Climax Technology Co CTC1052LTE Users manual

Page 1
+--E1
August 25, 2017
Page 2
Table of Contents
1. Application Overview ____________________________________________________ 1
1.1. Identifying The Parts _________________________________________________ 1
1.2. The Power Supply ___________________________________________________ 2
1.3. Insert GPRS/3G/LTE SIM Card _________________________________________ 2
1.4. How to install the Control Panel ________________________________________ 3
1.5. Compatible with Climax’s SMS Editor ___________________________________ 3
2. Learn-in the Devices ____________________________________________________ 4
2.1. Command Learning __________________________________________________ 4
2.2. Local Learning ______________________________________________________ 4
2.3. Learn-In Device using Device ID ________________________________________ 4
3. System Configuration ___________________________________________________ 5
3.1. Entering Programming Mode __________________________________________ 5
3.1.1. Local Programming Mode __________________________________________________________ 5
3.1.3. Remote Programming Mode ________________________________________________________ 5
3.1.4. SMS Remote Programming __________________________________________ 6
3.2. Programming Your 1052 ______________________________________________ 6
3.3. SMS Remote Programming ___________________________________________ 20
4. Operation ____________________________________________________________ 21
4.1. Idle Mode __________________________________________________________ 21
4.1.1. Answering Incoming Phone Calls ___________________________________________________ 21
4.1.2. AC Power Check Up _____________________________________________________________ 21
4.1.3. CTC-1052 Low Battery ___________________________________________________________ 21
4.1.4. CTC-1052 Battery Disconnection ___________________________________________________ 22
4.1.5. Devices Low Battery _____________________________________________________________ 22
4.1.6. Automatic Check-in Report = Periodic Test Call ________________________________________ 22
4.1.7. Mobility Timer __________________________________________________________________ 22
4.1.8. Country Code __________________________________________________________________ 23
4.2. Alarm Activation ____________________________________________________ 24
4.2.1. GPRS Reporting Method _______________________________________________________________ 24
4.2.2. Digital Reporting Method _______________________________________________________________ 25
Page 3
4.2.3. Help Arrived Mode _____________________________________________________________________ 27
4.2.4. Speech Reporting Method ______________________________________________________________ 28
4.2.5. Report Sequence ______________________________________________________________________ 28
4.3 Walk Test (Range Test) _______________________________________________ 29
4.3.1. In Learning Mode _______________________________________________________________ 29
4.3.2. In Walk Test Mode ______________________________________________________________ 29
4.3.3. In Idle Mode ___________________________________________________________________ 30
4.4 Global Test _________________________________________________________ 30
4.5 Factory Reset _______________________________________________________ 30
5. Appendix _____________________________________________________________ 31
5.1. CID Event Code __________________________________________________________________ 31
5.2. Tunstall Event Code_______________________________________________________________ 32
Page 4
1. Application Overview
1.1. Identifying The Parts
TOP VIEW
1. GREEN LED
ON: AC Power is ON.
FLASH every second: AC Power
failure
FLASH every 2 seconds: Panel or
Device Low battery
4. RED HELP BUTTON (with backlight)
Back-lit disigned for easy access at
night
Backlight illuminates when off-hook
Backlight flashes during the waiting
period until help arrives
5. Microphone
6. Speaker
REAR VIEW
7. GPRS/3G/LTE SIM Card Base
This slot is for inserting a SIM card.
8. GPRS/3G/LTE Reset Button
QUICK FLASH every 2 seconds:
Supervision failure
2. RED LED
ON: Off-hook / Waiting retry pause /
Ready to enter Programming Mode (before entering PIN code)
FLASH: Programming Mode /
Pendant Learning Mode
3. GREEN RESET BUTTON
Press once in normal mode to reset
mobility timer (see command 44)
Before CTC-1052 dials out for alarm
reporting, press once to cancel the alarm reporting
During or at-the-end of conversation,
press once to terminate two-way voice communication
Press & hold for 3 sec: dial the Non-
Emergency call. (See section 4.1.2.)
Press & hold for 6 sec: enter Learning
Mode
Press & hold for 16 sec: disable
mobility setting
Press & hold for 1 sec: GPRS/3G/LTE
automatically resets
9. GPRS/3G/LTE Module LED Indicator (Red)
When power is supplied to CTC-1052,
the LED will light up for 5 seconds.
One flash per second indicates
3G/LTE noraml connection.
Continuous 5-second flashes indicate
there is no 3G/LTE connection/signal.
10. GPRS/3G/LTE Fault Indicator (Yellow)
FLASH every 5 seconds: SIM card
missing
2 FLASHES every 5 seconds: No
signal/reception
3 FLASHES every 5 seconds:
GPRS/3G/LTE module abnormal
4 FLASHES every 5 seconds: SIM
card PIN code error
<NOTE>
Fault indicator priorities: GPRS/3G/LTE
module abnormal > SIM card missing > No signal/reception > SIM card PIN
1
Page 5
code error
11. DC Jack
DC 12V 1A switching power
connection
12. Battery Switch
13. Local Programming Telephone Unit Input
A special telephone cord to connect
CTC-1052 and your phone unit for Local Programming (optional).
BACK VIEW
1.2. The Power Supply
An AC power adapter is required to connect
to a wall outlet. Be sure only to use an adapter with the appropriate AC voltage rating to prevent component damage. A DC 12V output and 1A switching power is generally used to power CTC-1052.
In addition to the adapter, there is a
rechargeable battery inside CTC-1052, which serves as a back-up in case of a power failure.
During normal operation, the AC power
adapter is used to supply power to CTC­1052 and at the same time recharge the battery. It takes approximately 72 hours to fully charge the battery.
The battery can be manually disconnected
by the battery switch located at the bottom.
Battery Switch is set as OFF by factory
default, the battery will not be charged when AC power is connected, nor will it serve as a back-up power source when AC power is missing. You need to switch the battery to ON after supplying AC power to CTC-1052
14. Mounting Holes
15. Mounting Bracket
<NOTE>
Please make sure the battery switch is
slid back to ON position (as marked) after manually disconnected the rechargable battery.
1.3. Insert GPRS/3G/LTE SIM Card
CTC-1052 Panel features built-in GPRS/3G/LTE communication facility to report to the Monitoring Station.
To Insert SIM card:
<NOTE>
It is recommended to disable the SIM
card PIN code before inserting into the Control Panel.
The GPRS/3G/LTE SIM card base is located on the rear side of the unit:
2
Page 6
Insert the SIM card with the chip side facing
up.
Push to the furthest extend, then press on
the edge of the SIM card firmly to secure it.
Use the 2 holes of the Wall Mounting
Bracket as a template, mark off the holes’ positions.
Drill 2 holes and insert the wall plugs if
fixing into plaster or brick.
Screw the base to the wall.
Hook the Control unit onto the Wall
Mounting Bracket (holding the unit with the front facing you).
SIM Card will delete its SMS message
whenever the CTC-1052 is powered on.
To remove SIM card:
Press and release on the edge of SIM card, the card will spring out.
1.4. How to install the Control
Panel
Locating a suitable position for the Control Panel
The Control Panel requires main power and
a constant GPRS/3G/LTE reception.
The Control Panel should be easily
accessible.
The Control Panel should not be placed in
a damp location, such as a bathroom.
1.5. Compatible with Climax’s SMS Editor
CTC-1052 is compatible with Climax’s SMS Editor, which is designed to facilitate SMS remote programming via a PC. This tool allows you to program the panel easily from your computer, without sending complex SMS text messages from a mobile phone.
The Control Panel should not be placed
close to any heat source, such as microwave ovens, which can reduce signal strength.
The Control Panel should not be located
alongside other radio transmitting devices, such as mobile phones, cordless phone, or wireless computer network (Wi-Fi) devices.
Important: When drilling into a wall, ensure
there are no hidden cables or pipes.
Mounting the Control Panel
The Control Panel can be mounted on the wall or wherever desired (e.g. on the table). Ensure the Control Panel is fitted at approximately chest height where the buttons, microphone, and speaker can be easily accessed and operated.
3
Page 7
2. Learn-in the Devices
There are two methods to learn in devices: command learning and local learning. The system can learn a total of 20 sensors.
2.1. Command Learning
Command Learning:
2. Release the Green Reset Button at the voice prompt “Release the Green button, Ready to learn sensor.” CTC-1052 is now in learning mode and the Red LED will start flashing.
3. Press the (Learn) button on the device or sensor. Voice Prompt: “(Name of Sensor) learned.”
1. The user can use Commands 91-94 to learn devices into the system.
2. Command 93 is designed to learn in devices for silent reporting, including WTR, Fall Sensor, or Panic Button.
3. Command 93 & 94 is designed to learn in the following devices and sensors.
PIR Sensor ----- PIR Smoke Detector ---- SD Carbon Monoxide Detector---- CO Fixed Panic Button ---- PB Wrist Transmitter ---- WTR Pendant Transmitter ---- WTR Water Sensor ---- WS Fall Sensor ---- FS
2.2. Local Learning
Local Learning:
The user can also use the local learning method to learn in all devices.
4. If no action within 10 seconds after “Ready to learn sensor” prompt, CTC-1052 will prompt “Press sensor button.” This prompt will repeat two times if no action.
5. If no action after second “Press sensor button” prompt, CTC-1052 will prompt “Press Green button to exit learning mode.” This prompt will be repeated three times if no action continutes.
6. If no action after 5 minutes, the CTC-1052 will automatically exit Local Learning Mode and return to idle mode. Voice Prompt: “We are now in Normal Operation Mode.”
2.3. Learn-In Device using Device ID
If sensor device ID is given (please consult
the supplier), the users can learn the device into the Control Panel using device ID.
User can use SMS commands or the
programming tool SMS iWizard (sold separately) to learn devices using device ID.
1. When the device is learnt in for the first time, voice prompt will prompt the device/sensor name and “learned.”
2. Within 3 minutes after exiting learning mode, the control panel will emit 1 long beep everytime it receives a test code (from any device).
3. Local Learning Mode cannot remove devices or sensors.
To enter Local Learning Mode:
1. Press and hold the Green Reset Button of the CTC-1052. When pressed, the CTC­1052 will emit one beep sound initially, and then will emit a double beep on the 6 second.
Please refer to the table CTC-1052 SMS
Programming Command Table or the SMS
iWizard operation manual on how to learn in devices into different zones using device ID.
th
4
Page 8
3. System Configuration
3.1. Entering Programming Mode
Two CTC-1052 programming modes are available: Local Programming Mode and Remote Programming Mode.
<NOTE>
3.1.2. CTC-835 Programmer
CTC-835 is a powerful programming tool (sold separetely) that features a built-in keypad and LCD display to help you to program the medical alarm panels effeciently and conveniently. It also features Once-for-All Uploading, which allows you program on a computer via the supplied Pilot software and you can then upload all the settings to the medical alarm panel simultaneously with a single mouse click.
GPRS/3G/LTE module will be powered
down when in Programming Mode. When AC Power resumes or when exits from Programming Mode, GPRS/3G/LTE module will be powered on again.
3.1.1. Local Programming Mode
From Idle mode, follow the steps below to enter Local Programming mode.
Step 1. Plug in the telephone set into LOCAL
PROGRAMMING input located on the
rear side of CTC-1052.
Step 2. Pick up the handset.
RED LED lights up.
Step 3. Enter default ACCESS CODE, 1111
followed by #.
Step 4. CTC-1052 will emit 2 short beeps and
the red LED starts to flash, indicating it is in Programming Mode.
Step 5. Proceed to program system by
referring to the Commands in section
3.2 Programming Your 1052.
For detailed usages, please refer to the Operation Manual of CTC-835 Programmer.
3.1.3. Remote Programming Mode
To allow Remote Programming, there are two options for CTC-1052 to answer the incoming calls.
(1) Auto Answering by ring count
(2) Dial in twice (Ring Count disable)
The two options are set by Command #41. Please refer to Command 41 under section 3.2
Programming Your 1052.
3.1.3.1. Auto Answering by Ring Count
By using Command 41, you can set the number of rings for CTC-1052 to answer (00-Rings is set as factory default).
Step 1. Dial CTC-1052 and wait for CTC-1052
to answer.
Step 2. Enter 1111 (defau lt 4-digi t Ac cess
Code) followed by #, via the phone set.
<NOTE>
Local programming is prohibited when
AC Power fails.
The first digit of Access Code must be
entered within 15 seconds, otherwise CTC-1052 will exit automatically.
Failure to enter the correct Access
Code within 2 minutes will cause CTC­1052 to exit the Programming mode automatically.
To exit Programming mode, enter 99
followed by #, or place the handset on hook, or disconnect the Programming telephone set.
Step 3. CTC-1052 will respond with two quick
beeps to indicate it is ready for Remote Programming. The RED LED will flash as a visual indication.
Step 4. You are now in Programming Mode.
Proceed to program by referring to the Command under section 3.2 Programming Your 1052.
3.1.3.2. Dial in Twice (Ring Count Disable)
As 00 is set in Command 41 by default, it means CTC-1052 is disabled to auto answer the incoming calls by ring count. If Remote programming is required, you will need to call CTC-1052 twice.
5
Page 9
Step 1. Dial CTC-1052 and hang up after first 2
rings, wait for another 8-20 sec then call again. CTC-1052 will answer the call on the first ring. You will enter the Remote Programming Mode after the first ring from the 2nd call.
Step 2. Enter 1111 (the default 4-digit Access
Code) followed by #, via the phone set.
Step 3. CTC-1052 will respond with two quick
beeps to indicate it is ready for Remote Programming Commands. The RED LED will flash as a visual indication.
Step 4. You are now in Programming Mode.
Proceed to program by referring to the Command in section 3.2
Programming Your 1052.
3.2. Programming Your 1052
How to enter Commands?
Please make sure CTC-1052 is in Programming Mode (RED LED flashes continuously) before trying any CTC-1052 Command Functions. Please refer to section
System Configuration, Entering Programming Mode.
Follow the protocol below to command
CTC-1052:
CC # DTMF
ACK
Function
Selection
# DTMF
ACK
<NOTE>
The first digit of Access Code must be
entered within 15 seconds; otherwise CTC-1052 will exit automatically.
To exit Remote Programming mode,
enter 99 followed by #.
3.1.4. SMS Remote Programming
CTC-1052 can be remotely programmed via
SMS commands. Please refer to section 3.3 SMS Remote Programming for usage.
1. 2. 3. 4. 5. 6.
1. CC = 2-digit DTMF Command
2. # = Termination of the DTMF Command
3. ACK = DTMF Command
Acknowledgement
On CTC-1052:
Short beep: Command succeeded
Long beep: Command failed
On the programming phone set:
Short beep: Command succeeded
Long beep: Command failed
4. Function Selection = According to different Command you will have different entering in this part, e.g. Tel. Number, Account number, etc.
5. # = Terminates Function Selection
6. ACK = Function Selection
Acknowledgement
On CTC-1052:
Short beep: Command succeeded
Long beep: Command failed
On the programming phone set:
Short beep: Command succeeded
Long beep: Command failed
6
Page 10
Follow the Command Steps to program
your CTC-1052:
Up to 20 digits including () are
allowed for each telephone number.
Step 1. Enter Command number (DTMF
Numeric Command, ex. (01), (02)…)
Step 2. Press (#) to terminate the DTMF
Command.
Step 3. One short beep will be heard for
successful Command entry.
Step 4. Enter the desired Command function
number.
Step 5. Enter (#) to terminate the Command
Operation.
Step 6. CTC-1052 will emit a short beep,
indicating successful programming.
The maximum interval between key strokes is 2 minutes. Otherwise, commands will be ignored and CTC-1052 will automatically exit to Idle Mode.
Any erroneous programming must be
rectified and program again correctly.
Command 01-04
Telephone Number Programming
Used to program the 1
respectively.
To program the 1
followed by (#). After one short beep, enter (telephone number) followed by (#).You can hear one beep from the telephone speaker that indicates the programming is successful.
st
- 4th Tel. numbers
st
Tel. number: enter (01)
Delete Telephone Number
To delete the 1
followed by (#), after one short beep, enter another (#). You can hear one beep from the telephone speaker that indicates the telephone number has been successfully deleted.
If you hear CTC-1052 emit one beep instead, that means you have failed to delete the telephone number. Please repeat the deleting steps again.
Likewise, you can erase the respective 2
rd
3
or 4th Tel. Numbers, by following the
above procedure.
st
Tel. number, enter (01)
nd
,
Command 05-06
Select Telephone Number for Alarm Reporting and Status Reporting
<IMPORTANT NOTE>
If the Tel. number is selected in Commands #5, #6 and #7, then Command #7 holds the top priority to overwrite the setting. The Tel. number selected in Command #7 will not be used for alarm and/or status reporting.
Command (05): Select which telephone
number & GPRS/IP (1-6) is/are to be used for Alarm Reporting.
Command (06): Select which telephone
number & GPRS/IP (1-6) is/are to be used for Status Reporting.
If you hear CTC-1052 emit one beep instead, that means the programming of the
st
1
telephone number has failed. Please
repeat the programming steps again.
nd
Likewise, the 2
rd
, 3
or 4th Tel. numbers can be programmed using Command (02), (03) or (04) respectively.
<NOTE>
When entering the phone number,
entering () means a 3-second pause. (e.g. Switchboard system, extension, etc.). For example, the phone number is 2 1111111 and extension number is 255 . Ent er: 2 1111111*255 .
Available Key-in options:
Tel. Number /
IP Address
1st Tel. #
2nd Tel. #
3rd Tel. #
th
4
Tel. #
5th GPRS1 #
6th GPRS2 #
7
Function Selection
Sequence
(1)
(2)
(3)
(4)
(5)
(6)
Page 11
1st & 2
1st & 3rd Tel. #s
1st & 4th Tel. #s
1st Tel & 5th GPRS. #s
1st Tel & 6th GPRS. #s
nd
Tel . #s
(12)
(13)
(14)
(15)
(16)
<NOTE>
The Tel. number selected in Command
#7 will not be used for alarm and/or status reporting, even if it is selected in command #5 and/or #6.
When multiple Tel. numbers are
selected, CTC-1052 will always dial in respective programmed order.
2nd & 3rd Tel. #s
2nd & 4th Tel. #s
2nd Tel & 5th GPRS. #s
2nd Tel & 6th GPRS. #s
3rd & 4th Tel. #s
3rd Tel & 5th GPRS. #s
3rd Tel & 6th GPRS. #s
4th Tel & 5th GPRS. #s
4th Tel & 6th GPRS. #s
th
5
& 6th GPRS. #s
1st, 2nd & 3rd Tel. #s
(23)
(24)
(25)
(26)
(34)
(35)
(36)
(45)
(46)
(56)
(123)
The latest Command (05-06) setting(s)
will overwrite any previously enter setting(s).
When CTC-1052 reports, GPRS has
the highest priority.
Command 10-14
Account Number Programming
Commands (10-14) are used to set the
account number for the telephone numbers used for Digital Reporting.
Command (10): Set the same account
number for all telephone numbers. and 5 & 6th GPRS. #s
Command (11-14): Set the account
numbers for the 1 for Digital Reporting respectively.
st-4th
Tel. numbers used
In (Function Selection) key in 4 or 6 or 8
digit Account Number.
th
1st, 2nd & 4th Tel. #s
1st , 3rd & 4th Tel. #s
2nd, 3rd & 4th Tel. #s
1st, 2nd, 3
1st, 2nd, 3rd, 4th Tel. & 5th GPRS. #s
1st, 2nd, 3rd, 4th Tel. 5
th
6
GPRS. #s
rd
& 4th Tel. #s
th
&
(124)
(134)
(234)
(1234)
(12345)
(123456)
Factory default is set as (123456). Alarm &
Status will be reported to all of 4 Telephone Numbers+2 GPRS (IP).
8
Page 12
Command 20-24
Reporting Method
or 0 on their phone set to reset to the original communication duration (set by Command #46).
Commands (20-24) are used to program
the Alarm reporting method for each Tel. Number.
Command (20): Program the same Alarm
Reporting Method for all 4 Tel. Numbers.
Command (21-24): Program the alarm
reporting method for the 1 Numbers respectively.
st-4th
Tel.
Available Options:
Method
Digital
Reporting
Method
Speech Method
SMS
Reporting
Method
Function
Selection
(0) Contact ID
(1) Scancom
(2) Tunstall
(3)
(4) SMS (CID)
Open Two-way
communication
(0), Contact ID, is set as factory default for
all 4 telephone Numbers.
<NOTE>
To terminate the call, press (9) or RESET BUTTON on CTC-1052.
During the Speech period, CTC-1052 will emit two beeps via the telephone handset to alert the call recipient the remaining time of 20 & 10 secs.
Speech Reporting made under Silent
Mode (set by Command #35) will automatically be switched to Listen-in, but call recipient can press DTMF keys to open two-way communication or change modes.
If any of SMS Reporting Methods is
selected:
CID sent over SMS is a backup path when alarm can’t go through in digital reporting method. Once alarm or emergency data is successfully transmitted, the CTC-1052 will automatically send out a SMS (CID) Message.
Command 31
Ringer Enable for Incoming Calls
CTC-1052 can be programmed to emit a
ring tone as an audio alert, or silent for incoming calls.
The latest Command (20-24) setting(s)
will overwrite any previously entered setting(s).
If any of Digital Reporting Methods
is selected:
Once alarm or emergency data is successfully transmitted, CTC-1052 will automatically enter specific Follow-On and/or Call Back Mode as specified by Command (38).
If Speech Method is selected:
After the dialing for alarm/emergency trigger is successful, CTC-1052 opens a two-way voice communication between the Call Recipient and CTC­1052 for 1-10 minutes (set by Command #46).
If the Call Recipient needs more talk time, they can press any keys except 9
Function Selection Result
(0) OFF (Ring Tone Disable)
(1)
(Ring Tone Enable)
ON
Factory Default is set as (0), OFF.
If the function is set to ON, you can answer
the incoming call by pressing the Active button of WTR, PB, or Fall Sensor, or the Red Help Button on CTC-1052.
The time-out period for the incoming call is
30 minutes.
To terminate the incoming call, either press
the Active button of WTR, PB, or Fall Sensor, or press the Green Reset Button on CTC-1052.
During the AC Power failure period, Ring
Tone is automatically disabled.
9
Page 13
Command 32
<NOTE>
Audible Fault Alert
CTC-1052 can be programmed to emit
Fault Alert Beeps every 30 seconds from AC Failure.
Function Selection Result
(0)
(1)
(No Warning Beep)
(With Warning Beep)
OFF
ON
Factory Default is set as (0), OFF.
Command 33
Help Arrived Signaling
This function is available for Digital reporting, SMS reporting and GPRS reporting methods.
It is used for the Monitoring Center
personnel to confirm if the help has arrived for the user or not.
This function will be activated after
successfully reported from the following situations:
Pressing the Red Help Button on
CTC-1052.
Pressing the Active button on WTR,
PB or Fall Sensor is pressed.
If the Green Reset Button is not
pressed within the period set by Command 67 (Help Arrived Timer), CTC-1052 will send the alarm report to summon help again and inform the Monitoring Center that no help has arrived within the period set by the Help Arrived Timer.
Command 33 (Help Arrived Signaling)
has to be set as ON for Command 67 (Help Arrived Timer) to be activated.
If help has not arrived after sending the
alarm report for 4 times, CTC-1052 will dial the telephone number set by Command 75 and open two-way communication when the call is answered.
Command 34
Emergency Button Enable
The Red Help Button can be enabled or
disabled to send an Emergency alarm report:
Function Selection Result
OFF
(0)
(Disable)
A fall detection.
If Help Arrived Signaling is set to ON, once
the Alarm Reporting is completed, the Red Help Button will start to flash as the panel
enters Help Arrived Mode.
If Help Arrived Signaling is set to OFF,
CTC-1052 will return to idle mode when Alarm Reporting is completed.
Function Selection Result
OFF
(0)
(Disable)
ON
(1)
(Enable)
Factory Default is set as (0), OFF.
(1)
ON
(Enable)
Factory Default is set as (1), ON.
OFF: Pressing the Red Help Button is
unable to send an emergency alarm.
ON: Pressing the Red Help Button will
activate the panel send an emergency alarm.
10
Page 14
Command 35
Command 38
Silent Mode
CTC-1052 can be selected to operate in
Silent Mode. This will mute all normal operation warning beeps, guard time tone and key tone.
<NOTE>
Speech Reporting made under Silent
Mode will automatically be switched to Listen-in, but call recipient can press DTMF keys to open two-way communication or change modes.
If Command #31 is set as Enable,
CTC-1052 will emit ring tone for incoming calls even in silent mode.
Silent mode will not mute the long beep
emitted during walk test.
Function
Selection
(0) ON (Silent)
(1) OFF (Normal)
Result
Follow-On & Call-Back Function
The Command is available for Digital
Reporting Methods (when Command #20 ­#24 is set as (0), (1) or (2))
Function Selection Result
(0) Follow-On
(1) Call-Back
(2) Follow-On & Call-Back
Factory Default is as (0), Follow-On.
When this function is programmed as (0),
after a successful reporting to the Monitoring Center, CTC-1052 will automatically enter the Follow-On mode as specified by Command (45).
When this function is programmed as (1),
after a successful reporting to the Monitoring Center, CTC-1052 will automatically hang up the line and start a 5­minute waiting period to auto answer any incoming phone calls from the Monitoring
Center.
Factory Default is set as (1), OFF.
Command 37
AC Fault Report
The CTC-1052 can be programmed to send
a Fault Report when an AC power failure is detected.
Function Selection Result
(0)
(Send No Report)
(1)
OFF
ON
(Send Report)
Factory Default is set as (1), ON.
<NOTE>
Reporting will only be made after
detecting AC Fault condition
continuously for one hour.
When this function is programmed as (2),
after a successful reporting to the Monitoring Center, CTC-1052 will automatically enter the Follow-On mode as
specified by Command (45).
Once Follow-On Mode is terminated, CTC­1052 will automatically start a 5-minute waiting period to auto answer any incoming
phone calls from the Monitoring Center.
When the Monitoring Center calls back
within the 5-minute period (when call back function is enabled), CTC-1052 will auto­answer the call after the 1st-2nd ring and waits for Access Code (default is 1111) and the (#) key entry within 15 seconds.
When the correct Access Code is received, CTC-1052 will then open a Full-Duplex Communication to allow the Call Recipient to speak to CTC-1052 directly.
You can use DTMF command to switch the communicating method. Please refer to
section 4.2. Alarm Activation.
<NOTE>
The Access Code must be entered
11
Page 15
within 15 seconds. Otherwise, CTC­1052 will disconnect the call automatically.
Command 42
Guard Time Delay
To terminate the call, press DTMF (9),
(0) or Green Reset Button on CTC-
1052.
If the 5-minute waiting period is up,
CTC-1052 will automatically exit this waiting mode and return to idle mode.
Command 40
Set Access Code
The Access Code is used to enter Programming Menu (locally or remotely), and the Call-Back Function.
It consists of 4 digits and has been set to (1111) as factory default. Before you set your own Access Code, (1111) must be keyed in.
To set a new Access code; enter the desired (4-digit number) in Function Selection.
This command is designed for any compatible sensor, except Fall Sensor (fall detection).
Guard Time Delay time is a time period programmed to delay alarm reporting. If a false alarm is raised, it can be cancelled within this Guard Time Delay time.
The programmable delay time range from (00) (instant reporting) to (99) seconds.
Emergency alarms activated by Smoke Detectors (SD), Carbon Monoxide Detectors (CO), and Water Sensors (WS) do not have Guard Time Delay and will be reported immediately.
Function Selection Result
(00) INSTANT REPORTING
(01) - (99) DELAY
Factory Default is (10), 10 SECONDS.
Command 41
Auto Answer for Remote Programming
CTC-1052 can be programmed to auto answer incoming phone calls after a pre-set number of rings have been reached. The number of rings range from (00) (no auto answer) to (32) rings.
Function Selection Result
(00) OFF
(01) - (32) ON
Factory Default is (00) Rings.
<NOTE>
When (00), it means CTC-1052 cannot
auto-answer the call by ring count. If you want to do Remote programming, please follow the Remote Programming
method described in 3. System
Confguration, 3.1. Entering Programming Mode, 3.1.3 Remote Programming Mode.
Alarm activated by pressing a button cannot be cancelled after the Guard Time is elapsed.
<NOTE>
The Guard Time Delay time from
pressing the Active Button on a Fall sensor is determined by Command #42 instead of Command #66.
The Guard Time Delay from a fall
detection (of a Fall Sensor) is set by Command #66.
12
Page 16
Command 43
<NOTE>
Periodic Test Call
CTC-1052 can be programmed to make test
calls periodically from (00) (no test call) to every (1) - (7) or 30 days:
Function Selection Result
(0) OFF
(1) - (7) 1 - 7 DAYS
(8) 30 DAYS
Factory Default is set as (0), OFF.
<NOTE>
Whenever programming mode is
accessed, CTC-1052 will reset the Periodic Test Call timer.
Periodic Test Call will only function with
telephone numbers assigned to Digital or SMS reporting method in Command 20-24.
The Mobility Timer counting down can
be reset by:
1. Pressing the Green Reset Button on CTC-1052, or,
2. Movement detected by PIR Detector
3. Only workable by entering 2 digits.
When Mobility Timer expires and no
reset signal is received, CTC-1052 starts to emit one long beep every 5 minutes to alert the user. (You can enable or disable long beep sound, see Command 78 for details).After 30 minutes, if reset signal is not received, a mobility alarm reporting will be made.
The reporting method for mobility alarm
is the same as the emergency alarm. The report will be sent based on your reporting methods without guard time waiting.
When (00) is selected, no code is sent
to Monitoring Center.
Command 44
Mobility Timer
This function monitors user movement around the premises and sends an inactivity report to the Monitoring Center if the user fails to reset the inactivity timer.
This will disable or enable the Inactivity
Timer with selectable count down periods. Options are:
Function Selection Result
(00) DISABLE
(01) 1HR
(02) 2HR
..........
.........
When CTC-1052 is in idle mode, press
and hold the Green Reset Button for 16 seconds, until you hear a long beep. Release the button and the Mobility function will be disabled.
(36) 36HR
Factory Default is set as (00), DISABLE.
13
Page 17
Command 45
Command 46
Follow-On Mode Choice
This Command is only available for Digital
reporting with Command #38 set as (0) or (2).
It is used to select the Follow-On Choice for
CTC-1052 after it has made a report to the Monitoring Center.
After reporting, CTC-1052 can wait for
further commands, or enter a Two-Way Full Duplex Communication, or Listen-In Half Duplex Communication immediately according to the setting selection:
Function Selection Result
(0) WAIT COMMAND
(1) LISTEN
(2) TWO WAY
Factory Default is set as (2), TWO WAY.
When (0) is selected, after CTC-1052 has
made a report to the Monitoring Center, it will wait for 1-10 minutes (set by Cammand
46), and then follows the DTMF commands that are received from the Central Monitoring Station for action.
Follow-On Mode & Two-Way Period
This command is used to program the
allowable time duration for Follow-On mode choice (Command #45) & Two-way voice communication period (Speech mode). It can be set from (01) (1 minute) - (10) (10 minutes).
Function Selection Result
(01) 1 MINUTE
(02) 2 MINUTES
(03)-(10) 3-10 MINUTES
Factory default is set as (05), 5 minutes.
The allowable time duration for either Wait
Command, Two-way, Listen-In Only or Two-way voice comminucation in Speech mode is 5 minutes. During the 5-
minute period, CTC-1052 will emit two beeps via the telephone handset to alert the call recipient the remaining time of 20 & 10 seconds. Press any DTMF key except the hang up key to reset the communication time to its preset duration.
If no command is received after the waiting period, the system will automatically return to Idle mode.
When (1) is selected, after CTC-1052 has
made a report to the Monitoring Center, it will automatically enter Listen-In Half Duplex for 1-10 minutes (set by Command
46) allowing the Monitoring Center Personnel to listen in to what is happening on the other side.
When (2) is selected, after CTC-1052 has
made a report to the Monitoring Center, it will immediately enter a Two-way Full- duplex Communication mode for 1-10 minutes (set by Command#46), that gives the user the ability to speak directly with the Monitoring Center Personnel.
<NOTE>
If either Scancom or Tunstall reporting
format is selected, CTC-1052 will ignore Command#45 selections. It will always open a Two-way voice for Follow-On choice.
Command 47
Off-Set Time
After the Control Panel‘s power is supplied,
the time of the Check-in Report starts calculating.
According to the setting of Off-Set Time, the
Control Panel will send Check-in Report once, and then send report according to the setting of Command 43 Test call.
Function
Selection
(1) 1 Hour
(2) 2 Hour
(3) 3 Hour (4)
(5)
(6) 12Hour
Result
4 Hour
8 Hour
14
Page 18
Factory default is set as (1) 1 Hour. When
the Off-Set Time is reset in programming Mode, the time of the Off-Set period will recalculate.
Off-Set time Report will be sent only once,
and then the Control Panel sends Check-in Report according to setting of period test call, unless the Control Panel restarts or the Off-Set time is reset.
Command 61
Check SIM Card PIN Code
This option is used to check SIM card PIN
Code.
Function Selection Result
(0) OFF (Disable)
<NOTE>
Whenever programming mode is
accessed, CTC-1052 will reset the Off­Set timer.
Command 49
Supervision
This function is not available for the digital Scancom reporting method.
This option is used to enable system
Supervision function. Once enabled, CTC­1052 will be able to receive the check-in signals from Wrist Pendants (WTR) to indicate their proper functioning.
Function
Selection
(0) Disable
(1) 4 Days
(2) 5 Days
(3) 6 Days (4)
(5)
(6) 9 Days
(7) 10 Days
Factory default is set as (0) Disable. No
code is sent to Monitoring Center.
When the supervisory timer expires and no
supervision signal is received from WTR , CTC-1052 will send a Supervisory Failure report.
Supervisory Failure is a status report.
Result
7 Days
8 Days
(1) ON (Enable)
Factory default is set as (0) OFF.
<NOTE>
If this function is disabled, the system
will not check the entered SIM Card PIN Code set by Command 62.
If the SIM card PIN Code is entered, be
sure to enable this function.Otherwise, the SIM card will be locked.
Command 62
Input SIM Card PIN Code
This function is used to input SIM card PIN
Code to access the mobile service.
Program the panel to input SIM card PIN
code by entering a 4-8 digit SIM card PIN code.
Factory default is set as (Null).
Command 62 is functional only when the
SIM card PIN code is activated and when Command 61 is enabled.
When the SIM card requires the PIN code to
access the mobile service, please make sure Command 61 is set as ON, enabled, and that the PIN code set by Command 62 is exactly the same as the SIM card PIN code.
If the SIM card PIN code is not required,
CTC-1052 can receive calls normally regardless of the settings of Commands 61 and 62.
Please set the SIM card PIN code correctly
before putting in another SIM card to prevent locking the SIM card.
Follow the steps below to changing a SIM card without locking:
Step 1. Enter local programming mode (SIM
15
Page 19
card module is disabled during this time).
Step 2. Remove the old SIM card and insert
a new SIM card.
Example: if you want to raise the speaker
volume to level 5 in the Two Way mode, please enter: 2*5
<NOTE>
Please DO NOT remove the SIM
card except when the Control Panel is turned off or is in local programming mode to prevent errors or malfunctions.
Step 3. Setup the new SIM card PIN code
using Command 62.
Step 4. Exit local programming mode. The
SIM card module will start up and attempts to activate the SIM card by entering the SIM card PIN code.
<NOTE>
This function is not used to change the
SIM card PIN code. If you want to change your SIM card PIN code, please use a mobile phone to change it.
If the SIM card is locked, please contact
your local telecommunications service provider.
Command 63
Speaker Volume Adjustment
This function is used to adjust speaker
volume. To set speaker volume in different communication channels, please set different parameters.
Function Selection Result
(2) Two-way
To set speaker volume in two-way modes,
the sequence is:
Communication
Channel
DTMF Speaker Volume
The volume value in the Listen In or Talk-
Only mode is adjusted for the best communication quality. It is fixed and can not be changed.
Echo volume varies depending on
adjustment of speaker volume and microphone sensitivity. To minimize the impact of echo, if you raise speaker volume, please be sure to lower microphone sensitivity, and vice versa.
Command 64
Microphone Sensitivity Adjustment
This function is used to adjust microphone
sensitivity. The microphone sensibility only can be adjusted in the two-way mode.
To set the microphone sensitivity with a
number, ranging 1 to 5. This value represents the received sound source range. The higher the value, the wider range of sound source. Factory default is set as (3).
Please refer to programming command table
section for configuration.
<NOTE>
The sensitivity level in the Listen In or
Talk-Only mode is adjusted for the best communication quality. It is fixed and can not be changed.
Echo volume varies depending on
adjustment of speaker volume and microphone sensitivity. To minimize the impact of echo, if you raise speaker volume, please be sure to lower microphone sensitivity, and vice versa.
2 * 1 to 5
* Communication Channel: 1 digit ( 2: Two-way)
* Be sure to put * between communication channel value
and speaker volume value.
To set the speaker volume with a number,
ranging 1 to 5. The higher the value, the louder the voice. Factory default is set as (3) for Two-Way mode.
Please refer to programming command
table section for configuration.
Command 66
Set Guard Time Delay Time for Fall Sensor
This command is used to set the Guard
Time Delay time for fall sensor.
CTC-1052 can be programmed to delay
alarm reporting triggered by a fall detection from (00) (instant reporting) to (99) seconds.
16
Page 20
During this time period, a continuous series
(1 beep every 0.5 second) of beeps will be emitted to alert user.
If a false alarm is triggered by a fall
detection, it can be cancelled within the Guard Time Delay by pressing the Active
Button of the Fall Sensor for 4 seconds.
Function Selection Result
(00) INSTANT REPORTING
enter (telephone number) followed by (#).
If the number is successfully programmed, the telephone handset will emit one short beep.
If the number is unable to be programmed, the Control Panel will emit one long beep.
Auto-Answer Number 2 can be programmed
using the same method, except command (71) is replaced by (72).
<NOTE>
(01) - (99) DELAY
Factory Default is (15), 15 SECONDS.
<NOTE>
This command is used if a fall is
detected.
If an emergency alarm is triggered by
pressing the Active Button on Fall sensor, the guard time delay time is determined by Command 42.
Command 67
Setting the Help Arrived Timer
This command is used to set the countdown
timer for CTC-1052 to resend the alarm report if no help has arrived after the initial report is made (meaning the reset button has not been pressed before the timer expires).
Function Selection Result
(01)-(15) 1-15 MINUTES
Up to 20 digits including () are
allowed for each telephone number.
Delete Telephone Number
To delete Auto-Answer Number 1, enter (71)
followed by (#), after one short beep, enter another (#).
If the number is successfully deleted, the telephone handset will emit one short beep.
If the number is unable to be deleted, the Control Panel will emit one long beep.
Auto-Answer Number 2 can be erased using
the same method, except command (71) is replaced by (72).
Command 75
Help Not Arrived Call
If help has not arrived after sending the
alarm report for 4 times, CTC-1052 will dial the telephone number programmed by Command 75 and open two-way communication when the call is answered.
Enter a telephone number followed by (#)
to program the telephone number.
 Factory default is (15), 15 MINUTES.
<NOTE>
The Help Arrived function (Command 33)
must be set as ON for this function to work.
Command 71-72
Auto-Answer Numbers #1 & #2
Used to program the 1
Numbers 1 and 2 respectively.
To program Auto-Answer Number 1: enter
(71) followed by (#). After one short beep,
st
& 2nd Auto-Answer
<NOTE>
When you program the phone number,
entering () will cause a 3-second pause is for a switchboard system, extension, etc.
The telephone number can contain up
to 20 digits, including ().
The Help Arrived function (Command
33) must be set as ON for this function to work.
CTC-1052 only dials this telephone
number once. If this phone call fails, CTC-1052 will not try again.
17
Page 21
Command 76
Command 78
Call Progress Tone
This command is used to turn on/off the
dialing tone of phone calls while making alarm reporting.
Function Selection Result
(0)
(1) ON
OFF
(Disable)
<NOTE>
When this function is set to ON, you will
hear a dialing tone from the speaker indicating the status of phone calls.
When this function is set to OFF, you
will not hear the dialing tone of phone calls.
This function will be disabled if
Command 35 is set as Enable.
This function will be disabled if alarm
activation is made from a Silent Device (learnt using Command #93).
Factory default is (0), OFF.
Mobility Time Out Warning
When Mobility Time expires and no reset
signal is received, CTC-1052 will emit a long beep every 5 minutes in 30 minutes. This warning can be enabled or disabled.
Factory default is (1), Enable.
Function Selection Result
(0) Disable
(1) Enable
Command 80
Remove Devices
CTC-1052 can be programmed to remove
ALL previously learnt devices by entering
(80) followed by ().
After entering command (80) (), the system will immediately emit an
acknowledging beep over the phone. Continue to hold the phone set until you hear the second acknowledging beep after 12 seconds.
Command 77
Speech Report ACK
A two-way communication is established
when a call is made from CTC-1052 to the Monitoring Center by sending out a speech report.
When speech report is set to (0), press any
DTMF key for panel to regard speech reporting
successful.
When speech reporting is set to (1), off-hook
phone for panel to regard speech reporting successful.
Factory default is (0), Any DTMF.
Function Selection Result
(0) Any DTMF
(1) OFF-HOOK
Command 93
Learn-In Silent Pendant
<NOTE>
This command is not available in
Remote Programming Mode.
Only one Silent Pendant can be learnt into
CTC-1052 by using Command #93.
For learning Silent Pendant:
Step 1: Enter 93 + # on the phone set, then
a short beep will be heard via the phone set. (If no command is dialed, CTC-1052 will exit Programming mode automatically and return to idle mode).
Step 2: Press the Pendant Button within 20
seconds.
Learning can only be completed
within the signal reception range of CTC-1052.
18
Page 22
If no signal is received within 20
sec, CTC-1052 will emit a long beep and automatically returns to Programming mode.
Step 3: CTC-1052 will emit 2 beeps to
indicate that Silent Pendant is learnt­in successfully.
Adding a Pendant for a second time
is prohibited unless it is removed from the system first.
If one long beep is emitted instead
of 2 beeps, it indicates:
The device has already been
learnt-in.
Another device has been learnt-in
before.
<NOTE>
When CTC-1052 received the alarm
signal from the Silent Pendant, it will not emit any warning beeps during Reporting and Guard time period.
within 20 seconds.
Learning can only be completed
within the signal reception range of CTC-1052.
If no signal is received within 20
sec, CTC-1052 will emit a long beep and automatically returns to Programming mode.
Step 3: CTC-1052 will emit 2 beeps to
indicate the device is learnt-in successfully.
Adding a Pendant for a second time
is prohibited unless it is removed from the system first.
If one long beep is emitted instead
of 2 beeps, it indicates:
The device has already been
learnt-in.
th
When an 8
to learn-in.
device is attempted
Command 94
Learn-In Device
<NOTE>
This command is not available in
Remote Programming Mode.
Up to 17 devices can be learnt into CTC-
1052 by using Command #94.
The available devices that can be learnt-in
Command #94 are:
PIR Sensor ----- PIR  Smoke Detector ---- SD  Carbon Monoxide ---- CO  Fixed Panic Button ---- PB  Wrist Transmitter ---- WTR  Pendant Transmitter ---- WTR  Water Sensor ---- WS  Fall Sensor
Step 1: Enter 94 + # on the phone set, then
a short beep will be heard via the phone set. (If no command is dialed, CTC-1052 will exit Programming mode automatically and return to idle mode).
Step 4: Repeat steps 1-3 until all devices
are learnt-in.
<NOTE>
Adding a device for a second time is
prohibited unless it is removed from the system first.
If the Follow on or Call Back function
is set by Command 38, the Control Panel will follow the preset parameter to open the two-way communication.
Step 2: Press the learn button on the device
19
Page 23
Command 98
3.3. SMS Remote
Factory Default Reset
To Reset CTC-1052 to factory default
settings, enter (98) and then (#).
After one short beep, continue by entering
() and then end with another (#), one beep will be heard for termination.
Once the Factory Default Reset is
executed, all the programmed data is returned to its default value and all the devices that have been learnt-in are removed. You have to do the programming and learn-in the device one by one again.
Command 99
Exit Programming Mode
Enter (99) and (#), after one short beep,
CTC-1052 exits the Programming Mode and returns to idle mode.
Programming
<NOTE>
Prior to procced, please be reminded to
change the language setting of your mobile phone to English.
Step 1: Use your handset and go into the SMS
edit screen.
Step 2: Enter the SMS keyword (default is
PROG).
Step 3: Enter a space.
Step 4: Enter the access code (default is 1111
as defined by Command 40).
Step 5: Enter a space.
Step 6: Enter the programming command.
Step 7: Editing is complete; you may send to the
Control Panel.
<EXAMPLE>
E.g. PROG_1111_TEL1:0227940001
PROG
SMS Keyword
__
Space
1111
Access Code
__
Space
TEL1
Telephone number 1
Colon
0227940001
<NOTE>
For a complete list of SMS commands,
please refer to section 5.5. CTC-1052
SMS Remote Programming Command Table.
Programming data/option
20
Page 24
4. Operation
4.1. Idle Mode
When the system is in Idle Mode, CTC-1052 is ready to execute the following functions:
4.1.1. Answering Incoming Phone Calls
This function is only available when Command #31 is set as ON (factory default is OFF).
For an Incoming telephone call, CTC-1052
will emit cycles of 2 quick beeps.
User can answer the call either by pressing
the Active button of WTR, PB, or Fall Sensor or the Red Help Button on CTC-
1052. Once CTC-1052 answers the call, it will open a Two-Way Voice Communication. The Red Help Button illuminates.
You can use the following DTMF
commands to change the communication type:
DTMF (1) to TALK ONLY Enter DTMF (2) to open TWO-WAY
VOICE COMMUNICATION Enter DTMF (3) to LISTEN-IN ONLY
Enter (7) to Speaker Volume Control
and then press (6) or (4) to increase or decrease the levels of speaker volume in the “Two-Way” communication mode(not in TALK ONLY mode).
Enter (8) to Microphone Sensitivity
Control and then press (6) or (4) to increase or decrease the levels of microphone sensitivity in the “Two­Way” communication mode.
If the speaker volume and microphone
sensitivity was adjusted, the adjusted value will be kept for the next communication.
To hang-up, press either the Active
button of WTR, PB, or Fall Sensor, or
the Green Reset Button on CTC-
1052.
To hang-up as the caller, he/she can
press DTMF 9 or just put the handset back into the base cradle.
30 minutes is allowed for each call.
Auto-Answer Numbers
The Control Panel can program up to 2 Auto­Answer Numbers. If a user calls the Control Panel using an auto-answer number, the Control Panel will pick up the call and instantly open up a two-way communication with the caller.
The Control Panel will auto-answer calls from the auto-answer numbers and are unaffected by Command #31. Please refer to Command #71 &
#72 or the SMS Programming table (5.5. SMS Remote Programming Command Table) on
how to program these numbers.
4.1.2. AC Power Check Up
If the AC Power failure is detected for 10
seconds or longer, the GREEN LED starts to flash as a visual warning to the user and voice prompt “Power failure, check power cord.” 3G/LTE/3G/LTE module will be turned off to conserve power. Remote Programming will thus become unavailable. 3G/LTE/3G/LTE module will only be turned on when activated from the Control Panel side.
When AC Power resumes, the GREEN
LED will turn on again, and will voice prompt “Power restored.”
If the AC Power failure lasts for an hour,
CTC-1052 will send an AC Failure report to the Monitoring Center.
After the Power restoration lasts more than
one hour, CTC-1052 will report AC Restore to the Monitoring Center.
During the AC Power failure period, the
Call-Back function are automatically disabled.
4.1.3. CTC-1052 Low Battery
CTC-1052 continuously checks its own
Battery Condition 30 minutes after powering up.
When the low battery condition lasts for 4 -
6 mins, CTC-1052 will report to the
Monitoring Center and the GREEN LED flashes slowly.
After the battery voltage is restored and
lasts for 12 hours, CTC-1052 will send Battery Restore report to Monitoring Center and the GREEN LED returns to steady ON.
21
Page 25
4.1.4. CTC-1052 Battery Disconnection
CTC-1052 can detect the absence of
battery in the following cases:
Battery switch OFF
Battery not connected
Battery failure.
When the battery disconnection lasts for
10-15 minutes, CTC-1052 will report to the Monitoring Center and the GREEN LED flashes slowly.
After the battery is restored for 10-15min,
CTC-1052 will send Battery Restore report to Monitoring Center and the GREEN LED returns to steady ON.
4.1.5. Devices Low Battery
When CTC-1052 receives a battery low
signal from a particular device, it will report to the Monitoring Center and the GREEN LED will flash rapidly until the fault condition is cleared.
Press the Green Reset Button on CTC-
1052, the LED will turn on.
If any device Low Battery signal is received
again, the LED will light up accordingly. Press the Green Reset Button again, the LED will turn on.
After the faulty battery is replaced, CTC-
1052 will immediately send Battery Restore report to the Monitoring Center for that particular device.
4.1.6. Automatic Check-in Report = Periodic Test Call
When CTC-1052 is programmed to send a
periodical check-in report, CTC-1052 will report to the Monitoring Center accordingly.
The Periodic-Check-in Timer will be reset
whenever Programming Mode is entered.
Immediately after powering up CTC-
1052
Exit Programming Mode
After the pre-set Timer expires, CTC-1052
will emit a long beep and voice prompt reminder “Inactivity timer expiring, please reset.” at every 5 minutes to notify the user
for 30 minutes. (You can enable or disable
the long beep sound, see Command 78 for details).
When the Mobility timer is not reset after 30
minutes, CTC-1052 will send a Mobility Timer Expired report to the Monitoring Center.
After CTC-1052 sends a Mobility Timer
Expired Report, but the Mobility timer still
not be reset, when reaching next pre-set time, the CTC-1052 will emit a beep at every 5 minutes to notify the user for 30 minutes. Yet, if no reset action after 30 minutes, the panel will send another Mobility Timer Expired report to the Monitoring center and the step will repeatedly until Mobility timer is reset.
Mobility Timer can be reset by pressing
RESET button once on CTC-1052 or whenever a movement is detected by PIR Detector. CTC-1052 will also play a voice prompt “Inactivity timer reset.” to inform the user.
To disable the Mobility Timer function:
Set Command #44 to 00 (Disable), or,
Press and hold the RESET button on
CTC-1052 for 16 seconds or longer.
<NOTE>
If no movement is detected during preset
mobility time, CTC-1052 will send a CID event code 641 with a fixed zone number 071 regardless of the zones the triggered motion detectors occupy.
Disable the Mobility function in idle
mode:
4.1.7. Mobility Timer
In order to check the user’s well being, a
Mobility Timer can be set by using Command #44.
If Mobility Timer is set as Enable, a
counting down period starts from:
Step 1: When the system is in Idle Mode, press
& hold the Reset Button for 16 seconds.
Step 2: During the 16-sec period, CTC-1052 will
emit one short beep a double beep
continuous three short beeps a long beep.
22
Page 26
Step 3: Release the Reset Button when you
hear the last long beep; a short beep will sound to indicate the mobility function is disabled.
<NOTE>
0 = number to substitute
After this is completed, Country Code “886”
will be replaced by “0”.
Please use Command #44 to enable the
Mobility timer again.
4.1.8. Country Code
The Phone Number Format for each SIM card may vary between different Telecom companies. Thus, you can either check with your Telecom provider or follow the steps described below to check the correct format.
Step 1: Remove the SIM card from SIM card
holder on the Panel, and insert it into a workable mobile phone.
Step 2: Power on the mobile phone and send
a test SMS message to another mobile telephone number.
Step 3: Once the test message is received,
you can then check the phone number format shown in the received message.
<EXAMPLE>
With the phone number 0987654321, the format should either INCLUDE or EXCLUDE Contry Code, which is “886” for Taiwan as below:
INCLUDE Country Code
EXCLUDE
Country Code
Step 4. Remove the SIM card from the Mobile
phone and insert it back into SIM Card holder on Panel.
A. If the Phone Number Format EXCLUDES
Country Code, please skip this section.
B. If the Phone Number Format INCLUDES
Country Code, please proceed to SMS Remote Program and send in this format:
“PROG 1111 REPLA:886&0”
Where:
PROG = SMS Keyword
+886987654321
0987654321
1111 = Access Code
REPLA = SMS command for Country Code
886 = number to be replaced
23
Page 27
4.2. Alarm Activation
When an alarm is triggered, CTC-1052 will
enter the Guard Time Delay period (see Command 42). Both Red LED and Red Help Button backlight will turn on.
During the Guard Time period,
pressing the Green Reset Button on CTC-1052 will stop alarm reporting and return to Idle Mode.
If the Guard Time Delay is set as 00,
CTC-1052 will dial immediately.
An alarm report can be canceled anytime
by pressing the Green Reset Button on CTC-1052.
Call Progress Tone
Once Guard Time Delay expires, CTC-1052
will summon help based on the programmed reporting method. If Call Progress Tone is set as On, dailing tones will be heard once the CTC-1052 goes off­hook.
call” voice prompt, when fall detection has been cancelled.
Confirmation Beeps
After Guard Time expires, CTC-1052 will
summon help based on the programmed reporting method. The Control Panel will start emitting a continuous confirmation beeping sound (about 1 beep every second) and voice prompt “Emergency call in progress” to indicate that the call is in progress.
The Control Panel will emit Confirmation
beeps and voice prompt during the following situations:
After the Control Panel dials out to
summon help and until handshake (for Digital Reporting Method).
After the Control Panel dials out to
summon help and until the call is answered (for Speech Reporting Method).
When the first reporting failed, and the
Control Panel retries.
Guard Time Delay
Guard Time Delay time is a time period
programmed to delay alarm reporting (by command #42). If a false alarm is raised, the user can cancel the alarm before the Control Panel starts reporting.
Emergency alarms activated by Smoke
Detectors (SD), Carbon Monoxide Detectors (CO) and Water Sensors (WS) do not have Guard Time Delay and will be reported immediately. CTC-1052 will play voice prompt “Fire Alarm,” “Carbon Monoxide Alarm,” “Water Leak Alarm” to inform the user of the alarm at hand.
During this time period, a continuous series
of beeps (1 beep every 0.5 second) will be emitted and voice prompt “Emergency call was pressed” to alert the user(s).
<NOTE>
The Guard Time Delay triggered from a
fall detection (of a Fall Sensor) has its own timer (programmed using Command 66). The CTC-1052 will play voice prompt “A fall has been detected,” to notify the user; and “Fall detection has restored, cancelling help
The Control Panel stops emitting
confirmation beeps once the first reporting succeeded and it is in the process of back­up reporting.
4.2.1. GPRS Reporting Method
Please program GPRS Report settings via
SMS Remote Programming Commands for GPRS Reporting Methods. Below are the settings required for GPRS reporting:
Access Point Name (APN): the name of
an access point for GPRS. Please inquire your SIM card service provider for your APN.
User Name: offered by your SIM card
service provider. Please inquire your service provider for your GPRS username. If no username is required, you may skip this step.
Password: offered by your SIM card
service provider. Please inquire your service provider for your GPRS password. If no Password is required, you may skip this step.
IP Address: Central Monitoring Station
server IP. Please refer to 5.5. CTC-1052 SMS Remote Programming Table on how
24
Page 28
to set CMS IP Address(es) (SMS Commands: TCIP1 and TCIP2).
Port Number: Central Monitoring Station
server port number. Please refer to 5.5.
CTC-1052 SMS Remote Programming Table on how to set Port Number(s) (SMS
Commands: PORT1 and PORT2).
GPRS/IP Account Number: There are 2
account numbers available for GPRS/IP
reporting. Please refer to 5.5. CTC-1052 SMS Remote Programming Table on how
to set GPRS/IP Account Number(s) (SMS Commands: IPAC1 and IPAC2).
To disable GPRS Reporting Method: by
removing the IP address, GPRS reporting becomes ineffective. Proceed to SMS Remote Programming and send in this format:
PROG 1111 TCIP1:
Where:
PROG = SMS Keyword
1111 = Access Code
TCIP1 = SMS command for IP Address (no
input value means deletion of characters)
If Command 33 is enabled, the panel will
enter Help Arrived Mode after GPRS
reporting. Please refer to Help Arrived Mode below.
4.2.2. Digital Reporting Method
If Digital Reporting Method is selected, after
dialing, the Control Panel will report digital event codes according to the format of the report (set by Commands 20-24).
If SMS CID reporting is selected, the event
codes will be sent in the form of a SMS message to the reporting destination.
Post-Digital-Alarm Operation
After a successful digital report, CTC-1052
will then follow the choice of Command #38, to enter Follow-On and/or Call-Back mode.
Call-Back Operation
If Command #38 is set as Call-Back (1) or
Follow-On & Call-Back (2) after alarm reporting, it will then wait 5 minutes for Monitoring Center Personnel to call-back after reporting.
<NOTE>
Call-back option is disabled by default.
If Auto-Answer Number is programmed:
If the Monitoring Center calls back within the 5-minute Call-Back period using an auto-answer number, the Control Panel will pick up the call and instantly open up a two­way communication with the caller.
If at least one Auto-Answer Number is programmed, the Control Panel will only answer calls from the Auto-Answer Numbers.
If no Auto-Answer Number is
programmed:
If the Monitoring Center calls back within the 5-minute Call-Back period, the Control Panel will automatically answer the call after the 1 Acc ess Code ( defa ult is 1111) and the (#) key entry within 12 seconds.
Upon receiving the correct Access Code and the (#) key, CTC-1052 will then open a Full-Duplex Communication to allow the caller to communicate directly.
During a call-back communication,
Monitoring center can use the following DTMF command to control the Control Panel:
Enter (1) to TA LK ON LY Enter (2) to open TWO-WAY VOICE
Enter (3) to LISTEN-IN ONLY End a Call: enter (9) or (0) to HANG
Enter (7) to Speaker Volume Control
Enter (8) to Microphone Sensitivity
st-2nd
rings and wait for proper
COMMUNICATION
UP or put the handset back into the
base cradle.
and then press (6) or (4) to increase or decrease levels of speaker volume in the “Two-Way” communication mode(not in TALK ONLY mode).
Control and then press (6) or (4) to increase or decrease levels of microphone sensitivity in the “Two­Way” communication mode.
25
Page 29
If the speaker volume and microphone
sensitivity was adjusted, the adjusted value will be kept for the next communication.
Press any DTMF key,
designated “hang-up” keys to reset the communication time to its preset duration. Please note that when a particular DTMF key is pressed, its designed shortcut function will be executed & the communication time will be extended at the same time.
Pressing the Green Reset Button
can also terminate the call.
The Control Panel will only allow one
call per call-back mode. Terminating a call during call-back period will therefore terminate the call-back mode.
A special conditioned call-back mode
is when both Call-Back mode and Help Arrived mode are activated. For the duration of Help Arrived mode, the Callback function is always available. The Monitoring Center can call CTC­1052 as many times as possible until Help Arrived Mode is terminated (Please refer to Help Arrived Signaling section for more details).
except the
<NOTE>
If you wish to enable a designed
shortcut function, please press the DTMF keys for over 1 second to enable the function you desire.
Follow On Operation
Enter (8) to Microphone Sensitivity
Control and then press (6) or (4) to increase or decrease the levels of microphone sensitivity in the “Two­Way” communication mode.
If the speaker volume and microphone
sensitivity was adjusted, the adjusted value will be kept for the next communication.
Press any DTMF key
designated “hang-up” keys to reset the communication time to its preset duration. Please note that when a particular DTMF key is pressed, its designed shortcut function will be executed & the communication time will be extended at the same time.
Communication can be terminated by the
following:
DTMF Commands:
Pressing the Green Reset Button.
Automatically hangs up after the
The allowable time duration for Follow-On
Period is set by Command #46 (1-10 mins).
During Two-way Voice Communication, at
20 & 10 seconds before the Follow-On period expires, CTC-1052 will emit two beeps to alert both the user and the Monitoring Center Personnel.
Contact ID: 9 or 0
Scancom: 5 or 0
Tunstall: # or 0
Follow-On Period expires.
except the
Follow-On options are only available for Digital Reporting methods.
If Command #38 is set as 0, Follow-On, or
2, Follow-On & Call-Back, it will then follow its setting as in Command #45, Follow-On Choice to open Two-way Voice, or, Listen-
In, or just waiting for commands.
During the Follow-On period, the Monitoring
Center can remotely control CTC-1052 by the DTMF commands below:
Enter (7) to Speaker Volume Control
and then press (6) or (4) to increase or decrease the levels of speaker volume in the “Two-Way” communication mode (not in TALK ONLY mode).
<NOTE>
If you wish to enable a designed
shortcut function, please press the DTMF keys for over 1 second to enable the function you desire.
The DTMF commands for different digital reporting are listed below:
1. CONTACT ID FORMAT:
Enter (1) to TA LK ON LY Enter (2) to open TWO-WAY VOICE
COMMUNICATION
Enter (3) to LISTEN-IN ONLY End a Call: enter (9) or (0) to HANG
26
Page 30
UP or just put the handset back into the base cradle.
report, retry no more, and return to idle mode.
2. SCANCOM FORMAT:
Enter (1) to LISTEN-IN ONLY Enter (2) to TA LK ONLY Enter (3) to open TWO-WAY VOICE
COMMUNICATION
End a Call: enter (5) or (0) to HANG
UP or put the handset back into the
base cradle.
Enter () to TOGGLE
3. TUNSTALL FORMAT:
Enter (C) to TA LK ON LY Enter () to LISTEN-IN ONLY
Enter (3) to open TWO-WAY VOICE
COMMUNICATION
End a Call: enter (#) or (0) to HANG
UP or put the handset back into the
base cradle.
4.2.3. Help Arrived Mode
This function is available for Digital reporting, SMS reporting and GPRS reporting methods, and when Help Arrive Signaling (Command #33) is set to enable.
Help arrived mode will be activated
after Contact ID code 100, 101 or 120 is reported. CTC-1052 will start counting down the Help Arrive Timer according to the length of time set by Command 67. The Red Help Button starts flashing.
The Help Arrived Timer starts as soon
as the first CID reporting finishes (even when the Control Panel has started reporting the next report destination).
If the Green Reset Button is not
pressed before the timer expires, CTC-1052 will send the alarm report again to inform the Monitoring Center that no help has arrived.
After sending the alarm report for 4
times and that the Green Reset Button is still not pressed, CTC-1052 will dial the telephone number programmed by Command 75 and open two-way communication when the call is answered. If the call is not answered, CTC-1052 will end the
When help has arrived, the Green
Reset Button can be pressed twice quickly to send a Help Arrived Mode Canceled report to the Monitoring
Center (if the emergency is resolved and no further observation is needed). The Red Help Button will stop flashing and CTC-1052 will return to idle mode
When help has arrived, pressing the
Green Reset Button once will enable CTC-1052 to send a Nurse Present report to the Monitoring Center (if further observation / treatment is needed). The Red Help Button will continue to flash. The Help Arrived Timer will be reset and start counting down from the beginning again.
When the nurse has completed
treatment, he/she should press the Green Reset Button again to send a Nurse Finished report to the Monitoring Center. The Red Help Button will stop flashing and the Help Arrived Timer will stop counting as the system returns to idle mode
If the nurse needs more help,
he/she should press the Red
Help Button to send a Nurse Needs Help report to the
Monitoring Center to call for more help.
If the Green Reset Button is not
pressed (to send a Nurse
Finished report) after sending a Nurse Present report, CTC-
1052 will continue to resend the Nurse Present report when the Help Arrived Timer expires.
After sending the Nurse Present report for 4 times and the Reset Button was not pressed during this period, CTC-1052 will dial the telephone number programmed by Command 75. When answered, a Two-way communication is established. If the call is unanswered, CTC­1052 will stop reporting completely and return to idle mode.
Green
27
Page 31
If both Call-Back mode and Help
Arrived mode are enabled, for the duration of Help Arrived mode, call­back mode is always on and the Callback function is always available. The Monitoring Center can call CTC­1052 as many times as possible until Help Arrived Mode is terminated.
Calls established in help arrived mode
can be terminated by pressing DTMF 9 or 0 on the caller handset or pressing the Green Reset Button on the Control Panel.
The Help Arrived Timer is paused
during Call-Back communications.
The control panel will still remain in
help arrived mode (and call-back mode) after the call and until Help Arrived Mode is terminated.
4.2.4. Speech Reporting Method
If Speech Reporting Method is selected,
after dialing, CTC-1052 will open a two-way voice communication between the Call Recipient and CTC-1052 for 1-10 minutes (set by Command #46).
At 20 & 10 seconds before the time period
expires, CTC-1052 will emit two beeps via the telephone handset to alert the user.
If the Call Recipient needs more talk time,
they can press any keys except 9 or 0 on their phone set to reset the communication time to its preset duration.
The Monitoring Center can remotely control
CTC-1052 by the DTMF commands below:
Enter (1) to TA LK ON LY Enter (2) to open TWO-WAY VOICE
COMMUNICATION
Enter (3) to LISTEN-IN ONLY Enter (9) or (0) to end the call Enter (7) to Speaker Volume Control
and then press (6) or (4) to increase or decrease levels of speaker volume in the “Two-Way” communication mode (not in TALK ONLY mode).
Enter (8) to Microphone Sensitivity
Control and then press (6) or (4) to increase or decrease levels of microphone sensitivity in the “Two­Way” communication mode.
<NOTE>
Speech Reporting made under Silent
Mode or using a Silent Device will automatically be switched to Listen-in, but the call recipient can press DTMF keys (as listed above) to change modes.
If Speech Reporting is set to 0, press any
DTMF key, for panel to regard the report successful.
If Speech Reporting is set to 1, off-hook
phone for panel to regard reporting successful.
If the report was unsuccessful, the Control
Panel will keep on dialing the CMS number conditioned by Retry Method described below.
4.2.5. Report Sequence
There are 6 reporting destinations available
and the Control Panel will report sequentially according to the following report sequence: GPRS #1, GPRS #2, Te l. #1, Tel. #2, Tel. #3 to Tel. #4.
4 reporting methods are available: GPRS,
Digital (that includes CID, Scancom, Tunstall), SMS CID and Speech Reporting.
Report and Retry
When the panel is reporting, the Red LED
will stay turned on while the Red Help Button backlight dims.
If an emergency event occurs while the
system is going through a status report call sequence, the system will immediately pause the status report sequence, and start the emergency report sequence. The paused status report sequence will start reporting again when the emergency report(s) is completed. Any other status events happened before the emergency event will also wait until emergency report is completed.
Emergency Report:
If GPRS reporting, Digital Alarm reporting, SMS CID reporting and Speech Reporting methods are set, the Control Panel will report according to the following rules:
1. Control Panel will retry one report destination for a maximum of 5 times.
28
Page 32
2. Control Panel will retry all report destinations up to 15 times in total.
3. If more than 1 report destinations are set to a report method (e.g. Digital), the panel will consider the report method to be successful if reporting to one of the destinations succeeds. Control Panel will completely stop reporting to this report method after receiving a successful report.
4. If any report method fails after the total of 15 retries, the Control Panel will pause for 10 minutes before restart reporting. Only failed report method(s) will be retried
During the 10-minute pause, CTC-1052 returns to normal mode with Red LED on:
Press the Green Reset Button to
terminate the reporting.
If new event happens, CTC-1052
starts the reporting immediately.
5. The control panel will not stop reporting until receiving at least 1 successful report from each report methods
Examples:
4.3 Walk Test (Range Test)
Walk Test, or Range test, is a test to check whether learned-in devices are within signal range.
You can conduct Walk Test in CTC-1052 under 3 different modes as listed below.
4.3.1. In Learning Mode
Learning Mode is applicable to all devices.
Step 1. From Idle Mode, press and hold the
Green Reset Button of the CTC-1052. When pressed, the CTC-1052 will emit one beep sound initially, and then will emit a double beep on the 6
Step 2. Release the Green Reset Button at the
voice prompt “Release the Green button, Ready to learn sensor.” CTC­1052 is now in learning mode and the Red LED will start flashing.
Step 3. Move the device to your desirable
location in the house, and press the Learn/Test button of the device to observe the range of its operation.
th
second.
Example 1: If one destination is set, the panel will report as shown below:
1 > 1 > 1 > 1 > 1 > Wait 10 minutes and restart reporting
Example 2: If two destinations are set, the panel will report as shown below:
1 > 2 > 1 > 2 > 1 > 2 > 1 > 2 > 1 > 2 > Wait 10 minutes and restart reporting
Example 3: If six destinations are set, the panel will report as shown below:
1 > 2 > 3 > 4 > 5 > 6 > 1 > 2 > 3 > 4 > 5 > 6 > 1 > 2 > 3 > Wait 10 minutes and restart reporting
Example 4: If destinations 1 and 2 utilize digital report method while destination 3 utilizes speech report method:
1 > 2 > 3 > 1 > 2 > 3 > 1 success > 3 > 3 > 3 > End of report
Status Report
Step 4. If CTC-1052 responds with one long
beep, then the particular device is
within the operation range.
Step 5. To exit Learning Mode, press both
RESET and HELP buttons at the same
time. Otherwise, CTC-1052 will exit Learning mode automatically after 5 minutes of inactivity.
4.3.2. In Walk Test Mode
Walk Test Mode is only applicable to Smoke Detector (SD), Carbon Monoxide Detector (CO), Motion Sensor (IR), and Water Sensor (WS).
Step 1. Upon exiting Learning Mode, CTC-
1052 will automatically enter Walk Test Mode for the devices mentioned above (SD, CO, IR, WS).
Step 2. Move the device to your desirable
location in the house, and press the TEST button to observe the range of its operation.
Status report will report according to the rules described in Emergency Report, except that there will only be a maximum of 15 retries regardless of whether the reports were successful or not.
Step 3. If CTC-1052 responds with one long
beep, then the particular device is
within the operation range.
Step 4. CTC-1052 will automatically exit Walk
Test Mode after 3 minutes.
29
Page 33
4.3.3. In Idle Mode
4.4 Global Test
Idle Mode is only applicable to Smoke Detector (SD), Carbon Monoxide Detector (CO), Motion Sensor (IR), and Water Sensor (WS).
Step 1. Press the Test button of the devices
mentioned above (SD, CO, IR, WS), and a signal will be sent to CTC-1052 indicating it is ready to conduct Walk Test.
Step 2. Within 30 seconds, Move the device to
your desirable location in the house, and press its TEST button again to observe the range for its operation.
Step 3. If CTC-1052 responds with one long
beep, then the particular device is
within the operation range.
Step 4. Please wait for at least 30 seconds
before conducting Walk Test for another device under Idle Mode.
Global Test is used to test if the complete
system is working properly.
To do the Global Test:
Step 1. Press the Green Reset Button
once.
Step 2. Within 5 seconds, press Pendant
button.
Step 3. CTC-1052 will emit a short beep
and report to Monitoring Center.
4.5 Factory Reset
CTC-1052 will clear all programmed parameters by the following sequence:
Step 1. Unplug the power cord from the DC
Jack.
Step 2. Slide the Battery Switch to OFF
position (or the opposite direction of the ON marking).
Step 3. Plug the power cord into the DC jack
while holding down both the HELP & RESET buttons, until one long beep is heard, indicating that the Factory Reset is successful.
Step 4. Release both buttons.
Step 5. Unplug and replug the power cord. The
Control Panel will emit 2 beeps.
Step 6. Slide the Battery Switch back to ON
position again.
<NOTE>
Once the Factory Reset is executed, all
the programmed data is returned to its default value and all the devices that have been learnt-in are removed. You will have to do the programming and learn-in the devices one-by-one again.
30
Page 34
5. Appendix
5.1. CID Event Code
111 - Smoke emergency
When the Smoke Detector (SD) is
triggered.
The message composition for CID Event code is in the form:
ACCT MT QXYZ GG C
And is explained in the following table:
Where
ACCT
MT
Q
XYZ
GG
C1C2C3 = 1. For devices: area + zone
= 4 Digit Account number (0-9)
= Message Type, 18H.
= Event qualifier, which gives specific
event information:
= Event code (3 Hex digits 0-9, B-F)
= Group or Partition number (00H)
C
= Area number
1
0=Area 1,1= Area 2
C2C3 = Zone number
001 Area 1, Zone 1
002 Area 1, Zone 2
…………………..
080 Area 1, Zone 80
1C2C3
When the Test Button of the Smoke
Detector (SD) is pressed.
120 - Fall emergency
When Fall Sensor is triggered
147 - Sensor Supervisory Failure
When CTC-1052 is unable to receive
the signal transmitted from the Wrist Transmitter for a pre-set period by Command #49, the Green LED flashes every 2 seconds.
154 - Water emergency
When Water Sensor (WS) is triggered
162 - Carbon Monoxide emergency
When Carbon Monoxide Detector (CO)
is triggered
When the Test Button of Carbon
Monoxide Detector (CO) is pressed.
301 - Panel AC Failure
When AC power fails for more than 10
sec, the Green LED flashes every sec with a beep every 30 seconds.
302 - Panel Low battery
When CTC-1052 is under Low Battery
status, the Green LED flashes every 2 seconds.
100 - Panel emergency
When Red HELP button is pressed.
101 - Personal emergency
When the Wrist Transmitter /
Emergency Pendant (WTR) or Fall Sensor is pressed.
102 - Inactivity
If no sudden movement within 10
seconds after fall detection, an inactivity code will be sent to Central Monitoring Station.
311 - Panel Battery Disconnection
When CTC-1052 is under Battery Not
Connected status, the Green LED flashes every 2 seconds.
373 - Smoke Low Battery
When Smoke Detector is under Low
Battery Status, the Green LED flashes every 2 seconds.
380 - WTR Low Battery
When Wrist Transmitter / Emergency
Pendant (WTR) is Low on Battery, the Green LED flashes every 2 seconds.
383 - IR Tamper open
When the IR Tamper is opened.
384 - Other devices Low Battery
31
Page 35
When other devices are under Low
Battery Status, the Green LED flashes every 2 seconds
602 - Periodic test report
When CTC-1052 reports Periodic test
call to monitoring Center.
606 - Follow-On Function
When CTC-1052 receives kiss-off from
Monitoring Center for opening Speech channel.
611 - Global test
When CTC-1052 reports Global Test to
Monitoring Center.
641 - Mobility
When CTC-1052 makes Mobility Timer
Expired reporting.
<NOTE>
This event code will be sent with a fixed
zone number of 071
661 - Nurse arrived/nurse finished his
work
When the nurse arrives within the
preset time and presses the green reset button. The event qualifier Q is “1”.
When the nurse finishes treatment for
the caller and presses the green reset button again. The event qualifier Q is “3”.
If the nurse has pressed the green
reset button once in help arrived mode but did not press the green reset button again within the preset time to end help arrived mode, CTC-1052 will send this event code with the event qualifier Q “1” every 15 minutes for four times.
662 - Nurse needs help
When the nurse needs more help and
presses the red help button to call for assistance.
663 - Helped arrived mode canceled
When the green reset button is pressed
twice in help arrived mode to cancel help arrived mode.
5.2. Tunstall Event Code
D#1011 - Panel AC Restored/ Help
Arrived
When AC power is restored to CTC-
1052.
When CTC-1052 makes Help Arrived
reporting.
D#1012 - Global test & Periodic test
report
When CTC-1052 reports Global Test to
monitoring Center.
When CTC-1052 reports Periodic test
call to monitoring Center.
D#1013 - Sensor Supervisory Failure
When CTC-1052 is unable to receive
the signal transmitted from the Wrist Transmitter for a pre-set period by Command #49.
D#1014 - Device Low Battery
When devices are under Low Battery
Status, the Green LED flashes every 2 seconds.
D#1015 – Mobility/Inactivity
When CTC-1052 makes Mobility Timer
Expired reporting.
If no sudden movement within 10
seconds after fall detection, an inactivity code will be sent to Central Monitoring Station.
D#1016 - Personal emergency or Fall
emergency
When Wrist Transmitter / Emergency
Pendant (WTR), or Fall Sensor is pressed.
When a fall sensor is triggered
D#1017 - Panel emergency
When the Red HELP Panel button is
pressed.
When Water sensor is triggered.
D#1018 - Smoke emergency
When Smoke Detector (SD) is
triggered or Smoke Detector’s test button is pressed.
When Carbon Monoxide Detector (CO)
is triggered or Carbon Monoxide
32
Page 36
Detector’s test button is pressed.
D#1019 - Panel AC Failure
When AC power fails for more than 10
seconds, Green LED flashes every second with a beep every 30 seconds.
D#1019 – Panel Low Battery / Panel
Battery Disconnection
When CTC-1052 is under Low Battery
status, Green LED flashes every 2 seconds.
When CTC-1052 is under Battery Not
Connected status, the Green LED flashes every 2 seconds.
5.3. Scancom Event Code
515555517 - Panel emergency / Pendant
1 emergency / WS emergency / Fall emergency / WTR / PB emergency
When the Red HELP Panel button is
pressed.
When Pendant 1 is pressed or
triggered.
When Water Sensor is triggered.
When Fall Sensor is pressed or
triggered.
When WTR (non Pendant 1 or Pendant
2) or PB is pressed.
555155517 - Pendant 2 emergency
555556558 - Panel Low battery / Panel
Battery Disconnection
When CTC-1052 is under Low Battery
status, the Green LED flashes every 2 seconds.
When CTC-1052 is under Battery Not
Connected status, the Green LED flashes every 2 seconds.
555551557 - AC Failure
When the AC power fails for more than
10 seconds, the Green LED flashes every second with a beep every 30 seconds.
555553557 - AC Failure Restore / Panel
Low Battery restore / Panel Battery Disconnection restore
When the AC power failure status is
restored. .
When the Panel Low Battery status is
restored.
When the Battery Disconnection status
is restored.
515555559 - Global test / WTR
Supervision Failure
When CTC-1052 reports Global Test to
monitoring Center.
When CTC-1052 is unable to receive
the signal transmitted from the Wrist Transmitter for a pre-set period by Command #49.
When Pendant 2 is pressed or
triggered.
515555518 – Pendant 1 Emergency (Low
Battery)
When Pendant 1 is pressed or
triggered under Low Battery status.
555155518 – Pendant 2 Emergency (Low
Battery)
When Pendant 2 is pressed or
triggered under Low Battery status.
551555517 – Mobility/Inactivity
When CTC-1052 makes Mobility Timer
Expired reporting.
If no sudden movement within 10
seconds after fall detection, an inactivity code will be sent to Central Monitoring Station.
555555559 - Periodic test report / Help
Arrived
When CTC-1052 reports Periodic test
call to Monitoring Center.
When CTC-1052 makes Help Arrived
reporting.
535555557 - WTR Supervision Failure
Restore / WS Emergency Restore
When the WTR supervision failure
status is restored.
When WS emergency status is
restored.
555555558 - Device Low Battery
When devices are under Low Battery
Status, the Green LED flashes every 2 seconds.
555555557 - Device Low Battery Restore
33
Page 37
When the device Low Battery status, is
restored.
155555517 - SD or CO emergency
When Smoke Detector (SD) is
triggered or Smoke Detector’s test button is pressed.
When Carbon Monoxide Detector (CO)
is triggered or Carbon Monoxide Detector’s test button is pressed.
355555557 - SD or CO emergency restore
When the Smoke Detector (SD) or
Carbon Monoxide Detector (CO) emergency status is restored.
FCC Statement This device complies with Part 15 of the FCC Rules.
Operation is subject to the following conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. (3) This device should be installed and operated with a minimum distance of 20 centimeters between the radiator and your body. (4) The antennas used for this device must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.
34
Page 38
5.4. CTC-1052 Programming Command Table
r
r
r
r
DTMF
CHARACTER
COMMANDS
01# Bi Telephone number 1 # Bi No number
02# Bi Telephone number 2 # Bi No number
03# Bi Telephone number 3 # Bi No number
04# Bi Telephone number 4 # Bi No number
05# Bi
06# Bi
10# Bi Global account number, 4 or 6 or 8 digits # Bi No account number
11# Bi 4 or 6 or 8 digits Account number 1 (Tel. Number 1) # Bi No account numbe 12# Bi 4 or 6 or 8 digits Account number 2 (Tel. Number 2) #Bi No account numbe 13# Bi 4 or 6 or 8 digits Account number 3 (Tel. Number 3) # Bi No account number 14# Bi 4 or 6 or 8 digits Account number 4 (Tel. Number 4) # Bi No account numbe
20# Bi
21# Bi
22# Bi
23# Bi
24# Bi
DTMF
ACK
COMMAND OPERATION
Telephone number & GPRS/IP for alarm report 1=TEL1 , 2=TEL2 , 3=TEL3 , 4=TEL4, 5=GPRS1 , 6=GPRS2
Telephone numbe 1=TEL1 , 2=TEL2 , 3=TEL3 , 4=TEL4, 5=GPRS1 , 6=GPRS2
All formats the same, 0 = Contact ID, 1= Scancom, 2 = Tunstall, 3 = Speech, 4 = SMS CID
0 = Contact ID, 1= Scancom, 2 = Tunstall, 3 = Speech, 4 = SMS CID (Tel. Number 1)
0 = Contact ID, 1= Scancom, 2 = Tunstall, 3 = Speech, 4 = SMS CID (Tel. Number 2)
0 = Contact ID, 1= Scancom, 2 = Tunstall, 3 = Speech, 4 = SMS CID (Tel. Number 3)
0 = Contact ID, 1= Scancom, 2 = Tunstall, 3 = Speech, 4 = SMS CID (Tel. Number 4)
& GPRS/IP for status report
TERM
I-
NATO
DTMF
ACK
DEFAULT
R
# Bi 1,2,3,4,5,6
# Bi 1,2,3,4,5,6
# Bi Contact ID
# Bi Contact ID
# Bi Contact ID
# Bi Contact ID
# Bi Contact ID
31# Bi Ringer enable, 0 = Disable, 1 = Enable # Bi Ringer Disabled
32# Bi Audible fault alert, 0 = Off, 1 = On # Bi Off
33# Bi Help arrived signalling, 0 = Off, 1 = On # Bi
34# Bi
35# Bi Silent Mode, 0 = Silent mode On, 1 = Silent mode Off # Bi Silent mode Off
37# Bi AC fault report, 0 = Off, 1 = On # Bi On
38# Bi
40# Bi Set Access Code # Bi 1111
41# Bi
42# Bi
43# Bi
Emergency button enable, 0 = Button off, 1 = Button on
Follow-On & Call Back Function, 0 = Follow-On, 1= Call-Back, 2= Follow-On & Call-Back
Auto answer for Remote programming, 00 = call twice, 01 - 09 = Auto answer 1 - 9 rings
Guard time delay for any compatible sensor (except Fall Sensor), 00 = Instant reporting; … 99 = 99 seconds Test call, 0 = OFF, 1 = 1 Day, 2 = 2 Days, 3 = 3 Days, 4 = 4 Days. 5 = 5 Days, 6 = 6 Days, 7 = 7 Days, 8 = 30 days
# Bi
# Bi Follow-On
# Bi
# Bi 10 seconds
# Bi No test call
0
Help arrived
signalling Off
Emergency button
On
35
Page 39
DTMF
CHARACTER
COMMANDS
44# Bi
45# Bi
46# Bi
47# Bi
49# Bi
61# Bi
62# Bi Set Input SIM CARD PIN CODE : 4 - 8 digital # Bi Null
63# Bi
64# Bi
DTMF
ACK
COMMAND OPERATION
Mobility time 00= Disable, 01 - 36= 1 - 36 Hours
Follow-On Choice, 0 = Wait command, 1 = Listen, 2 = Two way voice communication
Follow-On mode & Two-Way Period, 01=1 min, 02=2mins, 03=3mins, 04=4mins, 05=5mins, 06=6mins, 07=7mins, 08=8mins, 09=9mins, 10=10mins.
Off-set time, 1=1 hour, 2=2 hours, 3=3 hours, 4=4 hours, 5=8hours, 6=12 hours
Supervision, 0 = disable, 1 = 4 days, 2 = 5 days, 3 = 6 days,4 = 7 days, 5 = 8 days, 6 = 9 days, 7 = 10 days
Check SIM CARD PIN CODE 0: Disable 1: Enable
Set Speaker Volume Enter: Mode Number + + Speaker Volume Note: Mode Number: 1 digit (2:Two-way)
Speak volume: 1 digit (1-5 level)
Set Microphone Sensitivity: Note: Mic sensitivity: 1 digit (1-5 level)
Only can be adjusted in the two-way mode.
TERMI­NATOR
DTMF
ACK
# Bi
# Bi
# Bi 5 minutes
# Bi 1 Hour
# Bi Disable
# Bi Disable
# Bi Two way mode: 3
# Bi Two way Mode: 3
DEFAULT
Mobility time
disable
Two-way voice
communication
66# Bi
67# Bi
71# Bi Auto-Answer Number 1. Up to 20 digits. # Bi No Number
72# Bi Auto-Answer Number 2. Up to 20 digits. # Bi No Number
75# Bi Help Not Arrived Call # Bi No number
76# Bi Call progress tone, 0 = Off, 1 = On # Bi Off
77# Bi
78# Bi Mobility Timeout Prompt, 0= Disable, 1= Enable
80# Bi Remove all device (learnt in Command 91-94) --- --- ---
93# Bi Learn-in silent emergency transmitters --- Bi Bi No device
94# Bi
98# Bi
Guard time delay for Fall Sensor, 00 = Instant reporting; … 99 = 99 seconds
Help Arrived Timer 01-15 = 1-15 minutes
Speech report acknowledgement, 0 = Any DTMF On, 1 = OFF-HOOK
Learn-in smoke detectors, CO detectors, pendants and fixed emergency transmitters, long range pendants
Load defaults when ** is pressed (DTMF A is heard after defaults have been loaded)
# Bi 15 sec
# Bi 15 minutes
# Bi Any DTMF
#
--- Bi Bi No device
# Bi ---
Bi Enable
99# Bi Exit programming mode ---
36
Page 40
5.5. CTC-1052 SMS Remote Programming Command Table
If the SMS Keyword is set as PROG, and Access Code is set as 1111 (factory default).
CORRESPON-
DING DTMF
CHARACTER
COMMANDS
---
01#
02#
03#
04#
05#
06#
10#
11#
12#
13#
14#
20#
21#
22#
23#
24#
ITEM COMMAND EXAMPLE & USAGE DEFAULT
SMS
Keyword
(Installer)
Telephone
number 1
Telephone
number 2
Telephone
number 3
Telephone
number 4
Telephone
number for
alarm report
Telephone
number for
status report
Global account number
Account
number 1
Account
number 2
Account
number 3
Account
number 4
Reporting
method for
all 4
Telephone
numbers
Reporting
method for
Telephone
number 1
Reporting
method for
Telephone
number 2
Reporting
method for
Telephone
number 3
Reporting
method for
Telephone
number 4
KEYWD
TELN1
TELN2
TELN3
TELN4
ALMRP
STARP
ACNTG
ACNT1
ACNT2
ACNT3
ACNT4
FMATG
FMAT1
FMAT2
FMAT3
FMAT4
PROG 1111 KEYWD:IPOG To set/change the SMS keyword for installer (4-character)
PROG 1111 TELN1:0227940559 To set/change Telephone number 1 (Max. 20 digits, Null=to clear Telephone number 1)
PROG 1111 TELN2:0227940559 To set/change Telephone number 2 (Max. 20 digits, Null=to clear Telephone number 2) PROG 1111 TELN3:0227940559 To set/change Telephone number 3 (Max. 20 digits, Null= to clear Telephone number 3) PROG 1111 TELN4:0227940559 To set/change Telephone number 4 (Max. 20 digits, Null=to clear Telephone number 4) PROG 1111 ALMRP:1234 To select the number for alarm report 1=Telephone 1 , 2=Telephone 2 , 3=Telephone 3 4=Telephone 4 , 5=GPRS1 , 6=GPRS2 PROG 1111 STARP:1234 To select then number for status report 1=Telephone 1 , 2=Telephone 2 , 3=Telephone 3 4=Telephone 4 , 5=GPRS1 , 6=GPRS2
PROG 1111 ACNTG:1234, To set/change the same 4- 6- 8­digit account number for all 4 telephone numbers (Null=to clear 4 Telephone numbers)
PROG 1111 ACNT1:1234, To set/change the 4- 6- 8-digit account number for Telephone number 1(Null=to clear account number for Telephone number 1)
PROG 1111 ACNT2:1234, To set/change the 4- 6- 8-digit account number for Telephone number 2 (Null=to clear account number for Telephone number 2)
PROG 1111 ACNT3:1234, To set/change the 4- 6- 8-digit account number for Telephone number 3 (Null=to clear account number for Telephone number 3)
PROG 1111 ACNT4:1234, To set/change t the 4- 6- 8-digit account number for Telephone number 4 (Null=to clear account number for Telephone number 4)
PROG 1111 FMATG:0 To set the reporting methods for all 4 Telephone numbers 0=Contact ID, 1=Scancom, 2=Tunstall, 3=Speech, 4=SMS CID
PROG 1111 FMAT1:0 To set the reporting method for Telephone number 1 0=Contact ID, 1=Scancom, 2=Tunstall, 3=Speech, 4=SMS CID PROG 1111 FMAT2:0 To set the reporting method for Telephone number 2 0=Contact ID, 1=Scancom, 2=Tunstall, 3=Speech 4=SMS CID
PROG 1111 FMAT3:0 To set the reporting method for Telephone number 3 0=Contact ID, 1=Scancom, 2=Tunstall, 3=Speech 4=SMS CID
PROG 1111 FMAT4:0 To set the reporting method for Telephone number 4 0=Contact ID, 1=Scancom, 2=Tunstall, 3=Speech 4=SMS CID
No number
No number
No number
No number
1,2,3,4,5,6
1,2,3,4,5,6
Contact ID
Contact ID
Contact ID
Contact ID
Contact ID
account
number
account
number
account
number
account
number
account
number
PROG
No
No
No
No
No
0 =
0 =
0 =
0 =
0 =
37
Page 41
Ringer
A
31#
32#
33#
34#
35# Silent mode SILMO
37#
38#
40#
42#
43#
44#
45#
46#
47# Off-set time OFFST
49# Supervision SUPPR
61#
62#
enable for
incoming
calls
Audible fault
alert
Help arrived
signalling
Emergency
button
AC fault
report
Follow-On &
Call Back
Set access
code
Guard time
delay
Periodic test
call
Mobility
timer
Follow-on
choice
Follow-on &
two-way
period
Check SIM
card Pin
code
Input SIM
card Pin
code
ENRIN
FAUTA
HELPA
EMBUT
ACRPT
FOLON
ACCES
GUDTI
TESTC
MOBTI
LFOLL
FOLTI
SIMPE
SIMPC
PROG 1111 ENRIN:0 To enable/disable ring tone for incoming calls 0=Disable, 1=Enable
PROG 1111 FAUTA:0 To enable/disable audible fault alert 0=Disable, 1=Enable PROG 1111 HELP To enable/disable help arrived signalling 0=Disable, 1=Enable
PROG 1111 EMBUT:1 To enable/disable the Emergency button to send an emergency alarm report 0=Disable, 1=Enable
PROG 1111 SILMO:1 To enable/disable silent mode 0=Silent mode On, 1=Silent mode Off PROG 1111 ACRPT:1 To enable/disable AC fault report 0=Disable, 1=Enable PROG 1111 FOLON:0 To set the follow-on & call back mode 0=Follow-on, 1=Call-back, 2=Follow-on & Call-back PROG 1111 ACCES:1234 To change the access code for installer (4-digit)
PROG 1111 GUDTI:10 To set the guard time delay time for a compatible sensor (except Fall Sensor) 00=Instant, 01-99=1-99 seconds
PROG 1111 TESTC:0 To set the periodic test call 0=Off, 1=1 Day, 2=2 Days, 3=3 Days, 4=4 Days 5=5 Days, 6=6 Days, 7=7 Days ,8=30 Days PROG 1111 MOBTI:00 To set the Mobility timer 00=Disable, 01-36 =1 - 36 Hours PROG 1111 LFOLL:2 To set the follow-on choice for digital reporting 0=Wait command, 1=Listen 2=Two-way voice communication
PROG 1111 FOLTI:02 To set the duration for follow-on & two-way voice communication period 01-10=1-10 minutes
PROG 1111 OFFST:1 To set the off-set time 1=1 Hour, 2=2 Hours, 3=3 Hours 4=4 Hours, 5=8 Hours, 6=12 Hours
PROG 1111 SUPPR:0 To set the supervision timer 0=Disable, 1=4 Days, 2=5 Days, 3=6 Days 4=7 Days, 5=8 Days, 6=9 Days, 7=10 Days
PROG 1111 SIMPE:0 To set Check SIM Card Pin Code 0 = Disable , 1 = Enable
PROG 1111 SIMPC:0000 PROG 1111 SIMPC:12345678 To input SIM CARD Pin Code: 4-8 digits are allowed to be entered.
:0
0 = Disable
0 = Disable
0 = Disable
1 = Enable
1 = Silent mode Off
1 = Enable
0 = Follow-
on
1111
00= instant
reporting
10=10
seconds
0 = Off
00 =
Disable
2 =
Two-way
voice
comm.
05 =
5 minutes
1 =
1 Hour
0 = Disable
0 = Disable
Null
38
Page 42
63#
r
r
Set speaker
volume
SPKVL
Set
64#
microphone
MICSN
sensitivity
Set guard
66#
time for fall
FAGUD
sensor
67#
Set Help
Arrive Timer
HTIME
Auto-
71#
Answer
CTEL1
Number 1
Auto-
72#
Answer
CTEL2
Number 2
75#
77#
Help Not
Arrived Call
Speech
report ack
HTEL1
SPACK
Mobility
78#
Timeout
MOBBP
Prompt
---
Country
code
REPLA
--- IP address TCIP1
--- IP address TCIP2
---
IP address
confirm
COMIP
--- Port number PORT1
--- Port number PORT2
---
Port number
confirm
COMPO
GPRS/IP
---
account
IPAC1
number
GPRS/IP
---
account
IPAC2
number
---
Access
Point Name
APNSR
--- User name GPUSE
--- Password GPASS
PROG 1111 SPKVL:2&1-5
To set a communication channel: 2=Two
Way
To set the speaker volume with a number, ranging
1-5.The higher the value, the louder the voice. Default is set as (3) for two-way mode.
PROG 1111 MICSN:1-5
To set the microphone volume with a number, ranging
1-5. The higher the value, the wider range the
sound received. Default is set as (3). Note: only can be adjusted in the two-way mode.
PROG 1111 FAGUD01-99 To set the guard time delay time for fall sensor.
00=Instant, 01-99=1-99 seconds PROG 1111 HTIME01~15 To set the Hep Arrive Timer.
01-15=1-15 minutes PROG 1111 CTEL1: 0227940559
To set/change Auto-Answer Number 1 (Max. 20 digits, Null=to clear number) PROG 1111 CTEL2: 0227940559 To set/change Auto-Answer Number 2 (Max. 20 digits, Null=to clear number) PROG 1111 HTEL1:0227940559 To set/change No Help Arrived Call (Max. 20 digits, Null=to clear ) PROG 1111 SPACK:1 Speech report acknowledgement. 0 = Any DTMF On, 1 = OFF-HOOK PROG 1111 MOBBP:1 To Enable/Disable Mobility Timeout Prompt 0 = Disable , 1 = Enable PROG 1111 REPLA:886&0 To replace the Country Code with 0 886 Country Code
PROG 1111 TCIP1:192.168.1.110 To set/change the IP address for the Monitoring Station Input IP address: 000.000.000.000 to 255.255.255.255
PROG 1111 TCIP2:192.168.1.110 To set/change the IP address for the Monitoring Station Input IP address: 000.000.000.000 to 255.255.255.255
PROG 1111 COMIP:192.168.1.110 (for confirmation) To set/change the IP address for the Monitoring Station Input IP address: 000.000.000.000 to 255.255.255.255
PROG 1111 PORT1:3301 To set/change the port number for the IP address Input 1 to 5 digits
PROG 1111 PORT2:3301 To set/change the port number for the IP address Input 1 to 5 digits PROG 1111 COMPO:3301 (for confirmation) To set/change the port number for the IP address Input 1 to 5 digits
PROG 1111 IPAC1:1052 To set/change the GPRS/IP account number (4-10digit)
PROG 1111 IPAC2:1052 To set/change the GPRS/IP account number (4-10digit)
PROG 1111 APNSR:INTERNET To set/change the Access Point Name (APN server, 31 digits)
PROG 1111 GPUSE:123 To set/change the user name Input 1 to 15 alphanumeric characters
PROG 1111 GPASS:65536 To set/change the password Input 1 to 5 digits
Two way: 3
Mic: 3
15 sec
15 minutes
No Numbe
No Numbe
No number
Any DTMF
Enable
No country
code
No IP
address
No IP
address
No IP
address
No port number
No port number
No port number
No
account
number
No
account
number
No APN
No user
name
No
password
39
Page 43
Reset to
---
---
---
--- Add Device DEVAD
---
factory
default
3G/LTE RSSI
(3G Version
Only)
Delete
Device
Get Current
Panel
Settings
(3G Version
Only)
FTSET PROG 1111 FTSET:YyS
GRSSI PROG 6336 GRSSI?
DEVDL
ULOAD
PROG 1111 DEVDL:SCMD To delete devices learnt into the panel. SCMD: 80 = delete All Devices.
PROG 1111 DEVAD:SCMD,ID PROG 1111 DEVAD:94010203A001 To add devices into the panel SCMD: 93 = add silent device 94 = add device The devices are added sequentially into zone 1-20 ID: The 10-digit device ID (usually labelled on the back of the device)
PROG 1111 ULOAD:IP address,PORT,ID To obtain the current panel settings IP address – The IP address to receive the current panel settings. Format: IP:xxx.xxx.xxx.xxx PORT – Enter the port number of the IP address. Format: PORT:xxxxx (up to 5 digits). ID: 5-digit ID number. For Example: PROG 1111 ULOAD:IP:123.123.123.123,PORT:54321,2222
<NOTE>
1. IP Address confirm (COMIP) & Port number confirm (COMPO) commands are used for GPRS server confiramtion purpose only. They do not change the IP address nor the port number settings.
2. GPRS functions can only be programed via SMS messages, and the commands MUST be sent in this sequence: Country code IP address Port number GPRS/IP account number Access Point Name User name Password.
One comand per one SMS message. Multiple command in one SMS message is not allowed.
3. When setting IP Address Confirm (COMIP) and Port Number confirm (COMPO)
commands together, the confirmation will send to assigned IP address. However, if COMIP and COMPO are set respectively or one of their commands is deleted or unset, the confimation will be sent over SMS to cell phone.
4. User and Central Monitoring Station will receive the SMS confirmation message in this format:
Confirmed_PROG_1111_COMIP: 192.168.1.110”, or
“Confirmed_PROG_1111_COMPO: 3301”.
5. 3G/LTE RSSI (3G Version Only)
1. < RSSI 10, poor signal.
2. RSSI 15-30 , normal signal.
3. RSSI 99 , 3G/LTE not connected
6. To set multiple SMS commands:
1. Ex: PROG_1111_TELN1:0227940559_TELN2:0227940559 (underline represents <space>).
2. Maximum of 70 digits, including <space>, are allowed to be contained in a SMS
40
Page 44
message sent by the cell phone.
3. SMS remote programming command can only be sent in the standby mode.
4. The SMS command is successfully set after getting a confirmation message.
41
Page 45
Federal Communication Commission Interference Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15, Part 22,
Part 24, and Part 27 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by
one of the following measures:
. Reorient or relocate the receiving antenna.
. Increase the separation between the equipment and receiver.
. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
. Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: To assure continued compliance, any changes or modifications not expressly approved by the party
responsible for compliance could void the user's authority to operate this equipment. (Example - use only shielded interface
cables when connecting to computer or peripheral devices).
FCC Radiation Exposure Statement
This equipment complies with FCC RF radiation exposure limits set forth for an uncontrolled environment. This equipment
should be installed and operated with a minimum distance of 20 centimeters between the radiator and your body.
This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.
The antennas used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons
and must not be co-located or operating in conjunction with any other antenna or transmitter.
This device complies with Part 15, Part 22, Part 24, and Part 27 of the FCC Rules. Operation is subject to the following two
conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
42
Page 46
Industry Canada Statement
This device complies with Industry Canada RSS-130, RSS-132, RSS-133, RSS-139 standard. Operation is subject to the
following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference,
including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence.
L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur
de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le
fonctionnement.
IC Radiation Exposure Statement:
This equipment complies with IC RSS-102 radiation exposure limit set forth for an
uncontrolled environment. This equipment should be installed and operated with
minimum distance 20 cm between the radiator and your body.
Cet équipement est conforme aux CNR-102 d'Industrie Canada. Cet équipement
doit êtreinstallé et utilisé avec une distance minimale de 20 centimètres entre le
radiateur et votrecorps. Cet émetteur ne doit pas être co-localisées ou opérant en
conjonction avec autreantenne ou émetteur. Les antennes utilisées pour cet
émetteur doivent être installés etfournir une distance de séparation d'au moins 20
centimètre de toute personne et doit pas être co-située ni fonctionner en conjonction
avec une autre antenne ou émetteur.
43
Loading...