Climate Technologies Bonaire 3, Bonaire 4 Installation Instructions

Part 5442225 issue E
General Information &
Installation Instructions
Read general information instructions first followed by
the relevant installation instructions.
3 & 4 STAR DUCTED GAS CENTRAL HEATER
ABN 13 001 418 042
Telephone No.: 61 8 8307 5100 Fax No.: 61 8 8283 0401
2
Part 5442225 issue E
I
General Information
Name of appliance: Bonaire & Pyrox 3 & 4 Star Gas Central Heater
Models: MB314iNG, MB320iNG, MB330i NG, MB330i NG X/A, MB314e
NG, MB320e NG, MB330e NG, MB414i NG, MB420i NG, MB420i NG X/A, MB430i NG, MB430i NG X/A, MB414e NG, MB420e NG, MB430e NG, MB430e NG X/A.
Gas Consumption: 14i unit – 60MJ/h
20i unit – 80MJ/h 30i unit – 120MJ/h
Burner Pressures:
Gas Connection: Connection on gas valve is via ¾” BSP (female) flare nut
onto which the inlet pipe and ¾” manual shut-off valve (Refer to AS/NZS 5601) Use only gas copper pipe which complies with AS 1432 Type B.
When connecting the gas supply inlet pipe to the gas valve, hold the connection nipple on the valve with a spanner while tightening the inlet pipe compression nut. This ensures the nipple is not over tightened. Cracked
gas valves or regulator castings due to over tightening during installation or service are not the manufacturerʼs responsibility.
Statutory Requirement: This product must be installed only by
an authorised person and in accordance with the current editions AS/NZS 5601 & AS/NZS 3000.
DO NOT OPERATE THIS APPLIANCE BEFORE READING THIS GENERAL INFORMATION & INSTALLATION BOOKLET.
Checking Supply & Burner Pressures:
Refer to data plate on the product for burner pressures.
NOTE: All wiring coming out of the unit (mains power lead, thermostat wiring etc…) must be fully extended and securely anchored using the cable tie provided.
3
Part 5442225 issue E
General Information (cont)
I
Items to be supplied by the Installer:
- Suitable base material for heater.
- Platform/Walkway for roof installation (heat resistant material not required).
- Electric lighting above the central heater and switch to be placed next to the access opening.
- AGA approved manual shut-off valve (3/4” Natural Gas Heater).
- AGA approved metal flue pipe and required elbows where a flue pipe with bends is present. AGA approved flue cowl for the flue pipe.
- At the completion of the installation compliance certificates must be completed for gas & electrical work.
Locations:
1) Do not install the heater in a location where combustible vapours from flammable or combustible liquids may be present as these can be drawn into the heater and ignited.
2) Do not install the heater in any location where noise from its operation may disturb occupants or neighbours. Before installing this product consider placement of this unit away from areas of the home where occupants will sleep or relax, such as bedrooms, lounge and dining rooms. Check local council regulations to ensure compliance.
3) Do not install the heater downstream of an evaporative air conditioner, air washer or refrigeration coil.
DESCRIPTION OF OPERATION OF ELECTRONIC CONTROL MODULE.
The design of the control module conforms to the Australia Gas Association AS4622 and AS4625 Standards and is classified as a Class 2Ca device. It receives instructions via a wired or RF Controller/thermostat.
Electrical rating:
240V, 50 Hz, 10 VA input.
Start up sequence for Central Heater:
1) Turn gas supply on.
2) Turn on power supply to unit.
3) A 2-second self-diagnosis is performed and the fans will run for a few seconds. If a successful diagnosis is completed the unit will then go to stand-by mode.
NOTE: Where Navigator RF thermostat is used this must be configured (paired) with the transceiver before the unit can be operated refer to section 7.
4) To start unit set the thermostat temperature above the room temperature.
5) Combustion air fan will commence operation.
4
Part 5442225 issue E
General Information (cont)
I
6) When combustion fan reaches required pressure level, the pressure
switch closes.
7) A further 20 seconds elapses as purge time.
8) Igniter function commences.
9) Gas valve is energised allowing 4 seconds for the gas to ignite.
10) If flame is detected by a sensor. The gas valve remains energised.
11) Room air fan will commence 20 seconds after the gas valve is
energised.
12) At the end of the heating cycle, the room air fan will have a run down
period of 80-180 seconds.
13) Should the flame not ignite after the 6th attempt, the unit will go to
lockout. Reset unit to restart.
14) To reset the unit, switch the mains power OFF then wait 2 seconds
before switching the power back ON or with the navigator control a error code is displayed when a lockout has occurred. When the word “enter” appears in the display press the enter key to reset the unit.
CHECKING THE SYSTEM PERFORMANCE
Having set the gas pressure check the discharge temperature of the air in the discharge duct to confirm the correct operation of the central heater. For best performance, the discharge temperature should be 50C – 60C when measured 300mm from the appliance inside the discharge air duct.
Checking the correct operation of the heater:
1) Using the thermostat, switch the heater OFF. Wait for the room air fan
to cease operation (approximately 80 -180 seconds), then switch ON again to recheck the starting sequence.
2) Using the thermostat, switch the heater OFF unless the customer
requires that it be left running.
3) Before leaving, make sure that the customer understands how to
operate the heating system.
4 Star (MB4XXX) product will not operate unless the thermistor has been connected and the sensor installed correctly in the air discharge duct.
5
Part 5442225 issue E
General Information (cont)
I
Special Conditions:
Blocked fresh air inlet or flue outlet:
The unit will go to lockout. ʻWhen the restriction is removed the unit can then be reset. NOTE: If the fresh air inlet, the flue outlet is blocked or combustion fan is not operating correctly the red LED on the controller may not light-up. If this occurs, the unit will not commence the ignition sequence and will then lockout. The green LED will then flash the appropriate fault code.
Electric power loss: 3 star units – The unit will restart automatically if the manual
controller/thermostat is ON, once power is resumed. 4 star units – if a manual controller/thermostat is left switched ON, the unit will automatically lock-out when power is resumed. The reset procedure must then be followed to restart the unit. Once power is resumed.
Gas interruption:
A gas interruption will cause the unit to lockout. The Controller/thermostat must be reset after gas supply is re-established.
Controller diagnostic LED flash codes:
The controller will flash a coded message if an operation fault occurs. For 3 star product refer to the table listed on the appliance data plate for further details. For 4 star product refer to page 11-13 of this book or the service manual.
Normal Operation: 3 star units – Green LED will flash a single short flash (approximately 0.2
seconds/pulse) when in the idle state and flash one short pulse when calling for heat. Red LED will light-up when combustion fan is operating correctly. 4 star units – Green LED will flash four short pulses (approximately 0.2 seconds/pulse) when in the idle state and flash one short pulse when calling for heat. Red LED will light-up when combustion fan is operating correctly.
Trouble Shooting:
Check there is power and gas supplied to the heater.
Check thermostat set temperature is above room temperature.
Confirm thermistor is connected correctly installed in the air discharge
duct. (4 star models only)
Check that the power LED is lit on the controller. If it isnʼt check power is
available at the GPO, check the circuit breaker and check the fuses on electrical panel within the unit.
If the heater will still not operate, the safety shut down device within the
heater may have locked the control. Reset the control.
If the heater still fails to operate correctly, contact service.
For Service Australia Wide see the contact details on the rear cover.
6
Part 5442225 issue E
1
Starting Collars
Starting collars are manufactured from pre-painted or galvanised steel and supplied as a flat part
Use pliers to bend the four stop tabs out. Be sure to bend them out to at least a 90 angle.
Four ducting retention hooks are provided to assist with fixing duct to collar.
7
Part 5442225 issue E
2
Gas supply and manual shut-off valve
3
Product Dimensions
All gas piping must comply with AS/NZS 5601. Piping must be correctly sized to
suit product supply requirements and ensure a minimum supply pressure of
1.13kpa (natural gas). The maximum gas consumption for this product can be found on the product label affixed to the unit. An AGA approved manual shut-off valve must be installed in the gas supply line for this unit. The valve should be installed in a suitable location adjacent to the unit which will ensure easy access for service.
Once an A.G.A approved manual shut-off valve is fitted it may be positioned horizontally or vertically subject to location of heater and ease of access.
External products Internal products
8
Part 5442225 issue E
5
4 Star Thermostat Connection
4
3 Star Thermostat Connection
For manual thermostat installation and wiring connection information, refer to instruction sheet supplied with the thermostat.
For navigator thermostat control installation refer to the navigator user manual.
Where a 2 wire manual thermostat is used the connecting wiring used must have a minimum cross sectional area of 0.75mm or greater.
For manual thermostat installation and wiring connection information refer to instruction sheet supplied with thermostat.
For navigator thermostat control installation refer to the navigator user manual.
Where a 2 wire manual thermostat is used connecting wiring used must have a minimum cross sectional area of 0.75mm or greater.
9
Part 5442225 issue E
6
4 Star Zone Connection and Dual Cycle cooling
The control module in every 4 star heater has integrated zone outputs. This control has four relay switched outputs for connection of zone dampers. The control will manage zone outputs in accordance with commands sent by the Navigator thermostat. Zone control can be expanded from four to eight if required by purchasing an expansion card and a connection cable.
The installer is responsible for all electrical cabling and sizing and compliance with AS/NZS 3000 (latest edition).
Zone Power Supply:
Zone power can be taken from the 24VAC supply on the control by connecting as shown below or from an external supply.
Zone Output Connections:
Depending on the desired configuration each zone output has a common (COM) connection and a normally open (NO) or normally closed (NC) as shown. Connect either to NC or NO as required.
Enabling Zone Control:
To activate zone control and zone expansion board installation parameters must be enabled. Refer to the Navigator digital thermostat user manual for instructions. For each zone required, the control parameter number must be set for the total number of zones required (e.g. for “4” zones set parameter to “4”). NOTE: For zone expansion board installation, refer to instructions supplied with expansion board kit.
Dual Cycle Cooling:
The control has available a 24 volt only connection for installations where a refrigerated cooling coil is installed. To activate this function a installation parameter must be enabled using the Navigator thermostat (refer to Navigator thermostat user manual). NOTE: For cooler connection details, refer to installation instructions supplied with the cooler.
10
Part 5442225 issue E
7
Installation of Navigator Controller
BEFORE STARTING
Before attempting to use the setup instructions for the controls system, make sure the transceiver (remote control units only) or the wired low voltage cable is connected, batteries have been correctly installed in the Navigator Controller (remote control units) and the 240 volt power has been turned on to the product.
NOTE: Do not run the low voltage loom in long parallel runs with 240V mains cables. Keep the low voltage loom 200mm away from any long runs of mains wiring. Cross over mains wiring at right angles. Do not use existing access holes in wall cavities where 240V mains wiring exist. Drill a new access hole 200mm from the existing hole.
INSTALLATION
Where the control is using the thermostat for operation, it must be installed approximately 1.5 metres above the floor level on a room wall which is most commonly used for best average sensing.
Secure the Navigator Controller cradle to the wall using the screws and plugs provided.
For hard wired versions drill an access hole through the cradle to bring the cable into the control. Once connected snap the control into the cradle.
For the remote Navigator Controller (wireless) install batteries and slide the Navigator Control into the cradle. The Navigator Controller should remain in the cradle during normal operating conditions for optimum temperature thermostat control.
Do not locate Navigator Controller near concealed hot or cold water pipes, warm air ducts, radiators, sunlight, televisions or draughts from hallways, stairways and fireplaces or external walls. These can all affect the temperature.
Remote Control Units ONLY
Ensure the transceiver has been installed at least 500 mm clear of all metal masses. The transmissions between the remote Navigator Controller (wireless) and the unit control box are radio signals which are subject to interference. The primary causes for signal interference are:
Metal Construction buildings or metal masses near the antenna.
Incorrect location of the antenna
Cordless RF door bells
Other Faulty appliances
Navigator Controller too close to computers
Powerful radio scanners
11
Part 5442225 issue E
8
Installation of Navigator Controller
(cont)
INSTALLATION OF TRANSCEIVER
The transceiver cable connects to the control box as shown. Fully extend the transceiver cable (4 meters) and attach the transceiver housing to a solid surface such as a rafter or vertical column using the two screws provided. Avoid direct contact with metal surfaces. Connect the transceiver plug to one of the two thermostat connections on the control box. When the installation is complete and the power to the heater is turned on, a green LED in the transceiver case should be visible confirming it is connected correctly and is ready for pairing with a Navigator controller.
To ensure trouble free operation, the transceiver housing & connecting cable should not be installed within 200mm of any power cables or other radio transmitting devices. The transceiver housing should be placed 1m away from any metal object.
Do not screw the transceiver to the back of the control box; it must be run into roof space.
PAIRING THE NAVIGATOR CONTROLLER (Remote Only)
The BONAIRE Navigator Controller and transceiver does not have any pairing information when they are delivered from the factory. On the first power up, the transceiver will request to PAir with Navigator Controller for period of a 30 min window and its green light will be illuminated. If it does not PAir within that time, it will PAir on the next power up. Put the Navigator Control in pairing mode -
1. Press & hold the ENTER button for 3 seconds.
2. Press the Heat/Cool, Mode & Setup buttons in
sequence. The display will flash “PAir”.
3. After a few seconds the Navigator Controller displays
the “ro XX” (“XX” is the unique serial number. For example “ro 22”). It will also display the strength of the signal.
4. Press the ENTER button to pair the transceiver and the
Navigator Controller.
NOTE: Wait until the backlight turns off and press any key after 2 minutes.
5. Press the ON/OFF button to go to the main display.
RF Transceiver & cable
assembly
   

12
Part 5442225 issue E
9
Multiple Navigator Controller 9 Operation
OPERATION OF MULTIPLE NAVIGATOR CONTROLLERS
The Navigator control system is capable of supporting up to 4 controllers. By default, the system will allow one controller to control the appliance or multiple appliances. Certain parameter set ups must be made to configure multiple controllers. The options available are
2 wired Navigators only
1 wired Navigator and up to 3 Remote Navigators.
MULTIPLE WIRELESS REMOTE CONTROLLERS
In a multiple Navigator controller system, the other controller may be joined to a master by putting the slave controller into a PAir mode. It will then send out a PAir request to the master controller. The master controller is then put in a JOin state and can then join the request to set up a Navigator system.
JOINING NAVIGATOR CONTROLLERS (JO
IN
)
Controllers requesting to JOIn another controller in the Navigator system, can be put in the join mode as follows.
1. To enter the JOIn state, press and hold the ENTER
button for 3 seconds & release.
2. Press and release the, MODE, HEAT/COOL and SETUP buttons in sequence.
3. The master wireless Remote controller should display JOin state to receive a command from the other handset to JOIn the Navigator system.
4. The slave controller should be placed into a Pair state
to join with the master controller. The slave controller should display Pair.
13
Part 5442225 issue E
10
Accessing Navigator Controller Installer Setups
NOTE: The Navigator Controller must be in the OFF
status to change the parameters.
1. Press and hold the ENTER button for 3 seconds.
2. Press & release the Ï then Ð then SETUP
buttons to enter the installer set up mode.
3. The word “InST”, ”nSTA”, ”STAL”, ”TALL”, ”ALLE”, ”LLEr” (Installer) scrolls across the upper part of the display. Press the ENTER button.
4. When the CodE “11 11” appears, input the code “98 76” using the Ï and Ð buttons to select each digit, and press the ENTER button to move to the next digit
NOTE: The Navigator Controller will display
the abbreviated name of the appliance such as “EC XX” for Evaporative Cooler, “HE XX” for Central Heater or “th XX” for the Navigator controller settings (“XX” is the unique serial number). For example “th 06”.
5. Use the Ï and Ð buttons to scroll to the “th XX” and then press the ENTER button to access Navigator Installer setup.
The display will now show digits “1 1”. The lower left digit is the parameter number and the lower right digit is the parameter option value. Parameter numbers and option values can be found in the Navigator Controller Installer Parameters Table.
6. To select the parameter number use the Ï and Ð buttons to find the desired parameter and press
ENTER.
7. Adjust the option value (See Navigator Parameter Table) to the required value and press ENTER. This will set the option value and return you to the parameter number selection menu.
8.
When finished Press the ON/OFF button to exit.
Parameter
Options value
14
Part 5442225 issue E
11
Navigator Controller Parameters Table
th parameter Table (“th XX”)
Parameter Description Default Definition Options Values
1
Un switched Zone Option
1
Tells system if there is a common zone present
1= common zone present. 0= no common zone (Note that a cooler is usually installed into the common zone)
2
Switched
Zones
15
To display all available switched zones
15= Zone 1, 2,3 & 4 6 = Zone 2&3 127 = 8 Using ZONE and ÐÏ buttons whilst in this parameter will set the number
3
Temperature Display zone
0
Selects which zone the Navigator will display the temperature of
0 –Common zone 1-8 Zones 1-8
4
Temperature
Measurement
-Un switched Zone option
1
Determines if the navigator is measuring the temperature in the common zone
1Measuring common zone. 0= Not measuring common zone
5
Temperature
Measurement
- Switched Zones
15
Determines which of the switched zones the Navigator is measuring,
15= Zone 1, 2,3 & 4 6 = Zone 2&3 127 = 8 Using ZONE and ÐÏ buttons whilst in this parameter will set the number
6
Not used
0
7 Not used
8
RF Network
(RF handset
only)
0
The current RF network number
0 = not assigned Any other = actual network
0
Not used
0
15
Part 5442225 issue E
12
Accessing Ducted Gas Central Heater (DGCH) Installer Setup
NOTE: The Navigator Controller must be in the
OFF status to change the parameters. (Except Fan Speed)
1. Press and hold the ENTER button for 3 seconds.
2. Press & release the Ï then Ð then SETUP
buttons to enter the installer set up mode.
3. The word “InST”, ”nSTA”, ”STAL”, ”TALL”, ”ALLE”, ”LLEr”(Installer) will scroll across the upper part of the display. Press the ENTER button now to access.
4. When the CodE “11 11” appears, input the code “98 76” using the Ï or Ð buttons to change each digit, and press the ENTER button to move on to the next digit.
NOTE: The Navigator Controller will display
the appliance controller ID “HE XX” for a central heater (“XX” is the unique ID number).For example “HE 44”.
5. Press the ENTER button when “HE XX” appears.
The display will now show digits “1 1”. The lower left digit is the parameter number and the lower right digit is the parameter option value. Parameter numbers and option values can be found in the Ducted Gas Central Heater Installer Parameters Table.
6. To select the parameter number use the Ï or Ð buttons to find the desired parameter and press
ENTER.
7. Adjust the option value (See DGCH parameter table) to the required value and press ENTER. This will set the option value and return you to the parameter number selection menu.
8. When finished press the ON/OFF button to exit.
Parameter
Number
Options Value
Loading...
+ 33 hidden pages