ClimateMaster AG series Installation, Operation And Maintanance Manual

AG Series Electric Heaters
Auxiliary Electric Heat
Installation, Operation &
Maintenance Instructions
97B0005N04
Revised: 04 August, 2015
Table of Contents
Overview 3
Vertical Upow Installation - External 4
Horizontal Installation - External
Wiring 6
Setup 6
Ratings 7
Electrical Data 7
Staging Options 7-8
Accessory Heater Dimensions 9
Warranty 10
Revision Log 12
This page was intentionally left blank.
Electric Heat - Installation, Operation, and Maintenance
Remove bolts and drop blower
Locate electric heat assembly on pins in discharge panel and insert bolts
Relocate blower in electric heat assembly in same manner
Air Coil
Electric Heat
Assembly
Field-supplied
disconnect
(refer to local codes)
Low voltage control harness
is prewired on all
distributor class units
Revised: 04 August, 2015
Overview
Overview
The AG Series Auxiliary Electric Heat mounts internally on
TS, TE and TT upow (Figure 1b) or downow units and all
TAH units. It mounts directly to the blower outlet of TS, TE
and TT horizontal units (Figure 8) and on all TZ units. Note the model compatibility Table 1. Horizontal units are rated for zero clearance at the unit and 1" clearance for rst three
feet of duct, vertical units rated for zero clearance for both
unit and duct. Downow units can not be located directly
over a discharge register. The discharge plenum must be constructed from non combustible material. The AG electric heat contains a four stage relay control board which activates the elements directly via an internally wired low voltage
harness. Low voltage signals (W1 and W2) are staged from
the CXM or DXM control of the unit.
TS ,TT and TE Vertical Upow or Downow and TAH Installation - Internal
1. Disconnect power to the unit.
2. Remove blower access panel(s) from the unit and
control box cover from the electric heater.
3. Remove blower mounting bolts and drop blower
assembly as shown in gure 2. Removal of electrical
wiring should not be necessary.
4. Position the electric heater as illustrated in gure 3 with its control box facing the front access panel of the unit. Attach heater to unit using the support pins on the back and bolts on the front.
The electric heater air inlet dimensions should match the unit blower outlet, installer should stop and refer to the unit/heater compatibility chart later in this instruction or consult factory if they do not match.
5. Re-install blower assembly on to electric heater using pins and bolts as before. Check blower electrical wiring
for proper connection and remedy any pinched wire(s) or
contact with sharp edges.
6. Route the low voltage control harness through one of the ‘pie’ bushings in the heater control box and plug on to
the P2 connector. See gure 6.
7. Install power conduit through the unit cabinet as shown
in gure 7 and attach directly to the electric heater control box. See gures 9a-c.
8. Replace all covers and panels, heater installation is
complete. Proceed to wiring and setup.
Figure 1b: Typical vertical unit installation
Figure 2: Blower removal
Figure 3: AG electric heat mounting and blower re-installation
Figure 1a: Typical air handler installation
climatemaster.com
3
Electric Heat - Installation, Operation, and Maintenance
Revised: 04 August, 2015
Vertical Installation - External
1. Disconnect power to the unit.
2. Remove blower access panel(s) from the unit and control
box and element covers from the electric heater.
3. Locate remove and discard blower discharge anges
from the unit but save the screws. Flanges will be
packaged loose inside the blower compartment of
vertical upow units. TZ036 and 042 units require a
transition bracket between the cabinet top and the electric heater. This bracket is packaged inside the
blower compartment for eld installation.
4. Position the electric heater as illustrated herein. Heater control box should be facing the front access panel of vertical units.
The electric heater air inlet dimensions should match the unit air outlet, installer should stop and refer to the unit/heater compatibility chart later in this instruction or consult factory if they do not match.
Electric Heat Assembly
Auxiliary electric heat power supply knockout
Air Coil
opposite air coil
Low Voltage control harness
*
is prewired on all distributor class units.
5. Use the saved blower ange screws to attach the heater by its anges to the unit panel except do not fasten ange on control box side.
6. Use aluminum tape (not provided) to seal all four heater anges to the blower panel.
7. Locate and route the low voltage control harness through
the top panel knockout(s). Seal the penetration ‘air tight’. This harness is factory installed on all TZ units (wire-tied to the fan housing).
8. Route the control harness through one of the ‘pie’ bushings in the heater control box and plug on to the P2 connector. See gure 5.
9. Install power conduit and attach directly to the electric heater control box. See gures 5a-c.
10. Replace all covers and panels, heater installation is
complete. Proceed to wiring and setup.
4