High efficiency cooling only packaged air-conditioner condenser, ductable for
indoor installation
Installation use and maintenance manual
M04T40G12-05 28-04-14
Dear Customer,
We congratulate you on choosing these product.
Clivet is being working for years to offer systems able to assure the maximum
comfort for long time with high reliability, efficiency , quality and safety. The
target of the company is to offer advanced systems, that assure the best comfort, reduce the energy con-sumption, the installation and maintenance costs
for all the life-cycle of the system.
With this manual, we want to give you information that are useful in all the
phases: from the reception, to the installation and use until the disposal so
that a system so advanced offers the best procedure of installation and use.
Best regards and have a nice reading !
CLIVET Spa
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice. All reproduction, even partial, is prohibited.
2
INDEX
General
1
Reception
2
Positioning
3
Water connections
4
5
Aeraulic connections
6
Electrical connections
Start-up
7
8
Control
9
Maintenance
4
7
8
9
12
13
17
20
26
Decommissioning
10
Technical information
11
Residual risks
12
30
31
36
3
1 - GENERAL
1.1 MANUAL
The manual provides correct unit installation, use and
maintenance.
Pay particolar attention to:
Warning identifies particularly important operations or
information .
Prohibited operations that must not be carried out, that
compromise the operating of the equipment or may cause
damage to persons or things.
• It is advisable to read it carefully so you will save time
during operations.
• Follow the written indications so you will not cause
damages to things and injuries people. The preliminary
information must be read prior to carrying out any of the
following operations.
1.2 GENERAL INSTRUCTIONS
Preliminaries
The positioning, hydraulic system, refrigerating, electrics and
the channelisation of the air must be determined by the
system designer in accordance with local regulations in force.
On the unit can operate only qualified personal , as
determined by the regulations in force.
Using the unit in case of breakdown or malfunction :
• voids the warranty
• may compromise the safety of the machine
• may increase time and repair costs.
Follow local safety regulations. .
Keep packing material out of children’s reach it may be
dangerous. .
Recycle and dispose of packing material in conformity with
local regulations. .
Risk situations
The unit has been designed and created to prevent injures to
people.
During designing it is not possible to plane and operate on all
risk situation.
Read carefully "Residual risk" section where all situation
which may cause damages to things and injuries to people
are reported.
Installation, starting, maintenance and repair required specific
knowledge; if they are carried out by inexperienced personnel,
they may cause damages to things and injuries people.
Intended use
Use the unit for :
within limits defined in the technical bulletin and on this
manual.
Any use other than intended does not involve the
manufacturer in any commitment or obligation. .
CIVIL AIR-CONDITIONING
Installation
Verify that the electrical line characteristics are in compliance
with data quotes on the unit serial number label.
Maitenance
Plan periodic inspection and maintenance in order to avoid or
reduce repairing costs.
Turn the machine off before any operation.
Modification
All unit modifications will end the warranty coverage and the
manufacturer responsibility. .
Breakdown/Malfuction
Disable the unit immediately in case of breakdown or
malfunction. .
Contact a constructor certified assistance service.
Use original spares parts only.
User training
The installer has to train the user on :
• start-up / shutdown;
• set points change;
• standby mode;
• maintenance;
• what to do / what not to do in case of breakdown.
Data update
Continual product improvements may imply manual data
changes .
Visit manufacturer web site for updated data
1.3 INDICATIONS FOR THE USER
Keep this manual with the wiring diagram in an accessible
place for the operator.
Note the unit lable data so you can provide them at the assistance centre in case of intervention (see "Unit identification"
section).
Provide a machine notebook that allows any interventions
carried out on the machine to be noted and tracked making it
easier to suitably note the various interventions and aids the
search for any breakdowns.
In case of breakdown or malfunction:
.
• immediately deactivate the unit .
• contact a constructor certified assistance service.
• use original spares parts only
Ask the installer to format on:
• start-up / shutdown;
• set points change;
• standby mode;
• maintenance;
• what to do / what not to do in case of breakdown.
4
1 - GENERAL
1.4 UNIT INDENTIFICATION
Serial number label
The serial number label is positioned on the unit and allows to
indentify all the unit features.
It has not to be removed for any reason.
It reports the regulations indications such as:
• machine type,
Series CAS-X
Size 31 ...... 222
• serial number
Axxxxxxxxxxx
• year of manufacture
• wiring diagram number
• electrical data
• manufacturer logo and address .
Serial number
It identifies uniquely each machine.
It identifies specific spare parts for the machine.
Assistance request
Note data from the serial number label and write them in the
chart on side, so you will find them easily when needed.
In case of intervention you have to provide data.
Typology
Size
1.5 UNIT DESCRIPTION
R Air intake
Optional: front, bottom or rear.
S Treated air supply
Optiona: upwards or rear.
A Supply fan and air filter
Electronic control, which returns the air to the setting
after having taken it in, strained it with G4 efficiency and
treated it
B Internal exchanger
It transfers energy (heat/cool)to the fresh supply air
C Source side exchanger
It exchanges energy (heat or cool) with the outdoor air
D Direct expansion circuit
Produces cool or heat energy through Scroll
compressors and an electronic expansion valve
E User interface
Easy to use, with automatic control sensors built-in
MAIN OPTIONS
1 Hot gas post-heating /Hot water heating
Gas post-heating recovers condensation energy in
summer humidity control. The hot water heating
(available as an alternative), when necessary,
integrates or substitutes the workings of the direct
expansion circuit
2 Electric heating
Integrates or substitutes the workings of the direct
expansion circuit when necessary
.
Serial number
Year of manufacture
Wiring diagram
A
R
D
S
2
1
B
E
C
5
1 - GENERAL
1.6 ACCESSORIES
CONFIGURATIONS
CHW2 two-rows hot water coil
REFRIGERANT CIRCUIT
MHP high and low pressure gauges
EVE Electronic expansion valves
CPHG hot gas re-heating coil (available only with options: CSOND-CTERM)
AIR SIDE FEATURES
M5 Upward supply air - standard
MP Rear supply air
R3 Downflow return
R4 Rear air inlet
RF Front air inlet - standard
PCOSM Constant supply airflow
FPG4 Pleated air filter class G4 (EN779 norm) - standard
PSAF differential pressure switch for dirty air filters
PO3X Air supply plenum on three sides (separately supplied accessories)
PF500X Front air supply plenum H=500mm (separately supplied accessories)
WATER CIRCUIT
CUE External humidifier control with 0-10V command (available only with options: CSOND-CTERM)
3WVM modulating three-way valve (available only with options: CHW2)
3WVPX modulating three-way valve (separately supplied accessories)
MIPC Hydraulic pipework arrangement for loop with constant flow rate with manual valves
MIPV Hydraulic pipework arrangement for loop with variable flow rate with 2 way ON-OFF valve
MIPM Hydraulic pipework arrangement for loop with disposable water system with 2-way modulating valve
ACIS Antifreeze heater protection on the water side exchanger
IFWX Steel mesh strainer on the water side (separately supplied accessories)
SYSTEM ADMINISTRATORS
CMSLWX LonWorks serial communication module (available only with options: MOB) (separately supplied accessories)
BACX BACnet serial communication module (available only with options: MOB) (separately supplied accessories)
ELECTRIC CIRCUIT
MOB serial port RS485 with Modbus protocol
CTERM Remote keypad for indoor temperature and humidity control
CSOND Temperature and humidity ambient control with built-in probes (available only with options: CONTE)
CTEM Temperature ambient control with built-in probe (available only with options: CONTE)
EH09 4,5 kW electric heaters
EH10 6 kW electric heaters
EH12 9 kW electric heaters
EH14 12 kW electric heaters
EH17 18 kW electric heaters
EH22 27 kW electric heaters
EH24 36 kW electric heaters
CWM Electronic room control with display, for wall installation
CONTE Electronic room control with display visible on the unit (available only with options: CSOND-CTEM)
CIWM Electronic room control with display, for wall installation in built-in box
PM phase monitor
PFCP power factor correction capacitors (cosfi > 0.9)
Operate in compliance with safety regulations in force .
For detailed information (dimensions, weight, technical
characteristics etc.) please refer to the “Technical
information” section.
Use single protection devices : gloves, glasses ecc.
Stocking
Observe external packing instructions .
Handling
Verify unit weight and handling equipment lifting
capacity .
Identify critical points during handling (disconnected
routes, flights, steps, doors).
Verify the position of the barycentre in the Technical
information - DIMENSIONS section.
Before handling verify that the unit keeps its balance.
Packing removing
Be careful not to damage the unit.
Recycle and dispose of packing material in conformity
with local regulations.
2.3 HANDLING
Considerer that the barycentre could out of centre
Use protection to avoid the unit damaging
2.2 DELIVERY CONTROL
Before accepting the delivery you have to check:
• That the unit hasn’t been damaged during tran-
sport.
• Check that the materials delivered correspond
with that indicated on the transport document
comparing the data with the identification label ‘A’
positioned on the packaging.
In case of damage or anomaly:
• Write down on the transport document the da-
mage you found and quote this sentence:
"Conditional acceptance — clear evidence of
deficiencies/damages during transport".
• Contact supplier and the carrier by fax and regi-
stered mail with advice of receipt.
Any disputes must be made within the 8 days following
the delivery. Complaints after this period are invalid.
7
3 - POSITIONING
3.1 PRELIMINARY INFORMATION
Operate in compliance with safety regulations in force.
For detailed information (dimensions, weight, technical
characteristics etc.) please refer to the TECHNICAL
INFORMATION section.
Use single protection devices : gloves, glasses ecc.
During positioning consider these elements :
• technical spaces required for the machine and system
• place where the machine will be installed
• electrical connections
• water connections
• air / aeraulic ducts
Do not considerer these elements could decrease
performances and operational life of the unit.
3.2 FUNCTIONAL SPACES
Functional spaces are designed to:
• guarantee good unit operation
• Carry out maintenance operations
• protect authorized operators and exposed people
Respect all functional spaces indicated in the TECHNICAL
INFORMATION section.
Double all functional spaces if two or more unit are aligned.
3.3 POSITIONING
Units are designed to be installed:
• INTERNAL
• in fixed positions.
Limit vibration transmission:
• use antivibration devices on unit bearing/supporting
points;
• install flexible joints on the hydraulic.
Installation standards:
• Safe accessible position;
• avoid flood-prone places;
• verify unit weight and bearing point capacity;
• verify that all bearing points are aligned and leveled;
8
4 - WATER CONNECTIONS
4.1 PRELIMINARY INFORMATION
Selection and installation of system components must
be carry out by installer.
Following you will find some indications to integrate
with what is provided by the local regulations in force
and by the good technical laws.
4.2 COMPONENTS
CUT-OFF VALVES :
• installed at inlet and outlet allow maintenance
operations without having to empty the system .
THERMOMETERS AND MANOMETERS :
• installed at entry and exit of the main elements
facilitate inspection and maintenance.
AN AIR BLEED VALVE :
• installed in all of the highest points of the system
allowing the venting of the circuits air.
DRAINAGE TAPS :
• installed in the lowest points of the system to allow
bleeding.
EXPANSION TANK :
• It keeps a correct system pressure when the water
temperature changes. It must be dimensioned as a
function of water content. Could be necessary install
in addition on the unit one or more of it
WATER FILTER :
.
• must be installed immediately in the water input of
the unit, in a position that is easily accessible for
cleaning.
• The filter should never be re-moved, this operation
invalidates the guaranty .
• filter features:
Size
Ø1”
filtration mesh (micron)
SUPPORTS :
31-81 82-102 122-222
1"
¼
500μm 600μm 600μm
1" ½
• The hydraulic pipes weight mustn’t burden on the
unit connections ..
FLOW SWITCH
• The flow switch must be present as a component of
the system
4.3 OPERATION SEQUENCE
Before connecting the unit, carefully wash the system by
filling it and emptying it several times with clean water.
In the units equipped with hydraulic pipeworks use the
bypass.
Ignoring this operation will lead to several filter cleaning
interventions and at worst cases can cause damages to
the exchangers and the other parts.
Execute leakage test before isolate the pipes.
To avoid heat dispersions and formation of condensate
isolate all the pipes.
Leave various point of service free (wells, vent-holes
etc )
4.4 WATER QUALITY
The water quality is determined by the following
factors, avoid therefore:
• Inorganic salts
• pH
• Biological load (seaweeds etc)
• Suspended solids
• Dissolved oxygen
Water with inadequate characteristics can cause:
• pressure drop increase
• energy efficiency decrease
• corrosive symptom increase
4.5 RISK OF FREEZE
If the unit or the relative water connections can be
subject to temperatures close to 0°C adopt measures
for prevent risk of freeze.
For example:
• Mix water with ethylene glycol
• Safeguard the pipes with heating cables placed
under the insulation
• Empty the system in cases of long non-use and
check that:
• there are no closed taps present that could trap
water even after emptying
• there are no low points in which water can
stagnate even after emptying; carry out any
blowing required .
4.6 ANTI-FREEZE SOLUTION
Consider that the use of anti-freeze solution determines an increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not
corrosive) and compatible with the hydraulic circuit
components (pump etc).
9
CONNECTION SOURCE SIDE
4.7 STANDARD UNIT
4 - WATER CONNECTIONS
4
3
The standard unit is equipped with the following components:
1. plate heat exchanger complete with water side differential
pressure switch and a water temperature control probe
2. drain bibcock
3. bleed bibcock
3
T
PD
1
2
4.8 PLUMBING ASSEMBLY
FOR LOOP WITH CONSTANT
The plumbing assembly for the constant flow rate loop
includes, in addition to 1, 2 and 3 standard components :
4 two-way manually activated valves to make it possible
to disconnect the unit from the plumbing system for
maintenance.
5 manually activated three-way valve for loop wash by-
pass (to allow washing of the pipes of the system and
protect the heat exchanger against fouling);
4
3
T
PD
1
2
5
4.10 PLUMBING ASSEMBLY
FOR LOOP WITH DISPOSABLE WATER
The plumbing assembly for systems with disposable water
(from well or groundwater) includes in addition to 1, 2 and 3
standard components :
1 2-way motorised modulating valve at the exchanger
outlet (the operation is linked to that of the
refrigeration circuit:modulating the valve opening by 010V signal the water content is reduced and the unit
operation values are maintained within the limits
allowed)
2 manually activated three-way valve for loop wash by-
pass (to allow washing of the pipes of the system and
protect the heat exchanger against fouling);
In summer operation, the device, complete with modulating
valve, makes it possible to maximize the thermal differential
of the water and hence to reduce the water flow rate.
In winter operation, modulation of the water flow rate allows
the unit to function with the water loop at high temperature. An
additional advantage of using this device is the extension of
the operating limits of the unit in summer and winter.
T
PD
1
2
5
4.9 PLUMBING ASSEMBLY
FOR LOOP WITH VARIABLE
The plumbing assembly for the constant flow rate loop includes, in addition to 1, 2 and 3 standard components :
4 two-way motorize ON/OFF valve, operation is linked
to that of the refrigeration circuit: with the compressor
off the valve stays closed and as a result less water is
used
5 manually activated three-way valve for loop wash by-
pass (to allow washing of the pipes of the system and
protect the heat exchanger against fouling);
MAX. WORKING PRESSURE
• Standard unit = 700 kPa
• With ON/OFF valves = 700 kPa
• With manual valves = 700 kPa
• With modulating valve = 300 kPa
Aries effects and air bubbles can produce the overcoming and
cause water drops.
10
4 - WATER CONNECTIONS
4.11 CONDENSATE DISCHARGE
The condensate must be dispersed to avoid damages
to persons and property .
• Unit discharge fitting : the connection must avoid the
transmission of mechanical stresses and must be
performed paying attention to avoid the damaging of
the unit discharge fitting .
• Make a trap that, eliminating the depression caused
by the fan, stops the return of gas from the
discharge pipe
• The ducting must have an appropriate slope to allow
the downflow
• Anchor the ducting with an appropriate number of
supports.
Otherwise are generated ducting failures and air
pockets that prevent the downflow.
• Insulate the ducting and the siphon to avoid
condensate drippings
• Connect the condensate discharge to a rainwater
drain.
• Do NOT use sewerage drains, so as to avoid the
return of odours if the water contained in the trap
evaporates
• Finally, check that the condensate will drain
correctly by pouring water into the tray stud
Calculation of the siphon height T = 2P
S = T/2
P is the pressure determinate by the fan in
correspondence of the drain pain (1mm c.a = 9.81 Pa)
4.12 HEATING COIL - OPTION
B
A
A drain cock
B air vent
Supplied by the customer :
1 vibration isolators
2 ducting supports
3 shutoff valves
1
23
P
H
T
S
Exsample :
P = 300 Pa = 30 mm
T = 2P = 60 mm
S = T/2 = 30 mm
11
5 - AERAULIC CONNECTIONS
5.1 GENERAL
Proper execution and sizing of air connections are essential
for ensuring correct operation of the unit and an acceptable
level of silence in the room.
When designing and creating ducts, consider PRESSURE
DROPS, FLOW RATE and AIR SPEED which need to be
compatible with the characteristics of the unit.
Special consideration needs to be made for pressure drops
that are greater than the unit's static pressure, which would
lead to a reduction in flow rate resulting in unit shutdown.
• the weight of the ducts must not be supported by the
connection flanges
• place anti-vibration joints between the ducts and the unit
• the connection to the flanges and between the various
sections of the ducts must ensure an airtight seal, preventing leakage in delivery and return which would compromise overall system efficiency.
• limit pressure drops by optimizing the path, the type and
number of curves and the branches
• use curves with a wide radius. Consider whether it might
be useful to equip them with deflectors (especially if the air
speed is high or if curves are tight )
For purposes of comfort, the following things need to be considered:
• air diffusers must be selected by checking the sound
power generated at nominal flow rate conditions
• the disconnections to the diffusers are to be made
using flexible elements
• the return grilles must be amply sized
APPLICATIONS AT HIGH DEGREE OF SILENCE
For applications that require a high degree of silence in the
system:
• In delivery and return, provide septum silencers, pre-
ferably inserted in sections of ducts located outside
the building. The septums must ensure the required
dampening with minimum pressure drops (ONLY
OUTDOOR UNITS – do not print note).
• Equip all curves with deflectors.
5.2 FEATURES FOR DUCTS FOR TREATED AIR
• The inner surface of the duct must be smooth and washa-
ble. It must not contaminate the air.
• Thermally insulate the ducts and the flanges so as to pre-
vent loss of energy and condensation build-up.
GRILLES OUTLETS DIFFUSERS
Proper distribution of air in the room is essential for ensuring
comfort levels.
In the selection and positioning of grilles, outlets and diffusers,
the following are to be avoided:
• excessive air speed
• formation of stagnant zones and layering
• entry of cold air into the room
• formation of localized currents (due to uneven air
distribution)
• excessive variations in ambient temperature in the
vertical and horizontal planes
• short circuiting of delivery air towards return air
12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.