CLIMAVENETA BRA2 0021, BRA2 0031, BRA2 0041, BRA2 0025, BRA2 0061 Installation, User And Maintenance Manual

...
Page 1
Water chillers and air/water heat pumps with centrifugal fans
EN
BRA2 0021÷0061 BRN2 0021÷0061
INSTALLATION, USER AND MAINTENANCE MANUAL
Page 2
BRA2 - BRN2 EN
INDEX
The manufacturer reserves the right to modify the data in this manual without warning.
ENVIRONMENTAL INFORMATION: This unit contains fluorinated greenhouse gases covered by the Kyoto Protocol. The maintenance and disposal operations must only be carried out by qualified personnel.
General warnings 3
Waiver of liability 3
Fundamental safety rules 3
Identification 4
Receiving, handling and installing the 4 product
Characteristics 5
Dimensioned drawings 6
Water connections 7
Air ducting 11
Electrical connections 13
Mains power supply connections 14
Installer connections 14
General technical data 16
Operating limits 18
Pressure drop and pressure head available 19 to system
Fan pressure gain curves 21
Checking and starting up the unit 22
Led e displays 23
Displaying alarms 32
Peak limiter alarm signals 33
Operating characteristics 35
Shutting down for long periods 36
Routine maintenance 36
Special maintenance 36
Disposal 36
Troubleshooting 37
Useful information 39
U I A
AAI
I
A
I A
I A
I A
I A
A
A
A
A
I A
I AU
U I A
UIA
I
A
I A
I
I
A
I
A
I
I
A
I A
IU
A
I A
I
A
User
Installer
Assistance
Important
Prohibition
Danger voltage
Danger high temperatures
The following symbols are used in some parts of this publication and inside the unit:
U
I
A
Page 3
BRA2 - BRN2 EN
GENERAL WARNINGS
U I A
These appliances have been designed to chill and/or
heat water and must be used in applications compatible with their performance characteristics; these appliances are designed for residential or similar applications. Incorrect installation, regulation and maintenance or improper use absolve the manufacturer from all liability, whether contractual or otherwise, for damage to people, animals or things. Only those applications specifically indicated in this list are permitted Read this manual carefully. All work must be carried out by qualified personnel in conformity with legislation in force in the country concerned.
The warranty is void if the above instructions are not respected and if the unit is started up for the first time with­out the presence of personnel authorised by the Company (where specified in the supply contract) who should draw up a “start-up” report.
The documents supplied with the unit must be consigned to the owner who should keep them carefully for future con­sultation in the event of maintenance or service. When the items are consigned by the carrier, check that the packaging and the unit are undamaged. If damage or missing components are noted, indicate this on the delivery note. A formal complaint should be sent via fax or registered post to the After Sales Department within eight days from the date of receipt of the items. All repair or maintenance work must be carried out by the Company’s Technical Service or qualified personnel follow­ing the instructions in this manual. Do not modify or tamper with the appliance as this may cre­ate situations of danger; in such cases the manufacturer of the appliance is not liable for any damage caused.
FUNDAMENTAL SAFETY RULES
U I A
WAIVER OF LIABILITY
U I A
When operating equipment involving the use of electricity and water, a number of fundamental safety rules must be observed, namely:
This publication is the sole property of Climaveneta. Any reproduction or disclosure of such is strictly prohibited with­out the written authorisation of Climaveneta. This document has been prepared with maximum care and attention paid to the content shown. Nonetheless, Cli- maveneta waives all liability deriving from the use of such document. Read this document carefully.
All work must be performed, components selected and materials used professionally and in complete accordance with the legislation in force in material in the country con­cerned, and considering the operating conditions and intended uses of the system, by qualified personnel.
The unit must not be used by children or by unfit per­sons without suitable supervision. Do not touch the unit with bare feet or with wet or damp parts of the body. Never perform any cleaning operations before having disconnected the unit from the mains power supply. Do not modify safety or control devices without authori­sation and instructions from the manufacturer. Do not pull, detach or twist the electrical cables coming from the unit, even when disconnected from the mains electricity supply. Do not open doors or panels providing access to the internal parts of the unit without first ensuring that the mains switch is in the off position. Do not introduce pointed objects through the air intake and outlet grills. Do not dispose of, abandon or leave within reach of children packaging materials (cardboard, staples, plastic bags, etc.) as they may represent a hazard.
Power supply to the unit must be disconnected using a switch with suitable characteristics, to be supplied and installed by the installer.
Respect safety distances between the unit and other equipment or structures. Guarantee adequate space for access to the unit for maintenance and/or service opera­tions (see the figure on page 5). Power supply: the size of the electrical cables must be adequate for the power of the unit and the power supply voltage must correspond with the value indicated on the respective units. All units must be earthed in conformity with legislation in force in the country concerned.
Some terminals in the electrical panel may be pow­ered even after the unit is disconnected. Make sure power is not connected before proceeding. Water connections should be carried out as indicated in the instructions to guarantee correct operation of the unit. Add glycol to the water circuit if the unit is not used dur­ing the winter or the circuit is not emptied. Handle the unit with the utmost care (see weight distrib­ution table) to avoid damage.
Page 4
BRA2 - BRN2 EN
MODEL:
VOLTAGE:
CODE:
De' Longhi S.p.a. - 31100 Treviso / Italia Via L.Seitz, 47 - tel. 04224131 fax 0422413659
COOLING CAPACITY ------------------- kW HEATING CAPACITY ------------------- kW REFRIGERANT TYPE ------------------­REFRIGERANT CHARGE ------------------- Kg MAXIMUM PRESSURE ------------------- bar MAIN ELECTRICAL POWER SUPPLY ------------------- V---Hz AUXILIARY ELECTRICAL POWER SUPPLY ------------------- V---Hz MAX. POWER INPUT ------------------- kW MAX. CURRENT INPUT ------------------- A START-UP CURRENT ------------------- A WIRING DIAGRAM ------------------- N° OPERATING WEIGHT ------------------- Kg YEAR OF FABRICATION -------------------
IDENTIFICATION
U I A
The chiller can be identified by the:
Packaging label
Giving the data identifying the product.
Rating plate
Giving the technical and performance data of the unit. If this is lost, ask the After Sales Service for a replacement.
Tampering with or the removal or absence of rating plates or other means enabling the unit to be identified causes problems during installation and maintenance.
RECEIVING, HANDLING AND INSTALLING THE PRODUCT
I A
The chillers are supplied accompanied by:
- installation, user and maintenance manual;
- CE declaration;
CHOICE OF INSTALLATION SITE
Before installing the unit, agree with the customer the site where it will be installed, taking the following points into con­sideration:
• Check that the fixing points are adequate to support the weight of the unit;
• Pay scrupulous respect to safety distances between the unit and other equipment or structures to ensure that air entering the unit and discharged by the fans is free to cir­culate.
HANDLING AND POSITIONING
The unit should always be handled by qualified personnel using equipment adequate for the weight of the chiller.
• Before handling the unit, check the capacity of the lift equipment used, respecting the instructions on the pack­aging.
• To move the unit horizontally, make appropriate use of a lift truck or similar, bearing in mind the weight distribution of the unit. To lift the unit, insert tubes long enough to allow position­ing of the lifting slings and safety pins in the special feet on the unit. For the sizes of these tubes, see the figures shown in the corresponding section.
• To avoid the slings damaging the unit, place protection between the slings and the unit. Position the unit in the site indicated by the customer. Place either a layer of rubber (min. thickness 10 mm) or vibration damper feet (optional) between the base and support surface. Fix the unit, making sure it is level and that there is easy access to water and electrical components. If the site is exposed to strong winds, fix the unit ade­quately using tie rods if necessary. If a heat pump unit is being installed, make sure the con­densate is drained using the drain hose supplied as stan­dard.
Prevent leaves, branches or snow from accumulating around the unit. These could reduce the efficiency of the unit.
The installation, user and maintenance manual is an integral part of the unit and should therefore be read and kept carefully. It is recommended that the packaging should not be removed until the unit is located in the installation site. During transport, the chiller should be kept in a verti­cal position The weight of the chiller is biased towards the com­pressor side (side of the packaging with the barcode, see the figure at the foot of the page).
Do not dispose of packaging materials in the environ­ment or leave them within reach of children as they may represent a hazard.
Page 5
BRA2 - BRN2 EN
CHARACTERISTICS
I A
H
P
L
BAR CODE
Hole Ø22
The BRA2 and BRN2 appliances are air-water units operat­ing on R-410A and refrigerant are suitable for outdoor instal­lation. The units are CE marked, as established by the EU directives, including the latest amendments, and the corre­sponding approximated national legislation.
They are factory tested and on site installation is limited to water and electrical connections.
10
9
5
6
4
3
219
11
7
13
14
8
12
15
1 Electrical panel 2 Control panel 3 Heat exchanger installation side 4 Low pressure switch 5 High pressure switch 6 Scroll compressor 7 Filter 8 Thermostatic valve 9 Centrifugal fan 10 Heat exchanger external side 11 Pump (accessory) 12 Liquid receiver (BRN2 only) 13 Expansion tank
(models WITH HYDRONIC UNIT only) 14 Reversing valve (BRN2 only) 15 Fan board
BRA2 Dimensions and weight with standard packaging
Size
0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
Dimension L mm 970 970 970 970 970 970 Dimension P mm 660 660 660 660 660 710 Dimension H mm 840 1140 1140 1440 1440 1590 Weight
Kg 125 140 145 190 210 220
BRN2 Dimensions and weight with standard packaging Size
0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
Dimension L mm 970 970 970 970 970 970 Dimension P mm 660 660 660 660 660 710 Dimension H mm 840 1140 1140 1440 1440 1590 Weight
Kg 135 150 155 205 225 235
BRA2 Dimensions and weight with wooden crate Size
0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
Dimension L mm 1070 1070 1070 1070 1070 1070 Dimension P mm 760 760 760 760 760 810 Dimension H mm 890 1190 1190 1490 1490 1640 Weight difference
Kg 150 170 175 225 245 265
BRA2 Dimensions and weight with wooden crate Size
0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
Dimension L mm 1070 1070 1070 1070 1070 1070 Dimension P mm 760 760 760 760 760 810 Dimension H mm 890 1190 1190 1490 1490 1640 Weight difference
Kg 160 180 185 240 260 280
Page 6
600
W1
W2
W4
W3
900
D
C
=E=
A
400
400
*
B
400
* For installation with open outlet, the minimum distance is increased from 400mm to 1500mm
BRA2 - BRN2 EN
DISEGNI DIMENSIONALI
I
HYDRAULIC CONNECTIONS
I A
The choice and installation of components is the responsibil­ity of the installer who should follow good working practice and current legislation. Before connecting the pipes, make sure they do not contain stones, sand, rust, dross or other foreign bodies which might damage the unit. Construction of a bypass is recommended to enable the pipes to be washed through without having to disconnect the unit (see drain valves). The connection piping should be supported in such a way as to avoid it weighing on the unit. It is recommended that the following devices are installed in the water circuit of the evaporator:
1. Two pressure gauges with a suitable scale (inlet and outlet).
2. Two vibration damper joints (inlet and outlet).
3. Two gate valves (normal in inlet and calibrating in outlet).
4. A flow switch on the unit outlet to the system circuit (com­pulsory). The flow switch must be calibrated by the installer to a value equal to 70% of rated flow.
5. Due termometri (in ingresso e in uscita).
6. An intake filter must be installed as close as possible to the evaporator and positioned to allow easy access for routine maintenance. 500 micron filter
7. All the pipes must be insulated with suitable material to pre­vent the formation of condensate and heat loss. The insu­lating material must be a vapour barrier. Make sure that the control and shut-off devices protrude from the insulation.
8. At the lowest points in the system, install drain valves for easy emptying.
9. At the highest points in the system, install automatic or manual air vent valves.
Failure to install the flow switch will mean the heat exchang­er is not protected in the event of no flow of liquid. Climaveneta cannot be held liable for any damage to the unit and/or the system following the failure to install these devices or the filter. The correct operation of the components that help ensure the safety of the appliance and the system should be checked regularly. Specifically, this involves cleaning the filters and checking the operation of the flow switches installed. Water flow to the chiller unit must conform to the values shown in the section on “General Technical Data”. The flow of water must be maintained constant during oper­ation. The water content of the unit must be such as to avoid dis­turbing operation of the refrigerant circuits.
Dimension 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
A 900 900 900 900 900 900 B 640 940 940 1240 1240 1390 C 580 580 580 580 580 630 D 320 320 320 320 320 370 E 580 580 580 580 580 580
Weight Distribution BRA2 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
W1 30 35 36 48 54 57 W2 11 12 13 17 19 20 W3 23 26 27 36 40 42 W4 41 47 49 64 72 76 TOT 105 120 125 165 185 195
Weight Distribution BRN2 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
W1 33 38 39 52 58 61 W2 12 13 14 18 20 21 W3 25 28 30 40 44 46 W4 45 51 53 70 78 82 TOT 115 130 135 180 200 210
Page 7
BRA2 - BRN2 EN
Minimum system water content Size
0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
Minimum water content BRA2
l 18 21 24 31 36 44
Minimum water content BRN2
l 25 35 40 50 55 65
Expansion vessel size Size
0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
Expansion vessel BRA2 l 2 2 2 2 2 2 Expansion vessel BRN2 l 2 2 2 2 2 5
Safety valve calibration Size
0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T
Safety valve l 6 6 6 6 6 6
FACTORY CONNECTED INSTALLER CONNECTIONS
UTILITY RETURN
UTILITY OUTLET
12
12
14
14
2
10
2
4
3
5
11
6
1
15
15
7
15
8
12
13
System water circuit connection diagram, BRA2 version WITHOUT HYDRONIC KIT
1 PRESSURE GAUGE 2 VIBRATION-ISOLATING JOINT 3 SHUT-OFF VALVE 4 CALIBRATING VALVE 5 FLOW SWITCH 6 THERMOMETER 7 CIRCULATOR PUMP 8 SAFETY VALVE 9 EXPANSION VESSEL 10 MESH FILTER 11 FILL/TOP-UP 12 TEMPERATURE PROBE 13 DIFFERENTIAL PRESSURE
SWITCH
14 DRAIN/CHEMICAL WASHING
VALV E
15 SYSTEM VENT
FACTORY CONNECTED INSTALLER CONNECTIONS
UTILITY RETURN
UTILITY OUTLET
12
12
9
15
8
14
14
2
10
2
4
3
5
11
6
1
15
15
7
13
System water circuit connection diagram, BRA2 version WITHOUT HYDRONIC KIT
1 PRESSURE GAUGE 2 VIBRATION-ISOLATING JOINT 3 SHUT-OFF VALVE 4 CALIBRATING VALVE 5 FLOW SWITCH 6 THERMOMETER 7 CIRCULATOR PUMP 8 SAFETY VALVE 9 EXPANSION VESSEL 10 MESH FILTER 11 FILL/TOP-UP 12 TEMPERATURE PROBE 13 DIFFERENTIAL PRESSURE
SWITCH
14 DRAIN/CHEMICAL WASHING
VALV E
15 SYSTEM VENT
UTILITY RETURN
UTILITY OUTLET
FACTORY CONNECTED INSTALLER CONNECTIONS
12
121512
13
14
10
2
4
11
1
15
14
2
3
5
6
15
7
8
System water circuit connection diagram, BRN2 version WITH HYDRONIC KIT
1 PRESSURE GAUGE 2 VIBRATION-ISOLATING JOINT 3 SHUT-OFF VALVE 4 CALIBRATING VALVE 5 FLOW SWITCH 6 THERMOMETER 7 CIRCULATOR PUMP 8 SAFETY VALVE 9 EXPANSION VESSEL 10 MESH FILTER 11 FILL/TOP-UP 12 TEMPERATURE PROBE 13 DIFFERENTIAL PRESSURE
SWITCH
14 DRAIN/CHEMICAL WASHING
VALV E
15 SYSTEM VENT
Page 8
BRA2 - BRN2 EN
UTILITY RETURN
UTILITY OUTLET
FACTORY CONNECTED INSTALLER CONNECTIONS
12
12
15
8
7
13
14
2
3
5
6
15
14
10
2
4
11
1
15
System water circuit connection diagram, BRN2 version WITH HYDRONIC KIT
1 PRESSURE GAUGE 2 VIBRATION-ISOLATING JOINT 3 SHUT-OFF VALVE 4 CALIBRATING VALVE 5 FLOW SWITCH 6 THERMOMETER 7 CIRCULATOR PUMP 8 SAFETY VALVE 9 EXPANSION VESSEL 10 MESH FILTER 11 FILL/TOP-UP 12 TEMPERATURE PROBE 13 DIFFERENTIAL PRESSURE
SWITCH
14 DRAIN/CHEMICAL WASHING
VALV E
15 SYSTEM VENT
Must be provided with a filling/top-up system connected to the return line and a drain cock in the lowest part of the installation. Installations containing antifreeze or covered by spe­cific legislation must be fitted with water circuit discon­nectors.
The manufacturer is not liable for obstruction, breakage or noise resulting from the failure to install filters or vibration dampers. Particular types of water used for filling or topping up must be treated with appropriate treatment systems. For reference values, see the table.
Risk of freezing
The unit must be prevented from freezing at outside air tem­peratures around 0°C. The following are recommended:
• use suitable percentages of antifreeze (see “Ethylene gly­col solutions”)
• protect the piping with heating sheaths,
• empty the system, making sure no water remains at the lowest points in the circuit or there are closed valves where water may stagnate.
It is recommended to use non-toxic food grade antifreeze, compliant with the standards in force in the countries where the unit is used, if domestic hot water production is also fea­tured. The antifreeze used must be corrosion inhibited and com­patible with the water circuit components.
Ethylene glycol solutions
Water and ethylene glycol solutions used as a heat carrier in the place of water reduce the performance of the unit. Multiply the performance figures by the values given in the following table.
The heat pumps must be fitted with a filling/top-up sys­tem connected to the return line and a drain valve in the lowest part of the system. Systems containing antifreeze or covered by specific legislation must be fitted with low-loss headers.
cPf
cQ
cdp
0 1 1 1
12%
0,985
1,02 1,07
20% 0,98 1,04 1,11
28% 0,974 1,075
1,18
35% 0,97 1,11 1,22
40%
0,965
1,14 1,24
0 -5 -10 -15 -20 -25
Freezing point (°C)
Percentage of ethylene glycol by weight
cPf: cooling capacity correction factor cQ: flow rate correction factor cdp: pressure drop correction factor
Water quality
The water used in the system and domestic hot water cir­cuits must comply with the following characteristics:
PH 6-8 Electrical conductivity less than 200 mV/cm (25°C) Chlorine ions less than 50 ppm Sulphuric acid ions less than 50 ppm Total iron less than 0.3 ppm Alkalinity M less than 50 ppm Total hardness less than 50 ppm Sulphur ions none Ammonia ions none Silicon ions less than 30 ppm
Page 9
BRA2 - BRN2 EN
Condensate drain
In heating mode the unit produces a significant quantity of condensate, which must be suitably drained. Proceed as follows:
• Connect the unit condensate drain
• Make sure the drain hose has a incline of at least 2 cm/m, without obstructions or choking.
• Connect the condensate drain hose to a rainwater drain. Do not connect to the sewage system as odours may be sucked up if the water in the drain trap evaporates.
• After connecting, check correct drainage of the conden­sate by pouring water into the pan.
• If necessary, suitably insulate the condensate drain hose.
• Condensate drainage must not cause problems to objects or people.
• If the outside air temperature is less than 0°C, the conden­sate may freeze.
Use hot wires on the condensate drain hose downstream of the unit to protect against frost.
C
AB
Safety valve
D
OUT
IN
C
AB
D
OUT
IN
Safety valve
BRA2 BRN2
Dimensions
0021 0025-0031 0041-0051 0061
A mm 72 372 431 581 B mm 516 516 757 757 C mm 62 62 62 62 D* mm 65 65 65 65 Water connections in/out, male Ø 1” 1” 1”1/4 1”1/4
*D Safety valve connector position, only on the models with hydronic kit
SIZE AND POSITIONING OF CONNECTIONS, BRA2 AND BRN2
Fouling factors
The performance data given refer to conditions with clean evaporator plates (fouling factor = 1). For different fouling factors, multiply the figures in the perfor­mance tables by the coefficient given in the following table.
f1: capacity correction factor fk1: compressor power input correction factor fx1: total power input correction factor
4,4 x 10
-5
0,86 x 10
-4
1,72 x10
-4
­0,96 0,93
­0,99 0,98
­0,99 0,98
Fouling factors (m2°C/W) f1
Evaporator
fk1 fx1
Page 10
10
BRA2 - BRN2 EN
FILLING THE SYSTEM
- Before filling, check that the system drain valve is closed.
- Open all system and terminal air vents.
- Open system shut off valves.
- Start filling by slowly opening the system water fill cock outside the unit.
- When water begins to leak out of the terminal air vent valves, close them and continue filling until the pressure gauge indicates a pressure of 1.5 bar.
The system must be filled to a pressure of between 1 and 2 bars. It is recommended that this operation be repeated after the unit has been operating for a number of hours. The pressure of the system should be checked regularly and if it drops below 1 bar, the water content should be topped-up.
Check the tightness of the joints.
EMPTYING THE SYSTEM
- Before emptying, place the mains switch in the “off” posi­tion.
- Make sure the system fill/top-up water cock is closed.
- Open the drain cock outside the unit and all the system and terminal air vent valves.
If the fluid in the circuit contains antifreeze, it should not be allowed to drain freely, as it is pollutant.It should be collected for possible reuse.When draining after heat pump operation, take care as the water may be hot (up to 50°).
Page 11
BRA2 - BRN2 EN
11
AIR DUCTING
I
The BRA2-BRN2 models are designed for indoor and out­door installation. The cooling air outlet can be ducted to the outside
Ducting the air outlet
The air outlet ducting connection has the following charac­teristics.
A
B
A
B
C
G
LMNO
HI
D
EF
A
B
C
G
LMN O
HI
D
EF
A
B
C
G
LM
I
EF
A
B
C
G
L
M
I
EF
The length of the outlet ducts must be established by qualified personnel, considering the performance of the fan shown in the table "General technical data"
Suitable measures should be taken to avoid the bypass of air between the outlet and intake.
For the heat pump appliances, the section of ducting inside the environment must be suitably insulated.
Use vibration damper joints on the duct fittings.
The outlet is supplied as standard on the side; for sizes 0021 - 0031 only, the air outlet can be turned from the side to the top position
Model 0061 Model 0041 - 0051 Model 0025 - 0031 Model 0021
BRA2 - BRN2 0021 0025 0031 0041 0051 0061
A mm 203 203 203 203 203 203
B mm 640 900 900 1240 1240 1390
C mm 486 556 556 521 521 521
D mm - - - 521 521 521
E mm 13 18 18 18,5 18,5 18,5
F mm 18 18 18 18 18 18
G mm 53 218 218 81,5 81,5 104
H mm - - - 11,5 11,5 121,5
I mm 62 127 127 27 27 52
L mm 19,5 19,5 19,5 19,5 19,5 19,5
M mm 19,5 19,5 19,5 19,5 19,5 19,5
N mm - - - 19,5 19,5 19,5
O mm - - - 19,5 19,5 19,5
Page 12
The appliance is factory fitted with the air outlet in position A (side).
To move it to position B (top) for model 0021.
- Undo the fastening screws and remove the fan holder cov­er P on the air outlet collar.
- Unscrew the four fastening bolts and remove the air outlet collar.
- Turn the air outlet collar 90° clockwise and fasten the four bolts that were removed previously.
- Replace the fan holder cover P with the fan fitted and tighten the fastening screws.
To move it to position B (top) for models 0025 - 0031.
- Undo the fastening screws and remove the protection grill.
- Undo the fastening screws and remove the closed panel F.
- Invert the protection grid G with the panel F.
- Tighten the fastening screws..
P
F
G
BRA2 - BRN2 EN
12
Page 13
BRA2 - BRN2 EN
13
ELECTRICAL CONNECTIONS
I A
The BRA2 and BRN2 units leave the factory already wired, and require the installation of an omnipolar thermal overload switch, a lockable mains disconnecting switch for the con­nection to the mains power supply, and the connection of the flow switch to the corresponding terminals. All the above operations must be carried out by qualified personnel in compliance with the legislation in force. For all electrical work, refer to the electrical wiring diagrams in this manual.You are also recommended to check:
- that the characteristics of the mains electricity supply are adequate for the absorptions indicated in the electrical characteristics table below, also bearing in mind
Power to the unit must be turned on only after installa­tion work (hydraulic and electrical) has been completed. All electrical connections must be carried out by quali­fied personnel in accordance with legislation in force in the country concerned. Respect instructions for connecting phase, neutral and earth conductors. The power line should be fitted upstream with a suitable device to protect against short-circuits and leakage to earth, isolating the installation from other equipment.
Voltage must be within a tolerance of ±10% of the rated power supply voltage for the unit (for three phase units, the unbalance between the phases must not exceed 2%). If these parameters are not respected, contact the electricity supply company. For electrical connections, use double insulation cable in conformity with current legislation in the country con­cerned.
An omnipolar thermal overload switch and a lockable mains disconnecting switch, in compliance with the CEI-EN stan­dards (contact opening of at least 3mm), with adequate switching and residual current protection capacity based on the electrical data table shown below,must be installed as near as possible to the appliance.
The devices on the unit must be lockable. An efficient earth connection is obligatory. Failure to
earth the appliance absolves the manufacturer of all lia­bility for damage. In the case of three phase units, ensure the phases are connected correctly.
Do not use water pipes to earth the unit.
ELECTRICAL DATA, BRA2 AND BRN2 WITHOUT HYDRONIC KIT
F.L.I. Maximum power input F.L.A. Maximum current input S.A. Start-up current S.A. LIM Peak current with peak limiter Maximum values for sizing the protection switches and power supply cables
Size
Power supply Maximum values Fuses (5x20T 250V)
(V-Ph-Hz) FLA [A] FLI [kW] SA [A] SA LIM [A] FU1 FU2 FU3
BRA2 - BRN2 0021 230-1N-50 18,4 3,42 63,4 29,4 4A 3,15A 2A BRA2 - BRN2 0025 230-1N-50 21,4 4,19 84,4 39,4 4A 3,15A 2A BRA2 - BRN2 0031 230-1N-50 25,4 5,09 99,4 46,4 4A 3,15A 2A BRA2 - BRN2 0041 230-1N-50 29,4 6,34 134,7 49,7 4A 6,3A 2A BRA2 - BRN2 0021 400-3N-50 7,9 3,42 34,4 20,4 4A 3,15A 2A BRA2 - BRN2 0025 400-3N-50 8,4 3,95 37,4 21,4 4A 3,15A 2A BRA2 - BRN2 0031 400-3N-50 10,4 4,76 50,4 28,4 4A 3,15A 2A BRA2 - BRN2 0041 400-3N-50 12,4 6,36 68,7 39,7 4A 6,3A 2A BRA2 - BRN2 0051 400-3N-50 14,2 6,42 68,7 39,7 4A 6,3A 2A BRA2 - BRN2 0061 400-3N-50 17,4 7,75 78,7 45,7 4A 6,3A 2A
ELECTRICAL DATA, BRA2 AND BRN2 WITH HYDRONIC KIT
F.L.I. Maximum power input F.L.A. Maximum current input S.A. Start-up current S.A. LIM Peak current with peak limiter Maximum values for sizing the protection switches and power supply cables
Size
Power supply Maximum values Fuses (5x20T 250V)
(V-Ph-Hz) FLA [A] FLI [kW] SA [A] SA LIM [A] FU1 FU2 FU3
BRA2 - BRN2 0021 230-1N-50 19,0 3,50 64,0 30,0 1,25A 1,25A 2A BRA2 - BRN2 0025 230-1N-50 22,0 4,27 92,2 40,0 1,25A 3,15A 2A BRA2 - BRN2 0031 230-1N-50 26,0 5,17 100,0 47,0 1,25A 3,15A 2A BRA2 - BRN2 0041 230-1N-50 30,3 6,47 135,7 50,7 1,25A 6,3A 2A BRA2 - BRN2 0021 400-3N-50 8,5 3,50 35,0 21,0 1,25A 1,25A 2A BRA2 - BRN2 0025 400-3N-50 9,0 4,03 38,0 22,0 1,25A 3,15A 2A BRA2 - BRN2 0031 400-3N-50 11,0 4,84 51,0 29,0 1,25A 3,15A 2A BRA2 - BRN2 0041 400-3N-50 13,3 6,49 69,7 40,7 1,25A 6,3A 2A BRA2 - BRN2 0051 400-3N-50 15,1 6,55 69,7 40,7 1,25A 6,3A 2A BRA2 - BRN2 0061 400-3N-50 18,3 7,88 79,7 46,7 1,25A 6,3A 2A
Page 14
BRA2 - BRN2 EN
14
MAINS POWER SUPPLY CONNECTIONS
I A
• Before connecting the unit to the power supply, makes sure that switch QF1 is open, suitably padlocked and marked.
• Remove the inspection panel by unscrewing the screws.
• Use cable gland A for the main electrical power cable and cable gland B for other external cables to be connected by the installer.
• Identify the terminals used for electrical connections on the layout drawing shown in this manual.
• Make the connections as shown on the wiring diagram enclosed with the product.
• Replace the covers on the electrical panel and the closing panel.
• Make sure that all the covers removed to make the electri­cal connections have been replaced before powering up the unit.
• Position the main switch QF1 (outside the unit) in the “ON” position.
A
B
INSTALLER CONNECTIONS
I A
All terminals referred to in the explanations below are to be found on the terminal block inside the electrical panel and described as “installer terminals” (see the wiring diagram enclosed with the product).
REMOTE ON/OFF (SA1)
To use a remote on/off device, an external contactor must be connected to installer terminals 14 and 15, setting para­meter CL42 to -1 (CL42=-1). For timed operation, connect a daily or weekly timer between terminals 14 and 15.
REMOTE ALARM (RD1)
For remote display of unit shut-down, an audible or visual alarm warning device can be connected between terminals 12 and 13. Connect the phase to terminal 13 and the alarm signal device between terminal 13 and the neutral (maximum load applicable 500 mA at 24 V).
REMOTE COOLING/HEATING CHANGEOVER (SA2)
To use a remote cooling/heating changeover device, con­nect the contact of the device to installer terminals 16 and
17. To activate the device, proceed as follows:
- From the HSW15 control panel select parameter CL43 and set it to the value +3 (contact closed = cooling, con­tact open = heating) or -3 (contact closed = heating, con­tact open = cooling)
COMPRESSOR ON SIGNAL (GN1)
For remote display of compressor operating status, an audi­ble or visual alarm warning device can be connected between terminals 10 and 11. Connect the phase to terminal 11 and the signal device between terminal 10 and the neu­tral.
Page 15
15
BRA2 - BRN2 EN
OUTSIDE AIR PROBE (BT3) (Accessory)
The outside air probe allows the system water temperature set point to be compensated during heating or cooling opera­tion.
Installation instructions
The outside air probe must be installed:
• outside of the home
• not in direct sunlight, away from flue gas discharges, air outlets, or doors and windows.
• on a perimeter wall facing north/north-west
• at a minimum height of 2.5 metres above the ground or at most half way up the house.
H
H
2
/
1
N
N-W
m 5,2nim
Mounting method:
• Open the cover of the sensor.
• Attach a probe to the wall and the correct position as described above.
• For the electrical connections see “Connection diagram”.
• Re-place the cover of the sensor.
TECHNICAL DATA
Sensing element NTC 10Kohm ± 1% (25°C) Degree of protection IP65 Perm. ambient / carriage temperatur
e -50°C...+100°C Measuring range -50°C...+100°C Materials PA 15% GK, Colour RAL 9010
12
20 21
BT3
REMOTE KEYPAD KIT (A5) (Accessory)
The remote keypad kit can be used to display all unit func­tions and access the parameters of the electronic board from a point located at some distance from the unit itself. It consists of a remote control module. To install the kit, proceed as follows:
- access the unit’s electrical panel after having disconnect­ed the power supply;
- connect the remote control module with 3 wires to termi­nals 22, 23 and 24 on the installer terminal block:
- terminal 22 connected to the GND terminal on the module;
- terminal 23 connected to the Signal terminal on the mod­ule;
- terminal 24 connected to the +12V DC terminal on the module;
FLOW SWITCH CONNECTION (F3)
The system flow switch must be connected to terminals 18 and 19. If this is not connected, the unit will not be able to operate and the controller will display alarm code ER20 (see "Dis­playing alarms").
Page 16
BRA2 - BRN2 EN
16
GENERAL TECHNICAL DATA
I A
BRA2 without hydronic kit 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061 Cooling capacity 1 [kW] 7,71 9,50 11,5 15,0 7,70 9,0 11,60 15,7 17,9 20,5 Power consumption 1 [kW] 2,29 2,79 3,80 4,60 2,22 2,59 3,55 4,79 5,19 6,03 COP 1 3,37 3,41 3,03 3,26 3,47 3,47 3,27 3,28 3,45 3,40 Cooling capacity 2 [kW] 5,74 7,03 8,68 11,4 5,72 7,10 8,76 11,8 13,3 15,6 Power consumption 2 [kW] 2,22 2,68 3,60 4,33 2,17 2,54 3,32 4,47 5,00 5,57 EER 2 2,59 2,62 2,41 2,63 2,63 2,80 2,64 2,64 2,66 2,80 ESEER 1 3,11 3,22 2,98 3,06 3,21 3,45 3,16 3,13 3,02 3,26 Flow-rate 1 m3/h 1,33 1,63 1,98 2,58 1,32 1,55 2,00 2,70 3,08 3,53 Pressure drop 1 kPa 13 15 16 31 13 14 16 34 36 35 Flow-rate 2 m3/h 0,99 1,21 1,49 1,96 0,98 1,22 1,51 2,03 2,29 2,68 Pressure drop 2 kPa 7 8 9 18 7 8 9 19 20 20 Sound power 4 [dBA] 75 75 75 77 75 75 75 77 77 77 Power supply V-N/Ph-Hz 230-1N-50 400-3N-50 No. of compressors 1 1 1 1 1 1 1 1 1 1 No. of circuits 1 1 1 1 1 1 1 1 1 1 Type of compressor Scroll No. of fans 1 1 1 2 1 1 1 2 2 2 Air flow-rate 1 [m3/h] 3000 3400 3400 6450 3000 3400 3400 6450 6000 6350 No. of system heat exchangers 1 1 1 1 1 1 1 1 1 1 Type of system heat exchanger PLATE System water heat exchanger content l 2 2 2 2 2 2 2 2 2 3
BRA2 with hydronic kit 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061 Cooling capacity 1 [kW] 7,76 9,56 11,6 15,1 7,75 9,1 11,70 15,8 18,0 20,7 Power consumption 1 [kW] 2,21 2,69 3,71 4,48 2,14 2,50 3,45 4,66 5,04 5,91 COP 1 3,51 3,55 3,13 3,37 3,62 3,62 3,39 3,39 3,57 3,50 Cooling capacity 2 [kW] 5,77 7,08 8,73 11,5 5,75 7,15 8,81 11,9 13,4 15,7 Power consumption 2 [kW] 2,16 2,61 3,52 4,26 2,11 2,47 3,24 4,41 4,91 5,45 EER 2 2,67 2,71 2,48 2,70 2,72 2,90 2,72 2,70 2,73 2,88 ESEER 1 3,21 3,35 3,07 3,14 3,33 3,59 3,27 3,23 3,11 3,37 Flow-rate 1 m3/h 1,33 1,64 2,00 2,60 1,33 1,56 2,01 2,72 3,10 3,56 Available pressure head 1 kPa 59 50 40 37 60 53 39 33 26 23 Flow-rate 2 m3/h 0,99 1,22 1,50 1,98 0,99 1,23 1,52 2,05 2,30 2,70 Available pressure head 2 kPa 72 66 59 51 72 66 59 50 49 47 Sound power [dBA] 75 75 75 77 75 75 75 77 77 77 Power supply V-N/Ph-Hz 230-1N-50 400-3N-50 No. of compressors 1 1 1 1 1 1 1 1 1 1 No. of circuits 1 1 1 1 1 1 1 1 1 1 Type of compressor Scroll No. of fans 1 1 1 2 1 1 1 2 2 2 Air flow-rate [m3/h] 3000 3400 3400 6450 3000 3400 3400 6450 6000 6350 No. of system heat exchangers 1 1 1 1 1 1 1 1 1 1 Type of system heat exchanger PLATE System water heat exchanger content l 2 2 2 2 2 2 2 2 2 3
(1) outside air 35°C evaporator water IN/OUT 23/18°C (2) outside air 35°C evaporator water IN/OUT 12/7°C (3) maximum and minimum operating pressure refer to activation of the pressure switches (4) sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1 Performance in accordance with EN 14511:2013
(1) outside air 35°C evaporator water IN/OUT 23/18°C (2) outside air 35°C evaporator water IN/OUT 12/7°C (3) maximum and minimum operating pressure refer to activation of the pressure switches (4) Sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1 Performance in accordance with EN 14511:2013
Page 17
17
BRA2 - BRN2 EN
GENERAL TECHNICAL DATA
I A
BRN2 without hydronic kit 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061 Heating capacity 1 [kW] 6,76 8,37 10,5 12,9 6,73 8,3 10,00 13,4 14,8 17,3 Power consumption 1 [kW] 2,25 2,84 3,48 4,35 2,24 2,69 3,23 4,47 4,67 5,58 COP 1 3,01 2,95 3,01 2,97 3,01 3,08 3,10 2,99 3,17 3,10 Cooling capacity 2 [kW] 4,81 5,89 7,29 9,6 4,80 5,99 7,35 10,0 11,1 13,0 Power consumption 2 [kW] 1,96 2,39 3,27 3,81 1,92 2,27 2,99 3,95 4,42 4,95 EER 2 2,45 2,46 2,23 2,51 2,50 2,64 2,46 2,52 2,51 2,63 ESEER 1 3,07 3,05 2,87 3,03 3,09 3,29 2,99 3,09 2,85 3,11 Flow-rate 1 m3/h 1,16 1,44 1,80 2,22 1,16 1,43 1,72 2,30 2,55 2,98 Pressure drop 1 kPa 10 12 13 23 10 12 12 25 24 24 Flow-rate 2 m3/h 0,83 1,01 1,25 1,64 0,83 1,03 1,26 1,71 1,91 2,24 Pressure drop 2 kPa 5 6 6 13 5 6 6 14 14 14 Sound power 4 [dBA] 75 75 75 77 75 75 75 77 77 77 Power supply V-N/Ph-Hz 230-1N-50 400-3N-50 No. of compressors 1 1 1 1 1 1 1 1 1 1 No. of circuits 1 1 1 1 1 1 1 1 1 1 Type of compressor Scroll No. of fans 1 1 1 2 1 1 1 2 2 2 Air flow-rate 1 [m3/h] 3000 3400 3400 6450 3000 3400 3400 6450 6000 6350 No. of system heat exchangers 1 1 1 1 1 1 1 1 1 1 Type of system heat exchanger PIASTRE System water heat exchanger content l 2 2 2 2 2 2 2 2 2 3
BRN2 with hydronic kit 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061 Heating capacity 1 [kW] 6,72 8,32 10,4 12,8 6,68 8,2 9,99 13,3 14,8 17,2 Power consumption 1 [kW] 2,18 2,75 3,38 4,22 2,17 2,61 3,14 4,38 4,57 5,46 COP 1 3,08 3,02 3,08 3,03 3,08 3,16 3,18 3,04 3,24 3,15 Cooling capacity 2 [kW] 4,83 5,93 7,33 9,6 4,82 6,03 7,39 10,0 11,2 13,1 Power consumption 2 [kW] 1,92 2,34 3,19 3,76 1,88 2,22 2,91 3,88 4,38 4,85 EER 2 2,51 2,53 2,30 2,56 2,56 2,72 2,54 2,58 2,56 2,70 ESEER 1 3,17 3,17 2,97 3,09 3,19 3,43 3,09 3,14 2,93 3,20 Flow-rate 1 m3/h 1,16 1,43 1,79 2,20 1,15 1,42 1,72 2,29 2,55 2,96 Available pressure head 1 kPa 66 58 48 46 66 58 51 44 44 40 Flow-rate 2 m3/h 0,83 1,02 1,26 1,65 0,83 1,04 1,27 1,72 1,93 2,25 Available pressure head 2 kPa 74 73 67 56 74 73 67 55 55 55 Sound power [dBA] 75 75 75 77 75 75 75 77 77 77 Power supply V-N/Ph-Hz 230-1N-50 400-3N-50 No. of compressors 1 1 1 1 1 1 1 1 1 1 No. of circuits 1 1 1 1 1 1 1 1 1 1 Type of compressor Scroll No. of fans 1 1 1 2 1 1 1 2 2 2 Air flow-rate [m3/h] 3000 3400 3400 6450 3000 3400 3400 6450 6000 6350 No. of system heat exchangers 1 1 1 1 1 1 1 1 1 1 Type of system heat exchanger PLATE System water heat exchanger content l 2 2 2 2 2 2 2 2 2 3
(1) outside air 7°C; condenser water in/out 40/45°C (2) outside air 35°C; evaporator water IN/OUT 12/7°C (3) maximum and minimum operating pressure refer to activation of the pressure switches (4) Sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1 Performance in accordance with EN 14511:2013
(1) outside air 7°C; condenser water in/out 40/45°C (2) outside air 35°C; evaporator water IN/OUT 12/7°C (3) maximum and minimum operating pressure refer to activation of the pressure switches (4) Sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1 Performance in accordance with EN 14511:2013
Page 18
18
BRA2 - BRN2 EN
OPERATING LIMITS
U I A
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-15 -10 -5 0 5 10 15 20
Outside air temperature [°C]
Water outlet temperature at evaporator [°C]
COOLING
Operating range in COOLING Water temperature head min-max= 3-8 K Water circuit pressure min-max= 1÷6 bars Max storage temperature= 63°C Maximum percentage of glycol= 40% As standard, the unit is manufactured with operating parameters allowing water produced at the evaporator down to +5°C. If needing to produce water down to -10°C, contact technical service.
OPERATION WITH
WATER-GLYCOL MIX
20
25
30
35
40
45
50
55
60
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
Water outlet temperature at condenser [°C]
Outside air temperature [°C]
HEATING
Operating range in heating Water temperature head min-max= 4-10 K Water circuit pressure min-max= 1÷6 bars Maximum water temperature at system heat exchanger water inlet +50°C Max storage temperature= 63°C Maximum percentage of glycol= 40%
Page 19
BRA2 - BRN2 EN
19
U I A
PRESSURE DROP AND PRESSURE HEAD AVAILABLE TO SYSTEM
I A
SYSTEM HEAT EXCHANGER PRESSURE DROP, UNIT WITHOUT HYDRONIC KIT
0
10
20
30
40
50
60
70
80
90
100
012345
Pressure drop [kPa]
System heat exchanger pressure drop
Water flow-rate [m3/h]
0021 0025 0041 0031
0051
0061
AVAILABLE PRESSURE HEAD, UNIT WITH HYDRONIC KIT
0
10
20
30
40
50
60
70
80
90
100
01234
Available pressure head [kPa]
Water flow-rate [m3/h]
Available pressure head
0025
0021 0031
Page 20
BRA2 - BRN2 EN
20
U I A
PRESSURE DROP AND PRESSURE HEAD AVAILABLE TO SYSTEM
I A
AVAILABLE PRESSURE HEAD, UNIT WITH HYDRONIC KIT
0
10
20
30
40
50
60
70
80
90
100
012345
Available pressure head [kPa]
Water flow-rate [m3/h]
Presión estática útil
0051 0041 0061
The pressure head refers to the value available to the system.
The pump installed on the unit, if the “hydronic kit” option is purchased as an accessory, is a circulator pump with built-in inverter, including water pressure transducer and micro­processor to manage the following control modes adjust­ment:
CONSTANT ΔP: the pressure differential between pump suction and discharge is kept constant, pump speed decreases progressively when the terminals close.
VARIABLE ΔP: the pressure differential reduces as flow­rate decreases, to account for the lower pressure drop along the piping running to the terminals (recommended for long sections of piping)
The type of control can be set using the selector on the pump body. As standard, the type of control is set to CON­STANT ΔP.
CONSTANT ΔP (standard setting)
VARIABLE ΔP
Page 21
300
250
200
150
100
50
0
2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500
0051
0041
0061
21
BRA2 - BRN2 EN
The characteristics indicated above refer to units with ducted outlets, with a 0.5m long straight duct and a cross-section equal to the cross-section of the fan.
The BRA2-BRN2 0041÷0061 units are supplied with two fans
Do not operate in the dashed section of the curves.
Air flow-rate (
m3/h)
300
250
200
150
100
50
0
2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100 3200
0011
0021
GRAPH OF FLOW-RATE - FAN PRESSURE GAIN
MOD. 0021
Residual static pressure gain (Pa)
Air flow-rate (
m3/h)
300
250
200
150
100
50
0
2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500
0031
0025
MOD. 0041-0061
MOD. 0025 - 0031
Residual static pressure gain (Pa)Residual static pressure gain (Pa)
Air flow-rate (
m3/h)
FAN PRESSURE GAIN CURVES
I A
Page 22
22
BRA2 - BRN2 EN
CHECKING AND STARTING UP THE UNIT
A
PREPARING FOR FIRST START UP or restarting after shutting down for long periods.
The unit must be started up for the first time by the Techni­cal Service.
Before starting up the units, make sure that:
- All safety conditions have been respected;
- The unit is adequately fixed to the surface it rests on;
- Clearances have been respected
- Water connections have been carried out as indicated in the instruction manual;
- The water circuit is filled and vented.
- The water valves are open;
- Electrical connections have been carried out correctly
- Voltage is within a tolerance of 10% of the rated voltage for the unit;
- The unit is correctly earthed;
- All electrical connections are tight and all water connec­tions have been carried out correctly.
The unit must be started up for the first time with standard settings. Set Point values may be modified only after testing has been completed. Before starting up, power up the unit for at least two hours by switching QF1 and QS1 ON (see "wiring diagram" and the control panel in standby) so as to allow the oil in the compressor sump to heat up.
STARTING UP FOR THE FIRST TIME (after two hours)
Before starting the chiller:
-
Make sure the switch QF1 is in the OFF position.
- Make sure the contact of the on/off device SA1 (see the wiring diagram) is open (if fea­tured).
- Close the door of the electrical panel.
- Move the main unit switch QS1 to the ON position.
- Move the switch QF1 (outside the unit) to “ON”.
-
The icon with the off symbol ( ) lights up on the control panel, indicating power is connected.
For the position of internal components, see the dia­grams.
ON
OFF
ON
OFF
ACTIVATING AND DEACTIVATING THE UNIT
- Move the contact on the on/off device SA1 (if featured) to ON.
During this phase, if the following indications appear on the display, follow the instructions:
- ER20 check the water flow-rate and the connection of the flow switch.
- ER01 (three-phase heat pumps only): check the power supply connection and if necessary reverse two phas­es.
At every change of season, make sure the operating conditions fall within the limits specified. Make sure the current input of the compressor is less than the maximum shown in the table of technical speci­fications. Make sure the voltage is within the established limits and that, for three phase units, the unbalance between the phases is less than 2%. Check that the cover is closed again following the setting procedure.
To access the control panel, open the door:
- remove the screw 1;
- press the points 2 simultaneously and lift the door 3.
ON
OFF
set
esc
1
2
2
3
3
Page 23
BRA2 - BRN2 EN
23
LEDS AND DISPLAY
A
Alarm
Heating
Cooling
Standby
Defrost
1 STATUS AND OPERATING MODE LEDS
Compressor
Fans
System pump
Frost protection heater system heat exchanger
3 UTILITY LEDS
Clock
Degrees centigrade
Pressure (Bar)
Menu (ABC)
2 VALUE AND UNIT OF MEASURE LEDS
set
esc
Page 24
BRA2 - BRN2 EN
24
To set the clock of the unit, starting from the main display, press the set button.
Pressing the set button once displays the various directo­ries. Scroll the menu using the UP and DOWN buttons until reaching the directory CL.
SETTING THE CLOCK
The HSW15 controller is fitted with a clock for managing time bands to control specific events. Follow the procedure shown below to set the hours, minutes and date.
To enter menu CL press the set button.
Once having entered this menu, HOUr will be shown. Select whether to set the time, date or year using the UP and DOWN buttons. Once having decided which value to set, press the [set]** button to enter the corresponding menu. **pressed and held for 3 around seconds.
To set the time, date and year simply scroll with the UP and DOWN buttons until the desired value and
Page 25
BRA2 - BRN2 EN
25
... press the set button.
To exit the clock setting menu press the esc button until returning to the main display.
Page 26
26
BRA2 - BRN2 EN
SCHEDULER SETTING
The HSW15 controller can manage the unit based o the time and the day of the week. The controller features four time bands in three profiles that can be combined, when programming, with the days of the week. The profile defines the behaviour of the unit over a 24 hour period. Time band management must be enabled by parameter tE00 = 1 (tE00 = 0 standard setting).
Programming example
1) Define the profile for each time band, as shown in the following table.
Description Description Profile 1 Profile 2 Profile 3
Hour / Minutes hours 00 (tE10=0) / min.00 (tE11=0) hours 00 (tE38=0) / min.00 (tE39=0) tE66..tE67 Operating mode ON/Standby ON (tE12=0) ON (tE40=0) tE68
TIME BAND 1 Cool set point tE13=15 tE42=15 tE69
Heat set point tE14=30 tE42=30 tE70 DHW set point tE15=50 tE43=50 tE71 Hour / Minutes hours 6 (tE17=6) / min.00 (tE18=0) hours 7 (tE45=6) / min.00 (tE46=0) tE73..tE74 Operating mode ON/Standby ON (tE19=0) ON (tE47=0) tE75
TIME BAND 2 Cool set point tE20=12 tE48=12 tE76
Heat set point tE21=33 tE49=33 tE77 DHW set point tE22=45 tE50=45 tE78 Hour / Minutes hours 9 (tE24=9) / min.00 (tE25=0) hours 7 (tE52=12) / min.00 (tE53=0) tE80..tE81 Operating mode ON/Standby ON (tE26=0) ON (tE54=0) tE82
TIME BAND 3 Cool set point tE27=15 tE55=12 tE83
Heat set point tE28=30 tE56=33 tE84 DHW set point tE29=50 tE57=45 tE85 Hour / Minutes hours 17 (tE31=17) / min.00 (tE32=0) hours 17 (tE59=17) / min.00 (tE60=0) tE87..tE88 Operating mode ON/Standby ON (tE33=0) ON (tE61=0) tE89
TIME BAND 4 Cool set point tE34=12 tE62=12 tE90
Heat set point tE35=33 tE63=33 tE91 DHW set point tE36=45 tE64=45 tE92
Example of profile 1 to be used on opening days
Example of profile 2 to be used on closing days
2) Associate one of the three programmed profiles with each day of the week. The days of the week are identified by the parameters tE01 to tE07; tE01 = Monday, tE02= Tuesday……tE07=Sunday. Once having displayed the day of the week, tE01 to tE07, select the value 1, 2 or 3 corresponding to Profile 1, Profile 2 and Profile 3 respectively.
Follow the operations shown below to program the profiles and combine them with the day of the week:
To access directory tE from the main display, press esc and set together. [esc+set].
Pressing these two buttons enters the menu with the list of directories. Use the up and down buttons to scroll to the directory PAr. Press the set button and use the up and down buttons to scroll to the directory tE.
Press the set button to display the first parameter, tE00. Use the up and down buttons to scroll to the other parameters.
To set the selected parameter, press the set button and enter the value using the up and down buttons. Confirm the changes by pressing the set button or alterna­tively cancel by pressing esc.
Page 27
27
BRA2 - BRN2 EN
For example, to switch operation from StbY to COOL.
To change the operating mode, press and hold the mode button for at least 2 seconds.
A scroll menu will start flashing with the values StbY (stand­by) and COOL (cool). Use the up and down buttons to select the desired operating mode.
SELECTING THE OPERATING MODE
There are three different modes:
• Standby mode (StbY)
• Cooling mode (COOL)
• Heating only mode (HEAT)
The unit will automatically return to the main display and the Stby LED, previously on, will now be off and the COOL LED will be on.
To change the set point, starting from the main display, press the set button.
Pressing the set button once displays the various directo­ries. Scroll the menu using the up and down buttons until reaching the SP directory.
To enter the SP directory press the set button.
The active mode will be displayed (COOL).
SETTING THE SET POINTS
As an example, the Set Point in COOL mode will be changed from 12.0 degrees centigrade to 12.5 degrees centigrade.
Taking the example of changing the set point for the operat­ing mode. Press the SET button.
Page 28
BRA2 - BRN2 EN
28
The instrument will display the current set point (in this case
12.0 degrees centigrade).
To increase or decrease the value, use the up and down buttons. For example, to change the set point to 12.5 degrees, press the up button until the desired value is displayed.
Once having reached the desired set point, press the set button. In this way, the instrument will save the value 12.5.
To return to the main display, press esc or wait for the menu timeout to expire (15 seconds).
SETTING THE PARAMETERS
Accessing the PASS directory (from the main display, press­ing the esc and set buttons together [esc+set] and scrolling to the directory with up / down) and setting the PASS accesses the parameters visible for the password entered.
To access the PASS directory from the main display, press esc and set together [esc+set].
Pressing the two buttons accesses the menu listing the directories. Scroll using the up and down buttons to the PASS directory.
To enter the PASS directory press the set button. Then enter the password (installer or manufacturer), press set and exit. Access the parameters to display or change the values.
Press the up and down buttons to select the Par submenu. Press the set button to display the desired directory.
Page 29
BRA2 - BRN2 EN
29
The first directory displayed by the instrument will be the CF directory (configuration). To set the individual CF parameters, simply press set again.
The instrument will display parameter CF00 (default factory settings). To scroll the various parameters, simply press the up button to go to the next parameter (in this case CF01) or the down button to go to the previous parameter (in this case CF47). CF00->CF01->CF02->...->CF47->CF00 CF47<-CF00<-CF01->...<-CF46<-CF47
NOTE: -> UP, <-DOWN
To display the value of the parameter (in this case CF00), press the set button.
For parameter CF00, the value displayed will be 2. To change the value of the parameter, press the up or down button.
When having selected the value, press the set button. ** To exit the display and return to the previous level, press esc.
**NOTE: pressing the set button confirms the new value; pressing the esc button returns to the previous level without changing the existing value.
Press the SET button for 3 seconds.
The display shows YES, to confirm that the alarm log has been reset.
RESETTING THE ALARM LOG (Er90)
From the main display press “esc + set”, the display will show “Par”. Scroll using the UP and DOWN buttons until displaying the label “FnC”. Press the SET button, the display will show “dEF”. Scroll using the UP and DOWN buttons until displaying “EUr”.
Page 30
BRA2 - BRN2 EN
30
Example of displaying and resetting (tens) the Pump operat­ing hours. From the main display, press the set button.
The display will show label Ai. Scroll the labels using the UP and DOWN buttons until reaching label Hr.
DISPLAYING AND RESETTING COMPRESSOR / PUMP HOURS
Press the set button to display the first label, in this case the operating hours for compressor 1 (CP01).
Scroll using the UP and DOWN buttons until displaying (if featured among the resources) the operating hours for com­pressor 2 (CP02) and the operating hours for the pump (PU02).
Press the set button to display the operating hours for the pump PU02.
The tens of operating hours are equal to 2. (The hours are expressed in tens: 2 indicates 20 operating hours). To reset the operating hours for the pump PU02, press and hold [set].
Note: to reset the operating hours for the other resources, repeat the procedure described.
To exit the menu, press esc until returning to the main display.
Page 31
BRA2 - BRN2 EN
31
LIST OF ACCESSIBLE PARAMETERS
Directory labe
l Parameters Parameters for:
CF CF00... CF77 Configuration
Ui UI00... UI18 User interface
tr tr00... tr20 Temperature control
St St00... St04 Operating status
CP CP00... CP10 Compressor Primary pump PI PI00... PI24 Primary water circuit pump Fans FE FE00... FE30 Fans Electric
HI HI00... H15 System heat exchanger electric heater
heater
dS dS00... dS07 Dynamic set point
Ad Ad00... Ad07 Adaptive
AF AF00... AF03 Frost protection
AL AL00... AL48 Alarms
CL C00... CL97 Local I/O configuration
Note 1: when setting the parameters the COMPRESSOR and HEATER LEDs will flash alternating with the DEFROST
LED.
Note 2: the above table shows a list of parameters that are all or partly available only on entering the password.
Page 32
BRA2 - BRN2 EN
32
DISPLAYING ALARMS
I A
FAULT CAUSE SOLUTION
Values display indication
Er01
High pressure switch tripped, manual reset after 3 activations in one hour, incorrect connection of power supply phases (three­phase models only)
Check fault (see high discharge pressure) Reset manually Change the position of two phases.
Values display indication
Er05
Low pressure switch tripped manual reset after 4 activations per hour
Check fault
Values display indication
Er30
System frost prevention alarm (manual reset)
Check water outlet temperature Check water flow Check temperature set point Check correct positioning of sensor BT2
Values display indication
Er20
Differential pressure switch or flow switch tripped Manual reset if active for more than 30 seconds
Check inadequate water flow Check for air in water circuit Check electrical connection (see unit wiring dia­gram)
Values display indication
Er 10
Fan circuit breaker tripped Manual reset if active for more than 30 seconds
Check correct sequence of power supply phases (versions 0071-0121)
Display indication
Er47
HSW15 communication error with remote keypad (only if remote keypad featured)
Check electrical connection
Values display indication
Er60
Faulty BT1 system water return sensor (automatic reset)
Check electrical connections Replace component
Display indication
Er75
Pressure transducer malfunction
Check electrical connection (see unit wiring dia­grams) Replace component
Display indication
Er81
Compressor maintenance interval
Check operating pressure Check condition of the compressor Reset the clock
Display indication
Er85
Water pump maintenance interval
Check condition of the water pumps Reset the clock
Display indication
Er90
Maximum alarm log size exceeded
Reset alarm log (paragraph "Reset alarm log")
Values display indication
Er61
Faulty BT2 system water outlet sensor (automatic reset)
Check electrical connections Replace component
Display indication
Er46
Set the clock
See procedure on p. 24
Page 33
33
BRA2 - BRN2 EN
PEAK LIMITER ALARM SIGNALS
I A
The heat pumps can be fitted with a single-phase or three-phase peak limiter to reduce compressor start-up current.
Single-phase peak limiter
The green LED on steady indicates line voltage is present. The red LED identifies the type of alarm, based on the sequence of flashes. The orange LED indicates the delay between unit starts and/or stops.
* monitored during inactivity and bypass ** In this situation, the red LED flashes 4 times; the service
centre needs to be contacted to reset the device.
Three-phase peak limiter
The three-phase peak limiter has 2 built-in indicator LEDs. The green LED indicates line voltage is present and correct operation. The red LED identifies different alarm conditions based on the sequence of flashes, as shown in the enclosed table.
Orange LED Condition Action
ON
Minimum recovery
time between starts
and/or recovery time
between stop and start
Autoreset when the
minimum recovery
time has elapsed
Red LED Condition Action
2 flashes
Undervoltage
Ue < 190VAC)
Autoreset after
5 minutes *
3 flashes
Overcurren
(>80 A for 1 sec.)
Autoreset after
5 minutes
4 flashes Protection relay
Autoreset after
5 minutes **
5 flashes Ramp incomplete
Autoreset after
5 minutes
Green LED Condition Action
Flashing Power supply alarm
Contact service
centre
ON
Device powered,
no faults
Awaiting
compressor
start signal
Red LED Condition Action
2
Incorrect phase sequence
Reverse the phases
3
Line voltage out
of limits
Autoreset after
5 minutes
4 Frequency out of limits
Autoreset after
5 minutes
5
Locked rotor
(during ramp)
Autoreset after
5 minutes
6
Ramp starting
> 1 sec
Autoreset after
5 minutes
7 Excess temperature
Autoreset after
5 minutes
8
Low current
(during bypass)
Autoreset after
5 minutes
9 Voltage unbalanced
Autoreset after
5 minutes if all the
three phases (L1, L2,
L3) are connected
Green LED Condition Action
Flashing
1 minute recovery
between starts and/or
recovery time between
stop and start
ON
Device powered,
no faults
ON
Device powered
during ramp
Page 34
34
BRA2 - BRN2 EN
OPERATING CHARACTERISTICS
I A
Cooling set point
(factory setting) = 12°C, Hysteresis = 3°C. The compressor starts at outlet water temperatures above 12°C+3°C (15°C). The compressor stops at water temperatures below 12°C. In the event of temporary power failure, when power returns, the mode set previously will be retained in the memory.
Heating set point
(factory setting) = 40°C, Hysteresis = 3°C. The compressor starts at water outlet temperatures below 37°C. The compressor stops at water temperatures above 40°C. In the event of temporary power failure, when power returns, the mode set previously will be retained in the memory.
COMPRESSOR START-UP DELAY
Two functions prevent the compressor from starting up too frequently.
- Minimum time since last shut-down 180 seconds.
- Minimum time since last start-up 300 seconds.
CIRCULATING PUMP
The electronic board includes a pump control output. The pump starts when “cool” mode is activated and stops a few seconds after “standby” mode is selected. After the first few seconds of pump operation when the water flow is at full speed, the water flow alarm functions are activated (differential pressure switch and flow switch).
FAN SPEED CONTROL
To enable the unit to function correctly at different outside temperatures, a microprocessor with pressure reading via pressure sensor controls the fan rotation speed. This allows the exchange of heat to be increased and/or decreased, maintaining condensing or evaporation pressures essential­ly constant. The fan operates independently of the compressor.
FROST ALARM
The frost protection function is always active, so as to pre­vent the water freezing and damaging the plate heat exchanger; to do this, the microprocessor shuts down the compressor if the temperature measured by the heat exchanger outlet temperature sensor is less than: +4°C on the system side. The frost prevention temperature set point can be modified by an authorised service centre only and only after verifying that the water circuit contains antifreeze. Tripping of this alarm shuts down the compressor but not the pump, which remains active. To reset normal functions, the water outlet temperature must rise to more than: +7°C on the system side. Reset is manual.
WATER FLOW ALARM
The microprocessor provides for the management of a water flow alarm controlled by a differential pressure switch fitted as standard on the appliance and flow switches to be installed on the water inlet piping. This safety device may trip after the first 60 seconds of pump operation when the water flow is up to speed. Tripping of this alarm shuts down the compressor but not the pump, which remains active. The alarm is reset automatically is it lasts less than 20 sec. If it lasts longer, it must be reset manually.
Page 35
BRA2 - BRN2 EN
35
OPERATING CHARACTERISTICS
I A
SYSTEM WATER SET POINT COMPENSATION BASED ON THE OUTSIDE TEMPERATURE
Set point compensation based on the outside temperature must be enabled by setting a parameter, see the table.
Outside air temperature probe to be purchased as an accessory, not supplied with the unit.
System water set point compensation in COOLING mode based on the outside temperature
Graph with factory settings
Outside air temperature
Ds05 + Ds01 = 20°C Ds05 = 25°C
12°C
15°C
Water temperature set point
Ds01 = -5°C
Ds03 = 3°C
System water set point compensation in HEATING mode based on the outside temperature
Graph with factory settings
Outside air temperature
Ds06 + Ds02 = 10°CDs06 = -5°C
28°C
33°C
Water temperature set point
Ds02 = 15°C
Ds04 = -5°C
Parameter Value Unit of measure Description
ds00 1 Enable system water set point compensation function
OPERATION IN COOLING MODE
Ds01 -5 °C Differential applied to the value of ds05
DS03 3 °C Differential applied to the system water temperature set point in cooling mode
Ds05 25 °C Outside air temperature activation/deactivation value for set point
compensation function in COOLING
OPERATION IN HEATING MODE
Ds02 15 °C Differential applied to the value of ds06
DS04 -5 °C Differential applied to the system water temperature set point in heating mode
Ds06 -5 °C Outside air temperature activation/deactivation value for set point
compensation function in HEATING
Page 36
BRA2 - BRN2 EN
36
SHUTTING DOWN FOR LONG PERIODS
A
After deactivating the chiller:
- Make sure the remote switch SA1 (if featured) is off.
- Make sure the remote keypad (if featured) shows “OFF”.
- Place QF1 in the OFF position (see wiring diagram)
- Deactivate the indoor terminal units by placing the switch of each unit in the “OFF” position.
- Close the water valves.
If the mains switch is turned to “off” for more than four hours, after turning it on and before reactivating the unit, leave the power on but the unit deactivated for at least two hours to preheat the oil in the compressor sump.
ROUTINE MAINTENANCE
A
UNSCHEDULED MAINTENANCE
A
Never perform any cleaning operations before having
disconnected the unit from the mains power supply. Terminals 10, 11, 12, 13, 14, 15, 16, 17, 18 and 19 may be live even when the unit has been disconnected. Make sure power is not connected before proceeding
CHEMICAL WASHING
It is recommended to chemically flush the plate heat exchanger after every 3 years of operation. For instructions on how to carry out this operation, call the toll free number.
REFRIGERANT GAS CONTENT
The chillers are charged with R-410A refrigerant gas and tested in the factory. In normal conditions, there should be no need for the Tech­nical Service to intervene to check the refrigerant gas. However, over time, small leaks may develop at the joints leading to loss of refrigerant and draining of the circuit, causing the unit to function poorly. In this case, the leaks of refrigerant must be identified and repaired and the refrigerant circuit recharged. Proceed as follows:
- Empty and dry the entire refrigerant circuit using a vacuum pump connected to the low and high pressure tap until the vacuometer reads about 10 Pa. Wait a couple of minutes and check that this value does not rise to more than 50 Pa.
- Connect the refrigerant gas cylinder or a filling cylinder to
the low pressure line pressure gauge connection.
- Charge the quantity of refrigerant indicated on the unit’s rating plate.
- Always check the superheat and subcooling values, which should be between 5 and 10 °C and 4 and 8 °C.
- After a couple of hours operation, check that the liquid indicator indicates a dry circuit (dry-green).
In the event of partial leaks, the circuit must be com­pletely emptied before being recharged. The R-410A refrigerant must only be charged in the liq­uid state. Operating conditions other than rated conditions may produce considerably different values. Tightness testing or identification of leaks must only be carried out using -R410A refrigerant gas, checking with a suitable leak detector. The refrigerant circuit must not be charged with a refrigerant other than that indicated. The use of a different refrigerant may cause serious damage to the compressor.
Oxygen, acetylene or other flammable or poisonous gas­es must never be used in the refrigerant circuit as they may cause explosion or poisoning. Oils other than those indicated on page 16 must not be used. The use of a different oil may cause serious damage to the compressor.
Never perform any cleaning operations before having disconnected the unit from the mains power supply. Terminals 10, 11, 12, 13, 14, 15, 16, 17, 18 and 19 may be live even when the unit has been disconnected. Make sure power is not connected before proceeding. Regular maintenance is fundamental to maintain the effi­ciency of the unit both in terms of operation and energy con­sumption. The Technical Service maintenance plan must be observed, with an annual service which includes the following opera­tions and checks:
- Filling of the water circuit;
- Presence of air bubbles in the water circuit
- Efficiency of safety devices
- Power supply voltage
- Power consumption
- Tightness of electrical and water connections
- Condition of the compressor contactor
- Verification of operating pressure, superheat and subcool­ing
- Efficiency of the compressor heater
During the maintenance operations, the chiller inspection panel may need to be removed. If this is the case, proceed as follows:
- Open the door of the electrical panel.
- Undo the screws as shown in the figure
- Remove the inspection panel
To replace the inspection panel, repeat the procedure in reverse.
DISPOSAL
A
The unit must be disposed of according to the legislation in force in the country concerned.
Page 37
BRA2 - BRN2 EN
37
U I A
TROUBLESHOOTING
AI
Power failure
Power supply voltage too low
Switch QF1 in OFF position Remote switch (if featured) in OFF position Control panel in standby Main switch QS1 in OFF Compressor circuit breaker OFF
Check presence of voltage Check safety systems upstream of the appliance
Check power line
Switch ON
Contactor coil faulty HSW15 controller fault Start-up capacitor faulty (if featured) Compressor faulty Reversed phases (three-phase units only)
Replace the component
Check
Replace the component
Check
Check
Check
Protection devices trip and shut down the com­pressor
Excessive discharge pressure Low suction pressure Low voltage Electrical connections not sufficiently tight Operation outside permitted limits
Faulty operation of pressure switches
Circuit breaker tripped Check supply voltage Check electrical insulation of wind­ings
Replace the component
Insufficient capacity
Insufficient refrigerant Unit sized too small Operation outside recommended limits
Noise and vibrations
Contact between metal bodies
RepairWeak foundations
Tighten screws
Loose screws
Compressor noisy
Liquid returning to compressor Inadequate fastening
The unit doesn’t start
FAULT CAUSE SOLUTION
Page 38
BRA2 - BRN2 EN
38
Low suction pressure (less than 4 bars)*
Low utility water inlet temperature Low outside water inlet temperature Thermostatic expansion valve faulty or blocked Blocked water filter Blocked plate heat exchanger
Check
Low discharge pressure (less than 16 bars)*
Low utility water inlet temperature
Check
Air in water circuit Vent
Insufficient gas charge Check
Moisture in the refrigerant circuit (flow indicator ­moisture yellow)
Empty and refill
Faulty operation of outside heat exchanger control (pressure regulating valves)
Check
High suction pressure (greater than 20 bars)*
High utility water inlet temperature Thermostatic expansion valve faulty or excessively open
Check
High discharge pressure (greater than 32 bars)*
High outside water temperature High utility water inlet temperature
Insufficient water flow-rate in outside heat exchanger
Check
Check pump operation
Faulty operation of outside heat exchanger control (pressure regulating valves)
Check
Air in water circuit Vent
Excessive refrigerant charge
Check
*Values indicative only
FAULT CAUSE SOLUTION
Page 39
39
BRA2 - BRN2 EN
A U
USEFUL INFORMATION
U I A
For information on technical assistance and obtaining spare parts, contact:
CLIMAVENETA S.P.A. AFTER SALES DEPARTMENT - RESIDENTIAL BUSINESS
Via Duca d’Aosta 121 - 31031 Mignagola di Carbonera (TV) ITALY
Tel: +39.0424.509500 Fax: +39.0424.509563
www.climaveneta.com - [email protected]
Page 40
COD. C01002793C_02
Loading...