ClimateMaster MPC Application, Operation & Maintenance

MPC MULTIPROTOCOL DDC CONTROLS
Application, Operation & Maintenance
97B0031N01
Revised: November 19, 2018
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
Table of Contents
MPC Controller Overview .................................................................................................. 3-10
BACview6 Service Tool and Addressing ......................................................................... 11-13
Equipment Touch Tool Overview ..........................................................................................14
MPC LED Codes .....................................................................................................................17
MPC Sequence of Operation .......................................................................................... 18-23
Multi-Generation Water-to-Air Point Matrix ................................................................... 24-34
MPC Feature Conguration ............................................................................................. 35-37
Generation 4 Water-to-Water Points Matrix ................................................................... 38-41
MPC Wall Sensors ............................................................................................................ 42-47
Android App Installation ........................................................................................................48
Equipment Touch Manual- Screen Descriptions ............................................................ 50-68
Frequently Asked Questions (FAQs) .....................................................................................49
Revision History ......................................................................................................................72
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC Controller Overview
MPC MultiProtoCol DDC Controls
November 19, 2018
The Multi-Protocol (MPC) Heat Pump controller is a dual purpose controller. It contains the logic to perform as an advanced customizable thermostat when combined with a wall sensor and is designed to allow the integration of water source heat pump equipment into DDC systems. The MPC Controller has the ability to communicate through a choice of four widely used protocols:
1. BACnet MS/TP
2. Johnson Controls N2
3. Modbus
4. LonWorks.
The protocol of choice for the particular system is
selected by simply conguring DIP switches on the MPC
Controller with the exception of LonWorks. The LonWorks option requires an additional Lon option card (LOC).
This exibility allows one controller, the MPC, to be used
in a multitude of buildings which use any of these four common protocols.
The MPC serves as a node of information processing between the heat pump and the DDC network. The MPC commands the heat pump to heat and cool based upon sensor inputs. The MPC monitors the operation of the heat pump and communicates the operating parameters to the DDC network. The MPC will always work in conjunction with a CXM, DXM or DXM2 controller, which also resides in the heat pump control box. The MPC has factory pre­loaded application software which allows optimal control of the heat pump equipment. The MPC can run in stand­alone operation as well as with the DDC network. The heat pump arrives at the jobsite with the factory installed MPC Controller. The heat pump is ready to run stand-alone and then can be connected to the DDC network at any time.
Features
System Controls: In conjunction with the wall sensors, the
MPC offers features such as:
• Room temperature sensing.
• Local setpoint adjustment.
• Local override into Occupied Mode.
• LED for alarm status.
• LED for fault status type.
• Heat pump reset at the wall sensor.
• Digital room temperature display.
• Information from the wall sensors can then be reported to the DDC network system.
• Various sensors such as occupancy sensors, supports various sensors for occupancy determination. Also avalable in combination with humidity and/or
sensors.
Co
2
• Supports water to air application or water to water applications.
• The MPC can be programed with a 7-day schedule.
• One binary Aux output can be programmed to control various functions.
Communications: The Multi-Protocol communications provides DDC system flexibility.
• Supports native BACnet MS/TP communications (the ASHRAE standard protocol for interoperability).
• Supports Johnson Controls N2 communications (for integration into Johnson Controls Metasys (DDC systems).
• Supports Modbus communications for integration into Modbus DDC networks.
• Supports LonWorks communications. Requires LOC daughter card (PN-17B0012N08).
• Four baud rate levels offer flexible communications speeds of 9600, 19.2k, 38.4k, or 76.8k baud.
• High speed 16-bit Hitachi Processor with 1024 kBytes RAM and 4096 kBytes Flash Memory which allows, if needed, MPC programs to be upgraded and easily downloaded in the field.
• Removable field wiring connectors for ease of field service.
• Engineered for quality and reliability.
• Enables building operators to easily upgrade firmware in the future.
• Program archival feature.
• Supports up to five AWS13,14,15 (Rnet) sensors.
• Supports equipment touch maintenence and configuration tool.
Added Features on Gen 7
• Ability to operate in heating or cooling only mode.
• Ability to operate in full time electric or external
heat mode.
• Ability to archive the current control program.
• Input for pressure switch for dirty filter notice
applications.
• Can operate without ASW sensor if so equiped with
an Equipment Touch unit (temperature and humidity only).
• Can alternate compressor (lead LAG) based on manual
control, timed control or compressor accumulated time High time compessor becomes secondary or LAG at beginning of next heat/cool cycle.
• Supports Android based tablet in place of Equipment
Touch (does not support temp/humidity control).
• Selectivly supports zone averaging using up to 5 ASW
wall sensors.
• 17B0012N10 uses new maintenance tool/user interface
(Equipment Touch).
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Entering Air
DDC Communications Network
Ent
MPC MultiProtoCol DDC Controls
November 19, 2018
MPC Controller Overview
Figure 1: Typical System
Water to Air Heat Pump
Heat Pump
Regerant/Water Heat Exchanger
LWT Sensor
CXM
MPC
Controller
LAT Sensor
Leaving Air
Figure 2: Typical System
Water to Water Heat Pump
DDC Communications Network
CXM
Source
MPC
LWTS Sensor
Controller
Switch
Load
Digital Wall Sensor
EWTL Sensor
LWTL Sensor
Ent
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
MPC General Specications
Power: 24VAC ± 10%, 50 or 60Hz, 15VA max. power consumption.
Size: 5-1/16” [129mm] width x 5-11/16” [144mm] height x 1-1/2” [38mm] (minimum panel depth).
Housing: Rugged GE C2905HG Cycoloy plastic housing (complies with UL 94 V-O).
Environmental: 0-130°F (-17.8 to 54.4 °C), 10% to 95% non-condensing.
Protection: Surge & transient protection circuitry for the power and I/O. Optical isolation for communications port.
Processor/Memory: High speed 16-bit Hitachi Processor with 1024kB RAM and 4096kB Flash Memory.
LED Indicators: Individual LEDs for digital outputs, power, run, error, transmit, and receive.
Compliance: UL916; FCC Part 15, Subpart B, Class A; ICES, Class A; EN55022, Class A; IEC61000-6-1; RoHS complaint, WEEE Complaint; BTL listed
I/O Point Count: 5 digital outputs (on-board relays rated for 1A resistive at 24VAC). 6 universal inputs (IN-1 and IN-2 are jumper selectable for dry contact or 0-5VDC). 1 analog wall sensor port for non-communicating (Lstat) wall sensors. 1 digital wall sensor port for communicating (Rnet) wall sensors.
Communications: EIA-485 communications port using twisted pair. A two position DIP switch allows for manual
selection of desired protocol. Available protocols are BACnet MS/TP, Johnson Controls N2, Modbus and LonWorks (requires Loc daughter card. Another 2 position DIP switch allows for manual selection of desired baud rate. Available baud rates are 9600, 19.2k, 38.4k, and 76.8k.
Addressing: 2 rotary switches are provided for setting the individual controller’s primary network address (for more information on network addressing, see Addressing & Power Up).
Wall Sensor: The wall sensors provide room temperature sensing with digital display, local setpoint adjust, local override, LED for alarm status and fault type indication, and heat pump reset. The wall sensors require a 4 wire connection for communication or 5 wire connection for non-
communicating.
Mounting Hole Two mounting holes center line as below with 5-9/16” [141mm] height spacing. Dimensions: Factory mounted.
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
Figure 3:
Communications
LonWorks Daughter
Card Connection
Module Hardware
Addressing
(Communicating ASW13 - 15 (Rnet)
Inputs
Sensor)
1-4
Local
Access Port
Room Sensor
Type Selection
Gain
Jumper
24Vac
Connector
IN-1*
IN-2**
Protocol & Baud Rate
Outputs
(Non-Communicating)
ASW 6 - 8 (LStat) Sensor
Connector
Physical Dimension: 5.88" (149.4mm) x 5.66" (143.8mm)
Output LED’s
Communications Type Selection
BACnet Over ARC156
Communications Selection
‘PRO’ Space Sensor Connection (w/display)
RS-485 Communications Options
PROTOCOLS
BACnet
MS/TP
N2 Modbus
Thermistor/dry contact
0-5Vdc
Thermistor/dry contact
0-5Vdc
Power
Run
Error
IN-1
IN-2
24 Vac
Gnd
Hot
Rx
Tx
Batt
TensOnes
G
G
R
G
G
RS-485 Options
DIP
Protocols
Baud Rate
IN-1
IN-2
Communications Select
Factory 2
Factory 1
Room Sensor
Basic or Plus/Loginet
Therm Input Gain
Jumper 1x/ No Jumper 3x
8
9
0
1
2
7
6
5
4
3
8
9 0 1
2
7
6
5
4
3
8
9
0
1
2
7
6
5
4
3
8
9
0
1
2
7
6
5
4
3
Dry
0-5Vdc
Dry
0-5Vdc
RS 485
BACnet over ARC156
RS-485
Off
Off
On
SW3 SW4
Off
On
Off
Figure 3:
Factory Use Only - 1
Default = no jumper
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
Selects 1x (jumpered) or 3x (no jumper)
gain for “Therm” Input.
W3 Selects “LSTAT (ASW 6 - 8) Sensor
Connection” or “RNET” (ASW 13 - 15) port as
the active port for room sensor.
Default = RNET
Default = 3x (no jumper)
Selects “Thermistor/Dry
contact or “0 to 5Vdc” input
for ALI/AL2
Default = “Thermistor/Dry
Contact”
Address
Wheels
02 Default
Factory Use Only - 2
Default = jumpered
Selects “Thermistor/Dry
contact or “0 to 5Vdc” input
for EHZ/GND
Default = “Thermistor/Dry
Contact”
Selects “RS-485 MS/TP” or “ARC156”
Default = “RS-485 MS/TP”
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
MPC Controller Overview
Communications Selection
When the Communications Selection jumper is in the “BACnet over ARC156” position, DIP switch selectors SW1, SW2, SW3, and SW4 are all disabled. When the communications selection jumper is in the “BACnet over ARC156” position, BACnet protocol is selected and the baud rate is also selected to be 156 kbps.
When the communications port is congured for RS-
485 communications, use standard dedicated 22AWG­18AWG twisted pair wire.
When the communications port is congured for the
ARC156, use a ARC156 cable available from Automated Logic.
For complete details on wiring, termination, for BACnet MS/TP, refer to ANSI/ASHRAE 135-1995, clause 9.2.2. Refer to the Application Note for the BACnet devices
that you will be interfacing with for specic wiring.
Communications Wiring Instructions
1. Be sure the module’s power is off before wiring it to the ARC156 or RS-485 communications bus.
2. Check the network communication wiring for shorts and grounds.
3. Connect the ARC156 or RS-485 wires and shield to the module’s screw terminals as shown in Figure 9. Be sure to follow the same polarity as the rest of the ARC156 or RS-485 communications network.
4. Power up the module.
5. Proper communications for all protocols
and baud rates can be veried by making
sure the transmit (Tx) and receive (Rx) LEDs are active.
Protocol Congure
The communications port on the MPC has MultiProtoCol
capability which means the MPC can be congured
to communicate via BACnet, Johnson Controls N2, or
ModBus communication protocols. This conguration is
done via the “Communications Selection” jumper and the 4-position DIP switch package (SW1, SW2, SW3, SW4) located on the MPC. The communications port’s baud rate is also set with this same 4-position DIP switch package. See Figure 5 below.
Note: If using ARC156 wiring, then only BACnet protocol can be used. When using RS-485 wiring, any of the 3 protocols (BACnet, N2, ModBus) can be used.
Figure 5: Wiring the ARC156
Figure 6: Communications Selections
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC Controller Overview
BACnet Setup – The MPC can be set up to communicate
via “BACnet over ARC156” or “BACnet MS/TP”. Refer to Table 1 for setup.
N2 Setup – N2 must be congured for RS-485
communications with a baud rate of 9600, using 8 data bits, no parity, and 1 stop bit. The MPC is always an N2 slave. Refer to Table 1 for setup.
ModBus Setup – ModBus must be congured for RS-485
communications. Baud rate can be selected from 38.4 kbps, 19.2 kbps, or 9.6 kbps. Refer to Table1 for setup.
Table 1: Communications Set Up
MPC MultiProtoCol DDC Controls
November 19, 2018
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
Additional Information
Room Sensors
The MPC is design to work with specic sensors. Two
types of sensors may be used:
1. Lstat
2. RNet
The RNet connection is at the upper left of the MPC and
the LSat is at the lower left. Both are four to ve wire
sensors. The MPC comes factory set for the Lstat sensor at the room sensor jumper. To utilize the RNet sensors the jumper must be changed to RNet.
The use of the RNet sensor allows for an extra input into the MPC. The sensors are available with additional internal sensors possibilities including Humidity, CO2 or VOC. When using a unit equipped with Climadry Reheat, a combination temperature and humidity sensor is required. Refer to ASW section.
It is also possible to use the equipment touch as a wall sensor if only temperature or temperature and humidity
are required. See the Equipment Touch IOM for specic
instructions on enabling the Equipment Touch internal sensors. The ASW 6, 7, 8 ase LSTAT sensors. The ASW 13, 14, 15 are RNET sensors.
The LSTAT sensors are the ASW06, 07 and 08. The RNET sensors are the ASW13, 14 or 15. Additional sensors included can be humididity and CO2 . This is designated
by the H and/or C sufx.
Retrotting MPC to Existing Units
The MPC can be added to any ClimateMaster unit with
the CXM, DXM, DXM2 thermostat boards. A retrot
kit has been assembled with the board, the wiring and additional sensors are required.
LAT
The leaving air temperature is reported to the BNS. LAT control is not supported.
iGate Communication
On units equiped with a DMX2 board, the iGate functions are not available when the MPC is installed. The Service Tool can be connected directly to the DXM2 – to access the board functions. The MPC does not access these functions.
Additional Inputs
The AL1/AL2 and EHZ/GND inputs are available with either type of sensor. Two additional inputs are available when the Rnet sensor is used. These are Temp/GND and SW/GND.
AL1/AL2 and EH2 input terminals can accept 0-5VDC, Thermistor, or dry contact signals. Terminals LAT/LWTL and LWT/LWTS accept thermistor or dry contact signals.
LAT/LWTL and LWT/LWTS come with leaving air and leaving water temperature thermistors installed but can be repurposed. The Lsat terminals can be used for a additional thermistor input (Gnd/Temp) and SW can be used as a dry input contact.
The MPC allows custom factory programing of the various inputs to accomplish various sequence of operations as the building may require.
Certain options can be added to the MPC programing after installation of controls system upgrades/changes are being considered. Consult factory for applicability. The MPC can be programmed with a 7 day program: the routine is built into the software.
10
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
BACview6 Service Tool and Addressing
For existing installations only! For new installations use Equipment Touch Service Tool (BACview6 or Equipment Touch is required
to set up unit)
The BACview6 Service Tool provides local access to control and operational properties of equipment. The BACview6 simply plugs into an Rnet connection (local access port) and
allows you to display and modify Climate Master-dened properties without any computer
software. The BACview6 features a numeric keypad, directional keys, and four function keys. A large 4-line by 40-character backlit LCD display is provided for easy reading even in poor lighting conditions. The device also includes an alarm indicator light and audible warning. ClimateMaster recommends this service tool for sites over 25 units or units with the stand­alone application.
Part#1: ABACVIEW6 Part#2: ABACVIEW6A (cable)
November 19, 2018
Figure 6:
HOW TO WIRE ABACVIEW to ABACVIEW6A
When prompt for password. ClimateMaster Password: 1111
Red
Blue
White
Black&Green
12v Rnet­Rnet+ GND
11
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
BACview6 Service Tool and Addressing
Addressing & Power Up
Before setting or changing the module's hardware address, make sure the MPC Controller power is off. The MPC only reads the address when the module is turned on. The MPC has two rotary switches for assigning the module’s hardware address. One switch corresponds to the “tens” digit and the second switch corresponds to the “ones” digit, allowing for hardware- based address­ing of up to address 99. For example, if the module’s address is three, set the tens switch to zero and the ones switch to three. The station ID for each MS/TP node must be unique on a MS/TP segment. The MPC’s rotary address switches are used to set this unique ID.
Figure 8: Setting Module Address
After setting the address, turn power on to the MPC. The Run, Error, and Power LEDs should turn on. The Run LED should begin to blink and the Error LED should turn off.
Note: Set address for heat pump #1 (HP-1) at 02 per typical BMS naming conventions. All other heat pump addresses should be assigned as HP# + 1.
Changing the device instance when using a network of more than 99 MPC units
Note – This applies to Gen4 MPC’s only. When using
Gen3 MPC’s, to allow for more than 99 unique addresses, a special request should be made through the Product Management and Applications team.
The Gen 4, 5 and 6 MPC allows the device instance to be changed using the BACview6 service tool. This feature allows an installation with more than 99 MPC­based units to be set and managed on-site rather than factory preset.
In order to change the device instance, the MPC must be powered up. Connect the BACview6 service tool to the MPC using the local access port. When the main screen appears, scroll down to “Manual Control” using the down arrow and press “Enter”;
At the “Manual Control” screen, press “Enter” with
“Unit Conguration” highlighted and again with “BAC-
net” highlighted. The following screen should appear:
Figure 9:
1
12
THE SMART SOLUTION FOR ENERGY EFFICIENCY
BACview6 Service Tool and Addressing
Addressing & Power Up
MPC MultiProtoCol DDC Controls
November 19, 2018
Figure 10:
2
The device instance is typically six digits long. The last two digits correspond to the addressing roatary dials so these should not be changed using the BACview6.
To change the device instance, use the down arrow to highlight the numbers beside “Base BACnet Device ID” and press “Enter”. Leave the leading zeros (ex: "0001", "0002" You will be prompted for an Admin Password, the
password is 1111. A cursor underlining the nal digit of
the “Base BACnet Device ID” will appear.
Figure 11:
3
Figure 12:
4
13
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
Equipment Touch Service Tool Overview
Figure 12:
Touch to Display: Home Screen
Previous Screen
Alarm Screen
Wire the Equipment Touch to the controller's RNet port. The RNet can have one
Equipment Touch device and up to ve RNet (ASW13) sensors.
Note: The Equipment Touch RNet does not support RS Sensors. When prompted for password: ClimateMaster Password = 1111
14
Touch a Button to Display that Screen
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Power
Rnet + (white)
Panel
MPC MultiProtoCol DDC Controls
Equipment Touch Service Tool Overview
The Equipment Touch (Figure 12) is a touchscreen device with a 4.3 Inch color LCD Screen that is connected to an MPC GEN 7 Controller Unit. It will allow access to most all internal control/ status points, alarms that would normally require access to the system server (WebCNTL) to access. It is a replacement for the BACVIEW 6 service tool previously used for this purpose, but has increased functionality. Equipment Touch does not currently support water to water applications. The Equipment Touch (or EQT) can also function as a wall sensor
providing Temperature and Humidity data to the Controller when congured correctly. The
EQT connects to the MPC Controller’s RNet port in the same manner as the RNET Wall sensors and can reside with up to 5 RNet Sensors. Each MPC GEN 7 controller can support up to 5 RNet Sensors and one EQT (Figure 13 and 14).
Figure 13: Basic Equipment Touch connection program
November 19, 2018
Display
Red
Green
White
Black
Supply
24
VAC
Panel
Controller
24 ac GND
Rnet
Rnet Wiring
Rnet - (black)
Figure 14: Equipment Touch wiring diagrams
• Wire the Equpment Touch in a daisy-chain conguration with up to 5 RNet zone sensors as shown below.
Equipment
Touch
Green
Red Black White
Rnet
Sensor
Green
Red Black White
Green
Red Black White
Rnet
Sensor
Green
Red Black White
Rnet
24V Sensor
GND
Controller
Rnet 210 mA 12 VDC
S1
S2
S1DCBA
S2
External
Thermistor
Power Wiring
24 V + (red)
GND + (green)
Note- You do not need to set an address for the Equipment Touch.
Green
Red
Power Supply
24
VAC
15
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
Equipment Touch Mounting Details
Wiring and Mounting the Equipment Touch
1. Remove the backplate from the Equipment Touch:
a. Hold the Equipment Touch as shown in the image below.
Figure 15:
b. While rmly pressing the two tabs on top of the Equipment Touch, pull on the back­ plate with your index nger untill the back- plate releases from the Equipment Touch.
2. Pull the communication cable, power cable and external thermistor wiring (if applicable) through the large hole in the center of the backplate.
3. Partially cut, then bend and pull off the outer jacket of the RNet cable(s). Do not nick the individual wire insulation.
4. If wiring 1 cable to the Equipment Touch, cut the shield wire off at the outer jacket, then wrap the cable with tape at the outer jacket to cover the end of the shield wire. If wiring 2 cables in a daisy-chain
conguration, twist together the shield wires, then wrap the cable with tape.
5. Strip about 0.25 inch (0.6) insulation from the end
of each wire.
6. Connect wiring to the Equipment Touch as shown below:
7. Attatch the backplate to the wall or panel. If mounting in or on a panel: a. Drill two 3/16 inch (4.8mm) pilot holes in the panel. b. Attatch a backplate using pan head 6-32 x 3/8" to 1/2" long machine screws. Do not over tighten screws to prevent damage to plastic housing. Recommendation: Use Loctite 220 on screw
threads if the Equipment Touch will be subject to vibration.
8. Attatch the Equipment Touch to the backplate:
a. Place the bottom of the equipment touch onto the backplate by aligning the 2 slots on the Equipment Touch with the tabs on the backplate. b. Push the Equipment Touch onto the backplate until the tabs at the top of the Equipment Touch snap onto the backplate.
9. Turn off the controller's Power.
10. Connect the other end of the RNet wiring to the
controller's RNet port or to a zone sensor.
Notes- Insert the shield wire with the ground wire into the controller's GND terminal. Use the same polarity throughout the RNet.
11. Connect power wiring to a 24 Vac power supply.
12. Tur n on the controller's power.
CAUTION!
Allow no more than 0.6 inch (1.5mm) bare communication wire to protrude. If bare communiaction wire contacts the cables foil shield, shield wire or a metal surface other than the terminal block, the device may not communicate correctly.
Figure 16:
16
MPC LED Codes
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
The MPC Controller has the following LEDs:
Power - indicates when power is on. Run - blinks when the processor is running. Error - lights when an error is detected. Receive (Rx) - lights when the Comm Port receives data. Transmit (Tx) - lights when the Comm Port transmits data. Digital Output - lights when the associated digital output turns on.
LED Power-Up Sequence
During power-up, the module goes through an initialization and self test sequence.
Proper module power-up can be veried by observing
the LEDs as follows:
1. The Run and Error LEDs turn on and begin blinking.
2. The Error LED then turns off.
3. The Run LED continues blinking.
Note: The Error LED ashes three times in sync with
the Run LED when the module is being formatted.
The Run LED should never stop ashing. If it stops ashing for 1.5 seconds, the watchdog timer will reset
the module.
Overcurrent Protection
The MPC Controller is protected by internal solid state polyswitches (polymeric PTC, resettable overcurrent protection device, also called PPTC) on the incoming power. The overcurrent protection circuitry is a positive
temperature coefcient (PTC) thermistor that increases
in resistance as it warms up and stays in that mode until the power is removed. Once the power is removed, the polyswitch resistance lowers to operational level as the device cools down. After power has been re-applied, the unit will operate properly if the fault condition has been removed.
It is not necessary to remove power on the communication line in order to reset the solid state overcurrent circuit. Once the power level is low enough, the overcurrent circuit cools down to operating temperature. A blown polyswitch can indicate incorrect wiring if the polyswitch is blown during installation. Generally, a blown polyswitch indicates a power surge was received by the board.
Digital Output LEDs
There are 5 digital outputs on the MPC. One output
(AUX) can be custom congured to control an external
device (1amp at 24VAC.). G, O, Y2, and Y1 are required to operate the heat pump and are connected to the CXM, DXM or DXM2 board.
Table 2: MPC Flash Codes
Run LED
2 ashes
per second
2 ashes
per second
2 ashes
per second
2 ashes
per second
2 ashes
per second
2 ashes
per second
5 ashes
per second
5 ashes
per second
7 ashes
per second
14 ashes
per second
Error
LED
OFF Normal
2 ashes,
alternating
with Run
LED
3 ashes
then OFF
4 ashes
then
pause
6 ashes
then OFF
ON
ON
OFF
7 ashes
per
second,
alternating
with Run
LED
7 ashes
per
second,
alternating
with Run
LED
Condition Action
Expected behavior of a congured controller
Controller will count down the ve minutes,
Five minute auto­restart delay after system error
Module has just been formatted
Two or more devices on this network have the same ARC156 network address
Module’s response to a LonTalk ‘wink’ command received from a LonWorks Network Management Tool
Exec halted after frequent system errors or GFB’s halted
Exec start-up aborted, Boot is running
Firmware transfer in progress, Boot is running
Ten second recovery period after brownout
Brownout
then attempt to restart normally if the condition that caused the fault returns to normal. Disconnect all wiring and see if the controller will restart normally.
This condition should not occur with a congured controller. Memory archive ensures the controller will always have a conguration.
Disconnect the comm connector then assign a unique network address.
If this condition occures you have two options:
• Manual restore of memory from archive
• Download memory
Normal behavior during a memory download
Precedes the brownout
condition
Check power supplied to the controller
N/A
N/A
17
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
MPC Sequence of Operation
Fan Operation – Digital output point G (DO4) is the fan
output and is connected to the "G" terminal on the CXM, DXM or DXM2 control. If fan Mode is set to "Auto" ECM, then the fan is energized only during a call for heating or cooling. "Auto" mode is the default mode of operation At 30% PID, the fan(G) energizes in Auto
mode.
Heating/Cooling Changeover – The Digital output
"O" (DO3) is the RV output and is connected to the "O" terminal on the CXM, DXM or DXM2 board. "O" is energized during call for cooling. The RV (O) energizes
at 40% PID in cooling only.
Compressor Operation – The Digital outputs Y1 (DO1)
and Y2 (DO2) are the outputs for compressors stage 1 and 2. Y1 is connected to Y terminal on the CXM/ DXM/DXM2 and if the heat pump is dual stage, Y2 is connected to a second CXM Y input or Y2 on the DXM/DXM2.
Y1 and Y2 are off when the zone temperature is between the heating and cooling set points. As the zone temperature rises above cooling set point or below heating setpoint, Y1 is energized at 50% PID and Y2 is
energized at 75%.
Troubleshooting Tips – If the BMS is having trouble
communicating with the MPC, check the following items before contacting technical support.
• Make sure the MPC wiring is correct. Make sure all color codes match and that no wire strands are shorting over to other terminals.
• Make sure the MPC and other network controllers have power and are turned on. Make sure all equipment have power and LEDs lit with no solid error light. Some devices, especially communication devices, receive power from a source other than a power cable or adapter. Some panels can be reinitialized by resetting the panel.
• Verify operation of all LEDs: RX, TX, Power, Run, DOs and error.
• Make sure that all jumpers are set to default and that there is nothing jumped on the format pin.
There is also a load sharing mode which permits swapping the primary status of Y1 with Y2 depending on compressor run time. The low time compressor becomes primary and the high time compressor assumes secondary status.
Note: All 5 digital outputs have associated LEDs to indicate operating status. If the digital output is on, then the associated LED will be on.
Occupied/Unoccupied Changeover – When the
MPC is in the stand-alone mode of operation, the MPC defaults to the occupied mode of operation. Occupancy changeover may be provided through the communications network.
18
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC Sequence of Operation
MPC MultiProtoCol DDC Controls
November 19, 2018
Water -to-Water Start Up Check
1. Unit powered up and running.
2. LED check: Rx, Tx, Power, Run and no solid red error led.
3. Program initializing schedule status for Occupied Mode (default) or Unoccupied Mode to determine set point range. Occupied set points will be defaulted to 60 cooling and 105 heating. If a schedule is implemented, the unoccupied set points will default to 80 cooling and 85 heating.
4. The Program will determine if the unit is either a Master or Slave.
5. The Program will control the water temperature based on the Entering Water Temperature (EWT) load sensor. This can be changed to control based off of the LWT via BAS or BACview6 service tool.
6. The Program will check for which water temperature set point to use based on Heating Mode or Cooling Mode determined by the state of the RV.
7. In a water to water application, the mode has to be manually changed via Bacnet or with BACVIEW6 service tool. If it is in heating, it will permanently stay
in heating mode until it is changed to specically
cooling mode.
8. Like water to air, Y1 will come on a 50% and Y2 at 75% and not off until the EWT/LWT conditions have
been satised.
9. 5-minute delay is built in between compressor cycles.
10. While the unit is on, the program will continue to monitor the CXM/DXM/DXM2 board for faults. If an event of a fault occurs and the unit is in lockout mode, then the relay will close (IN1/AL1/AL2/GND) and the fault code is transmitted via EH2 output to the EHZ input on the MPC. This is available through BAS network points. A history counter will also keep track of past and present faults which can also be seen via BAS or BACview6.
11. The MPC can also function in metric mode (Celsius mode).
Water-to-Air Startup Check­Equipment Touch Method
1. Unit is Powered up? YES: Go to step 2 NO: Apply power to MPC.
2. Check Led status. a. Green (TxD) LED should be blinking rapidly. b: Green power LED should be on solid . c: Green RUN LED should be blinking at 1-2 blinks per second. d: RED error LED should be off. YES: Go to step 3. Power down MPC and wire up the Equipment Touch Service Tool and RNet Sensor(s). Once these are installed, power MPC back up.The Equipment Touch should power up and display the “Main” (Home)
Figure 16: Menus screen
3. Navigate to the “Sensor Setup and Status” screen by pressing <MPC Setup/Status> then <Sensor Setup/Status> buttons. Press the <ZS Sens Active>
button. This should display the correct address and number of ZS Sensors that are attached to the MPC. Press the <Back> and go to the “ZS Sensor Setup screen where you will need to enable the alarms for each sensor installed and detected in the previous step.
4. From the EQT menu press <Temp Setup and Status> then press <Temp Units>. “Current Mode should be set to <Fahrenheit>. If this is ok, you are
nished here and can move on to Step 5. Otherwise
uncheck the “Metric Mode” (BV:39) point to set the MPC to Fahrenheit mode. Make sure the “Current Mode” changes to “FAHRENHEIT” before pressing <BACK> and exiting this screen.
19
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
MPC Sequence of Operation
From the <Temp Setup and Status> screen press <Temp Setpoints>.
• The default settings for the Fahrenheit and Celsius operation modes are listed here in this screen. If your setpoints differ from the default values listed here, please enter them in the appropriate box.
Table 3:
Description Fahrenheit° Celsius°
Master Zone Temp 73.0 22.7
Unoccupied Dead Band 17 9.44
Occupied Dead Band 2 1.11
Unoccupied Heat Setpoint 82 27.7
Occupied Cool Setpoint 74 23.3
Slave Heat Setpoint 72 22.2
Slave Cool Setpoint 74 23.3
• Press the <Manual SP> button to go to the MANUAL SP” Screen in which you can edit the Manual Setpoint Adjust Range. It is defaulted to +/- 5° Fahrenheit or 2.8 ° Celsius. This will allow you to have a 10 F° / 4.6 C° adjustment range of the setpoint from the sensor. If you wish a looser or tighter range, please enter it now. Note: if it is set to zero, no adjustment can
be made from the Wall Sensor.
5. The MPC will default to RNet Sensors. If you have LSTAT Sensor types you will need to set jumper W3 to LSTAT.
6. From the “MPC Setup/Status” screen press <Compressor Setup>. Please check the compressor setting to ensure all are set to the default factory settings. Load Balance Select controls the stage assignment of compressors. The default setting assigns compressor 1 as primary and compressor 2 as secondary. Note: For single compressor systems
C1 should always be primary.
Table 4:
Description Point Default
Load Balance Select AV:59 2
Compressor Shut Down BV:53 Unchecked
C1 Manual BV:30 Unchecked
C2 Manual BV:31 Unchecked
C1 Runtime Reset BV:2 Unchecked
C2 Runtime Reset BV:5 Unchecked
C1 Cycle Reset BV:21 Unchecked
C2 Cycle Reset BV:22 Unchecked
7. From the “MPC Setup/Status” screen press <Heat/ Cool Control>. Ensure that the following points
are set to the default values. The default values enable both the heating and cooling modes and ensures the reversing value is not in manual mode. If you need “Heat Only” or “Cool Only” modes, uncheck the appropriate enable for the mode you wish to disable. 99% of all applications will have both enabled.
Table 5:
Description Point Default
Heat Mode Enabled BV:61 Checked
Cool Mode Enabled BV:54 Checked
Reversing Valve Manual BV:30 Unchecked
8. From the <MPC Setup/Status> screen press <Fan/ Filter Control>.Check the following point for the
correct default value. The Supply FAN is congured
to cycle anytime the compressor is “ON”.
Table 6:
Description Point Default
Emergency Shutdown BV:8 Unchecked
Supply Fan Manual BV:28 Unchecked
Supply Fan Congure AV:33 1
Dirty Filter Reset BV:7 Unchecked
Dirty Filter Interval AV:30 1500
Dirty Filter Mode BV:60 Time
Dirty Filter Sens BV:59 Unchecked
Fan Speed Enable BV:51 Unchecked
Fan Speed Trigger Type AV:56 75%
9. From the “MPC Setup/Status” screen press <Heat/ Cool Control>. Check Occupancy BV:12 and make
sure it is set to “Occupancy”.
From the “MPC Setup/Status” screen press
<AUX Outputs>. Check the “AUX CFG” setting for the default value of 1. This is Emergency Electric Heat. If other functions are needed please consult the Control Points Matrix for other functional settings associated with this point.
20
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC Sequence of Operation
MPC MultiProtoCol DDC Controls
November 19, 2018
From the “MPC Setup/Status” screen press <Maintenance>. From this screen, you can adjust
the temperature setpoint and watch the function of the MPC. You can remove the Y1, Y2 output wires to keep unit from going into Heat or Cool mode for this operation.
1. You should see both the Occupied ICON and the ”AUX Mode = Emergency ELEC Heat”. If there is no RNET Sensor installed with a humidity sensor present, the “RH” Icon will be equal to 0.0.
2. Read the Zone Temperature and adjust the Zone Heating Setpoint at least 2 ° above the ambient zone temperature. (You can use the RNet Sensor or the Equipment Touch for this operation). You should be able to observe the “Heat PID” Icon start increasing as the MPC is set to go into a heating cycle. a. When the PID value increases above 30% the FAN ICON for the Supply Fan will appear. b. When the PID rises above 40% the RV ICON will appear indicating the Reversing Valve is on. c. When the PID gets to 50% the Compressor C1 will turn on after a 2 minute delay. You should see the C1 ICON after the delay. d. If the Heating unit is wired to the unit and thus not heating, the PID will continue until it reaches 75% and then you should see Compressor 2 or C2 ICON appear. If the PID is allowed to rise it will trigger the Emergency Electric Heat (AUX) output when it goes above 90%. This assumes heat demand has not been satised. e. Decrease the Heating Setpoint 2° below the Zone Temperature and the Heating PID will begin to move downward. f. Once it falls below 90%, the ”AUX” output will turn off and below 75%, C2 will turn off. g. When it falls below 50%, the compressor output C1 will turn of and once it falls below 40% the Supply Fan will turn off.
3. Read the Zone Temperature and adjust the Zone setpoint at least 2° below the ambient Zone Temperature. You should be able to observe the Cool PID start increasing as the MPC is set to go into a Cooling cycle. a. When the PID rises above 40% the FAN ICON will appear indicating the Fan has cycled on. b. When the PID gets to 51% the Compressor C1 will turn on after a 2 minute delay. You should see the C1 Icon after the delay. c. When the Compressor C1 is “ON” decrease the Zone Cooling Setpoint 2° above the Zone Temperature and the Cooling PID will begin to move downward. d. Once it falls below 90%, C2 will turn off. e. When it falls below 50%, C1 will turn of and once it falls below 40% the Supply Fan will turn on.
21
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
MPC Sequence of Operation
Table 7:
Water-to-Air Startup Check­BACview6 Method
1. Unit is Powered up? YES: Go to step 2 NO: Apply power to MPC.
2. Check Led status.
a. Green (TxD) LED should be blinking rapidly. b: Green Power LED should be “ON” Solid (not Blinking). c: Green RUN LED should be blinking at 1-2 blinks per second. d: RED error LED should be "OFF". YES: Go to step 3.
3. Power down the MPC and wire up the BACview6
Service Tool and ZS Sensor(s). Once these are installed, power MPC back up. The BACview6 should power up and display the “Main” (Home)
Figure17: Main menu screen
4. Navigate to the “Sensor Setup and Status” screen
by highlighting [Manual Control] and clicking <Enter>, then highlighting [Unit Control], and
clicking <Enter> cursor down the list and make sure the following are set correctly.
Description Point Default
Test Mode OFF
Reversing Valve Output OFF
Supply Fan Output OFF
Compressor 1 Output OFF
Compressor 2 Output OFF
Auxillary Output OFF
Supply Fan Mode AUTO
Dirty Filter Interval 1500
Emergency Shutdown OFF
Heating Mode ON
Cooling Mode ON
Dirty Filter Mode Time
Load Balance Select 2
EXT OCC/ Dirty FILT Sens OCC
Archive Enable OFF
RNET Sens1 Enable ON
RNET Sens2 Enable OFF
RNET Sens 3 Enable OFF
RNET Sens4 Enable OFF
RNET Sens5 Enable OFF
5. Navigate to “AUX Output Conguration” by
highlighting [Manual Control] and clicking <Enter>, then highlighting [Unit Conguration], and clicking <Enter> cursor down the list and make sure “AUX
OUTPUT” Conguration is set to 1 and Supply Fan Conguration is set to 1.
6. Navigate to Zone Temperature Control settings by highlighting [Manual Control] and clicking <Enter>, then highlighting [Zone Temperature Control], and clicking <Enter> cursor down the list and make sure “Occupied Mode” is set to Occupied and “Metric Mode” is OFF.
22
Loading...
+ 50 hidden pages