ClimateMaster NC Series, ND Series, NE Series, NF Series, NG Series Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
97B0042N05
Rev.: 04 April, 2014
ENERGY RECOVERY VENTILATOR SERIES NB, NC, ND, NE, NF, & NG
Installation Instructions For Energy Recovery Wheel (Fixed)
For Stand Alone Over/Under Mechanical Room Application
Energy recovery COMPONENT certifi ed to the ARI Air-to- Air Energy Recovery Ventilation Equipment Certifi cation Program in accordance with ARI Standard 1060-2000. Actual performance in packaged equipment may vary.
ETL Certifi ed per UL 1995 and CSA 22.2
Inspection
Upon receipt of shipment at the job site, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the carton or crating housing of each Rooftop Unit and inspect each unit for damage. Assure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and that he completes a Carrier Inspection Report. Concealed damage not discovered during unloading must be reported to the carrier within 15 days of receipt of shipment. NOTE: It is the responsibility of the
purchaser to fi le all necessary claims with the carrier.
Storage
Upon the arrival of equipment at the job site, immediately store units in a clean, dry area. Do not stack units. Do not remove
equipment from pallets until equipment is required for installation.
Unit Protection
Cover rooftop units on the job site. Cap the open ends of pipes. In areas where painting, plastering, roofi ng, or the spraying of reproof material has not been completed, all due precautions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and
contamination may prevent proper start-up and may result in costly equipment cleanup.
Application
Field supplied balancing dampers in duct are recommended.
Rigging Unit For Lifting
1. Maximum weight 300-1200 lbs. See Physical Data Table.
2. Remove crating.
3. All panels must be in place for rigging.
4. Remove barometric exhaust hood from door marked fi lter access. Install barometric exhaust hood over exhaust blower outlet.
5. Forklift channels must be removed from the base of
ERV.
6. Position unit and provide service access to ERV control access door and wheel.
7. Duct work should be installed into roof curb before installing ERV on curb.
8. Roof curb gasket must be applied to all top surfaces of the curb.
9. Position unit on roof curb and provide service access to ERV control access door and wheel.
CAUTION!
CAUTION! Danger of sharp metallic edges. Can cause
injury. Take care when servicing unit to avoid accidental contact with sharp edges.
WARNING!
WARNING! Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
Recovery Wheel Mode
The Recovery Wheel mode is accomplished by two blowers providing continuous exhaust of stale indoor air and replacement by equal amount of outdoor air. Energy recovery is achieved by slowly rotating the energy recovery wheel within the cassette frame work. In winter, the ERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold, drier intake air supply during the other half rotation. In summer, the process is automatically reversed. Heat and moisture are absorbed from incoming fresh air supply and transferred to the exhaust air stream. This process allows outdoor air ventilation rates to be increased by factors of three or more without additional energy penalty or increase in size of heating or air conditioning systems.
WARNING!
WARNING! To avoid equipment damage, do not use these
units as a source of heat during the construction process. The mechanical components and fi lters used in these units will quickly become clogged with construction dirt and debris which may cause system damage.
WARNING!
WARNING! The installation of water-source heat pumps and
all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes, regulations and ANSI/NFPA No. 70
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
N (ERV) Series
Rev.: 04 April, 2014
This Page Intentionally Left Blank
2
ClimateMaster Water-Source Heat Pumps
THE SMART SOLUTION FOR ENERGY EFFICIENCY
N (ERV) Series
Rev.: 04 April, 2014
8. Ground unit with a suitable ground connection either
through unit supply wiring or an earth ground.
NOTE: Unit voltage entries must be sealed
weather tight after wiring is complete.
9. Remove motor access panels. Locate belts fastened
to blower assembly. Install belt onto motor and blower pulley. Adjust motor sheave to correct blower RPM for CFM and external static pressure requirements. See charts in this instruction. Multiple pulley arrangements are available to meet the entire range.
CAUTION!
CAUTION! Blower speed must be adjusted for the given
external static pressure and airfl ow (CFM) requirements. If blower speed is not adjusted for conditions, possible motor over loading can occur.
Installation
1. Attach duct work to duct fl anges on ERV.
2. Remove ERV control access panel to connect fi eld wiring.
3. Route class II low voltage wire (3 conductor) from thermostat or energy management through small bushing in end panel of ERV. See wiring diagram.
a. Thermostat (dependent) - connect in parallel at
rooftop unit with “G”, “C” and “W”. Then connect matching color at terminal 1, 2, and 3 respectively on ERV circuit board.
b. Energy Management - provide +24 VAC to “1” and
common, 24 VAC to “2’ terminals on ERV circuit board.
c. Thermostat (dedicated) - splice into +24 vac
(blue wire) at (control circuit board) transformer connection run wire to “R” terminal. Then run another wire from “G” terminal to ERV (control circuit board) terminal block #1.
4. All electrical connections must conform to any local codes and current National Electric Codes (NEC) and Canadian Electric Codes (CEC). Refer closely to unit wiring diagram in unit and/or in these instructions for proper wiring connections.
5. Refer to the unit nameplate for minimum circuit ampacity (MCA) and maximum overcurrent protection size (fuse).
6. Electrical data is listed on unit rating plate and motor name plates.
7. Connect line voltage power supply to ERV fuse block in control box of unit from disconnect switch. See
wiring diagram.
10. Replace access panel onto the ERV unit and secure.
11. Restore power to unit.
12. Cleanup once unit is operating properly, caulk any open joints, holes or seams to make the units completely air and water tight.
13. Leave this instruction manual with owner or in an envelope to be kept near unit.
Operation (How It Works)
The unit contains an Energy Recovery Wheel (ERW) that is a new concept in rotary air-to-air heat exchangers. Designed as a packaged unit for ease of installation and maintenance, only the connection of electrical power is required to make the system operational.
When slowly rotating through counter fl owing exhaust and fresh air streams the ERW adsorbs sensible heat and latent heat from the warmer air stream and transfer this total energy to the cooler air stream during the second half of its rotating cycle. Rotating at 50-60 revolutions per minute, the wheel provides constant fl ow of energy from warmer to cooler air stream. The large energy transfer surface and laminar fl ow through the wheel causes this constant fl ow of recovered energy to represent up to 85% of the difference in total energy contained within the two air streams.
Sensible and latent heat are the two components of total heat. Sensible heat is energy contained in dry air and latent heat is the energy contained within the moisture of the air. The latent heat load from the outdoor fresh air on an air conditioning system can often be two to three
climatemaster.com
3
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
N (ERV) Series
Rev.: 04 April, 2014
times that of the sensible heat load and in the winter it is a signifi cant part of a humidifi cation heat load.
During both the summer and winter, the ERW transfers moisture entirely in the vapor phase. This eliminates wet surfaces that retain dust and promote fungal growth as well as the need for a condensate pan and drain to carry water.
Because it is constantly rotating when in the air stream, the ERV is always being cleaned by air, fi rst in one direction then the other. Because it is always dry, dust or other particles impinging on the surface during one half cycle, are readily removed during the next half cycle.
During the heating season, when outdoor air temperatures are below 15ºF, it is recommended to use the (optional) low ambient kit (fi eld installed). Low Ambient Kit is appropriate for climates with limited HVAC system operation when outdoor temperatures are below 10ºF.
The frost threshold is the outdoor temperature at which frost will begin to form on the ERV wheel. For Energy Recovery Ventilators, the frost threshold is typically below 10ºF. Frost threshold is dependent on indoor temperature and humidify. The table shows how the frost threshold temperatures vary depending on indoor conditions.
FROST THRESHOLD TEMPERATURE
INDOOR RH AT 70ºF
FROST THRESHOLD
TEMPERATURE
20% 0ºF
30% 5ºF
40% 10ºF
Because Energy Recovery Ventilators have a low frost threshold, frost control options are not necessary in many climates. Where outdoor temperatures may drop below the frost threshold during the ERV operational hours, exhaust only frost control option is available.
Low Ambient Kit (Optional)
Low Ambient Kit turns off the supply blower when outdoor temperatures fall below the frost threshold. The exhaust only thermostat set points are fi eld adjustable. Supply fan operation is automatically restored when the exhaust air temperature rises above the thermostat set point. Provisions for introducing make-up air into the building when the supply blower is off to avoid depressurization should be considered.
Recovery Wheel Mode
On a thermostat call for blower operation in heating, cooling or continuous blower, the ERW will rotate between fresh air and exhaust air streams. Both the fresh air and exhaust air blowers will also be operating to overcome the air resistance of the ERV.
System Check
1. Disconnect main power.
2. Turn to “Cont” for blower operation on thermostat controlled models.
3. Restore power to unit. Observe ERV wheel rotation and both fresh air and exhaust air blowers will operating.
NOTE: If Low ambient kit is used the jumper between TB37-5 & TB37-6 should be removed. Also if system check out is being conducted at low ambient temperatures, technician should be aware that this kit can cause system not to operate.
4. Verify that the ERV (3) three phase blower motors are phased sequentially ensuring correct rotation and operation.
a. Disconnect power. b. Reverse any two fi eld power leads to the ERV.
c. Reapply power.
5. Verify that both blower motors are operating under their full load AMP rating (FLA). The FLA can be found on each motor and the unit nameplate.
A. Return Damper Settings
Manually adjust position of fi eld installed dampers to
balance air fl ow.
B. Air Flow / Blower Speed Adjustment
Blower speed selection is accomplished by changing
the sheave setting on both fresh air and exhaust air blowers. To set ERV for the required air fl ow (CFM), the external static pressure applied to the ERV (duct static) must be known. See the CFM vs External Static Pressure chart for the appropriate unit to determine the correct blower RPM for the specifi ed CFM and External Static Pressure.
After blower speed adjustments have been made. Ensure that when the belt is replaced it is tensioned correctly. The motor mounting plate can be adjusted to tension the belt. If using a belt tension checker, adjust the span to the appropriate setting and check the belt defection force. The belt defl ection force should be between 5-8 lbs or the lowest tension at which the belt will not slip under peak
4
ClimateMaster Water-Source Heat Pumps
THE SMART SOLUTION FOR ENERGY EFFICIENCY
N (ERV) Series
Rev.: 04 April, 2014
load conditions.
1. Disconnect main power to unit before making adjustment to economizer and/or ERV unit.
2. Replace ERV control access cover.
3. Set thermostat to normal operating position.
4. Restore power to unit.
Maintenance
1. All motors use pre-lubricated sealed bearings; no further lubrication is necessary.
2. Make visual inspection of motors, belts and wheel rotating bearings during routine maintenance.
3. Eight pie-shaped segments, are seated on stops between the segment retainer which pivots on the wheel rim and secured to the hub and rim of wheel. Annual inspection of the self cleaning wheel is recommended. With power disconnected, remove ERV access panels (rear) and unplug [J150 & P150]
(Refer to wiring diagram in this instruction manual). Remove segment and wash with water and/
or mild detergent.
4. To install wheel segments follow steps A through E . See Figure 1. Reverse procedure for segment removal. A. Unlock two segment retainers (one on each side of
the selected segment opening.
B. With the embedded stiffener facing the motor side,
insert the nose of the segment between the hub plates.
C. Holding segment by the two outer corners, press
the segment towards the center of the wheel and inwards against the spoke fl anges. If hand pressure does not fully seat the segment, insert the fl at tip of a screw driver between the wheel rim and outer corners of the segment and apply downward force while guiding the segment into place.
D. Close and latch each segment retainer under
segment retaining catch.
E. Slowly rotate the wheel 180º. Install the second
segment opposite the fi rst for counterbalance. Rotate the two installed segments 90º to balance the wheel while the third segment is installed. Rotate the wheel 180º again to install the fourth segment opposite the third. Repeat this sequence with the remaining four segments.
Figure 1
WHEEL RIM
E
SPOKE
SEGMENT RETAINER CATCH
D
C
B
HUB
SEGMENT RETAINER
A
D
SEGMENT
static settings. To install a pulley kit.
1. Check content of pulley kit, if pulley kit contains: a. An adjustable sheave and a fi xed pitch pulley then
remove belt and both motor and blower pulley
b. An adjustable sheave then remove the motor
pulley.
c. A fi xed pitch pulley then remove the blower pulley.
2. Replace pulley(s) with the pulley(s) from pulley kit.
Make sure each pulley is installed with a key. Tighten the set screw on the pulley(s) to 100 in.lb.
3. Install the belt that came with the pulley kit. Tension
belt as explained in the blower speed adjustment section.
4. Check the speed of the blower. Adjust the motor
sheave to increase or decrease the speed of the blower. See blower adjustment section.
Pulley Kit Installation
The units are shipped from the factory at the low static setting. Pulley kits are available for the medium and high
climatemaster.com
5
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
N (ERV) Series
Rev.: 04 April, 2014
N Series Stand Alone ERV’s for Over and Under Indoor Application
Features and Notes:
1. Stand alone design allows higher levels of outdoor air to be introduced into the conditioned space.
2. Static test ports provided to verify intake and exhaust CFM.
3. Balancing damper(s) is fi eld provided when connected to ductwork. System may not operate properly without balancing damper.
4. See blower performance charts for airfl ow at various E.S.P.
5. Filter rack with 2” pleated fi lters included.
RETURN AIR
TREATED AIR
FRESH AIR
EXHAUST AIR
ERV with Horizontal Ductwork
(balancing damper(s) fi eld supplied)
A
K
D
C
J
D
I
B
ERV Data Dimensional Data
ERV Series CFM Range A B C D E F G H I J K
NB 300-1100 56.75 32.13 39.50 11.00 27.00 4.50 10.00 2.56 1.00 10.00 4.50
NC 1200-2000 54.38 37.25 37.50 12.00 30.00 8.00 4.00 3.63 1.50 7.00 5.00
ND 1200-2800 60.00 42.62 43.56 14.00 32.00 9.56 4.50 5.31 1.50 8.81 5.25
NE 2000-3600 60.00 46.69 57.37 16.50 39.50 12.13 6.38 3.59 5.88 11.75 6.75
NF 3000-4600 60.00 52.69 57.37 16.50 39.50 12.13 6.38 6.59 5.88 11.75 6.75
NG 4600-6200 72.00 70.88 63.63 19.50 39.50 12.13 6.50 15.69 5.88 12.00 6.75
F
D
G
D
I
H
E
H
6
ClimateMaster Water-Source Heat Pumps
THE SMART SOLUTION FOR ENERGY EFFICIENCY
N (ERV) Series
Rev.: 04 April, 2014
ERV UNIT SCHEMATIC DIAGRAM
(FIELD INSTALLED) Wired in parallel at thermostat connection.
Notes:
1. Remove jumper to install field optional low ambient switch.
2. Se lec tive volt age ter mi nals for proper unit volt age.
3. Optional low ambient switch.
4. Optional motorized intake damper.
5. Op tional Stop, Start and Jog Con trol.
6. For energy man age ment systems connect +24v to “G” and common 24v to “C”.
COMPONENT CODE
A131 Fixed Relay Board
B26 Motor, Exhaust Air
B27 Motor, Fresh Air
B28 Motor, Desiccant Wheel
B30 Motor, Damper (Optional)
C23 Capacitor, Wheel Motor
C25 Capacitor, Exhaust Air
C26 Capacitor, Fresh Air
DL43 Delay, Cycle Timer (Optional)
F29 Fuse
J33 Jack, Cycle Control (Optional)
J34 Jack, Cycle Control Harness (Optional)
J40 Jack, Cycle (Optional)
J48 Jack, Control Box (Fresh Air)
J50 Jack, Control Box (Wheel)
J51 Jack, Control Box (Exhaust Air)
J56 Jack, Control Box (Damper)
J148 Jack, Fresh Air Motor Harness
J150 Jack, Wheel Motor Harness
J151 Jack, Exhaust Air Motor Harness
J160 Jack, Damper Motor Harness
K94 Relay, On/O (Optional)
K163 Contactor , Exhaust Air Motor
K164 Contactor, Fresh Air Motor
P33 Plug, Cycle Control (Optional)
P34 Plug, Cycle Control Harness (Optional)
P40 Plug, Wheel Cycle (Optional)
P48 Plug, Fresh Air Motor Harness
P50 Plug, Wheel Motor Harness
P51 Plug, Exhaust Air Motor Harness
P56 Plug, Damper Motor Harness
P148 Plug, Fresh Air Motor
P150 Plug, Wheel Motor
P151 Plug, Exhaust Air Motor
P160 Plug, Damper Motor
S23 Thermostat - Low Ambient (Optional)
S26 Switch, Low Ambient (Optional)
S51 Switch, Door
S125 Switch, Ambient Override (Optional)
T27 T27 Transformer, Control
T28 T28 Transformer, Step-down (Optional)
WIRE COLOR
BK Black
BL Blue
GR Green
GY Gray
OR Orange
PK Pink
RD Red
WH White
YL Yellow
208/230-1-60
B-C
climatemaster.com
7
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
N (ERV) Series
Rev.: 04 April, 2014
ERV UNIT SCHEMATIC DIAGRAM
(FIELD INSTALLED) Wired in parallel at Thermostat connection.
Notes:
1. Remove jumper to install field optional low ambient switch.
2. Step-down transformer assembly for 460/575 volt only units.
3. Move wire for dif fer ent volt age in put.
4. Optional low ambient switch.
5. Optional motorized intake damper.
6. For energy man age ment systems connect +24v to green and common 24v to black.
COMPONENT CODE
A131 Fixed Relay Board
B26 Motor, Exhaust Air
B27 Motor, Fresh Air
B28 Motor, Desiccant Wheel
B30 Motor, Damper (Optional)
C23 Capacitor, Wheel Motor
DL43 Delay, Cycle Timer (Optional)
F29 Fuse
J33 Jack, Cycle Control (Optional)
J34 Jack, Cycle Control Harness (Optional)
J40 Jack, Cycle (Optional)
J48 Jack, Control Box (Fresh Air)
J50 Jack, Control Box (Wheel)
J51 Jack, Control Box (Exhaust Air)
J56 Jack, Control Box (Damper)
J148 Jack, Fresh Air Motor Harness
J150 Jack, Wheel Motor Harness
J151 Jack, Exhaust Air Motor Harness
J152 Jack, Transformer (High Voltage)
J160 Jack, Damper Motor Harness
K94 Relay, On/Off (Optional)
K163 Contactor, Exhaust Air Motor
K164 Contactor, Fresh Air Motor
P33 Plug, Cycle Control (Optional)
P34 Plug, Cycle Control Harness (Optional)
P40 Plug, Wheel Cycle (Optional)
P48 Plug, Fresh Air Motor Harness
P50 Plug, Wheel Motor Harness
P51 Plug, Exhaust Air Motor Harness
P56 Plug, Damper Motor Harness
P148 Plug, Fresh Air Motor
P150 Plug, Wheel Motor
P151 Plug, Exhaust Air Motor
P152 Plug, Transformer (High Voltage)
P160 Plug, Damper Motor
S23 Thermostat - Low Ambient (Optional)
S26 Switch, Low Ambient (Optional)
S51 Switch, Door
S125 Switch, Ambient Override (Optional)
T27 Trans former, Control
T28 Trans former, Step-down (Optional)
WIRE COLOR
BK Black
BL Blue
GR Green
GY Gray
OR Orange
PK Pink
RD Red
WH White
YL Yellow
208/230-3-60
460-3-60 575-3-60
NB-GERV
8
ClimateMaster Water-Source Heat Pumps
THE SMART SOLUTION FOR ENERGY EFFICIENCY
N (ERV) Series
Rev.: 04 April, 2014
ERV UNIT WIRING DIAGRAM
Notes:
1. Remove jumper to install field optional low ambient switch.
2. Selective voltage terminals for proper unit voltage.
3. Optional low ambient switch.
4. Optional motorized intake damper.
5. Optional Stop, Start and Jog Control.
6. For energy management systems connect +24v to “G” and common 24v to “C”.
climatemaster.com
Desiccant Wheel for Roof top Unit
208- 230V (1 PH)
NB-C
9
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
N (ERV) Series
Rev.: 04 April, 2014
ERV UNIT WIRING DIAGRAM
Notes:
1. Remove jumper to install field optional low ambient switch.
2. Step-down transformer assembly for 460/575 volt units.
3. Selective voltage terminals for proper unit volt age.
4. Optional low ambient switch.
5. Optional motorized intake damper.
6. Optional Stop, Start and Jog Control.
7. For energy management systems connect +24v to “G” and common 24v to “C”.
10
Desiccant Wheel for Roof top Unit
208- 230/460/575V (3 PH)
NB-G
ClimateMaster Water-Source Heat Pumps
Blower RPM for NB
SUPPLY
300 N/A N/A 980 1065 1320 1400 1520
500 N/A
CFM
EXHAUST
CFM
700 865
900 1030
1100 1200
300 N/A 815 1030 1185 1305 1450 1535
500 N/A
700 810
900 995
1100 1
THE SMART SOLUTION FOR ENERGY EFFICIENCY
N (ERV) Series
Rev.: 04 April, 2014
Mist Eliminator Filter in Intake Hood (1.5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
905 1050 1215 1360 1495 1595
1035 1210 1330 1440 1535 1620
1205 1325 1435 1530 1615 1725
1320 1430 1525 1605 1720 1800
Barometric Hood, 2" Pleated Filters (1.5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
950 1075 1220 1375 1490 1610
1070 1195 1295 1445 1510 1645
1125 1290 1405 1500 1600 1690
120 1280 1400 1495 1595 1685 1770
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Blower RPM for NC
SUPPLY
Mist Eliminator Filter in Intake Hood (2HP)
0 0.25 0.5 0.75 1 1.25 1.5
1200 990 1075 1220 1380 1480 1605 1720
CFM
EXHAUST
CFM
1400 1030
1600 1
1800 1240
2000 1295
1200 900 1085 1235 1380 1495 1585 1680
1400 1050
1600 1205
1800 1315
2000 1390
135 1250 1340 1445 1570 1665 1760
0 0.25 0.5 0.75 1 1.25 1.5
1165 1280 1410 1520 1620 1740
1330 1425 1550 1625 1720 1785
1405 1540 1615 1705 1760 1830
Barometric Hood, 2" Pleated Filters (2HP)
1220 1345 1490 1535 1630 1715
1335 1430 1520 1625 1705 1790
1425 1510 1580 1655 1775 1850
1490 1570 1650 1735 1750 N/A
RPM Range
Low 1000-1300 Standard Unit
Medium 1300-1750 Optional Kit
High 1750-2200 Optional Kit
External Static Pressure (in water)
External Static Pressure (in water)
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
climatemaster.com
RPM Range
Low 1000-1300 Standard Unit
Medium 1300-1700 Optional Kit
High 1700-2080 Optional Kit
11
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
N (ERV) Series
Rev.: 04 April, 2014
Blower RPM for ND
SUPPLY
Mist Eliminator Filter in Intake Hood (3HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
1200 N/A 900 1045 1135 1255 1395 1410
1600 880 1035 1130 1245 1385 1405 1450
CFM
EXHAUST
CFM
2000 1045
2400 1
2800 1295
1200 N/A 955 1075 1185 1285 1355 1495
1600 945
2000 1045
2400 1210
2800 1315 1475 1500 1595 1710 1755 1790
135 1300 1375 1435 1505 1550 1590
0 0.25 0.5 0.75 1 1.25 1.5
1145 1235 1325 1400 1440 1555
1365 1435 1515 1580 1625 1695
Barometric Hood, 2" Pleated Filters (3HP)
External Static Pressure (in water)
1055 1175 1265 1335 1445 1635
1170 1330 1395 1440 1570 1695
1325 1435 1510 1580 1620 1675
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Blower RPM for NE
SUPPLY
Mist Eliminator Filter in Intake Hood (3HP)
0 0.25 0.5 0.75 1 1.25 1.5
2000 735 860 920 1005 1075 1150 1220
CFM
EXHAUST
CFM
2400 850
2800 935
3200 1015
3600 1065
0 0.25 0.5 0.75 1 1.25 1.5
2000 740 855 930 970 1080 1155 1240
2400 800
2800 885
3200 950
3600 1055 1130 1235 1280 1310 N/A N/A
945 1030 1090 1110 1215 1265
1020 1080 1145 1200 1255 1335
1075 1105 1195 1285 1325 1380
1125 1220 1305 N/A N/A N/A
Barometric Hood, 2" Pleated Filters (3HP)
925 1015 1075 1145 1225 1280
1010 1070 1140 1235 1255 1330
1065 1135 1230 1290 1325 N/A
RPM Range
Low 950-1320 Standard Unit
Medium 1325-1565 Optional Kit
High 1570-1880 Optional Kit
External Static Pressure (in water)
External Static Pressure (in water)
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
12
RPM Range
Low 700-1025 Standard Unit
Medium 1030-1305 Optional Kit
High 1325-1575 Optional Kit
ClimateMaster Water-Source Heat Pumps
Blower RPM for NF
SUPPLY
3000 840 990 1065 1135 1215 1265 1335
3400 875 1060 1130 1205 1255 1320 1385
CFM
EXHAUST
CFM
3800 1015
4200 1080
4600 1
3000 850 995 1065 1135 1220 1270 1335
3400 925 1060 1130 1225 1265 1330 1375
3800 1020 1120 1220 1285 1325 1370 1430
4200 1
4600 1
THE SMART SOLUTION FOR ENERGY EFFICIENCY
N (ERV) Series
Rev.: 04 April, 2014
Mist Eliminator Filter in Intake Hood (5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
1120 1200 1245 1315 1365 1450
1195 1240 1350 1395 1445 1510
120 1200 1315 1380 1460 1515 1560
Barometric Hood, 2" Pleated Filters (5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
100 1215 1280 1345 1400 1435 1480
150 1275 1340 1415 1475 1520 1565
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Blower RPM for NG
SUPPLY
Mist Eliminator Filter in Intake Hood (5HP)
0 0.25 0.5 0.75 1 1.25 1.5
4600 795 900 960 1010 1090 1135 1165
CFM
EXHAUST
CFM
5000 835
5400 895
5800 940
6200 990
0 0.25 0.5 0.75 1 1.25 1.5
4600 780 910 900 1045 1085 1135 1185
5000 825
5400 890
5800 940
6200 980
945 1000 1060 1135 1155 1230
985 1040 1130 1155 1220 1265
1025 1085 1145 1225 1250 1300
1070 1105 1210 1245 1290 N/A
Barometric Hood, 2" Pleated Filters (5HP)
945 1015 1075 1125 1180 1230
990 1065 1105 1170 1220 1270
1025 1085 1165 1215 1250 1310
1060 1150 1205 1235 1305 N/A
RPM Range
Low 780-1020 Standard Unit
Medium 1000-1315 Optional Kit
High 1315-1700 Optional Kit
External Static Pressure (in water)
External Static Pressure (in water)
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
climatemaster.com
RPM Range
Low 700-900 Standard Unit
Medium 900-1100 Optional Kit
High 1100-1300 Optional Kit
13
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
N (ERV) Series
Rev.: 04 April, 2014
CLIMATE MASTER, INC.
LIMITED EXPRESS WARRANTY/ LIMITATION OF REMEDIES AND LIABILITY
GRANT OF LIMITED EXPRESS WARRANTY
CM warrants CM products purchased and retained in the United States of America and Canada to be free from defects in material and workmanship under normal use and maintenance as follows: (1) All complete air condition-
ing, heating and/or heat pump units built or sold by CM for twelve (12) months from date of unit start up or eighteen (18) months from date of shipment (from factory), whichever comes fi rst; (2) Repair and replacement parts,
which are not supplied under warranty, for nintey (90) days from date of shipment (from factory). All parts must be returned to CM’s factory in Oklahoma City, Oklahoma, freight prepaid, no later than sixty (60) days after
the date of the failure of the part; if CM determines the part to be defective and within CM’s Limited Express Warranty, CM shall, when such part has been either replaced or repaired, return such to a factory recognized dealer,
written or contained in any sales literature, catalog or any other agreement, are not express warranties and do not form a part of the basis of the bargain, but are merely CM’s opinion or commendation of CM’s products.
EXCEPT AS SPECIFICALLY SET FORTH HEREIN, THERE IS NO EXPRESS WARRANTY AS TO ANY OF CM’S PRODUCTS. CM MAKES NO WARRANTY AGAINST LATENT DEFECTS. CM MAKES
NO WARRANTY OF MERCHANTABILITY OF THE GOODS OR OF THE FITNESS OF THE GOODS FOR ANY PARTICULAR PURPOSE.
It is expressly understood that unless a statement is specifi cally identifi ed as a warranty, statements made by Climate Master, Inc., a Delaware corporation, (“CM”) or its representatives, relating to CM’s products, whether oral,
14
contractor or service organization, F.O.B. CM’s factory, Oklahoma City, Oklahoma, freight prepaid. The warranty on any parts repaired or replaced under warranty expires at the end of the original warranty period.
This warranty does not cover and does not apply to: (1) Air fi lters, fuses, refrigerant, fl uids, oil; (2) Products relocated after initial installation; (3) Any portion or component of any system that is not supplied by CM, regardless
of the cause of the failure of such portion or component; (4) Products on which the unit identifi cation tags or labels have been removed or defaced; (5) Products on which payment to CM is or has been in default; (6) Products
which have defects or damage which result from improper installation, wiring, electrical imbalance characteristics or maintenance; or are caused by accident, misuse or abuse, fi re, fl ood, alteration or misapplication of the prod-
uct; (7) Products which have defects or damage which result from a contaminated or corrosive air or liquid supply, operation at abnormal temperatures, or unauthorized opening of refrigerant circuit; (8) Mold, fungus or bacteria
Warranty; (2) The costs of labor, refrigerant, materials or service incurred in removal of the defective part, or in obtaining and replacing the new or repaired part; or, (3) Transportation costs of the defective part from the installa-
damages; (9) Products subjected to corrosion or abrasion; (10) Products manufactured or supplied by others; (11) Products which have been subjected to misuse, negligence or accidents; (12) Products which have been operated
tion site to CM or of the return of any part not covered by CM’s Limited Express Warranty.
in a manner contrary to CM’s printed instructions; or (13) Products which have defects, damage or insuffi cient performance as a result of insuffi cient or incorrect system design or the improper application of CM’s products.
CM is not responsible for: (1) The costs of any fl uids, refrigerant or other system components, or associated labor to repair or replace the same, which is incurred as a result of a defective part covered by CM’s Limited Express
Limitation: This Limited Express Warranty is given in lieu of all other warranties. If, notwithstanding the disclaimers contained herein, it is determined that other warranties exist, any such warranties, including without limita-
tion any express warranties or any implied warranties of fi tness for particular purpose and merchantability, shall be limited to the duration of the Limited Express Warranty.
LIMITATION OF REMEDIES
In the event of a breach of the Limited Express Warranty, CM will only be obligated at CM’s option to repair the failed part or unit or to furnish a new or rebuilt part or unit in exchange for the part or unit which has failed. If
after written notice to CM’s factory in Oklahoma City, Oklahoma of each defect, malfunction or other failure and a reasonable number of attempts by CM to correct the defect, malfunction or other failure and the remedy fails
of its essential purpose, CM shall refund the purchase price paid to CM in exchange for the return of the sold good(s). Said refund shall be the maximum liability of CM. THIS REMEDY IS THE SOLE AND EXCLUSIVE
REMEDY OF THE BUYER OR THEIR PURCHASER AGAINST CM FOR BREACH OF CONTRACT, FOR THE BREACH OF ANY WARRANTY OR FOR CM’S NEGLIGENCE OR IN STRICT LIABILITY.
LIMITATION OF LIABILITY
CM shall have no liability for any damages if CM’s performance is delayed for any reason or is prevented to any extent by any event such as, but not limited to: any war, civil unrest, government restrictions or restraints, strikes
or work stoppages, fi re, fl ood, accident, shortages of transportation, fuel, material, or labor, acts of God or any other reason beyond the sole control of CM. CM EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABIL-
ITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGE IN CONTRACT, FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTY, OR IN TORT, WHETHER FOR CM’s NEGLIGENCE OR AS
STRICT LIABILITY.
OBTAINING WARRANTY PERFORMANCE
Climate Master, Inc. • Customer Service • 7300 S.W. 44th Street • Oklahoma City, Oklahoma 73179 (405) 745-6000
Normally, the contractor or service organization who installed the products will provide warranty performance for the owner. Should the installer be unavailable, contact any CM recognized dealer, contractor or service organiza-
tion. If assistance is required in obtaining warranty performance, write or call:
Please refer to the CM Installation, Operation and Maintenance Manual for operating and maintenance instructions.
NOTE: Some states or Canadian provinces do not allow limitations on how long an implied warranty lasts, or the limitation or exclusions of consequential or incidental damages, so the foregoing exclusions and limitations may
not apply to you. This warranty gives you specifi c legal rights, and you may also have other rights which vary from state to state and from Canadian province to Canadian province.
ClimateMaster Water-Source Heat Pumps
*LC083*
Rev.: 11/09 LC083
THE SMART SOLUTION FOR ENERGY EFFICIENCY
N (ERV) Series
Rev.: 04 April, 2014
Notes
climatemaster.com
15
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
N (ERV) Series
Rev.: 04 April, 2014
Revision History
Date: Item: Action:
04/04/14 Logos - page 1 & 16 Updated
11/21/13 Created
*97B0042N05*
97B0042N05
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products. For the latest version of this document go to climatemaster.com.
ClimateMaster is a proud supporter of the Geothermal Exchange Organization - GEO. For more information visit geoexchange.org.
© ClimateMaster, Inc. 2013
16
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
Fax: 405-745-6058
climatemaster.com