compromise the safety of the machine
may increase time and repair costs.
Follow local safety regulations. Keep packing material out of children’s reach it may be dangerous. Recycle and dispose of packing material in conformity with local regulations.
Risk situations
The unit has been designed and created to prevent injures to people. During designing it is not possible to plane and operate on all risk situation. Read carefully "Residual risk" section where all situation which may cause damages to things and injuries to people are reported. Installation, starting, maintenance and repair required specific knowledge; if they are carried out by inexperienced personnel, they may cause damages to things and injuries people.
Intended use
Use the unit for the:
- air treatment.
Follow the limits defined in the technical bulletin and on this manual.
Not treat air containing :
high concentration of dust;
aggressive substances ;
residual of industrial processes.
Any use other than intended does not involve the manufacturer in any commitment or obligation.
Installation
Verify that the electrical line characteristics are in compliance with data quotes on the unit serial number label.
Maintenance
Plan periodic inspection and maintenance in order to avoid or reduce repairing costs.
Turn the machine off before any operation.
Modification
All unit modifications will end the warranty coverage and the manufacturer responsibility.
Breakdown/Malfunction
Disable the unit immediately in case of breakdown or malfunction. Contact a constructor certified assistance service Use original spares parts only. .
User training
The installer has to train the user on :
start-up / shutdown;
set points change;
standby mode;
Maintenance;
what to do / what not to do in case of breakdown.
Data update
Continual product improvements may imply manual data changes
Visit manufacturer web site for updated data.
1.3 INDICATIONS FOR THE USER
Keep this manual with the wiring diagram in an accessible place for the operator.
Note the unit label data so you can provide them at the assistance centre in case of intervention (see "Unit identification" section)
Provide a machine notebook that allows any interventions carried out on the machine to be noted and tracked making it easier to suitably note the various interventions and aids the search for any breakdowns.
In case of breakdown or malfunction:
immediately deactivate the unit.
Contact a constructor certified assistance service.
Use original spares parts only.
Ask the installer to format on:
start-up / shutdown
set points change
standby mode
maintenance
what to do / what not to do in case of breakdown
4
1 - GENERAL
1.4 UNIT IDENTIFICATION Serial number label
The serial number label is positioned on the unit and allows to indentify all the unit features.
It has not to be removed for any reason. It reports the regulations indications such as:
Machine type
series EVH-SPACE
Size 21 ....101
Serial number
xxxxxxxxxxxx
Year of manufacture
Wiring diagram number
Electrical data
Manufacturer logo and address
Serial number
It identifies uniquely each machine. It identifies specific spare parts for the machine
Assistance requests
Note data from the serial number label and write them in the chart on side, so you will find them easily when needed.
In case of intervention you have to provide data
Serie
Size
Serial number
Year of manufacture
Wiring diagram
5
2 - RECEPTION
2.1 INFORMAZIONI PRELIMINARI Generali
Operare rispettando le normative di sicurezza in vigore. Per le informazioni di dettaglio (dimensioni, pesi,
caratteristiche tecniche, etc) far riferimento al capitolo INFORMAZIONI TECNICHE.
Per effettuare le operazioni usare dispositivi di protezione: guanti , occhiali ecc.
Stoccaggio Rispettare le indicazioni riportate sull’esterno
dell’imballo. Movimentazione
Verificare peso dell’unità e capacità del mezzo di sollevamento.
Individuare i punti critici nel percorso di movimentazione : percorsi sconnessi, rampe, scalini, porte.
Considerare che il baricentro potrebbe essere spostato rispetto al centro dell'unità .
Assicurarsi che l’unità sia in equilibrio stabile. Rimozione imballo
Fare attenzione a non danneggiare l’unità. Riciclare e smaltire il materiale di imballaggio secondo
le norme locali.
A
2.3 MOVIMENTAZIONE CON IMBALLO
Sollevamento con forche:
Inserire le forche come indicato in figura.
È vietato sollevare più colli contemporaneamente
lasciandoli sciolti.
In caso di sollevamento di più unità contempora-
neamente deve essere utilizzato un contenitore idoneo.
2.2 CONTROLLO ALL’ARRIVO
Prima di accettare la consegna controllare:
Che l’unità non abbia subito danni nel trasporto
Che il materiale consegnato corrisponda a quanto
indicato sul documento di trasporto confrontando i dati con l’etichetta matricolare ‘A’ posizionata sull’imballo.
In caso di danni o anomalie :
annotare immediatamente sul documento di tra-
sporto il danno riscontrato e riportare la dicitura: “Ritiro con riserva per evidenti ammanchi/danni da trasporto”.
contestare via fax e con raccomandata A.R. al vet-
tore e al fornitore.
Le contestazioni devono essere effettuate entro 8 gior­ni dal ricevimento, le segnalazioni oltre tale termine non sono valide.
30°
2.4 RIMOZIONE IMBALLO
Tagliare le reggette di fissaggio.
Rimuovere l’imballo sollevandolo verso l’alto.
Rimuovere il nylon di protezione.
6
3 - POSITIONING
3.1 PRELIMINARY INFORMATION
Operate in compliance with safety regulations in force . For detailed information (dimensions, weight, technical
characteristics etc.) please refer to the “Technical information” section.
Use single protection devices : gloves, glasses ecc. . During positioning consider these elements :
technical spaces required for the machine and system
place where the machine will be installed
electrical connections
water connections
air / aeraulic ducts
Do not considerer these elements could decrease performances and operational life of the unit.
3.2 POSITIONING
Unit has been designed to be installed:
inside
in fixed positions
Limit vibration transmission:
use antivibration devices on unit bearing/supporting points;
install flexible joints on the hydraulic/ aeraulic/cooling
connections.
plan in the false ceiling the openings indicated in the
functional clearances to allow the access to the unit for the maintenance operations
Ceiling positioning : let free the projection to the ground
of the unit and of the functional clearances to allow the access with ladders or other means
Installation standards:
Safe accessible position;
avoid flood-prone places;
verify unit weight and bearing point capacity;
The functional clearances have to :
guarantee the unit good operating
allow the maintenance operations
safeguard the authorized operators and the exposed
person.
position the unit taking into consideration the clearances
indicated in the figure.
300
300
500
A
EVH SPACE A
21-71 550
81-101 620
7
3 - POSITIONING
Hanging
(1) Tapped bar M10 (M12 for sizes 81-91-101) (2) galvanized steel nuts (3) galvanized steel plain washer Ø external 30mm (4) rubber plain washer Ø external 30mm thickness 6mm (5) Anti-vibration rubber or spring (6) galvanized steel plain washer Ø external 40mm
3.3 THERMOSTAT POSITIONING (OPTIONAL)
The choice of the installation point is important for the comfort of the served area and the energy consumptions. The thermostat must be positioned:
in a room with medium temperature and humidity
conditions, representative of the other rooms;
at a height of 150 cm;
preferably on an inner wall;
Positions to avoid:
near heat sources;
exposed to direct solar radiation;
in a position with exhaust air from outlets or diffusers;
behind curtains or pieces of furniture;
- near doors and windows to the outside;
- on walls crossed by heating chimneys or pipes;
- on external walls.
in support
8
4 - WATER CONNECTIONS
4.1 PRELIMINARY INFORMATION
Selection and installation of system components must be
i
carry out by installer. Following a series of instructions that must be integrated with what required by local regulations and by the code of practise.
4.2 COMPONENTS
INTERCEPTING VALVES
Installed on the input and output, they allow to carry out all
the maintenance operations and possible without emptying the installation.
THERMOMETERS AND PRESSURE GAUGES:
Installed on the input and output of the main parts facilitate
the controls and the maintenance.
BLEED VALVES :
Installed in all the highest points of the system, they allow
the venting from the circuit.
BLEEDING COCKS :
Installed at the lowest points of the circuit, so as to allow
emptying .
EXPANSION TANK :
It allows the system correct pressure to be maintained at
the water temperature changing. It has to be sized according to the system water content.
WATER FILTER :
If it is not built-in, it has to be immediately installed at the
i
unit water inlet, in a position easily accessible for cleaning.
The filter should never be removed, the operation will void
the warranty.
SUPPORTS :
for the weight of the water piping that must not rest on the
unit fittings.
FLOW SWITCH
as a component of the system must always be provided.
4.4 CONDENSE DRAIN
The condense must be disposed of in order to avoid damaging things and persons.
Unit drain coupling: the connection must not transmit
mechanical stresses and must be carried out paying attention not to damage the unit drain coupling.
Foresee a siphon that, by eliminating the depression
caused by the fan, prevents suction of air from the drain piping.
The piping must have adequate slope to allow out flow.
Anchor the piping with an adequate number of supports.
On the contrary, cracking in the piping and air pockets
obstructing the outflow, are generated.
Isolate piping and siphon to avoid condense dripping.
Connect the condense drain to a rain drain network.
DO NOT use white waters or sewage drains to avoid
possible inhaling of odours in case of evaporation of the water contained in the si phon.
At work end, check the regular outflow of the condense by
i
pouring water in the bowl.
Siphon height calculation T = 2P S = T/2 P is the pressure determined by the fan in correspondence of the condense collection bowl (approx. 1 mm = 9.81 Pa)
Example :
P = 300 Pa = 30 mm T = 2P = 60 mm S = T/2 = 30 mm
4.5 RISK OF FREEZING
4.3 OPERATION SEQUENCE
Before connecting the unit, carefully wash the system by filling it and emptying it several times with clean water.
Ignoring this operation will lead to several filter cleaning interventions and at worst cases can cause damages to the exchangers and the other parts.
Execute leakage test before isolate the pipes. To avoid heat dispersions and formation of condensate isolate
all the pipes. Leave various point of service free (wells, vent-holes etc )
Adopt measures to prevent risk of freezing if the unit or
!
relative hydraulic connections can be subject to temperatures
near 0°C.
isolate the piping
protect the piping with heating cables laid underneath
the insulation
9
4 - WATER CONNECTIONS
WATER LOOP WITH CONSTANT WATER FLOW
WATER LOOP WITH VARIABLE WATER FLOW
(1) antifreeze protection (2) differential pressure switch, water side (3) Steel mesh filter on the water side (optional) (4) shut-off valve on the system water connections
(optional) (5) by-pass cleaning valve (optional) The dotted line indicates the supply limit of the stan-
dard unit (field A)
(1) antifreeze protection (2) differential pressure switch, water side (3) Steel mesh filter on the water side (optional) (4) shut-off valve on the system water connections
(optional) (5) by-pass cleaning valve (optional) (6) ON/OFF solenoid valve water side (optional) The dotted line indicates the supply limit of the stan-
dard unit (field A)
WATER SOURCE
(1) antifreeze protection (2) differential pressure switch, water side (3) Steel mesh filter on the water side (optional) (4) shut-off valve on the system water connections
(optional) (5) by-pass cleaning valve (optional) (6) Water side modulating valve (optional) The dotted line indicates the supply limit of the stan-
dard unit (field A)
10