ClimateMaster ACDU03 Operation Manual

ACDU03 Communicating
Service Tool
Operation Manual
97B0106N01
Rev.: 11/3/17
Caution:
These instructions are intended to be used by the installer or service personnel. End users are NOT advised to change or modify any of these settings. Doing so may cause the equipment to stop working properly and/or may void the warranty on both the thermostat and the equipment.
Table of Contents
Section Title Page
1.0 Connection 3
2.0 Menu Structure 4
3.0 System Confi guration 4
3.1 Airfl ow Selection 4
3.2 Option Selection 5
3.3 Unit Confi guration 5
3.4 Pump Confi guration 6
3.5 Valve Confi guration 6
3.6 Multi-Unit Confi guration 7
4.0 Service Mode 8
4.1 Manual Operation 8
4.2 Control Diagnostics 8
4.3 Dipswitch Confi guration 9
4.4 Fault History 9
4.5 Clear Fault History 11
5.0 Revision History 12
This page was intentionally left blank.
ACDU03 Communicating Service Tool
P1
Alarm
O
Y1
Y2
W
G
C
R
AL1
R
C
R
NSB
AL2
JW1
P2
P5
B-
Gnd
A+ 24V
DXM2
Board
Rev.: November 3, 2017
1.0 Connection
ClimateMaster’s Communicating Service Tool (ACDU03) allows install and service technicians to confi gure and diagnose ClimateMaster Digital Communicating Units without installing a digital communicating thermostat.
Using the Service Tool, a technician can ELECTRONICALLY:
1. Confi gure items like: airfl ow, heat pump options and confi guration, pump or modulating valve operation, unit family, unit size, etc.
AND
2. Diagnose the unit by operating it manually, performing control diagnostics, viewing dip switch confi gurations, or by viewing fault history and operating conditions when a fault occurred.
The Service Tool connects to the DXM2 board with a 4-Wire Connector as shown below:
Note: For Vertical Stack models (TSM, TSL) must order harness for connection to service port outside chassis. Harness part number 11B0100N27. DXM2 to service port is factory wired.
DXM2
Board
WARNING!
WARNING! powered on or connecting backward may damage service tool.
Connecting wire harness while unit is
DXM2
Board
Service tool
connection
3
ACDU03 Communicating Service Tool
Rev.: November 3, 2017
2.0 Menu Structure
Menu Structure
System Confi guration Airfl ow Selection Option Selection Unit Confi guration Pump Confi guration Valve Confi guration Service Mode Manual Operation Control Diagnostics Dipswitch Confi guration Fault History Clear Fault History
SERVICE TOOL MENU
SYSTEM CONFIG
3.0 System Confi guration
Use the System Confi guration option on the start-up screen to adjust critical equipment settings.
The System Confi guration information will be automatically obtained from each communicating control in the system.
Note 1: The Airfl ow Selection menu (section 3.1) will not be present if the connected communicating control system has no blower.
Note 2: The Pump Confi guration menu (section 3.4) will not be present if the connected communicating control is confi gured for No Loop Confi guration (OTHER).
Note 3: The Valve Confi guration menu (section 3.5) will not be present if the connected communicating control is confi gured for No Loop Confi guration (OTHER).
3.1 AIRFLOW SELECTION
Adjust the airfl ow settings for each system operating mode using the up/down arrow buttons. Press the center button to select each item.
• Airfl ow Settings (defaults stored in control) - valid range: obtained from control (in 25 CFM increments)
• Blower Off Delay (default 60 seconds) – valid range: 0 to 255 seconds (in 5 second increments)
SERVICE MODE
ACDU03 1.00 SELECT OPTION
Start-up Screen
SYSTEM CONFIGURATION AIRFLOW SELECTION OPTION SELECTION
UNIT CONFIG TES026
PUMP CONFIGURATION
SELECT OPTION
PREVIOUS SELECT
System Confi guration Menu
NOTE 1: The Airfl ow Settings will only be present if the connected communicating control is confi gured for ECM blower.
NOTE 2: If multiple units are connected to one thermostat, refer to section 3.6 for unit selection.
4
Geothermal Heat Pump Systems
Loading...
+ 8 hidden pages