Cleveland Motion Controls Classic UPB Transducer Load Cell User Manual

CLEVELAND-KIDDER® UNDER PILLOW BLOCK
WASHDOWN-DUTY
LOAD CELL
INSTRUCTION MANUAL . . . TYPE UPB WASHDOWN-DUTY
Phone: 216-524-8800 Or 800-321-8072 Fax: 216-642-2100
Visit Us: www.cmccontrols.com
INSTRUCTION NUMBER: AO-70136 BA 1 of 9
1.0 GENERAL INFORMATION
1.1 RECEIVING AND UNPACKING
Handle and unpack the equipment carefully. Immediately upon arrival, check the shipment against the packing list. Any damage should be reported immediately to the carrier and to the nearest CMC representative.
Equipment that will not be installed immediately should be stored in a clean, dry location. Precautions should be taken to prevent moisture, dust and dirt from accumulating in storage and installation areas
1.2 PRECAUTIONS
1.2.1 Shipping roll be removed when the machine is shipped with the transducers mounted. The shock and vibration transmitted to the transducers by the sensing roll during transporting can damage them.
1.2.2 Roll Balance balanced to prevent forces caused by imbalance. These forces cause a noise signal to be superimposed on the tension signal. The centrifugal force (F) caused by imbalance can be calculated using the equation below.
F = 28.6 x 10
W = Weight of roll in pounds
R = Displacement of mass of roll from the axis of rotation in inches
RPM = Revolution per minute
It is recommended that the force (F) be less than 5% of the resultant web force at the maximum web speed for most applications.
1.2.3 Critical Roll Speed vibration can be set up in a stationary shaft. If this vibration (in cycles per minute) occurs at the harmonic frequency of the shaft, the transducers can be damaged. To determine the critical roll speed, use the following formula:
- It is recommended that the sensing
- The sensing roll should be
-6
x W x R x (RPM)2 Lbs.
- Even with a balanced roll, a
Critical roll = 4.8 x 10 speed in RPM (Shaft Length)
6
x Shaft O.D.
2
Dimensions are in inches.
To assure that this problem is avoided, the critical roll speed should at least be 20% above the roll speed attained at maximum web speed.
1.2.4 Overloading
- Repetitive overloading above the maximum working force or severe overloading should be avoided because it will damage the transducers.
1.3 SPECIFICATIONS
Gage Resistance - End to end resistance 440-480
Ohms
Gage Factor - 100 nominal
Excitation Voltage -10 VDC or VAC (RMS)
maximum
Output Signal at Rated MWF - 100 mV nominal per
Transducer (1/2 bridge)
200 mV nominal per
Transducer pair (full bridge)
Output Impedance - Approximately 880 Ohms for
UPB2 and UPB3
Approximately 120 for UPB 1
Required Input Impedance of Tension Amplifier - 5K ohms per Transducer (1/2
bridge)
Maximum Voltage, Gage to Beam or Base (Ground) - 50 VDC
Operating Temperature Range - 0
F to +200 F
Compliant
INSTRUCTION NUMBER: AO-70136 BA 2 of 9
1.4 DESCRIPTION
The Cleveland-Kidder Washdown Duty UPB transducers utilize a sensing twin beam to which semiconductor strain gages are bonded. With these high output signal gages a very small force on the sensing beam will be shown as a change in the tension signal.
The type UPB transducers are for use with shafts that are mounted in Pillow Block Bearings. See Figure 1. For mounting dimensions see Figure 2.
Pillow Block Bearing
Washdown UPB Transducer
Figure 1
BM N
A
F G
PILLOW BLOCK
MOUNTING PLATE
LOAD CELL
C
L
J
E
H
K
D
W
No.
Size
No.
*Allow 2.5 inches (64 mm) clearance for connector **Approximate rating in Newtons
A B C D E F(Max.) G H J (Max.) K L M N W 1 1.5 0.55 5.8 1.5 5/16 (4) 5.8 1.6 1.95 ½ (2) 1.40 6.5 1.3 2.2 2.2 25, 50, 100, 250, 500, 1000 2 3 0.80 10.0 3.0 ½ (4) 10.0 3.0 2.5 ¾ (4) 1.71 11.0 3.3 3.95 4.0 1000, 2500, 5000, 10000, 20000 3 4.5 1.63 15.0 4.5 1 (4) 15.6 5.0 4.2 1-1/8 (4) 2.80 17.0 4.8 5.2 6.5 10000, 20000, 30000
A B C D E F(Max.) G H J (Max.) K L M N W 1 38 14 147.5 38 M8 147 40.5 49.5 M12 (2) 35.5 165 33 56 56 110, 225, 450, 1100, 2250, 4500 2 76 20 254 76 M12 254 76 63.5 M20 (4) 43.5 279.5 84 100 101.5 4500, 11000, 22000, 45000, 9000 3 114 41.5 381 114 M24 396 127 106.5 M30 (4) 71 432 122 132 165 45000, 9000, 13500
Dimensions in Inches* Size
Dimensions in Millimeters*
Figure 2
Maximum Working Force (lb.)
Maximum Working Force (N.)**
INSTRUCTION NUMBER: AO-70136 BA 3of 9
2.0 INSTALLATION
2.1 SELECTION OF TRANSDUCER MOUNTING LOCATION
When selecting a transducer mounting location, keep in mind that the tension-sensing roll must NOT be mounted where the web wrap angle can vary. Any change in the wrap angle will be sensed by the transducers as a change in tension, and indicated as such on the tension indicator.
WRAP VARIESWRAP VARIES
PROCESS
OK FOR TENSION SENSING
Figure 3
In some cases, it may be impossible to find a location for the transducers where the wrap angle does not vary. The change in indicated tension that will result can be calculated and, if small, may not be significant.
2.2 MOUNTING SURFACE PREPARATION
The mounting surfaces for the transducers should be flat and parallel. Prepare the machine frames or mounting surfaces by removing any loose paint, rust, scale, etc.
2.3 INSTALLATION PRECAUTIONS
To insure proper installation and operation of the system, the following steps should be performed in sequence. Failure to do so could seriously damaged the Transducers and void the warranty.
PRECAUTION
Always install, orient and firmly bolt down the transducers BEFORE installing the tension-sensing roll. When disassembling or installing, DO NOT remove the transducer and the tension­sensing roll as an assembly - remove the roll first, before loosening the transducer mounting bolts.
2.4 INSTALLATION OF TYPE UPB TRANSDUCERS
Instructions for Mounting the UPB Load Cell to the Machine Frame (see Figure 6)
Remove the pillow block mounting plate (it is held in place by four stainless steel corner bolts) in order to gain access to the four load cell mounting holes. Drill and tap the machine frame to match the load cell mounting holes (refer to section 2.5 to properly position the load cell). Bolt the load cell in place. The UPB load cell is designed so that either imperial or metric mounting bolts can be used when mounting the load cell to the machine frame. Refer to E in the Figure 2 above for the proper bolt size. Before remounting the pillow block mounting plate, refer to section 2.6.
WEB FORCE
INCORRECT
CORRECT
INCORRECT
CORRECT
LOAD ZONE DIRECTION LABEL
Figure 4
2.5 POSITIONING THE TRANSDUCER
Once the four tapped holes have been drilled, you need to orient the UPB load cell properly to obtain
INSTRUCTION NUMBER: AO-70136 BA 4of 9
a good tension measurement. See Figure 4 for details.
Note: the UPB must be oriented so that the resultant tension force direction (bisector of the wrap angle) is in the same quadrant as the load direction arrow on the side of the UPB. Once the correct orientation is selected, you need to tighten four locking bolts (not supplied) accordingly to Figure 5.
English Metric
UPB
Length
min. (in.)
Torque
(ft.-lbs.)
Length
min. (mm)
Torque
(N-m) 1 1.00 10 25 15 2 1.50 30 40 40 3 2.50 150 65 200
Figure 5
2.6 INSTALLATION OF PILLOW BLOCK BEARING
Remove the mounting plate, then drill and tap it to match the pillow block mounting dimensions. A centerline mark is provided on the mounting plate. The plate is to be drilled and tapped by utilizing this centerline mark to insure that the pillow block bearing is centered on the plate. Remount the plate and bolt the pillow block bearing to it. The mounting plate is 304 Stainless Steel, which is amenable to drilling but offers corrosive and chemical resistance. Refer to J in the table above for the maximum bolt diameter recommended for bolting the pillow block bearing to the mounting plate.
2.7 EXTREMELY SEVERE APPLICATIONS
For applications that can create major build-ups of material (paint, glue…), it is recommended to close the exposed gaps of the transducer. A good way to do this is to use Electrical Tape all around the side of the UPB Transducer (See figure 7).
Figure 7
Figure 6
Instructions for Mounting the Pillow Block Bearing to the UPB Load Cell (see Figure 6)
Mounting the pillow block bearing to the UPB is
2.8 SHAFT EXPANSION
If the roller is subjected to higher temperatures after installation, thermal shaft expansion may damage the transducers. To prevent damage to the transducers, an expansion type pillow block bearing should be used.
simple and convenient. The UPB is shipped with a pillow block mounting plate. The mounting plate is held in place by four stainless steel corner bolts.
INSTRUCTION NUMBER: AO-70136 BA 5of 9
3.0 ELECTRICAL CONNECTION
EXCITATION
VOLTAGE
SHIELD
OUTPUT
SIGNAL
(-)
(+)
(-)
(+)
WIRING DIAGRAM FOR TRANSDUCERS
BLK
WHT
RED
BLK
WHT
RED
Figure 8
Refer to the installation wiring diagrams supplied with the Cleveland-Kidder tension indicator or controller for making the transducer connections. Make certain that the cables do not interfere with the web path and that they are away from gearing or other moving parts.
Many of the Cleveland-Kidder indicators and controllers use only half bridge transducer inputs and then sum the two transducer signals internally. See the applicable installation wiring diagrams for the tension indicator or controller.
3.1 MATING CONNECTORS FOR
TRANSDUCERS
USE CMC P/N
Mating Straight Connector, Boot and Clamp Kit MO-09854
Mating 90
Angle Connector,
Boot and Clamp Kit MO-09855
These are not sealed for washdown duty. For washdown duty mating connector consult CMC.
3.2 INTRINSICALLY SAFE
TRANSDUCERS
These transducers are intrinsically safe only when they are part of a complete intrinsically safe
TENSION GAGE
B
TEMP. COMPENSATION
NETWORK
A
COMPRESSION GAGE
C
TENSION GAGE
B
TEMP. COMPENSATION
NETWORK
A
COMPRESSION GAGE
C
NO. 1
TRANSDUCER
NO. 2
TRANSDUCER
system using the TIX-1 tension indicator or wired per CMC control drawings.
Barrier block assemblies and/or the individual barrier blocks may be purchased from CMC. Please contact CMC for part numbers and pricing.
4.0 TEMPERATURE COMPENSATION
The transducers are supplied with a temperature compensation network (except size 1 which don’t require it) which is in series with the output signal lead. The compensation circuit is designed to be used with a tension amplifier which has an input impedance of 10K Ohms when a pair of transducers connected as a full bridge is used. If only one transducer is used, the tension amplifier impedance should be 5K Ohms. If other than the input impedances given above are used, drift will occur in the tension amplifier output when the transducer temperature changes.
5.0 SINGLE TRANSDUCER
OPERATION
For those applications where only one transducer is required, a dummy circuit may or may not be required depending upon the input circuit of the tension amplifier. Consult the factory for this information. The dummy circuit consisting of two resistors is substituted in place of the second transducer. The resistors should have a resistance value between 100 and 150 Ohms and should be matched to within 1%. Dummy circuits are available from the factory for connecting to tension indicators or controllers.
6.0 TROUBLESHOOTING
6.1 EXCESSIVE OUTPUT SIGNAL
WITH NO LOAD
There may be a high degree of misalignment of the transducers causing a severe pre-load.
Or
The sensing guide roll assembly may be excessively heavy. The sensing guide roll should
INSTRUCTION NUMBER: AO-70136 BA 6of 9
not weigh more than ½ the maximum working force of the transducers in most cases.
Or
The surface under the UPB is not flat enough.
Or
The bolting torque is not in accordance with Figure 5 (especially for UPB with MWF under 250 lb.).
6.2 LOW OUTPUT SIGNAL
The transducer may have too large a maximum working force for the application. Replace with a lower maximum working force transducer or increase web wrap angle.
6.3 WRONG POLARITY OF OUTPUT SIGNAL
Transducers may have been incorrectly oriented. See Section 2.4 for proper load direction. Alternately, change the transducer excitation voltage by interchanging the B and C connections.
6.4 OUTPUT SIGNAL NOT LINEAR, ZERO SHIFTS DURING OPERATION
Check transducer and tension roll mounting. All mounting bolts must be tight. Check that there is no dirt or foreign matter interfering with the transducer mounting. Check that mounting surface is flat and rigid.
6.5 NO OUTPUT SIGNAL
Check to see that all connections have been made completely. Check for places where the connecting cables might be crimped or cut.
6.6 VERY HIGH OUTPUT WITH NO
LOAD
Check cables and connectors for good connections and check continuity of cables with an ohmmeter. Check for proper wiring to transducers. Check transducer gage resistance as given in the following chart at room temperature with no load applied.
TRANSDUCER GAGE RESISTANCE CHECK
Resistance
(ohms) Pin C to B 420±20 420±20 Pin A to B 210±10 900-1100 Pin A to C 210±10 900-1100
UPB 1 UPB 2/3
7.0 SERVICE ASSISTANCE AND REPAIR
For additional service assistance, please obtain the Type, MWF, and Serial Number from the nameplate. Contact the Factory Service Department.
Phone: 216-524-8800
Or 800-321-8072 Fax: 216-642-2100
Visit Us: www.cmccontrols.com
Disassembly by improperly trained personnel may result in additional damage to these units. Should repairs be required or for warranty repairs, contact the Customer Service Department for a return authorization number before returning the units.
INSTRUCTION NUMBER: AO-70136 BA 7of 9
8.0 USEFUL SPECIFICATIONS
8.1 WEIGHT
Complete
Unit
Without
mounting plate
8.2 RATINGS
SIZE RATING (LB) * ULTIMATE OVERLOAD (%)
UPB 1 25 to 1000 500
UPB 2
UPB 3 10000 to 30000 500
* Ultimate overload: Maximum force applied on the transducer without risking permanent deformation. For the Washdown duty UPB the output is linear up to the point of the ultimate overload.
1000 to 10000 500
8.3 SIZING CALCULATION
T = Max Tension A = Wrap Angle (degrees) W = Roll Weight B = Angle of tension force K = Overload for Transients (Nominally 1.4 for most applications) MWF = Maximum Working Force (This is used to select the proper force rating of the transducer) C = Mounting Angle H = Bearing Height + D
SIZE L (in) D (in) UPB 1 2.5 0.98 UPB 2 4.5 1.25 UPB 3 6.5 2.10
See figure 9.
 
=
MWF
SIZING CALCULATION:
* The MWF calculation defines the force on each
individual load cell. ** If Angle b is below horizontal use + in calculation If Angle b is above horizontal use - in calculation
Weight lb. (kg.) Each
UPB 1 UPB 2 UPB 3
3.7 (1.7) 22 (10) 102 (47)
1.5 (0.7) 12 (5.4) 59 (27)
20000 250
A
[][]
sin 2KT
2
±+
2L
∗∗
sinC H-cosC LWB LcosBHsin
Note: Consult CMC for assistance in sizing the load cell to your specific application.
A
A/2
T
C
B
L
T
W
H
D
Figure 9
8.4 SELECTION CHART
Transducer MWF (lbs.)
UPB1
UPB2
UPB3
Ordering procedure:
1. Calculate the Maximum Working Force
2. From the Selection Chart, determine the part
3. Obtain pricing and delivery information by
Rating 25 50 100 250 500 1000
M846-12171- 000 100 200 300 400 500
Rating 1000 2500 5000 10000 20000
M846-12172- 000 100 200 300 400
Rating 10000 20000 30000
M846-12173- 000 100 200
(MWF) rating based upon your calculations from the sizing calculation equation.
number for the UPB Washdown-Duty LC. Select a MWF rating that equals or exceeds the MWF from your sizing calculation. Then, make sure that your pillow block bearing fits the UPB type that you selected (UPB 1, 2 or 3).
Example: If you calculate a MWF of 2,204 lbs., select a UPB 2 rated at 2500 lbs. MWF from the Selection Chart. You part number is M846-12172-100. Then, from Figure 2. make sure that you pillow block bearing fits on the Size 2 transducer. If it does not, please consult factory.
contacting a CMC sales representative, distributor, or the factory.
INSTRUCTION NUMBER: AO-70136 BA 8of 9
LIMITED WARRANTY.
ALL GOODS ARE SOLD SUBJECT TO THE MUTUAL AGREEMENT THAT THEY ARE WARRANTED BY THE COMPANY TO BE FREE FROM DEFECTS IN MATERIAL AND WORKMANSHIP FOR ONE YEAR FROM THE DATE OF SHIPMENT. THE COMPANY'S WARRANTY DOES NOT COVER, AND IT MAKES NO WARRANTY WITH RESPECT TO ANY DEFECT, FAILURE, DEFICIENCY OR ERROR WHICH IS:
A) NOT REPORTED TO THE
COMPANY WITHIN THE APPLICABLE WARRANTY PERIOD; OR
B) DUE TO MISAPPLICATION,
MODIFICATION, DISASSEMBLY, ABUSE, MISUSE, IMPROPER INSTALLATION, UNAUTHORIZED REPAIR, IMPROPER MAINTENANCE OR ABNORMAL CONDITIONS OF TEMPERATURE, DIRT OR CORROSIVE MATTER; OR
C) DUE TO OPERATION, EITHER
INTENTIONAL OR OTHERWISE, ABOVE RATED CAPACITIES OR IN AN OTHERWISE IMPROPER MANNER.
THE FOREGOING WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES. THE PARTIES AGREE THAT THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, ARE EXCLUDED FROM THE SALE OF GOODS.
LIMITATION OF REMEDY AND LIABILITY.
THE REMEDY PROVIDED HEREIN IS BUYER'S SOLE AND EXCLUSIVE REMEDY. THE BUYER'S REMEDY
AND THE COMPANY'S LIABILITY (WHETHER UNDER THE THEORIES OF BREACH OF WARRANTY, CONTRACT, TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR ANY OTHER LEGAL THEORY) SHALL BE LIMITED EXCLUSIVELY AT THE COMPANY'S OPTION TO REPLACING OR REPAIRING WITHOUT CHARGE AT THE COMPANY'S FACTORY OR ELSEWHERE ANY MATERIAL OR WORKMANSHIP DEFECTS WHICH BECOME APPARENT WITHIN ONE YEAR FROM THE DATE ON WHICH THE GOODS WERE SHIPPED. THE
COMPANY SHALL NOT BE LIABLE FOR SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING BUT NOT LIMITED TO DAMAGES FOR LOSS OF USE, INCOME OR PROFIT, OR LOSSES SUSTAINED AS A RESULT OF INJURY (INCLUDING DEATH) TO ANY PERSON OR DAMAGES TO PROPERTY. THE COMPANY SHALL HAVE NO LIABILITY FOR DAMAGES OF ANY KIND ARISING FROM THE INSTALLATION AND/OR USE OF THE GOODS BY ANYONE. BY THE ACCEPTANCE OF THE GOODS, THE BUYER SHALL ASSUME ALL LIABILITY FOR ANY DAMAGES WHICH MAY RESULT FROM USE OR MISUSE BY THE BUYER, ITS EMPLOYEES OR BY OTHERS.
INSTRUCTION NUMBER: AO-70136 BA 9of 9
Loading...