CLIVET CPAN-XHE3 Installation And Maintenance Manual

CPAN-XHE3 size1 - size6
Make-up unit, full fresh air
With return/exhaust and thermodynamic heat recovery Reversible heat pump technology
Installation use and maintenance manual
Dear Customer,
Congratulations for having chosen this product.
Clivet has been working for years to offer the market systems able to assure maxi­mum and long-lasting wellbeing with high reliability, efficiency, quality and safety. The company aim is that to offer its customers developed systems that assure the best comfort, reduce energy consumptions and installation and maintenance costs for the entire life-span of the system.
With this manual, we intend giving information useful throughout all phases: from reception, to installation, to use and even disposal, so that such a developed system meets the best installation and use methods.
With kind regards and... good reading!
CLIVET Spa
TABLE OF CONTENTS
Generality .........................................
1
Receipt ..............................................
2
Positioning .......................................
3
Hydraulic connections ....................
4
Aeraulic connections ......................
5
Electric connections .......................
6
Start-up ............................................
7
Control .....................................
8
Maintenance ...................................
9
4
6
7
9
11
13
19
28
39
Residue risks ...................................
10
The data contained in this manual are not binding and can be changed by the manufacturer without prior notice.
Disposal ..........................................
11
Technical information .....................
12
45
46
47
3
1 - GENERALITY
!
i
1.1 General warnings
Purpose of the manual
This manual has been realised to enable a correct installation, adjustment and maintenance of the unit.
Manual instructions
It is of fundamental importance that the manual is carefully read. Pay particular attention to:
PROHIBITIONS indicate operations that cannot be carried out as they jeopardise the machine operation or can cause personal injuries or damage things.
WARNINGS indicate potentially dangerous or damaging situations.
INFORMATION indicate particularly useful information.
The manufacturing company declines every liability for any damages, directly or indirectly, to persons or things, following the non-compliance with these instructions.
Preserving the manual
This manual and the wiring diagram of the unit must be carefully kept and be available to the operator for future consultation.
Systems designing Installation, electric, hydraulic system, etc., must be defined
by enabled designers in accordance with the current standards.
Qualified personnel
The unit must be installed, tested and assisted by qualified personnel having the legal requisites.
Installation
The installation must be carried out in accordance with the local safety standards.
Electric network
Check that the features of the electrical network are conform with the data on the unit matriculation plate, found on the inside of the main electric control board.
Packaging
The packaging material (plastic bags, expanded polystyrene, nails, etc.) must be kept out of the reach of children as it is a potential source of danger and must be correctly recycled in accordance with the local standards in force.
Maintenance
Disconnect the electric power supply to the unit before carrying out any maintenance. The operations must be carried out in accordance with the local safety
standards.
Periodical checks
Carry out periodical checks to identify any loose, damaged or broken parts. The lack in repair
entails the risk of damages to things and personal injuries.
Fault – Malfunctioning
Disconnect the equipment in case of fault or malfunctioning.
Repair
For any repairs, only contact an after-sales technical assistance centre authorised by the manufacturer and request the use of original spare parts. The non-compliance with the above can jeopardise the safety of the equipment.
Modifications
Every liability is declined by the manufacturer with voiding of the warranty in the event of electrical and/or mechanical modifications. Tampering in general, not expressly authorised and not respecting that reported in this manual, void the warranty.
Destination of use
The unit must only be intended to be used for that it was expressly conceived:
CIVIL AIR CONDITIONING
Keep to the limits foreseen in the technical schedule and in this manual.
Any use different to that specified does not entail any kind of commitment or obligation by the manufacturer.
Safety integration principles
The unit is designed and manufactured so as not to expose the personal health and safety to risk.
In this regard, project solutions have been adopted act at eliminating, where possible, the possible causes of risk or significantly reduce the probability of the event-risk. Should it not have been possible to intervene during designing to prevent and/or eliminate the risk, refer to the behavioural prescriptions reported in the residue risks section.
Data update
The continuous improvements made to the product can determine variations to data, even without prior notice by the manufacturer.
User training
The installer must train the user, particularly on:
Switch-on/off Setpoint modification Stand-by Maintenance What to do/not to do in case of fault.
4
i
1 - GENERALITY
1.2 Machine identification
Matriculation plate
The matriculation plate is found on the unit and indicates all machine features.
The matriculation plate must never be removed. The matriculation plate shows the indications foreseen by the
standards, in particular:
the type of machine
range → CSNX-XHE size → 82 or 102 or ….
the serial number
12 characters → Axxxxxxxxxxx
the year of manufacture the wiring diagram number electrical data manufacturer logo and address
Serial number
Unambiguously identifies each machine. Enables identifying the specific spare parts for the machine.
Intervention requests
From the matriculation plate, take note of the characteristic data on the table so they are easily available if required.
For request of intervention, always give the following data.
MCHSX Steam-powered humidifying module FEL Electronic filters std
ELECTRIC CIRCUIT
CRC Remote control with user interface std NCRC Remote control with user interface: not required MOB Serial port RS485 with MODBUS protocol LON Serial port RS485 with LONWORKS protocol BAC Serial port RS485 with BACnet protocol CTU Temperature and humidity control std RE Electric heaters std DESM Smoke detector PM Phase monitor std
INSTALLATION
II Indoor installation IO Outdoor installation std AMRX Rubber antivibration mounts
1.4 Example referred on Size 2
G
F
Range Size Serial number Year of manufacture Wiring diagram
1.3 Versions - Options
VERSIONS
RTA Active thermodynamic recovery standard (std)
REFRIGERANT CIRCUIT
CCSTD Standard exchanger on exhaust air std CESTD Standard exchanger on outdoor air std EVE Electronic expansion valves std CPHGM Hot gas re-heating coil with capacity modulation
std
AIR SIDE FEATURES
PCOSME Air flow constant in delivery and expulsion std PVARC Variable air flow on supply and exhaust with CO2
probe
PVARCV Variable air flow on supply and exhaust with
CO2+VOC probe FG4EE G4 class air filters on outdoor and exhaust air std PSTAF Filters dirty differential pressure switch on extract
and delivery std MHSEX Immersed electrodes steam humidifying module
E
D
B
A
C
Main components: A Electronic filters B Outdoor air exchanger C Hot gas re-heating coil with capacity modulation D Capacity modulating compressors E Variable air flow fan on supply air F Variable air flow fan on exhaust air G Exhaust air exchanger
5
1
2
!
i
2 - RECEIPT
!
!
2.1 Preliminary information
Work respecting the current safety standards. For detailed information (dimensions, weights, technical features,
etc.) refer to the TECHNICAL INFORMATION chapter. To perform the operations use the protective equipment: gloves, goggles, etc.
2.2 Check upon arrival
Before accepting delivery, check: The unit has not been damaged during tran sport. That the
delivered material corresponds to that indicated on the transport document, comparing data with the matriculation plate positioned on the pack.
In case of damages or anomalies:
immediately make a note of the found damage on the
transport document and write the wording: "Collection with reserve for evident shortages/damages due to transport".
notices via fax and with registered letter with
acknowledgement receipt to carrier and supplier. The notifications must be made within 8 days from receipt, after this date they will not be accepted.
2.5 Handling
Check the weight of the unit (TECHNICAL INFORMATION chapter) and capacity of the lifting mean.
Identify the critical points in the handling path (holy paths, ramps, steps, doors).
Check the position of the centre of gravity in the TECHNICAL INFORMATIONSDIMENSIONS section.
Ensure the unit is stably balanced before starting handling.
Use protections to avoid damaging the unit.
2.3 Storage
Respect the indications on the outside of the pack.
2.4 Removal of packaging
Attention not to damage the unit. Recycle and dispose of the packaging material according to local standards.
Size1, size2 - lifting holes insert safety pins (1) and split pins (2)
Size3....size6
lifting bracket
6
3 - POSITIONING
!
i
!
3.1 Preliminary information
Work respecting the current safety standards. For detailed information (dimensions, weights, technical features, etc.) refer to the TECHNICAL INFORMATION chapter. To perform the operations use the protective equipment: gloves, goggles, etc.
3.2 Functional spaces
The functional spaces have the aim of:
guarantee good operation of the unit allow maintenance operations protect the authorised operators and exposed
persons. Respect the functional spaces indicated in the TECHNICAL INFORMATION chapter Double the functional spaces if more units are aligned.
3.3 Positioning
The units have been designed to be installed :
OUTDOORS INDOORS (OPTION) in permanent position.
Choose the place of installation depending on the following criteria:
level of sound emissions admitted by the local
standards
Customer approval safely accessible position technical spaces requested by the unit maximum distance admitted from the electric
connections
support points with adequate capacity for the unit
weight
spaces for air ejection and suction disposal of condensate water
Prefer places where the unit does not disturb neighbours. Avoid snow accumulating obstructing the coils Avoid places that may be subject to floodings Install the unit lifted from the ground. Protect the unit with suitable fence in order to avoid access to unauthorised personnel (children, vandals, etc.) Limit the transmission of vibrations:
use anti-vibration devices or neoprene strips on the
unit support points
install flexible joints on the hydraulic connections install flexible joints on the aeraulic connections.
A correct air circulation on the coil is essential to guarantee the good operation of the machine. Avoid:
obstacles to air flow (strong prevailing winds, hedges,
fences, etc.)
difficulty of exchange leaves or other bodies that can obstruct the exchange
coils
winds contrasting or favouring the air flow heat sources near the unit (chimneys, extractors, etc.) sources of dust or pollutants stratification (cold air that stagnates at the bottom) recirculation (ejected air that is taken back via suction) positioning underneath the ground level, near very
high walls, underneath roofs or in corners (can give rise to stratification or recirculation phenomena).
Neglecting the previous indications can lead to:
worsening of the energy efficiency. blocks due to HIGH PRESSURE (in summer) or LOW
PRESSURE (in winter). Avoid snow and ice accumulation in front of the external air outlets and of the exhaust air ejection.
Positioning on concrete floor
1 strisce in neoprene di spessore 2 cm 2 platea in calcestruzzo 3 solaio
Positioning on steel structure
1 anti-vibration devices 2 steel structure 3 steel structure
7
3 - POSITIONING
!
Avoid snow and ice accumulating in front of the exhaust air ejection.
3.4 INDOOR INSTALLATION SET-UP
A Rain-proof protection B Safety and anti-intrusion for small animals grille C Rain drain D Condensate drain
3.6 STEAM HUMIDIFICATION MODULE - OPTION
IMMERSED ELECTRODE STEAM HUMIDIFICATION MODULE
This accessory requires connection to a water supply network and discharge water circuit with adeguate frost protection. Requires its own power supply and have to be connected to the unit. Installation and wiring to customer care.
CENTRALISED STEAM HUMIDIFICATION MODULE A shut-off valve in the unit’s steam input line is to be provided
(responsibility of the customer). Install the steam line in a
position higher to the unit. If the available steam supply exceeds the pressure operating
range indicated, the required de-pressurization must take place outside the unit (responsibility of the customer).
Operating pressure: 1 bar Risk of freezing: see par. 4.2
3.5 ELECTRONIC FILTER - OPTION
The most common contaminants for which the filter is desi­gned, are : air pollution by PM10, PM 2,5 and PM1 Contaminants that can be filtered:
Dry smokes powder (up to 0.3 microns) Smoke electrostatically charged
Contaminants that can NOT be filtered:
Water vapors also in low concentrazione Oil vapors large amounts of dust Metal shavings,iron filing dusts and waste generally gas
Absolutely to avoid:
Metal dusts also fine fumes produced by combustion of organic and not
materials (wood, coal, gasoline, etc.)
(1) Power input (2) Steam inlet / Water inlet (3) Condensate discharge
SIZE SIZE 1 SIZE 2 SIZE 3 SIZE 4 SIZE 5 SIZE 6
A mm 640 640 760 760 760 760 B mm 800 800 835 1060 1060 1060
C mm 905 905 1630 1630 1920 2225
8
!
4 - HYDRAULIC CONNECTIONS
i
P
H
S
T
4.1 Condensate drain
The condensate must be disposed of in order to avoid damaging things and persons.
Unit drain coupling: the connection must not transmit
mechanical stresses and must be carried out paying attention not to damage the unit drain coupling.
Foresee a siphon that, by eliminating the depression
caused by the fan, prevents suction of air from the drain piping.
The piping must have adequate slope to allow out flow. Anchor the piping with an adequate number of supports. On the contrary, cracking in the piping and air pockets
obstructing the outflow, are generated.
Isolate piping and siphon to avoid condensate dripping. Connect the condensate drain to a rain drain network. DO NOT use white waters or sewage drains to avoid
possible inhaling of odours in case of evaporation of the water contained in the si phon.
At work end, check the regular outflow of the condensate
by pouring water in the bowl.
4.2 Risk of freezing
Adopt measures to prevent risk of freezing if the unit or relative hydraulic connections can be subject to temperatures near 0°C.
isolate the piping protect the piping with heating cables laid underneath
the insulation
4.3 Hydronic recovery - option
The device is shipped filled with water and glycol.
Siphon height calculation T = 2P S = T/2 P is the pressure determined by the fan in correspondence of the condensate collection bowl (approx. 1 mm = 9.81 Pa)
Example :
P = 300 Pa = 30 mm T = 2P = 60 mm S = T/2 = 30 mm
A. vent B. filling glycol C. water filling tap
9
4 - HYDRAULIC CONNECTIONS
4.4 Immersed electrodes humidifier - option
SUPPLY WATER The humidifier must be supplied with mains water having the
following features:
pressure between 0.1 and 0.8 Mpa (1 – 8 bar) temperature between 1 and 40°C
Do not use :
water treated with softeners: it can corrode the
electrodes and form foam with possible faults/ malfunctionings
pit, industrial or potentially polluted (chemically or
bacteriologically) water
disinfectants or anti-corrosive substances mixed with
water, as potentially irritating
Supplying the humidifier with water treated with reverse osmosis filtering system gives the following advantages:
reduces limescale deposits reduces energy consumptions reduces maintenance costs increases humidifier duration.
Check that the filter guarantees a water flow rate higher than the flow rate of the installed humidifier.
DRAINAGE WATER It can reach a temperature of 100°C. It contains the same substances of the supply water but in
higher concentration. As it is not toxic, it can be disposed of with white waters.
Limit values for the supply water with medium-high conductivity in an
Hydrogen ions pH 7 8,5 Specific conductivity at 20°C μS/cm 300 1250 Total dissolved solids TDS mg/l Dry residue at 180°C R Total hardness TH mg/l CaCO3 100 Temporary hardness mg/l CaCO3 60 Iron + Manganese mg/l Fe+Mn 0 0,2
Chlorides ppm Cl 0 30
Silica mg/l SIO2 0 20 Residual chlorine mg/l Cl- 0 0,2 Calcium sulphate mg/l CaSO4 0 100 Metallic impurities mg/l 0 0 Solvents, diluents, soaps,
lubricants
Limit values for the supply water with medium-low conductivity in an
Hydrogen ions pH 7 8,5 Specific conductivity at 20°C μS/cm 125 500 Total dissolved solids TDS mg/l Dry residue at 180°C R Total hardness TH mg/l CaCO3 50 Temporary hardness mg/l CaCO3 30
immersed electrode humidifier
mg/l
180
mg/l 0 0
immersed electrode Humidifier
mg/l
180
min max
(1) (1)
(1)
(1)
(2)
400
(3)
300
min max
(1) (1)
(1)
(1)
(2)
250
(3)
150
Iron + Manganese mg/l Fe+Mn 0 0,2
Chlorides ppm Cl 0 20
Silica mg/l SIO2 0 20 Residual chlorine mg/l Cl- 0 0,2 Calcium sulphate mg/l CaSO4 0 60 Metallic impurities mg/l 0 0 Solvents, diluents, soaps,
lubricants
(1) Values depending on specific conductivity; in general:
(2) not lower than 200% of the chloride content in mg/l of Cl­(3) not lower than 300% of the chloride content in mg/l of Cl-
mg/l 0 0
No relation can be demonstrated between water hardness and conductivity.
10
i
5 - AERAULIC CONNECTIONS
!
!
5.1 Generality
The dimensioning and correct execution of the aeraulic connections are fundamental to guarantee good unit operation and adequate level of silence in the room.
When designing and manufacturing the channels, consider LOAD LOSSES, AIR FLOW AND SPEED that must be consistent with the unit features.
Particularly consider that load losses higher than the unit useful prevalence, lead to reduction in flow rate, with consequent unit blocks.
the weight of the channels must not burden on the
connection flanges
place anti-vibration joints between channels and unit connection to the flanges and between the various
sections of the channels must guarantee air seal, avoiding dispersions penalising the overall efficiency of the system
limit the load losses by optimising the path, the type and
number of bends and junctions
use wide bends evaluating the opportunity of equipping
them with deflectors (in particular with high air speed or bends with reduced radius).
5.2 Treated air channelling
The internal surface of the channel must be smooth, enable its washing and must not contaminate the air
Thermally isolate the channels and the flanges to avoid energy losses and forming of condensation
DIFFUSERS INLETS GRILLES A correct diffusion of the air in the room is determining for the
level of comfort. When choosing and positioning the grilles, inlets and
diffusers, avoid:
excessive air speed forming of stagnant and stratification areas cold air delivery in room forming of localised currents (also due to uneven
distribution of air)
excessive room temperature variations, vertically and
horizontally
short circuits of the supply air towards the return air.
For sound comfort, consider that :
the air diffusers must be chosen verifying the sound power
generated at nominal flow rate conditions
the cut-off to diffusers must be carried out with flexible
elements
the return grilles must be widely dimensioned.
Thermally isolate the channels and the flanges to avoid energy losses and forming of condensation
11
5 - AERAULIC CONNECTIONS
Remote supply air sensor (standard size 3, 4, 5, 6)
3
1
2
1. Probe kit position
2. Probe cable outlet
12
!
i
!
6 - ELECTRIC CONNECTIONS
6.1 Preliminary information
The features of the lines must be determined by personnel enabled to the designing of electric systems, complying with the standards in force.
The protective equipment of the unit supply line must be able to shut-off the presumed short circuit current, which value must be determined in accordance with the system features.
The section of the power supply cables and of the protective cable must be determined in accordance with the features of the used protections.
All electrical operations must be carried out by personnel having the legal requisites, trained on the risks related to these operations.
Work respecting the current safety standards.
6.2 Electric data
The matriculation plate shows the electric data specific of the unit, including any electric accessories.
The electric data indicated in the technical schedule and in the manual refer to the standard unit, excluding accessories. Refer to the data reported in the matriculation plate.
6.4 Data-signal lines
Do not exceed the maximum admitted distance, that varies based on the type of cable and signal.
Lay the cables away from the power lines, with different voltage, or that emit interferences of electromagnetic origin.
Avoid laying the cables near the equipment that can create electromagnetic interferences.
Avoid laying in parallel with other cables, any intersection with other cables is admitted only if at 90°C.
The screen must be connected to earth without interferences. Guarantee screen continuity for the entire extension of the
cable. Respect the indications on impedance, capacity, attenuation.
6.5 Electric line input
Matriculation
plate
F.L.A. Full load ampere absorbed current at maximum admitted conditions
F.L.I. Full load input Power absorbed with full load (at maximum admitted conditions)
VOLTAGE
FLA (A)
FLI (kW)
6.3 Connections
Refer to the wiring diagram of the unit (the number of the wiring diagram is indicated in the matriculation plate)
Check the mains have features conform with the data reported on the matriculation plate
Before starting work, check the isolation device at unit power supply line start is open, blocked and provided with sign
First carry out the earth connection Protect the cables using adequately sized cable glands Before electrically powering the unit, ensure all protections
removed during electric connection are restored.
QS1 main isolator AUX Customer connections terminal box
Fix the cables: if left free they may be subject to tears. The cables must not touch the compressors or cooling piping
(they reach high temperatures)
13
6 - ELECTRIC CONNECTIONS
6.6 Connections by the Customer - XC
HA1 fire alarm SA1 remote ON-OFF selector SA5 remote SUMMER - WINTER selector
HLC1 compressor status signal lamp HLM supply fan status HLE indicating light of the return and/or supply fan status ALM remote alarm signal
6.7 STEAM HUMIDIFICATION MODULE - OPTION
14
6 - ELECTRIC CONNECTIONS
6.8 P.C. - not supplied
6.9 SERVICE KEYPAD - OPTION
Shift RJ45 from T-IP to T-HI RJ45 : standard connection
15
6 - ELECTRIC CONNECTIONS
6.10 Room keypad
Distance up to 350 mt Connections
Distance up to 700 mt
A user interface B = B1 KNX bus, max 350 mt twisted pair with shield, Ø 0,8 mm EIB/KNX cable marking recommended C power supply unit N125/11 5WG1 125-1AB11 C1 AC 120...230 V, 50...60 Hz
16
6 - ELECTRIC CONNECTIONS
6.11 MODBUS - RS485
LED BSP communication with AP1 module
green communication ok yellow software ok but communication with AP1
down red flashing : software error fixed : hardware error
LED BUS communication with MODBUS
green communication ok yellow startup / channel not communicating red communication down
Every RS485 serial line must be set up using the 'In/
Out' bus system. Other types of networks are not allowed, such as Star or Ring networks
The difference in potential between the earth of the
two RS485 devices that the cable shielding needs to be connected to must be lower than 7 V
Suitable arresters must be set up to protect the serial
lines from the effects of the atmospheric discharges
A 120 ohm resistance must be located on the end of
the serial line. Alternatively, when the last serial board is equipped with an internal terminator, it must be enabled using the specific jumper, dip switch or link
The cable must have insulation features and non-
flame propagation in accordance with applicable regulations
The RS485 serial line must be kept as far away as
possible from sources of electromagnetic interference.
CABLE MODBUS, BACNET, LONWORK REQUIREMENTS
Couple of conductors twisted and shielded Section of conductor 0.22mm Nominal capacity between conductors < 50 pF/m nominal impedance 120 Ω Recommended cable BELDEN 3105A
2
…0,35mm
2
A metal conduit B metal septums C metal-lined sheath (sleeve) D unit
17
6 - ELECTRIC CONNECTIONS
6.12 BACNET 6.13 LONWORK
LED BSP communication with AP1 module
green communication ok yellow software ok but communication with AP1
down red flashing : software error fixed : hardware error
LED BUS communication with BACNET
green ready for communication yellow startup red BACnet server down restart after 3 sec.
LED BSP communication with AP1 module
green communication ok yellow software ok but communication with AP1
down red flashing : software error fixed : hardware error
LED BUS communication with LONWORK
green communication ok yellow startup flashing: communicating not possible red communication down
18
7 - START-UP
Preliminary checks
Checks with machine in OFF, before start-up .
For details refer to the various chapters in the manual.
Unit OFF power supply
safe access
integrity of structure
functional spaces
fresh air intake: grille free
air expulsion: grille free
unit on anti-vibration devices
air filters present and clean
Start-up sequence
Machine start-up operations.
For details refer to the various chapters in the manual.
unit ON power supply
Powered unit
compressor carter heaters ON from at least 8 hours
phases sequence control
vacuum voltage measurement
unit ON
load voltage measurement and absorptions
fans operation check
completed aeraulic system
steam humidification module connections
cooling circuit visual control
earth connection
unit powered by fixed network or by electrogen group
electric connections by customer
set type reg.
set air flow rate
temperature set-point customisation
humidity set-point customisation
treated air flow rate measurement
supply, return and outdoor air temperature measurement
subcooling and overheating measurement
no anomalous vibrations check
set date and time
fire alarm configuration *
heater humidifier calibration *
available machine documentation
* only if present
19
7 - START-UP
!
!
L1 L2 L3
388V
379V
377V
388 + 379 + 377
3
=
381 (A)
MAX - A = 388 – 381 = 7
S =
7
A
x 100 = 1,83
OK
1)
2)
3)
!
7.1 Preliminary information
The indicated operations must be carried out by qualified technicians and specifically trained on the product.
Upon request, the after-sales assistance centres execute start­up.
The electric, hydraulic connections and the other work of the system are the responsibility of the installer.
Agree the start-up date with the after-sales assistance centre with sufficient advance
7.2 Preliminary checks
Before starting any check, verify that :
the unit is perfectly installed and in compliance with that
reported in this manual
the electric power supply line of the unit is isolated at start-
up
the isolation device of the line is open, blocked and
equipped with relative signal.
7.3 Cooling circuit
7.5 Electric circuit
Check the unit is connected to the earth system. Check fastening of the conductors: the vibrations caused by handling and transport may cause loosening.
Power the unit by closing the isolation device but leave in OFF.
Check the network frequency and voltage values, that are within the limits:
400/3/50 +/- 10% Check the unbalancing of the phases:
must be below 2% . Example :
1. Visually check the cooling circuit: any oil stains can be symptom of leaks (caused by, for example, transport, handling or other).
2. Check the cooling circuit is pressurised: use the machine pressure gauges, if present, or service pressure gauges.
3. Check all service sockets are closed with relative plugs; their absence may determine coolant leaks
7.4 Hydraulic circuit
Only with hot water coil - humidifier options
1. Find out if, before connecting the unit, the hydraulic
system has been washed and the washing water drained.
2. Check the hydraulic circuit has been loaded and
pressurised.
3. Check the shut-off valves on the circuit are in "OPEN"
position.
Operation outside the limits can entail irreversible damages.
7.6 Compressor carter resistors
Power the compressor oil heating resistors for at least 8 hours before starting the compressor itself:
upon unit commissioning after every prolonged stop period with unit not
powered
Power the resistors by closing the unit isolator. Check electric absorption of the resistors to be sure they are
working. Execute start only if the temperature of the compressor casing
on the lower side is at least 10°C higher than the outdoor temperature.
Do not start the compressor with carter oil not in temperature.
20
7 - START-UP
i
7.7 Voltages
Check the air and water temperatures are within the operational limits.
Start the unit; refer to the "Adjustment" section for indications on the control system.
With the unit running, meaning in stable conditions and near the work ones, check:
power supply voltage unit overall absorption absorption of the individual electric loads.
7.8 Scroll compressors (size 2, 3, 4, 5, 6)
The Scroll compressors have only one direction of rotation. In the event that the direction is reversed, the compressor will
not be damaged, but its noisiness will increase and pumping will be negatively affected.
After a few minutes, the compressor will stop because of the activation of the thermal protection.
In this event, cut the power and reverse the 2 phases on the machine power.
Prevent the compressor from working with in reverse rotation: more than 2-3 anomalous starts up can damage it.
Make sure the direction of rotation is correct, measure the condensation and suction pressure.
Pressure must clearly differ: at the start, the suction pressure decreases whilst the condensation pressure increases.
7.9 Remote consents
Check the remote controls (ON-OFF, etc.) are connected and, if necessary, enabled with relative parameters
(ELECTRIC CONNECTIONS sections and following pages)
Check the probes or optional components are connected and enabled with the relative parameters.
7.14 Start-up report
To detect the objective operational conditions is useful to control the unit over time.
With the unit running, meaning in stable conditions and near the work ones, detect the following data:
Overall absorptions and voltages with unit in full load Absorptions of the various electric loads
(compressors, fans, pumps etc)
Temperatures and flow rates of the various fluids
(water, air) at input and output of the unit
Temperatures and pressures in the feature points of
the cooling circuit (compressor, liquid, suction drain/ unload)
The detections must be kept and made available during maintenance interventions.
7.15 EC Directive 97/23 PED
From Directive 97/23 EC PED derive the prescriptions for the installers, the users and the maintenance operators of the unit also.
Refer to the local implemented standards; in synthesis and for merely indicative purposes:
Compulsory check of first system:
only for units assembled on site by the installer (e.g. condensing + direct expansion unit)
Declaration of start-up:
for all units
Periodical checks:
to be carried out as frequently as defined by the Manufacturer
(see MAINTENANCE section) .
7.10 Operation type setting
Refer to 7.11, 7.12, 7.13.
1. Define operation type
- maximum capacity available (MC)
- constant supply control (CS)
- high air flow (HA)
2. set air flow setpoint
3. set temperature setpoint
4. set humidity setpoint
5. confirm setting
21
7 - START-UP
7.11 Maximum capacity available (MC)
In this operating mode, the supply air temperature (T_SA) can vary in accordance with the temperature of the air extracted from the room (T_RA) and their deviation from the set value.
Therefore, there is feedback from the room. In cooling mode the humidity control of the supply air is standard and a priority.
Type of adjustment
Main index \ Parameter machine \ Plant config
set P0001 TypeReg = MC
Air flow rate
The air flow rate control depends on the device connected to the X2 input Constant air flow rate, X2 input not used:
set P0032 X2Config = None (Main index \ Parameter machine \ configure machine) set rated air flow rate P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
Variable air flow rate, CO2 probe connected to the X2 input:
set P0032 X2Config = CO2 (Main index \ Parameter machine \ configure machine) set air flow rate with quality NOT met: P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config) set air flow rate with quality met: P0004SetQAirCO2Ok (P0004<P0002) (Main index \ Parameter machine \ Plant config)
Constant supply pressure, pressure detector connected to the X2 input:
set P0032 X2Config = Supply (Main index \ Parameter machine \ configure machine) set the supply pressure setpoint: P0003 SetPSupplyPlant (Main index \ Parameter machine \ Plant config)
Temperature setpoint
Set the values related to the SPR return air setpoint in relation to the T_OA external temperature:
(Main index \ Parameter machine \ plant config)
P0005 SetCool P0006 SetHeat P0008 MC_TExtCool P0009 MC_TExtHeat
22
7 - START-UP
The T_SA supply setpoint is calculated in relation to the SPR return setpoint. Set the values related to the T_SA supply air setpoint in relation to the T_RA return temperature:
Main index \ Parameter machine \ Thermoregulator
P0070 LimMinSupplyT P0071 LimMaxSupplyT P0072 MC_BandPr P0073 MC_DeadBand
Humidity setpoint
Main index \ Parameter machine \ Plant config
set the specific supply humidity setpoint in cooling mode: P0017 SetXSA set the specific return humidity setpoint in heating mode: P0018 SetXSR
Confirm configuration
Main index \ Parameter machine \ Plant config
set P0020 ConfirmConf = Yes
23
7 - START-UP
7.12 Constant supply control (CS)
In this operating mode the external air is treated based on the supply conditions set in accordance with one of the following two criteria:
with two fixed seasonal setpoints, for operation in cooling and heating mode with two dynamic seasonal setpoints, in which the supply temperature is offset automatically in accordance with the external dry
bulb temperature T_OA, with climatic regulation.
There is no feedback from the room. In cooling mode the humidity control of the supply air is standard and a priority.
Type of adjustment
Main index \ Parameter machine \ Plant config
set P0001 TypeReg = CS
Air flow rate
The air flow rate control depends on the device connected to the X2 input Constant air flow rate, X2 input not used:
set P0032 X2Config = None (Main index \ Parameter machine \ configure machine) set rated air flow rate P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
Variable air flow rate, CO2 probe connected to the X2 input:
set P0032 X2Config = CO2 (Main index \ Parameter machine \ configure machine) set air flow rate with quality NOT met: P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config) set air flow rate with quality met: P0004SetQAirCO2Ok (P0004<P0002) (Main index \ Parameter machine \ Plant config)
Constant supply pressure, pressure detector connected to the X2 input:
set P0032 X2Config = Supply (Main index \ Parameter machine \ configure machine) set the supply pressure setpoint: P0003 SetPSupplyPlant (Main index \ Parameter machine \ Plant config)
24
7 - START-UP
Temperature setpoint
Set the values related to the T_SA supply air setpoint in relation to the T_OA external temperature:
(Main index \ Parameter machine \ plant config)
P0005 SetCool P0006 SetHeat P0010 CS_TExtCool P0011 CS_TExtHeat P0012 CS_GainCool (Ycool/Xcool) P0013 CS_GainHeat (Yheat/Xheat)
Humidity setpoint
Main index \ Parameter machine \ Plant config
set the specific supply humidity setpoint in cooling mode: P0017 SetXSA set the specific return humidity setpoint in heating mode: P0018 SetXSR
Confirm configuration
Main index \ Parameter machine \ Plant config
set P0020 ConfirmConf = Yes
25
7 - START-UP
7.13 High air flow (HA)
In this operating mode the external air T_OA is treated until it reaches the value of the supply air temperature T_SA). There is no feedback from the room.
The humidity control of the supply air is running only in heating mode.
x_Sa* solo con umidificatore
Type of adjustment
Main index \ Parameter machine \ Plant config
set P0001 TypeReg = HA
Air flow rate
The air flow rate control depends on the device connected to the X2 input Constant air flow rate, X2 input not used:
set P0032 X2Config = None (Main index \ Parameter machine \ configure machine) set rated air flow rate P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config)
Variable air flow rate, CO2 probe connected to the X2 input:
set P0032 X2Config = CO2 (Main index \ Parameter machine \ configure machine) set air flow rate with quality NOT met: P0002 SetQAirPlant (Main index \ Parameter machine \ Plant config) set air flow rate with quality met: P0004SetQAirCO2Ok (P0004<P0002) (Main index \ Parameter machine \ Plant
config)
Constant supply pressure, pressure detector connected to the X2 input:
set P0032 X2Config = Supply (Main index \ Parameter machine \ configure machine) set the supply pressure setpoint: P0003 SetPSupplyPlant (Main index \ Parameter machine \ Plant config)
Temperature setpoint
Set the values related to the T_SA supply setpoint in relation to the T_OA external temperature:
(Main index \ Parameter machine \ Plant config)
P0014 HA_SetHeat P0015 HA_TExtLg P0016 HA_GainExtLg (Yt_sa/Xt_oa)
26
7 - START-UP
Humidity setpoint
Main index \ Parameter machine \ Plant config
set the specific return humidity setpoint in heating mode: P0018 SetXSR
Confirm configuration
Main index \ Parameter machine \ Plant config
set P0020 ConfirmConf = Yes
27
8 - CONTROL
Keypad
change of status: OFF, ON, FAN
ALARMS menu access (if available)
set TIME and DATE set SCHEDULER (prolonged pressure)
to browse through the menus to set values
to browse through the menus to set values
access to the STATUS menu to confirm your selection
to access the PARAMETERS menu (password) KEYPAD LOCK menu (password)
HEAT - COOL mode change CLEAN function (prolonged pressure)
Keys and function
ON / OFF OFF status. On the top field of the thermostat, the
temperature and OFF indication are alternated every 2 seconds.
When the status is OFF, changes to the SETPOINT and schedule are blocked.
Defrosting Mode: The machine is defrosting.
Scheduling Mode: The scheduling is active.
Symbols
Humidifier / Dehumidifier mode The Humidifier mode is active If flashing, it means the Dehumidifier mode is
active
Compressor ON: At least one compressor is active
Alarm: There is at least one alarm Press the "alarm" key to view it
28
8.1 PARAMETERS MENU
8 - CONTROL
press
the access by password is reserved to qualified personnel, the parameters changes can cause malfunctions.
enter password (0047)
confirm
scroll the parameters
enable the parameter change P1 starts flashing
change the value of the parameter
confirm the new value
select to enable the new value and exit
when the time is displayed it is possible to carry out other
operations
16.3 C°
17:00
COD
47
P1
0
P1
1
ESC
code Short description Description
0 PriorityCmd Priority commands On/change mode (0=keyboard, 1=BMS) 1 Enscheduler Enable schedular (0=disable, 1=enable)
29
8.2 STATA MENU
8 - CONTROL
Press
scroll the statuses
exit
wait for 3 sec
when the time is displayed it is possible to carry out other
operations
16.3 C°
17:00
50
011.6
16.3 C°
:
16.3 C°
17:00
Code Description
0 Operating return temperature 1 Outdoor temperature 2 Supply temperature 3 Return specific humidity 4 Outdoor specific humidity 5 Supply specific humidity 6 Air quality (option) 7 Active compressors number 8 Compressors fuctioning mode: 0= off; 1=cool; 2=heat
9 Active cooling capacity 10 Active cooling capacity circuit 1 11 Active cooling capacity circuit 2 (only size 3, 4, 5, 6) 12 Capacity control circuit1 status: 0=off; 1=on 13 Postheating valve circuit 1 opening 14 Postheating valve circuit 2 status (only size 3, 4, 5, 6): 0=off, 1=on
30
8 - CONTROL
8.3 DATE AND HOUR
Press
HOUR digits start flashing
edit
confirm
MINUTE digits start flashing
edit
confirm
HOUR - MINUTE digits start flashing
choose format 24h / am - pm
set year, month, day
main menu
16.3 C°
17:00
17:00
17:00
17:00
16.3 C°
17:00
8.4 BUTTON LOCK
Press for 4 sec.
enter password confirm
example: T0 = "-" key ON = active key see codes-key table
scroll the keys
select the key (ALL starts flashing)
set active-ON / disabled-OFF example: ALL = OFF all keys disabled
select to confirm
exit
16.3 C°
17:00
COD
_ _ _ _
T0
ON
T1
OFF
ALL
OFF
ESC
Key-code table
n. key key n. key key
T0
T1
T2
T3
T4
T5
T6
T7
ALL All keys
16.3 C°
17:00
31
8.5 TO VISUALIZE ALARM IN PROGRESS
Before resetting an alarm identify and remove its cause. Repeated resets can cause irreversible damage.
8 - CONTROL
press only if the ALARM symbol is flashing
ee type of alarm (see table)
0 generic alarm (1 circuit1 alarm,
etc.)
030 progressive alarm number
press
7 days since the alarm was triggered 17:00 alarm time
previous menu
scroll the alarms
exit without alarms RESET
exit with alarms RESET: scroll and select RES
16.3 C°
17:00
ee
0030
007
17:00
ee
0030
ee
0030
RES
32
8 - CONTROL
8.6 SCHEDULER
Enable scheduler ( 8.1 menu parametres)
It is possible to set up to 7 schedules (1 for every day of the week)
It is possible to set up to 6 status changes for each day (On, Off, Eco, Fan).
In the days not included in the schedule, the unit maintains the most recent status defined in the schedule. Example:
Monday scheduled, 23h unit in ECO mode Tuesday not scheduled, the unit remains in ECO mode
Scheduling example:
-
-
-
-
-
-
3
Wedne-
FAN FAN
ECO ECO
OFF OFF
4
Thursday 5 Friday 6 Saturday 7 Sunday
sday
- - -
ON ON ON FAN
ON ON
- - -
- - -
- - -
- - -
- - -
Time Event
05:30 1 FAN
08:00 2 ON 13:00 3 FAN
15:00 4 ON 18:00 5 ECO
21:00 6 OFF
Sequence of operations.: Chose the days
(e.g. 1 = Monday, 3 = Wednesday, 4 = Thursday)
1. set event 1 time
2. set event 1
3. set event 2 time
4. set event 2
5. repeat for the other events (max. 6)
6. to insert other scheduling (max. 7) repeat from step 1 to 6
The most recent schedule saved overrides the existing one. For instance, if a day is included in two different schedules, the most recent one saved prevails.
1
Monday 2 Tuesday
Press 2 sec (only if the unit is not OFF)
day 1 starts flashing
to schedule day 1 press
(1 stays steady = day 1 scheduled)
to go to day 2 press
(2 starts flashing)
to schedule day 2 press
to schedule day 3 press
(3 starts flashing)
press
to schedule day 4 press
(4 starts flashing)
press
7 starts flashing
to confirm selected days press
1 3 4 starts flashing
press
press
(ref. A)
-- starts flashing
set
- time of the event
press
16.3 C°
17:00
1
1 2
1 3
1 3 4
1 3 4 7
1 3 4
000
--:--
1 3 4
000
05:--
1 3 4
33
8 - CONTROL
set
- minutes of the event
press
set
- desired event
0 = null, 1 = OFF, 2 = ON,
3 = Fan
press
example: 5:30 o'clock unit in FAN mode (003)
press to set altri the events 2,3,…..6
Ripeat from (ref. A)
press 2 times to exit
P flashing, active scheduling
000
05:30
1 3 4
003
05:30
1 3 4
003
05:30
1 3 4
16.3 C°
17:00
P
16.3 C°
17:00
4
Modify day 3 day scheduling
(ref. scheduling example)
Press 2 sec
press to schedule day 3 press (Wednesday)
press
(3 stays steady)
press 7 starts flashing
press to confirm selected days
press
select the event 3 (h.13:00)
press 3 times starts flashing 003 (= FAN)
press set
- desired event 002 (= ON)
press
press 2 times to exit
16.3 C°
17:00
3
3 7
003
13:00
3
002
13:00
3
16.3 C°
17:00
34
8.7 SERVICE KEYPAD
1/7
27.03.2013 10:15:30
Supply T. Setpoint 22.0°C Supply X. Setpoint 10.0 g/kg
StatoAttuale ON
Cmp:23% Res: Off Battery:Off
8 - CONTROL
Function keys
Main menu
Alarm display
Exit Previous level Keyboard settings
Up Increases value
Down Decreases value
Confirm Password
8.8 COMMON OPERATIONS
ON, OFF, ECO
change MODE
change SETPOINT
main menu
→ cmd local status
→ scegliere OFF - ON - FAN
main menu
→ cmd local mode
→ select COOL - HEAT
main menu
→ unit parameters
→ setpoint
35
8 - CONTROL
8.9 SCHEDULER
It is possible to set 6 events (Off, Eco, On, Recirculating) for each week day.
Scheduler must be enabled: display : actual value = On pag xy : unit parameters service-maintenance, P0500=1
Select
Confirm
Select
Confirm
Cmd Local state On Cmd Local mode Cool Unit stata Unit parameters System Objects
Schedulatore
Actual value On
01 : Monday Off
01 : Tuesday Off 01 : Wednesday Off 01 : Thursday Off 01 : Friday Off
Main index
Main index
8.10 KEYBOARD SETTINGS
Press 3 sec
Select
Confirm
exit :
To exit :
Select
Confirm
HMI settings
local connection
V9.08 B0024 Backlight color Blue Backlight turn off time 0 Contrast 60 Brightness 100 Firmware Update No
HMI settings
local connection
HMI settings
Select
Confirm
Setting
Exit
Select
Confirm
Setting
Exit
Scheduled day Active
d01 : Monday
Time 1 00:00
Value 1 ECO Time 2 5:00 Value 2 ON Time 3 17:00 Value 3 ECO Time 4 20:00 Value 4 OFF
d01 : Monday
Scheduled day Active Time 1 xx:yy
Value 1 Eco
Time 2 Value 2 Time 3 Value 3
36
8.11 ALARMS
Before resetting an alarm identify and remove its cause. Repeated resets can cause irreversible damage.
8 - CONTROL
Press Last alarm
Press alarm list
(*)
reset alarms access
Press alarm log
(*)
reset alarms access
alarm log detail
+ eE001 : Phase monitor : Fault
1 Critico (A)
14.02.2012 11.30.10
Alarm list
Acknowledge (*) 3
+ eE001 : Monitore fase : Fault
- EE003 : Guasto P1 Util : Ok
+ EE003 : Guasto P1 Util : Fault
alarm log
Acknowledge (*) Passivo
10
+ eE001 : Monitore fase : Fault
- EE003 : Guasto P1 Util : Ok
+ EE003 : Guasto P1 Util : Fault
Fault = active alarm Ok = resetted alarm
Press
Reset alarm log : select
RESET select
EXECUTED
alarm ing
----------
----------
---------­Reset
37
8 - CONTROL
Alarms encoding
Code Type Reset
eE Electrical From Auto to Man EE Electrical Manual ee Electrical Automatic iI Hydraulics From Auto to Man II Hydraulics Manual ii Hydraulics Automatic
Code Type Reset fF refr. circuit From Auto to Man FF refr. circuit Manual ff refr. circuit Automatic aA Air From Auto to Man AA Air Manual aa Air Automatic
Alarms encoding
From Auto to Man: automatic reset , after N alarm → manual reset
ALARMS - Tab 1
Code Short description description
AA003 Fire Units on alert for fire alarm in progress aa004 DirtyFilter Air dirty filter eE001 Phase monitor Fault on the network power supply EE002 Opening Vain Access compartments open EE005 Electrical Filter Electrical Filter fault ee006 PlantConfig Absence of a configuration of the type of unit operation upon starting eE007 SupplyFan Intervention of the protections of air supply fan eE009 Exhaust Fan Intervention of the protections of return / exaust fan EE010 High Temp. Integration Protection of maximum temperature on the auxiliary heater EE011 Ovl Integration Intervention of the protection of the auxiliary heater ee020 Offline thermostat. User POL822 interface module not responding ee027 ReturnTemp Return temperature probe fault ee028 SupplyTemp Supply temperature probe fault ee029 AirExtTemp External air temperature probe fault ee030 RHSupply Supply RH probe fault ee031 RHReturn Return RH probe fault ee032 RHOutdoor Outdoor air RH probe fault ee033 QualityAir Room air quality probe fault ee035 SupplyPDiff Differential pressure trasducer supply fan fault ee037 ExhaustPDiff Differential pressure trasducer exaust fan fault ee039 PSupply Pressure trasducer suply fan fault ee044 Humidifier alarm Humidifier board disconnected ee050 H2O plant temp Plant water temperature probe fault ee051 H2O freeze temp Heating water coil temperature probe fault ee052 Recover temp Recovery temperature probe fault ee059 PostRiscMod HwError Post-heating control board fault ee060 PostRiscMod BlkError Post-heating control board fault ee061 PostRiscMod FailSaveState Post-heating control board fault ee062 PostRiscMod UpsNotAv Post-heating UPS board fault ee063 PostRiscMod PBTime Post-heating control board not responding ee064 Pump recover Recovery pump fault ee065 PostRiscMod HW-FailSaveState Post-heating control board fault ee068 ExhaustPDiff 2nd Differential pressure trasducer exaust 2nd fan fault ee069 Exhaust Fan 2nd Intervention of the protections of return / exaust 2nd fan ee090 SafeMode SafeMode
38
8 - CONTROL
ALARMS - Tab 2
Code Short description description
ee101 TimeOutModCirc Circuit board not responding ee102 TimeOutDriver Expansion valve module not responding ee104 EEVBlockedOut Expansion valve blocked EE106 Comp 1 protections C1 compressor protection intervention EE107 Comp 2 protections C2 compressor protection intervention EE108 Comp 3 protections C3 compressor protection intervention ee122 Discharge temp. C1 Refrigerant discharge temperature probe fault - C1 ee125 Source 1 temp. Source side coil temperature probe fault ee126 DFR temperature Defrost temperature probe fault ee127 Suction temperature Refrigerant suction temperature probe fault ee128 Discharge pressure High pressure probe fault ee129 Suction pressure Low pressure probe fault ee201 Timoeout comm. Module circuit Control circuit board not responding ee202 Timeout comm. Driver Expansion valve control board not responding ee204 EEV blocked Expansion valve blocked EE206 Comp 1 protections C1 compressor protection intervention EE207 Comp 2 protections C2 compressor protection intervention EE208 Comp 3 protections C3 compressor protection intervention ee222 Discharge temp. C2 Refrigerant supply temperature probe fault - C2 ee226 DFR temperature Defrost temperature probe fault ee227 Suction temperature Refrigerant suction temperature probe fault - C2 ee228 Discharge pressure High pressure probe fault
ee229 Suction pressure Low pressure probe fault
ff055 Room condition Heat mode Heat mode - room temperature too low (outside operating limits). ff056 Outdoor condition Heat mode Heat mode - outdoor temperature too low (outside operating limits). ff057 Room condition Cool mode Cool mode - room temperature too high (outside operating limits) ff058 Outdoor condition Cool mode Cool mode - Outdoor temperature too high (outside operating limits) ff066 Freeze Extrapower Freeze Extrapower
FF067 Gas Alarm Gas Alarm
ff105 Min overheating Overheating too low fF109 Low pressure from DI low pressure, digital input fF112 Low pressure from AI low pressure alarm, analogic input fF113 High pressure from DI high pressure, digital input fF115 High pressure from AI high pressure, analogic input
FF134 VacuumCirc vacuum circuit (refrigerant ) FF137 Alarm Inverter 1 on Circuit 1 compressor 1 inverter alarm
FF138 Alarm missing comunication inv1 - C1 Missing comunication compressor 1 inverter FF139 Timeout comunication inv1 - C1 Missing comunication compressor 1 inverter FF140 Alarm Inverter 2 on Circuit 1 compressor 2 inverter alarm
FF141 Alarm missing comunication inv2 - C1 Missing comunication compressor 2 inverter FF142 Timeout comunication inv2 - C1 Missing comunication compressor 2 inverter
FF143 Alarm Inverter 3 on Circuit 1 compressor 3 inverter alarm FF144 Alarm missing comunication inv3 - C1 Missing comunication compressor 3 inverter FF145 Timeout comunication inv3 - C1 Missing comunication compressor 3 inverter
39
8 - CONTROL
ALARMS - Tab 3
Code Short description description
FF147 Alarm Envelop Comp1 - C1 Compressor 1 outside operating limits FF148 Alarm Envelop Comp2 - C1 Compressor 2 outside operating limits FF149 Alarm Envelop Comp3 - C1 Compressor 3 outside operating limits
ff205 Min overheating Overheating too low fF209 Low pressure from DI low pressure, digital input fF212 Low pressure from AI low pressure alarm, analogic input fF213 High pressure from DI high pressure, digital input fF215 High pressure from AI high pressure, analogic input
FF234 VacuumCirc vacuum circuit (refrigerant ) FF237 Alarm Inverter 1 on Circuit 2 compressor 1 inverter alarm - circuit 2 FF238 Alarm missing comunication inv1 - C2 Missing comunication compressor 1 inverter - circuit 2 FF239 Timeout comunication inv1 - C2 Missing comunication compressor 1 inverter - circuit 2 FF240 Alarm Inverter 2 on Circuit 2 compressor 2 inverter alarm - circuit 2 FF241 Alarm missing comunication inv2 - C2 Missing comunication compressor 2 inverter - circuit 2 FF242 Timeout comunication inv2 - C2 Missing comunication compressor 2 inverter - circuit 2 FF243 Alarm Inverter 3 on Circuit 2 compressor 3 inverter alarm - circuit 2 FF244 Alarm missing comunication inv3 - C2 Missing comunication compressor 3 inverter - circuit 2 FF245 Timeout comunication inv3 - C2 Missing comunication compressor 3 inverter - circuit 2 FF247 Alarm Envelop Comp1 - C2 Compressor 1 outside operating limits FF248 Alarm Envelop Comp2 - C2 Compressor 2 outside operating limits FF249 Alarm Envelop Comp3 - C2 Compressor 3 outside operating limits
40
P.C. CONNECTION
1 connect P.C. and main module with LAN cable
2 check in the taskbar that the connection is active
3 Open Control panel and select Network and sharing center
8 - CONTROL
4 Select Modify board setting
5 Select Local area connection (LAN)
6 Select Internet protocol version 4 (TPC) IPV4 and enter Property
7 Set the IP address 192.168.1.100
8 Set Subnet mask as 255.255.255.0
confirm (OK)
9
10 Enter Start (Windows button).
11 Write the command cmd and enter/do it
12 Write and run the command Ping 192.168.1.42
13 if will appear dawn an answer string, the connection is ok
14 enter the browser and the address 192.168.1.42
Userid = ADMIN
15
Password = SBTAdmin!
16
41
9 - MAINTENANCE
9.1 Recommended periodical checks sheet
Checks carried out on…………………….......by……………………………...………….company…..............…………………………………………….
presence corrosion
panel fixing
fans fixing
coil cleaning
bowl cleaning + sanitisation
outflow test
air filters cleaning/inspection
air flow rate measurement
channelling: anti-vibration devices and fastenings check
power supply cable isolation and fastening check
earth cable check
electric control board cleaning
power remote controls state
clamps closure, cables isolation integrity
phases unbalancing and power supply voltage (vacuum and loaded)
absorption of the individual electric loads
compressors carter heaters test
leaks control *
cooling circuit work parameters detection
four-way valve exchange check
safety valves
protective equipment test: pressure switches, thermostats, flow meters, etc.
protective equipment test: setpoint, climatic compensations, power slicing, air flow rate variations
control devices test: alarms signal, thermometers, probes, pressure gauges, etc.
electrical heaters check - option
water coil check - option
intervention frequency (months)
1 6 12
*
Notes/interventions recommended to Owner
* Refer to the local implemented standards.
Companies and technicians carrying out installation, maintenance/repair interventions, leaks check and recovery must be CERTIFIED as foreseen by the local standards. The leaks check must be carried out on a yearly basis
42
9 - MAINTENANCE
!
i
i
!
i
9.2 Generality
Maintenance must be carried out authorised after-sales assistance centres or by specialised personnel.
Maintenance allows:
maintaining the unit efficient reduce deterioration speed to which each equipment
is subject in time
collect information and data to understand the
efficiency state of the unit and prevent possible faults
9.3 Frequency of interventions
Frequency of the inspections must be at least six-monthly However, frequency depends on the type of use.
heavy (continuous or highly intermittent, near to
operation limits, etc.)
critical (essential service).
9.4 Machine schedule
Foresee a machine schedule to keep trace of the interventions made on the unit.
In this way, it will be easier to adequately schedule the various interventions and facilitate any troubleshooting.
On the schedule note:
date type of intervention made description of intervention measurements taken, etc. .
9.7 G4 Folded air filters
It is very important for the air treatment coil to offer maximum thermal exchange: the unit must always work with clean and installed filters. Cleaning and replacement of filters are very important from an hygienic-sanitary point of view.
Operation with clogged filters leads to a reduction in the air flow rate with malfunctionings and block, up to possible breaks in the unit.
The frequency with which the filters must be checked depends on the quality of the outdoor air, the unit operation hours, the dustiness and crowding of rooms.
Frequency can indicatively vary from WEEKLY to MONTHLY. It is advised to start with frequent checks, subsequently adjusting frequency to degree of detected dirt.
1. Remove the closing panels
2. Delicately remove the filter avoiding dirtying the area
below
3. Wash the filtering jacket in warm water with common detergent
4. Accurately rinse in running water avoiding spilling in the room
5. Dry the filter
6. Insert it back in its seat
7. Remount the closing panels
Old filters, washing wastewater and residues must be disposed of according to the current standards.
9.5 Stand-by
If foreseen a long period of inactivity:
disconnect voltage to avoid electric risks or damages
following lightning
prevent the risk of freezing (empty or glycol the
sections of the system exposed to negative temperatures, keep any antifreeze heaters powered)
It is advised that start-up after a period of inactivity be carried out by a qualified technician, in particular after seasonal stops or for seasonal switch-over.
Upon start-up, follow that indicated in the START-UP section. Plan in advance the technician intervention to prevent
misunderstandings and be able to use the system when required
9.6 Structure
Check the state of the parts constituting the structure. Treat those parts of the unit subject to oxidation, with paints
act at eliminating or reducing the oxidation phenomena. Check fastening of the unit external panelling. Bad fastening give rise to anomalous noises and vibrations.
43
9 - MAINTENANCE
9.8 Filtri elettronici - opzione
La regolazione elettronica è integrata nel filtro; la manutenzione può essere effettuata senza rimuoverla .
MATERIALS NECESSARY FOR MAINTENANCE
1. Acid detergent B01212 (code CLIVET C6460316)
2. plastic or steel tank (750x750x310 mm) with settling
bottom
3. Protective gloves and goggles
4. Graduated jug;
5. Pump for manual or pneumatic spraying.
Do not use aluminum tanks or galvanized. Foresee a stainless steel frame that keeps the filters lifted from the tank base to have a settling bottom for the muds.
750
750
Remove the pre-filter by lifting it of about 1 cm and remove it as shown in figure.
1. Position the filter to be washed on a support to facilitate
work.
2. Prepare a tank with a solution of B01212 detergent and water at 1÷20.Do not use galvanised steel sheet or aluminium tanks.
3. Immerse the filter in this solution
4. Ensure the solution covers the entire filter
5. Immerse it for about 5-7 minutes. A slight chemical
reaction is noticed within 2÷3 minutes with the development of foam indicating the occurred elimination of residues.
6. Rinse the filter with a jet of water or using a low-pressure water jet machine.
7. Leave the electrostatic cells to dry in a hot room or directly in the sun for a few hours.Keep the cells lifted from the ground using two metal or wooden laths.
Check the ionisation wires before remounting the filter. The cleaner can be used to clean about 20 filters. Can be recovered and placed in plastic containers closed; the air oxidizes the cleaner and reduces its effectiveness.
IONISATION WIRES
The impurities can determine oxidation or scaling on the wires, which can be removed using a cloth soaked in alcohol or an abrasive scourer with very fine grain. Due to the high voltage powering them, the ionisation wires are subject to wear. To foresee a yearly replacement OF ALL WIRES avoids unexpected breaks. In case of break: :
1. remove all wire pieces present in the cell and remove the
springs stretching the wire;
2. hook the spring to the wire eyelet;
3. grip the ionisation wire with curved beaks pliers;
4. hook the top of the spring with the open eyelet to the wire
stretcher rod of the electrostatic cell;
5. keeping the ionisation wire stretched, with the other hand
hook it to the other wire stretching rod, always by means of the curved beaks pliers.
310
44
9 - MAINTENANCE
!
9.9 Condensate collection bowl
Dirt or scale can give rise to clogging. Also, microorganisms and mould can flourish in the bowl. It is
very important to foresee periodical cleaning with suitable detergents and, eventually, disinfect with sanitising products.
Once cleaning is completed, pour water inside the bowl to check the regular outflow.
9.10 Indoor air coil
Accidental contact with the exchanger flaps can cause injuries from cut: use protective gloves.
The finned surfaces of the cooling coils and, in particular, the condensate collection bowls constitute places where microorganisms and moulds greatly flourish. It is very important to foresee periodical cleaning with suitable detergents and, eventually, disinfect with sanitising products.
45
9 - MAINTENANCE
9.11 Immerged electrodes humidifier- option
Do not use solvents or detergents to clean the plastic compo­nents.
For descaling use a vinegar or acetic acid solution at 20%, subsequently rinsing with water
PERIODICAL CHECKS
15
days
90
days
1 year
Cylinder: not over 300 hours of work checking operation, general state, no leaks
Cylinder: not over 1000 hours of work
checking operation, general state, no leaks, any replacement
Cylinder: not over 2500 hours of work (disposable cylinders) Load solenoid valve replacement: disconnect
electric power supply, dismantle valve, clean the drain solenoid valve filter:
disconnect electric power supply, remove reel and dismantle valve body and any impurity and rinse the power supply bowl, piping:
check they are free and without impurities
check the seal gasket between the cylinder and the drain
unit
remount the cylinder repeating the operations in reverse
order
Cylinder:
5 years
HUMIDIFIER CYLINDER DRAINAGE Cylinder must be drained in these situations:
not over 10000 hours of work (inspectional cylinders) replacement
cleaning of the cylinder emptying of the cylinder to avoid ice forming replacement of the cylinder
The manual drainage is carried out by means of selector SA7: see ELECTRIC CONNECTIONS chapter. REPLACEMENT OF THE CYLINDER To remove the cylinder: :
completely drain the water Interrupt power supply voltage of humidifier by means of
the unit isolator
remove the vapour pipe from the cylinder disconnect the electric connections of the electrodes and
remove the pins from the high level electrodes.
loosen the ring nut to remove the pipe unions and the filter
(when filter is outside the cylinder)
lift the cylinder to remove it
Before mounting it :
the filter body does not require replacing, wash it with
water and remount it on the new cylinder, using the new gasket provided with the latter
1. pipe fixing spring
2. vapour pipe
3. load pipe
4. vapour cylinder
5. seal O-rings
6. load valve
7. valves support
8. drain valve
9. bottom tank
10. pipe fixing spring
11. load pipe
12. too full pipe
46
10 - RESIDUE RISKS
Generality
The most common situations, as they cannot be controlled by the manufacturer, that may give rise to risk situations for things or persons are found in this section.
Dangerous area
It is the area in which only an authorised operator can act. The dangerous area is the area inside the unit, accessible only via removal of the cowling or parts of it.
Handling
The handling operations, if carried out without all the necessary safety devices and without the due caution, can cause the falling or overturning of the unit with consequent damages, even serious, to things, persons and the unit itself.
Handle the unit following the instructions on the packaging, in this manual and according to the local standards in force.
In case of coolant gas leak, refer to the coolant "Safety sheet".
Installation
An incorrect installation of the unit can cause water leaks, condense storage coolant leaks, electric shocks, fires, malfunctioning or damages to the unit itself.
Check installation is carried out only by qualified technical personnel and that the instructions in this manual and the local standards in force are complied with.
The unit installation in a place where, even occasionally, the flammable gas leaks and consequent storage of these gases in the area around the unit itself, can cause explosions and fires.
Installation of the unit in an unsuitable place to support the weight and/or guarantee an adequate anchoring, can cause the falling and/or overturning, with consequent damages to things, persons or the unit itself.
Carefully check positioning and anchoring of the unit. The easy access to the unit by children, unauthorised persons or
animals, may give rise to accidents and injuries, even serious. Install the unit in places accessible only by authorised personnel and/or
foresee protections against intrusions in the dangerous area.
General risks
Burnt odour, smoke or other signs of serious anomalies may show the arising of situations that can cause damages to things, persons or the unit itself.
Electrically isolate the unit (yellow-red isolator). Contact the after-sales authorised assistance centre to identify and
resolve the problem at origin of the anomaly. The accidental contact with exchange coils, compressors, supply piping
or other components can cause injuries and/or burns. Always wear adequate clothing that includes protective gloves for
operations inside the dangerous area. Maintenance and repair operations carried out by unqualified personnel
can cause damages to things, persons or the unit itself. Always contact a qualified after-sales assistance centre. The lack in closing the unit panels, or lack in checking the correct
fastening of all fastening screws of the panelling, can cause damages to things, persons or the unit itself.
Periodically check closing of all panels and their correct fastening. In the event of fire, the coolant temperature can reach values such to
bring the pressure over the safety value, with consequent possible projection of coolant or explosions of the circuit that remain isolated from closure of the cocks.
Do not stand near the safety valve and never leave the cooling system cocks closed.
Electrical part
An incomplete connection line to the electric mains and/or with incorrectly dimensioned cables, and/or with inadequate protective equipment, can cause electric shocks, intoxication, damages to the unit or fires.
Carry out all work on the electric system with reference to the wiring diagram and this manual, assuring use of a dedicated system.
An incorrect fastening of the lid of the electric components can favour entry of dust, water, etc. inside and consequently cause electric shocks, damages to the unit or fires.
Always securely fasten the lid to the unit. The metal masses of the unit, when powered and not correctly
connected to the earth system, can cause electric shocks or death for electrocution.
Carefully execute connection to the earth system. Contact with the accessible powered parts inside the unit after the
removal of guards can cause electric shocks, burns or death for electrocution.
Open and padlock the main isolator before removing the guards and signal the works in progress with relative sign.
Contact with parts that may power due to unit start-up, can cause electric shocks, burns or death for electrocution.
When not necessary.
Moving parts
Contact with the transmissions or suction of the fans can cause injuries. Before accessing inside the unit, open the isolator on the unit connection
line, padlock it and expose appropriate sign. Contact with the fans can cause injuries. Before removing the protective grilles or fans, open the isolator on the
unit connection line, padlock it and expose relative sign.
Coolant
The intervention of the safety valves and the consequent coolant gas expulsion can cause injuries and intoxication. Always wear adequate clothing and protective goggles for operations inside the dangerous area.
In case of coolant gas leak, refer to the coolant "Safety sheet". Contact between naked flames or sources of heat with coolant, or the
heating of the pressurised gas circuit (e.g. during welding), can cause explosions or fires.
Do not place any source of heat inside the dangerous area. The maintenance or repair interventions requiring welding must be done
with system drained.
Hydraulic part
Defects in the piping, in the connections or in the shut-off parts, can cause water leaks or projections, with consequent damages to things or short circuits of the unit.
47
11 - DISPOSAL
11.1 Disconnection
The disconnection operations must be carried out by qualified technicians.
Avoid pouring or leaking in room. Before disconnecting the unit recover, if present: :
- the coolant gas
- solutions to be cooled present inside the hydraulic circuits
While awaiting dismantling and disposal, the unit can be
stored, even outdoor, as bad weather and temperature changes do not cause damaging effects for the environment, as long as the unit has the electric, cooling and hydraulic circuits intact and closed.
11.2 Dismantling
FOR DISMANTLING AND DISPOSING THE UNIT MUST ALWAYS BE DELIVERED TO AUTHORISED CENTRES.
During dismantling, the fan, the motor and the coil, if working, may be recovered by the specialised centres for an eventual reuse.
All materials must be recovered or disposed or in compliance with the relative national standards in force.
For further information on the dismissal of the unit, contact the manufacturing company.
11.3 EC WEEE Directive
The units falling within the standard in question are marked with the symbol at the side.
With a view of respecting the environment, our units are manufactured in accordance with EC Directive on waste electric and electronic equipment (WEEE).
The potential effects on the environment and on personal health, due to the presence of dangerous substances, are reported inside the use and maintenance manual, in the residue risks section.
If necessary, additional information to that listed below can be requested from the manufacturer/distributor/importer, as responsible for the collection/treatment of waste deriving from equipment contemplated by EC - WEEE, and the dealer from where the equipment was purchased or the local services in charge of waste collection.
The EC-WEEE Directive foresees that the disposal and recycling of electric and electronic equipment, indicated therein, are compulsorily managed through appropriate collection, in adequate centres, separate to that used for the disposal of mixed urban waste.
The user must not dispose of the equipment at the end of its life-span, as urban waste, but convey it to appropriate collection centres, as foreseen by the current standards or indicated by the distributor.
48
General technical data
49
General technical data - Performance
Size
Operation with constant supply temperature
Standard air ow
Nominal air ow l/s 361 611 1278 2000 2638 3333 Nominal air ow m³/h 1300 2200 4600 7200 9500 12000 Max external static pressure (supply) Pa 630 630 630 600 420 630 Max external static pressure (extraction) Pa 630 630 630 630 540 630
Cooling
Total cooling capacity 1 kW 10,60 17,50 38,7 58,4 79,0 95,9 Re-heating capacity 1 kW 2,70 4,20 10,9 14,9 21,3 22,9 Compressor power input 1 kW 2,91 4,92 11,10 15,70 20,40 23,20 EER_C 1 - 4,57 4,41 4,47 4,67 4,91 5,12
Heating
Heating capacity 2 kW 5,93 10,00 21,0 32,9 43,4 54,9 Compressor power input 2 kW 0,71 1,35 2,54 4,22 5,75 8,77 COP_C 2 - 8,38 7,45 8,28 7,80 7,55 6,26
Operation at the maximum available capacity
Standard air ow
Nominal air ow l/s 361 611 1278 2000 2638 3333 Nominal air ow m³/h 1300 2200 4600 7200 9500 12000 Max external static pressure (supply) Pa 630 630 630 600 420 630 Max external static pressure (extraction) Pa 630 630 630 630 540 630
Cooling
Total cooling capacity 3 kW 10,60 17,50 38,7 58,4 79.0 95.9 Compressor power input 3 kW 3,26 5,52 12,5 17,7 22,9 26.1 Additional available capacity to space 3 kW 3,57 5,67 14,0 19.8 27.7 30.9 EER_C 3 - 3,25 3,18 3,10 3,31 3.45 3.68
Heating
Heating capacity 4 kW 10,50 17,80 37,1 58,2 76,8 96,9 Compressor power input 4 kW 2,28 3,77 7,13 11,2 14,4 18,3 COP_C 4 - 4,61 4,72 5,21 5,20 5,33 5,29
Operation with high airow
Maximum air ow
Nominal air ow l/s 528 972 1944 2556 3194 3889 Nominal air ow m³/h 1900 3500 7000 9200 11500 14000 Max external static pressure (supply) Pa 630 470 630 450 345 630 Max external static pressure (extraction) Pa 630 630 630 530 400 630
Cooling
Total cooling capacity 5 kW 9,20 18,20 31,9 45,1 62,0 80,6 Compressor power input 5 kW 1,56 3,38 4,46 6,97 13,8 17,8 EER_C 5 - 5,89 5,38 7,15 6,48 4,50 4,51
Heating
Heating capacity 6 kW 6,00 11,10 22,10 29,10 36,30 44,20 Compressor power input 6 kW 0,54 1,31 2,48 3,11 3,40 5,44 COP_C 6 - 11,10 8,46 8,91 9,36 10,7 8,14
DB = dry bulb WB = wet bulb EER_C = Thermodynamic eciency of the system in cooling mode COP_C = Thermodynamic eciency of the system in heating mode
1. Outdoor air temperature: 35°C D.B./ 24°C W.B.. Extracted air temperature 26°C D.B.. Supply air humidity ratio: 11g/kg. Supply air temperature 24°C D.B.
2. Outdoor air temperature 7°C D.B./ 6.0°C W.B.. External air temperature 20°C D.B. / 12°C W.B.. Supply air temperature 20°C D.B.
3. Outdoor air temperature 35°C D.B./ 24°C W.B.. Extracted air temperature: 26°C D.B.. Supply air humidity ratio: 11g/kg
4. Outdoor air: 7°C D.B./ 6.0°C W.B.. Extracted air temperature: 20°C D.B. / 12°C W.B.. Supply air temperature: 30°C D.B.
5. Outdoor air temperature 35°C D.B./ 24°C W.B.. Extracted air temperature 26°C D.B.. Supply air temperature 22°C D.B.
6. Outdoor air temperature: 7°C D.B./ 6.0°C W.B.. Extracted air temperature: 20°C D.B. / 12°C W.B.. Supply air temperature: 16°C D.B.
Size 1 Size 2 SIZE 3 Size 4 Size 5 Size 6
General technical data - Construction
50
Size
Compressor Type of compressors ROT Scroll Scroll Scroll Scroll Scroll No. of compressors No 1 1 2 2 3 3 Std Capacity control steps No 20-100% 20-100% 10-100% 10-100% 8-100% 8-100% Refrigeration circuits No 1 1 2 2 2 2 Air Handling Section Fans (Supply) Type of supply fan RAD RAD RAD RAD RAD RAD Number of supply fans No 1 1 1 1 1 2 Fan diameter mm 310 355 500 630 630 500 Minimum air ow l/s 278 444 917 1444 2083 2639 Minimum air ow m³/h 1000 1600 3300 5200 7500 9500 Maximum air ow l/s 528 972 1944 2556 3194 3889 Maximum air ow m³/h 1900 3500 7000 9200 11500 14000 Installed unit power kW 0,80 0,90 2,70 2,80 2,80 2,70 Max. static pressure supply fan Pa 630 630 630 600 420 630 Fans (Exhaust) Type of exhaust fan RAD RAD RAD RAD RAD RAD Number of exhaust fans No 1 1 1 1 1 2 Fan diameter mm 310 355 500 630 630 Exhaust air ow l/s 361 611 1278 2000 2638 3333 Installed unit power kW 0,80 0,90 2,70 2,80 2,80 2,70 Max. exhaust static pressure Pa 630 630 630 600 540 630 Connections Condensate discharge 1” GAS 1” GAS 1” GAS 1” GAS 1” GAS 1” GAS Power supply Standard power supply V 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 Dimensions A - Length mm 1895 1895 2465 2465 2465 2465 B - Width mm 950 950 1735 1735 2025 2330 C - Height mm 1025 1625 1810 2260 2260 2260 Standard unit weights Shipping weight kg 320 450 1070 1285 1450 1670 Operating weight kg 320 450 1070 1285 1450 1670
Size 1 Size 2 SIZE 3 Size 4 Size 5 Size 6
500
ROT = rotary compressor SCROLL = scroll compressor RAD = radial fan
Sound levels
51
The sound pressure level refers to a distance of 1 meter from the outer surface of the unit operating in open eld.
Static pressure 50 Pa (UNI EN ISO 9614-2)
For the standard air supply the total sound power levels for the diverse values of available static pressure are shown.
Please note that when the unit is installed in conditions dierent from nominal test conditions (e.g. near walls or obstacles in general), the sound levels may undergo substantial variations.
AIR SUPPLY MINIMUM (50 Pa)
Sound power level (dB) Sound
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
Size 1 54 52 56 59 68 69 62 70 58 74
Size 2 55 53 57 60 69 70 63 71 59 75
SIZE 3 60 58 61 64 72 73 66 74 61 79
Size 4 66 68 66 66 71 72 66 73 59 79
Size 5 67 69 67 67 72 73 67 74 60 80
Size 6 69 68 70 73 75 74 69 74 62 81
Octave band (Hz)
pressure
AIR SUPPLY STANDARD (50 Pa) AIR SUPPLY STANDARD (100,200,300 Pa)
level
Sound power
level
Sound power level (dB)
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
Size 1 59 60 65 69 72 72 63 69 60 77
Size 2 60 61 66 70 73 73 65 70 61 78
SIZE 3 66 65 67 70 73 74 67 74 61 80
Size 4 67 69 67 67 72 73 67 74 60 80
Size 5 74 75 75 74 75 74 69 74 62 83
Size 6 74 75 77 79 78 76 71 73 64 85
Octave band (Hz)
Sound
pressure
level
MAXIMUM AIR SUPPLY (50 Pa)
Sound power level (dB)
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
Size 1 65 69 75 77 77 73 65 68 64 82
Size 2 66 70 76 78 78 74 66 69 65 83
SIZE 3 74 75 77 79 78 77 72 74 66 85
Size 4 77 78 77 76 77 77 71 75 64 85
Size 5 78 80 79 78 77 76 71 74 64 86
Size 6 77 78 80 82 81 79 74 75 67 88
Octave band (Hz)
Sound
pressure
level
Sound power
level
Sound power
level
Sound power level (dB)
Size
Size 1 77 77 78
Size 2 78 78 79
SIZE 3 80 80 81
Size 4 80 80 81
Size 5 83 84 84
Size 6 85 85 86
Available head (Pa)
100 200 300
Operation with constant supply temperature T_OA = 35/24°C T_RA = 26°C T_SA = 24°C X_SA = 11g/kg T_OA = Outdoor air temperature at Dry/Wet bulb [°C] T_OA = Exhaust air temperature at Dry bulb [°C] T_SA = Dry bulb supply air temperature [°C] X_SA = Supply air humidity ratio [g/kg]
Operating ranges
52
Operating range (Cooling)
The limits are indicative and take into consideration:
general and non specic sizes
unit correctly installed and serviced
Outdoor air
1 = Normal operating range 2 = Operating range with capacity modulation 3 = With option RECH - “Hydronic recovery device”, with T_RA = 26° D.B. 4 = With option RECH - “Hydronic recovery device”, with T_RA = 24° D.B. 5 = With option RECH - “Hydronic recovery device”, with T_RA = 22° D.B.
Outdoor air temperature limit at wet bulb
T_OA (W.B)
A °C 10
B °C 14
C °C 26
T_RA = extracted air temperature
Extracted air
T_OA = outdoor air temperature T_RA = extracted air temperature DB = dry bulb WB = wet bulb
1 = Normal operating range 2 = Operating range with capacity modulation
T_RA = extracted air temperature DB = dry bulb WB = wet bulb
Operating range (Heating)
53
The limits are indicative and take into consideration:
general and non specic sizes
unit correctly installed and serviced
Outdoor air
1 = Normal operating range 2 = Operating range with capacity modulation 3 = With “RECH - Hydronic recovery device”
Extracted air
1 = Normal operating range 2 = Operation in which they could be defrost cycles
Extracted air temperature limit at wet bulb
T_RA (W.B)
A °C 10,2
B °C 6,0
T_RA = extracted air temperature WB = wet bulb
T_OA = outdoor air temperature DB = dry bulb WB = wet bulb
T_RA = extracted air temperature DB = dry bulb WB = wet bulb
WARNING: failure to comply with the lower limit of wet bulb temperature can cause the unit to stop.
Dimensional drawings
54
SIZE 1
DAA5Gsize1_0
Date: 21/09/2012
(1) Capacity modulating compressor (2) Electrical panel (3) Power input (4) Condensation drain pipe Ø 20 mm (5) Standard outdoor air exchanger (below) (6) Exhaust air standard exchanger (above) (7) Capacity modulating post-heating with hot gas recovery (8) Hydronic recovery device for extended operating range (Optional) (9) Electrical heaters (10) Electronic lters (11) Class G4 air lters on outdoor and exhaust air (12) Supply fan (below) (13) Exhaust fan (above) (14) Air lters access (15) Grid for indoor installation (Optional) (16) Lifting holes (17) Functional spaces (18) If the unit is placed against the wall provide the space for the replacement of the roof electric fan (R) Return Air (M) Supply Air (AE) Outdoor air intake (ES) Exhaust air
WEIGHT DISTRIBUTION
Size Size 1
W1 Supporting Point kg 78
W2 Supporting Point kg 82
W3 Supporting Point kg 82
W4 Supporting Point kg 78
Shipping weight kg 320
SIZE 2
55
DAA5Gsize2_0
Date: 21/09/2012
(1) Capacity modulating compressor (2) Electrical panel (3) Power input (4) Condensation drain pipe Ø 20 mm (5) Standard outdoor air exchanger (below) (6) Exhaust air standard exchanger (above) (7) Capacity modulating post-heating with hot gas recovery (8) Hydronic recovery device for extended operating range (Optional) (9) Electrical heaters (10) Electronic lters (11) Class G4 air lters on outdoor and exhaust air (12) Supply fan (below) (13) Exhaust fan (above) (14) Air lters access (15) Grid for indoor installation (Optional) (16) Lifting holes (17) Functional spaces (18) If the unit is placed against the wall provide the space for the replacement of the roof electric fan (R) Return Air (M) Supply Air (AE) Outdoor air intake (ES) Exhaust air
WEIGHT DISTRIBUTION
Size Size 2
W1 Supporting Point kg 110
W2 Supporting Point kg 115
W3 Supporting Point kg 116
W4 Supporting Point kg 109
Shipping weight kg 450
SIZE 3
56
DAA5Gsize3_0
Date: 21/09/2012
(1) Capacity modulating compressor (2) Electrical panel (3) Power input (4) Condensation drain pipe Ø 20 mm (5) Standard outdoor air exchanger (below) (6) Exhaust air standard exchanger (above) (7) Capacity modulating post-heating with hot gas recovery (8) Hydronic recovery device for extended operating range (Optional) (9) Electrical heaters (10) Electronic lters (11) Class G4 air lters on outdoor and exhaust air (12) Supply fan (below) (13) Exhaust fan (above) (14) Air lters access (15) Grid for indoor installation (Optional) (16) Support brackets (can be removed after the unit is positioned) (17) Functional spaces (18) If the unit is placed against the wall provide the space for the replacement of the roof electric fan (R) Return Air (M) Supply Air (AE) Outdoor air intake (ES) Exhaust air
WEIGHT DISTRIBUTION
Size SIZE 3
W1 Supporting Point kg 259
W2 Supporting Point kg 273
W3 Supporting Point kg 289
W4 Supporting Point kg 249
Shipping weight kg 1070
Size 4
57
DAA5Gsize4_0
Date: 21/09/2012
(1) Capacity modulating compressor (2) Electrical panel (3) Power input (4) Condensation drain pipe Ø 20 mm (5) Standard outdoor air exchanger (below) (6) Exhaust air standard exchanger (above) (7) Capacity modulating post-heating with hot gas recovery (8) Hydronic recovery device for extended operating range (Optional) (9) Electrical heaters (10) Electronic lters (11) Class G4 air lters on outdoor and exhaust air (12) Supply fan (below) (13) Exhaust fan (above) (14) Air lters access (15) Grid for indoor installation (Optional) (16) Support brackets (can be removed after the unit is positioned) (17) Functional spaces (18) If the unit is placed against the wall provide the space for the replacement of the roof electric fan (R) Return Air (M) Supply Air (AE) Outdoor air intake (ES) Exhaust air
WEIGHT DISTRIBUTION
Size Size 4
W1 Supporting Point kg 312
W2 Supporting Point kg 328
W3 Supporting Point kg 347
W4 Supporting Point kg 299
Shipping weight kg 1285
SIZE 5
58
DAA5Gsize5_0
Date: 21/09/2012
(1) Capacity modulating compressor (2) Electrical panel (3) Power input (4) Condensation drain pipe Ø 20 mm (5) Standard outdoor air exchanger (below) (6) Exhaust air standard exchanger (above) (7) Capacity modulating post-heating with hot gas recovery (8) Hydronic recovery device for extended operating range (Optional) (9) Electrical heaters (10) Electronic lters (11) Class G4 air lters on outdoor and exhaust air (12) Supply fan (below) (13) Exhaust fan (above) (14) Air lters access (15) Grid for indoor installation (Optional) (16) Support brackets (can be removed after the unit is positioned) (17) Functional spaces (18) If the unit is placed against the wall provide the space for the replacement of the roof electric fan (R) Return Air (M) Supply Air (AE) Outdoor air intake (ES) Exhaust air
WEIGHT DISTRIBUTION
Size Size 5
W1 Supporting Point kg 348
W2 Supporting Point kg 370
W3 Supporting Point kg 399
W4 Supporting Point kg 334
Shipping weight kg 1450
SIZE 6
59
DAA5Gsize6_0
Date: 21/09/2012
(1) Capacity modulating compressor (2) Electrical panel (3) Power input (4) Condensation drain pipe Ø 20 mm (5) Standard outdoor air exchanger (below) (6) Exhaust air standard exchanger (above) (7) Capacity modulating post-heating with hot gas recovery (8) Hydronic recovery device for extended operating range (Optional) (9) Electrical heaters (10) Electronic lters (11) Class G4 air lters on outdoor and exhaust air (12) Supply fan (below) (13) Exhaust fan (above) (14) Air lters access (15) Grid for indoor installation (Optional) (16) Support brackets (can be removed after the unit is positioned) (17) Functional spaces (18) If the unit is placed against the wall provide the space for the replacement of the roof electric fan (R) Return Air (M) Supply Air (AE) Outdoor air intake (ES) Exhaust air
WEIGHT DISTRIBUTION
Size Size 6
W1 Supporting Point kg 401
W2 Supporting Point kg 426
W3 Supporting Point kg 459
W4 Supporting Point kg 384
Shipping weight kg 1670
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy Tel. + 39 0439 3131 - Fax + 39 0439 313300 - info@clivet.it
CLIVET UK LTD (Sales)
4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - info@clivet-uk.co.uk
CLIVET AIRCON LTD (Service and Maintenance Division)
Units F5&F6 Railway Triangle Ind Est, Walton Road - Portsmouth, Hampshire - PO6 1TG - United Kingdom Tel. +44 (0) 2392 381235 - Fax. +44 (0) 2392 381243 - info@clivetaircon.co.uk
CLIVET ESPAÑA COMERCIAL S.L. (Sales)
Calle Gurb, 17 1º 1ª - 08500 Vic, Barcelona - España Tel: +34 93 8606248 - Fax +34 93 8855392 - info@clivetcomercial.com
CLIVET ESPAÑA S.A.U. (Service and Maintenance Division)
Calle Real de Burgos Nº 12 - 28860 Paracuellos del Jarama, Madrid - España Tel. +34 91 6658280 - Fax +34 91 6657806 - info@clivet.es
CLIVET GmbH
Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - info.de@clivet.com
CLIVET RUSSIA
Elektrozavodskaya st. 24, oce 509 - 107023, Moscow, Russia Tel. + 74956462009 - Fax + 74956462009 - info.ru@clivet.com
CLIVET MIDEAST FZCO
Dubai Silicon Oasis (DSO), High Bay Complex, Ind Unit No. 3, PO BOX 342009, Dubai, UAE Tel. + 9714 3208499 - Fax + 9714 3208216 - info@clivet.ae
CLIVET AIRCONDITIONING SYSTEMS PRIVATE LIMITED
4BA, Gundecha Onclave - Kherani Road,Saki Naka, Andheri (East) - Mumbai 400 072 - India Tel. +91 22 6193 7000 - Fax +91 22 6193 7001 - info.in@clivet.com
www.clivet.com
Loading...