1) These instructions must be retained By the owner / user tor future referenca. Forinstallation only in noncombustible
locations. Gas units am only to be installed in areas that have provisions tor adequate air supply
2) Position: For proper operation and drainage, steam generator must be level. It must be set near a floor drain. Attach
1 1/2" piping to an drain connections to carry exhaust steam away from the cabinet. Ends of drain lines must vent to
atmosphere to avoid back pressure. Allow a MINIMUM of 6" clearance to the rear and sides of the equipment. The
surrounding area must be free and clear of combustibles.
3) install in accordance with local codes and/or the National Electric Code ANSI/NFPA No. 70-1984. installation in
Canada shall be in accordance with the Canadian Electric Code CSA Standard C22-1. A unit mat a connected to
electricity must be grounded. A wiring diagram is provided inside the relay box.
4) Connect supply lines for 140— 160° hot water, and cold water, to the unit. Water pressure must Be maintained
between 35 and 60 PSI.Locations and pressure data are shown on the connection drawing. Long hot water lines
should beat least 1/2" IPS. Rush water supply lines thoroughly before connecting. Use water which is low in total
solids content and low in gas content. to prevent internal scaling, pitting and corrosion of the steam generator and
carry-over of minerals into the steam. Water which is fit to drink can still contain highly detrimental impurities. Refer
Water Quality Requirements page.
5) Turn on water supply to steam generator. Water valve is inside of base.
6) Connect fuel supply
Do not store or use gasoline or other flammable vapors and liquids in the
FOR YOUR SA FETY
vicinity of this or any other appliance.
For Steam Coil Steam Generators —
— Connect steam supply Location is shown on the connection drawing. Incoming steam pressure must be
regulated between 35 and 45 pa (30 —45 psi for pressure steamers), Install a strainer ahead of the regulating valve.
Flush line thoroughly before connecting.
— Connect the outlet end of the steam coil to an inverted bucket trap. Fill trap with water before installing.
— Connect electricity if unit is equipped with electrical controls. Permanent 115V connection is required. Junction
box location is shown on the connection drawing. Unit must be electrically grounded by the installer. For
Gas Fired Generators-
— Post in a prominent location, instructions to be followed in the event the user smells gas This information
shall be obtained by consulting the local gas supplier.
— Connect gas: Location and pressure data are shown on the connection drawing, installation snail be in
accordance with local codes, or in me absence of local codes, with the National Fuel Gas Code ANSI Z223-1 —1984
Installation in Canada shall be in accordance with Installation Codes tor Gas Burning Appliances and Equipment B149.1
and B149.2 Use a gas pipe joint compound which is resistant to LP gas. Test all pipe joints for leaks with soap and water
solution. Allow 12 inch clearance on right side of all Gas Fired Steam Generator models for servicing gas burners and tor
proper operation. 12" clearance also provides adequate air openings into me combustion chamber. Never obstruct the
flow of combustion and ventilation air. The appliance and its individual shutoff valve must be disconnected from the gas
supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 kPa). The
appliance must be isolated from the gas supply piping systern by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressure equal to or less than % psig (3.45 kPa).
— Connect electricity if unit is equipped with electrical controls. Permanent 115V connection a required.
Junction box location is shown on the connection drawing. Unit must be electrically grounded by the installer.
— Lighting and Shutdown Instructions: Rip electrical switch on Open water valve. Open gas valve. Slightly depress
and turn control knob to "off" for 5 minutes before lighting gas. Turn control knob to "pilot" depress it completety and light
pilot burner. Continue to hold knob in tor about 60 seconds, then release. Pilot burner a lighted through hole in panel at
bottom of steam generator. Never leave panel off. as this will damage controls. Turn control knob to "on". Depress
electrical "reset" switch tor main burner ignition. Burners will not light without water in the steam generator. For main
burner off. with pilot on, turn control knob to "pilot"- For main and pilot burner oft slightly depress and turn control knob to
"off" Flip electrical switch off. For Electrical Steam Generators
— Connect electric power Location is shown on the connection drawing. Provide connection as required by your unit
Electric supply must match power requirements specified on data plate attached to base. Wiring must be adequate to
carry required current at rated voltage. A separate fused disconnect must be supplied and instailed. Unit must be
electrically grounded by the installer.
CLEVELAND RANGE C0_ 1333 EAST 179th ST., CLEVELAND, OHIO 44110 LITHO IN U-S-A-
Manufacturer reserves right of design improvement or modification, as warranted.
Page 3
7) Turn on electricity at control circuit switch on steamer console A red light glows when electricity is on. If water level is correct
steam generator will operate by pressing me "reset" button. Heaters will not work without water in the steam generator This
manual reset button must be pressed to start up the generator initially, and to restart the steam generator after every shut oft. or
power interruption. No attempt should be made to operate the equipment during a power failure.
8) Check 10 make sure that me water in the sight gauge glass automatically stays at about 2/3 full when the unit is started up.
9) When installation is complete and tree of leaks, refer to Operating Procedures sheet.
Instructions For Steam Generator Care
Protect your steam generator, prolong its life and preserve its performance by giving it the required daily attention, on a regular
schedule. Follow servicing instructions for your steam generator which are printed on Data Sheet 260-LC in your Owner s Manual,
and also or an adhesive label attached to the unit. To obtain an additional data sheet or label carrying servicing instructions, write to
the Cleveland Range Company.
No work should be dorm on the steam generator while it pressurized or hot. Service of the steam generator
should only be performed by a trained and experienced service technician, thoroughly My familiar with servicing
steam generators. When maintenance or repairs are required, contact a located food service equipment service
agency, or call the factory, or a factory representative for the name and address of one in your area.
WARNING
Steam Generator (Boiler) Safety
Rigid regulations govern the design and construction of a boiler. However, the responsibility for the safe and efficient
operation of a boiler shifts to the owner/user after the boiler leaves the factory.
A sound boiler if improperly installed, or if improperly maintained, or if improperly repaired, will create a dangerous situation and
may cause injury to personnel.
Most sates, provinces and some cities nave a boiler safety law. Many underwriters require that their clients' boilers comply with these
boiler safety laws. These safety laws call for action by the boiler manufacturer and action by the boiler owner/user.
As a manufactur er. The Cleveland Range Company delivers steam generators built me ASME Boiler Code. Section IV. which have
been inspected by a National Board Inspector. Also. each Cleveland Range Company boiler is built to comply with the boiler safety
law of the state t o which it is sent
Safe and Effecient Boiler Operation Depends on Proper Installation
Install the boiler in compliance with following regulations, where they apply:
— The National Fuel Gas Code. ANSI Z223.1-1984
—— installation Codes for Gas Burning Appliances and
Equipment B149.1 and B149.2
— The Cleveland Range Company Installation instruc-
tions
— The National Electrical Code ANSI/NFPA No.70-1984
The water for the boiler should be analyzed by a reputable boiler water specialist to see if the quality will permit safe and
efficient boiler operation. Water treatment is becoming increasingly necessary because the quality of water sources is
deteriorating. although treatment will not be required in every case. A boiler will not operate properly for very long if the
water causes boiler corrosion or scale. Even water which 13 safe to drink may be detrimental to a boiler. Refer to Water
quality Requirements page for details.
Safety Requires Periodic Inspection and Maintenance
Any leaks around the boiler's hand note plate must be Quickly stopped. Small leaks, it unchecked, cause corrosion and
pitting on the boiler face around the hand hole gasket, making it unsealable.
Application of undue stress on the parts that are used to seal the boiler's hand hole opening, in an attempt to seal an
unsealable opening, by sledging the handle of the wrench, by increasing the leverage of the wrench a length of pipe. or
by other means, is dangerous because it may result the breakage of parts, or injury. No attempts should be made 10
tighten up the nut on the retaining stud beyond the recommended 15 foot pounds of torque.
When a repair affecting the safety of the boiler is necessary. call a National Board Inspector consultation and advice as to
the best method of making the repair, so that the completed work will get his approval. Repairs to the boiler must conform
to the applicable provisions in the ASME. Code or the National Board Rules for Repairs.
A boiler will last many years before it has to be retired from service. Periodic inspection will reveal the approaching
retirement time. It a better to schedule a convenient replacement time than to wait for the boiler to fail. When a boiler older
man 10 years is replaced, the entire steam generator base assembly should be replaced for a number reasons:
— Replacement parts become increasingly difficult to obtain for older controls.
— Dependable performance of the new controls can be assured for a longer time.
— The new steam generator, including controls, will comply with the latest industry and safety standards.
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHO 44110
— The local and municipal building code (plumbing ana
electrical
— The state and city boiler laws
— The recommendations of the owner/user's under-writers
Page 4
PRESSURE STEAMER OPERATING INSTRUCTIONS
NOTE: These instructions pertain to steamers equipped with self-contained steam generators (boilers).Forr steamers direct-connected to a
remote (in -house) steam source, disregard those instructions which are directly and solely related to the self-contained steam generator. These
instructions are to be retained by the owner/user for future reference.
1A Open the cabinet base door and close the drain valve if it is open.
B Make sure the hot and cold water supply valves are open
C For steamers equipped with a gas-fired steam generator (boiler) follow the lighting instructions noted on the instruction label displayed on
the unit before continuing to instruction in item 2.
2 Flip the t oggle switch on front of the cabinet console to "ON" The red console light should then glow and the boiler will automatically
begin filling with water (if it is not already full).
3 After approximately five minutes (after water appears in the sight gauge), depress the ""START" reset button on the console. This will
energize the electric heater elements or ignite the gas burners. This cannot be accomplished until the boiler is full of water.
4 in approximately 15 minutes you will notice the console's steam pressure gauge register 5 pounds.(10 pounds if the boiler is also supplying
steam to a kettle- Theupper pressure gauge will register 5 pounds.) You can now preheat the cooking compartments.
5 Compartments should be preheated before use and should be kept hot between loads. If a Kettle and steamer are to be used at the same
time, always heat the kettle unit first. When kettle contents begin to simmer, preheat the steamer compartments- When pressure on the
boiler gauge returns to 10 pounds, cooking may begin in the steamer
6 Close and latch door securely. Turn bar handle clockwise until the door gasket just touches the compartment face
7 Start steam supply by pulling steam valve handle out. If fined with automatic timer, set timer for 5 minutes. At the start, compartment
thermostatic traps should release air and wet steam tor about two minutes, then shut off.
8 Seal compartment door by turning bar handle clockwise just until steam leakage stops. DO NOT OVERTIGHTEN.
9 At the completion of the 5 minute preheatin g cycle, push steam valve slowly in, to avoid boilovers. This shuts off the steam supply and also
depressurizes and drains the compartment. If fitted with an automatic timer, the steam shuts off automatically and a bell rings when the
timer reaches zero. Setting the timer to "Off" stops the bell.
10 To open compartment door, turn bar handle counter-clockwise and delatch.
11 Cooking can now begin by following the above operating steps #6 through #10, but setting the timer for the required cooking time- At the
end of a cooking cycle 40 minutes long or longer, or when defrosting frozen foods, wait at least two minutes for the compartments) to
depressurize and drain before opening the compartment door.
CAUTION: After each cooking cycle, ensure that all water is draining, and not accumulating in the
compartment. Should a drain become obstructed, it must be cleared before attempting to cook in that
compartment.
12. At the end of each day's operation, flip the console toggle switch to the "Blowdown" position, open t he door in the cabinet base and open
the boiler drain valve, (red handle). This "Blowdown" drains the boiler and helps to keep it dean. When the boiler is empty, flip the console
toggle switch to the "OFF" position and dose the boiler drain valve
13. It is recommended that the boiler be refilled with water after the "Blowdown" is performed. This can be accomplished by flipping the
toggle switch to the "ON" position for a period of five minutes and then returning the switch to the "OFF" position.
1. Blow down the steam generator daily.
2. A periodic boiler inspection must be performed by a qualified serviceman to prolong its life and to minimize service calls
3. At the end of each day's operation, wash the pan slides, drain screen covers, door gaskets, and compartment interiors with mild detergent
and warm water- Thoroughly rinse with clean water. Rinse water should drain freely through the compartment drain openings. If it does not,
the drain must be cleaned before using the steamer.
4. Once a week. flush each compartment drain with a food service equipment drain cleaner and a deliming solution
5 Once every three months, shut off the water supply (hot and cold), and clean the water line strainers.
6. Compartment thermostatic traps can be disassembled and cleaned, by hand or in a mechanical dishwasher. This procedure is recommended
if the traps act sluggishly, as they may if contaminated by grease or other film. If cleaning fails to restore the trap's proper functioning,
replace the trap. For more detailed thermostatic trap servicing instruc tions., refer to Data Sheet 260-LH.
TO PROLONG LIFE AND MINIMIZE SERVICE REQUIREMENTS
CLEVELAND RANGE. INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
1
Page 5
7. Shelves, drain screens, and pan slides arc stainless steel, and can be washed safely in a mechanical dishwasher.
8. Exterior Care: Allow steamer 10 cool before washing. Use the same cleaners and cleaning procedures as for other kitchen surfaces of stainless
steel and aluminum. Mild soapy water, with a clear water rinse, ;s recommended. DC no: allow water to run into electncal controls- Always
turn off equipment power before using water to wash equipment.
9. Compartment Door Care:a. When doors are closed tor preheating or cooking, turn bar handle just enough to stop steam leakage. Overtightening shortens gasket life.
b. When doors are open or unlatched. Do not turn bar handle.
c Always leave compartment doors ajar when not in use, to extend gasket life and to prevent gaskets from adhering to the steamer.
Unnecessary compression of a gasket shorten its life.
d Keep bar handle screws clean. Lubricate frequently but not excessively.
e. Door gaskets provide many months of service when care is taken to operate doors properly. When a gasket finally wears and does not
maintain an effective seal, it must be replaced. Door gaskets can be replaced easily without special tools or cement, and the steamer may
be used immediately afterwards- Remove the old gasket and dean the channel. being careful not to damage the channel. The new gasket
can then be pressed into place. Insert the gasket in thecorners of the channel first, adjusting the slack evenly between the comers - Then
work from the comers to the center. Ridges hold the gasket firmly. The gasket is designed to be oversize, so once it is compressed into the
door's channel, it remains firmly in place.
PRESSURESTEAMER SAFETY
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
Being the owner of a steamer carries with it the responsibility for Keeping it in as safe a condition as when it was shipped from
the factory. Safe steamer operation dictates that every pressure steamer must have the following safety inspection at least every
12 months.
1. Steam Valve Linkages
Have a qualified serviceman examine the steam valve linkages which are attached to the inlet and exhaust valves' operating
handles on the left side of the steamer. This pivoted linkage, which is attached to both the steam inlet valve and the steam
exhaust valve, must prevent the door's latch from disengaging from its catch when the steamer compartment is pressurized. It
is important that the linkage operates as described so that the steamer door cannot be opened when the compartment is
pressurized.
It is also important that when the steam valve is closed, the exhaust valve should open. The proper operation of the steam inlet
valve and the steam exhaust valve should be confirmed and observed while the steam is on.
2. Pressure Gauge Check each pressure gauge. Gauge pointer must return to zero when the steam generator is shut down. Look
for signs of water, rust, corrosion, or scale, inside the pressure gauge. A faulty pressure gauge should be replaced
immediately.
a Door Gaskets
Inspect and replace compartment door gaskets once a year, or sooner if they are torn or hardened. The use of a hardened gasket
produces undue stress in the parts which comprise the door enclosure and may result in breakage and injury.
4. Compartment Thermostatic Trap
Observe compartment thermostatic traps for proper operation. A good compartment trap, at start-up of a cooking cycle, is
normally open and releases air and wet steam briskly for a few minutes. then holds steam within compartment. If brisk venting
doesn't begin immediately at start-up, or if brisk venting continues without stopping, and the compartment trap is over a year
old, it should be cleaned, or a new one installed- Refer to data sheet 260-LH for details
5 Compartment Steam Exhaust Valves and Drain Valves
Make sure that the compartment steam exhaust valves, and the drain lines attached to them, are free of food buildup internally
and are venting freely to the atmosphere. If drain lines from other steam-consuming equipment have been connected to the
drain line from the steamer, the other drain lines should be disconnected. Never operate a compartment without the drain
screen cover in place.
6. Refer to separate data sheets for steam generator operation, maintenance, and safety procedures.
WARNING
Service of steam cooking equipment should only be performed by a trained and experienced service technician,
thoroughly familiar with servicing steam equipment. No work should be performed on the steamer while it is
pressurized or hot. Be sure all energy sources are shut off before the start of any work. When maintenance or repairs
are required, contact a local food service equipment service agency, or call the factory. or a factory representative, for
the name and address of one in your area.
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
2
Page 6
PRESSURE STEAMERS: THERMOSTATIC TRAP AND
COMPARTMENT DOOR GASKET REPLACEMENT
The thermostatic trap and door gasket on your steamer stop the escape of steam from the compartment during operation. Steam leakage from
either source will cause loss of pressure. which will result in longer cooking time. wasted Steam and
excessive condensation.
To keep your steamer operating at peak efficiency. thermostatic traps and compartment door gaskets require periodic replacement Frequency
of replacement vanes from one piece of equipment to another depending on the amount of usage, and frequency and quality of maintenance.
A normal thermostatic trap at Startup releases air and wet steam briskly for the first few minutes, then holds steam within the compartment.
During cooking, the trap will also release accumulated condensate ana a small amount of air
It brisk venting doesn't begin immediately at startup or if brisk venting continues for much longer than two minutes. and the compartment
trap is over a year old, it should be cleaned, or removed and a new one installed.
A compartment trap less than a year old mayact sluggishly only because it is contaminated by grease and otherfilm.
To remove a thermostatic trap. unscrew the union nut
as shown on the sketch.
To clean the trap. unscrew the threaded! diaphragm cover from
the body and wash the entire assembly. A more thorough cleaning
can be accomplished by removing and disassembling the trap. and
washing the entire assembly in a mechanical dish washer.
With proper tools, the threaded diaphragm cover can be unscrewed
from the body. and the thermostatic diaphragm can be unscrewed
from the diaphragm cover, if the trap does not work property after
thorough cleaning. install a new one.
If the steamer is used heavily for cooking foods contain ing large
amounts of fat or starch. periodic cleaning is recommended as a routine procedure
Replace the gaskets on compartment doors once a year. or sooner if they are torn or hardened.
Door gaskets can be replaced easily without special tools or cement, and the steamer may be used immediately afterwards.
Remove the old gasket and clean the channel, being careful not to damage the channel. The new gasket can then be pressed into place.
insert the gasket in the corners of the channel first, adjusting the slack evenly between the comers. Then work from the comers to the center.
Ridges hold the gasket firmly. The gasket is designed to be oversize, so once it is compressed into the door's channel, it remains firmly in
place.
COMPARTMENTTHERMOSTATIC TRAP
COMPARTMENT DOOR GASKET REPLACEMENT
WARNING
Service of steam cooking equipment should only be performed by a trained and experienced service technician,
thoroughly familiar with servicing steam equipment, No work should be performed on the steamer while it is
pressurized or hot, Be sure all energy sources are shut off before the start of any work. When maintenance or
repairs are required, contact a local food service equipment service agency, or call the factory, or a factory
representative, for the name and address of one in your area.
CLEVELAND RANGE CO.. 1333 EAST 179th ST, CLEVELAND, OHIO 44110
Page 7
MODELS B,C, F, K PRESSURE STEAMERS DOOR
1 25303
Door Ann With Bushings
— Model B
&
C, Polished
25304
Door Arm With Bushings
— Model F
&
K. Polished
2
02568
Door Arm Hinge Bushing
(2
Req
uired) 3 41370
Standard Door Ann Screw With Ball
(1" x 8
thread)
41371
Oversize Door Ann Screw With Ball 1 3/32" x
8
thread)
4
081001
Screw Handle Bar, Polished
5
16305
Pin 6 15250
Oil Cup
7
122011
Door Ann Latch
— Model B, C.
&
F Chrome Plated
122021
Door Ann Latch
— Model K Chrome Plated
8
101018
Door Arm Latch Pin
— Model B, C, F,
&
K Brass
163101
Door Ann Latch Pin
— Model B, C, F,
&
K Chrome Plated
9
081031
Door Retainer
— Model B, C, F,
&
K Chrome Plated
10
19291
Screw
11
041631
Door
, Model B Polished
04164
Door, Model C Polished
04165
Door, Model F
&
K Polished
12
07132
Door Gasket
— Rubber, Model B
07134
Door Gasket
— Rubber, Model C, F, K
13
023001
Door Arm Hinge Post Bolt (Upper)
— Concentric Type
— 14
023061
Door Arm
Hinge Post Bolt (Lower)
— Eccentric Type
— 15
14643
Nut, For Lower Hinge Post Bolt
16
23181
Shim Washer
17
40547
60 Minute Bell Timer Assembly
18
08601
Timer Housing
— Model B
&
C Polished (Not Available)
08606
Timer Housing
— Model F Polished (Not
Available)
AND DOOR ARM ASSEMBLY
REFERENCE
NUMBER
PART NUMBER DESCRIPTION
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 8
MODEL J DOOR AND DOOR ARM ASSEMBLY
1 253021
Door Arm W/Bushings, Polished
2 02568
Door Arm Hinge Bushing
(2
Required)
3
41370
Standard Door Arm Screw With Ball
(1" x 8
thread)
41371
Oversize Door Arm Screw W
ith Ball (1 3/32'' x
8
thread)
4
081001
Screw Handle Bar, Polished
5
16305
Pin 6 15250
Oil Cup
7
41360
Striker Plate and Pin
8
43723
Door Hanger w/Screws and Washers
(2
Required)
9
53035
Door Arm Insert, Stainless
10
04162
Polished Aluminum Door, Le
ss Gasket
11
07136
Door Gasket
— Rubber
12
68140
Retainer, Yoke Hanger
(2
Required)
13
19228
Screw
14
23182
Washer
15
122001
Door Arm Latch, Chrome Plated
16
163141
Door Arm Latch Pin, Chrome Plated
17
18306
Retainer Clip,
(2
Required)
18
023001
Door Arm Hinge Post Bolt (Upper)
— Concentric Type
— 19
023061
Door Arm Hinge Post Bolt (Lower)
— Eccentric Type
— 20
14643
Nut, For Lower Hinge Post Bolt
21
23181
Shim Washers
REFERENCE
NUMBER
PART NUMBER DESCRIPTION
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 9
MECHANICAL COMPARTMENT CONTROLS
MODEL K PRESSURE STEAMERS-
DEC. 1977 THRU PRESENT
Page 10
MECHANICAL COMPARTMENT CONTROLS MODEL K PRESSURE
STEAMERS-DEC. 1977 THRU PRESENT
REFERENCEPART
NUMBER NUMBERDESCRIPTION
1 40650Pull Rod Handle
2 22130Valve, Safely, 8 psi
3 70411Tee, Special3/4"
4 22140Air Vent
5 42270Inlet Manifold Ass'y.—2-Compl.—Mech. "K", Less Valves
42279Inlet Manifold Ass'y.—3-Compl.—Mech. "K", Less Valves
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 14
AUTO SHELF ASSEMBLY MODELS B & F
1 41445
Angle Slide Ass'y With Rollers, Models B
&
F, Includes
2
Weld Studs
19915
(Current, Since
1968)
(Shown)
41446
Angle Slide Ass'y With Rollers. Mod
els B & F, Includes
2
Hex Mount
ing Studs
19924
41447
Angle Slide Ass'y With Rollers, Models B
&
F, Includes Original Style
Body Mounting Bolt
&
Washers, etc.
2
01250
Angle Casting, Machined, Welded Stud, Models B
& F 01251
Angle Casting,
Machined. Hex Stud, Models B
& F 01252
Angle Casting, Machined. Bolted Stud, Models B
& P 3
14629
Lockout
4
19900
Roller Stud
5
23133
Washer
6
18720
Roller
7
19572
Roller Spring
8
43800
Shelf Arm
&
Connecting Rod Ass'y, Model B
43801
Shelf Ann
&
Connecting Rod Ass'y, Model F (Shown)
9
51002
Sliding Shelf Arm, Model B
51004
Sliding Shelf Arm, Model F (Shown)
10
42190
Connecting Rod, Model B
42191
Connecting Rod, Model F (Shown)
11
42185
Auto Sliding Shelf. Model B
42186
Auto Sliding
Shelf, Model F (Shown)
PRESSURE STEAMERS
REFERENCE
NUMBER
PART NUMBER DESCRIPTION
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 15
MODELS J AND K PRESSURE STEAMER
SLIDE SETS
REFERENCE
NUMBER
1 41440Pan Support Slide Set, Model J Complete
2 41430Right or Left Side Slide Rack, 2 Per Compt Req'd. Model J
3 41435Center Slide Rack Model J, 1 Req'd Per Compt
4 19909Replacement Top Studs (Screw-In) J or K (Set of 6)
PART NUMBER DESCRIPTION
41442 Pan Support Slide Set, Model K Complete
41432Right or Left Side Slide Rack, 2 Per Compt Req'd. Mode) K
41437Center Slide Rack Model K, 1 Req'd Per Compt
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 16
START-UP MAINTENANCE PROCEDURES— STEAM GENERATOR
IMPORTANT: These instructions must be followed
in order to prevent premature failure of
the steam generator
START-UP:
1) Open the cabinet base door and close me drain valve
if it is open (Red Handle lever marked "blowdown")
2) Flip the toggle switch on front of the cabinet console
to "ON" (up position). The red console light should then
glow and wter will automatically begin filling the
generator.
3) When the water level in the sight gauge galss (on the
generator) reaches approximatley 2/3 full (afer
approximately five minutes0. depress the "ON" reset
button on the console. This will energize the electric
heater elements or ignite the gas burner. If the sight
gauge glass is completely filled, have the generator
serviced.
4) In approximatley ten minutes you will notice the steam
pressure gauge, on the console, register the steam
pressure contained inside the generator.
5) Cooking may now begin. Refer to "Cooking" and "Opening
Procedure" data sheets for specific instructions.
MAINTENANCE:
1) At the end of each day's operation, while the
generator is pressurized, flip the console toggle switch to
the "Blowdown" position, open the door in the cabinet
base and open the generator's drain valve.(red handle).
This "Blowdown" procedure drains the water out f the
generator and helps to prevent lime scale formation.
When the generator is empty, flip the console toggle
seitch to the "OFF" position and close the generator's
drain valve. It is recommended that the generator be
refilled with water after the "Blowdown" is performed.
This can be accomplished by flipping the toggle switch to
the "ON" position for a period of five minutes and then
returning the switch to the "OFF" position.
CAUTION:
Service on the generator should only be performed by a
trained and experienced service technician, thoroughly familiar
with servicing steam generators. No work should be done on
the steam generator while it is pressurized or hot. Be sure all
energy sources are shut off before the start of any work.
2) Even though the "Blowdown" is performed faithfully each day, it will still be necessary to periodically inspect the
inside of the generator. The generator's hand hole plate should be removed at regular intervals so that it isremoved. If the hand hole plate is chipped or cracked, orover three years old, install a new one. Replace the corrosion resistor if necessary, and chemically descale the
the generator if it is coated with lime scale. A new hand hole gasket should always be installed.
3) It will be necessary to periodcally have scale accumulations removed from the inside of the steam generator by a qualified service tchnician. Generator descaling instructions are provided on a seperate data sheet. Failure to periodically remove scale from the inside
of the generaotr will result in greatly reduced generator life.
4) Every steam generaotr is equipped with at least one corrosion and scaling. This corrosion resistor is sacrificial
and must be replaced at regular intervals just before it is
entirely consumed. In areas where the water is very hard,
the feedwater must also be treated to remove the harmful
mineral content.
Refer to seperate data sheets for corrosion resistor
servicing instructions.,feedwater treatment information, and
hand hole plate servicing instructions.
5) Check the safety valve once a week while steam
generaotr is pressurized. Test by pulling safety valve
extension wire. Valve must open freely and snap closed
when released. If it does not or if it drips constantly, a new
safety valve is needed.
6) If the steam generator is to be left idle for three months
or mre, it should be drained and dried out and the hand
hole plate left off.
7) Water level in the sight gauge normally should be about
2/3 full. This level is maintained automatically.
Refer to seperate data sheet for either mechanical or water
fill servicing instructions.
8) If gas fired the lighting instructions are on the AGA rating
plate. Pilot burner is lit through hole in panel at bottom of
steam generator. This panel should never be left off as this
will damage the controls. Burners will not light without
water in the steam generator.
CLEVELAND RANGE CO, 1333 EAST 179th ST.. CLEVELAND, OHIO 44110
Manufacturer reserves right of desingn improvement or modification as warranted.
Page 17
WATER QUALITY REQUIREMENTS— STEAM
GENERATOR PROTECTION AND MAINTENANCE
A steam generator, or boiler unlike other types of water-
using kitchen equipment, distills the water in order to make
steam. Nearly all feed-water sources contain dissolved
minerals in varying degrees of concentration. As this water
is boiled, pure steam rises from it's surface, upward to the
cooking compartments, leaving minerals behind, that can
become harmful to the steam generator. If minerals are
allowed to accumulate inside the steam generator, they will
solidify as a scale. Then malfunctioning will occur, and
serious equipment damage may result.
The use of good quality generator feed water is the
responsibility of the owner/user. The use of poor quality
feed water could void equipment warranties. The minimum
treatment required in most areas is water softening,
although local water conditions may require more intensive
pretreatment than simply a water softener.
Scale problems occur when feed water is high in hardness,
total dissolved solids, silica, and alkalinity. Water softening
will only reduce the water's hardness which is the presence
of dissolved salts of magnesium and calcium. Water
softening will not affect the multitude of other minerals, the
best property to control, for generator feed water, is total
dissolved solids, not just hardness.
the recommended minimum water quality standards,
whether untreated or pretreated, based upon 10hours of
use per day, and a Daily Blowdown are as follows:
TOTAL DISSOLVED SOLIDS less than 60 parts per million
TOTAL ALKALINITY less than 27 parts per million
SILICA less than 13 parts per million
pH FACTOR greater than 7.5
Consult a local water treatment specialist for an on the
premises water analysis and for recommendations
concerning steam generator and feed water treatment (if
required) in order to remove or reduce harmful
concentrations of minerals.
If the recommended water quality requirements are met
without supplemental treatment or if treatment is applied
resulting in feed water quality meeting the prescribed
standards the steam generator will need to be blown down
only once each day. In addition the inside of the generator
requires an inspection (for excessive lime accumulation
and consumed corrosion resistors) only once every six
months. Replace the corrosion resistor and chemically
descale the generator as required.
If a pre-treatment unit cannot be installed, and the
recommended water quality requirements are not met, the
following procedures should be followed in order to achieve
maximum steam generator service life. The steam
generator is heavily coated with scale, have it chemically
descaled by a qualified service technician.
INSTRUCTIONS FOR CHEMICALLY DESCALING STEAM GENERATORS
Warning: Steam under pressure may cause serious
injury and bodily harm when it is accidentally or
carelessly released. Improper handling of acid could
cause serious permanent injury. Therefore, service
of the steam generator should only be performed by
trained and experienced personnel, thoroughly
familiar with servicing generators.
There are a number of commercial descaling chemicals
available produced by various manufacturers. Thoseutilizing a sulfamic acid base, which can be identified by its
powdered form are sage and compatable with our food
preparation equipment. It is imperative that the acid used
for descaling be FDA approved for use in food preparation
equipment. Various manufacturers may include additional
chemicals to increase potency and therefore, instructions
are not provided with the deliming chemical you purchase
the following general guidelines may be followed.
WARNING: Exercise care when handling acid. Avoid
contact with skin, eyes, or clothing. Wear safety glasses or
face shield along with rubber gloves and rubber apron. In
case of exposure to clothing, remove clothing and flush
with water. In case of exposure to skin or eyes, flush with
water for 15 minutes and get immediate medical attention.
Do not take internally. Keep out of the reach of children.
Be sure the generator has been drained, de-pressurized,
and is cool. Open the hand hole access plate on the front
of the generator and place approximately 8-10 pounds of
sulfamic acid inside the generator. Put a new hand hole
plate and replace the hand hole plate tightening the bar
and nut assembly to a maximum of 15 foot pounds torque.
The generator must be completely filled with hot water (fill
the generator beyond its normal, automatic fill point to 2/3
up in the sight gauge.) On mechanical fill generators this
can be accomplished by adding weight to the float or
removing the float and regulating the fill level with a hand
valve in the water supply plumbing. On electric fill
generators (with probes) this can be accomplished by
temporarily jumpering terminals #3 & #4 of the water
control relay. Turn the main on-off toggle switch to the "ON"
position then turn the switch to the "OFF" position when the
generator is completely filled. Let the solution stand for
several hours, then flush with water. Rinse with a solution
of bicarbonate of sods to neutralize any acid residue and
again flush with water.
CAUTION: Never tighten the hand hole plate nut when
the steam generator is in use, hot, or otherwise
pressurized. Never tighten nut over 15 foot pounds
torque. Overtightening may cause uneven stress, which
may result in the weakening and possible breakage of
the plate.
CLEVELAND RANGE CO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Page 18
MAINTENANCE INSTRUCTIONS FOR STEAM GENERATORS
(EXCEPT THOSE EQUIPPED WITH TWO PROBES)
WARNING: Steam under pressure may cause
serious injury and bodily harm when it is
accidentally or carelessly released. Therefore,
service of the steam generator should only be
performed by trained and experienced personnel,
thoroughly familiar with servicing steam
generators.
CAUTION: Never work on the steam generator when
it is hot or pressurized.
Every steam generator shipped in equipped with at least one
corrosion resistor (cathodic). The larger capacity steam
generators will have two corrosion resistors.
The hand hole plate and gasket on your steam generator
stops the escape of steam through the hand hole
opening during operation.
1) Turn off all energy sources to steam generator. Drain steam
generator.
2) Remove hand hole cover plate from steam generator.
3) Hang corrosion resistor from the right side of the front
stay rod, away from the probes. Clean scale and rust off
a portion of the stay rod so the hanger will rest on the
bright, bare metal.
4) Re-install the hand hole plate, along with a new
gasket.
The hand hole plate should be cleaned and examined
every time it is removed. If the hand hole plate is chipped
or cracked or over three years old, install a new one.
Because continuous use and possible abuse cause
metal fatigue which weakens the hand hole plate. a new
one should be installed at least every three years.
CAUTION: Never tighten the hand hole plate nut
when steam generator is in use, hot, or otherwise
pressurized. Never tighten nut over 15 foot pounds
torque. Overtightening may cause uneven stress,
which may result in the weakening and possible
breakage of the plate.
er
CLEVELANO RANGE CO, 1333 EAST 179th ST., CLEVELAND. OHIO 44110
Replace the gasket whenever the hand hole plate is removed or
replaced. Keep a spare gasket on hand at all times. Replace the gasket at least once a year, or sooner if it is cracked,
torn, or hardened.
Leakage of water past the hand hole plate should not be allowed
to continue as this will cause pitting of the metal in contact with
the gasket.
5) After re-installing the hand hole plate, close the steam
generator drain valve. Turn on energy sources.
6)Start up and operate steam generator long enough to observe
that it is operating properly.
The corrosion resistor is sacrificial and must be replaced at
regular intervals just before it is entirely consumed. Frequency of replacement can only be established by a
regular inspection for how much of the protector remains
and whether scaling or pitting has begun. Scaling indicates
a very hard water condition. In either case, more protectors
or more frequent replacement of them in necessary. The
best way to reduce servicing time and to assure long
generator life is to provide feed water that is low in solids
content and low n gas content. Water that is fit to drink can
still be high in impurities that are highly detrimental to a
steam generator. Consult a water treatment specialist in
your area for recommendations concerning steam
generator feed water treatment.
Under average conditions, the corrosion resistor provides about
six months of service. An average condition would meet each of
the following tests:
1. Less than 8 hours of steam generation a day.
2. One generator blowdown every day
3. Moderatley hard water. Less than 85 ppm.
4. Water containing less than 60 ppm Total Dissolved Solids.
Page 19
STEAM GENERATOR (BOILER) IDENTIFICATION
Service Note
The above drawings showing the
sight gauge location and method of
mounting are for assisting in
determining the proper part number
for replacement generators. When
ordering please provide both the
proper part number and the
equipment's serial number.
CLEVELAND RANGE CO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Page 20
SERVICING INSTRUCTIONS STEAM
PRESSURE ADJUSTMENTS
WARNING: Adjustments must be made only by trained and experienced service personnel.
Normally there is no need to make pressure adjustments on a new steamer, because the proper settings are made at the factory.
In some cases however, the factory setting may shift due to shaking in transit, and resetting will be required after installation. The factory
pressure settings shown on the accompanying chart should never be exceeded.
For Gas and Electric Steam Generator
Steam pressure is controlled with two pressure switches located
toward the upper-front of the cabinet either to the extreme right.
The left switch is the operating pressure switch. This switch
controls the pressure in the steam generator, which is the
pressure indicated on the steam generator pressure gauge.
The right switch is a high limit, pressure safety control. It
breaks an electric circuit to shut off the energy source if the
steam pressure rises above a safe level.
Each switch has a screw on top of the case to permit the
pressure set point to be adjusted without removing the cover.
The correct settings are shown in the accompanying chart.
The pressure switch indicator scale is for reference only.
Actual pressure should be read on the pressure gauge and
the pressure switch adjusted to produce the proper pressure
gauge reading. Some models may also have a pressure
reducing valve to control the pressure in the steam line to the
steamer The adjustment of this discussed further on.
For Steam Coil Steam Generator
The steam supply to steam coil generators is controlled by one of
two methods.
Steam generator pressure may be controlled by a pilot
operated pressure regulating valve. The steam generator
pressure can be adjusted by turning the adjusting collar,
identified on the sketch. A steel rod is provided to turn the
collar. The correct settings are shown in the accompanying
chart.
On steam coil generators equipped with an electric
solenoid valve to control the steam supply to the steam
generator, one or two pressure switches control the steam
generator pressure. To adjust the switch(es), turn the
screw on the top of the case to achieve the pressure
reading shown in the accompanying chart.
Pressure Reducing Valve-Adjustment and Care
A screw at the top of the valve body, as shown on the sketch, permits the pressure set point to
be adjusted. The locknut must be loosened before adjustment is made, and tightened after.
Turning adjustment screw into housing raises pressure. If excessively high or low pressure
cant be corrected by adjustment, install a new valve.
To eliminate erratic performance, the internal steam strainer should be cleaned periodically.
The strainer can be reached by unscrewing the large hex head plug at the bottom of the valve
body.
(CONTINUED ON THE REVERSE SIDE)
CLEVELAND RANGE, INC, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification as warranted.
Page 21
Contained
Generator Only
Steam Generator Only
Super Steamcraft, or
GAUGE PRESSURE READING WITH NO STEAM FLOW (STATIC PRESSURE)
CLEVELAND RANGE, INC., 1333 EAST 179th ST.. CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification as warranted.
Page 22
SERVICING
INSTRUCTIONS
PROBE SYSTEM: ELECTRIC WATER FILL AND ELECTRIC LOW WATER FUEL CUT OFF FOR STEAM GENERATOR— 3 PROBE TYPE
WARNING: Service of the steam generator must be performed only by trained and
During operation of the steam generator. The water level is maintained automatically by unequal length probe extensions inside The probes and
extensions must be kept clean and free of scale deposits in order to function properly
The probe extensions are sensors in a control system which monitors and maintains the water level between the end of the short probe extension
and the end of the intermediate extension.
The long probe, called "Low Water." is a safety sensor which shuts off
experienced service technicians.
the fuel supply if there is insufficient water in the steam generator.
Since the control system is all electric and these parts don't move or
wear, they can be expected to have a Ions life. If they do malfunction, it
is generally because untreated hard feedwater is being used in the steam generator. This forms scale on the submerged ends of the
probe extensions and on the top horizontal surfaces of the probes. After this scale is removed, the parts will function properly.
To eliminate the cause of scaling, refer to separate data sheets for feedwater treatment information and corrosion protector
servicing instructions. Probes and probe extensions should be wiped clean each time the corrosion protector is replaced.
Erratic operation may result from loose connections on either end of the probe. The external end of the probe has a nut to hold the
wiring terminal snugly to the probe. This nut, if loose, may be tightened, firmly but gently. Too much torque will turn the center
peice of the probe and misalign the attached probe extension inside, causing the probe to become inoperative.
inside the steam generator, the screw which holds the probe extension to the probe may be loose, allowing the probe extension to
swing or rest against some part of the steam generator. This can be corrected by removing the hand hole plate and reaching inside
to align and hold the probe extensions vertically while tightening the screws.
To Service the Probes or the Probe Extensions
1) Turn off all utilitiesand fuel to steam generator. Drain Steam generator.
CAUTION: Never work on the steam generator when it is hot or pressurized.
2) Remove probe cover on outside of steam generator to expose probe terminals. Examine for loose wiring terminals.
3) Remove hand hole cover plate from steam generator. See separate data sheet for instructions.
4) Remove probe extensions from probes on inside of steam generator, clean off scale, and re-install Or. install new probe
extensions if preferred.
5) Remove scale from the probe (see sketch above) Do not use an abrasive on the teflon insulator. If the old probe needs
replacement, install a new one.
(CONTINUED ON THE REVERSE SIDE)
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 23
CONTINUES
SERVICING PROBE SYSTEM: ELECTRIC WATER FILL AND INSTRUCTIONS
ELECTRIC LOW WATER FUEL CUT OFF FOR STEAM GENERATOR— 3 PROBE
TYPE
6 Assemble probe extensions to probes on inside of steam generator so they hang vertically, parallel to each other Malfunctioning
will occur if an extension touches any part of the steam generator or another probe extension
7) If insulation on electrical wires to the probe snows signs of being broken, cut or deteriorated, the wires should be replaced
8) Connect wire terminals on outside of steam generator to probe terminals as follows:
Red wire to theshortest probe. Turns water off.
Black wire to the intermediate probe. Turns water on
White wire to the longest probe- Shuts off fuel (low water safety fuel shut-off)
9) Re-install hand hole plate and install a new gasket.
The hand hole plate should be cleaned and examined each time it is removed. If the plate is chipped or crackedit should be replaced
immediately. Because continuous use and possible abuse can cause metal fatigue which weakens the hand hole plate, a new one
should be installed at least every three years. Replace the gasket at least once a year —or sooner if it is cracked or hardened.
10) Replace probe cover and check to make sure that the cover does not contact probes.
11) Close steam generator drain valve. Turn on utilities and fuel supply to steam generator.
12) Operate and observe steam generator long enough to insure that it is functioning properly.
Low Water Fuel Cut Off Test
Proper operation of the "Low Water" probe extension should be checked periodically, by someone who is thoroughly familiar with
the equipment.
To Test: Open the drain of the steam generator while fuel is on- When the water has drained below the "Low Water" probe, the fuel
should shut off automatically- Indication of fuel shut off should occur just as the water level in the sight gauge drops from view. If it
does. close the drain, allow the steam generator to refill, and resume normal operations. If the fuel does not shut off. immediately
turn the on-off toggle switch to the "off position, and follow the steps outlined under "To Service the Probes or the Probe
Extensions" as given on the reverse side of this sheet.
For specific information pertaining to the operation of the electric water fill controls, and electric low water safety fuel cut-off, refer
to the following data sheets:
Electric Steam Generators
Gas-Fired Steam Generators
Steam Coil (electric operated) Generators
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 24
STANDING PILOT-IGNITION TYPE GAS CONTROLS FOR GAS-
FIRED STEAM GENERATORS
CAUTION: The following procedures, as well as other work on the gas controls, should be performed only by a trained and
experienced service technician, thoroughly familiar with gas controls.
Built in gas controls assure safe and automatic operation of the pilot and main burners of the steam generator
The controls consist of a pilot generator (thermocouple and a unit called the combination gas control This latter unit consists of a gas valve operator
and servo gas pressure regulator
Generally, there is no need to make an adjustment to any portion of the gas system. The main burner orifices and the pilot burner orifice
installed at the factory are correct for the kind of gas specified on the purchase order Also. the primaryair supply to the main burner is properly
adjusted for complete combustion.
Lighting and Shutdown Instructions
Flip electrical switch on. Open water valve Open gas valve Slightly depress and turn control knob to "off" for 5
minutes before lighting gas. Turn control knob to "pilot." depress it completely, and light pilot burner. Continue to hold Knob in for about 60
seconds, then release. Pilot burner is lighted through hole in panel at bottom of steam— generator Never leave panel off. as this will damage
controls. Turn control knob to "on". Depress electrical switch. for main burner ignition Burners will not light without water in the steam
generator. For main burner off. with pilot on control knob to pilot". For main and pilot burner off. slightly depress and turn control knob to
"of" Flip electrical switch off
Occasionally due to regional differences in the
gas supply the pilot burner flame may require
adjustment.
A normal flame is mostly blue and steady, and
envelops 3/8" to 1/2 of the tip of the pilot
generator, as illustrated at right
The pilot gas adjusting screw can be found under
a cover screw located near the gas control knob.
illustrated below
To adjust the pilot flame:
1) Remove the pilot adjustment cover screw
2 Turn PILOT FLOW ADJUSTMENT SCREW clockwise-—to
decrease or counterclocKwise—to increase pilot flame.
3) WARNING: Be sure to replace cover screw after adjustment to
prevent possible gas leakage
Electrical connections in the pilot generator circuit must be dean and secure.
Because the pilot generator operates in a severe environment, it may eventually need a replacement. The time before replacement will vary from
one piece of equipment to another, depending on the amount of usage. The pilot generator (thermocouple) should generate 450-750 MV in an open
circuit condition.
When a malfunction is traceable to the combination gas control unit. it is recommended that the entire unit be replaced with a new one. rather than
attempting repairs to the old unit.
WARNING: To prevent the danger of possible gas leakage, the installer must be a trained and experienced service technician,
thoroughly familiar with gas controls.
CLEVELAND RANGE CO.. 1333 EAST 179th ST.. CLEVELAND. OHIO 44110
Page 25
HOW THE ELECTRIC (WARRICK RELAY) WATER
LEVEL CONTROLS OPERATE— ON GAS FIRED
STEAM GENERATORS (WITH 3 PROBES)
Inside Cleveland Range Co- boilers which have electric water level controls, there are three probe extensions
vertically oriented above thewater with their lower ends
positioned at various levels
Water is admitted to the boiler and is shut oft in response to the
water level sensed by the tips of the short and the medium length
probe extensions The electrical conductance of the water is used in
this system tor controlling its level.
The third probe extensionis a low water safety cutout sensor and
operates on the same principle. Operation Sequence— Water Level Control
Assume an empty Boiler To fill. close Switch S for the following
operations:
1) Solenoid SV, is energized allowing the boiler to fill with water
at the same time the primary circuit of Transformer T, is also
energized.
2; The boiler will continue to fill until the water level reaches
the Water Off probe extension completing the T, secondary
circuit, and energized Relay Coil RC.
3) When Relay Coil RC. is energized the normally closed contact
opens, de -energizing Solenoid SV;
stopping the water fill. The normally open contact is closed,
complet ing the circuit to the Water On probe.
When the water boils away below the end of the Water On probe
extension the following occurs:
1) The secondary circuit of Transformer T, is broken and
the Relay Coil RC, is de-energized
2) When Relay Coil RC, is de-energized the normally open
contact opens, breaking the circuit to the Water Off probe
extension. And. the normally closed contact closes,
energizing Solenoid SV; allowing the boiler to fill as in Step
2 above.
Operation — Low Water Safety Cutout
When Swit ch S is closed the following operations occur
1) The primary circuit of Transformer T2; is energized.
2) When the water level reaches the low water safety cutout probe
extension and the momentary reset switch is manually closed.
Relay Coil RC, is energized.
3) When Relay Coil RC; is energized the normally open contacts
close, completing the low water safety circuit through Contacts 7
and 8 and completing the circuit through Contacts 3 and 4.
completing the 750 millivolt pilot generator circuit and allowing
the gas control package valve to operate.
If the water level drops below the Low Water Safety Cutout probe
extension, the following occurs:
1) The secondary circuit of Transformer T2 is broken and the
Relay Coil RC2 is de -energized- Contacts 7 and 8 and 3 and
4 open. breaking the 750 millivolt circuit
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted
which shuts off the flow of gas to the burners.
The burners will not operate until water level in the boiler is
normal and the reset switch is operated.
Operation-Boiler Drain Condenser
To activate the Boiler Drain Condenser System close switch S by
placing toggle in the down position.
To drain boiler, open boiler drain ball valve. The heat from the
boiler drain water will close the normally open thermal switch TS
and energize the condenser solenoid valve SV, . To de-activate the
Boiler Drain Condenser System open switch S by moving toggle
to center off position.
Page 26
HOW THE ELECTRIC (WARRICK RELAY)
WATER LEVEL CONTROLS OPERATE— ON
ELECTRIC STEAM GENERATORS (WITH 3
PROBES)
inside Cleveland Range Co- boilers which have electric water level
controls, there are three probe extensions vertically oriented above
the water with their lower ends positioned at various levels.Water is
admitted to the boiler and is shut off in response to the water level
sensed by the tips of the short and the medium length probe
extensions The electrical conductance of the water is used in this
system for controlling its level.
The third probe extension is a low water safety cutout sensor and
operates on the same principle. Operation Sequence— Water
Level Control
Assume an empty boiler. To fill. close Switch S tor the following
operations:
1) Solenoid SV; is energized allowing the boiler to fill with water at
the same time the primary circuit of Transformer T, is also
energized.
2) The boiler will continue to fill until the water level reaches the
Water Off probe extension completing the T, secondary circuit, and
energizing Relay Coil RC,.
3) When Relay Coil RC, is energized the normally closed contact
opens, de -energizing Solenoid SV2
stopping the water fill. The normally open contact is closed,
completing the circuit to the Water On probe.
When the water boils away below the end of the Water On probe
extension the following occurs:
1)) The secondary Circuit of Transformer T, is broken and the Relay
Coil RC, is de -energized.
2) When Relay Coil RC, is de -energized the normally open contact
opens, breaking the circuit to the Water Off probe extension. And.
the normally closed contact closes, energizing Solenoid SV2
allowing the boiler to fill as in Step 2 above.
Operation — Low Water Safety Cutout
When Switch S is closed the following operations occur
1) The primary circuit of Transformer T2 is energized.
2) When the water level reaches the low water safety cutout probe
extension and the momentary reset switch is manually closed. Relay
Coil RC2 is energized.
3) When Relay Coil RC2 is energized the normally open contacts
dose, completing the low water safety circuit through Contacts 7 and
8, and completing the circuit through Contacts 3 and 4. energizing
Contactor Coil C which closes the heater circuit
If the water level drops below the Low Water Safety Cutout probe
extension, the following occurs:
1) The secondary circuit of Transformer T2, is broken and the Relay
Coil RC2 is de -energized- Contacts 7 and 8 and 3 and 4 open.
breaking the circuits to Contactor C., thereby turning off the heaters.
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
The Contactor C, will not operate until water level in the boiler is
normal and the reset switch is operated.
Operation-Boiler Drain Condenser
To activate the Boiler Drain Condenser System .close switch S by
placing toggle in the down position.
To drain boiler, open boiler drain ball valve. The heat from the
boiler drain water will dose the normally open thermal switch TS
and energize the condenser solenoid valve SV3,. To de-activate the
Boiler Drain Condenser System open switch S by moving toggle to
center off position.
Page 27
ELECTRIC STEAM GENERATOR (BOILER) ASSEMBLY- 3 PROBE TYPE
1522140Air Vent
1616820Pigtail.1/4" ips
1719947Pressure Switch
1812161Signal Light 115/220 Volt
1919944On-Off Power Switch. 115/220 Volt DPST
2003503Contactor tor Side Heater. 50 amp. 208/240 Volt Coil
03505Contactor tor Side Heater. 75 amp. 208/240 Volt Coil
2120532Transformer — Optional (480/240/120 Volt Only)
2208170
08171
08184
08172
08180Electric Immersion Heater. Screw Type. 9KW. 240 Volt
08185Electric Immersion Heater. Screw Type. 9KW. 480 Volt
08182Electric Immersion Heater. Screw Type. 12KW. 208 Volt
08181
08183
2308201Heater. Screw Type. With Thermostat. 6KW. 208 Volt (Not Available)'
08200Heater. Screw Type. With Thermostat. 6KW. 240 Volt
08204Heater. Screw Type. With Thermostat 6KW. 480 Volt
08203Heater. Screw Type. With Thermostat 9KW. 208 Volt (Net Available)*
08202Heater. Screw Type. With Thermostat 9KW. 240 Volt (Not Available)'
08205Heater. Screw Type. With Thermostat 9KW. 480 Volt (Not Available)'
2419945Float Switch With Gasket — Low Water Cut-off
Electnc Immersion Heater. Screw Type. 6KW. 208 Volt
Electnc Immersion Heater. Screw Type. 6KW. 240 Volt
Electric Immersion Heater. Screw Type. 6KW. 480 Volt
Electric Immersion Heater. Screw Type. 9KW. 208 Volt
Electnc immersion Heater. Screw Type. 12KW. 240 Volt
Electric Immersion Heater. Screw Type. 12KW. 480 Volt
• Consult factory tor conversion to a low water cut-off float switch type of safety circuit
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 31
WIRING DIAGRAM ELECTRIC STEAM
WIRING DIAGRAM FOR ELECTRIC STEAM GENERATORS
GENERATORS
WITH ELECTRICAL LOW-WATER HEATER CUTOFF, WITHOUT
MANUAL SAFETY RESET CIRCUIT PRIOR TO JANUARY, 1978
CLEVELAND RANGE CO, 1333 EAST 179th ST.. CLEVELAND. OHIO 44110
Page 32
CLEVELAND RANGE CO.. 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 33
GAS STEAM GENERATOR (BOILER) ASSEMBLY— NO PROBES
100,000 BTU (2 BURNER) & 150,000 BTU (3 BURNER)
Page 34
GAS STEAM GENERATOR (BOILER) ASSEMBLY— NO PROBES 100,000 BTU (2
1 40300Boiler Shell Only, With Legs, Studs. Hand Hole Plate Assembly, and Top Flue Bracket.
1
1
3/4" Boiler Drain Valve
1/2" Combination Natural Gas Control Valve
2"
Combination LP Gas Control Valve
3/4" Pressure Reducing Valve.
3-15
psi Output (Optional)
BURNER) & 150,000 BTU (3 BURNER)
REFERENCE
NUMBER
240425Hand Hole Plate Assembly Including Bar, Nut. Gasket, and Hand Hole Plate
2A16545Hand Hole Plate Only
307116Hand Hole Gasket
443895Corrosion Resistor
540446Water Gauge Set With Glass
607301Glass Only—10 1/2" Long
743720Water Regulator Valve Assembly
806300Float Only
943740Float Ann and Block Assembly
1002411Float Pivot Bracket
1243735Float Plunger Assembly, 3 1/2"
1316833Plunger Disc
1443724Water Regulator Valve Sub-Assembly
1522112Water Shut Off Angle Valve
1622150
1716621Fusible Plug With Bushing
1819945Float Switch With Gasket—Low Water Cut-Off
1902498Main Gas Burner—24" Long
2015453Main Burner Orifice—Natural Gas
2119632Orifice Holder (After 7/76)
2263150Gas Manifold—100.000 BTU—2 Burner
2322182
2443651Pilot Generator Assembly With 02505 Burner. 20410 Thermocouple. 52449 Bracket and 15460
2520410Pilot Thermocouple
2602505Pilot Burner—Natural Gas
2715460Pilot Burner Orifice—Natural Gas
2852449Pilot Bracket (After 7/76)
28A52450Pilot Bracket (Before 7/76)
2907173Pressure Gauge. Rear Mount—0 to 30 psi
3019967On-Off Power Switch. 115/220 Volt 3 PDT
3119968Reset Switch
3212161Signal Light. 115/220 Volt
3319947Pressure Switch
3422140Air Vent
3522130Safety Valve—8 psi
3622122
3769934Rear Baffle and Burner Support—100,000 BTU—2 Burner
3852171Burner Compartment Front Baffle—100.000 BTU—2 Burner
3970920Twister
PART NUMBER
40307Boiler Shell Only, With Clip Locks, Studs. Hand Hole Plate Assembly, and Top Flue Bracket43826Boiler Shell 40300 Above. Also Including One Corrosion Resistor. Sight Gauge. Low Water Cut-Off
43828Boiler Shell 40307 Above. Also Including One Corrosion Resistor. Sight Gauge. Low Water Cut-Off
43653Pilot Generator Assembly with 02523 Burner. 20410 Thermocouple. 52449 Bracket, and 15461
02523Pilot Burner—LP Gas
15461Pilot Burner Orifice—LP Gas
22131Safety Valve—15 psi
69935Rear Baffle and Burner Support—150.000 BTU—3 Burner
52172Burner Compartment Front Baffle—150.000 BTU—3 Burner
DESCRIPTION
Switch, and Water Regulator.Switch, and Water Regulator.
Long) or 02499 (20" Long). 1963 Orifice Holder, and One 52450 Pilot Bracket (If Pilot's Burner is
Replaced.)
1/
Orifice.
Orifice.
CLEVELAND RANGE, INC., 1333 EA ST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 35
GAS STEAM GENERATOR (BOILER) ASSEMBLY— 3 PROBE TYPE
210,000 BTU (5 BURNERS)
Page 36
GAS STEAM GENERATOR (BOILER) ASSEMBLY— 3 PROBE TYPE
REFERENCE
NUMBER
PART
NUMBER
1 40302
Boiler Shell Only. With Legs, Studs. Hand Hole Plate Assembly, and Top Flue Bracket.
40309
Boiler Shell On
ly, With Angle Iron Mounting Bar, Studs. Hand Hole Plate Assembly, and
Top Flue Bracket.
43832
Boiler Shell
40302
Above, Also Including: Two Corrosion Resistors. Sight Gauge. Three
Probes and Extensions With Cover Box.
43833
Boiler Shell
40
309
Above, Also Including: Two Corrosion Resistors. Sight Gauge, Three
Probes and Extensions With Cover Box.
2
40425
Hand Hole Plate Assembly Including Bar, Nut. and Gasket
2A
16545
Hand Hole Plate Only
3
07116
Hand Hole Gasket
4
43895
Corrosion R
esistor
(2
Req'd.)
5
40446
Water Gauge Set With Glass
07108
Fibre Washers
(2
Req'd.)
23132
Gauge Glass Washers
(2
Req'd.)
6
07301
Glass Only, 10 1/2" Long
7
40462
Probe With Lockwasher and Screw
8
40455
Probe Extension Set
9
52350
Probe Cover
10 19870
1/4
" Line Strainer
11
44095
1/2" Water Feed Solenoid Valve
12
02499
Main Gas Burner
02500
Main Gas Burner Used on Units Built Before
7/76
(Not Shown). Replace With Burner
02498
—
24"
Long or
02499
—
20"
Long.
19632
—
Orifice Holder, and One
52450—
Pilot Bracket (If Pilot's Burner Is Replaced.)
13
15453
Main Burner Orifice
—
Natural Gas
15450
Main Burner Orifice
—
LP Gas
14
19632
Orifice Holder (After
7/76)
19631
Orifice Holder (Before
7/76)
15
63152
Gas Manifold
—
210,000 BTU
—5 Burner
16
22183
3/4" Combination Natural Gas Control Valve
16A 22189
3/4" Combination LP Gas Control Valve
17
43651
Pilot Generator Assembly With
02505
Burner,
20410
Thermocouple.
52449
Bracket, and
15460
Orifice.
43653
Pilot Generator Assembly With
02523
Burner,
20410
Thermocouple,
52449
Bracket, and
15461
Orifice.
18
20410
Pilot Thermocouple
19
02505
Pilot Burner
—
Natural Gas
02523
Pilot Burner
—
LP Gas
20
15460
Pilot Burner Orifice
—
Natural Gas
15461
Pilot Burner Orifice
—
LP Gas
21
52449
Pilot
Bracket (After
7/76)
21A 52450
Pilot Bracket (Before
7/76)
22
52177
Burner Compartment Front Baffle
23
69933
Burner Compartment Rear Baffle
24
07173
Pressure Gauge. Rear Mount
—0 to
30
psi 25 19941
On-
Off Power Switch,
115/220
Volt.
4
PDT 26 19968
Reset Switch
27
12161
Signal Light
115/220
Volt 28 19947
Pressure Switch
29
22140
Air Vent
30
22130
Safety Valve
—8 psi
22131
Safety Valve
—15 psi 31 22122
3/4" Pressure Reducing Valve.
3-15
psi Output (Optional)
32
19945
Float Switch With Gasket
—
Low
Water Cut
-
Off 33 03504
Water Control Relay,
115
Volt
(1
D1DO)
34
03514
Low Water
Cut-Off
Relay,
115
Volt (1C1DO)
35
22150
3/4" Boiler Drain Valve
36
16621
Fusible Plug With Bushing
37
70920
Twister
210,000 BTU (5 BURNERS)
DESCRIPTION
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 37
GAS STEAM GENERATOR (BOILER) ASSEMBLY— 3 PROBE TYPE
160,000 BTU (3 BURNER) & 200,000 BTU (4 BURNER)
Page 38
GAS STEAM GENERATOR (BOILER) ASSEMBLY— 3 PROBE TYPE 160,000BTU
40298
Boiler shell
43872
above, also including two corrosion resistors, sight gauge, insulation panels, top flue
collector with insulation and cover plate, three probes and extensions with cover box.
2
40421
Hand hole plate assembly inc
luding bar. nut and gasket
2A
43748
Hand note plate only
3
07106
Hand hole gasket flat
4x6
oval.4 43941
Left side insulating panel assembly
5
43943
Right side insulating panel assembly.
6
56320
Top flue collector.
7
40115
Top insulation baffle asse
mbly (flat).
40116
Top insulation baffle assembly (with flange).
8
42360
Internal flue riser assembly.
9
40462
Probe with lock washer and screw.
10
40455
Probe extension set
(3).11 52350
Probe cover.
12
43895
Corrosion resistor.
13
40445
Water ga
uge set with glass.
07108
Fibre washer
(2
required).
23132
Gauge glass washer
(2
required).
14
07302
Glass only
— 6"
long. 15 43851 3-
burner front baffle assembly
— Natural Gas.
43855 3-
burner front baffle assembly
— LP. Gas.
16
43852 4-
burner
front baffle assembly
— Natural Gas.
43856 4-
burner front baffle assembly
— LP. Gas.
17
41365 3-
burner rear burner support (after
7-76).
69952 3-
burner rear burner support (before
7-76). 18 41366 4-
burner rear burner support (after
7-76).
69953 4-
burner rear burner support (before
7-76). 19 19870
1/4" fine strainer.
20
44095
1/2" water feed solenoid valve.
21
22102
1/4 check valve.
22
03276
1/4" ball valve
— water supply shut
-
off. 23 03277 Generator drain valve
— ball type.
24
02499
Main g
as burner.
25
15453
Main burner orifice
— Natural Gas.
15450
Main burner orifice
— LP. Gas
- 26 40901 Gas manifold assembly
— 3
burner (after
7-76).
40905
Gas manifold assembly
— 3
burner (before
7-76). 27 40902
Gas manifold assembly
— 4
burner (af
ter 7-
76).
40906
Gas manifold assembly
— 4
burner (before
7-76) 28 19632
Orifice holder (after
7-76).
19631
Orifice holder (before
7-76). 29 43651
Pilot generator assembly with
02505
burner.
20410
thermocouple.
52449
bracket and
15460
orifice.
4
3653
Pilot generator assembly with
02523
burner.
20410
thermocouple.
52449
bracket and
15461
orifice.
30
20410
Pilot thermocouple.
31
02505
Pilot burner
— Natural Gas.
02523
Pilot burner
— LP. Gas.
32
52449
Pilot bracket
33
15460
Pilot burner orific
e —
Natural Gas.
15461
Pilot burner orifice
— LP. Gas.
34
22182
1/2 combination gas control valve
— Natural Gas.
35
22122 3/4" pressure reducing valve.
3-15
psi output (optional).
36
22130
Safe
ty valve
— 8
psi.
22131
Safety valve
—15 psi. 37 22140
Air vent
38
19947
Pressure switch.
39
03514
Low water cut
-
off relay.
115
volt (1C1DO).
40
03504
Water control relay.
115
volt.
(1D1
DO). 41 07173
Steam pressure gauge, rear mount
0-30
psi. 42 19
967
On-Off power switch.
115/220
volt 3 PDT. 43 19968
Reset switch.
44
12161
Signal light
115/220
volt 45 19945
Float switch with gasket
— low water cut
-
off (California only).
46
22104
1/4" solenoid valve
— boiler condenser water supply.
47
19979
Ther
mal switch
— boiler condenser.
48
22106
Valve, solenoid.
1/2" boiler auto blowdown.
115
volt (optional).
49
05263
Radiator Ell.
3/4" union.
(3 BURNER) & 200,000 BTU (4 BURNER)
REFERENCE
NUMBER
PART NUMBER DESCRIPTION
CLEVELAND RANGE CO., 1333 EAST 179th ST, CLEVELAND. OHIO 44110
Page 39
GAS STEAM GENERATOR (BOILER) ASSEMBLY— 3 PROBE TYPE
250,000 BTU (5 BURNERS) ft 300,000 BTU (6 BURNERS)
Page 40
GAS STEAM GENERATOR (BOILER) ASSEMBLY— 3 PROBE TYPE 250,000
NUMBER
NUMBER
2 40421Hand Hole Plate Assembly including bar. nut and gasket
2A 43748Hand hole plate only.
3
07106Hand hole gasket fla
t
4x6
oval.4 43942Left side insulating panel assembly
5
43943Right side insulating panel assembly
6
56321Top flue collector
7
40117
Top insulation baffle assembly (flat)
48118 Top insulation
baffle assembly (with flange)
8 42361 Internal flue riser assembly
9
40462 Probe with lock washer and screw
10
40455 Probe extension set (3)
11
52350
Prove cover
12 43895
Corrosion resistor
13 40445 Water gauge set with glass
07108 Fibre washer (
2 required)
23132 Gauge glass washer (2 required)
14 07302 Glass only
-
6" long
15
43853 5 burner front baffle assembly
-
Natural Gas
43857 5
burner front baffle assembly
-
L.P. Gas
16
43854 6 burner front assembly
-
L.P Gas
6 burner front assembly
-L.P 17 41367 5
burner rear burner support (after 7
-
76)
5
burner rear burner support (before 7
-
76)
18 41368 6 burner rear burner support (after 7
-
76)
89955 6 burner rear burner support (before 7
-
76) 19 18870 1/4" line strainer
20
44095
1/2"water
feed solenoid valve
21 22102 1/4" check valve
22 03276
1/4"ball valve
-
water supply shut off
23
02499 Main gas burner
24 15453 Main burner orifice
-
Natural Gas
15450 Main burner orifice
-
LP Gas
25
19632 Orifice Holder (after 7
-
76)
19631 Orifice Hol
der (before 7
-
76) 26 03277
Generator drain valve
-
ball type
27 40903
Gas manifold assembly
-
5 burner (after 7
-
76)
40907
Gas manifold assembly
-
5 burner (before 7
-
76)
28 40804 Gas manifold assembly
-
6 burner (after 7
-
76)
40906
Gas manifold assembly
- 6 burner (before 7
-
76)
2S 43652 Pilot generator assembly with 02505 burner, 20411 thermocouple and 52449 bracket
30
2011
Pilot thermocouple
31 02505 Pilot burner
-
Natural Gas
02523 Pilot burner LP Gas
32
52449 Pilot bracket
33
22183
3/4 combination g
as control valve
-
Natural Gas
33A 22189
3/4 combination gas control vale
-
LP Gas
34 15480 3/4 combination orifice
-
Natural Gas
15481 3/4 combination orifice
-
LP Gas
35
22122
3/4 pressure reducing valve,3
-
15 psi output (optional)
36 22130 Safety valve
-
8 psi
22131 Safety valve
-
15 psi
37
22148 Air Vent
38 19947 Pressure switch
39
03514 Low water cutoff relay 115 volt (1C1DO)
40 03504 Water control relay, 115 volt (1D1DO)
41
07173
Steam pressure gauge, rear mount, 0
-
30 psi
42 1—87 On-Off power
switch, 115/220 volt 3 PDT
43 19968 Reset switch
44
12161 Signal light, 115/220 volt
45
19945 Float switch with gasket
-
low water cut off (California only)
46 22104
1/4 solenoid valve
-
boiler condensor water supply
47 19979 Thermal switch
-
boiler condens
or 48 22106 Valve solenoid 1/2" boiler auto blowdown, 115 volt (optional)
48 05263 Radiator Ell. 3/4 union
BTU (5 BURNERS) & 300,000 BTU (6 BURNERS)
Reference
1 43873Boiler shell only, with legs, studs, hand hole plate assembly and top flue bracket.
40297
PART
DESCRIPTION
Boiler shell 43873 above, also including two corrosion resistors,sight gauge, insulation panels, top flue collector
with insulation and cover plate three— probes and extensions with cow box.
CLEVELAND RANGE, INC. 1333 EAST 179th SI., CLEVELAND, OHIO 44110
Page 41
WIRING DIAGRAM FOR 100,000 and 150,000 BTU STEAM GENERATORS, WITH PILOT IGNITION,
WITH AND WITHOUT SAFETY RESET CIRCUIT
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Page 42
WIRING DIAGRAM FOR 100,000 and150,000 BTU STEAM GENERATORS, WITH PILOT IGNITION. WITH
MECHANICAL LOW-WATER FUEL CUTOFF, WITH AND WITHOUT SAFETY RESET CIRCUIT
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification as warranted.
Page 43
STEAM COIL WIRING DIAGRAM
HOW THE ELECTRIC LOW WATER SAFETY SHUT -OFF OPERATES ON
STEAM COIL (ELECTRIC OPERATED) STEAM GENERATORS
Operation — Low Water Safety Shut-Off
When Switch S is closed the following operations occur
1. The primary circuit of Transformer T is energized.
2. When the water level reaches the low water safety cutout
probe extension and the momentary reset switch is
manually closed. Relay Coil RC is energized.
3. When Relay Coil RC is energized, the normally open
contacts close, completing the low water safety circuit
through Contacts 7 and 8, and completing the circuit
through Contacts 3 and 4. energizing Solenoid SV2,
allowing steam to flow into the boiler's steam coil.
If the water level drops below the Low Water Safety Cutout
probe extension, the following occurs:
1. The secondary circuit of Transformer T is broken and the
Relay Coil RC is de-energized. Contacts 7 and 8 and 3
and 4 open, breaking the circuits to Solenoid SV2.
thereby shutting off the flow of steam to the boiler's
steam coil.
The steam Solenoid SV2 will not operate until water level in
the boiler is normal and the reset switch is operated.
Operation — Boiler Drain Condenser
To activate the Boiler Drain Condenser System close Switch
S by placing toggle in the down position.
To drain the boiler, open the boiler drain ball valve. The heat
from the boiler drain water will close the normally open
Thermal Switch TS and energize the condenser Solenoid
Valve SV3. To deactivate the Boiler Drain Condenser System
open Switch S by moving toggle to the center off position.
CLEVELAND/ALCO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 44
SERVICING INSTRUCTIONS— MECHANICAL WATER FILL FOR STEAM
GENERATOR
The water level in the sight gauge should normally be about2/3 full.
If it is not, then (1) the water valve may be scaled up or (2) the water
valve plunger disc is in need of replacement or (3) the adjusting
screw at the top of the valve plunger is set incorrectly or (4) the float
needs to be replaced.
WARNING: Steam under pressure may cause serious
injury and bodily harm when It is accidentally or
carelessly released. Therefore, service of the steam
generator should only be performed by trained and
experienced personnel, thoroughly familiar with
servicing steam generators.
To service the water valve:
1. Turn off all utilities and fuel to steam generator. Drain
steam generator.
CAUTION: Never work on the steam generator while It
is hot or pressurized.
2. Remove hand hole plate from steam generator. Refer to
separate data sheet for proper procedures and cautions.
3. (Inside the steam generator as shown on the diagram).
Remove the float arm pivot screw. Disengage float arm
assembly.
4. Lift out valve plunger disc and install new plunger disc.
5. Remove scale from valve seat and other internal valve
surfaces.
6. Re-insert plunger in valve.
7. Install float arm assembly and check the adjustment. Float
travel should be approximately 6 inches.
8. To increase the travel, turn adjusting screw clockwise. To
decrease, reverse.
9. Re-install hand hole plate, never applying more than 15
ft./lbs- torque to the nut. The hand hole plate should be
cleaned and examined every time it is removed. If the
hand hole plate is chipped or cracked, or over three years
old, install a new one. Because continuous use and
possible abuse cause metal fatigue which weakens the
hand hole plate, a new one should be installed at least
every three years- Replace the gasket at least once a year
— or sooner if it is cracked or hardened. Replace the hand
hole gasket when re-installing the hand hole plate.
10. Close steam generator drain valve. Turn on utilities
and fuel.
11. Check the water level. Proper level in the sight gauge is
about 2/3 full.
12. Start up and observe steam generator long enough to see
that it is operating properly.
13. After the valve plunger disc is installed, order more to
have spares on hand at all times.
If hard water scale created the problem, the use of more
corrosion resistors or more frequent replacement of them is
required. Refer to separate data sheets for maintenance
instructions pertaining to scale problems.
CLEVELAND/ALCO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 45
STEAM COIL GENERATOR (BOILER) ASSEMBLY WITH VARIOUS
CONTROL OPTIONS (INCLUDES BOILERS EQUIPPED WITH 0, 1, or3
PROBES)
CLEVELAND/ALCO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 46
STEAM COIL GENERATOR (BOILER) ASSEMBLY WITH VARIOUS
3/
4
-
Ball valve
3/4" Steam control valve
3/4 "
Steam solenoid valve
3/4" Line strainer
1/4" Ball valve
1/4" Check valve
1/2" Water t
eed solenoid valve
1/4." Line strainer
19
020
**
*
CONTROL OPTIONS (INCLUDES BOILERS EQUIPPED WITH 0, 1, or 3
REFERENCE
NUMBER
2100636Hand note plate assembly, incl. bar. nut. ana gasket
water regulator. steam coil. one corrosionresistor, hand hole plate assembly. (For use with
mechanical pressure regulating valve torcontrolling the steam supply.)
cluding one probe and extension with cover box,tor electric operation of the steam supply controls (solenoid valve in lieu of the mechanicalpressure regulating valve).
note plate assembly. (Equipped with 3 probeholes, for use with electrically controlled water
and steam supplies).
including sight gauge, steam coil. 3 probes and
extensions with cover box (for use with
electrically controlled water ana steam supplies).
April. 1984)
PROBES)
REFERENCE PART NUMBER NUMBER
1962453*Probe extension (tor use only with single probe20101468Probe extension set (3) (for use only with three2-43895Corrosion resistor (no: used with 3 probe2222200
2307169Pressure gauge, bottom mount 0-100-psi)2403277
*Required for electric steam control and electric low water cut-off safety circuit Through November 1982, these components were used
in lieu of the #22151 steam control valve as standard equipment on all 24" and 60" wide cabinets and all California units, but optional on
36" and 42" wide cabinets. After November 1982, the #22151 was not used and the electric controls became standard equipment on all
steam coil generators.
**Required for electric (solenoid valve) water fill, used in lieu of the #43720 water regulator valve, beginning April 1984.
***Optional, if steam supply is wet.
CLEVELAND/ALCO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.