Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
Page 3
1. GENERAL
These are the installation, adjustment and maintenance instructions for Climecon CleanMaster® hoods.
The model range of Climecon CleanMaster® hoods includes:
• CleanMaster® hoods
• CleanMaster® hoods with capture air
• CleanMaster® hoods with supply air and capture air
Make sure you read and understand these installation, adjustment and maintenance instructions before starting to install and use the product. If you have any questions about the installation or operation of the product, please contact the Climecon customer service.
Climecon Oy
Lämmittäjänkatu 4 A
00880 HELSINKI
Puh 020 198 6600
Fax 020 198 6609
www.climecon.fi
1.1 Safety at work and safe installation of the product
Failure to observe these operating and safety instructions during operation, disregarding
these instructions or using the UV equipment not as specified can result in injuries!
NOTE! The electrical connection of the CleanMaster® system may only be carried out by an
authorized electrician. Warranty is subject to the condition of using Climecon spare parts and
UV lamps. Only the original parts or the spare parts or UV lamps ordered from Climecon may
be used in the device. The UV lamps should always be ordered from Climecon customer service
(tel. 020 198 6600).
Ultraviolet radiation and ozone are hazardous to health! The areas which are especially
exposed to the ultraviolet radiation are the skin and eyes. The radiation can cause burns and a
long-term exposure can result in a cataract. Always make sure that the UV lamps are turned
o when removing the grease filters!
ALWAYS wear safety goggles and safety gloves during installation for protection against
quartz fragments, which can become scattered around if the UV lamp breaks.
1.2 Receiving the goods
Check that the delivered product batch is according to your order and all the parts stated in
the delivery note are included. The carrier of the cargo should be informed immediately about
errors in the delivery and incorrect delivery as well as possible damages occurred during transportation, and the respective notice should also be sent to Climecon or the distributor.
The term of notice is 5 days from delivery. Climecon Oy shall take no responsibility for costs
arising from the replacement of products, which had not been installed according to the installation instructions.
In case of problems you should contact the Climecon customer service!
Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
Page 4
1.3 Warnings
UV light and ozone are harmful
The areas which are especially exposed to the UV light are the skin and
eyes. The light can cause burns and a long-term exposure can result in a
cataract; UV light damages the lens and cornea of the eyes.
BEFORE STARTING TO REMOVE THE GREASE FILTERS,
ALWAYS MAKE SURE THAT THE UV-LAMPS ARE SWITCHED OFF!
CAREFULLY READ THE OPERATING INSTRUCTIONS!
www.climecon.fi
The warning label shown in the figure is attached to a visible
place on the product already in the factory. Stick the other label included in the package next to the UV Multi control unit.
Varoitus/Caution
• Tämä keittiöhuuva on varustettu UV/otsoni puhdistinjärjestelmällä
• Kytke virta pois ennen kuin poistat rasvasuotimia
• UV-valo voi vahingoittaa silmiä ja ihoa
• This kitchen hood is equipped with UV/ozone purifying system
• Shut down the system before removing grease filters
• UV light is harmful for eyes and skin
USE PROTECTIVE GLASSES AND PROTECTIVE
GLOVES IN ALL INSTALLATION RELATED WORKS
(rupture of a pipe can cause quartz shards)
Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
Page 8
www.climecon.fi
3.3 Installation of the CCM control unit
Start with the installation of the CCM control unit by looking at the wiring diagram included in the
delivery.
1. The CCM control unit and possible slave units should be mounted on a wall in a visible place
which can be easily accessed.
2. Mount the safety switch included in delivery on a wall near the CCM control unit, where the
switch can be easily accessed.
3.4 Electrical wiring
3.4.1 Electrical wiring of the CCM control unit
1. Lead the voltage supply to the safety switch.
2. From the safety switch lead the voltage supply to the CCM control unit and to possible slave
units.
3. Connect the conductors coming out from the CCM control unit to the UV lamp. following the
wiring diagram provided at the end of these instructions.
4. Connect the conductors of the SlideSafe safety lock of the hoods to the CCM control unit or a
slave unit.
3.4.2 Connecting the CCM control unit with the automation system of the building
The CCM control unit gives the possibility to send operational information to the automation system of the real estate, and to request starting permission, if necessary. Detailed information is
provided in the wiring diagram at the end of these instructions.
Output:
Operating status
• The system functions normally. A green light is lit in the control panel.
Common alarm
• Alarm, the system has switch o. A red light is lit in the control panel.
Warning
• Warning, action by the user is required. The system still functions.
A yellow light is lit in the control panel.
Input:
External control
• The building automation has not given the permission for operation.
A red light is lit in the control panel.
Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
10
Page 11
www.climecon.fi
3.7 Before you start the CleanMaster® system
Check the following points before starting the CleanMaster® system:
• UV lamps are correctly installed
• Wires led from the UV lamps are connected through their quick connections to sockets in the
hood, and tightened
• The wires of UV lamps and SlideSafe safety lock from the UV control unit to the terminal block
box of the hood are fixed from both ends with a screw
• The air flow sensor has been installed in the ventilation duct and adjusted
• A maintenance / safety switch has been installed to supply voltage line before the UV control unit
• All grease filters have been installed and the safety lock of grease filters has been locked
• The labels about UV lamp replacement and maintenance instructions of the hood, which were
included in the delivery, have been attached to a visible place near the hood
3.8 Starting the CleanMaster® system
Start the CleanMaster® system by turning the main switch of the CCM control unit to ON-position.
After the start, the text «restart» appears on the display of the UV system, after which in about 60
seconds the starters of UV lamps become active (starting delay of the air flow sensor).
Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
Page 13
123,0
123,0
6
1
2
3
4
5
7
4. INSTRUCTIONS FOR ADJUSTMENT OF
CLEANMASTER® HOODS
4.1 Adjusting the supply air, exhaust air and capture air flow
www.climecon.fi
Adjusting the supply air flow
• First measure the pressure drop at the
measuring connection (5) of the supply air
chamber
• Remove supply air modules (6), using a
screwdriver
• Adjust the supply air by turning the adjusting
damper (7) inside the supply air chamber
• Lock the adjusting damper with a locking
screw
• Re-install the supply air modules (6) to their
places
• Measure the pressure drop at the measuring
connection (5) of the supply air chamber
• Repeat the above procedure, if necessary
Adjusting the exhaust air flow
• Carefully remove the grease filter cartridge
(1) by pushing its bottom edge inwards while
lifting the upper edge up and away from the
mounting groove
• Open the locking screw (3) of the adjusting
damper (4)
• Increase or decrease the suction opening by
moving the damper in its sliding rails
• Install properly the filter cartridge(s)
• Measure the pressure drop at the measuring
connection (2) of the chamber
• Repeat the above procedure, if necessary
• Finally lock the damper with a locking screw
and check that the filter cartridges are properly
in position
Adjusting the capture air
The thrust length of capture air can
be adjusted. You can adjust the thrust
by first turning the hand screws of
the capture air unit, then moving the
screws sideways and finally locking in
position by tightening the hand screws.
Maksimi (Fully open)1,42,84,25,67,08,4
Minimi (Fully open)*0,61,21,82,43,03,6
*Is only recommended if the pressure of the supply air is over 15Pa.
4.3 Calibration of the air flow sensor
Before you start calibrating the air flow sensor, check that
• the CCM control unit is installed
• ventilation has been adjusted and functions normally
1. Switch on the CCM control unit.
2. The air flow sensor measures the air flow for 60 seconds, during which both of the signal lights
are illuminated. When measuring is completed, one of the lights goes o.
a) If a red light is illuminated:
Turn the adjusting screw slowly to the right, until the red light goes o and the green led is illuminated. Then turn the adjusting screw a further 1/2 round to the right.
b) If a green light is illuminated:
Turn the adjusting screw slowly to the left, until the green light goes o and the red light is
illuminated. Then turn the adjusting screw a further 1/2 round to the right, until the green light
is illuminated.
When the air flows change in the system, repeat the calibration of the air flow sensor.
Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
Signal lights (red/green)
Page 15
5. OPERATING INSTRUCTIONS FOR
CLEANMASTER® HOODS
5.1 Functions of the control panel of the CCM control unit
Functions of the keys:
www.climecon.fi
INFO
ON/OFF
ARROW
DOWN
MENU
REMOTE
• changes the display screens
(Main Menu, filtering hours/
operating time/hours, meter
screen, depending on settings)
• cursor up in menu
• changes values (higher)
• to On/O menu
• cursor to the right
• cursor down in menu
• changes values (lower)
• to menus
• selection of a function
• confirms a change
• local/remote operation (NOTE! the display should read ”local”)
• cursor to the left
5.2 Fault conditions of the CleanMaster® system
In a fault situation, the colour of the display of the CCM control unit and the colour of LED lights
change into yellow or red, depending on the situation:
YELLOW LIGHT
Text on the screen: lamp age warning
The service hours of the UV lamp are approaching the end.
Order a new UV lamp from the Climecon customer service, tel. 020 198 6600.
Text on the screen: lamp age exceeded
The service hours of the UV lamp have been exceeded. Replace the old UV lamp with a
new UV lamp ordered from Climecon. See the instructions for replacing the UV lamp in
subsection 6.4.
RED LIGHT
Text on the screen: lamp age exceeded
The service hours of the UV lamp have been exceeded. Replace the old UV lamp with a
new UV lamp ordered from Climecon. See the instructions for replacing the UV lamp in
Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
Page 16
5. OPERATING INSTRUCTIONS FOR
CLEANMASTER® HOODS
5.1 Functions of the control panel of the CCM control unit
Functions of the keys:
www.climecon.fi
INFO
ON/OFF
ARROW
DOWN
MENU
REMOTE
• changes the display screens
(Main Menu, filtering hours/
operating time/hours, meter
screen, depending on settings)
• cursor up in menu
• changes values (higher)
• to On/O menu
• cursor to the right
• cursor down in menu
• changes values (lower)
• to menus
• selection of a function
• confirms a change
• local/remote operation (NOTE! the display should read ”local”)
• cursor to the left
5.2 Fault conditions of the CleanMaster® system
In a fault situation, the colour of the display of the CCM control unit and the colour of LED lights
change into yellow or red, depending on the situation:
YELLOW LIGHT
Text on the screen: lamp age warning
The service hours of the UV lamp are approaching the end.
Order a new UV lamp from the Climecon customer service, tel. 020 198 6600.
Text on the screen: lamp age exceeded
The service hours of the UV lamp have been exceeded. Replace the old UV lamp with a
new UV lamp ordered from Climecon. See the instructions for replacing the UV lamp in
subsection 6.4.
RED LIGHT
Text on the screen: lamp age exceeded
The service hours of the UV lamp have been exceeded. Replace the old UV lamp with a
new UV lamp ordered from Climecon. See the instructions for replacing the UV lamp in
Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
Page 17
6. INSTRUCTIONS FOR MAINTENANCE OF
CLEANMASTER® HOODS
Due to hygiene and fire safety in the kitchen, but also to ensure that the ventilation functions it
is important to keep the kitchen equipment clean. The cleaning interval of Climecon CleanMaster® hoods depends on their use and should be determined on the basis of the level of use.
The hoods can be cleaned with cleaning agents, which are suitable for cleaning stainless steel.
Extremely strong alkali (pH > 11) should be avoided. The Climecon UV lamps do not need cleaning
in case of normal use.
6.1 Cleaning the hood
1. The surfaces of the hood should be cleaned by wiping lightly.
2. Clean the side troughs and grease pans of the hood. Grease pans are machine-washable.
3. Gently wipe the covering glass of lights, if necessary.
4. Clean the exhaust air chamber, if necessary.
See the instructions for removing the grease filters in subsection 6.2 Removing the grease
filters.
5. Clean the supply air modules, if necessary.
www.climecon.fi
Supply air modules can be easily removed by opening first the fixing mechanism at the top of
the module with the help of a screwdriver and then pulling the supply air module away from the
supply air unit.
Lämmittäjänkatu 4 A, FI-00880 HELSINKI, Finland · Telephone +358 20 198 6600, Fax +358 020 198 6609
18
Page 19
6.4 Replacing the UV lamp
231
www.climecon.fi
Shut down the CleanMaster
by turning the main switch of the
CCM control unit to OFF position.
®
system
4
First remove the second grease filter from the left and then the other
grease filters.
8
91011
Open the SlideSafe safety lock by loosening the
hand screws and moving these to the lower position.
56
Remove the electrical connector (quick connector) of the UV
lamp from the ceiling of the
hood by turning the connector
counter clockwise.
Turn the hand screws of
the supports of the UV
lamp counter clockwise
and remove the UV lamp
from the suppor ts.
Move the grease filter on the
far lef t to the left.
7
Deliver the old UV
lamp to the recycling
station of fluorescent
lamps.
Replace the UV lamp with
a new lamp. Only Climecon
UV lamps may be used in the
CleanMaster
the new UV lamp from the
Climecon customer service.
®
system. Order
Mount the new UV
lamp to the holders and
tighten the hand screws
clockwise.
Attach the electrical connector (quick connector) of the
UV lamp to the ceiling of the
hood and tighten clockwise.
Install all the grease filters back into
the hood. First install the grease filters at far edges, leaving the second
grease filter from the left as the last.
1213
Lock the SlideSafe safety lock by first lifting the hand screws
to the upper position and then tightening the screws. NOTE!
The CleanMaster
safety lock has not been properly locked.