ClimateMaster Console CCE Series Installation & Operation Manual

Model Decoder 2 General Information 3 Inspection 3 Introduction 3 Storage 3 Unit Protection 3 Pre-Installation 3 Chassis Dimensions 5 Installation 6 Supply and Return Hoses 6 Installation of Supply and Return Piping 7 Condensate Piping 7 Electrical Wiring 8 Optional Wall Mounted Thermostat 8 Start-Up Preparation 10 System Checkout 10 Unit Start-Up 11 Maintenance 13 Physical Dimensions 14 Physical Data 18 Electrical Data 18 Wiring Diagrams Matrix 19 Wiring Diagrams 20 Functional Troubleshooting 25 Troubleshooting Form 27 Warranty 28 Start-Up Log 29 Revision History 30
Console 50Hz - HfC-407C
Water-sourCe Heat PumPs
InstallatIon, oPeratIon &
m
97B0035N02
Revised: 08/13/10
Console
CCE Series
Table of Contents
C l i m a t e M a s t e r Water- So ur ce Heating and Cooling Systems
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
C o ns ol es
R e v. : 0 8 /13/ 1 0
2
This Page Intentionally Left Blank
3
c l i m a t e m a s t e r. co m
C o ns ol es
R e v. : 0 8 /13/ 1 0
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
C C E AB0 7 CT S S C S R S
94 5 6
7
8 10 11 12 13 14 15
CCE = Console
Power Termination
Revision Level
Voltage
Controls
M = Bottom Return
Cabinet Insulation
Subbase
A = Copper Water Coil w/ Coated Air Coil
Heat Exchanger Options
C = Copper Water Coil J = Cupro-nickel Water Coil w/ Coated Air Coil N = Cupro-nickel Water Coil
R = Right Piping
Piping Connections
L = Left Piping
Standard
D = Bottom Return w/Locking Control Door B = Front Return
D = 3” Subbase w/Motorized Damper G = 5” Subbase
S = 3” Subbase
H = 5” Subbase w/Motorized Damper N = None
V = Copper Water Coil w/E-Coated Air Coil & Extended Range Insulation E = Copper Water Coil w/Extended Range Insulation M = Cupro-nickel Water Coil w/ Coated Air Coil & Extended Range Insulation F = Cupro-nickel Water Coil w/Extended Range Insulation
1 2 3
S = Standard
None S F M Motorized Water Valve A G N Autoflow (2.25 Gpm/Ton) B H P Autoflow (3.0 Gpm/Ton) C J Q Motorized Water Valve & Afr (2.25) D K R Motorized Water Valve & Afr (3.0) E L T
Water Circuit Options
E = Front Return w/Locking Control Door C = No Cabinet Chassis Only
07 09 12 15 19
Model Type
Unit Size
A = Field Connected (Hard Wire) F = Disconnect
Sweat IPT EPT
T = 220-240/50/1 - R407C
MCO Unit Mounted T-Stat
ACO Unit Mounted T-Stat
CE Compliant
CXM DXM
E J
F K
Remote Mounted T-Stat
Q G
Remote Mounted T-Stat w/LON
Remote Mounted T-Stat w/MPC
H V
T U
With UltraQuiet
S = Bottom Return L = Bottom Return w/Locking Control Door F = Front Return G = Front Return w/Locking Control Door N = No Cabinet Chassis Only
Without UltraQuiet
Model Decoder
C l i m a t e M a s t e r Water- So ur ce Heating and Cooling Systems
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
C o ns ol es
R e v. : 0 8 /13/ 1 0
4
Pre-Installation
Installation, operation and maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a CCE unit for installation.
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Keep both the chassis and cabinet covered with the shipping carton until all plastering, painting, and finish work is complete and it is time to install the chassis and cabinet.
3.
Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
4. Inspect all electrical connections. Connections must be clean and tight at the terminals.
To avoid equipment damage, do not use these units as a source of heating or cooling during the construction process. The mechanical components and lters used in these units quickly becomes clogged with construction dirt and debris which may cause system damage. To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians which meet local, state and federal prociency requirements. All refrigerant discharged from this unit must be recovered without exception. Technicians must follow industry accepted guidelines and all local, state and federal statutes for the recovery and disposal of refrigerants. When a compressor is removed from this unit, system refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.
General Information
Inspection
Upon receipt of shipment, carefully check the shipment against the bill of lading. Verify all CCE units have been received. Inspect each unit for damage. Be certain the carrier makes proper notation on the delivery receipt of all shortages and noticeable damage and he com­pletes a Carrier Inspection Report. Concealed damage not discovered during unloading must be reported to the carrier within fifteen (15) days of receipt of ship­ment. NOTE: It is the responsibility of the purchaser to file all necessary claims with the carrier. Notify the ClimateMaster Traffic Department within fifteen (15) days of receipt of all damaged shipments.
Introduction
ClimateMaster Console Air Conditioner Water Source Heat Pump units are decentralized room terminals designed for field connection to a closed-circuit piping loop. They are offered in capacities ranging from 2-5.6 kW cooling. Units must be installed indoors and are typically installed in perimeter zones, usually under windows. Supply air is discharged directly into the conditioned space through discharge grille located in the top of the unit.
Storage
CAUTION: DO NOT store or install CCE units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, ga­rages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.
Upon the arrival of the equipment at the job site, immediately store units in their shipping cartons in a clean, dry area. Store units in an upright position at all times. Stack units a maximum of 3 units high. Use pallets to separate each layer of units. Do not remove equipment from shipping cartons until equipment is required for installation.
Unit Protection
Cover CCE units on the job site with either shipping cartons, vinyl film, or an equivalent protective covering. Cap the open ends of pipes stored on the job site. In areas where painting, plastering, or the spraying of fire­proof material has not been completed, all due precau­tions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start­up and may result in costly equipment clean-up. Examine all pipes, fittings, and valves before installing the system components. Remove any dirt found on these components.
WARNING!
WARNING!
WARNING! The installation of water source heat pumps and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
5
c l i m a t e m a s t e r. co m
C o ns ol es
R e v. : 0 8 /13/ 1 0
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Chassis Dimensions
Figure 1a : Remove 4 shipping bolts on compressor isolation plate. (Not all models)
1/2” FPT or 1/2” MPT
1/2” FPT or 1/2” MPT
Notes: All dimensions are in mm. *For installed dimension, add to dimension shown 74mm with 3” subbase and 124mm for 5” subbase. **Dimension reduced by fitting if selected.
Chassis Dimensions
C l i m a t e M a s t e r Water- So ur ce Heating and Cooling Systems
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
C o ns ol es
R e v. : 0 8 /13/ 1 0
6
Installation
The installation of ConsoleWater Source Heat Pumps and all associated components, parts and accessories that make up the installation shall be in accordance with the regulations of ALL Authorities having jurisdic­tion and MUST conform to all applicable Codes. It is the responsibility of the Installing Contractor to de­termine and comply with ALL applicable Codes and
Regulations.
NOTE: An Installation Checklist is provided in this man­ual. Complete this checklist after all installation proce­dures are completed. A periodic maintenance checklist provided in the Maintenance section outlines recom­mended maintenance schedules. A Start-Up Inspection Log is also included at the end of this manual to encour­age thorough unit checkout at initial start-up. These checklists are not a substitute for the detailed informa­tion found in the Installation section of this manual.
1. CCE units are typically installed along an outside wall of the room. Provide adequate space in front of the unit for service and maintenance. Locate the Console Air Conditioner so that it provides adequate air circulation throughout the room.
2. Unpack the CCE Unit from the shipping carton. Remove the front cabinet by lifting up and away from the backplate. Protect the cabinet from damage during installation by returning it to its original vinyl pack until required.
3. Remove compressor isolation plate shipping screws (4) as shown in Figure 1a.
4. Using a carpenter's square and a level, ensure the unit is level. Shim the unit if necessary to assure proper installation.
CAUTION: Poor or inadequate installation may result in noisy unit operation or unattractive installa-
tion.
5. Select the proper fasteners to connect the backplate securely to the wall.
6. Fasten the backplate onto the wall through the screw holes located in the back flange. Secure the subbase in place.
7. Make all necessary electrical connections as described in the Electrical Wiring section of this manual. Consult the wiring diagram to ensure proper hook-up.
8. Connect the final piping as described in the Supply and Return Piping and Condensate Piping section of the manual. Install shut-off valves, piping and/or hoses and other accessories as specified.
9. Before making the final water connections, flush the system as described in the Start Up section of this manual. After flushing the system, connect piping and hoses to the proper supply, return and condensate connections of the unit.
NOTE: When necessary, use adapters to connect hoses.
10. Install any other system components as required following manufacturer's instructions.
11. After Start-up, reinstall the front cabinet by carefully lowering the front cabinet over the chassis onto the backplate.
Supply and Return Hoses
Optional pressure-rated hose assemblies are available for
use with ClimateMaster CCE Units. Use the following guidelines when installing supply and return hose assemblies.
1. Install supply and return hoses fitted with swivel­joint fittings at one end to prevent the hose from twisting.
2. Use male adapters to secure the hose assembly to the unit and the riser.
3. Do not allow the hose to twist during installation. Twisting may damage the hose wall or the rubber compound. (Not all models)
4. Use pipe joint compound sparingly on the male pipe threads of the fitting adapters.
5. Prevent sealant from reaching the flared surfaces of the joint.
6. Do not use pipe joint compound when teflon thread tape is pre-applied to hose assemblies or when flared-end connections are used.
7. Maximum torque which may be applied to brass fittings is 30 ft-lbs. When a torque wrench is not used, tighten brass fittings finger-tight plus one quarter turn.
8. Tighten steel fittings as necessary.
9. Shut-off/balancing valves, flow indicators, and drain tees in the supply runout and return at each floor aid in loop balancing and servicing.
CAUTION: Loop Fluids should be of good quality with no more than 0.50 ppm of chlorides w/ Cu (125 ppm w/ CuNi) to prevent corrosion and should also be filtered to a maximum 800 micron particle size to prevent
erosion of the heat exchangers.
Supply and Return Piping
System piping MUST comply with all applicable codes.
1. Install a drain valve at the base of each supply and return riser to enable system flushing at start-up and during routine servicing.
2. Install shut-off/balancing valves and unions at each unit to allow unit removal for servicing.
NOTE: If flex hoses are used, unions are not necessary.
3. Install strainers at the inlet of each system circulating pump.
7
c l i m a t e m a s t e r. co m
C o ns ol es
R e v. : 0 8 /13/ 1 0
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Installation
NOTE: If loop temperatures are expected below the am­bient dew point, the optional internal insulation package must be ordered. Insulation must also be installed on loop water piping on those sections which run through unheated areas or are located outside the building.
Condensate Piping
Unit is supplied with condensate drain hose, 15.9mm I.D. flexible plastic nonpressure-rated, protruding from piping side of unit. Connect this hose to building drain. Avoid making kinks in hose to ensure an unobstructed flow of condensate from the unit to the drain. DO NOT twist, pull hose out, or push excess hose into unit. If hose will not connect to your building drain several options include, relocate end of building drain, add to or cut hose, use hard plastic or copper elbow fittings for tight radii (put inside hose). Keep hose positioned within or over subbase area so hose does not interfer with front cabinet. Cabinet should not push or reroute hose. Clamp all joints watertight. Check for leaks.
Internally the drain hose is clamped to drain pan and pitched correctly. Horizontal runs of condensate hose should be pitched downward 6mm (1/4 inch) minimum for every 300MM of hose. Avoid low points and unpitch-
ing because dirt collects in these areas and may cause blockage. If blocked the condensate level in drain pan increases, when level gets too high, CCE unit has sensor switch that will shut unit off, overflow may still occur. Building drain connection if parallel with floor the height can be up to 38mm above subbase for proper pitch and correct drainage, up to 130mm above is allowable but drainage will be slower. When 65 to 130mm above the hose inside unit will act as a trap. Heights more than 130mm above subbase are NOT allowable (condensate overflow may occur). Check if your unit has a disconnect box option, this limits build­ing drain locations. See unit Configuration pages. Field installation of a trap or vent is not required unless specified by local codes. CCE units are designed in a blow-through configuration. The condensate drain pan is located on the outlet side of the blower so that the pressure in the drain pan is higher than atmosphere. When drain connection is completed check for proper drainage and leaks. Correct if necessary. If trap is used, check and clean often. See Maintenance Instructions.
1/2” FPT or 1/2” MPT
1/2” FPT or 1/2” MPT
Notes: All dimensions are in mm. *For installed dimension, add to dimension shown 74mm with 3” subbase and 124mm for 5” subbase.
Figure 1 Water Connection details
C l i m a t e M a s t e r Water- So ur ce Heating and Cooling Systems
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
C o ns ol es
R e v. : 0 8 /13/ 1 0
8
CAUTION: Use only copper conductors for field installed electrical wiring. Unit terminals are not
designed to accept other types of conductors.
All field installed wiring, including the electrical ground, MUST comply with the National Electrical Code as well as applicable local codes. In addition, all field low voltage wiring must conform to the Class II temperature limitations described in the NEC.
Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections shown in Figure 1 when using field supplied disconnect.
Units have dual voltage (220-240V) control transformer. The units are shipped for 240V operation. Modify the transformer connection when the actual power supply is 220 volts. Refer to the unit wiring diagram for details of this procedure.
Make all final electrical connections with a length of flexible conduit to minimize vibration and sound transmission to the building.
Optional Wall-Mounted Thermostat
CCE WSHP units are built with standard internal thermostats in either manual changeover (MCO) or automatic changeover (ACO) configuration. No external, field-installed low-voltage wiring is required.
When desired, the unit can be furnished with a 24-volt control circuit which is field-wired to a ClimateMaster­supplied accessory remote thermostat.
Zone integrity must be maintained to efficiently control units or groups of units. Unless zones of control are considered and accounted for, adjacent units may operate in heating and cooling modes simultaneously.
Low-voltage wiring between the unit and the wall thermostat must comply with all applicable electrical codes (i.e., NEC and local codes), and be completed before the unit is installed.
Table 2 lists recommended wire sizes and lengths to install the thermostat. The total resistance of low-voltage wiring must not exceed 1 ohm. Any resistance in excess of 1 ohm may cause the control to malfunction because of high voltage drop.
Field Supplied
Disconnect Switch
Heat Pump
A
Room Thermostat
B
A= Two power wires on single-phase units: three power wires on three-phase units. B= 1 heat /1 cool / manual or Auto Change-over remote 24V thermostat. Note: All customer-supplied wiring to be copper only and must conform to NEC and local electrical codes. Wiring shown with dashed lines must be field-
supplied and field-installed. "B" only required with systems employing remote mounted thermostats.
DISCONNECT ELECTRICAL POWER
SOURCE TO PREVENT INJURY OR DEATH
FROM ELECTRICAL SHOCK.
CAUTION: USE COPPER CONDUCTORS ONLY TO PREVENT EQUIPMENT DAMAGE.
Figure 1 Typical Field Installed Wiring
WIRE SIZE MAX. WIRE LENGTH*
18-Gauge 23 m 16-Gauge 38 m 14-Gauge 62 m
*Length = Physical distance from thermostat to unit.
Table 2 - Recommended Thermostat Wire Sizes
Electrical Wiring
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
WARNING!
WARNING!
9
c l i m a t e m a s t e r. co m
C o ns ol es
R e v. : 0 8 /13/ 1 0
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
System Cleaning and Flushing
Cleaning and flushing the unit and system is the single most important step to ensure proper start-up and continued efficient operation of the system. Follow the instructions below to properly clean and flush the
system: DO NOT FLUSH SYSTEM THROUGH THE UNIT!
To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect before servicing unit.
1. Verify that electrical power to the unit is disconnected and that the circulation pump is de-energized.
2. Connect the supply hose directly to the return riser valve. Use a single length of flexible hose as illustrated in Figure 2 below.
NOTE: When one hose is too short to make the connection without exceeding the minimum bend radius of the hose, substitute two length of flexible hose joined together with a field-supplied, standard MPT coupling. Use the adapter provided with the hose kit as shown in Figure 3.
3. Fill the system with water, leaving the air vents open. Bleed all air from the system but do not allow the system to over flow. Check the system for leaks and make any required repairs. Adjust the water and air level in the expansion tank.
4. With strainers in place, start the pumps. Systematically check each vent to ensure that all of the air is bled from the system.
5. Verify that make-up water is available and adjusted to properly replace any space remaining when all air is evacuated. Pressure test and inspect the system for leaks and make any additional repairs required.
Start-Up Preparation
6.
Open the drain at the lowest point in the system. Verify that make-up water replacement rate equals rate of bleed. Continue to bleed the system until the water appears clean or for at least three hours whichever is longer.
7. Completely drain the system.
8. Refill the system with clean, chemically treated water. Since water varies for each locality, contact a local water treatment company for the correct cleaning chemicals to use in your area.
CAUTION: To avoid possible damage to piping systems constructed of plastic piping, DO NOT
allow loop temperature to exceed 43 °C.
9. Set the boiler to raise the loop temperature to approximately 29.4°C. Circulate the solution for a minimum of 8 to 24 hours. At the end of this period, shut off the circulating pump and drain the solution. Repeat system cleaning if necessary.
10. When the cleaning process is complete, remove the short-circuit hoses. Connect the hoses to the proper supply and return connections to the unit. Refill the system and bleed off all air.
11. Test the system pH with litmus paper. The system water should be slight alkaline (pH 7.5 to 8.5). Add chemicals as appropriate to maintain acidity levels.
CAUTION: DO NOT use "Stop-Leak" or any similar chemical agent in this system. Addition of these chemicals to the loop water will foul the system and
will inhibit unit operation.
12. When the system is successfully cleaned, flushed, refilled and bled, check the main system panels, safety cutouts and alarms. Set controls to properly maintain loop temperature.
Figure 3
 
  



Figure 2
WARNING!
Loading...
+ 21 hidden pages