Cleveland SD-1200-K612 Installation Manual

SE95008 Rev. 6
Operators Manual
Table-Top Direct
Steam Kettles
MODELS: KDT- 1- T
KDT- 3- T KDT- 6- T KDT-12- T KDT-20- T
SD Stands
MODELS: SD- 450
SD- 650 SD- 760 SD-1050 SD-1200 SD-1600 SD-1800
Kettles on SD Stands
MODELS: SD-450 - K 6
SD-650 - K12 SD-760 - K12 SD-760 - K20 SD-1050- K 6 6 SD-1200- K 6 12 SD-1600- K 6 20 SD-1600- K 12 12 SD-1600- K 12 20 SD-1600- K 20 20
1333 East 179th St., Cleveland, Ohio, U.S.A. 44110
Phone: (216) 481-4900 Fax: (216) 481-3782 Visit our web site at www.clevelandrange.com
d
Enodis
For a complete Service Manual refer to www.clevelandrange.com
Direct Steam Table Top Kettles
Installation & Operation
Clev elan
For your safety
DANGER
Keep clear of pressure relief discharge.
IMPORTANT
Inspect unit daily for proper operation.
CAUTION
Surfaces may be extremely hot! Use protective equipment.
Keep hands away from moving parts and pinch points.
Do not fill kettle above recommended level marked on outside of kettle.
Wear protective equipment when discharging hot product.
Do not lean on or place objects on kettle lip.
SERVICING
Shut off power at main fuse disconnect prior to servicing.
GAS APPLIANCES
Do not attempt to operate this appliance during a power failure.
Stand clear of product discharge path when discharging hot product.
Ensure kettle is at room
0
temperature and pressure gauge is showing zero or less prior to removing any fittings.
Keep appliance and area free and clear of combustibles.
GENERAL
Installation of the unit must be accomplished by qualified installation personnel working to all applicable local and national codes. Improper installation of product could cause injury or damage.
This unit is built to comply with applicable standards for manufacturers. Included among those approval agencies are: UL, NSF, ASME/Ntl.Bd., CSA, ETL, CE, and others. Many local codes exist, and it is the responsibility of the owner/installer to comply with these codes.
INSPECTION
Before uncrating, visually inspect the unit for evidence of damage during shipping. If damage is noticed, do not unpack the unit, follow shipping damage instructions.
SHIPPING DAMAGE INSTRUCTIONS
If shipping damage to the unit is discovered or suspected, observe the following guidelines in preparing a shipping damage claim.
1. Write down a description of the damage or the reason for suspecting damage as soon as it is discovered. This will help in filling out the claim forms later. If possible, take a polaroid picture.
2. As soon as damage is discovered or suspected, notify the carrier that delivered the shipment.
3. Arrange for the carrier's representative to examine the damage.
4. Fill out all carrier claims forms and have the examining carrier sign and date each form.
CLEARANCE REQUIREMENTS
The first installation step is to refer to the SPECIFICATION DRAWINGS at the back of this manual in order to determine the exact location of the kettle.
CLEARANCE REQUIREMENTS TO COMBUSTIBLE AND NONCOMBUSTIBLE SURFACES:
RIGHT LEFT BACK
KDT-1-T 4" 0" 0" KDT-3-T & KDT-6-T 4" 4" 1" KDT-12-T & KDT-20-T 4" 4" 1.75"
Note: For SD Stands (with or without kettles) zero clearance is required on the sides and back.
KETTLES
Table-top models must be positioned on a firm stand or existing counter top and secured in place. An optional modular cabinet base (SD Stand), with level-adjustable legs is available .
1. Make two 1" holes for the kettle legs.
2. Remove the leg mounting locknuts and washers from the kettle's legs.
3. Install the legs into the two 1" holes.
4. Position washers as illustrated and secure the kettle to its' base by refastening the locknut from underneath the cabinet or countertop.
5. Once the kettle is secure, screw the tilt handle into the mounting block welded to the side of the kettle.
6. Install service requirements as required.
KETTLES c/w SD STAND
1. Place unit in desired location.
2. Place a carpenter's level on the kettle rim and
level the stand using the level adjustable feet.
3. Install service requirements as required.
INSTALLATION
A
KDT-1-T 8 1/8" KDT-3-T 10" KDT-6-T 12" KDT-12-T 19 1/2" KDT-20-T 23 3/4"
DRILL TWO
1" HOLES
A
COUNTERTOP
STEAM
All steam plumbing to and from the kettle and steam boiler should be thoroughly cleaned and inspected for dirt and debris before final connection to the kettle are made.
Generally, kettles require 1/2" i.p.s. pipe, 10-45 psi steam pressure. If the steam supply pressure exceeds 45 psi, a pressure reducing valve is required. The steam inlet is at the right side of the kettle, as n from the front.
A pressure reducing valve is required on the incoming line as shown below. The relief valve should have a capacity of 300 lb/hr (136 kg/hr).
CONDENSATE (Kettles without SD Stands)
Maximum pressure rating on table-top kettles is 50psi. It is highly recommended that a pressure relief valve equal to or less than this pressure be installed on the incoming steam line close to the kettle.
A steam condensate trap must be plumbed to a drain, using minimum 1/2" NPT plumbing. The condensate line is limited to a maximum rise of 10 feet in order for the steam pressure to adequately force the condensate through the plumbing. Any higher rise requires a pump.
If the steam boiler to which this kettle is installed has a condensate return (closed loop system), a 1/2" steam strainer, a 1/2" steam trap, and a 1/2" check valve must be installed on the output (condensate) side of the kettle.
CONDENSATE (Kettles c/w SD Stands)
The stand comes factory plumbed so the condensate is connected to the stands drain manifold.
POTABLE WATER
The water faucet (optional on kettles purchased without SD stands) with swing spout, requires 1/2 inch O.D. copper tube plumbing for hot or cold water supplies to the faucet (SPK - cold water connection only, DPK - hot and cold water connection).
FINAL INSTALLATION CHECK
1. Partially fill the kettle with water.
2. Slowly turn the steam supply valve's knob to
the open position.
3. Release the safety valve, ensuring that the steam escapes freely. Stay clear of steam exhaust when releasing the safety valve.
4.
Observe that the water in the kettle comes to a boil.
5. Close the steam supply valve.
6. Drain off the water by tilting the kettle.
KETTLES
RECOMMENDED PIPING SCHEMATICS
(all service connections shown supplied by others)
KETTLES c/w SD STANDS
TO DRAIN OR BOILER
CONDENSATE LINE
RELIEF VALVE
STRAINER
TO DRAIN (CONDENSATE RETURN PLUMBED TO 1 1/2" DRAIN MANIFOLD)
CONDENSATE RETURN
UNION
CHECK
PRESSURE REDUCING
VALVE
UNION
VALVE
STEAM
TRAP
SHUT OFF
VALVE
STRAINER
STEAM
MANUAL STEAM VALVE
STRAINER
RELIEF VALVE
IN
PRESSURE REDUCING
VALVE
UNION
STEAM
SHUT OFF
VALVE
IN
Loading...
+ 7 hidden pages