You have purchased the finest Steam Cooking Equipment
made. The following information we know will increase the
productivity and life span of the equipment.
Every product needs proper installation and with a
steamer it is critical. The following is some important
information you should check on before and during
installation of the equipment.
Water
The quality of water you put into the steam generator is
important. Poor quality water will create generator problems.
Water is no longer just plain and simple water has many
natural ingredients in it. These are called Total Dissolved
Solids, or TDS. This includes calcium, iron, and other
minerals in the water that collect in the steam generator
Because of the droughts in many areas, water and TDS's
are being pumped up from the bottom of the water
systems. If these TDS are not pre-filtered out or cleaned
out with a regular preventive maintenance program, your
steam generator could deteriorate and develop holes.
CHLORIDE is another chemical in our water creating
many problems with all steam generators. When the generator creates steam from the water it also carries the
chloride gas with it. These chlorides begin to eat away the
inside of the generator and follow the steam into the
compartments causing a rusting action (oxidation) as it
goes along.
A CARBON OR CHARCOAL FILTER must be installed on
the incoming water line to the steamer if the chlorine is
over 30 parts per million. These filters will remove the
chloride.
Figure 1. Drain Connections
If the drain line is not large enough, not open at the end, or
does not have a gravity flow; pressure and hot water will
back up into the compartments. If any of these conditions
exist and hot water does back up into the compartment
someone could be seriously burned and injured. This can
happen even with a correct installation if a drain cleaner is
not used on a regular basis.
An open and free flowing drain line IS REQUIRED for the
proper cooking performance of a CONVECTION
STEAMER. It helps create a swirling action around the
products being cooked. This movement of hot steam
around the product is your CONVECTION STEAM
COOKING.
The WATER QUALITY REQUIREMENTS for your
STEAMER are as follows:
Total Dissolved Solids less than 60 parts per million
Total Alkalinityless than 20 parts per million
Silica less than 13 parts per million
Chlorideless than 30 parts per million
pH Factorgreater than 7.5
Drain Line Connection
A proper drain line connection is important. If the drain line
is clogged it can create a back up of pressure causing
extreme and costly repairs.
DO NOT INSTALL UNIT OVER A FLOOR DRAIN. If it
becomes an absolute must, using an 18.' stainless steel or
aluminum pan turn it over and cut a notch in the side wall
to fit over the drain line. Place the pan directly over the
drain opening- DO NOT SEAL TO THE FLOOR. The
steam from the drain line will collect on the under side and
condense into the drain opening.
DO NOT INSTALL GAS UNITS ON
FLAMMABLEFLOORS OR NEAR WALLS. A flammable
floor or wall is any material such as wood, linoleum, or
vinyl that is easily ignitable and bums rapidly.
The intent of these instructions is to provide meaningful
information, which will help you obtain many years of
production. Before installing the steamer, please read
those instructions carefully to maintain your safety and
warranty
Qualified installation personnel, working to all applicable
local and national codes must accomplish installation of
this equipment. Improper installation of this product could
cause or damage.
Do not store or use gasoline or other flammable Vapors
and liquids in the vicinity of this or any other appliance.
The flooring that will be directly under the boiler must also
be made of a noncombustible material.
Cleveland Range equipment is designed and built to comply with applicable standards for manufacturers. Included
among those certification agencies which have approved
the safety of the equipment design and construction:
UL, A.G.A., NSF ASME, CSA, CGA, and others.
Cleveland Range equipment is designed and certified for
safe operation only when permanently installed in accordance with local and I or national codes. Many local codes
exist and it is the responsibility of the owner and installer
to comply with these codes
In no event shall Cleveland Range assume any liability for
consequential damage or injury resulting from installations
which is not in strict compliance with our installation
instructions. Specifically, Cleveland Range will not assume
any liability for damage resulting from improper installation
of equipment including, but not limited to, temporary or
mobile installations
INSTALLATION INSTRUCTIONS
1. These instructions must be retained by the owner/user
for future reference. Gas-fired boilers are only to be installed in noncombustible areas that have provisions for
adequate air supply. The term "boiler’
onymously with "steam generator".
2. Position: For proper operation and drainage, the equipment must be level. It should be placed next to an open
floor drain. DO NOT POSITION THE UNIT DIRECTLY
ABOVE WE FLOOR DRAIN. Observe all clearance requirements to provide air supply for proper operation, as
well as sufficient clearance for servicing. The
surrounding area must be free and clear of
combustibles. Dimensions and clearance specifications
are shown on the specification sheet.
3. Install in accordance with local codes and/or the National Electric Code ANSI/NFPA No.70-1987.
Installation in Canada must be in accordance with
Canadian Electrical Code CSA Standard C22.1. The
installer A wiring diagram is provided inside the
base cabinet must ground equipment that is
connected to electricity.
s
will be used syn-
WARNING
INJURY TO PERSONNEL AND EQUIPMENT DAMAGE
May result from an improper drain connection. No
connection lines are to be under the unit
4. Drain Line. The drain line outlet discharges exhaust
steam and hot condensate. Connect 1-1/2-inch IPS
piping (or larger) to extend the drain line to a nearby
open floor drain. Up to two elbows and six feet of 11/2-inch IFS (or larger) extension pipe should be
connected to the drain termination. No more than two
pieces of Cleveland Range Equipment should be
connected to one common drain line. The extension
piping must have a gravity flow and vent freely to the
air. This drain outlet must be free-vented to avoid the
creation of backpressure in the steamer cooking
compartments. To ensure a vented drain line, DO NOT
UNDER ANY CIRCUMSTANCES, CONNECT THE
DRAIN OUTLET DIRECTLY TO THE FLOOR DRAIN
OR SEWER LINE. Do not run the drain line discharge
into PVC drain piping or any other drain piping material
not capable of sustaining 180' F operation.
5. Water Supply. Connect COLD water plumbing to the
line strainer (Never conned hot water to the
condensate water fill line strainer) Constant flow
pressure must be maintained between 35 and 60 psi,
and not experience a pressure drop below 35 psi when
other appliances are used. If the water pressure
exceeds 60 psi, a pressure-reducing valve must be
installed in the water supply plumbing to reduce the
water pressure to less than 60 psi. Locations and
pressure data are shown on the specification sheet.
3/S-inch IPS plumbing is sufficient for water supply
lines up to 20 feet in length, but water supply lines
longer than 20 feet should be at least 1/2-inch IPS.
Flush water supply lines thoroughly before connecting
them to the unit. Use water, which is low in total
dissolved solids content and low in gas content to
prevent internal scaling, pitting and corrosion of the
steam generator, and carry-over of minerals into the
steam. Water, which is fit to drink, can still contain
highly detrimental impurities.
NOTE: If equipped with a kettle and kettle water fill
swing
spout, 3/8-inch (10 mm) hot and/or coldwater connection(s) will be required at the
swing spout valve.
6. Turn on the cold water supply to the unit Ensure that the
manual water valve, inside the base cabinet is open.
7. Fuel Supply. Connect the primary fuel supply in accor-
dance with the following instructions.
data are shown on the specification sheet.
For Gas-Fired Steam Generators: Post in a prominent
location, instructions to be followed in the event the user
smells gas. This information shall be obtained by the
consulting the local gas supplier.
Install a sediment trap (drip leg) in the gas supply line, and
then connect gas supply piping to the boiler gas valve
piping. GAS-FIRED EQUIPMENT IS DESIGNED FOR
INSTALLATION ONLY IN NONCOMBUSJJBLE
LOCATIONS. THIS INCLUDES THE FLOOR-INC THAT
WILL BE DIRECTLY UNDER THE EQUIPMENT Location,
plumbing size, and pressure data are shown on the
specification sheet. Boilers rated at less than 225,000 Btu
require 3/4-inch 'PS gas supply piping, and boilers rated at
225,000 Btu or more require 1-inch II'S gas supply piping.
Natural gas pressure must be between 4" -14" water
column and LP gas supply pressure must be between 12"
- 14" water column. NEVER EXCEED 14" WATER
COLUMN (1/2 psi) GAS PRESSURE. If the gas supply
pressure exceeds 14" water column, a pressure-regulating
valve must be installed in the gas plumbing to reduce the
gas pressure to less than 14" water column. Installation
must be in accordance with local codes, or in the absence
of local codes, with the National Fuel Gas Code, ANSI
Z223.1-1984. Installation in Canada must be in accordance with Installation codes for Gas Burning Appliances and Equipment B149.1 and B149.2. Use a gas pipe
joint compound, which is resistant to LP gas. Turn the gas
valve control knob to ON (the word "on" the knob will be
opposite the index on the valve's body). Test all pipe joints
for leaks with soap and water solutions. Never obstruct the
flow of combustion and ventilation air Observe all
clearance requirements to provide adequate air openings
into the combustion chamber. The appliance and it's individual shutoff valve must be disconnected from the gas
supply piping system during any pressure testing of that
system at test pressures in excess of 14" water column
(1/2 psi or 3.45 k}'a). The appliance must be isolated from
the gas supply piping system at test pressures equal to or
less than 14" water column (1/2 psi or 3.45 kpa). A permanent 115-volt electrical connection is required at the junction box. The junction box location is shown on the specification sheet. The installer must electrically ground the
unit.
and pressure data are shown on the specification sheet.
Incoming steam pressure must be regulated between 35
and 45 psi. A 3 /4inch strainer, equipped with a 20 mesh
stainless steel screen, must be supplied and installed at
the incoming steam connection
thoroughly before connecting it to the boiler. To ensure an
adequate volume of steam, the branch steam supply line
must be 3/~inch 'PS minimum. Connect the inverted
bucket trap to the outlet end of the steam coil. Pill the trap
with water before installing it. A permanent 115-volt
electrical connection is required at the junction box. The
junction box location is shown on the specification sheet.
The installer must electrically ground the unit.
For Direct-Steam Connected Steamers and Kettles:
Connect steam supply piping to the input side of the line
strainer. Location and pressure data are shown on the
specification sheet. Flush the steam line thoroughly before
connecting it to the steamer. To ensure an adequate
volume of steam, the branch steam supply line must be
3/4 inch 'PSI 'minimum. Direct-steam-connected kettles
require 1 /2-inch 'PS pipe if the kettle total capacity is 20
gallons or less, and 3/4-inch 'PS pipe if the total capacity
exceeds 20 gallons.) A permanent 115 volt electrical
connection is required at the junction box. The junction
box location is shown on the specification sheet. The
installer must electrically ground the unit
point. Flush the steam line
INSTALLATION CHECKS
Proper operation of the Cleveland Convection Steamer is
dependent upon proper installation. After the steamer has
been installed, a few quick checks could save
unnecessary service calls.
1. The unit must be level.
2. The Convection Steamer requires a cold water connection for proper efficient operation. DO NOT USE HOT
WATER. The cold water must be connected to the line
strainer, located at the front lower right of the steamer
base.
For Electric-Powered Steam Generators: Connect
electric power: location and data are shown on the
specification sheet. Provide connection as required by the
unit, either directly to the single contactor, or to the
terminal block (when equipped with multiple contactors).
Electric supply must match power requirements specified
on the data plate inside the base cabinet. The copper
wiring size must be adequate to carry the required current
at the rated voltage. A separate fused disconnect switch
must be supplied and installed. The installer must
electrically ground the unit
For Steam Coil Steam Generators: Connect steam
supply piping to the input side of the steam coil. Location
3. Check that the manual water supply valve is open.
4. Check all water supply lines and valves for leaks.
5. Check that the water supply pressure and water quality
meets the requirements of installation paragraphs.
6. On electrical units, verify that the supply voltage meets
the voltage requirements on the rating plate inside the
base cabinet and the voltage shown on the packing
slip. Verify that the unit is protected with a separate
fused disconnect and is properly grounded in
accordance with the National Electric Code.
7. On all gas, steam-coil, and direct steam connected
units, verify that there is a 115-Volt connection at the
handy-box located on the left side of the base.
8. On all steamcoil units, the incoming steam pressure
must be 35-50 psi. Less than 35 will not effectively
operate the unit. Pressure in excess of 50 psi must be
reduced (with a pressure-reducing valve) to 35-50 psi.
9. Check that the drain lines meet installation
requirements specified in installation paragraph 4
WARNING
INJURY TP PERSONNEL AND EQUIPMENT DAMAGE
may result from an improper installation.
10. After completing checks 1 through 9, correct any
deficiencies refer to the Start-Up and Pre heat
instructions in the Operation section. Verify that the
unit operates properly, make checks 11 and 12.
11.Check to ensure that the water in the boiler sight gauge
glass automatically stays about 1/3 full when boiler is
started up and operated.
12.Check to ensure that the steam pressure gauge
registers 10 psi. The steam pressure is factoryadjusted to 10 psi
Factory setting may shift due to shaking in transit and
resetting will be required after installation. Proper adjustments and maintenance procedures am detailed on a
separate data sheet entitled "Steam Pressure Adjustments." Adjustments should be made only by qualified
service personnel- the factory pressure settings shown in
the accompanying chart should never be exceeded.
GAUGE PRESSURE READING WITH
NO STEAM FLOW* (STATIC PRESSURE)
Self-Contained Steam Generator; Gas or Electric
Operating Pressure Switch10 psi
High Limit Safety Pressure Switch15 psi
Operation of the Cleveland Range Convection Steamer is
very easy. Each operator should read and understand the
following procedures to effectively start, operate, and shut
down the steamer each day. The owner(s) and operator(s)
of this equipment should be aware that live steam could
cause serious injuries, pay particular attention to the
WARNINGS in this text. These instructions are to be
retained by the owner(s)) and operator(s) for future
reference.
CONTROLS AND CONTROL PANELS
There are two steam generator control arrangements and
two steamer compartment control panels available for
Cleveland Range Convection Steamers. The steam
generator controls are illustrated in Figure 2. The steamer
compartment control panels are illustrated in Figures 3
and 4. Compare these figures with the equipment
supplied, and identify which control panel combinations
applies.
Steam Generator Controls
The steam generator controls are located on the front face
of the steamer base unit. The switches are to the left of
the pressure gage, as illustrated in Figure 2 Most
Cleveland Range Convection Steamers have a steam
generator built into the base unit which supplies steam to
the cooking compartments. However, an external steam
supply may also be used. Units with a built-in boiler have
both the POWER rocker switch and the STEAM
momentary switch next to the pressure gage. Units with no
internal generator have the POWER rocker switch only.
They do not have the STEAM momentary switch.
Installation, Use and Care Instructions Convection
Steamer
Convection
Figure 3. Key Pad Figure 4. Dial Timer
Control PanelControl Panel
Steamer Compartment Control Panels
Figure 3 illustrates the standard electronic controls: the
Key Pad Control Panel. This panel has a rocker switch, a
keypad, and a digital timer Figure 4 illustrates the optional
electromechanical controls: the Dial Timer Control Panel.
This panel has a rocker switch and dial timer. Steamer
functions are the same for both the standard and optional
panel configurations. Operating details are slightly
different especially when setting the automatic operating
time. For clarity two sets of instructions are provided for
cooking operations.
Figure 2. Steam Generator Controls
START-UP AND PREHEAT
WARNING
Do not attempt to start or operate the Convection
Steamers during a power failure. Critical safety
Circuits are not energized, and serious injury to personnel
or damage to equipment may result.
1. Stan the steam supplies. The steam is either an integral
steam generator boiler) built into the base unit, or an
external steam supply.
• For units without a built-in boiler, refer to the start-up
procedures for the external steam supply and be sure it
is running properly. As soon as the pressure gauge