CLIMIA CTK 240 Operating Manual

Page 1
CLIMIA
CTK 240 mobile air dehumidier
Operating manual
Edition 1.0 English
Page 2
Page 3
CTK 240 mobile air dehumidier
Contents
Carefully read this operating manual prior to commissioning/using the units! This operating manual is a translation of the German original.
This manual is an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modications; no liability accepted for errors or misprints!
1.0 Safety instructions 4
2.0 Environmental protection and recycling 4
3.0 Guarantee 4
4.0 Intended use 4
5.0 Transport and packaging 5
6.0 Air dehumidication 5-7
7.0 Unit description 8
8.0 Set-up 9
9.0 Commissioning 9-12
10.0 Shutdown 12
11.0 Unit transport 12
12.0 Care and maintenance 13-14
13.0 Troubleshooting and customer service 14
14.0 Electrical wiring 15
15.0 Electrical wiring diagram 15
16.0 General view of unit 16
17.0 Spare parts list 17
18.0 Technical data 18
19.0 Maintenance log 19
EC Declaration of Conformity 20
Page 4
CLIMIA
1.0 Safety instructions
Carefully read the operating manual before commissioning the unit for the first time. It contains useful tips and notes, as well as hazard warnings to prevent injury or material damage . Failure to follow the instructions in this manual can endanger people, the environment and the equipment itself and will void any claims for liability.
This unit can be used by children above the age of 8, as well as by people with impaired physical, sensory or mental capabilities or a lack of experience and knowledge if they are supervised or have received instruction in the safe operation of the unit, and if they understand the associated potential hazards. Children must never play with the unit. Cleaning and user maintenance must not be carried out by unsupervised children.
Keep this operating manual and the refrigerant data sheet near to the units.
The following notes must be observed in full:
• The units must not be operated
at an ambient temperature below 5 °C.
• The units may not be set
up or operated in explosive environments.
• The units must not be installed
or operated in atmospheres containing oil, sulphur, chlorine, salt or dust.
• Never insert foreign objects into
the units.
• The units may not be exposed to
direct jets of water.
• An unobstructed air inlet and air
outlet must be guaranteed at all times.
• The air-inlet grille must always
be kept free of dirt and loose objects.
• The units must not be covered
during operation.
•
The units must be installed upright and in a stable position.
•
The units must not be transported while they are running.
•
The units may only be transported upright (water will escape otherwise).
•
Before each change of location, the condensate container must be emptied
•
All electrical cables on the outside of the units must be protected against damage (e.g. by animals etc.)
.
•
Before each change of location, the condensate containers must be emptied
.
• Appropriate hazard prevention
measures must be taken to prevent risks to people when performing installation, repair, maintenance or cleaning work on the units.
• The units and components
should not be exposed to any mechanical load, extreme levels of humidity or direct exposure to sunlight.
3.0 Guarantee
As a prerequisite for any warranty claims to be considered, it is essential that the ordering party or its representative completes and returns the "certificate of guarantee" to Climia Intakt GmbH at the time when the units are purchased and commissioned. The guarantee conditions are listed in the "General terms and conditions of business and supply". Furthermore, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
Disposing of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
Disposing of the units and their components
Only recyclable materials are used in the manufacture of the units and components. Help protect the environment by ensuring that the units or components (for example batteries) are not disposed of in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g.using authorised disposal and recycling specialists or council collection points.
2.0 Environmental protection and recycling
Page 5
CTK 240 mobile air dehumidier
The units are shipped in sturdy transport packaging. Immediately check the unit on delivery and make a note of any damage (please take photos of the damage) or missing parts on the delivery note. Inform the forwarding agent and your contractual partner. Please retain the packaging for returns. Claims under guarantee made at a later date will not be accepted.
5.0 Transport and packaging
4.0 Intended use
The units are designed exclusively for drying and dehumidication purposes on the basis of their structural design and equipment. The units must not be used for any other purpose.
The units are only permitted to be operated by people with the relevant training and understanding of how to handle them.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no liability for damages arising from non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
It is evident that the corrosion rate below 50% relative humidity (RH) is low, and below 40% is negligible.
The corrosion rate increases signicantly above 60% RH. Thisthreshold for damage as the result of humidity also applies to other materials, such as powdery substances, packaging, wood and electronic units.
Buildings may be dried in a variety of ways:
1. By heating and air exchange:
The air in the room is heated in
order for moisture to be removed and then this air is fed outside. All of the energy that is involved is lost together with the moist air that is released.
2. By air dehumidication:
The moist air that is present
within an enclosed space is continuously dehumidied according to the condensation principle.
The correlations occurring when air is dehumidied are based on physical laws. These are depicted here in graphical form in order to provide you with abrief overview of the principles of air dehumidication.
Using Climia air dehumidiers
•
Even if windows and doors
are well insulated, water and moisture are still capable of penetrating thick concrete walls.
•
The water required for setting
in the production of concrete, mortar and plaster etc. may only be diused after 1-2 months.
•
Even moisture trapped in the
masonry after high-water or a ood is released very slowly.
•
The same is also true of moisture
contained in stored materials for example.
The moisture (water vapour) released from parts of a building or materials is absorbed by the surrounding air. As a result, the moisture content increases, which ultimately gives rise to corrosion, mould, rot, peeling of paint and other unwanted damage.
By way of example, the diagram shows the corrosion rate of metal in dierent levels of humidity.
6.0 Air dehumidication
Page 6
CLIMIA
With regard to energy consumption, air dehumidication has one distinct advantage:
Energy expenditure is limited exclusively to the air volumes present. The mechanical heat that is released by the dehumidication process is fed back into the room.
Under normal use, the
air
dehumidier
uses approximately 25% of the energy that is required for the
"heating and ventilating"
principle.
Relative air humidity
Our ambient air is a gaseous mixture which always contains acertain volume of water in the form of water vapour. This volume of water is specied in g per kg of dry air (absolute moisture content).
1m3 of air weighs approx. 1.2 kg at20°C
Depending on the temperature, each kg of air is only capable of absorbing a certain volume of water vapour. Once this capacity has been reached, the air is referred to as “saturated” and has a relative humidity (RH) of 100%.
Relative humidity is understood to mean the ratio between the current quantity of water vapour in the air and the maximum possible quantity of water vapour at the same temperature.
The ability of the air to absorb water vapour increases as the temperature rises. I.e. the maximum possible (absolute) water content becomes greater as the temperature rises.
Building materials and structures are capable of absorbing considerable volumes of water, suchas brick 90-190 l/m³, heavy concrete 140-190 l/m³ and limestone 180-270l/m³. The drying of moist materials such as masonry is eected as follows:
•
The moisture moves from the inside of the material to its surface
•
Evaporation occurs on the
surface = Transfer of water vapour to the ambient air
•
The air containing water vapour
is constantly circulated through the air dehumidier. The air is dehumidied and, slightly heated, leaves the unit in order to re-absorb water vapour
•
In this way, the moisture
contained in the material is reduced gradually.
The material is dried!
The accumulated condensate is collected in the unit and drained o from there.
Drying materials
% RH
Evaporator Condenser
Air temperature
Air direction
Air humidity
Progression
As it ows through or over the evaporator, the air stream is cooled to dew point. The water vapour condenses, and is collected in a condensate trap from where it is drained o.
Temp. Water vapour content in g/m3 at humidity of
°C 40% 60% 80% 100%
-5 1.3 1.9 2.6 3.3 +10 3.8 5.6 7.5 9.4 +15 5.1 7.7 10.2 12.8 +20 6.9 10.4 13.8 17.3 +25 9.2 13.8 18.4 23.0 +30 12.9 18.2 24.3 30.3
Page 7
CTK 240 mobile air dehumidier
Water vapour condensation
Because the capacity for the maximum possible volume of water vapour increases as the air is heated, the volume of water vapour contained remains constant and so relative humidity falls.
In contrast, because the capacity for the maximum possible volume of water vapour decreases as the air is cooled, the volume of water vapour contained remains constant and so relative humidity increases. If the temperature continues to fall, the capacity for the maximum possible volume of water vapour is reduced so much so that it is ultimately equal to the volume of water vapour contained in the air. This temperature is referred to as the dew point. If the air is cooled to below the dew point, the volume of water vapour in the air will become greater than the maximum possible volume of water vapour. At this point, the water vapour begins to precipitate. This condenses to water and moisture is removed from the air.
Examples of condensation include steamed-up window panes in winter, or the moisture on the outside of a cold drinks bottle.
As the relative humidity of the air increases, so too does the dew point, making it easier for the temperature to fall below it.
Condensation heat
The Energy transferred to the air from the condenser consists of:
1. The amount of heat derived beforehand in the evaporator.
2. The electrical drive energy.
3. The condensation heat released by liquefying the water vapour.
Energy must be supplied when liquid is converted into a gas. This energy is designated as evaporation heat. It does not cause any increase in temperature, but is required to convert a liquid into a gas. Conversely, energy is released when gas is liqueed, this is designated as condensation heat.
The amount of energy from evaporation heat and condensation heat is the same.
For water, this is: 2250 kJ/kg (4.18 kJ = 1kcal)
From this it is evident that the condensation of water vapour causes a large quantity of energy to be released.
If the moisture that it is to be condensed is not introduced by evaporation in the room itself, but from outside, e.g. through ventilation, the condensation heat released contributes to the heating of the room. With drying operations, a heat cycle is created, whereby heat is consumed for evaporation and released for condensation. When dehumidifying fed air, alarger contribution of heat is created, which manifests itself as atemperature increase.
Generally speaking, the time required for the drying process is not only dependent on the output of the unit, but is determined to a greater extent by the speed at which the material or building section loses its moisture.
Page 8
CLIMIA
nozzle into the condensate container below either continuously or only during the defrosting phases.
A oat is installed inside the condensate container. In the event that the container is full, the oat will activate a microswitch which will switch o dehumidication mode.
The units switch o and the “container full” indicator light on the control panel illuminates. Thisextinguishes again when theempty condensate container isre-inserted. The units then restart.
In unattended continuous operation with an external condensate connection, the condensate that occurs is drained continuously via a hose connection. The units then start.
In unattended continuous operation with an external condensate connection, the condensate that occurs is drained continuously via ahose connection.
Recirculating fan
Condensate container
Condenser
Evaporator
Condensate trap
Compressor
Moist room air
Dehumidied
room air
Fig. 1 Schematic depiction of the workings of the air dehumidier
7.0 Unit description
In dehumidication mode, one of the “Fan stage” indicator lights on the control panel illuminates.
The fan extracts the moist room air through the intake grill with lter, evaporator and the condenser behind.
Heat is removed from the room air on the cold evaporator. The air is then cooled to below dew point. The water vapour contained in the room air is then deposited as condensate or rime on the evaporator ns.
On the condenser (heat exchanger), the cold and dehumidied air is warmed up again and discharged back into the room via the outlet grill with a temperature increase of around 5 - 10°C above the room temperature. The processed, dry air then re-mixes with the room air. Continuous circulation of the room air through the unit gradually reduces the relative humidity (% RH) in the room to the desired humidity level.
Depending on the room air temperature and the relative humidity, condensed water will drip into the condensate trap and then through the integrated discharge
The units have been designed for universal and straightforward air dehumidication.
Their compact dimensions allow the unit to be transported and set up with ease.
The units operate in accordance with the condensation principle and are equipped with a hermetically sealed refrigerant system, heat gas defrosting, low-noise and low­maintenance fan and connection cable with plug.
The fully automatic control, the variable hygrostat, the condensate container with integrated overow protection and the connection nozzle for condensate drainage guarantee fault-free continuous operation.
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations.
The units are dependable and oer ease of operation.
The units are used in all locations, where dry air s a must and where economic consequential damage (such as that caused by mould) must be prevented.
The units may be used for the drying and dehumidication of areas such as:
•
Living rooms, bedrooms, shower
rooms or cellar rooms
•
Laundry rooms, weekend homes,
caravans
•
Warehouses, archives,
laboratories
•
Bathrooms, wash rooms and
changing rooms etc.
•
Basements, storage rooms
Operating sequence
The units are switched on and o by the power key.
Page 9
CTK 240 mobile air dehumidier
8.0 Set-up
For the best economic and safe use of the units, the following notes must be followed in full:
•
The units must be set up in an
upright and level position, to ensure that the condensate can drain freely
•
To ensure optimum air
circulation, the units should be set up in the centre of the room, where possible
•
Ensure that the room air can
be sucked in and discharged without hindrances
•
Observe a minimum clearance of
50 cm from walls at all times
•
Units must never be set up in the
immediate vicinity of heaters or other sources of heat
•
Air circulation is improved if the
unit is set up approx. 1 m above the ground
•
The room being dried or
dehumidied must be closed to the surrounding atmosphere
•
Avoid having opened windows
and doors etc., and avoid frequent entry to or exit from the room as much as possible
•
The units may not be used in
environments containing a great deal of dust or chlorine, or in places with atmospheres containing ammonia
•
The output of the unit is
entirely dependent on the conditions inside the room, room temperature, relative humidity and observance of the set-up instructions
Min. 0.5m
distance to wall
Maintain adequate clearance from
heaters or other sources of heat.
Keep windows and doors closed!
Fig. 2 Schematic depiction of how to set up the air dehumidier
9.0 Commissioning
Before commissioning the unit or if local requirements dictate, the air­inlet grill and air-outlet grill must be checked for contamination.
Important notes prior to commissioning
•
All extensions to the electrical
connection must be of asucient cable size and must only be used fully rolled out or unrolled
•
Never use the power supply
connection cable as a pull cord
•
After being switched on,
theunits operate fully­automatically until switched o by the hygrostat or oat when the condensate container is full
•
The condensate container must
be inserted properly
The unit cannot be operated if the condensate container isnot inserted properly!
•
In order to prevent damage to
the condenser, the units are equipped with a mechanism that prevents the compressor being immediately switched back on after it is switched o
The units do not switch back on until a waiting time of around 3 minutes has elapsed!
•
If the units work in continuous
operation with an external condensate drainage connection, refer to the relevant section
NOTE
A contaminated grille or lter must be cleaned or replaced immediately.
Page 10
10
CLIMIA
1. The power key switches the unit on and o.
2. The speed key sets the fan stage. The min/max fan stage indicator lights indicate the fan stage at which the unit is running.
3. If required, the unit can be switched to manual timer mode using the timer key.
4. Use the “Humidity/Time” arrow keys to set the required air humidity in the installation room or the required air humidier operating time.
5. After an operating time of 250hours, the “Check Filter” indicator light illuminates and the lter must be removed and cleaned according to the instructions. The unit can be reset using the lter reset key after inserting the lter.
6. The display shows the current air humidity or the required air humidity during regulation, or the required operating time. The display shows the current air humidity again 10 seconds after the setting is made.
NOTE
In room temperatures below
10°C
and relative humidity
below
40%
, economical use of the unit can no longer be guaranteed.
NOTE
After setting the required air humidity, the display shows this for another 10 seconds before displaying the current air humidity again.
NOTE
Note that the compressor does not switch on until a waiting time of 3 minutes has elapsed.
Restart protection!
Control panel
The control panel contains various keys, indicator lights and a display.
7. The bucket full indicator light indicates when the condensate bucket is full and must be emptied.
8. The unit is in defrost mode while the “Defrost” operating light is illuminated.
Commissioning the units
1. Connect the unit's electrical connection to a properly installed mains socket.
2. Press the power key once to switch on the unit.
3. Use the arrow keys to set the required air humidity of the installation room. The air humidity can be set at increments of 5 %.
The recommended approximate setting values are listed in the adjacent section.
Adjusting units/moisture
The unit’s dehumidication power is entirely dependent on the conditions inside the room, the room temperature, the relative humidity and observance of the notes in the “Setting up” chapter.
Page 11
11
CTK 240 mobile air dehumidier
The following notes must also be observed in full:
•
Ensure that the air can discharge
without hindrances
This is the only way to guarantee optimum unit operation!
•
Ensure that sensitive objects
such as house plants are not placed directly in the air ow emerging from the unit.
Automatic defrost system
The moisture contained in the room air condenses when cooling and coats the evaporator ns with rime or ice depending on the air temperature and the relative humidity (% RH).
The automatic defrost system that is integrated in the unit switches the defrost cycle on if required.
The rime or ice that has accumulated on the exchanger surfaces is defrosted using electronic circulation mode as required.
This tried and tested defrosting method guarantees high dehumidication performance.
Dehumidication mode is paused during the defrost phase. The “Defrost mode” indicator light indicates that the defrost cycle is running.
The higher the room temperature and relative air humidity, the higher the dehumidication power.
A relative humidity of around 45to60% is sucient in living rooms. The air humidity should not exceed 40 to 45% in warehouses, archives, etc.
Timer function
The units feature an integrated timer function.
Pressing the timer key switches the unit’s automatic mode on and o.
If automatic mode is switched o, the arrow keys can be used to set the required operating time.
The operating time can be set for a maximum of 24 hours in increments of an hour.
The unit will switch itself o automatically after the set time has elapsed.
NOTE
If the room temperature is suciently high (>12 °C), the surface of the ns will not be cold enough for rime formation to occur, rendering defrosting unnecessary. Therefore, the air dehumidier works economically.
Emptying the condensate container
The integrated condensate container must be emptied from time to time.
Dehumidication mode is switched o if the condensate container is full. The “BUCKET FULL” indicator light indicates that the unit has switched o.
1. Pull the full container forwards and out carefully.
2. Pour the water into a drain.
3. Re-insert the emptied container carefully into the unit.
The “BUCKET FULL” indicator light extinguishes and the unit continues to run automatically.
NOTE
For economical and technical reasons, the units must not be operated at an ambient temperature below 5 °C.
NOTE
After being emptied, the condensate container incl. oat must be checked for damage, contamination etc.
NOTE
The unit can only be started once the condensate container has been inserted correctly.
NOTE
The devices can be switched ON and OFF via an external timer or a Smart Home socket if required.
Page 12
12
CLIMIA
Press the power key once to switch on the unit.
If the units are inactive for long periods, disconnect them from the mains power supply.
Empty the condensate container completely and dry with a clean cloth.
Beware of dripping condensate!
The units must be cleaned and dried completely before storing.
When storing the unit, cover with a plastic sheet/foil if necessary andstore in an upright position inasheltered and dry location.
The units are only permitted to be stored upright in a suitable storage location that is protected against dust and direct sunlight.
Continuous operation with external condensate outlet
The units are equipped with a special connection nozzle on the rear. A standard 1/2” water hose can be connected to this.
1. The condensate hose connection must be switched o rst for this purpose. The rubber stopper can then be removed.
2. Pull the condensate hose connection over a suciently long and suitable drain hose.
3. Connect the drain hose to the connection nozzles and tighten the condensate hose connection by hand.
In unattended permanent operating mode, the condensate should preferably be drained into a lower­level drain. If using an external collection container (pan, bucket, etc.), theunit must be placed at a correct height.
10.0 Shutdown
The units are equipped with four foot rollers and two additional handles for easy and convenient transport.
•
Before each change of location,
switch o the unit and remove the power plug from the mains socket
•
Empty the condensate bucket
completely.
•
If residual moisture remains on
the evaporator or water remains in the condensate container, the units must only be transported in an upright position
•
The transport rollers are only
suitable for use on level and smooth ground
•
The units must be carried when
transporting on rough terrain or uneven surfaces
11.0 Unit transport
CAUTION!
There is no unit overow protection in this variant.
CAUTION!
Ensure that the drainage hose is placed at an incline to the drain to allow the condensate to drain without hindrance!
NOTE
Beware of dripping condensate. After switching o the units, the evaporator may continue to defrost under the inuence of the ambient temperature.
CAUTION!
The mains cable must never be used as a pull cord or xing device.
Page 13
13
CTK 240 mobile air dehumidier
All moving parts have a low­maintenance permanent coat of lubricant. The entire refrigerant system is designed as a maintenance-free, hermetically sealed system and may only be repaired by a specialist.
•
Observe the regular care and
maintenance intervals
•
In accordance with the operating
conditions, the units must be checked as required but at least yearly by a specialist to ensure that they are in a condition that is safe to use
•
Only clean the units with a dry or
damp cloth Do not use a water jet!
•
Never use abrasive or solvent-
based cleaners
•
Even with heavy contamination,
use only suitable cleaners
•
Check the inlet and outlet grille
for contamination on a regular basis
Clean or replace if required!
12.0 Care and maintenance
Cleaning the condenser and evaporator
The unit housing must be opened to allow the inside of the unit to be cleaned and to provide access to electrical components.
•
Clean the condenser and
the evaporator by blowing, vacuuming or using a soft brush.
Do not use water jets!
•
Clean the interior surfaces on the
units, the condensate traps with hose connection, the fan and the fan housing carefully
•
Check all unit components for
damage and repair if necessary
•
Carefully ret all parts that were
removed in reverse order
NOTE
Regular care and maintenance is fundamental to a long service life and fault-free operation of the unit.
CAUTION!
Before undertaking any work on the units, the power plug must be removed from the mains socket.
NOTE
Adjustment and maintenance work may only be carried out by authorised and qualied technicians.
NOTE
When cleaning the exchanger, particular care must be taken because the ne aluminium ns bend very easily.
CAUTION!
An electrical safety check must be carried out in accordance with VDE0701 after any work on the units.
Filter cleaning
To prevent damage to the unit, it is equipped with an intake grill with integrated air lter.
In order to prevent power losses or unit faults, the intake grill with lter must be inspected as required, but every 2 weeks at the latest, andcleaned if necessary.
1. Use the “POWER" key to switch the unit o.
2. Remove the power plug from the mains socket.
3. Reach into the recessed grip and remove the air lter.
4. Clean the air lter with lukewarm water or a vacuum cleaner.
CAUTION!
The unit is not permitted to be operated without the air lter tted!
Page 14
14
CLIMIA
13. 0
Troubleshooting
The units are manufactured using state-of-the-art production methods and tested several times to verify their correct function.
However, if a functional fault should occur, the unit should rst be checked in accordance with the following list.
5. Heavier contamination may be remedied by rinsing the lter in a lukewarm (max. 40°C) soap solution. Finally, always rinse the lter carefully with clear water and allow to dry!
6. Also check the intake grill for contamination and clean if necessary.
7. Before retting grill and lter, ensure that they are fully dry and that no damage has been sustained.
The unit runs but condensate is not formed:
•
Check the room temperature.
The operating range of the unit is between 5 °C and 32°C
•
Check the air humidity
min.30%RH required
•
Check the intake grill and air
lter for contamination
Clean or replace if required!
•
Have the heat exchanger ns
checked for contamination
This work requires the unit to be opened and must therefore only be carried out by an authorised specialist company!
The unit is loud or condensate runs out:
•
Check whether the unit is on
astable and even base
•
Check whether the unit is
standing upright and stably
•
Have the condensate trap or
the connection nozzles checked to see whether there are dirt deposits on them
This work requires the unit to be opened and must therefore only be carried out by an authorised specialist company!
NOTE
Heavily contaminated or damaged air lters must be replaced with new parts. Only original spare parts may be used.
NOTE
Adjustment and maintenance work may only be carried out by authorised and qualied technicians.
The unit does not start:
•
Check the hygrostat’s setting
The set value must be lower than the relative humidity in the installation room!
•
Check the power supply and
the power fuse provided by the customer 230V/1~/50 Hz
•
Check the power plug and the
cable for damage
•
Check the condensate bucket’s ll
level and seating
The “Bucket full” indicator light must not be illuminated!
•
Check that the microswitch [MS]
on the condensate bucket is functioning
•
Check that the inlet and outlet
are free Overheating!
•
Check the fuse on the control
board
NOTE
The units work with environmentally-friendly and ozone-neutral R134a refrigerant. The mixture of refrigerant and oil within the unit must be disposed of properly in accordance with the statutory or locally­applicable regulations.
NOTE
If the unit fails to function correctly after the checks have been carried out, contact an authorised specialist.
CAUTION!
Work on the refrigerant system and on the electrical equipment must only be conducted by a specially authorised specialist!
Page 15
15
CTK 240 mobile air dehumidier
15.0 Electrical wiring diagram
•
The units are operated with
230V / 50 Hz alternating current
•
The electrical connection is
established using a built-in mains cable with earthed safety plug
•
Extensions to the connection
cable may only be carried out by authorised electricians, subject to the length of the cable, connected load of the unit and taking into consideration how the unit is used at its location
CAUTION!
All cable extensions must only be used in fully unreeled or reeled o condition.
NOTE
The electrical connection to the units must be made at feedpoints with residual current devices in accordance with VDE 0100, Section 704. When installing the units in extremely damp environments such as laundry rooms, showers etc., the unit must secured with aresidual current device provided by the customer in accordance with the regulations.
14. 0 Electrical wiring
CN 1
NO
HUMIDITY SENSOR /
HYGROSTAT
COM.
CN 3
L
L
N
E
CN 4
CN 2
CN 1
POWER SUPPLY
T1A L 250V
H
COMPRESSOR
OL P
CN 7
N
N
P6
P3
P4
P5
TEMPERATURE PROBE
SWITCH
FAN
MOTOR
CONDENSER
CONDENSER
CONTROL BOARD
FUSE
BLUE
BLUE
BLUE
YELLOW / GREEN
BROWN
WHITE
RED
YELLOW
RED
BLUE
WHITE
BLACK
Page 16
16
CLIMIA
16.0 General view of unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
2
1
4
3
5
6
7
8
10
11
12
37
3
32
31
30
26
47
45
44
43
41
39
38
49
50
51
9
46
40
42
16
33
21
13
23
24
22
Page 17
17
CTK 240 mobile air dehumidier
17.0 Spare parts list
When ordering spare parts, please always state the EDP no. and unit number (see name plate)!
No. Designation EDP no.
1 Floor pan 2 Conveyor rollers 3 Compressor, cpl. 4 Vibration dampers 5 Suction pipe 6 Drain line 7 Centre wall 8 Condensate trap
9 Evaporator, complete. 10 Condenser, complete. 11 Capillary 12 Y-pipe 13 Condenser, (for compressor), complete) 16 Microswitch 21 Condensate trap cover 22 Fan housing 23 Fan wheel 24 Fan motor 26 Distribution block 30 Control board 31 Conductor board / board 32 Probe (evaporator/EVAP) 33 Hygrostat 34 Condenser (fan motor) 37 Mains cable with plug 38 Front wall 39 Back wall 40 Transport handle 41 Top cover 42 Intake grill 43 Air lter 44 Condensate bucket cover 45 Condensate container 46 Float, cpl. 47 Transport handle (condensate bucket) 49 Rubber stopper 50 Condensate hose connection 51 Control panel
Page 18
18
CLIMIA
18.0 Technical data
1)
Contains greenhouse gas according to Kyoto protocol
2)
Noise level measurement DIN 45635 - 01 - KL 3
Series CTK 240
Operating range, temperature °C 5 to 32
Operating range, humidity % RH 30 to 90
Dehumidication capacity max. l/day 30
At 27 °C/60 % RH l/day 18
Fan stages 2
Max. airow volume m3/h 240/186
Condensate container capacity Litres 6.3
Refrigerant
1)
--- R134A
Refrigerant quantity g 200
Power supply V/~/Hz 230/1/50
Max. rated current consumption A 4.1
Max. power consumption kW 0.57
Sound pressure level LpA 1m 2) dB (A) 46/41
Dimensions
Depth mm 272
Width mm 384
Height mm 610
Weight kg 17
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Page 19
19
CTK 240 mobile air dehumidier
19.0 Maintenance log
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
✍
Unit type: .................................. Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside -
Unit cleaned - inside -
Fan blade cleaned
Fan housing cleaned
Condenser cleaned
Evaporator cleaned
Fan function checked
Air-inlet grid with lter cleaned
Unit checked for damage
Safety devices checked
All fastening screws checked
Electrical safety check
Test run
1. Date: ..............
..............................
Signature
2. Date: ..............
..............................
Signature
3. Date: ..............
..............................
Signature
4. Date: ..............
..............................
Signature
5. Date: ..............
..............................
Signature
6. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
8. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
10. Date: ............
..............................
Signature
11. Date: ............
..............................
Signature
12. Date: ............
..............................
Signature
13. Date: ............
..............................
Signature
14. Date: ............
..............................
Signature
15. Date: ............
..............................
Signature
16. Date: ............
..............................
Signature
17. Date: ............
..............................
Signature
18. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
20. Date: ............
..............................
Signature
Comments: .....................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
Page 20
20
CLIMIA
EC – Declaration of Conformity
Original Declaration of Conformity
We do hereby declare that the units named below, produced and sold by us, satisfy the relevant basic requirements of the EC Directives, the EC safety standards and other product-specic EC standards.
Name of Manufacturer: Intakt GmbH Climia - Air conditioning and heating technology Niemeierstraße 13 D - 32758 Detmold, Germany
Name of the CE representative: Intakt GmbH Climia - Air conditioning and heating technology Niemeierstraße 13 D - 32758 Detmold, Germany
Unit (machinery) model: Air dehumidier
Series/ Class: CLIMIA CTK 240 Series/ Class Number: 1803...
Delegated regulations (EU): 2011/65/EU:2011 2014/30/EU:2014 2014/35/EU:2014
Applicable standards: DIN EN 12102-1:2018 DIN EN 55014-1:2017; DIN EN 55014-2:2015 DIN EN 60335-1:2012; DIN EN 60335-2-40:2014 DIN EN 61000-3-2:2015; DIN EN 61000-3-3:2014 DIN EN 62233:2008
Detmold, 19th June 2018 Intakt GmbH
................................................................
Managing Director’s signature
Page 21
21
CTK 240 mobile air dehumidier
Notes
Page 22
22
CLIMIA
Page 23
23
CTK 240 mobile air dehumidier
Page 24
Intakt GmbH
Climia - Klima- und Wärmetechnik
Niemeierstraße 13
D - 32758 Detmold
Loading...