ClimaCool UCW-H 30, UCW-H 50, UCW-H 70, UCW-H 85 User Manual

Water Cooled Ulmate Chiller Soluon
Model UCW/H 30, 50, 70, 85
Installaon, Operaon & Maintenance Manual
Table of Contents
Introduction .........................................1
Pre-Installation .......................................2
Unit Installation ......................................3
Model Key ...........................................4
Physical Data .........................................5
Dimensional Data and Drawings ........................6
Rigging and Lifting Procedures ........................7
Mounting Rail and Vibration Isolation ...................8
Recommended Service Clearances ......................9
Water Piping ......................................10-11
Water Piping Congurations ..........................12
Hydronic Refrigeration ...............................13
Filling the Water System ..............................14
Water Treatment ....................................15
Water Temperature Requirements ....................16
Condenser and Evaporator Water Pressure
Drop Charts ......................................... 17
Glycol Performance Adjustment Factors Charts .........18-19
Electrical Connection .................................20
Voltage/Phase Monitor Wiring ......................... 21
Pre-Startup .........................................22
Pre-Startup Check List ................................23
Superheat & Subcooling Flowchart ....................26
Startup and Warranty Form ........................ 27-29
Chiller Operation and Maintenance ....................30
Heat Exchangers ....................................31
Cleaning Arrangment ................................32
Operational Limitations ..............................33
Compressor Information .............................34
Refrigeration Circuit Diagram ......................35-36
Refrigeration System Re-Processing and Charging .......37
Options and Accessories ..............................38
Stainless Steel Strainer Option .....................39-43
Y Type and Basket Type Strainers ......................44
Electrical Data ....................................45-46
Power Distribution Drawing ...........................47
Wiring Diagrams ..................................48-57
Troubleshooting Guide ............................58-59
Warranty Certicate .................................60
Introduction
CAUTION
!
ATTENTION INSTALLER
3 Phase Scroll Compressor Units
• If this unit uses a 3 Phase Scroll Compressor, the following instructions MUST BE followed:
- Unit power supply MUST BE wired in the proper sequence to avoid
damage to the 3 Phase Scroll Compressor;
- Scroll Compressors with INCORRECT rotation show the following
characteristics:
1.) High sound level;
2.) High suction pressure and low dischage pressure;
3.) Low current draw.
- If any of the three above characteristics exist, swap two of the
three supply wires at the disconnect and recheck compressor for incorrect rotation.
General Description
ClimaCool’s dedication to energy and environmental leadership led to the Ultimate Chiller Solution design. Available in 30, 50, 70 and 85 tons, each module is compact,
redundant, maneuverable, ecient, reliable and serviceable. Combined tonnages can obtain specic project turndown
and capacity requirements from 30 to 1,000 tons per bank while having the ability to accommodate future growth and expansion needs.
The UCW/H model can oer hot gas bypass, heat pump and
heat recovery options utilizing environmentally friendly R-410A refrigerant for Green building designs.
WARNING
This unit contains HFC-(R410A), an azeotropic mixture of R-32 (Difluoromethane) and R-125 (Pentafluoroethane). DO NOT VENT HFC-(R410A) to the atmosphere. The U.S. Clean Air Act requires the recovery of any residual refrigerant. Do not use R-22 service equipment or components on R410A systems.
Safety
Throughout this manual warning, danger, caution and attention notices appear. Read these items carefully before attempting any installation, service or troubleshooting of the equipment. All labels on unit access panels must be observed.
DANGER: Immediate hazardous situation which, if not avoided, will result in death or serious injury.
WARNING: Potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION: Potentially hazardous situation or an unsafe practice which, if not avoided, could result in minor or moderate injury or product or property damage.
ATTENTION: Notication of installed, operation or
maintenance information which is important, but not hazard related.
High voltage is used to operate this equipment. Failure to observe standard electrical safety procedures may result in serious injury. Only persons qualified and / or properly trained should attempt to install, operate and maintain this equipment. These chillers come fully charged with refrigerant. Installation, and start – up should be accomplished by technicians who are fully certified to handle refrigerants, as required by 40 CRF Part 82, subpart F of the Recycling and Emissions Reduction Act. Scroll compressors are used in this equipment. Phase verification is required for proper rotation direction. Incorrect rotation will result in elevated sound and internal overload trip failure.
SAFETY WARNING
• Excessive Chlorine, Undissolved Solids and other improper water quality conditions
WILL DAMAGE the internal heat exchanger and WILL VOID YOUR WARRANTY!
WARNING
To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by
technicians who meet local, state and federal prociency
requirements.
All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state and federal statutes for the recovery and disposal of refrigerants.
If a compressor is removed from this unit, system refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.
!
• Electric shock hazard!
• May result in injury or death!
• Disconnect power supply(ies) before servicing!
• Refer servicing to qualified service personnel.
• Unit to be serviced by qualified personnel only.
• Refrigerant system under pressure.
• Relieve pressure before using tourch.
• Recover refrigerant and store or dispose of properly.
www.climacoolcorp.com
DANGER
! !
CAUTION ATTENTION
WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
CAUTION!
CAUTION! Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept other types of conductors.
!
WARNING!
DANGER
RECOVER
REFRIGERANT
• Risque de choc électrique!
• Résultat de mai dans dommages ou la mort!
• Debrancher avant d’entreprendre le dépannage de l’appareil!
• Consulter un réparateur qualifie pour le dépannage.
• Confier la maintenance á un technicien qualifie.
• Le systéme frigorifique sous pression.
• Décomprimer avant d’exposer á la flamme.
• Récuperér le frigorigene et le stocker ou le détrire correctement.
1
Pre-Installation
Inspection
Upon receipt of equipment, carefully check the shipment against the bill of lading and inspect each chiller for any damage incurred during shipment. Thoroughly check for any visible damage of control panels and electrical and/or refrigeration components or broken copper lines. The carrier must make proper notation of any damages or shortages on all copies of the bill of lading and complete
a common carrier inspection report prior to your nal
acceptance of the shipment. Note: It is the responsibility
of the purchaser to le all necessary claims with the
carrier. In addition, please notify the ClimaCool Customer Service Department at 405.815.3000 or customerservice@ climacoolcorp.com of all damage immediately.
Storage
Chillers should be stored in an upright position and kept in a clean, dry area.
Handling of Modules
Carefully remove the module’s packaging. The chiller’s steel base cutouts provide maneuverability by forklift or pallet
jack into its nal position (See Rigging and Lifting Procedures
on page 7). Verify that all header grooved couplings and mounting hardware kits are on site prior to connecting the modules. Note: Consult factory for handling other than in the upright position.
Rigging and Lifting
Each module should be lifted using a pallet jack or fork lift. If it is necessary to utilize a crane for rigging or lifting, each module shall be lifted using lifting straps and spreader
bars using rigging points identied on Rigging and Lifting
Procedures on page 7.
Warranty
To ensure proper equipment longevity, design performance and reliability, all ClimaCool chillers must be installed, operated and maintained in accordance with ClimaCool IO&M manuals. Water quality is of the utmost importance for the proper care and maintenance of your modular chiller system. Regular treatment of the water will increase longevity of your system. Failure to provide adequate ltration or treatment
of evaporator and condenser water will void the ClimaCool module’s warranty. A factory authorized technician is
required to perform the startup of your ClimaCool chiller. Please contact the ClimaCool Customer Service Department at 405-815-3000 or customerservice@climacoolcorp.com to schedule. There is a minimum of 3 weeks’ notice required to
schedule your factory startup.
2
www.climacoolcorp.com
Unit Installation
Unit Placement
ClimaCool modular chillers must be installed in a conditioned
and dehumidied space. The minimum foundation
requirement for the chiller is a level surface capable of bearing the combined operating weight of the modules (See Physical Data on page 5).
Service Access
The recommended service clearances are 36” for front access, 18” height clearance for 30, 50 and 70 ton modules, and 24” height clearance for 85 ton module, 30” for rear access and at least 12” for side clearance or as required for eld piping (see Recommended Service Clearances and Bank Dimensions on page 9). Local building or electrical codes may require additional clearance – please consult applicable codes.
Draining
When performing standard maintenance procedures such
as ushing a heat exchanger, it will be necessary to isolate either heat exchanger. ClimaCool modular chillers oer
optional water isolation valves for this purpose. Access
to a oor drain is helpful when performing standard
maintenance procedures. Warning: Water valves must be reopened after ushing is complete.
Assembling Modules
ClimaCool recommends locking down the chiller to a concrete base or to three (3) 4” base mounting rails using the six (6) bolt holes provided in each base pan. Although the compressors are installed on anti-vibration mountings, further isolation of the chiller from the structure is recommended by installing vibration-eliminating springs or pads under the base rails on which the chiller will rest (See page 8 – Mounting Rail and Vibration Isolation). One module should be chosen as the reference module and carefully located.
Field installed mounting accessories are provided for adjoining each module.
Header grooved coupling kits containing four (4) grooved couplings with gaskets
Mounting hardware kit containing necessary bolts, spacers, nuts and washers
Header bank end cap kit containing four (4) grooved couplings with gaskets and four (4) end caps
Field installing the mounting hardware kit will assist with
alignment of the modules in a bank and eliminate oset
inconsistencies. The 1/2” mounting holes are provided on sides of the unit base pan. First module should be set, set adjacent unit on mounting surface roughly aligned
1 ½ inches away from the rst unit. While holding spacer in place work through rst modules front base cutout to
place a washer and insert bolt through front mounting hole and spacer. Repeat the process for the rear mounting hole. Line up mounting hole of adjacent module with bolt from previous module and working through adjacent modules front base cutout place a washer, split lock washer and nut. Using the appropriate tools tighten hardware assembly until seated.
Inspect the pipe ends to ensure they are free from any indentations, projections, roll marks or other harmful surface defects such as loose paint, scale, dirt, chips, grease and rust. Inspect the grooved coupling gasket for any defects. Apply a thin layer of silicone or other non-petroleum lubricant to the sealing lips of the gasket as well as to the exterior of the gasket. Install gaskets on the pipe ends of one of the two modules to be mated.
Be sure the gasket is completely on the pipe to avoid damage in the next step. Move the second module into
position and line up the piping. Ensure you are maintaining alignment for any additional modules to be added. When pipe ends are aligned, slide the gasket over the ends and center it between the grooves. No part of the gasket should protrude into the groove of either pipe end. Place the coupling halves over the gasket and make sure that the coupling keys (the part that goes into the groove) are engaged into the grooves. Insert the bolts and install nuts to hand tight. Ensure the oval neck of the bolt engages into the bolt hole of the housing. Tighten nuts alternately and
equally until the bolt pads meet and make metal to metal contact. Tighten nuts by another ¼ to ½ turn to make sure
the nuts and bolts are snug and secure; the use of a torque wrench is usually not required. Uneven tightening of bolts
may cause the gasket to be pinched resulting in immediate or delayed leaks.
Header Insulation
Chilled water piping is pre-insulated on each module at the factory with ¾” closed cell insulation. After bolting all modules together and leak testing, the entire coupling connection will need to be insulated by the installing contractor.
Sound Attenuation Panels and Gasket
Attenuation panels are enclosures made of 18 gauge
galvanized steel with powder coat paint nish and berglass
insulation. Panel package includes one (1) upper panel made out of four (4) sections and one (1) lower panel for each side
of bank (eld installed), four (4) panels for each module
in the bank (factory installed) and gasket sealant tape for installation between modules. Install panels by setting in place and locking down with the half turn latches or self tapping screws. Note: Panel package includes a compressed
1” x 1” gasket sealant tape for installation between modules. Install the tape on the outer frame on the side of one module prior to installing the adjacent modules.
www.climacoolcorp.com
3



r
Model Key
RejectionMeans
W=Water ModelConfiguration
H=HighTemperature S=Standard
NominalTons
070 B=HotGasBypass‐BothCircuits
030 RefrigerantOptions
050 0=(None)
DesignSeries X=SpecialOptions
085 (NotavailablewithHeatPumpapplication)
S=Scroll
X=SpecialOptions
CompressorType
Controls&Electrical Application
A=StandardControls C=Cooling
X=SpecialOptions H=HeatRecovery
U=380/3/50 X=SpecialOptions
N=575/03/60 M=ManualValvesforEvap&Conds
F=460/3/60 B=Evap&CondsrMotorizedValves
H=208230/3/60 E=Evap.MotorizedValves&ManualCondsrValves
Voltage
A
UC F S
₁₂
W ASACA
₁₃ ₁₄
030
UltimateChillerSolutionModelKey
₄₅₆ ₁₀
A=R410A
X=SpecialOptions
Refrigerant
R=ReverseCycle(HeatPump)
X=SpecialOptions
0=(None)
WaterIsolationValves
R=PressureReliefValves
P=HotGasBypasswithPressureReliefValves
₁₂₁₁
M0
₁₅
X=SpecialOptions
4
www.climacoolcorp.com
Physical Data
Model UCW/H Module and Compressor
30 50 70 85
Capacity (tons) ¹
31.7 51.5 67.2 82.8
kW/Ton
0.738 0.746 0.744 0.740
Full-Load EER
2
16.3 16.1 16.1 16.2
Refrigerant Circuits (quantity)
2 2 2 2
Compressor Type
Scroll Scroll Scroll Scroll
Compressor Quantity
2 2 2 2
Compressor Nominal Hp (per circuit)
15 25 35 40
Refrigerant Charge (per circuit) R-410A (lbs)
15 32 34 40
Module Operating Weight w/Water (lbs)
3
1480 2200 2450 2855
Module Shipping Weight (lbs)
4
1290 1880 2130 2390
30 50 70 85
Heat Exchanger (type) Brazed Plate Brazed Plate Brazed Plate Brazed Plate
Independent Refrigerant Circuits (quantity)
2 2 2 2
Water Storage Volume HX Only (gals)
3.2 6.1 7.3 11.4
Water Storage Volume HX Plus Main Headers (gals)
13.1 16.7 17.9 26.2
Min
30 50 70 85
Max
165 250 250 485
Maximum Design Working Pressure - Water Side (psi)
300 300 300 300
Header Water Connections - Inlet/Outlet (inches)
6
6 6 6 8
30 50 70 85
Heat Exchanger (type) Brazed Plate Brazed Plate Brazed Plate Brazed Plate
Independent Refrigerant Circuits (quantity)
2 2 2 2
Water Storage Volume HX Only (gals)
2.8 5.1 6.5 9.7
Water Storage Volume HX Plus 6" Main Headers (gals)
12.8 15.7 17.1 24.5
Min
40 65 85 100
Max
165 250 250 350
System Volume (gals)
8
Min
180 300 420 510
Maximum Design Working Pressure - Water Side (psi)
300 300 300 300
Header Water Connections - Inlet/Outlet (inches)
6
6 6 6 8
Notes:
1.
2.
3.
4. Unit shipping weight includes refrigerant charge, compressor oil and packaging.
5.
6.
7.
8. Required to provide stable operation. Storage/buffer tanks in return piping may be utilized to meet the minimum volume requirements.
Main header water/fluid connections are 6" grooved coupling for the 30, 50 and 70 ton modules. The 85 ton module uses 8" grooved couplings.
85 ton module cannot be directly coupled with 30, 50 or 70 ton modules due to a difference in header and frame size.
Module operational weight includes water, compressor oil, and refrigerant charge. Multiply times the number of modules for a total system operational weight.
Tonnage ratings conditions: 44°F leaving chilled water temperature, 85°F entering condenser water temperature, flow rates are 3 gpm per ton through the condenser with a fouling factor of .00025 hr-ft2-°F/Btu and 2.4 gpm per ton through the evaporator with a .0001 hr-ft2-°F/Btu fouling factor.
Ratings in accordance with AHRI Standard 550/590.
The minimum/maximum flow rates are based on an approximate temperature differential of 5°F to 20°F through the evaporator and 5°F to 30°F through the condenser. Flow rates vary based on application; verify with selection software.
Model UCW/H Condenser
Flow Rate (gpm)
5
Model UCW/H Evaporator
Flow Rate (gpm)
5
www.climacoolcorp.com
5
Dimensional Data and Drawings
P5
Chiller Type Header A Header B
UCW Chilled Water Outlet Chilled Water Inlet
UCH Heat Recovery Chilled Water Outlet Chilled Water Inlet
UCH Heat Pump (Cooling Priority) Chilled Water Outlet Chilled Water Inlet
UCH Heat Pump (Heating Priority) Load Water Inlet Load Water Outlet
Load Water Piping Configuration Arrangement
6
www.climacoolcorp.com
Rigging and Lifting Procedures
Rigging
Each module should be lifted using lift straps threaded through the steel base cutouts and a spreader bar.
Note: If no spreader bar is used, damage to the module may occur.
Figure 1 Figure 2
Figure 1 Figure 2
Lifting Strap Lifting Strap
Spreader BarSpreader Bar
Spreader Bar
Lifting and Transporting Modules
Pallet jacks or forklifts are required for lifting and transporting the module. Each module has base cutouts provided for ease of maneuverability. 60” forks are recommended to prevent damage to chiller base.
Figure 3
www.climacoolcorp.com
7
Mounting Rail and Vibration Isolation
4” Rail Minimum Recommended (by others)
4” Rail Minimum Recommended (by others)
Spring Vibration Isolators (by others)
ClimaCool recommends locking down the chiller to a concrete base or to three (3) 4” base mounting rails using the six (6) bolt holes provided in each base pan. Due to the low vibration of the modules, the application of spring isolators or pads is not required. Should isolators or pads be desired install in accordance with Figures 4 and 5.
Figure 4 - Spring Vibration Isolators Option
4” Rail Minimum Recommended (by others)
Spring Vibration Isolators (by others)
Figure 5 – Vibration Isolation Pads Option
4” Rail Minimum Recommended (by others)
Note: Size and weight distribution is to be determined by a qualied structural engineer per individual job requirements.
8
www.climacoolcorp.com
Recommended Service Clearances
Top View
30”
Rear Service Access
12”
36”
Notes:
1. Allow 36" clearance for electrical panels and 30" clearance for rear service access to modules.
2. Allow a minimum of 18" height clearance for 30, 50 and 70 ton modules. Allow a minimum of 24” height clearance for 85 ton modules.
3. Local building and/or electrical codes may require additional clearance. Consult applicable codes.
Front Service Access
36”
30”
CoolLogic
Control Panel
(Wall Mounted)
www.climacoolcorp.com
9
Water Piping
HEADER BYPASS
REVERSE RETURN
HEADER BYPASS
REVERSE RETURN
No. 29 Reducing Tee
w/Thd. Branch
6 x 6 x 2
END VIEW
No.10 2" 9 Elbow
No.50 Reducer
6 x 2
Hose Kit
2"Belimo Ball Valve & Actuator
2" Grooved Coupling
HEADER BYPASS
DIRECT RETURN &
HEADER BYPASS
DIRECT RETURN &
No. 25 Grooved Branch
6 x 6 x 2
No. 29 Reducing Tee
w/Thd. Branch
6 x 6 x 2
END VIEW
Hose Kit
2"Belimo Ball Valve & Actuator
2" Grooved Coupling
As with any water system, it is important that the system be clean. The pipe work installer must remove weld scale, rust and contamination during pipe work fabrication.
The system water piping must be ushed thoroughly with recommended alkaline ush or other chemicals that
are compatible with 316 stainless steel, prior to making connections to the ClimaCool chiller. There are certain necessary components that should always be installed in both the chilled water and condenser water systems. (See
Water Piping Conguration Figures 9 and 10 on page 12). Piping congurations on multiple modules may also be
found on pages 12. All water piping must be installed in accordance with applicable codes and standards.
Temperature Sensor and Wells
ClimaCool provides four (4) temperature sensors and wells
with each chiller system congured by the CoolLogic Control System. They must be eld installed 36” - 60” away from
the bank and before the strainer on the chilled water inlet, chilled water outlet, condenser water inlet and condenser
water outlet (See Water Piping Congurations – page 12).
Note: Sensors must be fully inserted into the well to obtain proper readings.
Pressure Dierential Flow Sensor
It is imperative that minimum and maximum water ow rates, as dened in the Physical Data tables on page 5, are
not exceeded. To prevent operation of the chiller without
sucient water ow to the evaporator and condenser, it is required to install pressure dierential ow sensors in
both the chilled and condenser water circuits. Place one on each side, downstream of the strainers on the inlet and outlet of a straight pipe, as close to the module as possible. Do not put in an elbow on the outlet. (See Water Piping Congurations – page 12). Note: Evaporator and condenser
sides both require sensors of equal pressure ranges.
Strainers – Minimum 60 Mesh Screen Required
ClimaCool chillers utilize brazed plate heat exchangers which are extremely sensitive to debris. Therefore, it is
mandatory that all condenser and chilled water systems include a strainer with a minimum of 60 mesh screen for proper ltration. The strainers must be installed as shown in
the Water Piping Congurations on page 12 and be in place
at all times when the chiller(s) is/are in operation.
ClimaCool’s warranty does not cover and does not apply to products which have defects or damages due to freezing
of the water supply, an inadequate or interrupted water supply, corrosives or abrasives in the water supply, or
improper or inadequate ltration or treatment of the water supply.
Chiller/Heater System Water Header Bypass
A bypass is required for any chilled water/evaporator, hot water/condenser (heating load) and source water side (geothermal, cooling tower or closed circuit cooler) with variable pumping. The bypass must be piped in such a way
that the temperature and dierential pressure sensors are still sensing active ow. See Water Piping Conguration
Figures 9 and 10 on page 12 The purpose of the chiller/heater system bypass is to prevent deadheading of the pumps when all of the internal unit valves go closed as well as allow
temperature and dierential pressure sensors to sense active ow. The bypass should be sized for an absolute minimum of one module’s worth of design ow. (Please refer to selection submittals for design ow rates).
Modules can be designated for xed bypass for heating, cooling and source ow, however, this limits the number of
modules remaining for that duty. Also, with a module acting as a bypass increased wear of heat exchangers may be
caused by abrasion from bypass ow.
Pressure Taps
The installing contractor must provide access ports for
connecting both the pressure dierential ow sensor and
pressure gauges for both the condenser and chilled water systems. A ¼” pressure tap is required on the inlet and the outlet of both water systems for a total of eight (8) taps. If a
port is shared by the pressure dierential ow sensor and the
pressure gauge, it will require four (4) ½” taps. (See Water
Piping Congurations – page 12).
Water Isolation Valves
It is recommended to provide bank water isolation valves for proper isolation and maintenance of the chiller, pump
and strainer (See Water Piping Congurations – page 12).
10
Figure 6 ­Direct Return
Figure 7 ­Reverse Return
www.climacoolcorp.com
Grooved Coupling
No. 25 Grooved Branch
6 x 6 x 2
No.50 Reducer
No. 25 Grooved Branch
2" Grooved Coupling
6 x 6 x 2
Ball Valve &
No. 29 Reducing Tee
w/Thd. Branch
Hose Kit
SIDEVIEW
2"Belimo
Ball Valve &
Actuator
No. 29 Reducing Tee
6"
Grooved Coupling
Hose Kit
2" Grooved Coupling
No.10
2" 90°
2"Belimo
Actuator
SIDE VIEW
6 x 6 x 2
Module
w/Thd. Branch
6"
Header
6 x 6 x 2
Grooved Coupling
Module Header
No.50
Module
Reducer
6"
2"
Header
Grooved
Coupling
6 x 2
Grooved Coupling
Module
6"
Header
Grooved Coupling
Hose Kit
END VIEW
2"Belimo
Ball Valve &
Hose Kit
END VIEW
Actuator
No. 29 Reducing Tee
w/Thd. Branch
6 x 6 x 2
No. 29 Reducing Tee
w/Thd. Branch
2"Belimo
Ball Valve &
Actuator
6 x 6 x 2
2"
2" Grooved Coupling
No.10 2" 90° Elbow
6 x 2
ClimaCool oers two types of water header bypass kits, direct
LOAD 1
FROM CHILLER BANK
TYPICAL LOAD BYPASS VALVE ARRANGEMENT
TO CHILLER BANK
LOAD 2 LOAD 3 LOAD X
TYPICAL CHILLED AND HOT WATER
LOAD SIDE BYPASS VALVES
SIZE EQUIVALENT TO ONE MODULE
WORTH OF FLOW
return (Figure 6) and reverse return (Figure 7) as shown on page 10. The bypass kits must be installed on each water source loop and controls are integrated with the CoolLogic software. Installation location can be found on page 12 – Water Piping
Conguration.
This bypass can also be created with eld supplied piping. The
design piping must accommodate one module’s worth of design
ow, and be positioned so that the temperature and dierential ow sensors sense active ow in the bypass mode. See Figures 9 and 10 on page 12 - Water Piping Conguration. The eld
supplied piped chiller/heater system bypass must be controlled by others. There are system communication delays, polling and
network conicts that strictly prohibit the use of ClimaCool sensors and controls for control of eld supplied bypasses or other eld supplied items. Recommended method is to control via dierential pressure or gpm ow meters across the chilled
water/evaporator, hot water/condenser water systems.
Load Side System Bypass (Air Handlers, Fan Coils, etc.)
A load system bypass is required for preventing pump
deadheading, allowing active ow system sensing and preventing starving ow from the chiller/heater system.
Examples of an acceptable load side system bypass are:
•Utilize a quantity of 3-way control valves on the largest loads farthest from the chiller/heater system.
•Field piping with a control valve to provide a bypass across the larger system loads when their 2-way valves go closed.
Please refer to Figure 8 for a typical load bypass valve arrangement. The load side system bypass should be sized for an absolute minimum of one module’s worth of
design ow. (Please refer to selection submittals for design ow rates). A minimum of (6) six gallons per nominal system
ton are also required to maintain proper system thermal inertia. This is to avoid short cycling of compressors in the chiller/heater system as well as prevent nuisance alarms.
Figure 8 - Typical Load Bypass Valve Arrangement
11
www.climacoolcorp.com
Water Piping Congurations
Notes:
1. Figures 9 and 10 are required piping for proper water regulation and distribution through ClimaCool modular chillers.
2. Module order and incoming/outgoing water ow as shown in both Figure 9 and 10 can be set up as either a left-to-right or right-to-left conguration.
3. Condenser hydronic circuit shown. Piping congurations are similar for the chilled water hydronic circuit.
4. For condenser/heating and chilled water (evaporator) inlet/outlet location dimensions, refer to page 6 - Dimension Data.
5. A pressure dierential ow sensor is a required safety device for ClimaCool modular chillers on the chilled and condenser/heating water circuits.
6. A strainer with a minimum of 60 mesh stainless steel screen is a required safety to protect the brazed plate heat exchangers on both chilled and condenser/heating water sides of the system.
7. Maximum water ow rates for both evaporator and condenser/heating water header systems for 30, 50 and 70 ton modules in one bank is 1,000 gpm.
8. Maximum water ow rates for both evaporator and condenser/heating water header systems for 85 ton modules in one bank is 2,400 gpm.
9. Bypass is mandatory for systems utilizing motorized valves.
10. Header bypass valve may be installed at either end of bank.
11. For over seven (7) modules, please consult the factory.
Figure 10 - Field Piping Reverse Return
Figure 9 - Field Piping Direct Return
12
www.climacoolcorp.com
Hydronic Refrigeration
Figure 11- Condenser Hydronic Circuit
Isolation Ball Valve (2, 2-1/2 or 3”)
To Cooling Tower
Header
From Cooling Tower
Header
Isolation Ball Valve (2, 2-1/2 or 3”)
Water Circuit
Figure 12 - Chilled Water Circuit
Pete’s Port
Service Port (3/4”)Pete’s Port
Service Port (3/4”)
Heat Exchanger
Refrigerant Circuit #1
Refrigerant Circuit #2
Refrigerant Circuit #1
Refrigerant Circuit #2
Header
Header
Isolation Ball Valve (2, 2-1/2 or 3”)
Chilled Water Inlet
Chilled Water Outlet
Isolation Ball Valve (2, 2-1/2 or 3”)
Pete’s Port
Cap Tube to Low Limit
Protection Thermostat
Service Port (3/4”)Pete’s Port
Service Port (3/4”)
Sensor Well (internal)
Heat Exchanger
Note: Figure 11 and 12 depict hydronic piping in each ClimaCool chiller module and are shown with water isolation valves.
www.climacoolcorp.com
13
Filling the Water System
It is imperative that the water systems are free from debris prior to initial operation. See Water Treatment for a comprehensive list of precautions on page 15.
Filling, Purging and Leak Testing the System
After the water systems have been properly installed, visually inspect all joints for tightness. If the chiller is to be installed in an existing system, the cleanliness of the existing system can be judged from the operating conditions of the present machines. The cooling tower in particular, should be inspected and cleaned, if required. It is good practice to ush and, ideally, to acid wash the existing system before connecting a new chiller.
The following method is recommended to ll and leak check
the water system for modules WITH Water Isolation Valves:
1. Close all water isolation valves inside each module which isolate the individual heat exchangers.
2. Ensure that all drain valves are closed and that all water main isolation valves are opened.
3. The system should be lled with clean water sent
through the strainers and the system checked for leaks.
4. Once the main water lines and the chiller headers are
lled with clean water, purge and repeat the lling
process at least three times.
5. All modules are equipped with ¾” ll and ush valves
with lines teed into the inlet and outlet connections into and out of each heat exchanger. Ensure these ¾” valves are CLOSED.
6. Open the water isolation valves inside each modular
chiller and repeat the lling process, this time also
checking for leaks inside each module.
7. Following the nal lling and leak checking procedure,
air should be purged from the system.
The following system is recommended to ll and leak check
the water system for modules WITHOUT Water Isolation Valves:
1. Ensure that all drain valves are closed.
2. All modules are equipped with ¾” ll and ush valves
with lines teed into the inlet and outlet connections into and out of each heat exchanger. Ensure these ¾” valves are CLOSED.
3. The system should be lled with clean water sent
through the strainers and the system checked for leaks.
4. Once the main water lines and the chiller headers are
lled with clean water, purge and repeat the lling
process at least three times.
5. Following the nal lling and leak checking procedure,
air should be purged from the system.
Cleaning the System
The following method is recommended to properly clean the water systems:
1. Before cleaning the system, install a temporary bypass line between the main supply and return water headers of both chilled and condenser water systems when possible. Open the main header bypass lines to
divert the initial water ow around the module heat exchangers until you are condent the circulating water
is mostly pure.
2. Provided main header bypass lines are installed, close all water isolation valves inside all modular chillers equipped with manual or automatic water isolation valves. If the modules are NOT equipped with water isolation valves, we recommend installing 3-way main header bypass valves so the initial water ow bypasses all module heat exchangers.
3. It is mandatory to run the pumps with the strainers in place (see Starting the Pumps section below for proper pump startup). All external hydronic branches should be open to all devices in the system.
4. Pressure drop across the strainer must be observed and as pressure change reaches 50% of the initial read, strainers must be isolated and cleaned.
5. Open all water isolation valves inside each module equipped with manual or automatic water isolation valves (see step 6 for modules NOT equipped with water valves). If bypass lines are not installed (described in step
1) it is recommended to drain out the initial ll of water to help ush out debris. Close o the main header bypass lines referred to in step 1 and open the ow to the main
water headers. Repeat steps 3 and 4 until there is no more debris being collected by the strainers.
6. If bypass lines are not installed (described in step 1) and the modules are NOT equipped with water isolation
valves, it is recommended to drain out the initial ll of water to help ush out debris. Remove and clean the strainers before relling and purging the system again.
Repeat steps 3 and 4 until there is no more debris being collected by the strainers.
Starting the Pumps
Follow the manufacturer’s recommendations when starting
the pumps for the rst time. The system should be checked
for leaks and air purged with the pumps in operation. The pressure drop across the heat exchangers will give a good
indication of ow through the system (See Condenser
and Evaporator Water Pressure Drop Charts on page 17). This should be immediately checked against the expected
pressure drop for the ow rate required. If the pressure
drop begins to fall and the ow rate is falling, this could indicate the need to clean the strainers.
14
www.climacoolcorp.com
Water Treatment
CAUTION
Water quality is of the utmost importance for the proper care and maintenance of the modular chiller system.
Proper water treatment is a specialized industry and it is
recommended to consult an expert in this eld to analyze
the water for compliance with the water quality parameters listed in Table 1. The materials exposed to the water are type 316 stainless steel, pure copper and carbon steel. Other materials may exist external to the ClimaCool chiller. It is the user’s responsibility to ensure these materials are compatible with the treated water. Regular treatment of the water will increase longevity of your system.
Failure to provide adequate ltration or treatment of evaporator and condenser water will void the ClimaCool module’s warranty.
Heavy-Contaminated Water
In such instances whereby the particulates in the water are excessive, it is recommended to install an intermediate plate and frame heat exchanger to isolate the ClimaCool chiller from the building water system.
Cooling Tower
The cooling tower should be located away from sources of external contaminates such as trees, dust or grass cuttings.
Insect inltration can be reduced by eliminating lights near
the tower. A periodic visual inspection of the tower system should be made and contaminates removed as required.
• Excessive Chlorine, Undissolved Solids and other improper water quality conditions
WILL DAMAGE the internal heat exchanger and WILL VOID YOUR WARRANTY!
Table 1 - Water Quality Parameters
15
www.climacoolcorp.com
Water Temperature Requirements
Pressure Taps
Thermometer
Wells
Isolation Valves
Condenser Water
Flow Sensor or
Switch
Pressure Relief Valve
Flow to Tower Load
Flow from Tower
Cooling Tower Bypass Valve
Strainer Isolation Valve
Pump
Backflow Preventer
Strainer
Drain Valve
Backflow Preventer
Pressure Relief Valve
Condenser Water Temperature
The condensers are designed to operate most eciently
at lower entering water temperatures for lower power consumption. The expansion valve, however, relies on
the pressure dierence across the valve to drive the liquid
refrigerant through. It is necessary to maintain a minimum
pressure dierential across the thermal expansion valve (equivalent to a 30°F dierence between saturated
liquid temperature in the condenser and saturated vapor
temperature in the evaporator) to avoid loss of eciency and system performance. This pressure dierential is most
commonly ensured by cycling the fans on the cooling tower to maintain the entering condenser water temperature above the minimum temperature of 60°F. An alternate method to maintain the minimum entering condenser water temperature above 60°F is to employ a bypass arrangement as shown in Figure 13 below. This valve is an automatic 3-way bypass valve, which senses the temperature of the mixed water entering the condenser. If this mixed water temperature falls below 60°F the valve will re-circulate the leaving condenser water and mix it into the entering condenser water stream (bypassing the cooling tower). The full range of entering condenser water is 60°F to 95°F for standard applications and maximum leaving hot water temperature of 135°F for high temperature applications. For entering water less than 60°F refer to Options and Accessories (page 38) - Motorized Water Isolation Valves.
Chilled Water Temperature
Modules are designed for a leaving water temperature range from 40°F to 62°F. All cataloged modules can operate safely in this range without the need of special controls or glycol additives. Leaving water temperatures below 40°F can result in evaporator suction temperatures below the freezing point of water. Therefore, a glycol solution additive is required that will protect the evaporator from freeze ups at lower operating suction temperatures. The full range of
leaving chiller uid using glycol is 20°F to 62°F.
Figure 13– Condenser Water System
Note: Only required for equipment without motorized condenser valves.
16
www.climacoolcorp.com
Condenser and Evaporator Water Pressure Drop Charts - 030, 050, 070, 085
100
43.3
t
10
4.3
s
Condenser Water Pressure Drop
30, 50, 70 & 85-Ton, UCW/UCH Series
Model# UCW/UCH030 Model# UCW/UCH050 Model# UCW/UCH070 Model# UCW/UCH085
80
60
50 45 40
35
30 25
20 18 16
. of Water)
14
12
10
8
6
4
Pressure Drop (F
2
1
10 1000
120
100
80604030
140
160
180
240
200
280
350
260 300
220
400
500
Flow (GPM)
Evaporator Water Pressure Drop
30, 50, 70 & 85-Ton, UCW/UCH Series
34.7
26.0
21.7
19.5
17.3
15.5 13
10.8
8.7
7.8
7.0
6.1
5.2
4.3
3.5
2.6
1.7
0.87
0.43
Drop (PSI)
Pressure
Model# UCW/UCH030 Model# UCW/UCH050 Model# UCW/UCH070 Model# UCW/UCH085
(Ft. of Water)
100
80
60 50 45
40 35 30 25
20 18 16
14
12
8
6
4
43.3
34.7
26.0
21.7
19.5
17.3
15.5 13
10.8
8.7
7.8
7.0
6.1
5.2
3.5
2.6
1.7
ure Drop (PSI)
Pres
Pressure Drop
2
1
10 1000
120
100
80604030
140
160
180
200
220
240
280
400 500
300
260
0.87
0.43
Flow (GPM)
17
www.climacoolcorp.com
Loading...
+ 44 hidden pages