ClimateMaster Tranquility 97B0107N01, Tranquility Digital Quick Start Manual

Page 1
Tranquility® Digital
Quick Start Guide
97B0107N01
Residential Packaged and Split
DIGITAL Geothermal Heat Pumps
With iGate™ and vFlow™ Technology
Rev.: January 25, 2016
Step Title Page 1 Thermostat Confi guration 3 Staging 3 Auxiliary Heat 3 Programming 3 2 System Confi guration 4 Airfl ow Selection 4 Option Selection 4 Unit Confi guration 4 Pump Confi guration 5 Valve Confi guration 5 3 Accessory Confi guration 5 Air Filter 6 Humidifi er 6 UV Lamp 6 Air Cleaner 6
Table of Contents
Step Title Page 4 Input Dealer Information 6 5 Humidity Confi guration 6 6 Temperature Algorithm 6 7 Demand Reduction Confi guration 7 8 Unit and System 8
Pre-Start Checklist 9 Unit Start-up Procedure 8
Page 2
This page was intentionally left blank.
Page 3
Tranquility® Digital Quick Start Guide
Rev.: January 25, 2016
ClimateMaster Digital units are shipped from the factory with default values for key parameters such as air fl ow and water fl ow settings. The unit will operate with these default settings, however, the installer may wish to customize these settings to better match installation conditions. This guide will walk the installer through those settings. More detail is available in the unit IOM.
The fi rst step is to enter the Installer Menu. The fi rst time the unit is powered up the ATC series thermostat display will take you to the Installer’s Menu. Or you can enter the Installer’s Menu anytime by placing the thermostat/system in the “OFF” mode, then holding the “UP” and “DOWN” arrow keys simul­taneously for 5 seconds. Once in the Installer’s Menu the following menus will appear.
Step 1 Thermostat Confi guration
Upon initial power up, the communicating thermostat will prompt the installer for the thermostat confi guration settings.
The software version of the thermostat and DXM2 board it is connected to, are displayed on the thermostat Installer Screen. If the DXM2 version is not displayed, the ATC ther­mostat is of an earlier version.
2.0 Installer Menu Settings
2.1 INSTALLER MENU SETTINGS ACCESS
The Installer Settings can be accessed at any time from the Main Operating screen by holding the up/down arrows simul­taneously for 5 seconds while the thermostat is in OFF Mode.
2.2 THERMOSTAT CONFIGURATION
Upon initial power up, the communicating thermostat will prompt the installer for the thermostat confi guration settings.
Model number and software version of thermostat and software version of connected DXM2 are also displayed on this screen.
AUXILIARY HEAT
Adjust the Auxiliary Heat options using the up/down arrow buttons. Press the center button to save changes.
• Electric (default) – for control of a system with electric auxiliary heat
• Multi-Fuel – for control of a system with furnace for auxiliary heat
• No Auxiliary Heat – for control of a system with no auxiliary heat
THERMOSTAT
CONFIGURATION
ELECTRIC
MULTI FUEL
NO AUXILIARY HEAT
SELECT OPTION
PREVIOUS SAVE
PROGRAMMING
Adjust the Programming options using the up/down arrow buttons. Press the center button to save changes.
• Programmable (default) – enables 7-day programming
• Non-Programmable – disables 7-day programming
• Night Setback – enables night setback
programming
NOTE: When the thermostat is confi gured for nonprogrammable mode, the Display Date and Time setting defaults to NO.
THERMOSTAT
CONFIGURATION
PROGRAMMABLE
2.2.1 STAGING
Adjust the staging option using the up/down arrow buttons. Press the center button to save changes.
• Single Stage – for control of a single stage compressor applications
• Multi-Stage (default) – for control of multi- stage compressor applications
THERMOSTAT
CONFIGURATION
SINGLE STAGE
MULTI STAGE
SELECT OPTION
PREVIOUS SAVE
NON PROGRAMMABLE
NIGHT SETBACK
SELECT OPTION
PREVIOUS SAVE
3
Page 4
Tranquility® Digital Quick Start Guide
Rev.:January 25, 2016
Step 2 System Confi guration
Use System Confi guration to adjust critical equipment set- tings. The System Confi guration information will be auto- matically obtained from each communicating control in the system.
INSTALLER SETTINGS
THERMOSTAT CONFIG
SYSTEM CONFIG
ACCESSORY CONFIG INPUT DEALER INFO HUMIDITY CONFIG TEMPERA TURE ALGORITHM DEMAND REDUCTION CNFG SERVICE MODE RESTORY DEFAULTS
ATC32U01 SELECT OPTION
PREVIOUS
Note 1: The Air fl ow Selection menu will not be present if the connected communicating control is confi gured for No blower.
Note 2: The Pump Confi guration menu will not be present if the connected communicating control is confi gured for OTHER.
CFM
AIRFLOW SELECTION
HEAT STAGE 1 600
HEAT STAGE 2 750 AUXILIARY HEAT 850 EMERGENCY HEAT 850 COOL STAGE 1 525 COOL STAGE 2 700 COOL DEHUMID 1 425 COOL DEHUMID 2 550 CONTINUOUS FAN 350 HEAT OFF DELAY 60 COOL OFF DELAY 30
PREVIOUS NEXT
OPTION SELECTION
Adjust the Option settings using the up/down arrow buttons. Press the center button to select each item.
• Motorized Valve (defaults stored in control) –
valid range: Off, On
• Compressor ACSD (default stored in control) –
valid range: 5 to 8 (in 1 minute increments)
NOTE: The Compressor Anti-Short Cycle Delay setting provides equipment protection by forcing the compressor to wait a few minutes before restarting.
OPTION SELECTION
MOTORIZED VALVE OFF
Note 3: The Valve Confi guration menu will not be present if the connected communicating control is confi gured for OTHER.
SYSTEM CONFIGURATION AIRFLOW SELECTION OPTION SELECTION UNIT CONFIG TE026 PUMP CONFIGURATION
SELECT OPTION
PREVIOUS SAVE
AIRFLOW SELECTION
Adjust the airfl ow settings for each system operating mode using the up/down arrow buttons. Press the center button to select each item.
• Airfl ow Settings (default stored in control) –
valid range: obtained from control (in 25 CFM increments)
• Blower Off Delay (default 60 seconds) – valid range: 0 to 255 seconds (in 5 second increments)
NOTE: The Airfl ow Settings will only be present if the connected communicating control is confi gured for ECM blower.
4
COMPRESSOR ASCD 5
PREVIOUS NEXT
UNIT CONFIGURATION
The controller should be confi gured from the factory for its unit model. However, it is a good idea to review the confi guration to ensure it is correctly confi gured.
NOTICE: If installing MULTIPLE vFlow™ Internal VS Flow Controller units (in parallel) on one loop, ALWAYS select ‘VS PUMP PARALLEL’ under Installer Settings
System Confi g Unit Confi g Loop Confi g. Also, follow proper pump selection procedures for parallel pumping applications.
Adjust the Unit Confi guration settings including Heat Pump Family, Heat Pump Size, Blower Type, and Loop Confi guration using the up/down arrow buttons. Press the center button to select each item.
• Heat Pump Family (default stored in control) – valid range: TE, TZ, TES, TEP, TAH
• Heat Pump Size (default stored in control) –
valid range: depends on Heat Pump Family setting
• Blower Type (default stored in control) – valid range: NONE, PSC–2SPD, ECM, PSC–1SPD
Geothermal Heat Pump Systems
• Loop Confi g (default stored in control) – valid
NOTICE!
Page 5
Tranquility® Digital Quick Start Guide
Rev.: January 25, 2016
range: Other, VS PUMP SINGLE, VS PUMP PARALLEL, MOD VALVE, MOD VALVE MIN POS
THERMOSTAT
CONFIGURATION
SINGLE STAGE
MULTI STAGE
SELECT OPTION
PREVIOUS SAVE
vFlow™ PUMP CONFIGURATION
vFlow™ VS internal flow control pump can be controlled either through temperature differential (Delta T) or can be set to specific speed (fixed; % of full speed for each heat and cool stage).
Confi gure temperature differentials at the thermostat for vFlow™ units with an internal fl ow control pump.
Adjust the Pump Confi guration settings using the up/down arrow buttons. Press the center button to select each item.
• Heating Delta T (default stored in control) –
valid range: 4 to 12ºF (in 1ºF increments)
• Cooling Delta T (default stored in control) –
valid range: 9 to 20ºF (in 1ºF increments)
VARIABLE SPD INTERNAL
PUMP CONFIGURATION
LOOP OPTION SINGLE
PUMP CONTROL FIXED
HEATING STAGE 1 60% COOLING STAGE 2 75%
COOLING STAGE 1 50% COOLING STAGE 2 70%
PREVIOUS SELECT
If Pump Confi guration is set to ‘VS PUMP PARALLEL’, valid range changes to 50-90% (in 1% increments).
vFlow™ VALVE CONFIGURATION
Adjust the Valve Confi guration settings using the up/down arrow buttons. Press the center button to select each item.
• Heating Delta T (default stored in control) –
valid range: 4 to 12ºF (in 1ºF increments)
• Cooling Delta T (default stored in control) –
valid range: 9 to 20ºF (in 1ºF increments)
MODULATING VALVE
CONFIGURATION
DEG
HEATING DELTA T 8
COOLING DELTA T 15
Maximum Heat LWT (valid range based on specifi c model; refer to model IOM). Minimum Cool LWT (valid range based on specifi c model; refer to model IOM).
VARIABLE SPD INTERNAL
PUMP CONFIGURATION
LOOP OPTION PARALLEL
PUMP CONTROL DELTA T
HEATING DELTA T 7 F COOLING DELTA T 10 F
MAXIMUM HEAT LWT 80 F MINIMUM COOL LWT 40 F
PREVIOUS SELECT
To control vs pump by fi xed speed, select ‘Pump Control’, press save.
Default stored in control. Valid range: 15% - 90% (in 1% increments)
, use down arrow to select ‘Fixed’, and press to
PREVIOUS NEXT
Step 3 Accessory Confi guration
The ATC32 series thermostat can be confi gured to provide reminders to users when certain system maintenance is needed. A service message will fl ash at the top of the Main screen when a service timer expires to alert the user that it is time to service accessory options.
INSTALLER SETTINGS
THERMOSTAT CONFIG SYSTEM CONFIG
ACCESSORY CONFIG
INPUT DEALER INFO HUMIDITY CONFIG TEMPERA TURE ALGORITHM DEMAND REDUCTION CNFG SERVICE MODE RESTORY DEFAULTS
ATC32U01 SELECT OPTION
PREVIOUS
5
Page 6
Tranquility® Digital Quick Start Guide
Rev.:January 25, 2016
AIR FILTER
This feature displays an alert to remind the user to change the air fi lter after the selected time has passed. Adjust the Air Filter Reminder settings using the up/down arrow buttons. Press the center button to save changes.
• Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
• Calendar Time (default Off) – valid range: Off, 3 to 48 months (in 3 month increments)
HUMIDIFIER
This feature displays an alert to remind the user to change the humidifi er pad after the selected time has passed.
Adjust the Humidifi er Reminder settings using the up/down arrow buttons. Press the center button to save changes.
• Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
• Calendar Time (default Off) – valid range: Off, 3 to 24 months (in 3 month increments)
UV LAMP
This feature displays an alert to remind the user to change the UV lamps after the selected time has passed.
Adjust the UV Lamp Reminder settings using the up/down arrow buttons. Press the center button to save changes.
• Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
• Calendar Time (default Off) – valid range: Off, 3 to 48 months (in 3 month increments)
AIR CLEANER
This feature displays an alert to remind the user to clean the fi lter(s) after the selected time has passed.
Adjust the Air Cleaner Reminder settings using the up/down arrow buttons. Press the center button to save changes.
• Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
• Calendar Time (default Off) – valid range: Off, 3 to 24 months (in 3 month increments)
Step 4 Input Dealer Information
Enter/edit the Dealer Information settings, including Brand, Name, Model Number, Serial Number, Contractor Name, and Contractor Phone number, using the up/down arrow buttons. Press the center button to save changes.
Step 5 Humidity Confi guration
Confi gure humidity control settings (dehumidifi cation/ humidi- fi cation).
• Dehumidifi cation – This logic will communicate a Dehumidifi cation output when the humidity is greater than the setpoint (acts as a dehumidistat). The Dehumidifi cation output will not be communicated when the humidity is below the setpoint.
• Humidifi cation – This logic will communicate a Humidifi cation output when the humidity is less than the setpoint (acts as a humidistat). When the Humidifi cation output is active, the fan output will also be active. The Humidifi cation output will not be communicated when the humidity is above the setpoint.
• Both – Incorporates both Dehumidifi cation and Humidifi cation logic.
• None (default) – Dehumidifi cation and Humidifi cation outputs will not be communicated.
Step 6 Temperature Algorithm
Confi gure the logic the thermostat uses to meet the tempera- ture setpoints.
• Proportional Integral (default) – This logic will use a combination of temperature differential and operating time to determine the appropriate heating or cooling stages for operation (see NOTE 1).
• Proportional Integral (No Down Staging) – This logic includes the Proportional Integral logic, but in addition the logic keeps all active heating or cooling stages energized until the demand is fully satisfi ed (see NOTE 1).
• Differential – This logic will only use temperature differential to determine the appropriate heating or cooling stages for operation. This logic will keep all active heating or cooling stages energized until the demand is fully satisfi ed (see NOTE 2).
NOTE 1: The Proportional Integral options require fi rst stage heating or cooling to be active for a minimum of 5 minutes, before energizing second stage when confi gured for multi stage operation.
NOTE 2: The Differential option will activate fi rst stage heating or cooling when the temperature is more than the fi rst stage differential value (UM section 5.6.2.3), below or above the setpoint. Second stage heating or cooling will be activated when the temperature is more than the fi rst and second stage differential values combined, below or above the setpoint. Third stage heating will be activated when the temperature is more than the fi rst, second, and third stage differential values combined (UM section 5.6.2.3), below the setpoint.
Adjust the Humidity Control settings using the up/down arrow buttons. Press the center button to save changes.
6
Geothermal Heat Pump Systems
Page 7
Step 7 Demand Reduction Confi guration
Users may wish to take advantage of the Demand Reduction feature where utility companies offer special rates for demand reduction, or simply to save energy during certain time periods. Demand Reduction is activated by an input signal at the unit control board to reduce the electric load while peak utility rates are high. The Demand Reduction Confi guration mode selects which of the available unit control inputs is to be used as the activation signal. While a physical input signal is present at the selected input, the thermostat will implement load reduction by limiting operation or capacity.
Adjust the Demand Reduction Confi guration setting using the up/down arrow buttons. Press the center button to save changes.
• No Demand Reduction (default) – Demand Reduction operating mode will not be activated by a DXM2/CXM2 input.
• DXM2 Inputs – Assigns a DXM2 input to activate Demand Reduction operating mode.
Tranquility® Digital Quick Start Guide
Rev.: January 25, 2016
INSTALLER SETTINGS
THERMOSTAT CONFIG SYSTEM CONFIG ACCESSORY CONFIG INPUT DEALER INFO HUMIDITY CONFIG TEMPERA TURE ALGORITHM
DEMAND REDUCTION CNFG
SERVICE MODE RESTORY DEFAULTS
ATC32U01 SELECT OPTION
PREVIOUS
7
Page 8
Tranquility® Digital Quick Start Guide
Rev.:January 25, 2016
Start-Up Guide
Step 8 Unit and System Pre-Start Check List
BEFORE POWERING SYSTEM, please check the following:
UNIT CHECKOUT
Shutoff valves: Insure that all isolation valves are open. Line voltage and wiring: Verify that voltage is within
an acceptable range for the unit and wiring and fuses/ breakers are properly sized. Verify that low voltage wiring is complete.
Unit control transformer: Insure that transformer has the
properly selected voltage tap. Residential 208-230V units are factory wired for 230V operation unless specifi ed otherwise.
Loop/water piping is complete and purged of air. Water/
piping is clean.
Antifreeze has been added if necessary. Entering water and air: Insure that entering water and air
temperatures are within operating limits.
Low water temperature cutout: Verify that low water
temperature cut-out on the DXM2 control is properly set. (Only cut JW3 if you have anti-freeze protection to15°F (-9°C) in the loop)
Unit fan: Manually rotate fan to verify free rotation and
insure that blower wheel is secured to the motor shaft. Be sure to remove any shipping supports if needed. DO NOT oil motors upon start-up. Fan motors are permanently lubricated.
Condensate line: Verify that condensate trap is properly
installed and pitched.
Verify that HWG pump is turned off unless piping is
completed and air has been purged from the system. (S3 dipswitch #4)
Unit air coil and fi lters: Insure that fi lter is clean and
accessible. Clean air coil of all manufacturing oils.
Unit controls: Verify that DXM2 fi eld selection options are
properly set and that low voltage wiring is complete.
Desired Blower CFM and Water ∆T is set via
communicating thermostats or diagnostic tool.
Service/access panels are in place.
SYSTEM CHECKOUT
System water temperature: Check water temperature for
proper range.
System pH: Check and adjust water pH if necessary to
maintain a level between 6 and 8.5. Proper pH promotes longevity of hoses and fi ttings (see Water Quality Table in unit IOM).
System fl ushing: Verify that all air is purged from the
system. Air in the system can cause poor operation or system corrosion. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Some antifreeze solutions may require distilled water.
Internal Flow Controller: Verify that it is purged of air and
in operating condition.
Low water temperature cutout: Verify that low water
temperature cut-out controls are set properly (LT1 ­JW3).
Miscellaneous: Note any questionable aspects of the
installation.
CAUTION!
CAUTION! Verify that ALL water valves are open and allow water fl ow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.
CAUTION!
CAUTION! To avoid equipment damage, DO NOT leave system fi lled in a building without heat during the winter unless antifreeze is added to the water loop. Heat exchangers never fully drain by themselves and will freeze unless winterized with antifreeze.
Step 9 Unit Start-up Procedure
Unit Start-up Procedure
1. Turn the thermostat fan position to “ON.” Blower should start.
2. Turn Blower off .
3. Ensure all valves are adjusted to their full open position. Ensure line power to the heat pump is on.
4. Room temperature should be within the minimum­maximum ranges of listed in the unit IOM. During start­up checks, loop water temperature entering the heat pump should be between 30°F [-1°C] and 95°F [35°C].
5. It is recommended that water-to-air units be fi rst started in the cooling mode, when possible. This will allow liquid refrigerant to fl ow through the fi lter-drier before entering the TXV, allowing the fi lter-drier to catch any debris that might be in the system before it reaches the TXV.
6. Two factors determine the operating limits of geothermal heat pumps, (a) return air temperature, and (b) entering water temperature. When either of the factors is at a minimum or maximum level, the other factor must be at normal levels to insure proper unit operation.
a. Place the unit in Manual Operation. When in manual
mode activate Y1,Y2, and O to initiate the cooling mode. Also manually increase CFM until desired cooling CFM is achieved. Next adjust pump speed % until desired loop temperature diff erence (leaving water temperature minus entering water temperature) is achieved. (For modulating valve adjust valve %).
8
Geothermal Heat Pump Systems
Page 9
Tranquility® Digital Quick Start Guide
9 - 12
20 - 26
4 - 8
10 - 17
Rev.: January 25, 2016
INSTALLER SETTINGS
THERMOSTAT CONFIG SYSTEM CONFIG ACCESSORY CONFIG INPUT DEALER INFO HUMIDITY CONFIG TEMPERA TURE ALGORITHM DEMAND REDUCTION CNFG
SERVICE MODE
RESTORY DEFAULTS ATC32U01
SELECT OPTION
PREVIOUS
SERVICE MODE
MANUAL OPERATION
CONTROL DIAGNOSTICS DIPSWITCH CONFIG FAULT HISTORY CLEAR FAULT HISTORY
SELECT OPTION
PREVIOUS SELECT
MANUAL OPERATING MODE
Y1 COMM OUTPUT OFF
Y2 COMM OUTPUT OFF W COMM OUTPUT OFF O COMM OUTPUT OFF G COMM OUTPUT OFF H COMM OUTPUT OFF DH COMM OUTPUT OFF ECM AIRFLOW 0 PUMP SPEED 0% TEST MODE OFF
SELECT OPTION
PREVIOUS SELECT
b. Check for cool air delivery at the unit grille within a
few minutes after the unit has begun to operate.
NOTE: Units have a fi ve minute time delay in the control
circuit that can be bypassed on the DXM2 control board by placing the unit in the “Test” mode as shown in the unit IOM. Check for normal air temperature drop of 15°F to 25°F (cooling mode).
c. Verify that the compressor is on and that the water
temperature rise (cooling mode) is within normal range.
to provide a water seal.
e. Turn thermostat to “OFF” position. A hissing noise
indicates proper functioning of the reversing valve.
7. Allow fi ve (5) minutes between tests for pressure to equalize before beginning heating test.
a. Go into Manual Mode activate Y1, and Y2 for
Heating. Also manually increase CFM until desired heating CFM is achieved. Next adjust pump speed % until desired loop temperature diff erence (entering water temperature minus leaving water temperature) is achieved. (For modulating valve adjust valve %).
b. Check for warm air delivery at the unit grille within a
few minutes after the unit has begun to operate.
NOTE: Units have a fi ve minute time delay in the control circuit that can be bypassed on the DXM2 control board by placing the unit in the “Test” mode as shown in the unit IOM. Check for normal air temperature rise of 20°F to 30°F (heating mode).
c. Verify that the compressor is on and that the water
temperature fall (heating mode) is within normal range.
e. Check for vibration, noise, and water leaks.
8. If unit fails to operate properly, perform troubleshooting analysis (see troubleshooting section in the unit IOM). If the check described fails to reveal the problem and the unit still does not operate, contact a trained service technician to insure proper diagnosis and repair of the equipment.
9. When testing is complete, exit the Installer Menu and set thermostat to maintain desired comfort level for normal operation.
NOTE: If performance during any mode appears abnormal, refer to the DXM2 section or troubleshooting section of the unit IOM. To obtain maximum performance, the air coil should be cleaned before start-up. A 10% solution of dishwasher detergent and water is recommended.
WARNING! 
WARNING! When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with energized equipment.
d. Check the elevation and cleanliness of the
condensate lines. Dripping may be a sign of a blocked line. Check that the condensate trap is fi lled
CAUTION!
CAUTION! Verify that ALL water valves are open and allow water fl ow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.
9
Page 10
Tranquility® Digital Quick Start Guide
Rev.:January 25, 2016
Revision History
Date Page # Description
25 Jan., 2016 10 Updated Certifi cation Logos
5 Dec. 12 4 TES, TEP and TAH Digital Information Added 1 Oct., 12 4, 5 Unit Confi g, vFlow Pump Confi g Sections Updated 8 May, 12 All First Published
*97B0107N01*
97B0107N01
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warran- ties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
The management system governing the manufacture of ClimateMaster’s products is ISO 9001 compliant.
© ClimateMaster, Inc. 2012
10
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
Fax: 405-745-6058
climatemaster.com
Rev.: January 25, 2016T
Geothermal Heat Pump Systems
Loading...