Climate Master Flow Controller Installation Manual

C
LIMATE
M
ASTER
¤
Flow Controller
GEOTHERMAL PUMPING MODULE
INSTALLED BY:
Flow Controller
Installation, Operation, &
Maintenance Instructions
12/98
TABLE OF CONTENTS
Flow Controller Description 2 Flow Controller Mounting 2 Piping Installation 3 Electrical Wiring 4 Flushing the Earth Loop 5 Antifreeze Selection 6 Antifreeze Charging 7 Heat Pump Freezestat Setting 8 Pressure Drop Tables 9 Earth Loop Pressurization 9 Flow Controller Start-Up 10 Pump Cartridge Replacement 10 Closed Loop Design 11 Polyethylene Pressure Drop 14 Rubber Hose Pressure Drop 15 Closed Loop Installation 16 Building Entry 18
1
FLOW CONTROLLER DESCRIPTION
10.75"
Unit Side
13.75"
TTaacco
o
TTaacco
o
Loop Side
4.38"
8.75"
Figure 1 - Flow Controller Dimensions
The AFCS1A and 2A are insulated flow controllers containing all flush, fill, and isolation connections for a residential and light commercial geothermal closed loop system that require a flow rate of no more than 20 gpm. The AFCS1A and 2A are equipped with a large bore 1 1/ 4" FPT swivel fittings for both earth loop and heat pump unit connections. Either 1 (AFCS1A) or 2 (AFCS2A) Taco 0013 chilled water rated cartridge type circulators
3.75"
15.00"
8.50"
are included with the flow controller. Included in this kit are:
• 2 Lag bolts for mounting AFC onto stud walls
• 4 Self-drilling sheet metal screws for mounting AFC onto heat pump
• 2 1" MPT PVC plug for sealing flush ports after installation
FLOW CONTROLLER MOUNTING
General
The installation of the ClimateMaster Flow Controller shall be made in accordance with all applicable codes.
Mounting the Flow Controller
The flow controller should be located as close to the unit as possible to limit the length of the rubber hose kit and thus its associated pressure drop. In general the flow controller can be mounted in any orientation with the exception of when the pump shafts are in a vertical position as when it is laid flat on the floor or any similar position. The controller is typically mounted in one of three locations. Be certain there is adequate access to all required flush ports and valves before mounting.
Stud Wall - Mounting on stud wall with or without drywall can be accomplished by using the two supplied lag bolts through the top and bottom center holes directly into the studs as shown in Figure 2.
Self-drilling screws into sheet metal 4 places.
DO NOT PUNCTURE INTERNAL
COMPONENTS!
Unit Side
o
TTaacco
Loop Side
Heat Pump Cabinet
TTaacco
o
Figure 2 - Mounting Flow Controller on Stud Wall
2
Side of Unit - Mounting on the side of the unit can be accomplished by using the four self-drilling screws directly into the sheet metal access panels or cabinet as shown in Figure 3. Be careful not to puncture any internal piping or other components with the screws. It
should be remembered that heat pump access will be limited in this mounting position.
Tubing Insulation
brought up to cover
complete connection
1-1/4” MPT
Remove
Cover
TTaacco
Unit Side
o
Loop Side
Figure 4 - AFCS1 Piping Detail
Figure 3 - Mounting Flow Controller on Side of Unit Concrete wall - Mounting onto a concrete wall can be
accomplished by using 4 1/4" ‘Tapcon’ screws (supplied by others) directly into the concrete wall.
Piping Installation
The Flow controller features 1 1/4" FPT swivel fittings for flexible and easy installation. Table 1 illustrates the connection options available for the AFCS1A and 2A. Avoid using 3/4" piping on flows greater than 6 gpm. Pressure drop in piping systems should be calculated to insure adequate flow through the unit. All piping should
be insulated with closed cell insulation of 1/2" wall thickness. Table 2 shows the insulation requirements for
typical piping materials. Piping insulation should be glued and sealed to prevent condensation using closed cell insulation glue. The swivel connectors on the flow
controller are designed to be hand tightened only.
Table 2 - Typical Piping Insulation Materials
Piping Material Insul Description
1" Hose Kit 1-3/8" ID - 1/2" wall 1" IPS PE 1-1/4" ID - 1/2" wall 1-1/4" IPS PE 1-5/8" ID - 1/2" wall 2" IPS PE 2-3/8" ID - 1/2" wall
Loop side piping is typically polyethylene piping directly into the flow controller. Connection to the flow controller can be accomplished by a fusion-to-brass MPT adapter (GFMA66). In multiple flow controller systems such as multifamily housing, PVC can also be used on the loop side, remembering however that the transition from PVC to PE should be accomplished by a flange connection and PVC is approved for use only as an indoor piping material in earth loops.
Unit side piping is typically connected using the ClimateMaster hose kit (AHK5E) which contains all fittings necessary for connection between the flow controller and the unit as shown in Figure 5. In the AFCS1A remove cover and make connections as shown in Figure 4, remembering all areas of the piping should be insulated to prevent condensation.
In multiple unit systems, PVC adapters (1 1/4" MPT x PVC socket) to the flow controller and standard PVC piping materials can be used to ‘tee’ more than one unit into the flow controller. It is recommended that a hose kit still be used at the end of the PVC piping run to facilitate ease of installation and service of the units as shown in Figure 6. Insulate all exposed piping. Plastic-to-metal threads should not be used due to their leakage potential.
To Heat Pump 1"
Swivel Fitting
P/T Port
Rubber Hose Max of
15" Each Side
To Flow Controller 1 1/4"
Swivel Fitting
All Stainless
Hose Clamp
Figure 5 - AHK5E Hose Kit Typical Detail
Table 1 - AFCS1A and 2A Connection Materials
To Fittings
PVC 1-1/4" MPT x 1" PVC Glue Socket PE Fusion 1-1/4" MPT x 1-1/4" PE Fusion PE Barb 1-1/4" MPT x 1-1/4" insert barb* Copper Sweat 1-1/4" MPT x 1" sweat** Copper Thread 1-1/4" MPT x 1" MPT Nipple
* Use double all-stainless hose clamps ** Sweat before connecting to flow controller
From Flow Controller
1 1/4" MPT x Glue Socket
15" each side
1 or 1 1/2"
SCH 40 PVC
Insert Barb x Glue Socket
Rubber Hose Max of
15" each side
To Heat Pump #1 To Heat Pump #2
Rubber Hose Max of
Figure 6 - Two Units Utilizing One Flow Controller (one side shown)
3
FLOW CONTROLLER ELECTRICAL WIRING
Power wiring to the flow controller should conform to all applicable codes. Figure 7 illustrates the wiring required for the Classic and Figure 8a and 8b for Genesis. Note the flow controller is available in only in 230V single phase voltage. Pumps are fused through a pair of circuit breakers in the unit control boxes. See electrical table for flow controller characteristics.
External Loop Pump(s)
208/230 Volt-4 Amp Max.
Transformer
L2 L1
CRR
Unit Ground
Loop Pump
Term Blk
HWG Pump
Term Blk
PR
CCM PCB
T1
HPS LPS
Y
X
Compressor
Contactor
Pump Ground
Min Sec.
T C
Electrical Table
Model Volts Amps HP
AFCS1A 230 .88 1/8 AFCS2A 230 1.76 1/4
Circuit Breakers
Transformer
External Loop Pump(s)
208/230 Volt-4 Amp Max.
CRR
T1
Y
CCM PCB
HPS LPS
X
PR
Min Sec.
T C
Compressor
Contactor
L2 L1
Loop Pump
Term Blk
T1
HPS LPS
Y
X
Ground
CCM PCB
Min Sec.
T C
Thermostat Connection
Compressor
Contactor
HWG Pump
Term Blk
ICM2 Controller
Figure 7 - Power Wiring to Classic Series
o
TTaacco
External Pump Power Supply
See electrical table for
wire and breaker size
Figure 8B - Power Wiring to Genesis Series
Contactor -CC
Transformer
Figure 8A - Power Wiring to Ultra Classic Series
Capacitor
Circ Brkr
HWG PB2
Loop PB1
T2
Grnd
L1
L2
BR
CXM Control
CB
Low Voltage Connector
T1
T1
T2
4
FLUSHING THE EARTH LOOP
Once piping is completed between the unit, flow control­ler, and the ground loop, final purging and charging of the loop is needed.
A flush cart (at least a 1.5 hp pump) is needed to achieve adequate flow velocity in the loop, to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. All air and debris must be removed from the earth loop piping system before operation. Flush the loop with a high volume of water at a high velocity (2 fps in all piping) both directions, using a filter in the loop return line of the flush cart to elimi­nate debris from the loop system. The steps below must be followed for proper flushing.
Loop
Flush Cart
Flow
Controller
Valve
Positions
Garden Hose
Unit
Figure 9A - Valve Position A - Loop Fill
Fill loop with water from a garden hose through flush cart before using flush cart pump to ensure an even fill and increase flushing speed. When water consistently returns back to the flush reservoir switch to valve position B.
Flush Cart
Loop
Flow
Controller
Valve
Positions
This position should be switched while filling, to fill the unit heat exchanger and hose kit. This should be main­tained until water consistently is returned into the flush reservoir.
Loop
Dead Head
Pump Test
for Air
Unit
Flush Cart
Flow
Controller
Valve
Positions
Figure 9C - Valve Position C- Loop Flush
Switch to valve position C. The supply water may be shut off and the flush cart turned on to begin flushing. Once the flush reservoir is full, do not allow the water level in the flush cart tank to drop below the pump inlet line or air can be pumped back out to the earth loop. Try to maintain a fluid level in the tank above the return tee so that air cannot be continuously mixed back into the fluid. 50 psi surges can be used to help purge air pockets by simply shutting off the return valve going into the flush cart reservoir. This ‘dead heads’ the pump to 50 psi. To dead head the pump until maximum pumping pres­sure is reached, open the valve back up and a pressure surge will be sent through the loop to help purge air pockets from the piping system. Notice the drop in fluid level in the flush cart tank. If all air is purged from the
system, the level will drop only 1-2" in a 10" diameter PVC flush tank (about a half gallon) since liquids are incompressible. If the level drops more than this,
flushing should continue since air is still being com­pressed in the loop fluid. Do this a number of times. When the fluid level is dropping less than 1-2" in a 10" diameter tank the flow can be reversed.
Garden Hose
Unit
Figure 9B - Valve Position B - Unit Fill
5
Dead Head
Pump Test
for Air
Flush Cart
Add Antifreeze
Now if Needed
Loop
Flow
Controller
Valve
Positions
1
Dead Head
Pump to
Pressurize
to 50 PSI
Flush Cart
2 Close to Isolate Flow Controller
Loop
3
Close Flow
Controller Valves for Operation
Mode
Valve
Positions
Unit
Figure 9D - Valve Position D - Full Flush
Now by switching both valves to this position water will flow both through the loop and the unit heat exchanger. Finally the "dead head" test should be checked again for an indication of air in the loop. This fluid level drop is
your only indication of air in the loop. Antifreeze may be added during this part of the flushing procedure (see antifreeze section for details).
Close the flush cart return valve, and after pressurizing, close the flush cart supply valve to pressurize the loop to a static pressure of at least 50 psi. If water pressure is
ANTIFREEZE SELECTION
General
In areas where minimum entering loop temperatures drop below 40°F or where piping will be routed through areas subject to freezing, antifreeze is needed. Alcohols and glycols are commonly used as antifreezes, however your local representative should be consulted for the antifreeze best suited to your area. Freeze protection should be maintained to 15°F below the lowest expected entering loop temperature. For example, if 30°F is the minimum expected entering loop temperature, the leaving loop temperature would be 25-22°F and freeze protection should be at 15°F (30°F-15°F=15°F). All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under water level to prevent fuming. Initially calculate the total volume of fluid in the piping system using Table 3. Then use the percentage by volume shown in Table 4 for the amount of antifreeze. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specific gravity.
Unit
Figure 9E - Valve Position E - Pressurize and Operation
low, use an air compressor to bump the pressure up through the P/T port. The loop may be isolated by moving to valve position E keeping watch on the pressure gauge of the flush cart for pressure greater than 50 psi. Loop static pressure will fluctuate with the seasons and pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially. Unhook flush cart from the flow controller. Install counter sink plugs using sealant compatible with PVC.
Antifreeze Characteristics
Selection of the antifreeze solution for ClimateMaster closed loop earth coupled systems requires the consider­ation of many important factors which have long-term implications on the performance and life of the equip­ment. Each area of concern leads to a different “best choice” of antifreeze. The fact is that there is no “ideal”
antifreeze and any choice will require compromises in one area or another. Some of the factors to consider are
safety, thermal performance, corrosiveness, local codes, stability, convenience, and cost.
Methanol - Methanol or wood alcohol is considered toxic in any form, good heat transfer, low to mid price, flammable in concentrations greater than 25%, non­corrosive, and low viscosity. Methanol has delivered outstanding performance in earth loops for over 10 years. Its only drawbacks are toxicity and flammability. Although methanol enjoys widespread consumer use as a windshield washer fluid in even higher concentrations,
6
some local codes may limit its use in earth loops. To increase safety, a premixed form should be used on the job site to increase the safety factor. Pure methanol can be purchased from any chemical supplier.
Ethanol - Ethanol or grain alcohol exhibits good heat transfer (slightly less than methanol), higher price, and is flammable in concentrations greater than 10%. Ethanol is generally non-corrosive and has medium viscosity. Ethanol in its pure form is considered non toxic and shows promise as a geothermal heat transfer fluid, however, the U.S. Bureau of Alcohol, Tobacco, and Firearms (ATF) limit its distribution. All non-beverage ethanol is required to be denatured and rendered unfit to drink. Generally this is done by adding a small percent­age of toxic substances such as methanol, benzene, or gasoline as a denaturant. Many of these denaturants are difficult to identify by the casual user and many are not compatible with polyethylene pipe. Only denatured ethanol can be purchased for commercial use. CM does not recommend the use of ethanol because of the un­known denaturants included and their possible toxicity and damage resulting to polyethylene piping systems.
Ethylene glycol - Generally non-corrosive, expensive, medium heat transfer, however is considered toxic. Its toxicity has prevented its widespread use in the ground source industry in spite of its widespread use in tradi­tional watersource heat pump applications. CM does not currently recommend ethylene glycol as a ground source antifreeze.
Propylene glycol - Non toxic, non-corrosive, expensive, hard to handle when cold, poorest heat transfer, has formed “slime-type” coatings inside pipe. Poor heat transfer has required its removal in some systems. Propylene glycol (PG) is acceptable in systems anticipat­ing loops temperatures no colder than 40°F. These systems typically are antifreeze because of ambient conditions (outside plumbing or cooling tower, etc.). When loop temperatures are below 40°F., the fluid becomes very difficult to pump, and heat transfer characteristics suffer greatly. CM recommends only food grade propylene glycol be used to prevent the corrosion inhibitors (often present in other mixtures) from reacting with local water and "coming" out of solution to form slime type coatings inside heat exchangers and thus hinder heat transfer.
GS4 (Potassium acetate) - Non toxic, good heat transfer, high price, non-corrosive with added inhibitors, low viscosity. Due to its low surface tension, GS4 has been known to leak through mechanical fittings and certain thread sealants. A variant of the salt family, it can be extremely corrosive when exposed to air. CM does not recommend the use of GS4 with its products due to the leaking and ultimate corrosion problems associated with it.
Contact the ClimateMaster Technical Services Depart­ment if you have any questions as to antifreeze selection.
ANTIFREEZE CHARGING
It his highly recommended to utilize premixed antifreeze fluid where possible to alleviate many installation problems and extra labor.
The following procedure is based upon pure methanol and can be implemented during the Full Flush procedure with three-way valves in the Figure 9D ­Valve Position D. If a premixed methanol of 15°F freeze protection is used, the system can be filled and flushed with the premix directly to prevent handling pure methanol during the installation.
1) Flush loop until all air has been purged from system and pressurize to check for leaks before adding any antifreeze.
2) Run discharge line to a drain and hook up antifreeze drum to suction side of pump (if not adding below water level through approved container). Drain flush reservoir down to pump suction inlet so reservoir can accept the volume of antifreeze to be added.
3) Calculate the amount of antifreeze required by first calculating the total fluid volume of the loop from Table 3. Then use Table 4 for the appropriate freeze
protection level. Many southern applications require freeze protection because of exposed piping and flow controller ambient conditions. An extra 10°F of freeze protection is needed in Paradigm outdoor applications.
Table 3 - Fluid Volume of Common Piping Materials Fluid Volume (gal/100' pipe)
Pipe Size Volume
1" 4.1
Copper 1.25" 6.4
1.5" 9.2 Rubber Hose 1" 3.9 Polyethylene 3/4" IPS SDR11 2.8
1" IPS SDR11 4.5 1 1/4" IPS SDR11 8.0 1 1/2" IPS SDR11 10.9 2" IPS SDR11 18.0 1 1/4" IPS SCH40 8.3 1 1/2" IPS SCH40 10.9
2" IPS SCH40 17.0 Unit Heat Exchanger Typical 1.0 Flush cart tank 10" diam x 3 ft 10.0
7
Table 4 - Antifreeze Percentages by Volume
-50 -40 -30 -20 -10 0 10 20 30 40 50
0.960
0.965
0.970
0.975
0.980
0.985
0.990
0.995
1.000
Freeze Protection - Degrees F˚
Specific Gravity
Type Minimum Temperature for Freeze Protection
10°F15°F20°F25°F
Methanol 25% 21% 16% 10% 100% USP food grade Propylene Glycol 38% 30% 22% 15%
4) Isolate unit and prepare to flush only through loop. Start flush cart, and gradually introduce the required amount of liquid to the flush cart tank (always introduce alcohols under water or use suction of pump to draw in directly to prevent fuming) until attaining the proper antifreeze protection. Noting the rise in flush reservoir level indicates amount of antifreeze added. Some carts are marked with measurements in gallons. A ten inch diameter, three foot cylinder holds approximately eight gallons of fluid. If more than one tankful is required, the tank should be drained immediately by opening the waste valve of the flush cart, noting the color of the discharge fluid. Adding food coloring to the anti­freeze can help indicate where the antifreeze is in the circuit, which prevents the dumping of antifreeze out the waste port. Repeat if necessary.
5) Be careful when handling methanol. The fumes are flammable, and care should be taken with all flammable liquids, such as alcohols. Open flush valves to flush through both the unit and the loop; flush until fluid is homogenous and mixed. It is
recommended to run the unit in the heating and cooling mode for 15-20 minutes each to ‘temper’ the fluid temperature and prepare it for pressur­ization. Devoting this time to clean up can be useful. This procedure helps prevent the periodic “flat” loop condition.
6) Close the flush cart return valve; and immediately thereafter, close the flush cart supply valve, leaving a positive pressure in the loop of approximately 50psi. This is a good time to pressure check the system as well. Check the freeze protection of the fluid with the proper hydrometer to ensure that the correct amount of antifreeze has been added to the system. The hydrometer can be dropped into the flush reservoir and the reading compared to Figure 1A for Methanol and 1B for Propylene Glycol to indicate the level of freeze protection. Do not antifreeze more
8
than a +5°F freeze point. Specific gravity hydrom­eters are available from ClimateMaster. Repeat after reopening and flushing for a minute to ensure good second sample of fluid. Inadequate antifreeze
protection can cause nuisance freezestat lockouts during cold weather.
Note: Always dilute alcohols with water (at least 50%
solution) before using (when possible).
Chart 1A - Methanol Specific Gravity
Chart 1B - Propylene Glycol Specific Gravity
1.07
1.06
1.05
1.04
1.03
1.02
Specific Gravity
1.01
1.00
-40 -30 -20 -10 0 10 20 30 40
Freeze Protection - Degrees F˚
7) Close the flush cart return valve; immediately thereafter, close the flush cart supply valve, shut off the flush cart leaving a positive pressure in the loop of approximately 40-50 psi for summer and 50-75 psi for winter. Refer to Figure 9E for more details.
Heat Pump Freezestat Setting
When an antifreeze is used, the freezestat wires should be switched to activate the low temperature freezestat switch to avoid nuisance faults or lockouts. See the unit installation manual for further details on switching freezestat settings.
Pressure/Temperature Ports
The pressure/temperature ports (P/T ports) supplied with the earth loop connector kit are provided as a means of measuring flow and temperature. The water flow (GPM) through the unit can be checked by measuring the incoming water pressure at the supply water P/T port and subtracting the leaving water pressure at the return water P/T port. Comparing the pressure differential to the pressure drop/flow (Table 5) will determine the flow rate through the unit. For reference, every 1 psi equals
2.31 feet of head, if conversion is needed. ClimateMaster units require 2.25-3 gpm per nominal cooling ton when installed in conjunction with an earth loop. Note: Minimum flow for units is 2.25 gpm
per ton. Example: A VP036 with a 3.8 PSI pressure drop would
be equivalent to 9 GPM on the chart. More flow will not hurt the performance. However, insufficient flow can significantly reduce capacity and possibly even cause damage to the heat pump in extreme conditions. Digital thermometers and pressure gauges needed for the P/T ports are available from ClimateMaster.
Note: Pressure/temperature gauges should be pushed gently into P/T ports to prevent internal damage to the port.
Table 5 - Classic, Ultra Classic, and Paradigm Pressure Drop
Earth Loop Pressure
The earth loop must have a slight positive pressure to operate the pumps (>3 psi). The system pressure will drop as the plastic earth loop pipe relaxes and will fluctuate as the fluid temperature changes. Typical earth loop pressures range from approximately 15-50 psi. At the start-up of a system, you should leave the earth loops with a (static) holding pressure of approximately 40-50 psi summer or 50-75 psi winter. Maximum operating
pressure should never exceed 100 psi under any circumstance. It is recommended to run the unit in the heating and cooling mode for 15-20 minutes each to ‘temper’ the fluid temperature and prepare it for pressurization. This procedure helps prevent the periodic “flat” loop condition.
9
FLOW CONTROLLER INITIAL START-UP
After pressurization, be sure to insure the loop flow controller provides adequate flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures shown in Table 5. Flow
70 65 60 55 50 45 40 35 30 25 20 15 10
Total Head (ft. of hd.)
5 0
AFCS2A AFCS1A
controller pump performance is shown in Chart 2.
Chart 2 - Flow Controller Performance
Start-Up of Flow Controller
1) Check to make sure that the loop and unit isolation valves are completely open and the flush ports are closed and sealed.
2) Check and record the earth loop pressure via the P/T ports. Loop Pressure = In Out
3) Check and record the flow rate. Flow Rate = gpm
4) Check performance of unit. Refer to unit installation manual. Replace all caps to prevent pressure loss.
35302520151050
Flow Rate (gpm)
PUMP CARTRIDGE REPLACEMENT PROCEDURE
First isolate the pump in question as in Figure 10. Always disable power to the pumps and remove pump power
wiring if needed. Close valves as in Step 1 of Figure 10.
Flow
Controller
Return Valve
Supply Valve
Bucket/Drain
Garden Hose Supply
Unit
Figure 10 - Cartridge Replacement Procedure
Loop
1
Close to isolate
pump tor
Cartridge change
2 Open to flush unit with garden hose
and then pressurize
Valve
Positions
Remove two allen head mounting bolts and lift off pump stator housing. Lay out rags to soak up loop fluid.
Remove remaining two allen head mounting bolts and remove cartridge, noting the large ‘o’-ring seal. Loop fluid could spill from system.
Replace with new cartridge, insuring the ‘o’-ring is in place and install the two allen head mounting bolts.
Reinstall the stator housing using the remaining allen head mounting bolts.
Place garden hose supply and return on flush ports as shown in Figure 10 and open valves to flush through the unit portion of loop. When water flows clear, close return side to pressurize; finally, close the supply side valve. Close 3-way valves to operation position Figure 9E. The loop can also be reflushed, using the com­plete procedure outlined for installation.
Remember, this procedure will dilute the antifreeze mixture by a few gallons. If performed more than twice on any earth loop, the antifreeze concentration should be checked with a hydrometer and antifreeze added as needed.
10
GEOTHERMAL CLOSED LOOP DESIGN
Closed Loop Basics
Closed Loop Earth Coupled Heat Pump systems are commonly installed in one of three configurations: horizontal, vertical, and pond loop. Each configuration provides the benefit of using the moderate temperatures of the earth as a heat source/heat sink. Piping configura­tions can be either series or parallel.
Series piping configurations typically use 1-1/4 inch, 1-1/ 2 inch, or 2 inch pipe. Parallel piping configurations typically use 3/4 inch or 1 inch pipe for loops and 1-1/4 inch, 1-1/2 inch, or 2 inch pipe for headers and service lines. Parallel configurations require headers to be either “closed-coupled” short headers or reverse return design.
Select the installation configuration which provides the most cost effective method of installation after consider­ing all application constraints.
Loop design takes into account two basic factors. The first is accurately engineered system to function properly with low pumping requirement and adequate heat transfer to handle the load of the structure. The second is to design a loop with the lowest installed cost while still maintaining a high level of quality. These factors have been taken into account in all of the loop designs presented in this manual.
In general terms, all loop lengths have been sized by the ClimateMaster loop sizing software so that every loop has approximately the same operating costs. In other words, at the end of the year the home owner would have paid approximately the same amount of money for heating, cooling, and hot water, no matter which loop type was installed. This leaves the installed cost of the loop as the main factor for determining the system payback. Therefore, this analysis says "install the most economical system possible given the installation requirements".
Pipe Fusion Methods
Two basic types of pipe joining methods are available for earth coupled applications. Polyethylene pipe can be socket fused or butt fused. In both processes the pipe is actually melted together to form a joint that is even stronger than the original pipe. Although when either procedure is performed properly the joint will be stronger than the pipe wall. ClimateMaster prefers socket fusion in the fusion of 2" pipe or less because of the following:
Allowable tolerance of mating the pipe is much greater in socket fusion. According to general fusion guidelines, a 3/4" SDR11 butt fusion joint alignment can be off no more than 10% of the wall thickness (0.01 in.). A hundredth of an inch accuracy while fusing in a difficult position can be almost impos­sible to attain in the field.
The actual socket fusion joint is 3 to 4 times the cross sectional area of its butt fusion counterpart in
sizes under 2" and therefore tends to be more forgiving of operator skill.
Joints are frequently required in difficult trench connections and the smaller socket fusion iron is more mobile and operators will have less of a tendency to cut corners during the fusion procedure such as can happen during the facing and alignment procedure of butt fusion.
In general, socket fusion loses these advantages in fusion joints larger than 2", and of course socket fittings become very expensive and time consuming in these larger sizes as well. Therefore, butt fusion is generally used in sizes larger than 2". In either joining method, proper technique is essential for long lasting joints. All ClimateMaster supplied pipe and fittings are IGSHPA approved. All fusion joints should be performed by certified fusion technicians. Table 6 illustrates the proper fusion times for ClimateMaster Geothermal PE Pipe.
Table 6 - Fusion Times for ClimateMaster Polyethyl­ene Pipe
Pipe Size Socket Fusion Butt Fusion
Time (sec.)- Time (sec.) Bead (in.)
3/4" IPS 8-10 8 1/16
1" IPS 10-14 12 1/16 1-1/4" IPS 12-15 15 1/16-1/8 1-1/2" IPS 15-18 15 1/16-1/8
2" IPS 18-22 18 1/8
Holding time of 60 sec.Cure time of 20 min. Always use a timing device
Parallel vs Series Configurations
Initially, loops were all designed using series style flow due to the lack of fusion fittings needed in parallel systems. This resulted in large diameter pipe (>1 1/4") being used to reduce pumping requirements, due to the increased pressure drop of the pipe. Since the fusion fittings have become available, parallel flow using (3/4" IPS) for loops 2 ton and above, has become the standard for a number of reasons.
Cost of Pipe - The larger diameter (>1 1/4") pipe is
twice the cost of the smaller (3/4" IPS) pipe. However, due to the reduced surface area of the smaller pipe, the heat transfer capability is only decreased by approximately 10-20%. In loop designs using the smaller pipe the pipe length is simply lengthened to compensate for the small heat transfer reduction; however, it still results in around 50% savings in pipe costs over the larger pipe in series. In some areas 1 1/4" vertical bores can be more cost effective, where drilling costs are high.
Pumping power - Parallel systems generally can
have much lower pressure drop and thus smaller pumps, due to the multiple flow paths of smaller pipes in parallel.
11
Installation ease - The smaller pipe is easier to
handle during installation than the larger diameters. The "memory" of the pipe can be especially cumber­some when installing in cold conditions. Smaller pipe takes less time to fuse and is easier to cut.
When Should Series Loops Be Used?
In smaller loops of two tons or less, the reasons for parallel (listed above) may be less obvious. In these cases, series loops can have some additional advantages:
No header - Fittings tend to be more expensive and
require extra labor and skill to install.
Simple design - No confusing piping arrangement
for easier installation by less experienced installers.
Loop Configuration - Determining the style of loop primarily depends on lot size and "dirt" costs. For instance, horizontal 1 pipe will have significantly (400%) more trench than a horizontal 6 pipe. However the 6 pipe will have about 75% more feet of pipe, therefore if trenching costs are higher than the extra pipe costs, the 6 pipe is the best choice. Remember that labor is also a factor in loop costs. The 6 pipe could also be chosen because a small lot as well. Generally a contractor will know after a few installations which configuration is the most cost effective for him. Then this information can be applied to later installations for a more overall cost effective installation for his particular area. Depth of the loop in horizontal systems generally does not exceed 5
feet because of trench safety issues and the sheer amount of dirt required to move. In vertical systems, economic depth due to escalating drilling costs in rock can some­times require what is referred to as a parallel-series loop. That is, a circuit will loop down and up through two consecutive bores (series) to total the required circuit length required.
Loop Circuiting - Loops should be designed with a compromise between pressure drop and good turbulence in the heat exchange pipe for heat transfer. Therefore the following rules should be observed when designing a loop:
3 gpm per ton flow rate (2.25 gpm per ton mini­mum). In larger systems 2.5 to 2.7 gpm per ton is adequate in most cases. Overseeing the pumps to attain exactly 3 gpm per ton is generally not cost effective from an operating cost standpoint.
One circuit per nominal equipment ton with 3/4" IPS and 1/2 circuit per ton with 1 1/4" IPS pipe. This rule can be deviated by one circuit or so for different loop configurations.
Header Design - Headers for parallel loops should be designed with two factors in mind, the first is pressure drop and the second is flushability. The header shown in Figure 11A is a standard header design through 15 tons for polyethylene pipe with 2” supply and return runouts. The header shown in Figure 11B is a standard header
2" IPS PE
Pipe
2" x 2" x 3/4" IPS
Supply/Return Line
3/4" IPS PE
Pipe
PE Tee
Circuit 9 - 15 Circuit 5 - 8
2" x 1 1/4" x 3/4"
IPS PE Tee
Figure 11A - Typical Header through 15 tons
1 1/4" IPS PE Pipe
1 1/4” x 1 1/4" x
3/4" IPS PE Tee
Supply/Return Line
3/4" IPS PE
Pipe
Circ uit 5
1 1/4" IPS PE
3/4" IPS PE
Pipe
11/4" x 3/4" x 3/4"
IPS PE Tee
Circ uit 4
Pipe
3/4" IPS PE
11/4" x 3/4" x 3/4"
IPS PE Tee
Circ uit 4
Pipe
Circ uit 3
3/4" IPS PE
Pipe
3/4" x 3/4" x 3/4"
IPS PE Tee
3/4" IPS PE
Pipe
3/4" x 3/4" x 3/4"
Circ uit 3
Circ uit
IPS PE Tee
3/4" IPS PE
Pipe
3/4" IPS PE
Pipe
Circ uit
2
Circ uit 1
3/4" IPS PE
Pipe
Circ uit 1
12
Figure 11B - Typical Header through 5 tons
design through 5 tons for polyethylene pipe using 1-1/4” supply and return runouts. Notice the reduction of pipe from 2" IPS supply/return through circuits 12 to 8, and then the line is reduced to 1 1/4" IPS pipe for circuits 7 to 4, and then finally the header line is reduced to 3/4" IPS to supply circuits 3, 2, and 1. This allows minimum pressure drop while still maintaining 2 fps velocity throughout the header under normal flow conditions (3 gpm/ton), thus the header as shown is self-flushing under normal flow conditions. This leaves the circuits them­selves (3/4" IPS) as the only section of the loop not attaining 2 fps flush velocity under normal flow condi­tions (3 gpm/ton & normally 3 gpm/circuit). 3/4" IPS requires 3.8 gpm to attain 2 fps velocity; therefore to calculate flushing requirements for any PE loop using the header styles shown, simply multiply the number of circuits by the flushing flow rate of each circuit (3.8 gpm for 2 fps velocity). For instance on a 5 circuit loop the flush flow rate is 5 circuits x 3.8 gpm/circuit = 19 gpm.
Headers that utilize large diameter pipe feeding the last circuits should not be used. In PE1 1/4" IPS pipe requires
9.5 gpm to attain 2 fps and since increasing the flow through the last circuit would also require increasing the flow through the other circuits at an equal rate as well, we can estimate the flush flow requirements by multiply­ing the number of circuits by 9.5 gpm (in 1 1/4" IPS) or for instance a 5 circuit loop in PE would require 5 circuits x 9.5 gpm/circuits = 47.5 gpm to attain flush flow rate. This is clearly an impossible flow to achieve with a pump of any size.
Header Layout - Generally header layouts are more cost effective with short headers. This requires centrally locating the header to all circuits and then bringing the
circuits to the header. One of the easiest implementations is to angle all trenches into a common pit similar to a starburst. This layout can utilize the laydown or "L" header and achieves reverse return flow by simply laying the headers down in a mirror image and thus no extra piping or labor. Figure 12 details a "laydown header".
Inside Piping - Polyethylene pipe provides an excellent no-leak piping material inside the building. Inside, piping fittings and elbows should be limited to prevent exces­sive pressure drop. Hose kits employing 1" rubber hose should be limited in length to 10-15 feet per run to reduce pressure drop problems. In general, 2 feet of head pressure drop is allowed for all earth loop fittings which would include 10-12 elbows for inside piping to the flow controller. This allows a generous amount of maneuver­ing to the flow controller with the inside piping. 3/8 to 1/ 2" closed cell insulation should be used on all inside piping where loop temperatures below 50°F are antici­pated. All barbed connections should be double clamped.
Flow Controller Selection - The pressure drop of the entire ground loop should be estimated for the selection of the flow controller. In general, if basic loop design rules are followed, units of 3 tons or less will require only one circulating pump (AFCS1A). Units from 3.5 to 6 tons will require a two pump system (AFCS2A). As a caution, loop pressure drop calculation should be performed for accurate flow estimation in any system including unit, hose kit, inside piping, supply/return headers, circuit piping, and fittings. Use Table 7A, B, and C for pressure drop calculations, using methanol and various piping materials. Tables showing other anti­freezes are available from ClimateMaster Technical Support.
Supply Line
Circuit 4 Circuit 3 Circuit 2
Figure 12 - Typical "Laydown" Header
2 foot wide trench
Return Line
Circuit 4 Circuit 3 Circuit 2
13
Table 7A - Polyethylene Pressure Drop Table (using 20% methanol @ 30˚F per 100 ft. of pipe)
FLOW 3/4" IPS SDR 11 1" IPS SDR 11 1 1/4" IPS SCH 40 1 1/2" IPS SCH 40 2" IPS SCH 40 RATE PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re
1 0.36 0.55 1162 0.12 0.35 930 0.04 0.21 724 0.02 0.16 621 0.01 0.10 484 2 1.21 1.11 2325 0.42 0.71 1860 0.13 0.43 1449 0.06 0.32 1242 0.02 0.19 967 3 2.47 1.66 3487 0.85 1.06 2789 0.26 0.64 2173 0.13 0.47 1863 0.04 0.29 1451 4 4.08 2.21 4650 1.41 1.41 3719 0.43 0.86 2898 0.21 0.63 2484 0.06 0.38 1935 5 6.04 2.76 5812 2.09 1.77 4649 0.64 1.07 3622 0.31 0.79 3105 0.09 0.48 2418 6 8.30 3.32 6975 2.87 2.12 5579 0.88 1.29 4347 0.42 0.95 3726 0.13 0.57 2902 7 10.87 3.87 8137 3.76 2.48 6509 1.15 1.50 5071 0.55 1.10 4347 0.17 0.67 3386 8 13.74 4.42 9300 4.76 2.83 7439 1.45 1.72 5796 0.70 1.26 4968 0.21 0.77 3869
9 16.88 4.98 10462 5.84 3.18 8368 1.79 1.93 6520 0.86 1.42 5589 0.26 0.86 4353 10 20.30 5.53 11625 7.03 3.54 9298 2.15 2.15 7245 1.03 1.58 6209 0.32 0.96 4837 11 23.99 6.08 12787 8.30 3.89 10228 2.54 2.36 7969 1.22 1.73 6830 0.37 1.05 5320 12 27.93 6.63 13950 9.67 4.24 11158 2.95 2.58 8693 1.42 1.89 7451 0.43 1.15 5804 13 32.13 7.19 15112 11.12 4.60 12088 3.40 2.79 9418 1.63 2.05 8072 0.50 1.24 6288 14 12.66 4.95 13018 3.87 3.01 10142 1.86 2.21 8693 0.57 1.34 6771 15 14.29 5.30 13947 4.37 3.22 10867 2.10 2.37 9314 0.64 1.44 7255 16 16.00 5.66 14877 4.89 3.43 11591 2.35 2.52 9935 0.72 1.53 7739 17 17.79 6.01 15807 5.44 3.65 12316 2.61 2.68 10556 0.80 1.63 8222 18 19.66 6.37 16737 6.01 3.86 13040 2.89 2.84 11177 0.88 1.72 8706 19 21.61 6.72 17667 6.60 4.08 13765 3.17 3.00 11798 0.97 1.82 9190 20 23.64 7.07 18597 7.22 4.29 14489 3.47 3.15 12419 1.06 1.91 9673 21 25.75 7.43 19526 7.87 4.51 15214 3.78 3.31 13040 1.15 2.01 10157 22 27.93 7.78 20456 8.53 4.72 15938 4.10 3.47 13661 1.25 2.11 10641 23 30.19 8.13 21386 9.23 4.94 16663 4.44 3.63 14282 1.35 2.20 11124 24 9.94 5.15 17387 4.78 3.79 14903 1.46 2.30 11608 25 10.67 5.37 18111 5.13 3.94 15524 1.57 2.39 12092 26 11.43 5.58 18836 5.50 4.10 16145 1.68 2.49 12576 28 13.02 6.01 20285 6.26 4.42 17387 1.91 2.68 13543 30 14.69 6.44 21734 7.06 4.73 18628 2.16 2.87 14510 32 16.44 6.87 23183 7.91 5.05 19870 2.41 3.06 15478 34 18.28 7.30 24632 8.79 5.36 21112 2.68 3.25 16445 36 20.21 7.73 26080 9.71 5.68 22354 2.97 3.44 17412 38 22.21 8.16 27529 10.68 5.99 23596 3.26 3.64 18380 40 24.30 8.59 28978 11.68 6.31 24838 3.57 3.83 19347 42 26.46 9.02 30427 12.72 6.62 26080 3.88 4.02 20314 44 28.71 9.45 31876 13.80 6.94 27322 4.21 4.21 21282 46 31.03 9.88 33325 14.92 7.26 28564 4.55 4.40 22249 48 16.07 7.57 29806 4.91 4.59 23216 50 17.26 7.89 31047 5.27 4.78 24184
14
Table 7B - Canadian Polyethylene (CSA) Pressure Drop Table (using 20% methanol @ 30˚F per 100 ft. of pipe)
FLOW 3/4" IPS CSA 160 1" IPS CSA 160 1 1/4" IPS CSA 100 1 1/2" IPS CSA 100 2" IPS CSA 100
RATE PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re
1 0.49 0.63 1242 0.17 0.41 996 0.04 0.21 713 0.02 0.16 623 0.01 0.10 498 2 1.66 1.26 2484 0.58 0.81 1992 0.12 0.42 1425 0.06 0.32 1245 0.02 0.20 995 3 3.38 1.89 3726 1.18 1.22 2987 0.24 0.62 2138 0.13 0.48 1868 0.04 0.30 1493 4 5.59 2.52 4968 1.96 1.62 3983 0.40 0.83 2850 0.21 0.63 2490 0.07 0.41 1991 5 8.26 3.15 6210 2.89 2.03 4979 0.59 1.04 3563 0.31 0.79 3113 0.11 0.51 2488 6 11.37 3.79 7452 3.98 2.43 5975 0.81 1.25 4275 0.43 0.95 3735 0.15 0.61 2986 7 14.89 4.42 8694 5.21 2.84 6970 1.06 1.45 4988 0.56 1.11 4358 0.19 0.71 3483 8 18.80 5.05 9935 6.58 3.24 7966 1.34 1.66 5701 0.71 1.27 4980 0.24 0.81 3981
9 23.11 5.68 11177 8.09 3.65 8962 1.65 1.87 6413 0.87 1.43 5603 0.30 0.91 4479 10 27.79 6.31 12419 9.73 4.06 9958 1.99 2.08 7126 1.04 1.59 6225 0.36 1.01 4976 11 32.83 6.94 13661 11.50 4.46 10953 2.35 2.28 7838 1.23 1.74 6848 0.43 1.11 5474 12 38.23 7.57 14903 13.39 4.87 11949 2.73 2.49 8551 1.44 1.90 7470 0.50 1.22 5972 13 43.98 8.20 16145 15.40 5.27 12945 3.14 2.70 9264 1.65 2.06 8093 0.57 1.32 6469 14 17.53 5.68 13941 3.58 2.91 9976 1.88 2.22 8715 0.65 1.42 6967 15 19.78 6.08 14936 4.04 3.12 10689 2.12 2.38 9338 0.73 1.52 7465 16 22.15 6.49 15932 4.52 3.32 11401 2.38 2.54 9960 0.82 1.62 7962 17 24.63 6.90 16928 5.03 3.53 12114 2.64 2.69 10583 0.91 1.72 8460 18 27.22 7.30 17924 5.55 3.74 12826 2.92 2.85 11205 1.01 1.82 8957 19 29.92 7.71 18920 6.10 3.95 13539 3.21 3.01 11828 1.11 1.92 9455 20 32.73 8.11 19915 6.68 4.15 14252 3.51 3.17 12450 1.21 2.03 9953 21 35.65 8.52 20911 7.27 4.36 14964 3.83 3.33 13073 1.32 2.13 10450 22 38.67 8.92 21907 7.89 4.57 15677 4.15 3.49 13695 1.43 2.23 10948 23 41.80 9.33 22903 8.53 4.78 16389 4.49 3.65 14318 1.55 2.33 11446 24 45.03 9.73 23898 9.19 4.98 17102 4.84 3.80 14940 1.67 2.43 11943 25 9.87 5.19 17814 5.19 3.96 15563 1.79 2.53 12441 26 10.57 5.40 18527 5.56 4.12 16185 1.92 2.63 12939 28 12.03 5.82 19952 6.33 4.44 17430 2.19 2.84 13934 30 13.58 6.23 21377 7.15 4.76 18675 2.47 3.04 14929 32 15.20 6.65 22803 8.00 5.07 19920 2.76 3.24 15924 34 16.90 7.06 24228 8.90 5.39 21165 3.07 3.44 16920 36 18.68 7.48 25653 9.83 5.71 22410 3.39 3.65 17915 38 20.53 7.89 27078 10.81 6.02 23655 3.73 3.85 18910 40 22.46 8.31 28503 11.82 6.34 24900 4.08 4.05 19905 42 24.46 8.72 29928 12.88 6.66 26146 4.45 4.25 20901 44 26.54 9.14 31354 13.97 6.97 27391 4.82 4.46 21896 46 28.69 9.55 32779 15.10 7.29 28636 5.21 4.66 22891 48 16.27 7.61 29881 5.62 4.86 23887 50 17.47 7.93 31126 6.03 5.06 24882
Table 7C - Rubber Hose Pressure Drop Table (using 20% methanol @ 30˚F per 100 ft. of pipe)
FLOW 1" IPS RUBBER HOSE 1 1/2" IPS RUBBER HOSE 2" IPS RUBBER HOSE
RATE PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re PD (ft) Vel ft/s Re
1 0.18 0.41 1000 0.03 0.21 667 0.01 0.10 484 2 0.59 0.82 2000 0.09 0.43 1333 0.02 0.19 967 3 1.21 1.23 2999 0.18 0.64 2000 0.04 0.29 1451 4 2.00 1.64 3999 0.29 0.86 2666 0.06 0.38 1935 5 2.95 2.04 4999 0.43 1.07 3333 0.09 0.48 2418 6 4.06 2.45 5999 0.59 1.29 3999 0.13 0.57 2902 7 5.31 2.86 6998 0.77 1.50 4666 0.17 0.67 3386 8 6.71 3.27 7998 0.98 1.72 5332 0.21 0.77 3869
9 8.25 3.68 8998 1.20 1.93 5999 0.26 0.86 4353 10 9.92 4.09 9998 1.45 2.15 6665 0.32 0.96 4837 11 11.72 4.50 10997 1.71 2.36 7332 0.37 1.05 5320 12 13.64 4.91 11997 1.99 2.58 7998 0.43 1.15 5804 13 15.70 5.31 12997 2.29 2.79 8665 0.50 1.24 6288 14 17.87 5.72 13997 2.60 3.01 9331 0.57 1.34 6771 15 20.16 6.13 14996 2.94 3.22 9998 0.64 1.44 7255 16 22.57 6.54 15996 3.29 3.43 10664 0.72 1.53 7739 17 25.10 6.95 16996 3.66 3.65 11331 0.80 1.63 8222 18 27.74 7.36 17996 4.04 3.86 11997 0.88 1.72 8706 19 30.49 7.77 18995 4.44 4.08 12664 0.97 1.82 9190 20 33.36 8.18 19995 4.86 4.29 13330 1.06 1.91 9673 21 5.29 4.51 13997 1.15 2.01 10157 22 5.74 4.72 14663 1.25 2.11 10641 23 6.21 4.94 15330 1.35 2.20 11124 24 6.69 5.15 15996 1.46 2.30 11608 25 7.18 5.37 16663 1.57 2.39 12092 26 7.69 5.58 17329 1.68 2.49 12576 28 8.76 6.01 18662 1.91 2.68 13543 30 9.88 6.44 19995 2.16 2.87 14510 32 11.07 6.87 21328 2.41 3.06 15478 34 12.30 7.30 22661 2.68 3.25 16445 36 13.60 7.73 23994 2.97 3.44 17412 38 14.95 8.16 25327 3.26 3.64 18380 40 16.35 8.59 26660 3.57 3.83 19347 42 17.81 9.02 27993 3.88 4.02 20314 44 19.32 9.45 29326 4.21 4.21 21282 46 20.88 9.88 30659 4.55 4.40 22249 48 22.50 10.30 31992 4.91 4.59 23216 50 24.16 10.73 33325 5.27 4.78 24184
15
CLOSED LOOP INSTALLATION
Prior to installation, locate and mark all existing under­ground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential future damage to the installation.
Loop Piping Installation
The typical closed loop ground source system is shown in Figure 13. All earth loop piping materials should be limited to only polyethylene fusion in inground sections of the loop and galvanized or steel fittings should not be used at any time due to their tendency to corrode by galvanic action. All plastic-to-metal threaded fittings should be avoided as well, due to their potential to leak in earth coupled applications, and a flanged fitting substi­tuted. P/T plugs should be used so that flow can be measured using the pressure drop of the unit heat
exchanger in lieu of other flow measurement means. Earth loop temperatures can range between 25-110°F and
2.25 to 3 gpm of flow per ton of cooling capacity is recommended in any earth loop applications.
Horizontal Applications
To install Horizontal earth couplings, dig trenches using either a chain-type trenching machine or a backhoe. Dig trenches approximately 8-10 feet apart. Trenches must be at least 5 feet from existing utility lines, foundations, and property lines, and at least 10 feet from privies and wells. Trenches may be curved to avoid obstructions and may be turned around corners.
When multiple pipes are laid in a trench, space pipes properly and backfill carefully to avoid disturbing the spacing of the pipes in the trench. Figure 14 details common loop cross-sections used in horizontal loops.
Flow
Controller
AFSC1 or 2
Unit Power Disconnect
Concrete block or brick
Air Pad or Extruded polystyrene insulation board
AH5KE
Insulated
Hose Kit
Thermostat Wiring
P/T Plugs
16
Figure 13 - Typical Closed Loop Application
AA
AA
A
A
A
A
A
A
A
A
A
A
AAA
A
A
A
Vertical Bores
One Pair Series/Parallel One Pair
A
A
A
A
A
A
A
A
A
Avg Depth
Two Pair
A
A
A
A
A
A
A
A
A
Avg Depth
Avg Depth
A
A
A
A
A
A
A
A
A
A
When Loops are
shallower than
one ton per loop
A
2 ft
A
2 ft
Two-Pipe Four-Pipe Six-Pipe
Back-Hoe Loops
A A
2 ft
A
Two-Pipe Four-Pipe
Trenched Loops
Figure 14 - Typical Horizontal Loop Configurations
Vertical Applications
To install Vertical earth couplings, drill boreholes using any size drilling equipment. Regulations which govern water well installations also apply to vertical ground loop installations. Vertical applications typically require multiple boreholes. Space boreholes a minimum of 10 feet apart. In southern or cooling dominated climates 15 feet is required.
The minimum diameter for 3/4 inch or 1 inch U-bend well bores is 4 inches. Larger diameter boreholes may be drilled if convenient, unless local code requires an expensive method of backfilling. Assemble each U-bend assembly, fill with water and pressure test prior to insertion into the borehole.
To add weight and prevent the pipe from curving and digging into the borehole wall during insertion, tape a length of conduit, pipe, or reinforcing bar to the U-bend end of the assembly. This technique is particularly useful when inserting the assembly into a borehole filled with water or drilling mud solutions, since a water filled pipe is buoyant under these circumstances. Tape the pipes together approximately every 10 feet to prevent the assembly from separating under downward pressure and bowing out against the borehole wall.
Carefully backfill the boreholes to within 10 feet of the surface. Follow IGSPHA specifications for backfilling unless local codes mandate otherwise.
When all U-bends are installed, dig the header trench 4 to 6 feet deep and as close to the boreholes as possible. Use a spade to break through from ground level to the bottom of the trench. At the top of the hole, dig a relief to allow the pipe to bend for proper access to the header. The “laydown” header mentioned earlier is a cost effective method for connecting the bores. Figure 15 illustrates common vertical bore heat exchangers.
AA AA AA
2 ft
1 ft
AA AA
2 ft
AA
2 ft
Extended Slinky
A A A A A A A A A
Figure 15 - Typical Vertical Loop Configurations
A A A A A A A A A
A A A A A
A A A A A
Pond/Lake Applications
Pond loops are one of the most cost effective applications of geothermal systems. Typically, 1 coil of 300 ft of PE pipe per ton is sunk in a pond and headered back to the structure. Minimum pond sizing is 1/2 acre and 8 feet deep for an average residential home. Actual area can be 1500-3000 ft 2 per ton of cooling. In the north, an ice cover is required during the heating season to allow the pond to reach an average 39°F. Winter aeration or excessive wave action can lower the pond temperature preventing proper operation of the geothermal system. Direct use of pond or lake water is discouraged because of the potential problems of heat exchanger fouling and pump suction lift. Heat exchanger may be constructed of either multiple 300’ coils of pipe or slinky style (Figure
16). In northern applications, the slinky or matt style is recommended due to its superior performance in heating. Due to pipe and antifreeze buoyancy, pond heat ex­changer will most likely need weighted down to prevent floating. 300 foot coils require two 4” x 8” x 16” blocks (19 lbs. each) or 8-10 bricks (4.5 lbs each) and every 20 ft of 1-1/4” pipe requires one three-hole brick. Coils are supported off of the bottom by the concrete blocks or bricks. The supply/return trenching should begin at the structure and work toward the pond. Near the pond the trench should be halted and backfilled most of the way. A new trench should be started from the pond back toward the partially backfilled first trench to prevent pond from flooding back to the structure.
17
A
Concrete
Blocks for
weight
Nylon Cable
Ties to secure
blocks
4 ft between
300 ft coil per ton separated by scrap pipe
coils
Reverse
Return
Header
3 foot
separation
Heavy Duty
Plastic Safety
matting
Nylon Cable
Ties to secure
Netting and
bricks
8-10 Bricks for
weight
300 ft slinky
coil per ton
Traditional Coiled
Pond Loop - Southern
Climates
Figure 16 - Typical Pond Heat Exchanger Configurations
BUILDING ENTRY
Seal and protect the entry point of all earth coupling entry points into the building using hydraulic cement.
Slab on Grade Construction
New Construction: When possible, position the pipe in the proper location prior to pouring the slab. To prevent wear as the pipe expands and contracts, protect the pipe with a layer of insulation as shown in Figure 17. When the slab is poured prior to installation, create a chase through the slab for the service lines with 4 inch PVC street elbows and sleeves.
Insulation
Finished Grade
High Efficiency Slinky/Matt
Pond Loop - Northern
Climates
Retrofit Construction
Trench as close as possible to the footing. Bring the loop pipe up along the outside wall of the footing until it is higher than the slab. Enter the building as close to the slab as the construction allows. Shield and insulate the pipe to protect it from damage and the elements as shown in Figure 18.
Enter Building As
Soon As Possible
Insulation Inside
Protective Shield
Finished Grade
18
4-6'
Loop Pipe
Figure 17 - Slab on Grade Entry Detail
4-6'
Loop Pipe
Figure 18 - Retrofit Construction Detail
Pier and Beam (crawl space)
New and Retrofit Construction: Bury the pipe beneath the footing and between piers to the point that it is directly below the point of entry into the building. Bring the pipe up into the building. Shield and insulate piping as shown in Figure 19 to protect it from damage.
Horizontal Systems: Test individual loops as installed. Test entire system when all loops are assembled.
Vertical U-Bends and Pond Loop Systems: Test Vertical U-bends and pond loop assemblies prior to installation with a test pressure of at least 100 psi. Either water or air may be used as the testing medium.
Finished Grade
Insulation Inside
4-6'
Protective Shield
Loop Pipe
Figure 19 - Pier and Beam Entry Detail
Below Grade Entry
New and Retrofit Construction: Bring the pipe through the wall as shown in Figure 20. For applications in which loop temperature may fall below freezing, insulate pipes at least 4 feet into the trench to prevent ice forming near the wall.
Upon completion of the ground loop piping, pressure test the loop to assure a leak-free system.
1-1/2” SDR21
1-1/2” PVC
repair coupling
2” hole &
Silcone Caulk
Hydraulic Cement
each side
Footer
Concrete Wall
Final Grade
Dirt Fill
Gravel backfill
PVC Sleeve
Undisturbed Earth
Figure 20 - Below Grade Entry Detail
1-1/4” x 1-1/2” Fernco
gasket coupling
1-1/4” SCH40
PE Pipe
19
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
*69197310*
69197310
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
Rev.: 12/98 © ClimateMaster 1997
FAX: 405-745-2051
www.climatemaster.com
Loading...