CLIVET CAS Series, CAS-41, CAS-51, CAS-31, CAS-61 Installation, Use And Maintenance Manual

...
Page 1
CAS-X 31-222
Installation use and maintenance manual
M04T40G12-05 28-04-14
Page 2
Dear Customer, We congratulate you on choosing these product. Clivet is being working for years to offer systems able to assure the maximum
comfort for long time with high reliability, efficiency , quality and safety. The target of the company is to offer advanced systems, that assure the best com­fort, reduce the energy con-sumption, the installation and maintenance costs for all the life-cycle of the system.
With this manual, we want to give you information that are useful in all the phases: from the reception, to the installation and use until the disposal so that a system so advanced offers the best procedure of installation and use.
Best regards and have a nice reading ! CLIVET Spa
The data contained in this bulletin is not binding and may be changed by the manufacturer wi­thout prior notice. All reproduction, even partial, is prohibited.
2
Page 3
INDEX
General
1
Reception
2
Positioning
3
Water connections
4
5
Aeraulic connections
6
Electrical connections
Start-up
7
8
Control
9
Maintenance
4
7
8
9
12
13
17
20
26
Decommissioning
10
Technical information
11
Residual risks
12
30
31
36
3
Page 4
1 - GENERAL
1.1 MANUAL
The manual provides correct unit installation, use and maintenance.
Pay particolar attention to:
Warning identifies particularly important operations or information .
Prohibited operations that must not be carried out, that compromise the operating of the equipment or may cause damage to persons or things.
It is advisable to read it carefully so you will save time
during operations.
Follow the written indications so you will not cause
damages to things and injuries people. The preliminary information must be read prior to carrying out any of the following operations.
1.2 GENERAL INSTRUCTIONS Preliminaries
The positioning, hydraulic system, refrigerating, electrics and the channelisation of the air must be determined by the system designer in accordance with local regulations in force.
On the unit can operate only qualified personal , as determined by the regulations in force.
Using the unit in case of breakdown or malfunction :
voids the warranty
may compromise the safety of the machine
may increase time and repair costs.
Follow local safety regulations. .
Keep packing material out of children’s reach it may be dangerous. .
Recycle and dispose of packing material in conformity with local regulations. .
Risk situations
The unit has been designed and created to prevent injures to people.
During designing it is not possible to plane and operate on all risk situation.
Read carefully "Residual risk" section where all situation which may cause damages to things and injuries to people are reported.
Installation, starting, maintenance and repair required specific knowledge; if they are carried out by inexperienced personnel, they may cause damages to things and injuries people.
Intended use
Use the unit for :
within limits defined in the technical bulletin and on this manual.
Any use other than intended does not involve the manufacturer in any commitment or obligation. .
CIVIL AIR-CONDITIONING
Installation
Verify that the electrical line characteristics are in compliance with data quotes on the unit serial number label.
Maitenance
Plan periodic inspection and maintenance in order to avoid or reduce repairing costs.
Turn the machine off before any operation.
Modification
All unit modifications will end the warranty coverage and the manufacturer responsibility. .
Breakdown/Malfuction
Disable the unit immediately in case of breakdown or malfunction. .
Contact a constructor certified assistance service.
Use original spares parts only.
User training
The installer has to train the user on :
start-up / shutdown;
set points change;
standby mode;
maintenance;
what to do / what not to do in case of breakdown.
Data update
Continual product improvements may imply manual data changes .
Visit manufacturer web site for updated data
1.3 INDICATIONS FOR THE USER
Keep this manual with the wiring diagram in an accessible place for the operator.
Note the unit lable data so you can provide them at the assi­stance centre in case of intervention (see "Unit identification" section).
Provide a machine notebook that allows any interventions carried out on the machine to be noted and tracked making it easier to suitably note the various interventions and aids the search for any breakdowns.
In case of breakdown or malfunction:
.
immediately deactivate the unit .
contact a constructor certified assistance service.
use original spares parts only
Ask the installer to format on:
start-up / shutdown;
set points change;
standby mode;
maintenance;
what to do / what not to do in case of breakdown.
4
Page 5
1 - GENERAL
1.4 UNIT INDENTIFICATION
Serial number label
The serial number label is positioned on the unit and allows to indentify all the unit features.
It has not to be removed for any reason.
It reports the regulations indications such as:
machine type,
Series CAS-X
Size 31 ...... 222
serial number
Axxxxxxxxxxx
year of manufacture
wiring diagram number
electrical data
manufacturer logo and address .
Serial number It identifies uniquely each machine.
It identifies specific spare parts for the machine. Assistance request
Note data from the serial number label and write them in the
chart on side, so you will find them easily when needed.
In case of intervention you have to provide data.
Typology
Size
1.5 UNIT DESCRIPTION
R Air intake Optional: front, bottom or rear.
S Treated air supply
Optiona: upwards or rear.
A Supply fan and air filter
Electronic control, which returns the air to the setting after having taken it in, strained it with G4 efficiency and treated it
B Internal exchanger
It transfers energy (heat/cool)to the fresh supply air
C Source side exchanger
It exchanges energy (heat or cool) with the outdoor air
D Direct expansion circuit
Produces cool or heat energy through Scroll compressors and an electronic expansion valve
E User interface
Easy to use, with automatic control sensors built-in
MAIN OPTIONS
1 Hot gas post-heating /Hot water heating
Gas post-heating recovers condensation energy in summer humidity control. The hot water heating (available as an alternative), when necessary, integrates or substitutes the workings of the direct expansion circuit
2 Electric heating
Integrates or substitutes the workings of the direct expansion circuit when necessary
.
Serial number
Year of manufacture
Wiring diagram
A
R
D
S
2
1
B
E
C
5
Page 6
1 - GENERAL
1.6 ACCESSORIES
CONFIGURATIONS
CHW2 two-rows hot water coil
REFRIGERANT CIRCUIT
MHP high and low pressure gauges EVE Electronic expansion valves
CPHG hot gas re-heating coil (available only with options: CSOND-CTERM)
AIR SIDE FEATURES
M5 Upward supply air - standard MP Rear supply air R3 Downflow return R4 Rear air inlet RF Front air inlet - standard PCOSM Constant supply airflow FPG4 Pleated air filter class G4 (EN779 norm) - standard PSAF differential pressure switch for dirty air filters PO3X Air supply plenum on three sides (separately supplied accessories) PF500X Front air supply plenum H=500mm (separately supplied accessories)
WATER CIRCUIT
CUE External humidifier control with 0-10V command (available only with options: CSOND-CTERM) 3WVM modulating three-way valve (available only with options: CHW2) 3WVPX modulating three-way valve (separately supplied accessories) MIPC Hydraulic pipework arrangement for loop with constant flow rate with manual valves MIPV Hydraulic pipework arrangement for loop with variable flow rate with 2 way ON-OFF valve MIPM Hydraulic pipework arrangement for loop with disposable water system with 2-way modulating valve ACIS Antifreeze heater protection on the water side exchanger
IFWX Steel mesh strainer on the water side (separately supplied accessories)
SYSTEM ADMINISTRATORS
CMSLWX LonWorks serial communication module (available only with options: MOB) (separately supplied accessories) BACX BACnet serial communication module (available only with options: MOB) (separately supplied accessories)
ELECTRIC CIRCUIT
MOB serial port RS485 with Modbus protocol CTERM Remote keypad for indoor temperature and humidity control CSOND Temperature and humidity ambient control with built-in probes (available only with options: CONTE) CTEM Temperature ambient control with built-in probe (available only with options: CONTE) EH09 4,5 kW electric heaters EH10 6 kW electric heaters EH12 9 kW electric heaters EH14 12 kW electric heaters EH17 18 kW electric heaters EH22 27 kW electric heaters EH24 36 kW electric heaters CWM Electronic room control with display, for wall installation
CONTE Electronic room control with display visible on the unit (available only with options: CSOND-CTEM)
CIWM Electronic room control with display, for wall installation in built-in box PM phase monitor PFCP power factor correction capacitors (cosfi > 0.9)
INSTALLATION
AMRX Rubber antivibration mounts (separately supplied accessories)
6
Page 7
2 - RECEPTION
2.1 PRELIMINARY INFORMATION General
Operate in compliance with safety regulations in force .
For detailed information (dimensions, weight, technical characteristics etc.) please refer to the “Technical information” section.
Use single protection devices : gloves, glasses ecc. Stocking
Observe external packing instructions . Handling
Verify unit weight and handling equipment lifting capacity .
Identify critical points during handling (disconnected routes, flights, steps, doors).
Verify the position of the barycentre in the Technical information - DIMENSIONS section.
Before handling verify that the unit keeps its balance. Packing removing
Be careful not to damage the unit.
Recycle and dispose of packing material in conformity with local regulations.
2.3 HANDLING
Considerer that the barycentre could out of centre
Use protection to avoid the unit damaging
2.2 DELIVERY CONTROL
Before accepting the delivery you have to check:
That the unit hasn’t been damaged during tran-
sport.
Check that the materials delivered correspond
with that indicated on the transport document comparing the data with the identification label ‘A’ positioned on the packaging.
In case of damage or anomaly:
Write down on the transport document the da-
mage you found and quote this sentence: "Conditional acceptance — clear evidence of deficiencies/damages during transport".
Contact supplier and the carrier by fax and regi-
stered mail with advice of receipt.
Any disputes must be made within the 8 days following the delivery. Complaints after this period are invalid.
7
Page 8
3 - POSITIONING
3.1 PRELIMINARY INFORMATION
Operate in compliance with safety regulations in force.
For detailed information (dimensions, weight, technical characteristics etc.) please refer to the TECHNICAL INFORMATION section.
Use single protection devices : gloves, glasses ecc.
During positioning consider these elements :
technical spaces required for the machine and system
place where the machine will be installed
electrical connections
water connections
air / aeraulic ducts
Do not considerer these elements could decrease performances and operational life of the unit.
3.2 FUNCTIONAL SPACES
Functional spaces are designed to:
guarantee good unit operation
Carry out maintenance operations
protect authorized operators and exposed people
Respect all functional spaces indicated in the TECHNICAL INFORMATION section.
Double all functional spaces if two or more unit are aligned.
3.3 POSITIONING
Units are designed to be installed:
INTERNAL
in fixed positions.
Limit vibration transmission:
use antivibration devices on unit bearing/supporting
points;
install flexible joints on the hydraulic.
Installation standards:
Safe accessible position;
avoid flood-prone places;
verify unit weight and bearing point capacity;
verify that all bearing points are aligned and leveled;
8
Page 9
4 - WATER CONNECTIONS
4.1 PRELIMINARY INFORMATION
Selection and installation of system components must be carry out by installer.
Following you will find some indications to integrate with what is provided by the local regulations in force and by the good technical laws.
4.2 COMPONENTS
CUT-OFF VALVES :
installed at inlet and outlet allow maintenance
operations without having to empty the system .
THERMOMETERS AND MANOMETERS :
installed at entry and exit of the main elements
facilitate inspection and maintenance.
AN AIR BLEED VALVE :
installed in all of the highest points of the system
allowing the venting of the circuits air.
DRAINAGE TAPS :
installed in the lowest points of the system to allow
bleeding.
EXPANSION TANK :
It keeps a correct system pressure when the water
temperature changes. It must be dimensioned as a function of water content. Could be necessary install in addition on the unit one or more of it
WATER FILTER :
.
must be installed immediately in the water input of
the unit, in a position that is easily accessible for cleaning.
The filter should never be re-moved, this operation
invalidates the guaranty .
filter features:
Size
Ø 1”
filtration mesh (micron)
SUPPORTS :
31-81 82-102 122-222
1"
¼
500μm 600μm 600μm
1" ½
The hydraulic pipes weight mustn’t burden on the
unit connections ..
FLOW SWITCH
The flow switch must be present as a component of
the system
4.3 OPERATION SEQUENCE
Before connecting the unit, carefully wash the system by filling it and emptying it several times with clean water.
In the units equipped with hydraulic pipeworks use the bypass.
Ignoring this operation will lead to several filter cleaning interventions and at worst cases can cause damages to the exchangers and the other parts.
Execute leakage test before isolate the pipes.
To avoid heat dispersions and formation of condensate isolate all the pipes.
Leave various point of service free (wells, vent-holes etc )
4.4 WATER QUALITY
The water quality is determined by the following factors, avoid therefore:
Inorganic salts
pH
Biological load (seaweeds etc)
Suspended solids
Dissolved oxygen
Water with inadequate characteristics can cause:
pressure drop increase
energy efficiency decrease
corrosive symptom increase
4.5 RISK OF FREEZE
If the unit or the relative water connections can be subject to temperatures close to 0°C adopt measures for prevent risk of freeze.
For example:
Mix water with ethylene glycol
Safeguard the pipes with heating cables placed
under the insulation
Empty the system in cases of long non-use and
check that:
there are no closed taps present that could trap
water even after emptying
there are no low points in which water can
stagnate even after emptying; carry out any blowing required .
4.6 ANTI-FREEZE SOLUTION
Consider that the use of anti-freeze solution determi­nes an increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not corrosive) and compatible with the hydraulic circuit components (pump etc).
9
Page 10
CONNECTION SOURCE SIDE
4.7 STANDARD UNIT
4 - WATER CONNECTIONS
4
3
The standard unit is equipped with the following components:
1. plate heat exchanger complete with water side differential pressure switch and a water temperature control probe
2. drain bibcock
3. bleed bibcock
3
T
PD
1
2
4.8 PLUMBING ASSEMBLY
FOR LOOP WITH CONSTANT
The plumbing assembly for the constant flow rate loop includes, in addition to 1, 2 and 3 standard components :
4 two-way manually activated valves to make it possible
to disconnect the unit from the plumbing system for maintenance.
5 manually activated three-way valve for loop wash by-
pass (to allow washing of the pipes of the system and protect the heat exchanger against fouling);
4
3
T
PD
1
2
5
4.10 PLUMBING ASSEMBLY FOR LOOP WITH DISPOSABLE WATER
The plumbing assembly for systems with disposable water (from well or groundwater) includes in addition to 1, 2 and 3 standard components :
1 2-way motorised modulating valve at the exchanger
outlet (the operation is linked to that of the refrigeration circuit:modulating the valve opening by 0­10V signal the water content is reduced and the unit operation values are maintained within the limits allowed)
2 manually activated three-way valve for loop wash by-
pass (to allow washing of the pipes of the system and protect the heat exchanger against fouling);
In summer operation, the device, complete with modulating valve, makes it possible to maximize the thermal differential of the water and hence to reduce the water flow rate. In winter operation, modulation of the water flow rate allows the unit to function with the water loop at high temperature. An additional advantage of using this device is the extension of the operating limits of the unit in summer and winter.
T
PD
1
2
5
4.9 PLUMBING ASSEMBLY FOR LOOP WITH VARIABLE
The plumbing assembly for the constant flow rate loop inclu­des, in addition to 1, 2 and 3 standard components :
4 two-way motorize ON/OFF valve, operation is linked
to that of the refrigeration circuit: with the compressor off the valve stays closed and as a result less water is used
5 manually activated three-way valve for loop wash by-
pass (to allow washing of the pipes of the system and protect the heat exchanger against fouling);
MAX. WORKING PRESSURE
Standard unit = 700 kPa
With ON/OFF valves = 700 kPa
With manual valves = 700 kPa
With modulating valve = 300 kPa
Aries effects and air bubbles can produce the overcoming and cause water drops.
10
Page 11
4 - WATER CONNECTIONS
4.11 CONDENSATE DISCHARGE
The condensate must be dispersed to avoid damages to persons and property .
Unit discharge fitting : the connection must avoid the
transmission of mechanical stresses and must be performed paying attention to avoid the damaging of the unit discharge fitting .
Make a trap that, eliminating the depression caused
by the fan, stops the return of gas from the discharge pipe
The ducting must have an appropriate slope to allow
the downflow
Anchor the ducting with an appropriate number of
supports. Otherwise are generated ducting failures and air pockets that prevent the downflow.
Insulate the ducting and the siphon to avoid
condensate drippings
Connect the condensate discharge to a rainwater
drain.
Do NOT use sewerage drains, so as to avoid the
return of odours if the water contained in the trap evaporates
Finally, check that the condensate will drain
correctly by pouring water into the tray stud
Calculation of the siphon height T = 2P S = T/2 P is the pressure determinate by the fan in correspondence of the drain pain (1mm c.a = 9.81 Pa)
4.12 HEATING COIL - OPTION
B
A
A drain cock
B air vent
Supplied by the customer :
1 vibration isolators
2 ducting supports
3 shutoff valves
1
23
P
H
T
S
Exsample :
P = 300 Pa = 30 mm T = 2P = 60 mm
S = T/2 = 30 mm
11
Page 12
5 - AERAULIC CONNECTIONS
5.1 GENERAL
Proper execution and sizing of air connections are essential for ensuring correct operation of the unit and an acceptable level of silence in the room.
When designing and creating ducts, consider PRESSURE DROPS, FLOW RATE and AIR SPEED which need to be compatible with the characteristics of the unit.
Special consideration needs to be made for pressure drops that are greater than the unit's static pressure, which would lead to a reduction in flow rate resulting in unit shutdown.
the weight of the ducts must not be supported by the
connection flanges
place anti-vibration joints between the ducts and the unit
the connection to the flanges and between the various
sections of the ducts must ensure an airtight seal, preven­ting leakage in delivery and return which would compromi­se overall system efficiency.
limit pressure drops by optimizing the path, the type and
number of curves and the branches
use curves with a wide radius. Consider whether it might
be useful to equip them with deflectors (especially if the air speed is high or if curves are tight )
For purposes of comfort, the following things need to be consi­dered:
air diffusers must be selected by checking the sound
power generated at nominal flow rate conditions
the disconnections to the diffusers are to be made
using flexible elements
the return grilles must be amply sized
APPLICATIONS AT HIGH DEGREE OF SILENCE
For applications that require a high degree of silence in the system:
In delivery and return, provide septum silencers, pre-
ferably inserted in sections of ducts located outside the building. The septums must ensure the required dampening with minimum pressure drops (ONLY OUTDOOR UNITS – do not print note).
Equip all curves with deflectors.
5.2 FEATURES FOR DUCTS FOR TREATED AIR
The inner surface of the duct must be smooth and washa-
ble. It must not contaminate the air.
Thermally insulate the ducts and the flanges so as to pre-
vent loss of energy and condensation build-up.
GRILLES OUTLETS DIFFUSERS
Proper distribution of air in the room is essential for ensuring comfort levels.
In the selection and positioning of grilles, outlets and diffusers, the following are to be avoided:
excessive air speed
formation of stagnant zones and layering
entry of cold air into the room
formation of localized currents (due to uneven air
distribution)
excessive variations in ambient temperature in the
vertical and horizontal planes
short circuiting of delivery air towards return air
12
Page 13
6 - ELECTRICAL CONNECTIONS
6.1 PRELIMINARY INFORMATION
The characteristics of the electrical lines must be determined by specialized personnel able to design electrical installations; moreover, the lines must be in conformity with regulations in force. The protection devices of the unit power line must be able to stop the presumed short circuit current, whose value must be determined in function of system features. The power cables and the protection cable section must be defined in accordance with the characteristics of the protections adopted. All electrical operations should be performed by trained personnel having the necessary requirements by the regulations in force and being informed about the risks relevant to these activities. Operate in compliance with safety regulations in force .
6.2 ELECTRICAL DATA
The serial number label reports the unit specific electrical data, included any electrical accessories .
The electrical data indicated in the technical bulletin and in the manual refer to the standard unit, accessories excluded.
Refer to the electrical data report on the serial number label.
6. Before power the unit, make sure that all the protections that were removed during the electrical connection work have been restored.
6.4 SIGNALS / DATA LINES
Do not overpass the maximum power allowed, which varies, according to the type of signal.
Lay the cables far from power cables or cables having a diffe­rent tension and that are able to emit electromagnetic distur­bances.
Do not lay the cable near devices which can generate electro­magnetic interferences.
Do not lay the cables parallel to other cables; cable crossings are possible, only if laid at 90°.
Connect the screen to the ground, only if there aren’t distur­bances
Guarantee the continuity of the screen during the entire exten­sion of the cable.
Respect impendency, capacity and attenuation indications.
6.5 ELECTRIC LINES INLET
serial number
label
F.L.A. full load ampere Full load current at max admissible conditions
F.L.I. Full load input Full load power input ( at max. admissible condition )
n° WIRING DIAGRAM
VOLTAGE
FLA (A)
FLI (kW)
6.3 CONNECTIONS
1. refer to the unit electrical diagram (the number of the diagram is shown on the serial number label)
2. verify that the network has characteristics conforming to the data shown on the serial number label
3. Before starting work, verify that the sectioning device at the start of the unit power line is open, blocked and equip­ped with cartel warning
4. Primarily you have to realize the earthing connection
5. Shelter the cables using adequate measure fairleads
Unit top view Unit front view
QS1 main isolator switch PE protection conductor
13
Page 14
6.6 ELECTRICAL PANEL
6 - ELECTRICAL CONNECTIONS
AP1 Master module AP2 XC Customer connection
QS1 Main isolator switch QM1 - QM2 Compressor magnetothermic switch KM1 - 2 Compressor contactor
Layout of the standard unit electrical panel. With special configurations the layout can be modified: refer to the layout indicated on the unit specific electrical panel.
Electronic thermostatic module
QM8 - QM9 KM8 - KM9 Heater contacotr QM6 Outlet fan motor overload switch
QM15
ST8 High temperature saftey thermostat T1
Electric heart thermal magnetic circuit breakers
Auxiliary circuit thermal magnetic circuit
breaker
Auxiliary circuit transformer
6.7 CONNECTIONS
SA1 remote on/off selector
SA5 remote winter/summer selector
ALC free contact from signalling system of fire alarm
ALM cumulative fault signal
KPC heating coil pump control
HLC1 compressor 1 status
HLC2 compressor 2 status
HLM indicating light of the supplì fan status
AP23 remote umidification group
14
Page 15
6 - ELECTRICAL CONNECTIONS
6.8 WALL AMBIENT THERMOSTAT
Install the room thermostat far from heat sources (radiators, sunbeam, kitchens), from doors , windows etc.
Provide 230 VAC power supply
1
2
3
OK
ASSEMBLY
1,5 m
separate the front from the rear of the terminal using a
screwdriver (Fig. 1);
disconnect the 4-pin connector from the front part (Fig. 2);
to remove cover A1, unscrew screw A2 and press the
point of attachment (Fig. 3); access terminal block A3 (Fig. 4)
drill the holes in the wall (dia. 5 mm); then insert the plugs
and screws supplied, making sure that the electrical wires pass through hole E (Fig. 5);
perform the electrical connections between thermostat
ambient and XC terminal block in the unit electric panel (Fig 6) Connect RT2 (provided with room thermostat)
close cover A1, completing the same operations as
descrive above in reverse;
plug the 4-pin connector back in (Fig. 8);
fi nally replace the terminal, starting with the bottom tabs
and applying a hinge movement. Make sure that the electrical wires are inside to ensure correct fastening (click on).
DISMANTLING Insert a screwdriver into the clot at the top (Fig. 1) and press
downwards to detach the display.
4
5
xc
F+
F-
6
GND
7
MAX 200mt
230 VAC
GND
Rx+ / Tx+
Rx- / Tx-
N 230V~
L 50/60Hz
= RT2 = 120
15
Page 16
6 - ELECTRICAL CONNECTIONS
For maintenance operations it is possible to remove the thermostat from its base, wall installed, and connect it to the base inside the unit electrical panel.
6.10 RS 485 WITH MODBUS PROTOCOL
J6
- + GND
UNIT 2
XC
UNIT 1
­+
GND
UNIT 3
­+
GND
6.11 SERIAL WITH LONWORKS PROTOCOL
J6
B A GND
- + GND
UNIT 2
XC
UNIT 1
­+
GND
UNIT 3
­+
GND
6.12 CHARACTERISTICS CABLE
Couple of conductors twisted and shielded
Section of conductor 0.22mm
Nominal capacity between conductors < 50 pF/m
nominal impedance 120
Recommended cable BELDEN 3105 A
2
…0,35mm
2
16
Page 17
7 - START-UP
Preliminary checks
Checks with machine in OFF, before start-up .
For details refer to the various chapters in the manual.
safe access
functional spaces
air flow: free return and supply (no bypass, no
stratification)
integrity of structure
fans turn freely
unit on anti-vibration devices
Unit input water filter + shut-off valves for cleaning
Start-up sequence
Machine start-up operations.
For details refer to the various chapters in the manual.
Powered unit
compressor carter heaters ON from at least 8 hours
phases sequence control
vacuum voltage measurement
unit ON
load voltage measurement and absorptions
fans operation check
Vibration isolators on water connections
Expansion tank (indicative volume = 5% system content)
Cleaned system
Loaded system + possibile glicole solution + corrosion
inhibitor
Under pressure system
Vented system
cooling circuit visual control
earth connection
unit powered by fixed network or by electrogen group
electric connections by customer
treated air flow rate measurement
supply, return and outdoor air temperature measurement
subcooling and overheating measurement
no anomalous vibrations check
static pressure relief in return
set date and time
set-point customisation
available machine documentation
17
Page 18
7 - START-UP
7.1 PRELIMINARY INFORMATION
The indicated operations should be done by qualified technician with specific training on the product.
Upon request, the service centres performing the start-up; the electrical, water connections and the other system works are by the installer.
Agree upon in advance the star-up data with the service centre.
7.2 PRELIMINARY CHECKS
Before checking, please verify the following :
the unit should be installed properly and in conformity with
this manual.
the electrical power supply line should be sectioned at the
beginning.
The line sectionalizing device is open, locked and equip-
ped with the suitable warning
make sure no tension is present
7.3 REFRIGERANT CIRCUIT
1. Check carefully the refrigerating circuit: the presence of oil stains can mean leakage caused by transportation, move­ments or other).
2. Verify that the refrigerating circuit is in pressure: Using the unit manometers , if present, or service manometers.
3. Make sure that all the service outlets are closed with pro­per caps; if caps are not present a leak of refrigerant can be possible.
7.5 ELECTRICAL CIRCUIT
Verify that the unit is connected to the ground plant
Check the conductors tightening: the vibrations caused by handling and transport might cause loosing
Feed the unit by closing the sectioning device, but leave it on OFF.
Check the tension and line frequency values which must be within the limits :
400/3/50 +/- 10% Control the unbalancing of the phases:
it must be lower than 2%
Example:
L1 L2 L3
388 V
379 V
377 V
388 + 379 + 377
1)
2)
3)
The working out of the limits can cause irreversible damages and voids the warranty.
3
388 (max)381 = 7
7
x 100 = 1,83 OK
381
381
=
7.4 HYDRAULIC CIRCUIT
1. Before realizing the unit connection make sure that the
hydraulic system has been cleaned up and the clearing water has been drained
2. Check that the water circuit has been filled and
pressurized
3. Check that the shut-off valves in the circuit are in the
"OPEN" position.
4. Check that there isn’t air in the circuit, if required,
evacuate it using the air bleed valve placed in the system high points.
5. When using antifreeze solutions, make sure the glycol
percentage is suitable for the type of use envisaged.
Weight of glycol (%)
Freezing temperature (°C)
Safety temperature (°C)
10 20 30 40
-4 -9 -15 -23
-2 -7 -13 -21
7.6 COMPRESSOR CRANKCASE RESISTANCES
Feed the oil resistances on the compressor crankcase at least 8 hours before the start compressor :
at the first unit start-up
after each prolonged periods of inactivity
1. Feed the resistances closing the unit isolator (sorter??).
2. Control the resistances electrical absorption to be sure that they’re function .
3. Carry out start-up only if the compressor crankcase temperature on the lower side must be higher at least of 10° C than the outside temperature.
Do not start the compressor with the crankcase oil below ope­rating temperature .
18
Page 19
7 - START-UP
7.7 TENSIONS
Check that the air and water temperatures are included in the working limits
For information on the control system, refer to the paragraph CONTROL.
Start the unit With unit of full load, namely in stable conditions and close to
those of work, check :
Power supply tension
Total absorption of the unit
Absorption of the single electric loads
7.8 REMOTE CONSENT
Check that the remote commands (ON-OFF, etc.) are con-
nected and if necessary enabled with the relevant parame­ters as described in ELECTRICAL CONNECTIONS sec­tion
Check that probes or optional components are connect
and enable with the relative parameters( ELECTRICAL CONNECTION section)
7.9 APPLICATIONS WITH TEXTILE DUCTING
It is possible to modify the fan start-up ramp to personalize it in case of applications with textile ducting.
Set the parameter P62 EnRampaEsp : 0 = disabile ramp 1 = slow ramp 10 = rapid ramp
It is also possible to set intermediate values.
7.12 STARTING REPORT
Realize the operating objective conditions is useful for check the unit over time.
With unit of full load, namely in stable conditions and close to those of work, take the following data:
Tension and general absorptions with unit at full load
Absorption of varied electrical loads (compressors, fans,
pumps etc)
Temperatures and capacities of different liquid (water, air)
in the inlet and outlet of the unit
Temperatures and pressures on the refrigerant circuit cha-
racteristic points (compressor discharge, liquid, intake)
The remarks should be preserved and available during
maintenance .
7.13 CE 97/23 PED DIRECTIVE
97/23 CE PED DIRECTIVE gives instructions for installers, users and maintenance technicians as well.
Refer to local actuation norms; briefly and as an example, see the following
Compulsory verification of the first installation :
only for units assembled on the installer’s building site (for ex. Condensing circuit + direct expansion unit)
Certification of setting in service :
for all the units
Periodical verifications:
to be executed with the frequency indicated by the
manufacturer (see the maintenance section)
7.10 AIR FLOW SETTING
The real unit flow is according to the aeraulic system features.
It is therefore necessary to check the air flow and in case to set the parameter:
P57 FanSpeedOut
Before checking, make sure that the system has been completed
In all its parts (shunts, dampers, grilles, diffusers etc.)
7.11 FIRE ALARM : CONFIGURATION
It is possible to set the unit operating in case of an alarm si­gnal from the fire signalling controller.
Par 151 TypeFireMode = complete unit shutdown
The unit cannot be used as smoke extractors.
19
Page 20
8 - CONTROL
SETPOINT
the display visualizes the ambient temperature
1. Press once ▲ or ▼ to display the setpoint ( it appears on the display
2. press ▲▼ to modify the working setpoint
3. Wait that the ambient temperature appears again on the display ( disappears
set
)
set
)
OK
+
+
ON / OFF
Press for 5 seconds
KEY FUNCTION
ON-OFF
MODE
CLOCK
OK
UP-DOWN
5 sec
5 sec
Press 5 seconds to access or switch off the unit.
Change the operating mode : summer, winter, automatic
Date and hour control
Confirm, display setpoint, display the outside temperature ( tE )
Shift in the menu, increase­decrease the value
Access to the password menu ( Code)
Access to the alarm menu ;
only if the icon is present
mode
°c
20.3
10:00
OK
Mon
DISPLAY MEANING
Operating mode : summer
Operating mode : winter
Operating mode : automatic
supply fan speed
alarm
Keyboard locked
Time band activated
Time band scheduling
Active compressor
Defrosting in progress
electric heaters , hot water coil - option
OFF
BUTTON LOCK / UNLOCK
Press together for 5 seconds
Symbol appears
mode
OFF
10:00
OK
Mon
MODE CHANGE
Press to set the operating mode:
mode
°c
22.5
10:00
OK
Mon
mode
°c
20.3
10:00
OK
Mon
Cooling
Heating AUTO Automatic
Operating in:
Cooling
mode
°c
20.3
10:00
OK
Mon
mode
°c
20.3
10:00
OK
Mon
20
Page 21
8 - CONTROL
8.1 OPERATING MODES
SUMMER :
With ambient temperature higher than the set, the unit cools;
With a temperature lower than the set, it is in stand-by (ambient fan On, compressor OFF) .
WINTER :
With ambient temperature lower than the set, the unit heats
With a temperature higher than the set, the unit is in stand-by (ambient fan ON, water coil compressor, electric heaters, humidifier in OFF)
8.2 CHANGE OF THE OPERATING MODE
AUTO The change of the SUMMER-WINTER mode is automatic. The unit is in :
SUMMER if the ambient temperature is higher than
the set
WINTER if the ambient temperature is lower than the
set .
The set changes automatically according to the outside temperature. The variation is defined by the climatic curve,
which can be personalized by the parameters.....
It is anyway possible to modify any time the working set by the buttons. MANUAL The operating mode (SUMMER-WINTER) is chosen by the MODE button. It possible to modify any time the working set by the ▲ ▼ buttons.
setECO is different.
The fan is started at time intervals defined by P19 TimeECO parameter, and remains active for a time defined by the P20 TimeTestECO parameter :
If the set is satisfied
the fan is stopped and will start again after the time defined by P19
If the set is not satisfied
the fan, the compressor and the other thermoregulation resources are activated.
Once the set is satisfied, the cycle is repeated :
Fan shutdown
After P19 TimeECO time fan ON
The fan remains on for P20 TimeTestECO time
Temperature check, etc.
8.4 -DAY MODIFICATION
Press the CLOCK button for 5 sec.
By the ▲ ▼ buttons, select the clock menu
Confirm with OK
The hour is flashing : set with the ▲ ▼ buttons
Confirm with OK
Repeat the procedure for the minutes and week’s day
To go back to the main screen, select the Esc menu
and confirm with OK
8.3 ECONOMIC SETPOINT
The ECO setpoint is optimized to reduce the Energy consumption :
in summer the ECO setpoint is higher than the
standard set
in winter it is lower.
To activate the setECO , modify the P04 parameter (instructions at the following page)
In ECO mode if the setECO is satisfied, the unit stops the ambient fan and the compressor.
When the setECO is active :
If the set is satisfied
the fan, the compressor and the other thermoregulation resources are stopped
If the set is not satisfied
the fan, the compressor and the other thermoregulation resources are activated.
If the thermoregulation is based on the return probe(option) instead on the ambient thermostat, the behaviour with active
21
Page 22
8.5 TIME BAND SCHEDULING
8 - CONTROL
It Is possible to set 4 types of scheduling:
7 days (from monday to sunday)
5 days (from monday to friday)
2 days (from saturday to sunday)
Day by day
Day scheduling
At home
Outside
Return to home
Night scheduling
At home
Outside the home
Return to the home
Day by day scheduling
Press for 5 seconds
Select Time bands
Press OK
Select the scheduling:
- Day by day
Press OK
Press OK
Set the hour
Press OK
Set the minutes
Press OK
Set the temperature
Press OK
mode
20.0
07:15
OK
Mon
Select the next time band
Press OK and repeat from
point 05
mode
----
--:--
OK
Mon
As all the programming is finished, select ESC
Press OK
mode
ESC
OK
Press OK to program the next day
mode
Time
band
OK
Select the next day
Press OK Repeat from point 04
mode
°c
20.3
10:00
OK
Mon
To exit from the scheduling select ESC
Press OK
Select Esc to exit
Press OK
mode
SEL
day
OK
Mon
ON / OFF SCHEDULING
Press for deactive or enable the
mode
----
--:--
OK
Mon
scheduling.
The deactived schedulino, the
mode
symbol doesn’t appear
OFF
07:00
OK
Mon
mode
mode
SEL
day
OK
Tue
mode
ESC
OK
mode
Time
band
OK
mode
°c
20.3
10:00
OK
Mon
mode
°c
20.3
10:00
OK
Mon
OFF
07:15
OK
Mon
22
Page 23
8 - CONTROL
8.6 ALARMS
Malfunctions are displayed with the ALARM icon.
Before resetting an alarm, identify and remove the cause that generated it.
Repeated reset may cause irreversible damages as a system malfunction.
To reset the alarm in progress :
1. Press the Mode + Clock button for 5 sec.
2. The alarm code is displayed
3. If more alarms are active at the same time, scroll the list
4. With buttons ▲ ▼ select the alarm reset menu
( resALM )
5. press OK
6. The main screen reappears without the alarm icon
The alarm can be signalled by the thermostat also by a buzzer.
To disable the buzzer, modify the P200 parameter.
LIST OF ALARMS
CODE Description
AE01 Alarm of faulty return temp. probe µPC A
AE02 Alarm of faulty supply temp. probe µPC A
AE03 Alarm of faulty outside temp. probe µPC A
AE04 Alarm of faulty coil probe temp. probe µPC A
AE05
AE06 Alarm of faulty condensing pressure probe µPC A
AE07
AE08 Alarm of faulty return temp. probe µPC A
AE09
AE10 Alarm of faulty air quality probe µPC A
AE11 Alarm of faulty ext. RH probe µPC A
AE12 Alarm of faulty return RH probe µPC A
AE13
AE14 Alarm of faulty ambient thermostat temp. probe A
Alarm of faulty differential pressure probe of the supply fan µPC
Alarm of faulty evaporating pressure probe µPC
Alarm of faulty antifreeze probe temp. probe of the additional coil µPC
Alarm of faulty diff. Detector of the fresh/ ambient air
A
A
A
A
AE15 Alarm of faulty ambient thermostat RH% A
AE20 pCOE communication alarm A
AE21 Alarm of the humidifier communication A
AE22 Alarm of ambient thermostat communication A
AE23
AE26 Compressor 1 overload alarm M
AE27 Compressor 2 overload alarm M
AE28 Phase monitor alarm M
AF01 HP alarm of the refrigerant circuit M
AF02 LP alarm of the refrigerant circuit A / M
AF03 HP1 high pressure prealarm A
AF04 LP1 low pressure prealarm A
AF05 HP2 high pressure prealarm A
AF06 LP2 low pressure prealarm A
AA01 Fire alarm M
AA02 Dirty filter warning A
AA03 Resistance high temperature alarm M
AI01 Source water flow-rate alarm A
AI02 Antifreeze alarm of the source exchanger M
AI10 Humidifier alarm group 1 A
AI11 Humidifier alarm group 2 A
Alarm of supply fan overload (cond. fan/pump) or compartment opening or supply flow alarm
Cn communication failure thermostat-main board
M
A = alarm at AUTOMATIC reset
M = alarm at MANUAL reset
A/M = alarm at AUTOMATIC reset, after 3 alarms in 1 hour, it
becomes at MANUAL reset
23
Page 24
8 - CONTROL
STORED ALARM (installer use only)
Press buttons for 5 sec
Enter password
Confirm with OK
Select S ALM
Confirm with OK
Scroll alarm list (AL1, AL2...) and dysplay alarm detail
1° alarm - 1°display
new alarm
AL1
XX
alarm code
mode
OK
mode
OK
mode
OK
mode
OK
20.3
10:00
Mon
000
CODE
SALM
21.0°
S001
AL1
21.0°
XX
S001
8.7 PARAMETERS
°c
c
c
The setting parameters are protected by password to avoid inadvertent changes that can affect the unit operating.
To access to the parameters
1. press On/Off + Fan button for 5 sec.
2. enter password : with the ▲ ▼ button set Code = 2
3. Confirm with OK
4. Select the PAr menu and confirm with OK
5. Scroll the list ▲ ▼
6. Select the parameter with OK
7. Modify the value ▲ ▼ and confirm with OK
8. To esc, scroll the lost, select ESC and confirm with OK
P02 Economic SetPoint in heat mode
P03 Economic SetPoint in cool mode
P04 Enable the set and the economical functions
P05 Enables the automatic setpoint
P06 Set CO2
P200
Enables buzzer in case of alarm : 0=disabled, 1=enabled
1° alarm - 2°display
alarm day 1
dA1
YY
day number after alarm
1° alarm - 3°display
alarm hour 1
HA1
hhmm
mode
dA1
c
OK
mode
HA1
hhmm
OK
21.0°
YY
S001
21.0°
S001
c
24
Page 25
8.8 STATA
8 - CONTROL
To access to the stata:
1. Press the On/Off + Fan button for 5 sec.
2. Enter the password: with ▲ ▼ buttons, set
Code = 1
3. Confirm with OK
4. The Sta menu appears, confirm with OK
5. Scroll the list of stata with ▲ ▼ buttons
6. To esc scroll the list, select ESC
and confirm
with OK
S01 ManSet °C
S02 SetUR %
S03
Request of total Vc capacity
S04
Capacity request to compressors
S05
Capacity delivered from free cooling/heating
S06
Capacity requested to the aux. element
S07
N. of active compressors
S08
Ext. damper opening
S09
Exhaust fan modulation
S10
Return air differential pressure
Additional element modulation
S11
(electric resistances / hot water coil)
S12
Operative return temperature
S13
Supply temperature
S14
Operative ambient RH%
S15
CO2 probe
S16
Fresh air temperature
S17
Fresh air RH%
S18
Temperature of the coil probe/source exchanger
S19
Temperature of the aux. element antifreeze probe
S20
Condensing pressure
S21
Evaporating pressure
S22
Condensing fan signal
S23
Return temperature
S24
Current overheating
S25
Thermostatic valve opening
S26
Supply air flow
S27
Signal of modulating supply fan
S28
Supply differential pressure
S29
Modulating humidifier signal
S30
Post heating request
S31
Functionning compressor 1 hours
S32
Functionning compressor 2 hours
S33
Compressor 1 starts
S34
Compressor 2 starts
S35
Software type
S36
Software version number
S37
Software release day
S38
Software release month
S39
Software release year
%
%
%
%
-
%
%
Pa
%
°C
°C
%
Ppm
°C
%
°C
°C
Bar
Bar
%
°C
°C
%
m3/
h*10
%
Pa
%
%
25
Page 26
9 - MAINTENANCE
9.1 GENERAL
Maintenance must be done by authorized centres or by
qualified personnel
The maintenance enables:
maintain the unit efficiency
Reduce the deterioration speed to whom every equipment
is subject over time
Assemble information and data to understand the state of
the unit efficiency and avoid possible damages
9.2 INSPECTIONS FREQUENCY
The inspections should be carried out at least:
Every year for only the cooling units
Every six months for the cooling and warming units
The frequency, however, depends on the use . in the event of frequent use it is recommended to plan inspec-
tions at close intervals :
frequent use (continuous or very intermittent use, near the
operating limits, etc)
critical use (service necessary) .
9.3 MACHINE BOOKLET
It’s advisable to create a machine booklet to take notes of the
unit interventions.
In this way will be easier marker the various interventions and
will be e facilitate any troubleshooting.
Report on the booklet :
data
type of intervention effected
intervention description
Carried out measures etc ..
9.4 PUT A REST
If a long period of inactivity is foreseen :
put the unit in OFF
wait for 1 minute, so that the water valves are in rest
position
Turn of the power in order to avoid electrical risks or
damages by lightning strike
avoid the risk of frosts (empty or add glycol in the plant
sections subjected to temperatures below zero , power antifreeze resistances if are present )
It’s recommended that the starter after the period of detention is made by a qualified technician, especially after seasonal stops or seasonal switch.
When restarting, refer to the START-UP section .
Schedule technical assistance in advance to avoid hitches and be able to use the installation when necessary.
9.5 STRUCTURE
Check the condition of the parts making up the structure. Paint so as to eliminate or reduce oxidation at the points in the unit where this problem may occur.
Check that the paneling is fastened correctly. Poor fastening may give rise to malfunctions and abnormal noise and vibration .
9.6 PLEATED FILTERS
It is very important for the air treatment coil to be able to offer maximum thermal exchange. Therefore, the unit must always operate with the filters installed and clean.
Cleaning and replacement of filters are very important in terms of health and hygiene.
Operation with clogged filters leads to a reduction in the air flow rate, resulting in malfunctions and unit shutdowns. It may even cause the unit to break down.
How often the filters need to be checked depends on the quality of outdoor air, unit operating hours, dust and number of persons in the rooms.
As a guideline, cleaning should ideally take place between WEEKLY and MONTHLY. It is advisable to start with frequent checks, and to adjust the frequency based on how much dirt is discovered .
Remove the closing doors
Carefully extract the filter so that no dust reaches the
parts below
Wash the filtering mattress in warm water with a
common detergent.
Carefully rinse it under water while preventing to pour
water in the room
Dry the filter
Reinsert it to its seat
Reassemble the closing doors
Old filters, washing residuals and residual parts must be disposed of, according to the law in force .
26
Page 27
9 - MAINTENANCE
9.7 INTERNAL AIR COIL
Accidental contact with the fins of the exchanger may cause
small cuts. When performing the following steps, use
protective gloves.
The finned surfaces of the cooling coils and especially the
condensation collection trays are the places where micro-
organisms and moulds most easily flourish. It is therefore
very important to clean regularly with suitable detergents and
disinfect with appropriate products as necessary.
9.8 CONDENSATE DISCHARGE
Dust and deposits could cause obstructions .
In the tank can also proliferate microorganisms and mold.
Very important to provide for a periodic cleaning with
appropriate detergents and in case to a disinfection with
sanitizing products.
Clean the tank, pour some water into the tank and check
water flows normally.
9.9 DUCTING
Check the fixing screws and the operation of the anti-vibration
devices in order to prevent the transmission of vibrations in
the room .
9.13 WATER FILTER
Verify that there are no impurities which hinder the smooth
passage of water.
9.14 TENSIONS
After switching off the power, wait at least 5 minutes before
accessing to the electrical panel or any other electrical
component. Check with a multimeter that there are no residual tensions
9.15 OIL COMPRESSOR ELECTRIC HEATERS
Regularly check the fixing status .
9.10 ELECTRICAL HEATING ELEMENTS
Regularly check the cleaning and the fixing status .
9.11 ELECTRIC FANS
Check :
the fans and the relative protection gridsare well fixed
The fan bearings (evident by noise and anomalous
vibrations )
the terminal protection covers are closed and the cable
holders are properly positioned
9.12 WATER EXCHANGER
It is very important for the exchanger to be able to provide the
maximum thermal exchange. Therefore, it is essential for the
inner surfaces to be clean of dirt and incrustations.
Periodically check the difference between the temperature of
the supply water and the condensation temperature. If the
difference is greater than 8 °C – 10 ° C it is advisable to clean
the exchanger.
The clearing must be effected :
With circulation opposite to the usual one
With a speed at least 1,5 times higher than the nominal one
With an appropriate product moderately acid (95% water +
5% phosphoric acid
After the cleaning rince with water to inhibe the detergent
rests.
27
Page 28
9 - MAINTENANCE
9.16 CONTROL BOARD
Controls effected on ……………………………..By …………………………………. Of the Company………..……………………………….
STRUCTURE
1. Presence of corrosions
2. Panel fixing
3. Fan fixing
4. Coil cleaning
CONDENSATE DISCHARGE
1. Drain pain cleaning + sanification
2. down flow test
AERAULIC CIRCUIT
1. Air filter cleaning
2. Air flow test
3. Ducting : test of fixing and vibration isolators
WATER CIRCUIT
1. Water filter cleaning
2. Check the exchanger efficiency
3. Circulating pumps, valve, pressure and flow switches
ELECTRICAL CIRCUIT
1. Check of the fixing and the insulation of the power lead
2. Electric panel cleaning
3. Capacity contactor status, terminal closing, cable insulation integrity
4. Voltage and phase unbalancing (no load and on-load)
5. Absorptions of the single electrical loads
6. Test of the compressor carter resistances
REFRIGERANT CIRCUIT
1. Leak check ( tapping connections, fittings, saftey valves, etc…)
2. Survey of the refrigerant circuit operating parameters (see TECHNICAL INFORMATION section)
CONTROL & CONTROL
1. Protective device test : safety valves, pressure switches, thermostats, flow switches etc
2. Control system test: setpoint, climatic compensations, capacity stepping, water / air flow-rate variations etc
3. Control device test : alarm signalling, thermometers, probes, pressure gauges etc
OPTIONAL COMPONENTS
1. Check of the electrical resistances
2. Check of the water coil
Notes / interventions recommended to the owner
*European regulation 303/2008
Refer to the local actuation regulations; in short and just as an indication the regulation order as follow.
Companies and technicians that effect interventions of installation, maintenance/repairs, leak control and recovery must be CERTIFIED as expected by
the local regulations.
The leak control must be effected with annual renewal.
28
Page 29
9 - MAINTENANCE
9.17 MALFUNCTIONINGS
No power supply
NUL AIR FLOW
unit in alarm
HP alarm (in summer)
INSUFFICIENT AIR FLOW Dirty filters Clean the filters
Check the alarm code Contact the authorized service centre
Dirty exchanger
Water temperature out of operating limits
WATER DRAGGING
NOISINESS
THE AMBIENT DOESN’T REACH THE DESIRED TEMPERATURE
siphon or clogged tray discharge Clean the siphon / tray
No siphon / not well produced See WATER CONNECTIONS section
Ducting or loosened panels Check closings
Fan bearings Replace fans
Wrong compressor phase sequence See START-UP section
To much flow Calibrate the flow
Dirty exchanger
Clean the exchanger see previous pages
29
Page 30
10 - DECOMMISSIONING
10.1 DISCONNECTING
Only authorised personnel must disconnect the unit.
Avoid leak or spills into the environment .
Before disconnecting the unit, the following must be
recovered, if present:
- refrigerant gas
- Anti-freeze solutions in the hydraulic circuit
Awaiting dismantling and disposal, the unit can also be
stored outdoors, as bad weather and rapid changes in
temperature will not cause damage to the environment, if
electric, cooling and hydraulic circuits of the unit are
integral and closed.
10.2 DISMANTLING AND DISPOSAL
THE UNIT MUST ALWAYS BE SENT TO AUTHORISED CENTRES FOR DISMANTLING AND DISPOSAL.
When dismantling the unit, the fan, the motor and the coil, if operating, may be recovered by the specialist centres for reuse.
All the materials must be recovered or disposed of in compliance with the corresponding national standards in force.
For further information on the decommissioning of the unit, contact the manufacturer.
cycle as urban waste. It must instead be handed over to
appropriate collection centres as set forth by current
standards or as instructed by the distributor.
If disposal takes places at the same time as delivery of a
new electrical or electronic equipment for the same
family, the product may be collected directly by the
distributor.
10.3 CE RAEE CE DIRECTIVE
The units covered by the legislation in question are
marked with the symbol on the side.
With the aim of protecting the environment, all of our
units are produced in compliance with Directive EC on
waste electrical and electronic equipment (WEEE).
The potential effects on the environment and on human
health due to the presence of hazardous substances are
shown in the use and maintenance manual in the section
on residual risks.
Information in addition to that indicated below, if
required, can be obtained from the manufacturer/
distributor/importer, who are responsible for the
collection/handling of waste originating from equipment
covered by EC - WEEE. This information is also
available from the retailer who sold this appliance or
from the local authorities who handle waste.
Directive EC - WEEE requires disposal and recycling of
electrical and electronic equipment as described therein
to be handled through appropriate collection, in suitable
centres, separate from collection for the disposal of
mixed urban waste.
The user must not dispose of the unit at the end of its life
30
Page 31
11.1 DIMENSIONS 31 - 51
11 - TECHNICAL INFORMATION
1. COMPRESSOR
2. ELECTRICAL PANEL
3. ACCESS TO THE ELECTRICAL PANEL
4. SUPPLY FAN
5. DIRECT EXPANSION COIL
6. PLATE EXCHANGER
7. G4 AIR FILTERS
8. WATER COIL (OPTIONAL) OR ELECTRIC HEATERS (OPTIONAL)
9. POWER INPUT
10. WATER LINE OUTPUT OF THE HEATING COIL Ø1" GAS
11. WATER LINE INPUT OF THE HEATING COIL Ø1" GAS
12. PLATE EXCHANGER WATER OUTPUT Ø 1”
13. PATE EXCHANGER WATER INLET Ø 1”
SIZE 31
Weigt kg 178
41
179
188
14. CONDENSATE DISCHARGE
15. ONAL CLEARANCES
16. WATER CONNECTION SIDE
17. FRONT OUTLET PLENUM (OPTIONAL)
(R ) AMBIENT AIR INTAKE STANDARD (M ) AIR SUPPLY STANDARD (MP ) REAR AIR OUTLET (OPTIONAL) (MF) FRONT AIR OUTLET (OPTIONAL) (RP ) REAR AIR INLET (OPTIONAL)
51
31
Page 32
11.2 DIMENSIONS 61 - 81
11 - TECHNICAL INFORMATION
1. COMPRESSOR
2. ELECTRICAL PANEL
3. ACCESS TO THE ELECTRICAL PANEL
4. SUPPLY FAN
5. DIRECT EXPANSION COIL
6. PLATE EXCHANGER
7. G4 AIR FILTERS
8. WATER COIL (OPTIONAL) OR ELECTRIC HEATERS (OPTIONAL)
9. POWER INPUT
10. WATER LINE OUTPUT OF THE HEATING COIL Ø1" GAS
11. WATER LINE INPUT OF THE HEATING COIL Ø1" GAS
12. PLATE EXCHANGER WATER OUTPUT Ø 1”
13. PATE EXCHANGER WATER INLET Ø 1”
SIZE 61 71 81
Weigt kg 207 208 210
14. CONDENSATE DISCHARGE
15. ONAL CLEARANCES
16. WATER CONNECTION SIDE
17. FRONT OUTLET PLENUM (OPTIONAL)
(R ) AMBIENT AIR INTAKE STANDARD (M ) AIR SUPPLY STANDARD (MP ) REAR AIR OUTLET (OPTIONAL) (MF) FRONT AIR OUTLET (OPTIONAL) (RP ) REAR AIR INLET (OPTIONAL)
32
Page 33
11.3 DIMENSIONSI 82 - 102
500
11 - TECHNICAL INFORMATION
19
11
44
Mp
M
Mf
1980
6
18
54 942
1050
Rp
860
Mp
742
1050
400 **
780
400 **
1000**
95
138
504
138
154 154
SIZE 82
Weigt kg 310
102 315
95
3
1
54
400 **
17
11
340
4
10
2
8
5
7
R
12
Rp
282
13
106
9
54
(1) COMPRESSOR (2) ELECTRICAL PANEL (3) ACCESS TO THE ELECTRICAL PANEL (4) SUPPLY FAN (5) DIRECT EXPANSION COIL (6) PLATE EXCHANGER (7) G4 AIR FILTERS (8) WATER COIL (OPTIONAL) - RE-HEATING COIL (OPTIONAL) (9) 3 WAYS-VALVE (OPTIONAL) (10) ELECTRIC HEATERS (OPTIONAL) (11) POWER INPUT (12) HOT WATER HEAT EXCHANGER WATER OUTLET Ø 3 / 4 " (13) HOT WATER HEAT EXCHANGER WATER INLET Ø 3 / 4 " (14) EXCHANGER WATER OUTLET Ø1" 1/2 GAS (15) EXCHANGER WATER INLET Ø1" 1/2 GAS (16) CONDENSATE DISCHARGE (17) FUNCTIONAL CLEARANCES (18) WATER CONNECTION SIDE (19) FRONT OUTLET PLENUM (OPTIONAL) (R ) AMBIENT AIR INTAKE STANDARD (M ) AIR SUPPLY STANDARD (MP ) REAR AIR OUTLET (OPTIONAL) (MF) FRONT AIR OUTLET (OPTIONAL) (RP ) REAR AIR INLET (OPTIONAL) (RI ) FLOOR AIR INLET (OPTIONAL) (**) CLEARANCE ACCESS RECOMMENDED
Ri
16
238
14
15
6
33
Page 34
11.4 DIMENSIONS 122 - 162
11 - TECHNICAL INFORMATION
19
500
11
44
Mp
340
M
Mf
4
10
2
3
1980
6
18
54
1342
1450
54
8
5
7
R
12
Rp
282
13
10 6
9
Ri
16
238
54
14
15
6
Rp
1260
1142
1450
95
Mp
162 410
400 ** 400 **
95
138
780
504
138
15 4 154
400 * *
1000**
SIZE 122
Weight kg 400
(1) COMPRESSOR (2) ELECTRICAL PANEL (3) ACCESS TO THE ELECTRICAL PANEL (4) SUPPLY FAN
17
11
(5) DIRECT EXPANSION COIL (6) PLATE EXCHANGER (7) G4 AIR FILTERS (8) WATER COIL (OPTIONAL) - RE-HEATING COIL (OPTIONAL) (9) 3 WAYS-VALVE (OPTIONAL) (10) ELECTRIC HEATERS (OPTIONAL) (11) POWER INPUT (12) HOT WATER HEAT EXCHANGER WATER OUTLET Ø 3 / 4 " (13) HOT WATER HEAT EXCHANGER WATER INLET Ø 3 / 4 " (14) EXCHANGER WATER OUTLET Ø1" 1/2 GAS (15) EXCHANGER WATER INLET Ø1" 1/2 GAS (16) CONDENSATE DISCHARGE (17) FUNCTIONAL CLEARANCES (18) WATER CONNECTION SIDE (19) FRONT OUTLET PLENUM (OPTIONAL) (R ) AMBIENT AIR INTAKE STANDARD (M ) AIR SUPPLY STANDARD (MP ) REAR AIR OUTLET (OPTIONAL) (MF) FRONT AIR OUTLET (OPTIONAL) (RP ) REAR AIR INLET (OPTIONAL) (RI ) FLOOR AIR INLET (OPTIONAL) (**) CLEARANCE ACCESS RECOMMENDED
34
Page 35
11.5 DIMENSIONS 182 - 222
11 - TECHNICAL INFORMATION
500
1980
19
11
44
Mp
340
3
10
M
8
Mf
4
2
5
7
1
12
R
6
18
54
95 1660
138
Rp
1742
Mp
Rp
282
13
54
95
106
Ri
9
54
16
238
17
400 **
14
15
780
504
138
15 4
400 **
1000**
SIZE 182
Weight kg 490
15 42
1850
222 500
15 4
11
(1) COMPRESSOR (2) ELECTRICAL PANEL (3) ACCESS TO THE ELECTRICAL PANEL (4) SUPPLY FAN (5) DIRECT EXPANSION COIL (6) PLATE EXCHANGER (7) G4 AIR FILTERS (8) WATER COIL (OPTIONAL) - RE-HEATING COIL (OPTIONAL) (9) 3 WAYS-VALVE (OPTIONAL) (10) ELECTRIC HEATERS (OPTIONAL) (11) POWER INPUT (12) HOT WATER HEAT EXCHANGER WATER OUTLET Ø 3 / 4 " (13) HOT WATER HEAT EXCHANGER WATER INLET Ø 3 / 4 " (14) EXCHANGER WATER OUTLET Ø1" 1/2 GAS (15) EXCHANGER WATER INLET Ø1" 1/2 GAS (16) CONDENSATE DISCHARGE (17) FUNCTIONAL CLEARANCES (18) WATER CONNECTION SIDE (19) FRONT OUTLET PLENUM (OPTIONAL) (R ) AMBIENT AIR INTAKE STANDARD (M ) AIR SUPPLY STANDARD (MP ) REAR AIR OUTLET (OPTIONAL) (MF) FRONT AIR OUTLET (OPTIONAL) (RP ) REAR AIR INLET (OPTIONAL) (RI ) FLOOR AIR INLET (OPTIONAL) (**) CLEARANCE ACCESS RECOMMENDED
35
Page 36
11 - TECHNICAL INFORMATION
11.6 GENERAL TECHNICAL SPECIFICATIONS
36
Page 37
11.7 SOUND LEVELS
11 - TECHNICAL INFORMATION
The sound levels are referred to units working at full load in nominal conditions. The sound pressure level is referred at a distance of 1 m. from the ducted unit surface working in free field conditions.
External static pressure 50 Pa.
Measurements are made in compliance with UNI EN ISO 9614-2.
Please note that when the unit is installed in conditions different from nominal test conditions (e.g. near walls or obstacles in general), the sound levels may undergo substantial variations.
11.8 OPERATING LIMITS - COOLING
30
°C
25
20
(2)
15
(1)
Ta W.B. [°C]
10
5
10 15 20 25 30 35 40 45 50
T H2O [°C]
WET TEMPERATURE - EXAMPLE
24°C D.B. / 63% R.H.
19° C W. B.
26°C D.B. / 52% R.H.
27°C D.B. / 4 8% R .H.
°C
the limits are indicative and have been calculated considering:
- values general and not specifications,
- standard air flow-rate,
- non-critical positioning and correct use of the unit,
- operation at full load
- difference between inlet / outlet water temperature = 5°C
Ta = air temperature entering the air handling coil (°C)
CAUTION! temperature measured with wet bulb
(W.B.=WET BULB)
TH2O = Water temperature at plate exchanger input (°C)
1 = Standard operating range
2 = field of use for unit equipped with plumbing
assembly for waste water system (Optional)
37
Page 38
12 - RESIDUAL RISKS
12.1 General
In this section the most common situations are signalled. As these cannot be controlled by the manufacturer these could be a source of risk situations for people or things
12.2 Danger zone
This is an area in which only an authorised operator may work.
The danger zone is the area inside the unit which is accessible only with the deliberate removal of protections or parts thereof
12.3 Handling
The handling operations, if implemented without all of the protection necesssary and without due caution, may cause the fall or the tipping of the unit with the consequent damage, even serious, to persons, things or the unit itself.
Handle the unit following the instructions provided in the present manual regarding the packaging and in compliance with the local regulations in force.
Should the gas refrigerant leak please refer to the refrigerant "Safety sheet".
12.4 Installation
An incorrect installation of the unit could cause water leaks, condensate accumulation, leaking of the refrigerant, electric shock, bad functioning or damage to the unit itself.
Check that the installation has been implemented by qualified technical personnel only and that the instructions contained in the present manual and the local regulations in force have been adhered to.
The installation of the unit in a place where even infrequent leaks of inflammable gas and the accumulation of this gas in the area surrounding the area occur could cause explosions or fires.
Carefully check the positioning of the unit.
The installation of the unit in a place unsuited to support its weight and/or guarantee adequate anchorage may cause the fall or the tipping of the unit with the consequent damage to things, people or the unit itself.
Carefully check the positioning and the anchoring of the unit.
Easy access to the unit by children, unauthorised persons or animals may be the source of accidents, some serious.
Install the unit in areas which are only accessible to authorised person and/or provide protection against intrusion into the danger zone .
12.5 General risks
Smell of burning, smoke or other signals of serious anomalies may indicate a situation which could cause damage to people, things or the unit itself. Electrically isolate the unit (yellow-red isolator).
Contact the authorised service centre to identify and resolve the problem at the source of the anomaly.
Accidental contact with exchange batteries, compressors, air delivery tubes or other components may cause injuries and/or burns.
Always wear suitable clothing including protective gloves to work inside the danger zone.
Maintenance and repair operations carried out by non-qualified personnel may cause damge to persons, things or the unit itself.
Always contact the qualified assistance centre.
Failing to close the unit panels or failure to check the correct tightening of all of the panelling fixing screws may cause damage to persons, things or the unit itself.
Periodically check that all of the panels are correctly closed and fixed.
If there is a fire the temperature of the refrigerant could reach values that increase the pressure to beyond the safety valve with the consequent possible projection of the refrigerant itself or explosion of the circuit parts that remain isolated by the closure of the tap.
Do not remain in the vicinity of the safety valve and never leave the refrigerating system taps closed.
12.6 Electric parts
An incomplete attachment line to the electric network or with incorrectly sized cables and/or unsuitable protective devices can cause electric shocks, intoxication, damage to the unit or fires.
Carry out all of the work on the electric system referring to the electric layout and the present manual ensuring the use of a system thereto dedicated.
An incorrect fixing of the electric components cover may favour the entry of dust, water etc inside and may consequently can electric shocks, damage to the unit or fires.
Always fix the unit cover properly.
When the metallic mass of the unit is under voltage and is not correctly connected to the earthing system it may be as source of electric shock and electrocution.
Always pay particular attention to the implementation of the earthing system connections.
Contact with parts under voltage accessible inside the unit after the removal of the guards can cause electric shocks, burns and electrocution.
Open and padlock the general isolator prior to removing the guards and signal work in progress with the appropriate shield.
Contact with parts that could be under voltage due to the start up of the unit may cause electric shocks, burns and electrocution.
When voltage is necessary for the circuit open the isolator on the attachment line of the unit itself, padlock it and display the appropriate warning shield.
12.7 Moving parts
Contact with the transmissions or with the fan aspiration can cause injuries.
Prior to entering the inside of the unit open the isolater situated on the connection line of the unit itself, padlock and display the suitable sign.
Contact with the fans can cause incurie.
Prior to removing the protective grill or the fans, open the
38
Page 39
12 - RESIDUAL RISKS
isolator on the attachment line of the unit itself, padlock it and display the appropriate warning sign.
12.8 Refrigerant
The intervention of the safety valve and the consequent expulsion of the gas refrigerant may cause injuries and intoxication. Always wear suitable clothing including protective gloves and eyeglasses for operations inside the danger zone.
Should the gas refrigerant leak please refer to the refrigerant "Safety sheet".
Contact between open flames or heat sources with the refrigerant or the heating of the gas circuit under pressure (e.g. during welding operations) may cause explosions or fires.
Do not place any heat source inside the danger zone.
The maintenance or repair interventions which include welding must be carried out with the system off.
12.9 Hydraulic parts
Defects in tubing, the attachments or the cut-off parts may cause a leak or water projection with the consequent damages to peopl, things or shortcircuit the unit.
39
Page 40
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy Tel. + 39 0439 3131 - Fax + 39 0439 313300 - info@clivet.it
CLIVET UK LTD 4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - info@clivet-uk.co.uk
CLIVET AIRCON LTD (Service and Maintenance Division) Units F5&F6 Railway Triangle Ind Est, Walton Road - Portsmouth, Hampshire - PO6 1TG - United Kingdom Tel. + 44 (0) 2392 381235 - Fax + 44 (0) 2392 381243 - info@clivetaircon.co.uk
CLIVET ESPAÑA COMERCIAL S.L. (Sales)
Calle Gurb, 17 1° 1
a
- 08500 Vic, Barcelona - España
Tel. + 34 93 8606248 - Fax + 34 93 8855392 - info@clivetcomercial.com
CLIVET ESPAÑA S.A.U.(Service and Maintenance Division)
Calle Real de Burgos N° 12 - 28860, Paracuellos del Jarama, Madrid - España Tel. + 34 91 6658280 - Fax + 34 91 6657806 - info@clivet.es
CLIVET GmbH
Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - info.de@clivet.com
CLIVET NEDERLAND B.V.
Siliciumweg 20a, 3812 SX Amersfoort - Netherlands Tel. + 31 (0) 33 7503420 - Fax + 31 (0) 33 7503424 - info@clivet.nl
CLIVET RUSSIA
Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia Tel. + 74956462009 - Fax + 74956462009 - info.ru@clivet.com
CLIVET MIDEAST FZCO
Dubai Silicon Oasis (DSO), High Bay Complex, Ind Unit No. 3, PO BOX 28178 - Dubai, UAE Tel. + 9714 3208499 - Fax + 9714 3208216 - info@clivet.ae
CLIVET AIRCONDITIONING SYSTEMS PRIVATE LIMITED 4BA, Gundecha Onclave - Kherani Road, Saki Naka, Andheri (East) - Mumbai 400 072 - India Tel. + 91 22 6193 7000 - Fax + 91 22 6193 7001 - info.in@clivet.com
Riproduzione anche parziale VIETATA © Copyright - CLIVET S.p.A. - Feltre (BL) - Italia
I dati contenuti nel presente manuale non sono impegnativi e possono venire cambiati dal costruttore senza obbligo di preavviso.
www.clivet.com
Loading...