Cleveland Range 21-CET-16 General Manual

Steam Craft
SERVICE
5.1
COUNTER TYPE CONVECTION STEAMER
MANUAL
Model21-CET-16
Printed 12/90
Cleveland Range, Inc.
•UNITED STATES CANADA
UlHI Mi',sissauua. Ontariu CM.4\V 1X4 Phone: (216) 4Sl-4y(ll» • 1 cle \: ^.1)54^
• FAX: (216) 4S1-37S2 Phone: (416) 64-026» • FAX: 1416) 624-(1623
CTS-02
PROTECTING WARRANTY COVERAGE
Electrical Power Requirements and Line Voltage
6 and 17
Water Quality Require
ments and Analysis
6 Water Pressure
18 Vented Drain
14 Level Operation
10 Blowdown Frequency
41
and
52 Steam Generator Maintenance and Maintenance Records
55 Descaling Frequency and Procedure
56 Approved Chemical Cleaners
56
The warranty printed to the left specifies the owner/user's responsibility for proper installation, operation, and maintenance of the SteamCraft 51 If these respon­sibilities are not met, the Limited Warranty and/or Extended Limited Warranty coverage may be adversely affected The following table is provided to assist the owner/user in meeting these responsibilities In addition, the warranty advantages of installing a SteamerGard water treatment system are explained after the table
The Warranty Protection Table lists installation, operation, and maintenance fac tors that have in the past adversely affected warranty coverage The owner/user of a SteamCraft 51 should pay particular attention to these factors to protect his warranty coverage This table is not a comprehensive list of the owner/user's responsibilities Cleveland Range steam products are intended for use only by professionally trained personnel To meet his responsibilities, the owner/user must supplement this guide with any additional actions consistent with the operation of steam generating food preparation equipment by a trained professional
Warranty Protection Table SUBJECT PAGE
Authorized Maintenance and Repair 61
REFERENCE
SteamerGard Water Treatment System
A Steamer Gard water treatment system protects the SteamCraft 51 from impurities contained in regular tap water, especially Total Dissolved Solids (TDS) which cause lime and scale deposits in steamer equipment The protection is so effective that Cleveland Range increases the warranty coverage on a SteamCraft 51 installed in conjunction with a SteamerGard system to five years for parts and three years for labor on water related components, elements, valves, generators, piping, etc How­e'ver, even with a SteamerGard system installed, the owner/user should follow the guidance of the Warranty Protection Table
Model 21-CET-16 Service Manual Page i
MODEL NUMBER
1 SERIAL NUMBER
1 PRODUCT INFORMATION PLATE
1
INTRODUCTION
3 INSTALLATION POLICIES
3
INSTALLATION OVERVIEW
4
PREPARATION
FOR
INSTALLATION
6
Electric Power Requirements
6 Water Quality Requirements
6 Water Supply System
7 Selecting The Operating Location
7 INSTALLATION INSTRUCTIONS
9
Unpacking and Inspection
9 Shipping Da
mage Instructions
10 Position and Level The Steam Craft 51
10 Leg Mounting and Leveling
10 Surface Mounting and Leveling
11 Stand Mounting and Leveling
12 Install Slide Racks
14 Install the Free Air Vented Drain Lines
14 Connect Drain Lin
e
16 Install Electric Power Lines
16 Connect
Electrical Line
17 Install Water Supply Lines
18 Connect Water Supply Lines
20
General Connection Requirements
21
Untreated Water Connection (Without SteamerGard)
21
Treated Water Connection (With St
eamerGard)
21 Testing Water Supply Lines
21 Final Setup and Checkout
22
Setup and Blowdown Inspection
- All SteamCraft
51's 22 Operating Tests
- Key Pad Control Panel
24 Operating Tests
- Dial Timer Control Panel
26
Table of Contents
CHAPTER PAGE
CHAPTER 1 PRODUCT IDENTIFICATION 1
CHAPTER 2 INSTALLATION INSTRUCTIONS 3
Page ii Model 21 -CET-16 Service Manual
Table of Contents (continued)
CHAPTER PAGE CHAPTER 3 OPERATION 29 INTRODUCTION 29 OPERATIONAL SAFETY 29 CONTROL, PANELS 30 KEY PAD CONTROL PANEL SUMMARY 31 COOKING OPERATIONS -KEYPAD CONTROL PANEL 32 Manual and Timed Modes 32 Main Power Switch 32 Power ON (Automatic Fill) 34 Inspect the Cooking Compartment 34 Preheating the SteamCraft 51 35 Operating Procedure - Timed Mode 36 Operating Procedure - Manual Mode 39 Manual Timer 39 Temperature Compensation 39 Manual Cooking Procedure 40 Power OFF (Automatic Blowdown) 41 Blowdown Frequency 41 Blowdown Procedure 42 Shut Down and Cleaning (At end of day or shift) 42 DIAL TIMER, CONTROL PANEL SUMMARY 44 COOKING OPERATIONS-DIAL TIMER CO NTROL PANEL 44 Manual and Timed Modes 46 Main Power Switch 46 Power ON (Automatic Fill) 46 Inspect the Cooking Compartment - 47 Preheating the SteamCraft 5-1 47 Operating Procedure - Timed Mode 48 Operating Procedure - Manual Mode 50 Manual Timer 50 Manual Cooking Procedure 50 Power OFF (Automatic Blowdown) 52 Blowdown Frequency 52 Blowdown Procedure 52 Shut Down and Cleaning (At end of day or shift) 53
Model 21-CET-16 Service Manual Page iii
INTRODUCTION
55 MAINTENANCE RECORDS
55 DAILY MAINTENANCE
55
Clean SteamCraft
51
55 WEEKLY MAINTENAN
CE 55 MONTHLY MAINTENANCE
56 YEARLY MAINTENANCE
59 TROUBLESHOOTING NOTES
61
INTRODUCTION
63
Figure
s
And Illustrations
63 STEAMCRAFT 51 ELECTRICAL CIRCUITS
63
High Voltage Circuit
63 120
VAC Circuit
63 Timer
Circuits
64 CIRCUIT OPERATION
64
MANUAL Mode Circuit Operation
64 TIMED Mode, Circuit Operation
67 Electronic Key Pad Timer Units
68 Mechanical Dial Timer Unit
68 Shutdown, Steam Generator Blowdown and Float Cylinder Rinse
68 ELECTRICAL CIRCUI
T COMPONENTS
70 Terminal Block
(4,
Figure
6-7) 70 Heater Element
(4,
Figure
6-9) 70 Dryer Element
(7,
Figure
6-8) 71 Fuses
(8,
Figure
6-7) 71 ON/OFF Switch
(10,
Figure
6-
5) 71 TIMED/MANUAL Switch
(11,
Figure
6-5) 72 Relay K1
(9,
Figure
6-5) 72 3 Minute Timer
(14,
Figure 6
-5 ) 73 Rinse Solenoid Valve
(1,
Figure
6-11) 73 Drain Solenoid Valve
(4
Figure
6-12) 73 Fin Solenoid Valve
(1,
Figure
6-11) 73 Condenser Solenoid Valve
(1,
Figure
6-11) 74 Timer
74 Electronic Key Pad Timer
(3,
Figure
) 74 Compartment Thermal Switch (electronic key pad units only)
(17,
Figure
) 75
Table of Contents (continued)
CHAPTER PAGE CHAPTER 4 PREVENTATTVE MAINTENANCE AND TROUBLESHOOTING 55
CHAPTER 5- ELECTRICAL SYSTEM 63
Page iv Model 21-CET-16 Service Manual
3-Second Timer and Buzzer
(mechanical timer units only)
(11,15,
Figure
6-6) 75 High Tempera
ture Limit Switch
(1,
Figure 6
-9) 75 Float Assembly (Figure
6-10) 75 COMPONENT TESTING GUIDE INTRODUCTION
77
Nominal Voltage
77 FUNDAMENTAL COMPONENT TESTING
77 Visual Check
77
Fuses
78
Connection Points and Wiring
78 Solenoid Valves
78 Tim
ers
79 Thermostatic Snap Switches
79
Heater Element
80 Resistance Measurements
80
Insulation Resistance Measurements
80
Voltage Measurements
80 COMPONENT TEST PROCEDURES
81
Initial conditions for all testing
81 Fuses
81
Transformer
82 ON/O
FF Switch
83 Relay K1
83 Fill Solenoid Valve
84
3-Minute Timer
85 Drain Solenoid Valve
-
86 Rinse solenoid
-
valve
-
87 Condenser Solenoid Valve
88 TIMED/MANUAL Switch
89 High Temperature Limit Switch
90 Electronic Key Pad Timer
90 Compartme
nt Thermal Switch (key pad timer units only)
92 Mechanical Timer
93 Heater Contactor
93 Heater and Dryer Elements
95 Float Assembly
96 3-Second Timer and Buzzer (mechanical timer units only)
99
Table of Contents (continued)
CHAPTER PAGE
CHAPTER 5 ELECTRICAL SYSTEM (continued) Mechanical Timer (3, Figure 6-6) 75
Model 21 -CET-16 Service Manual Page v
INTRODUCTION
101 Parts Differences Among SteamCraft
5.1
Steamers
101 Electrical Schematics and Wiring Diagrams
101
Table of Contents (continued)
CHAPTER PAGE CHAPTER 6. ILLUSTRATED PARTS LISTS 101
MODEL NUMBER
SERIAL NUMBER
Model 21-CET-16 Service Manual Page 1
CHAPTER 1. PRODUCT IDENTIFICATION
Cleveland Range, Inc. assigns two product identification numbers to each SteamCraft 5.1: a model number and a serial number. The model number identifies the product characteristics. The serial number identifies the individual unit.
All-SteamCraft 5.1 steamers are identified by the same model number, 21-CET-16. Each character of this model number identifies a charac ­teristic of the steamer. The SteamCraft 5.1 is a Convection steamer, .Electric powered, and Table-mounted with an input energy rating of 16.5 kW. This manual covers all standard features and options available on SteamCraft 5.1 steamers.
Other than selection of options, there are presently no significant design, parts, or operating differences among steamers with this model number. Figure 1-1 illustrates the SteamCraft 5.1 and identifies the major com­ponents.
During manufacture, SteamCraft 5.1's are assigned individual serial numbers. A typical SteamCraft 5.1 serial number is: WC-7350-90G-02. The left half of the number carries design information. The right half of the number contains the manufacturing date and the unit of the manufac ­turing lot The date of our sample number is 90G-02:90= 1990, G=July. 02=the second unit of the manufacturing lot. Serial numbers are used when explaining differences in design, parts, or operation among units with the same model number. For example: a particular part may be used on SteamCraft 5.1's with serial numbers before WC-7350-90G-02, and a different part used on steamer WC-7350-90G-02 and those manufac tured after it
PRODUCT INFORMATION PLATE
The Product Information Plate on the back of the unit lists the model and serial number of the steamer. Refer to Figure 1-1 for the location of the plate. Figure 1-2 illustrates a typical SteamCraft 5.1 Product Information Plate. The plate also fists power and wiring requirements.
Figure 1-2. SteamCraft 5.1 Product Information Plate
INTRODUCTION
Model 21-CET-16 Service Manual Page 3
CHAPTER 2. INSTALLATION INSTRUCTIONS
This chapter is a guide for installation of the SteamCraft 5.1, model number 21-CET-16. The instructions are written for qualified, profes sional plumbers, pipe fitters, and electricians. This guide does not include all procedures and precautions in the common domain of licensed plumbers, pipe fitters, and electricians, or experienced food service equipment installers.These instructions must be used in conjunction with a thorough understanding of the Basic PIumbing Code of the Building Officials and Code Administrators International, Inc. (BOCA), the National Fuel Gas Code, ANSI Z223.1-1984, and the Food Service Sanitation Manual of the Food and Drug Administration (FDA).
Before starting installation, the owner and the installer should read through this chapter and thoroughly understand and agree upon:
• The installation policies of Cleveland Range, Inc. as stated in Installation Policies.
• Responsibility for electric power requirements as described in Preparation for Installation, Electric Power Requirements.
• Responsibility for feed water quality and its testing as described in Preparation For Installation, Water Quality Requirements.
INSTALLATION POLICIES
WARNING DEATH, INJURY, AND EQUIPMENT DAMAGE could result from improper installation of the SteamCraft 5.1, or from installation of a unit damaged during shipment or storage- Either of these conditions could also void the equipment
warranty.
DO NOT INSTALL a SteamCraft 5.1 suspected of
damage.
Install the SteamCraft 5.1 according to the policies
and procedures outlined in this manual.
The SteamCraft 5.1 must be installed by qualified plumbing and electrical personnel, working to all applicable national and local codes. Equipment installation must comply with the Basic Plumbing Code of the Building Officials and Code Administrators International, Inc. (BOCA) and the Food Service Sanitation Manual of the Food and Drug Administration (FDA). Cleveland Range designs and manufactures equipment to comply with applicable standards for manufacturers. Included among these certification agencies are: UL, A.G.A., ASME/N.Bd., NSF, CSA, CGA, ETL, and others.
Page 4 Model 21 -CET-16 Service Manual
Unpack and inspect SteamCraft 5.1
9
Install and connect water supply lines.
18-21
• This equipment is designed and certified for safe operation only when permanently installed in accordance with local and/or national codes.Many local codes east, and it is the responsibility of the owner and installer to comply with these codes.
• In no event shall the manufacturer assume any liability for damage or injury resulting from installations which are not in strict compliance with the Installation Instructions and the codes cited above.Specifically, the manufacturer will not assume any liability for damage or injury resulting from improper installation of equipment, including, but not limited to, temporary or mobile installations.
INSTALLATION OVERVIEW
Schematic Installation Diagram, Figure 2-1, illustrates the various drain, electrical, and water lines required; and their connection points on the SteamCraft 5.1. Table 2-1, Installation Check List, outlines the overall installation process in a recommended sequence; the instructions refer­enced provide details. Installation requirements may vary from site to site; adapt the check list accordingly.
Table 2-1. Installation Check List
TASK REFERENCE COMPLETED Preparation Check Electric Power Requirements. 6 Test supply water quality. 7 Select water supply system- 7 Install water treatment system- 7 Select operating location. 7 Installation
Position and level steamer. 10 Install and connect drain line. 14-16 Install and connect electrical lines. 16-18
Test water supply lines. 21 Perform final setup and checkout. 22
PAGE
Model 21-CET-16 Service Manual Page 5
INSTALLATION DIAGRAM NOTES
1. The Product Identification Plate located on the back panel specifies the electric power requirements.
2. For each unit, the installer must provide a ground connection and a separate fused disconnect switch.
3. Catastrophic damage will result from shifting the SteamCraft 5.1 more than 10° out of level while power is turned on at the unit's main power switch.
4. The unit must have a cold water supply, NOT HOT. The water supply must meet the quality requirements of Table 2-2, and the pressure requirements on page
18.
5. A SteamerGard system is recommended when water quality does not meet the Table 2-2 requirements.
Figure 2-1. Schematic Installation Diagram
6. A manual shut off valve must be installed between the main water supply and the steamer supply fines. Refer to figures 2-18 and 2-19 for the recommended component arrangements.
7. Run a single water fine between the main cold water supply and the tee. The separate steam generator and condenser/blowdown supply fines are comparatively short.
8. The drain One must have a gravity flow away from the steamer, and must not be connected to the dram lines of any other equipment.
9. The drain line must be free air vented- If the line empties into a floor drain, there must be a one inch minimum clearance between the drain fine and the floor drain openings.
Page 6 Model 21-CET-16 Service Manual
The characteristics of the e
lectric power supply must match the power
Water Quality Requirements
CAUTION
PREPARATION FOR INSTALLATION
Before unpacking the SteamCraft 5.1, check the electric power and water quality requirements and select the operating location-
Electric Power Requirements
requirements specified on the SteamCraft 5.1 product identification plate. The plate is located on the back of the unit as illustrated in Figure 2-2.
Using water not within the limits specified in this manual could void or adversely affect Cleveland Range's warranty coverage of the SteamCraft 5.1.
As with any steam generating equipment, poor water quality degrades SteamCraft 5-1 performance. If feed water is low in Total Dissolved Solids (TDS) and free of particulate matter, the steam generator, heating element, and valves of the SteamCraft 5.1 will give years of trouble-free service with a minimum of maintenance.
In some areas, even potable tap water contains a variety of impurities that can cause costly problems in steam generating equipment. Of primary concern are mineral salts and other impurities which remain behind as lime or scale deposits during the steam generating process. Th ese deposits have caused components to fail, including heating elements, probes and solenoid valves. Of equal importance is the decrease in heat transfer efficiency caused by lime and scale deposits. Decreased heat transfer increases water and power consumption. Use of the SteamCraft 5.1 in areas with poor water quality requires installation of a SteamerGard water treatment system or increased frequency of maintenance, cleaning, and descaling.
Model
21 -
CET-16 Service Manual
Page
7 For safe and efficient operation, observe the following criteria when
Check the quality of supply water as described below
before starting construction
Alkalinity
less than
20
parts per million
of the water supply lines. If a SteamerGard water treatment system must be installed to achieve acceptable water quality, install it before connecting the water supply lines to the SteamCraft 5.1.
Contact a local water treatment specialist for an on-the-premises water analysis. The recommeoded minimum feed water quality requirements for the SteamCraft
5.1 are listed in Table 2-2. Table 2-2. Minimum Water Quality Requirements
Total Dissolved Solids Silica less than 13 parts per million
ph factor greater than 7.5
less than 60 parts per million
Water Supply System
Select a water supply system that fulfills the requirements of the limits listed in Table 2-2. The supply must provide a minimum dynamic pressure of 35 psi (2.4 kg/cm2) and a maximum static pressure of 60 psi (4.1 kg/cm). Refer to page 18 for detailed pressure and fitting requirements, and recommended plumbing layouts.
• If analysis shows that the supply water is within the required limits, a
single line water system can be installed. A single water line system is illustrated in Figure 2-18 on page 18,
• If analysis shows that the supply water is NOT within the required limits,
install a SteamerGard water treatment system- Figure 2-19 on page 19 illustrates a treated water supply arrangement.
• If analysis shows that the supply water is NOT within the required limits,
and it is not possible to install a SteamerGard water treatment system; plan on increasing the frequency of maintenance, cleaning, and descaling beyond that recommended in the maintenance schedule
(Chapter 4).
Selecting The Operating Location
selecting an operating location for the SteamCraft 5.1.
1. The SteamCraft 5.1 fits in a small counter space- Figure 2-3 illustrates the dimensions and clearances required. Maintain the following minimum dimensions around the unit for safe and efficient operation, maintenance and service.
• A 3 inch clearance around the unit for ventilation.
• A 12 inch clearance on the right side for removing the service panel during descaling, maintenance and repair.
• A 3 inch clearance at the rear for the water inlet fittings, and the maximum size (2-inch NPT) drain fittings.
• Approximately 22 inches in front of the unit for opening the door and cafeteria pan clearance.
Page 8 Model 21 -CET-16 Service Manual
Figure 2-4. Equipment Stand
2. The SteamCraft5.1 is typically installed with four adjustable mounting legs, as shown in the dimension drawing. If clearance above the unit is limited, it can be installed 'without legs, surface mounted directly to the counter top.
3. The SteamCraft 5.1 must be level both front to back and side to side. Select an operating surface that is level enough to allow leveling the unit without extreme adjustment of the legs or shimming of surface mounts.
4. The SteamCraft 5.1 weighs approximately 155 pounds. The counter area selected must be capable of supporting an operating weight of approximately 200 pounds to include the weight of water and food.
5. The SteamCraft 5.1 has capacity for three 12" x 20" x 2-5' Cafeteria Pans (model # SP-2.5 or PP-2J). Convenient storage for pans should be considered when selecting the operating location.
6- Do not block the vents on the side or rear of the unit. Do not store
articles on top of the unit.
If a satisfactory counter location is not available, consider using a model ES-2130 Equipment Stand. This stand, illustrated in Figure 2-4, is designed to support the SteamCraft 5.1, and meets the above criteria.
Model 21 -CET-16 Service Manual Page 9
INSTALLATION INSTRUCTIONS
Unpacking and Inspection
After selecting the SteamCraft 5.1 operating location, the steamer can be unpacked, positioned, and installed. After Final Setup and Checkout, the SteamCraft 5.1 will provide years of reliable operation.
1. Before unpacking the shipping carton, visually inspect it for damage.
• If the shipping carton appears damaged, do not open the carton. Refer to the Shipping Damage Instructions on page 10.
• If the shipping carton is undamaged, proceed with step 2.
2. Slit the four comers of the carton and peel carton sides away from the SteamCraft 5.1. The slide racks and legs are shipped in separate packing on top of the unit. Be careful not to damage or throw away these unassembled parts.
3. Remove the carton from the top of the unit The package contains two slide racks as illustrated in Figure 2-5. These racks are snipped in separate packing on top of the unit
4. The SteamCraft 5.1 adjustable legs are also shipped on top of the unit in pockets at the edges of the packing. Refer to Figure 2-6.
5. Open the door of the SteamCraft 5.1. Several pre-assembled parts can be seen inside the unit Refer to Figure 2-7. Do not remove the Drain Screen, Steam Nozzles, and Slide Rack Mounting Pins.
6. Inspect the SteamCraft 5.1 and parts for damage or loss.
• If you discover or suspect shipping damage or loss, refer to the
Shipping Damage Instructions on page 10.
• If all items are accounted for and undamaged, place the packaged
slide rac ks inside the cooking compartment, and proceed to Position and Level The SteamCraft 5.1.
Page 10 Model 21 -CET-16 Service Manual
Shipping Damage Instructions
If shipping damage to the SteamCraft 5.1 is discovered or suspected, observe the following guidelines in preparing a shipping damage claim.
• Write down a description of the damage or the reason for suspecting damage as soon as it is discovered. This will help in filling oat the claim forms later.
As soon as damage is discovered or suspected, notify the carrier that delivered the shipment.
• Arrange for carrier representative to examine damage.
• Fill out all appropriate claims forms and have the examining carrier sign and date each farm.
Position and Level The SteamCraft 5.1
The SteamCraft 5.1 is typically counter top mounted on four adjustable legs. To compensate for height limitations, the steamer can be surface mounted directly to the counter top. If a suitable counter is not available, the unit can be secured to a Cleveland Range ES-2130 Equipment Stand. The following instructions cover each of these mounting methods.
CAUTION Malfunctions and equipment damage may result from improper mounting. Malfunctions and/or damage resulting from improper mounting are not covered by the equipment warranty.
The SteamCraft 5.1 MUST BE LEVEL BOTH FRONT TO BACK AND SIDE TO SIDE in all mount ing arrangements.
Catastrophic damage will result from shining the SteamCraft 5.1 more than 10° out of level while power is turned on at the unit's main power supply switch.
Leg Mounting and Leveling
The supporting legs of the SteamCraft 5.1 are four inches long when the adjustable feet are fully retracted. This provides the four inch space below the unit required by NSF sanitary standards. The adjustable feet can be extended approximately two inches for leveling the steamer.
Assembly
1. Check that the feet are fully retracted into the legs. Do not over­tighten. The feet should easily screw in and out using fingers only.
Model 21 -CET-16 Service Manual Page 11
Surface Mounting and Leveling
WARNING
INJURY AND EQUIPMENT DAMAGE could result from improper lifting. The SteamCraft 5.1 weighs approximately 135 pounds. Use enough workers with experience lifting heavy equipment to place the SteamCraft 5.1 on the counter.
2. Be sure electric power is turned off at the main power switch. Place the SteamCraft 5.1 on its left side.
3. Screw the four legs into the weldnuts mounting holes - All four lees must be installed for proper mounting of the SteamCraft 5.1.
4. Place the steamer upright on its four legs.
Positioning and Leveling
1. Thoroughly clean the counter top area that will support the steamer.
2. Using a level, determine and mark the highest comer of the counter top area that will support the steamer.
3. Lift the SteamCraft 5.1 into position on the counter.
4. Do not adjust the retractable foot of the leg in the highest comer (marked in step 2). Using a level, adjust the other three legs until the unit is level both front to back and side to side.
5. After the SteamCraft 5.1 has been positioned and leveled, refer to page 14, and install the slide racks.
Figure 2-8. Counter Top Mounting Holes
When a SteamCraft 5.1 is surface mounted (without legs), NSF standards require a sanitary counter top seal between the counter surface and the bottom of the unit. This seal closes any gap between the unit and counter top. A sanitary seal closing a gap greater than 1/4 inch may not meet NSF sanitation standards. Therefore, do not surfac e mount the SteamCraft 5.1 to a surface out of level more then 1/4 inch over the length or width of the unit. Shimming the unit level may leave a gap too large to seal within NSF standards.
1. Thoroughly dean the bottom perimeter of the steamer and the counter top area that will support the steamer.
2. Using a level, determine and mark the highest comer of the counter top area that will support the steamer- At each of the other three comers, measure and note the shim thickness required to level the SteamCraft 5-1 both front to back and side to side.
3. Refer to Figure 2-8. Leaving the required clearance (shaded area) around the unit, determine the exact front, back, and side lines of the SteamCraft 5.1 on the counter top. From these lines, locate and drill four 1/2 inch diameter mounting holes in the counter, as shown in the diagram.
Page 12 Model 21 -CET-16 Service Manual
4. Lift the SteamCraft 5.1 into position on the counter and align the steamer mounting holes with the counter mounting holes. The steamer mounting holes are the holes with the 3/8" -16 weldnuts usually used to mount the adjustable legs -
NOTE: If there is not enough clearance behind the steamer to install the
5. Install 3/8"-16 mounting screws and washers as shown in Figure 2-9. The screws should be long enough to pass through the washer, counter, shims, and weldnut without projecting more than 1/2 inch above the weldnut. Thread the screws only a few turns into the weldnuts, leaving enough play for leveling the unit and sealing the mounting holes -
6- Do not shim at the highest corner (marked in step 2). Shim the ot her
three comers until the unit is level both front to back and side to side.
7. Inject enough silicone sealant into each mounting hole in the counter to seal the hole as the hardware is tightened.
8. Tighten the mounting hardware enough to secure the unit in place but not change the level. After hardware is tightened, verify that the SteamCraft 5.1 is level front to back and side to side.
9. Seal the gap between the SteamCraft 5.1 and the counter top. Lay a generous bead of silicone sealant under the entire perimeter of the steamer bottom. See Figure 2-10.
10. Smooth the silicone seal into the crevice with finger or tool to provide a cove seal.
11. After the SteamCraft 5.1 has been positioned and leveled, refer to page 14, and install the slide racks.
WARNING INJURY AND EQUIPMENT DAMAGE could result from improper lifting. The SteamCraft 5.1 weighs approximately 135 pounds. Use enough workers with experience lifting heavy equipment to place the SteamCraft 5.1 on the counter.
drain, electrical, and water lines; skip the remainder of this procedure and go to page 14, Install the Free Air Vented Drain Lines- After installing all necessary drain, electrical, and water lines, proceed with step 5 of these instructions and mount the steamer to the counter top.
Stand Mounting and Leveling The Cleveland Range ES-2130 Equipment Stand provides a stable, level
mounting base for the SteamCraft 5.1. In addition, the stand has a slide­away work surface, and storage for five cafeteria trays. When mounting a SteamCraft 5.1 on the ES-2130, first install and level the stand, then surface mount the steamer to the top of the stand. Because the stand is level and designed to support the SteamCraft 5.1 it is not necessary to place shims or seals between the stand and steamer.
Model 21 -CET-16 Service Manual Page 13
Equipment Stand Installation
1. The equipment stand is shipped assembled except for the slide racks. The racks and the steamer mounting hardware are shipped in separate packing within the equipment stand packing. Refer to the Unpacking and Inspection instructions on page 9, and unpack the equipment stand,
NOTE: If there is not enough clearance behind the stand and steamer to install
2- Thoroughly clean the floor area that will support the equipment stand.
3. Using a level, determine and mark the highest corner of the floor area that will
4- Move the stand into position and level it. Do not adjust the retractable foot of
5. Once the stand is level, secure the rear two feet to the floor.
6. After the stand has been positioned, leveled, and secured in place;
Mount the Steamcraft 5.1 on the Stand
1. Thoroughly clean the bottom perimeter of the steamer and the mounting
the drain, electrical, and water lines; skip the remainder of this procedure and go to page 14, Install the Free Air Vented Drain Lines. After installing all necessary dram, electrical, and water lines, proceed with step 2 of these instructions and install the equipment stand.
support the equipment stand.
the leg in the highest comer (marked in st ep 3). Using a level, adjust the feet on the other three legs until the unit is level both front to back and side to side.
install the slide racks. The racks are mounted to the stand in the same manner as the slide racks are mounted inside the steamer. Refer to Install Slide Racks, below.
surface of the equipment stand.
WARNING
INJURY AND EQUIPMENT DAMAGE could result from improper lifting. The SteamCraft 5.1 weighs approximately 135 pounds. Use enough workers with experience lifting heavy equipment to place the SteamCraft 5.1 on the stand.
2. Lift the SteamCraft 5.1 onto the equipment stand and align the steamer mounting holes with the stand mounting holes. The steamer mounting holes are the holes with the 3/8" -16 weldnuts usually used to mount the adjustable legs .
3. Install mounting screws and washers supplied with the stand, as illustrated in Figure 2-11.
4. Tighten the mounting hardware to secure the steamer to the stand, and verify that the SteamCraft 5.1 is level front to back and side to side. If the steamer is not level, re-adjust the STAND level. DO NOT place shims between the stand and the steamer.
Page 14 Model 21-CET-16 Service Manual
Install the Free Air Vented
WARNING
5. After the steamer and stand have been positioned and leveled. install the slide
racks in the steamer as explained below.
Install Slide Racks
1. Refer to Figure 2-12. Each rack has four loops: two at the top and two at the bottom- Hold the slide rack so the ends of the hanger loops point down, as shown in the figure.
2. Slide one rack into the compartment with loops toward one side.
3. Hook the loops over the top and bottom pins.
4. Repeat steps 1 through 3 for the other rack.
Drain Lines
DEATH, INJURY, AND EQUIPMENT DAMAGE could result from improper installation of the drain outlet lines.
Improper installation of these lines could void the SteamCraft 5.1 warranty. The following restrictions are critical to the safety of personnel and equipment, and must not be violated under any circumstances.
Do not connect the drain fine into PVC pipe, or any other drain material that cannot sustain 180° F.
Do not connect drains from any other equipment to the SteamCraft 5.1 drain line.
Do not connect the drain outlet extension line directly to a floor drain or sewer line.
Furnishing and installing the drain line is the responsibility of the owner and/or installer. Figure 2-13 illustrates a drain layout recommended by Cleveland Range. Observe the following instructions to determine the pipe size, the number of fittings required, and the layout of the drain line.
Model 21-CET-16 Service Manual Page 15
NOTE: The drain line must be free air vented, have gravity flow
from steamer, and terminate outside the perimeter of the unit
The one inch minimum clearance between the drain opening and floor drain provides the SteamCraft 5.1 with free air venting. The drain outlet discharges exhaust steam and hot condensate from the steamer. The drain outlet must be free air vented to equalize the pressure in the SteamCraft 5.1 with the atmosphere. Without a free air vent, either high or low pressure in the compartment will cause malfunction or damage.
• Pressure build up in the steamer will cause steam and hot water leakage around the door.
• A vacuum will implode the steamer and cause permanent damage.
Figure 2-13. Drain Lay out
1. The drain lines must be installed in compliance with the Basic Plumb­ing Code of the Building Officials and Code Administrators Interna­tional, Inc. (BOCA), and the Food Service Sanitation Manual of the Food and Drug Administration (FDA).
2. The tot al length of pipe and number of bend fittings required to reach the open drain determines the pipe size used to extend the drain line to an open drain.
• If the drain outlet extension requires six feet or less of pipe, and no more than two elbows are required, use 1-1/4-inch pipe and fittings.
• If the drain outlet extension requires six to twelve feet of pipe, or requires three or more elbows, use 2-inch pipe and fittings -
3. The drain line must have a gravity flow from the SteamCraft 5.1 drain outlet to the floor drain. Do not install a trap in the drain line.
4. Free air venting requires a minimum of one inch clearance between the end of the drain line and the top of the floor drain.
5. Do not connect the steamer drain to drains or plumbing of any other equipment. If drains of two or more units are connected together
• Low pressure can develop, causing an implosion and physical collapse of the steamer-
Drainage from another unit can flow back into compartment of the steamer.
Page 16 Model 21 -CET-16 Service Manual
Connect Drain Line
Connect the drain to the steamer as described below.
1. The SteamCraft 5.1 is supplied with a 1-1/4-inch pipe connection at the rear of
the unit (Figure 2-14).
2. When assembling the pipes and fittings of the drain outlet extension, apply a hardening type pipe sealant to the threads, and thread them together FINGER TIGHT ONLY. DO NOT USE A WRENCH-
Install Electric Power Lines
Furnishing and installing the electrical power lines, switches, fuse box es, connectors and accessories is the responsibility of the owner and/or installer. Figure 2-15 illustrates an electrical layout recommended by Cleveland Range. When installing the electrical power lines and acces ­sories, observe the following instructions .
1. In the United States, install the electrical power lines in accordance with local codes and/or the National Electric Code, ANSI/NFPA No. 70-1990 (USA).
2. In Canada, install the electrical power Lines in accordance with local codes and/or the Canadian Electrical Code, CSA Standard C22.1 (Canada).
3. Install the proper size disconnect switch, circuit breaker or fuses, and wire and conduit to conform to all local codes and the national codes cited above. See Table 2-3 for wire requirements.
4. install a separate disconnect switch and fuses or breakers sized to meet the line amps required by the SteamCraft 5.1 (see Table 2-3). The fuses or breakers maybe an integral part of the disconnect switch or in a separate fuse box. Install the disconnect switch for easy access as needed for daily startup and shutdown. Throughout the remainder of this manual the fused disconnect switch is referred to as the main power switch.
Model 21 -CET-16 Service Manual Page 17
5. There should be a sufficient length of flexible conduit between me Steam Craft 5.1 connector and the wall so the unit can be moved for service.
6. Each steamer must be electrically grounded by the installer.
7. The characteristics of the electric power supply must match the power requirements specified on the SteamCraft 5.1 product identification plate. The plate is located on the back of the unit (refer to Figure 2-2).
Table 2-3. Minimum Wire Requirements
Connect Electrical Line
VOLTS KILO-
WATTS
208 165 46.8 16.2 87 4 220 14.4 37.2 19.8 106 6
240 16.5 40.7 19.8 106 4 440 14.4 18.6 79 423 10
480 165 203 79 423 10 380 16.5 25.6 54 289 8
415 16.5 235 65 344 10
AMPS 3 Phase
HEATER OHMS/COIL
DRYER OHMS
WIRE SIZE*
*Use solid copper wire rated for 75°C, wet location-Connect the electrical lines to the terminal block inside the right side cover as described below.
1. Remove the side panel by removing two screws (Figure 2-16) that hold it in place. Save the screws.
Page 18 Model 21 -CET-16 Service Manual
2.
Mechanically secure the flexible conduit to the electrical access hole (Figure
2
-
Furnishing and plumbing the water supply lines is the responsibility of the
17).
3. The terminal block and ground connection are near the center of the side
opening
4. Refer to the connection diagrams in Figure 2-17, and connect the wires to the
terminal block and ground connector accordingly.
5- The steamer must be electrically grounded by the installer.
6- If no further work inside the side panel is required at this time, such as plumbing
and leak checks, secure the side panel with the two mounting screws (Figure
2-16).
Install Water Supply Lines
owner and/or installer. This section illustrates plumbing layouts recommended by Cleve land Range. When installing water supply lines, observe the following instructions.
1. Always connect a cold water supply to the SteamCrart5.1 water supply lines.DO NOT USE HOT WATER. The steamer will not function properly or within design safety limits if hot or warm water is supplied to either the condenser connection or the steam generator fill connection.
2. Supply water must have a minimum dynamic pressure of 35 psi (2.4 kg/cm2) and a maximum static pressure of 60 psi (4.1 kg/cm2). If static pressure exceeds 60 psi, a pressure regulator must be installed in the supply lines. For best results, set the regulator for 50 psi dynamic pressure. Water pressure greater than 60 psi will cause damage to the solenoid valves. Local water pressure can be 100 psi or more. If possible, check supply pressure at non-peak demand time. A local water company can assist in this check.
3. Refer to the recommended plumbing layouts in Figures 2-18 and 2-19, and install the water supply lines and fittings in accordance with all local and national codes. Pay particular attention to the following requirements and recommendations.
Model 21 -CET-16 Service Manual Page -19
a. When installing a water supply system without a Steamer Gard.
Cleveland Range recommends the plumbing layout illustrated in Figure 2-18. This is a single water line from the main cold water supply to the tee just outside the SteamCraft 5.1- The two separate lines from the tee to the steam generator and condenser/blowdown connections are comparitively short.
b.When installing a water supply system with a SteamerGard,
Cleveland Range recommends the plumbing layout illustrated in Figure 2-19. Note the following details:
• This is a single water line from the main cold water supply to the tee just before the SteamerGard. The two separate lines from the tee to the SteamerGard intake connection and the Steam Craft
5.1 condenser/blowdown connection are comparatively short.
• The water supply to the condenser connection can be untreated.
• The treated water supply connects to the steam generator fill connection.
Page 20 Model 21-CET-16 Service Manual
The water supply connections are located at the rear of the SteamCraft
5.1,
c. Install 1/4-inch IPS water supply lines to match the 1/4-inch com-
pression fittings mounted on the rear of the SteamCraft 5.1. If larger lines are used, a pressure regulator must be installed in the supply line to maintain the pressure specified in step 2.
d.Install a manual water valve between the main cold water supply line and the SteamCraft 5.1 lines.
e. The National Sanitation Foundation (NSF) requires installation of a
check-valve in all supply lines in accordance with and as required by local plumbing codes.
f. At the points indicated in the recommended plumbing layouts, install a
40-mesh water strainer of the type and construction illustrated in Figure 2-20, Cleveland Range part number 102383.
4. Construct all supply lines up to the point of installing the strainer(s) illustrated in the recommended plumbing layouts. Rush the water supply lines before connecting the strainer(s).
• If the remaining water supply lines and/or SteamerGard are not
immediately installed and connected after flushing, temporarily cap
the water supply lines
• If the final installation and connections are performed immediately,
Connect Water Supply Lines
refer to the connection instructions in the SteamerGard manual, and Connect Water Supply Lines, on page 20.
as shown in Figure 2-21- Connect the water supply lines to the SteamCraft
5.1 by following both the general connection requirements and those requirements specific to the type of supply system, either untreated water
supply (Figure 2-18) or water supply treatment system (Figure 2-19).
Figure
2-22- Water Strainer installation
General Connection Requirements
Testing Water Supply Lines
Untreated
Water Connection (Without SteamerGard)
Model 21 -CET-16 Service Manual Page 21
1. Apply pipe dope or teflon tape to any threaded connection.
2. Flush the water supply lines before connecting the strainer(s), and again before
connecting the lines to the SteamCraft 5-1 connections.
3. When installing water strainer(s), use a strainer with a 40 mesh screen as illustrated in Figure 2-22.
• Make sure the arrow on the strainer body points in the direction of flow into the steamer.
• Install the strainer so the access nut points down-
4. If incoming line pressure exceeds 60 psi static pressure, install a pressure regulator to maintain the SteamCraft 5.1 pressure requirements specified in Install Water Supply Lines (page 18).
1. Refer to Figure 2-18. Verify that a suitable check valve is installed according to NSF and local codes.
2. Look. at the flow indicating arrows on the strainer and check valve and verify that flow is toward the steamer.
3. Install the tee and connecting Iines Hush these ones before connecting them to the water supply fittings on the steamer.
Treated Water Connection (With SteamerGard)
1. Verify that the SteamerGard water treatment system has been installed according to the SteamerGard installation manual The 40-mesh strainer supplied with the SteamerGard must be installed at the SteamerGard water inlet.
2. Refer to Figure 2-19. Verify that suitable check valves are installed according to NSF and local codes. The condenser line check valve should be installed between the tee and the steamer. The steam generator line check valve should be installed between the SteamerGard and the steamer.
3. Look at the flow indicating arrows on the strainers and check valves. Verify that flow is toward the steamer.
4. Install the connecting lines and flush them before connecting them to the water supply fittings on the steamer. Be sure the line from the SteamerGard water treatment system connects to the steam generator fitting on the SteamCraft
5.1.
1. Check all connections for proper tightness. Remove the side panel to inspect water connections inside the steamer (Figure 2-16).
2. Open the water supply valves.
Page 22 Model 21 -CET-16 Service Manual
3- Check all lines and connections for leakage, both inside and outside the steamer.
4. If Final Setup and Checkout win be performed next, leave the right side panel off; otherwise, replace the side panel and se cure it to the unit with the two screws (Figure 2-16).
NOTE: If the steamer has not been mounted yet:
Final Setup and Checkout
The Final Setup and Checkout procedures prepare a recently installed or repaired SteamCraft 5.1 for operation- The procedures check proper electrical, water, and drain connections to the SteamCraft 5.1, and verify basic steamer operation.
Model 21-CET-16 SteamCraft 5.1's have an electronic control panel with a key pad timer control. This control panel is illustrated in Figure 2-23 on page 23. An electro-mechanical control panel is also available. This panel has a dial timer control, as illustrated in Figure 2-24 on page 26. There are a few operating differences between steamers with the dial timer controls and steamers with the key pad controls. To avoid confusion during testing, there are two sets of testing instructions: one labeled Operating Tests - Key Pad Control Panel for the electronic control panel, and one labeled Operating Tests-Dial Timer Control Panel for the electro-mechanical control panel. After performing the setup procedure, perform the test procedure appropriate to the control panel on the SteamCraft 5.1 being tested.
For surface mounting, return to page 12, step 5, and finish the mounting procedure.
For equipment stand installation and steamer mounting, return to page 13, step 2, install the stand and mount the steamer.
Setup and Slowdown Inspection - All SteamCraft 5.1 's This procedure is appropriate for SteamCraft 5.1's with either key pad control
panels or dial ti mer control panels. Read through all steps of this procedure before starting. Complete this setup procedure before starting the operating tests.
1. Check that the water supply line valves are open.
2. If using a SteamerGrard water treatment system, refer to the Steamer -Gard manual and start the system. Check that all valves between the SteamerGard and the SteamCraft 5.1 are open.
3. Open the steamer door. Check for proper installation of the drain screen, slide racks, and door gasket assembly. Be sure the drain is not blocked. Shut the steamer door.
4. Refer to electrical layout, Figure 2-15, and Table 2-3. Be sure the main power switch is in the off position. Verify installation of proper size fuses or breakers.
Model 21 -CET-16 Service Manual Page 23
5. Set the control panel as follows: a. Press the OFF (bottom) end of the ON/OFF switch.
b. Press the TIMED (top) end of the TIMED/MANUAL switch.
c. The timer setting is not important while the ON/OFF switch is in the OFF position.
• The key pad timer display is blank without power.
• Even if the dial timer is not zeroed (pointing to the 0 mark), the timing circuits are not powered.
6. Remove the right side access cover (see Figure 2-16).
WARNING
Death, severe electrical shock or equipment damage can result from touching any component inside unit when main power switch is in the on position. Use extreme caution during testing with the access cover removed.
7. Turn on electric power to the SteamCraft 5.1 at the main power switch. The steamer will immediately start a blowdown cycle. During blowdown, the condenser and drain valves are fully open while the steam generator and float assembly are flushed with fresh water. The blowdown cycle lasts 3 minutes During the automa tic blowdown cycle, make the following checks.
• Look at the top of the float control. There should be a steady flow of water entering the top of the float chamber through the spray nozzle.
• Look at the one inch vent gap between the steamer drain pipe and the floor drain- A steady stream of water should be draining from the steamer.
* After about 3 minutes, the cycle is complete- Check the two points listed above; there should be no water flow at any of the points.
NOTE: If it is necessary to stop the blowdown cycle before it is finished, do so by
pressing the ON end of the ON/OFF switch.This energizes the operating control circuits, the red ON/OFF indicator lights, blowdown stops, and the steam generator fills with water. When the ON/OFF switch is tamed OFF. the blowdown cycle will start again.
8. If operating tests will be performed next, leave the right side panel off and perform step a below; otherwise perform step b.
a- Begin the operating tests appropriate to the control panel on the
SteamCraft 5.1 being tested. The key pad control panel tests start after this procedure. The dial timer control panel tests start on page 26.
Loading...
+ 108 hidden pages