ClimateWorx Series 7, 7AH15, 7AH20, 7AH25, 7CW15 Installation Manual

...
MISSION CRITICAL Air Conditioning Systems
Series 7,
Wall Mount Units
Installation Manual
S7-IM2014.DOC 2014 14 Chelsea Lane, Brampton, Ontario, Canada, L6T 3Y4
Series 7 Installation Manual
S7-IM2014.DOC 2014
2
Table of Contents
Table of Contents ................................................................................................................. 3
Site Preparation.................................................................................................................... 4
Location Consideration ....................................................................................................... 4
Positioning of Indoor units ................................................................................................ 4
Positioning of Condensing Unit ......................................................................................... 4
Positioning of Remote Controller Unit or Thermostat ....................................................... 5
Electrical Installation ........................................................................................................... 5
Power Feeding ................................................................................................................... 5
Series 7 Installation Manual
Interconnecting Wiring M52 only ...................................................................................... 5
Pipe Installation.................................................................................................................... 5
Recommended Pipe Size for Remote Condenser ................................................................ 6
Evacuation ......................................................................................................................... 6
Head Pressure Control System ........................................................................................... 7
Normal Charging ................................................................................................................. 9
Operating the Thermostat ................................................................................................... 9
Dimensional Details ............................................................................................................ 14
Appendix A: Dimensional Drawings ................................................................................ 15
Appendix B: Piping Schematic Drawings ........................................................................ 20
Appendix C: Electrical Schematic Drawings ................................................................... 24
S7-IM2014.DOC 2014
3
Site Preparation
In order to maximize operating efficiency and performance, the following areas should be observed at the site-planning stage:
- The room should be surrounded with a vapor seal to eliminate moisture migration through the building structure. Windows should be sealed and at least double-glazed to prevent sweating. All door jams should fit tightly and should not have any grilles in them. Polyethylene film type ceiling, vinyl wallpaper or plastic based paint on the walls and slabs are recommended to minimize absorption and transmission of moisture into the room.
- Owing to a generally small population, a typical room should have fresh air kept at only about 5% of the re-circulated air. This provides enough ventilation for personnel and pressurizes the room to prevent dust from entering through leaks. The incoming fresh air must be filtered very closely, and preferably pretreated. Otherwise heating, cooling, humidifying and dehumidifying loads of the incoming fresh air should be taken into account in determining total loading requirements.
Series 7 Installation Manual
Location Consideration
Positioning of Indoor units
The Series 7 unit is designed for mounting on a vertical wall. Care should be taken to ensure that the supply and return air-paths are not blocked by equipment.
The room layout should provide 508mm (20”) service clearance in the front of the unit for the routine service and maintenance.
Positioning of Condensing Unit
The condensing unit should be located as close to the indoor unit as possible. From a security and environment standpoint, the condensing units should be installed away from public access and occupied spaces where low ambient sound level is required.
In order to avoid short circuit and inter unit re-circulation, condensing units should be located at least 1m (3.3 ft.) away from any walls, obstructions or adjacent units. To ensure maintenance-free operation, condensing units should be located away from the areas that are continuously exposed to loose dirt and foreign materials that may clog the coil.
The condensing units should be firmly secured on steel supports or concrete plinths.
S7-IM2014.DOC 2014
4
Positioning of Remote Controller Unit or Thermostat
The remote mounted controller or thermostat should be located in an easily accessible area within reach of operating personnel. Consideration should be given to interconnecting wiring between indoor unit and controller. (Cables supplied pre-made from factory when unit is ordered with M52 controller). The maximum distance between indoor unit and controller should be 15 ft. (4.5 M)
Electrical Installation
Power Feeding
All models are fitted with a 3-terminal connection block, for live, neutral and earth connections, which are located at the lower right corner of the power panel.
Series 7 Installation Manual
The power cables should be sized in accordance with local and national codes. Refer to the unit nameplate for circuit ampacity, and wiring diagrams packed with each unit.
Interconnecting Wiring M52 only
Pre-made control cable sets are supplied with each unit for connecting both the outdoor unit and remote mounted controller to the indoor unit. All connectors are terminated with standard crimp connectors. Each cable will be clearly marked and care should be taken to ensure cables are connected correctly. See drawing No. S7ED500A – Interconnecting Wiring
Pipe Installation
Condensate Drain
For proper drainage a P-trap MUST be installed. Total height for the trap should be measured from the bottom of the drain pan (4” above unit bottom), to the bottom of the “U” in the trap. Minimum recommended height is 3.5” to ensure proper drainage.
Refrigerant Piping
Good practice should always be followed when connecting refrigerant piping in direct expansion systems. As many of the operational problems encountered in a refrigeration system can be traced back to improper design and installation of refrigerant piping, it is essential that the following guidelines be observed:
S7-IM2014.DOC 2014
5
Series 7 Installation Manual
- Use clean and dehydrated refrigeration quality tubing with both ends sealed.
- Cut and form tubes carefully to avoid getting dirt or metal particles into the refrigeration lines. Never use a hacksaw to cut the tubing.
- Once the system is open, complete the work as quickly as possible to minimize ingress of moisture and dirt into the system. Always put caps on ends of tubes and parts not being worked on.
- To prevent scaling and oxidation inside the tubing, pass an inert gas such as nitrogen through the line while carrying out brazing, silver soldering or any other welding processes.
- It is recommended that quality refrigeration solder (95% tin, 5% silver) is used for its excellent capillary action.
- Use minimum amount of solder flux to prevent internal contamination of the piping. Use flux with care as it is usually acidic in nature.
- Install a trap on the bottom of a vertical riser of the suction lin e and one every 6m (20ft.) in elevation to collect refrigerant and lubrication oil during off cycle.
- Insulate the suction line. Insulate liquid lines that may be subjected to high heat gains.
- Design and arrange refrigerant piping for the evaporator in such a way that it minimizes pressure drop to 3 psig and allows adequate velocity of refrigerant to prevent oil trapping. Recommended pipe sizes are tabulated as follows:
Recommended Pipe Size for Remote Condenser
Models 7A1.5 7A2.0 7A2.5 Liquid Line
25 ft. equivalent pipe length 3/8” 3/8” 3/8” 50 ft. equivalent pipe length
Suction Line
25 ft. equivalent pipe length 5/8” 5/8” 5/8” 50 ft. equivalent pipe length
Consult Factory for additional distances
3/8” 3/8” 3/8”
5/8” 3/4” 3/4”
Evacuation
The procedure for leak testing and evacuation of the system is as follows:
S7-IM2014.DOC 2014
6
Series 7 Installation Manual
1. Connect a gauge manifold to the compressor suction and liquid service valves.
2. Open all service valves.
3. Charge the system with dry nitrogen to approximately 150 psig.
4. Leave pressure in system for at least 12 hours. If pressure holds, continue with next step. If the pressure drops detect and seal leak before continuing.
5. Release all pressure.
6. Connect a vacuum pump to the suction and liquid service valves with refrigerant or high vacuum hoses. Provide an isolating valve and a pressure gauge for pressure checking.
7. Evacuate the system to an absolute pressure not exceeding 1500 microns. Break the vacuum to 2psig with dry nitrogen. Repeat the evacuation process and then re-break the vacuum with dry nitrogen.
8. Open the liquid and suction ports. Evacuate to an absolute pressure not exceeding 500 microns. Let the vacuum pump run without interruption for minimum two hours.
9. Stop the vacuum pump. Let the system remain in vacuum for 30 minutes. If the vacuum holds, break the vacuum and weigh in the system charge with vapor R22/R407C (see nameplate for operating gas) through the suction side of the compressor. If the vacuum doesn’t hold, repeat leak test and continue from the top.
10. Allow the pressure to equalize.
Head Pressure Control System
For condenser or condensing units, possibly subjected to extremely low ambient temperatures, it is recommended that a head pressure control system be installed to avoid starving the evaporator coil resulting in oil logging; short cycling by low pressure control; reduction of the system capacity and erratic expansion valve operation.
A drop in the condensing pressure often occurs in air-cooled systems as a result of low ambient conditions encountered during fall-winter-spring operation. Head pressure control renders part of the condenser surface inactive. The reduction of active condensing surface results in a rise in condensing pressure and hence provides a sufficient liquid line pressure for normal system operation. The head pressure control system allows operation at extremely low ambient te mperature down to -40°F.
S7-IM2014.DOC 2014
7
Series 7 Installation Manual
ClimateWorx uses a single valve head pressure control, with a heated receiver for factory ordered condensers. The OROA is located in the liquid drain line between the condenser and the receiver, and has a bypass line from the hot gas line.
During periods of low ambient temperature, the condensing pressure falls until it approaches the setting of the OROA valve. The valve (non-adjustable) then throttles, restricting the flow of liquid from the condenser. This causes refrigerant to back up in the condenser thus reducing the active condenser surface. This raises the condensing pressure. Since it is really the receiver pressure that needs to be maintained, the bypass line is required to heat up the cold liquid being passed by the OROA. Thus the liquid reaches the receiver warm and with sufficient pressure to assure proper expansion valve operation. As long as sufficient refrigerant charge is in the system, the valve modulates the flow automatically to maintain proper receiver pressure regardless of outside ambient.
Charging
When head pressure control is utilized, there must be enough refrigerant to flood the condenser at the lowest expected ambient and still have enough charge in the system for proper operation. After completing the evacuation procedures follow these guidelines for charging:
1. Close the main power and allow the compressor crankcase heater to operate for at least one hour.
2. Connect the gauge manifold to both suction and liquid service valves, with the common connection
to the refrigerant drum. Purge the lines and open the refrigerant drum vapor valve.
3. Start the compressor using the test mode to energize the main fan and compressor.
4. Open the suction connection on the gauge manifold. Modulate the rate of charging with the gauge
manifold valve. Watch the discharge pressure closely during the charging operation to ensure that the system is not overcharged. It is a good practice to weigh the amount of gas added.
5. Charge the system until the sight glass is clear of bubbles. The system is now correctly charged for
operating under head pressure control at the ambient temperature charging is being carried out.
6. If the system is designed to operate at ambient belo w the ambient that exists during the charging, additional
charge will have to be added now.
7. Read from the following table the percentage of condenser to be flooded at charging and that at expected
minimum ambient temperature, then calculate the difference:
Ambient Temperature in °F Percentage of Condenser to be Flooded
70 0 65 0 60 10 55 24 50 33 45 41 40 46 35 52
S7-IM2014.DOC 2014
8
Series 7 Installation Manual
30 55 25 59 20 62 10 66 0 70
-10 73
-20 76
-30 77
-40 79
8. The flooded condenser capacity on all Series 7 condensing units is 4.4 lbs.
9. Multiply the value found in Step 8 by the difference in percentages calculated in Step 7; this gives the
additional charge needed.
10. Fill in the required charge to the receiver.
Normal Charging
Proper performance of the system depends largely on proper charging. Adhere to the following guidelines for charging:
1. Close the main isolator and allow the compressor crankcase heater to operate for at least one hour.
2. Connect the gauge manifold to both liquid and suction service valves, with a common connection
to the refrigerant cylinder. Purge the lines and open the refrigerant cylinder vapor valve.
3. Start the compressor using the test mode to energize the main fan and compressor valve.
4. Open the suction connection on the gauge manifold. Modulate the rate of charging with the gauge
manifold valve. Watch the discharge pressure closely during the charging operation to ensure that the system is not overcharged.
5. Charge the system until the sight glass is just clear of bubbles.
6. Compare the temperature of the liquid line leaving the condenser with the saturation temperature
equivalent to the condensing temperature. Continue charging until the liquid line temperature is approximately 5°F below the condensing temperature.
Operating the Thermostat
S7-IM2014.DOC 2014
9
Setting the Current Day and Time
1. Press the CLOCK Button. The display will flash a day of the week.
2. Press the up or down arrow buttons until the current day show s.
3. Press the CLOCK button again. The display will flash the hour. (Note the AM/ PM indicator.)
4. Press the up or down arrow buttons until the current hour shows.
5. Press the CLOCK button again. The display will flash the minutes.
6. Press the up or down arrow buttons until the current minutes show.
7. Press the CLOCK button and the current day and time are now set. * Note: If a button is not pushed in 15 seconds, the thermostat will automatically return to normal
operation.
Setting your Program Temperatures
With your specific program determined, you are ready to begin programming. You will now enter the individual program period temperatures for the heating program.
1. Press the MODE button until HEAT is displayed.
Series 7 Installation Manual
2. Press the SET TEMP button. The first program period (Morning) will be displayed.
3. Press the up or down arrow buttons to adjust that program period’s temperature for heating.
4. Repeat Steps 2 and 3 for the Day, Evening and Night program periods. Remember, if your
thermostat was set for two program periods, you will only have to repeat Steps 2 and 3 for the Night program period.
5. Press the MODE button until COOL is displayed. You now will enter the indiv id ual program period
temperatures for the cooling program.
6. Repeat Steps 2, 3 and 4 for the cooling temperatures.
7. Press the MODE button until your desired mode of operation appears: HEAT- AUTO- OFF- COOL.
8. Press the RESUME button to return to normal operation.
Note: If a button is not pushed in 15 seconds, the thermostat will automatically return to normal operation. You may go back into the programming portion simply by repeatedly pressing the SET TEMP button until you get back to where you left off.
Setting your Program Times
Referring to your Schedule Planner, you now will enter the times for the program periods.
S7-IM2014.DOC 2014
10
Series 7 Installation Manual
1. Press the PROGRAM button. The display will flash a day of the week.
2. Press the up or down arrow buttons to select the day you wish to program. (We suggest starting with Monday.)
3. Press the PROGRAM button. The display will flash the hour of the first period (Morning). (Note the AM/ PM indicator.)
4. Press the up or down arrow buttons to adjust the desired hour for the first program period.
5. Press the PROGRAM button again. The display will flash the minutes.
6. Press the up or down arrow buttons to adjust the desired minutes for the first period. (Note th e minutes are in increments of 10.)
7. Repeat Steps 3- 6 for the Day, Evening and Night periods. Rememb er that if your thermostat was set for two program periods, you will only have to repeat Steps 3- 6 for the Night period.
8. After entering the Night period, press the PROGRAM button. COPY will be displayed. The copy function will allow program times to be copied to sequential days. If you do not wish to copy the program times to another day (or block of days), proceed to Step 11.
9. Press the up or down arrow buttons to select the next individual day, or block of days, to copy the program times to.
10. Press the PROGRAM button to copy the program times to the selected days of the week.
11. Repeat Steps 1- 10 for any remaining unprogrammed days of the week.
12. When finished, you can verify th at all program periods are programmed correctly by repeatedly pressing the PROGRAM button. When COPY appears, press the PROGRAM button to skip to the next day.
* Note: If a button is not pushed in 15 seconds, the thermostat will automatically return to normal operation. You may go back into the programming portion simply by repeatedly pressing the PROGRAM button until you get back to where you left off.
Temperature Override
Temporary Override (3 hours)
You may change the temperature setting temporarily at any time without affecting the program. Press the up or down arrow buttons. The current event temperature and mode of operation will be displayed. Press the up or down arrow buttons again to adj ust the temperature. This temperature will be maintained for three hours. To cancel, simply press the RESUME button.
Temporary Override with Keyboard Locked (1 hour) (300- 225, 300- 227, 300- 229)
S7-IM2014.DOC 2014
11
Loading...
+ 25 hidden pages