ClimateMaster ATC32U02 iGate Installation Manual

ATC32U02 iGate™ Communicating,
Programmable Thermostat
Installation Manual
97B0055N03
Rev.: 2/24/14
These instructions are intended to be used by the installer or service personnel. End users are NOT advised to change or modify any of these settings. Doing so may cause the equipment to stop working properly and/or may void the warranty on both the thermostat and the equipment.
Table of Contents
Section Title Page Safety/Installation Considerations 3
1.0 User Menu Settings 4
2.0 Installer Menu Settings 6
2.1 Installer Menu Settings Access 6
2.2 Thermostat Confi guration 6
3.0 System Confi guration 7
3.1 Airfl ow Selection 7
3.2 Option Selection 7
3.3 Unit Confi guration 8
3.4 Pump Confi guration 8
3.5 Valve Confi guration 9
3.6 Multi-Unit Confi guration 9
4.0 Accessory Confi guration 10
4.1 Air Filter 10
4.2 Humidifi er 10
4.3 UV Lamp 10
Section Title Page
4.4 Air Cleaner 10
5.0 Input Dealer Information 10
6.0 Humidity Confi guration 1 1
7.0 Temperature Algorithm 11
8.0 Demand Reduction Confi guration 12
9.0 Service Mode 12
9.1 Manual Operation 12
9.2 Control Diagnostics 12
9.3 Dipswitch Confi guration 13
9.4 Fault History 13
9.5 Clear Fault History 14
9.6 Multi-Unit Diagnostics 14
9.7 Multi-Unit Fault Information 15
10.0 Restore Defaults 15
11.0 Revision History 16
This page was intentionally left blank.
ATC32U02 Communicating, Programmable Thermostat - IOM
Rev.: 24 Feb., 2014
ClimateMaster’s ATC32U** Communicating, Programmable Thermostat is the perfect compliment to a ClimateMaster Geothermal Heat Pump System and represents a signifi cant advancement in thermostat communicating technology. For homeowners, the ATC32U** provides highly customizable cli­mate control features designed to maximize comfort and re­duce the amount of energy consumed by the ClimateMaster Geothermal Heat Pump System. For dealers, it represents a signifi cant, industry leading advancement in confi guration, monitoring and diagnostics from the thermostat. Please read the following instructions carefully to maximize the comfort and cost-saving potential of your ClimateMaster Geothermal Heat Pump System.
SAFETY CONSIDERATIONS
Improper wiring or installation may damage thermostat. Wir­ing must conform to local and national electrical codes
WARNING!
WARNING! power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
INSTALLATION CONSIDERATIONS
The thermostat requires no batteries. The thermostat is not a power stealing device and MUST have both R and C termi­nals connected. See Diagram 1.
Before installing thermostat, turn off all
a time. Be careful not to allow wires to fall back into the wall.
C. As each wire is disconnected, record wire color
and terminal marking.
D. Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and MUST be dis­posed of properly.
3. Separate the thermostat from base.
4. Route thermostat wires through hole in base. Level base against wall (for aesthetic value only - thermo­stat need not be leveled for proper operation) and mark wall through 2 mounting holes.
5. Drill two 3/16-in. mounting holes in wall where marked. (Note: Mounting holes on thermostat are designed to fi t on a horizontal J-box).
6. Secure base to wall with 2 anchors and screws provided making sure all wires extend through hole in base.
7. Connect wires to proper terminal of the connector block in the thermostat.
8. Push any excess wire back into wall. Excess wire inside the thermostat case can interfere with proper air fl ow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can affect operation.
9. Install thermostat on base.
10. Turn on power to the unit.
III. WIRING DIAGRAMS
All excess wire should be pushed back into the wall as far as possible. Excess wire inside the thermostat plastic case may interfere with the air fl ow across the temperature sensor.
Diagram 1: Thermostat Connections
INSTALLATION I. THERMOSTAT LOCATION
Thermostat should be mounted:
• Approximately 5 ft. (1.5m) above fl oor.
• Close to or in a frequently used room, preferably on an inside partitioning wall.
• On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
• Close to a window, on an outside wall, or next to a door leading to the outside.
• Exposed to direct light and heat from a lamp, sun, replace, or other temperature-radiating object which may cause a false reading.
• Close to or in direct airfl ow from supply registers.
• In areas with poor air circulation, such as behind a door or in an alcove.
II. THERMOSTAT INSTALLATION
1. Turn off all power to unit.
2. If an existing thermostat is being replaced:
A. Remove existing thermostat from wall.
B. Disconnect wires from existing thermostat, one at
ATC32U** Thermostat
24Vac Common
24Vac Hot
Comm +
C
Comm -
R
A+
B-
OD
GND
ID
Thermostat Connections
C 24V Common for Control Circuit R 24V Supply for Control Circuit A+ Communications (Positive) B – Communications (Negative) GND Ground OD Outdoor Temperature Sensor ID Indoor Temperature Sensor
DXM2
Control
Gnd
A+
B-
24V
Outdoor
Sensor
(Optional)
Remote Indoor
Sensor
(Optional)
3
ATC32U02 Communicating, Programmable Thermostat - IOM
Rev.: 24 Feb., 2014
1.0 User Menu Settings
1.1 OFFSETS
If you fi nd that the temperature displayed on the
thermostat does not accurately represent the room temperature where the thermostat is located, this offset function compensates for the difference. The thermostat will apply an offset between what temperature the thermostat is measuring versus the temperature that is displayed.
1.1.1 TEMPERATURE OFFSET
The Temperature Offset function allows for
calibration of the temperature sensor.
Adjust the Temperature Offset settings using the
up/down arrow buttons. Press the center button to save changes.
• Indoor Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
• Remote Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
• Outdoor Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
• 1st Stage (default 1°F): options: 1°F to 4°F
(in 1°F increments)
• 2nd Stage (default 1°F): options: 1°F to 4°F (in 1°F increments)
• Aux Heat (default 1°F): options: 1°F to 4°F (in 1°F increments)
The Auto Changeover Time is the amount of time that elapses before operation switches from heating to cooling mode or from cooling to heating mode.
Adjust the Auto Changeover Time using the up/
down arrow buttons. Press the center button to save changes.
• Auto Change Over Time (default 15 minutes): options: 0 to 120 minutes (in 15 minute increments)
1.3 DEMO MODE
Demo mode is designed to showcase heat pump
operation when the unit is connected to an above ground water loop with the supply air being blown directly over the water loop.
1.3.1 ENTER DEMO MODE
To enter Demo Mode, navigate to the Service
Information screen (Menu>Settings>Service Information) then press and hold the right arrow for 5 seconds
SERVICE INFORMATION
FAULT STATUS
CLEAR FAULT HISTORY SYSTEM STATUS
NOTE 1: The thermostat must be confi gured for
Multistage by installer to access the 2nd Stage Differential setting. The thermostat must be confi gured for Auxiliary Heat by installer to access the Auxiliary Heat Differential setting.
NOTE 2: The temperature control algorithm must
be confi gured for Differential control to access the Differential settings by installer.
1.1.2 HUMIDITY OFFSET
If you fi nd that the Humidity level displayed on
the thermostat does not accurately represent the Humidity level of the room in which the thermostat is located, use the Humidity Offset function to calibrate the humidity sensor.
Adjust the Humidity Offset setting using the up/
down arrow buttons. Press the center button to save changes.
Indoor Humidity (default 0%): options:
-10% to +10% (in 1% increments)
1.2 AUTO CHANGEOVER TIME
When the thermostat is confi gured for AUTO mode,
the thermostat automatically selects heating or cooling mode depending on the indoor temperature.
SELECT OPTION
PREVIOUS
1.3.2 DEMO MODE OPERATION
Control Demo Mode operation parameters from the
Demo Operation screen shown below.
DEMO OPERATION
OUTDOOR FAN AUTO
78% HEATING
RH 36% HUMID ON
72%
AUTO
SETPOINT HEAT 70 COOL 74
RH TEMP MODE FAN MENU
4
Geothermal Heat Pump Systems
ATC32U02 Communicating, Programmable Thermostat - IOM
The starting mode (heating or cooling) depends
on the loop temperature at the time when Demo Mode is entered. The unit will operate in heating or cooling based upon the following algorithm.
Start in Cooling Mode Start in Heating Mode
90°F
70°F
50°F
Solid lines represent heating operation. Dashed lines represent cooling operation.
Rev.: 24 Feb., 2014
1.3.3 EXITING DEMO MODE
To exit demo mode, remove power to the
thermostat.
5
Loading...
+ 11 hidden pages