CLIMAVENETA AW HT User Manual

USER MANUAL
High temperature air/water heat pump for heating water up to 65°C and operation with outside temperatures down to -20°C. Domestic hot water production and built-in water circuit assembly.
AW HT 0031÷0061
2 AW HT GB 05/2009
OPERATION OF THE ROOM TEMPERATURE CONTROL UNIT
A
BUTTONS
Select heating mode
Room temperature probe
Select central heating or DHW
Display information
Correct ambient Comfort set point
Browse and set parameters
Occupancy button
Confirm setting
Display
Heating to Comfort set point
Heating to reduced set point
Heating to frost protection set point
Process in progress - please wait
Replace battery
Vacation function active
Reference to heating circuit
Maintenance / Special functions
Error messages
Info level active
Programming level activated
Heating temporarily OFF - ECO function active
Xxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxx
Xxxxxxxxxxxxxxxxxx
Hour and minutes
Temperature and parameters display
Programming menu display
3GB 05/2009 AW HT
OPERATION AND FUNCTIONS OF THE ROOM UNIT USING THE BUTTONS
A
Select heating operating modes
Repeatedly pressing button 1 selects the different heating operating modes:
Automatic heating mode
Automatic operation controls the room tem­perature based on the set time program.
Characteristics of automatic opera­tion:
• Characteristics of automatic opera­tion:
• Heating mode based on the time program.
• Temperature set point according to the “Comfort set point” or “Reduced set point” program
• Protection functions active.
• Summer / winter switching (ECO functions) and 24 hour heating limit not active.
Continuous operation or
Continuous operation keeps the room temperature constant at the selected level.
Characteristics of continuous operation:
• Heating without considering the time program.
• Protection functions active.
• Summer / winter switching (ECO functions) and 24 hour heating limit not active, for continuous operation with Com­fort set point.
Protection mode
In Protection mode, the heating sys­tem is not active. However the frost protection function is guaranteed (frost protection temperature), as long as the power supply is connected. On the display the operating mode is indicated by a line under the corresponding symbol.
Select domestic hot water mode (DHW)
Operating mode only available only if the three way selector valve is installed as an accessory outside of the unit. Pressing button 3 starts and stops domestic hot water production.
DHW mode
• Active (indicator shown under the symbol) Domestic water is heated based on the selected operating program.
• Not active (no indicator shown under the symbol). No domestic water is heated; the frost protection function is active.
Push DHW
This is activated by pressing the DHW mode button for at least three seconds. This manually activates the production of domestic hot water only. Activating this function starts the heat pump in DHW mode until reaching the DHW set point, and cannot be deactivated.
Room temperature control
Knob 4 is used to control the desired room temperature.
Temperature correction in Heating mode: For the Comfort set point select the temperature value by turning the knob and confirming by pressing OK.
For the Reduced set point
• Press OK.
• Select the “Heating circuit” page
• Set the “Reduced set point” parameter 712.
After having made the settings, wait at least 2 hours to allow the desired room temperature to be reached.
Occupancy button (extended absence)
If the rooms are not used for long periods, the room temperature can be reduced by pressing the occupancy button 5, thus sav­ing energy. When the rooms are used again, pressing the pressing the occupancy button 5 returns the room temperature to the set value.
• The occupancy button is only enabled in automatic opera­tion.
• The setting remains active until the heating program is next changed.
Information button
The information button 6 displays different types of information, as described in this manual, such as temperature, heat pump operating status and errors.
In exceptional situations, the display shows the following symbols:
Error warning
This symbol indicates an error in the system. Press the information button and read the additional infor­mation shown on the display. Follow the instructions described in the paragraph “Maintenance and Service”.
Maintenance warning
This symbol indicates the need for maintenance or a special operating mode. Press the information button and read the additional infor­mation shown on the display. Follow the instructions described in the paragraph “Mainte­nance and Service”.
1
4
5
6
3
Operating mode
indication
Operating mode
indication
Operating mode
indication
Operating mode
indication
Heating to daytime room tem­perature setting Heating to reduced room tem­perature setting
4
AW HT GB 05/2009
The settings that are not available directly using the buttons are managed in programming mode. The individual settings are arranged into operating pages and rows and are divided into levels, “Enduser and Engi­neer”, so as to allow access only to specific groups of para­meters. The “OEM” level is protected against accidental modifications by a password.
The main screen shown in the figure is the starting point for all the settings.
ENDUSER level.
The procedure described below is used to access the oper­ating pages in the “Enduser Level” and set the correspond­ing group of parameters. Below is an example of the procedure used to set the lan­guage. The same procedure is valid for displaying and set­ting all the Enduser level parameters.
1. Main display If the main display is not shown, press ESC.
2. Press OK The operating pages are shown at the bottom of the dis­play.
3. Turn the knob and select the desired operating page. For example Operator section.
4. Press OK to confirm. In this example the bottom of the display shows the first row “language” and at the top right the parameter num­ber, “20”.
5. Press OK to set the parameter. The display shows the value flashing, in the example “Italian”.
6. Turn the knob and select the desired value of the para­meter. For example, “English”.
7. Press OK to confirm. The settings have been saved. The display stops flashing.
8. Either continue setting other parameters or press ESC once to access other operating pages twice to return to the main display.
AUTO
0
4 8 12 16 20 24
Room temperature
AUTO
0
4 8 12 16 20 24
Room temperature
Ora e Data
0
4 8 12 16 20 24
AUTO
Unità di comando
PROG
No.
0
4 8 12 16 20 24
AUTO
PROG
Ora e Data Unità di comando Programma orario CR 1
No.
Operating page
0
4 8 12 16 20 24
AUTO
PROG
No. 20
Operator section Language
English
0
4 8 12 16 20 24
AUTO
PROG
No.
20
Operator section Language
English
Parameter number
0
4 8 12 16 20 24
AUTO
PROG
No.
20
Operator section Language
English
0
4 8 12 16 20 24
AUTO
PROG
No.
20
Operator section Language
English
AUTO
0
4 8 12 16 20 24
Room temperature
OPERATION AND FUNCTIONS OF THE ROOM UNIT IN PROGRAMMING MODE
A
5GB 05/2009 AW HT
The rows shown in light grey cannot be selected as they are not available in the Enduser level. They can be selected in higher levels.
Example of subdivision into Enduser levels, operating pages and rows:
User level
User level
Enduser
Commissioning
Engineer OEM
Time of day and date Operator section
Radio
User diagnostics
Time program heating circuit 1 Time program 3/HCP
Hours / Minutes Day / Month Year
Hours 1...24 h Minutes 0 to 60 min
Start daylight saving End daylight saving
Page
SETTING THE TIME AND DATE
The controller is fitted with a clock that manages the hour, minutes, month, day of the week and year. To ensure correct operation of the controller, the time and date must be set correctly.
Parameter
number
Screen displayed
Description
Hour and minutes setting
Month and day setting
Year setting
AUTO
0
4 8 12 16 20 24
Room Temperature
0
4812162024
AUTO
Operator section
PROG
+
-
OK OK
2x
OK
Time of day and date
0
4 8 12 16 20 24
AUTO
PROG
No.
1
Time of day and date
Hours / minutes
00 : 00
0
4 8 12 16 20 24
AUTO
PROG
No.
1
Time of day and date
Hours / minutes
14 : 00
0
4812162024
AUTO
PROG
No.
2
Time of day and date
Day / month
00 : 00
0
4812162024
AUTO
PROG
No.
2
Time of day and date
Day / month
02 : 05
0
4812162024
AUTO
PROG
No.
3
Time of day and date
Year
0000
0
4 8 12 16 20 24
AUTO
PROG
No.
2
Time of day and date
Day / month
00 : 05
+
-
OK
0
4 8 12 16 20 24
AUTO
PROG
No.
1
Time of day and date
Hours / minutes
14 : 25
+
-
OK
+
-
OK
+
-
OK
+
-
OK
+
-
OK
0
4 8 12 16 20 24
AUTO
PROG
No.
3
Time of day and date
Year
2009
ESC
2x
1
2
3
Parameters contained on the TIME OF DAY AND DATE operating page (Enduser level)
6 AW HT GB 05/2009
AUTOMATIC DAYLIGHT SAVING CHANGEOVER
Parameter
number
Screen displayed
Description
Setting the start of the summer period ensures automatic changeover of the time. On the first Saturday following to the date set, the time changes from 02:00 (winter) to 03:00 (summer).
Default setting: Day 25 Month 03
Setting the end of the summer period ensures automatic changeover of the time. On the first Saturday following to the date set, the time changes from 03:00 (summer) to 02:00 (winter).
Default setting Day 25 Month 10
AUTO
0
4 8 12 16 20 24
Room Temperature
0
4812162024
AUTO
Operator section
PROG
OK
Time of day and date
0
4 8 12 16 20 24
AUTO
PROG
No.
5
Time of day and date
Day / Month
27 : 04
+
-
+
-
OK
+
-
OK
+
-
OK
+
-
OK
+
-
OK
+
-
OK
ESC
2x
OK
2x
3sec.
0
4 8 12 16 20 24
AUTO
PROG
No.
6
Time of day and date
Day / Month
End of summertime
25 : 10
0
4 8 12 16 20 24
AUTO
PROG
No.
6
Time of day and date
Day / Month
End of summertime
24 : 09
0
4 8 12 16 20 24
AUTO
PROG
No.
5
Time of day and date
Day / Month
Start of summertime Start of summertime
25 : 04
0
4 8 12 16 20 24
AUTO
PROG
Commissioning Engineer OEM
0
4812162024
AUTO
PROG
No.
1
Time of day and date
Hours / minutes
14 : 25
0
4812162024
AUTO
PROG
No.
5
Time of day and date
Day / Month
Start of summertime
25 : 03
0
4 8 12 16 20 24
AUTO
PROG
No.
6
Time of day and date
Day / Month
End of summertime
25 : 09
5
6
Parameters contained on the TIME OF DAY AND DATE operating page (Engineer level)
7GB 05/2009 AW HT
LANGUAGE SETTING
Parameter
number
Screen displayed
Description
The following languages can be selected: German English French Italian
Default setting: Italian
AUTO
0
4 8 12 16 20 24
Room Temperature
0
4 8 12 16 20 24
AUTO
Operator section
PROG
OK
Time of day and date
+
-
+
-
OK
ESC
2x
OK
ESC
2x
OK
2x
0
4 8 12 16 20 24
AUTO
PROG
Time of day and date Operator section Time prog heating circuit 1
0
4 8 12 16 20 24
AUTO
PROG
No.
20
Operator section
Language
English
0
4812162024
AUTO
PROG
No.
20
Interface utilisateur Langue
Francais
0
4 8 12 16 20 24
AUTO
PROG
No.
20
Operator section
Language
Italiano
20
Parameters contained on the OPERATOR SECTION operating page (Enduser level)
8 AW HT GB 05/2009
AUTO
0
4 8 12 16 20 24
Room temperature
0
4 8 12 16 20 24
AUTO
Operator section
PROG
OK
Time of day and date
+
-
+
-
+
-
OK
+
-
OK
+
-
OK
+
-
OK
+
-
OK
OK
OK
2x
0
4 8 12 16 20 24
AUTO
PROG
Operator section Time prog heating circuit 1 Time program 3 / HCP
0
4 8 12 16 20 24
AUTO
PROG
No.
500
Time prog heating circuit 1 Preselection
0
4 8 12 16 20 24
AUTO
PROG
No.
500
Time prog heating circuit 1 Preselection
0
4 8 12 16 20 24
AUTO
PROG
No.
500
Time prog heating circuit 1 Preselection Mo
+
-
+
-
OK
0
4 8 12 16 20 24
AUTO
PROG
No.
501
Time prog heating circuit 1 Mo : 1st phase On
06 : 00
0
4812162024
AUTO
PROG
No.
501
Time prog heating circuit 1 Mo : 1st phase On
07 : 15
0
4 8 12 16 20 24
AUTO
PROG
No.
502
Time prog heating circuit 1
Mo : 1st phase Off
22 : 00
0
4812162024
AUTO
PROG
No.
502
Time prog heating circuit 1 Mo : 1st phase Off
09 : 30
0
4812162024
AUTO
PROG
No.
503
Time prog heating circuit 1 Mo : 2st phase On
-- : --
0
4812162024
AUTO
PROG
No.
500
Time prog heating circuit 1
Preselection Tu
Mo - Su
Mo - Su
TIME BAND PROGRAMMING
Time prog heating circuit 1
Parameter
number
Description
The controller manages the heating circuit based on the time and the day of the week. The on and off times can be selected in groups, that is, common for a group of days, or individually, different for each day. The presetting of the days into groups, for example Mon to Fri and Sat-Sun simplifies the time band set­tings. Groups: Mon-Sun; Mon-Fri; Sat-Sun; Individual: Mon, Tue, Wed, Thu, Fri, Sat, Sun
1st On Time 1st Off Time 2nd On Time 2nd Off Time 3rd On Time 3rd Off Time
The time programs can be reset to the original values (default setting).
Default setting
Mon – Sun
6:00 (h:min) 22:00 (h:min)
--:-- (h:min)
--:-- (h:min)
--:-- (h:min)
--:-- (h:min) Yes or no
Repeat the same sequence to pro­gram the 2nd and 3rd On / Off period.
The procedure for programming the 1st, 2nd and 3rd On / Off period must be repeated for each group or for each day. In this example: once having pro­grammed the On and Off times for Monday, select Tuesday (par. 500) and repeat the procedure for pro­gramming the 1st, 2nd and 3rd On / Off period.
500
501 502 503 504 505 506 516
Parameters contained on the TIME PROG HEATING CIRCUIT 1 operating page (Enduser level)
9GB 05/2009 AW HT
AUTO
0
4 8 12 16 20 24
Room temperature
0
4 8 12 16 20 24
AUTO
Operator section
PROG
OK
Time of day and date
+
-
+
-
+
-
OK
+
-
OK
+
-
OK
+
-
OK
+
-
OK
OK
OK
2x
0
4 8 12 16 20 24
AUTO
PROG
Time program 3 / HCP Time program 4 / DHW Time program 5
0
4 8 12 16 20 24
AUTO
PROG
No.
560
Time program 4 / DHW Preselection Mo - Su
0
4 8 12 16 20 24
AUTO
PROG
No.
560
Time program 4 / DHW
Preselection Mo - Su
0
4 8 12 16 20 24
AUTO
PROG
No.
560
Time program 4 / DHW Preselection Mo
+
-
+
-
OK
0
4 8 12 16 20 24
AUTO
PROG
No.
561
Time program 4 / DHW Mo : 1st phase On
06 : 00
0
4812162024
AUTO
PROG
No.
561
Time program 4 / DHW Mo : 1st phase On
07 : 15
0
4 8 12 16 20 24
AUTO
PROG
No.
562
Time program 4 / DHW
Mo : 1st phase Off
22 : 00
0
4812162024
AUTO
PROG
No.
562
Time program 4 / DHW
Mo : 1st phase Off
09 : 30
0
4812162024
AUTO
PROG
No.
563
Time program 4 / DHW Mo : 2st phase On
-- : --
0
4812162024
AUTO
PROG
No.
560
Time program 4 / DHW
Preselection Tu
Time program 4/DHW (domestic hot water production)
Parameter
number
Description
The controller manages domestic hot water production based on the time and the day of the week. The on and off times can be selected in groups, that is, common for a group of days, or individually, different for each day. The presetting of the days into groups, for example Mon to Fri and Sat-Sun simplifies the time band settings. Groups: Mon-Sun; Mon-Fri; Sat-Sun; Individual: Mon, Tue, Wed, Thu, Fri, Sat, Sun
1st On Time 1st Off Time 2nd On Time 2nd Off Time 3rd On Time 3rd Off Time
The time programs can be reset to the original values (default setting).
Default setting
Mon – Sun
6:00 (h:min) 22:00 (h:min)
--:-- (h:min)
--:-- (h:min)
--:-- (h:min)
--:-- (h:min) Yes or no
Repeat the same sequence to pro­gram the 2nd and 3rd On / Off period.
The procedure for programming the 1st, 2nd and 3rd On / Off period must be repeated for each group or for each day. In this example: once having pro­grammed the On and Off times for Monday, select Tuesday (par. 500) and repeat the procedure for pro­gramming the 1st, 2nd and 3rd On / Off period.
560
561 562 563 564 565 566 576
Parameters contained on the TIME PROGRAM 4/DHW operating page (Enduser level)
10 AW HT GB 05/2009
AUTO
0
4 8 12 16 20 24
Room Temperature
0
4 8 12 16 20 24
AUTO
Operator section
PROG
OK
Time of day and date
+
-
+
-
+
-
OKOK
OK
0
4 8 12 16 20 24
AUTO
PROG
Time program 5 Holidays heating circuit 1 Heating circuit 1
+
-
OK
+
-
OK
+
-
OK
OR
0
4 8 12 16 20 24
AUTO
PROG
No.
642
Holidays heating circuit 1 Period 1: Start Day / month
-- : --
+
-
OK
0
4 8 12 16 20 24
AUTO
PROG
No.
642
Holidays heating circuit 1 Period 1: Start Day / month
01 : 08
0
4 8 12 16 20 24
AUTO
PROG
No.
642
Holidays heating circuit 1 Period 1: Start Day / month
01 : 08
0
4 8 12 16 20 24
AUTO
PROG
No.
642
Holidays heating circuit 1 Period 1: Start Day / month
05 : 08
+
-
+
-
OK
0
4 8 12 16 20 24
PROG
No.
643
Holidays heating circuit 1 Period 1: End Day / month
01 : 08
0
4 8 12 16 20 24
PROG
No.
648
Holidays heating circuit 1 Operating level
Frost protection
0
4812162024
PROG
No.
648
Holidays heating circuit 1 Operating level
0
4 8 12 16 20 24
AUTO
AUTO
AUTO
PROG
No.
643
Holidays heating circuit 1 Period 1: End Day / month
-- : --
0
4 8 12 16 20 24
AUTO
PROG
No.
643
Holidays heating circuit 1 Period 1: End Day / month
01 : 08
0
4 8 12 16 20 24
AUTO
AUTO
PROG
No.
643
Holidays heating circuit 1 Period 1: End Day / month
26 : 08
OK
ESC
2x
Reduced
Holidays program
The holidays program can only be used in “Automatic” mode
Parameter
number
Description
Start Vacation period End Vacation period Operating modes during the vacation period. The operating modes may be:
- Frost protection
- Reduced set point (Temperature selected by parameter 712).
Default setting
--.-- (day/month)
--.-- (day/month) Frost protection
642 643 648
Parameters contained on the HOLIDAYS HEATING CIRCUIT 1 operating page (Enduser level)
11GB 05/2009 AW HT
AUTO
0
4 8 12 16 20 24
Room temperature
0
4 8 12 16 20 24
AUTO
Operator section
PROG
OK
Time of day and date
+
-
OK
2x
0
4 8 12 16 20 24
AUTO
PROG
Heating circuit 1 Domestic hot water Service/special operation
0
4 8 12 16 20 24
AUTO
PROG
No.
1610
Domestic hot water
Nominal setpoint
55 C
+
-
OK
0
4812162024
AUTO
PROG
No.
1610
Domestic hot water Nominal setpoint
58 C
ESC
2x
DHW set point control and time program
The vacation program can only be used in “Automatic” mode
Parameter
number
Description
Select DHW set point
To set the desired temperature of the domestic hot water inside the storage cylinder, change the value of parameter 1610, as described below.
Default setting
1610 = 55
1610
Parameters contained on the DHW operating page (Enduser level)
USEFUL INFORMATION
For information on technical assistance and obtaining spare parts, contact:
TECHNICAL SERVICE DEPARTMENT CLIMAVENETA HOME SYSTEM S.R.L. ROOM AIR-CONDITIONING
via. L. Seitz, 47 - 31100 Treviso (ITALIA)
www.climaveneta.it - info@climavenetahs.it
Climaveneta S.p.a.
Via Sarson 57/c 36061 Bassano del Grappa (VI) Italy Tel. +39 0424 509 500 Fax +39 0424 509 509 info@climaveneta.com www.climaveneta.com
Climaveneta Home System
Via Duca d’Aosta 121 31030 Mignagola (TV) Italy Tel. +39 0422 4131 Fax +39 0422 413659 info.cvhs@climaveneta.com www.climaveneta.com
Climaveneta France
3, Village d’Entreprises ZA de la Couronne des Prés Avenue de la Mauldre 78680 Epône France Tél. +33 (0)1 30 95 19 19 Fax +33 (0)1 30 95 18 18 info@climaveneta.fr www.climaveneta.fr
Climaveneta Deutschland
Rhenus Platz 2 59439 Holzwickede Germany Tel. +49 2301 91222-0 Fax +49 2301 91222-99 info@climaveneta.de www.climaveneta.de
Climaveneta España - Top Clima
Londres 67, 1° 4° 08036 Barcelona Spain Tel. +34 963 195 600 Fax +34 963 615 167 topclima@topclima.com www.climaveneta.com
Climaveneta Chat Union Refrig. Equipment Co Ltd
88 Bai Yun Rd, Pudong Xinghuo New dev. zone 201419 Shanghai China Tel. 008 621 575 055 66 Fax 008 621 575 057 97
COD. 5790003300_00