Cleveland PEM36-3K Operators Manual

Page 1
Cleveland Range
UNITED STATES
CANADA
REPAIR MANUAL
PEM24/36/48-2/3K
PGM160/200/250/300-2/3K
PDL/PDM/PDP-2/3K
Model No. PSM-2/3K
1333 East 179th St. Cleveland, Ohio 44110 Phone: (216) 481-4900 • FAX: (216) 481-37S2
Garland Commercial Ranges • 1777 Kamato Rd. Mississanga, Ontario CN L4W 1X4
Phone: (416) 624-0260 • FAX: (416) 624-0623
PS-02
Page 2
Installation Instructions For Steam Generators, Steamers, Steamer/Kettles: Gas Electric Steam Coil
Installation Instructions For AS Models
1) These instructions must be retained By the owner / user tor future referenca. For installation only in noncombustible locations. Gas units am only to be installed in areas that have provisions tor adequate air supply
2) Position: For proper operation and drainage, steam generator must be level. It must be set near a floor drain. Attach 1 1/2" piping to an drain connections to carry exhaust steam away from the cabinet. Ends of drain lines must vent to atmosphere to avoid back pressure. Allow a MINIMUM of 6" clearance to the rear and sides of the equipment. The surrounding area must be free and clear of combustibles.
3) install in accordance with local codes and/or the National Electric Code ANSI/NFPA No. 70-1984. installation in Canada shall be in accordance with the Canadian Electric Code CSA Standard C22-1. A unit mat a connected to electricity must be grounded. A wiring diagram is provided inside the relay box.
4) Connect supply lines for 140 160° hot water, and cold water, to the unit. Water pressure must Be maintained between 35 and 60 PSI. Locations and pressure data are shown on the connection drawing. Long hot water lines should be at least 1/2" IPS. Rush water supply lines thoroughly before connecting. Use water which is low in total solids content and low in gas content. to prevent internal scaling, pitting and corrosion of the steam generator and carry-over of minerals into the steam. Water which is fit to drink can still contain highly detrimental impurities. Refer Water Quality Requirements page.
5) Turn on water supply to steam generator. Water valve is inside of base.
6) Connect fuel supply
Do not store or use gasoline or other flammable vapors and liquids in the
FOR YOUR SA FETY
vicinity of this or any other appliance.
For Steam Coil Steam Generators —
— Connect steam supply Location is shown on the connection drawing. Incoming steam pressure must be regulated between 35 and 45 pa (30 —45 psi for pressure steamers), Install a strainer ahead of the regulating valve. Flush line thoroughly before connecting.
— Connect the outlet end of the steam coil to an inverted bucket trap. Fill trap with water before installing.
— Connect electricity if unit is equipped with electrical controls. Permanent 115V connection is required. Junction
box location is shown on the connection drawing. Unit must be electrically grounded by the installer. For
Gas Fired Generators-
— Post in a prominent location, instructions to be followed in the event the user smells gas This information shall be obtained by consulting the local gas supplier.
— Connect gas: Location and pressure data are shown on the connection drawing, installation snail be in accordance with local codes, or in me absence of local codes, with the National Fuel Gas Code ANSI Z223-1 —1984 Installation in Canada shall be in accordance with Installation Codes tor Gas Burning Appliances and Equipment B149.1 and B149.2 Use a gas pipe joint compound which is resistant to LP gas. Test all pipe joints for leaks with soap and water solution. Allow 12 inch clearance on right side of all Gas Fired Steam Generator models for servicing gas burners and tor proper operation. 12" clearance also provides adequate air openings into me combustion chamber. Never obstruct the flow of combustion and ventilation air. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 kPa). The appliance must be isolated from the gas supply piping systern by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than % psig (3.45 kPa).
— Connect electricity if unit is equipped with electrical controls. Permanent 115V connection a required. Junction box location is shown on the connection drawing. Unit must be electrically grounded by the installer.
— Lighting and Shutdown Instructions: Rip electrical switch on Open water valve. Open gas valve. Slightly depress and turn control knob to "off" for 5 minutes before lighting gas. Turn control knob to "pilot" depress it completety and light pilot burner. Continue to hold knob in tor about 60 seconds, then release. Pilot burner a lighted through hole in panel at bottom of steam generator. Never leave panel off. as this will damage controls. Turn control knob to "on". Depress electrical "reset" switch tor main burner ignition. Burners will not light without water in the steam generator. For main burner off. with pilot on, turn control knob to "pilot"- For main and pilot burner oft slightly depress and turn control knob to "off" Flip electrical switch off. For Electrical Steam Generators
— Connect electric power Location is shown on the connection drawing. Provide connection as required by your unit Electric supply must match power requirements specified on data plate attached to base. Wiring must be adequate to carry required current at rated voltage. A separate fused disconnect must be supplied and instailed. Unit must be electrically grounded by the installer.
CLEVELAND RANGE C0_ 1333 EAST 179th ST., CLEVELAND, OHIO 44110 LITHO IN U-S-A-
Manufacturer reserves right of design improvement or modification, as warranted.
Page 3
7) Turn on electricity at control circuit switch on steamer console A red light glows when electricity is on. If water level is correct steam generator will operate by pressing me "reset" button. Heaters will not work without water in the steam generator This manual reset button must be pressed to start up the generator initially, and to restart the steam generator after every shut oft. or power interruption. No attempt should be made to operate the equipment during a power failure.
8) Check 10 make sure that me water in the sight gauge glass automatically stays at about 2/3 full when the unit is started up.
9) When installation is complete and tree of leaks, refer to Operating Procedures sheet.
Instructions For Steam Generator Care
Protect your steam generator, prolong its life and preserve its performance by giving it the required daily attention, on a regular schedule. Follow servicing instructions for your steam generator which are printed on Data Sheet 260-LC in your Owner s Manual, and also or an adhesive label attached to the unit. To obtain an additional data sheet or label carrying servicing instructions, write to the Cleveland Range Company.
No work should be dorm on the steam generator while it pressurized or hot. Service of the steam generator should only be performed by a trained and experienced service technician, thoroughly My familiar with servicing steam generators. When maintenance or repairs are required, contact a located food service equipment service agency, or call the factory, or a factory representative for the name and address of one in your area.
WARNING
Steam Generator (Boiler) Safety
Rigid regulations govern the design and construction of a boiler. However, the responsibility for the safe and efficient operation of a boiler shifts to the owner/user after the boiler leaves the factory.
A sound boiler if improperly installed, or if improperly maintained, or if improperly repaired, will create a dangerous situation and may cause injury to personnel. Most sates, provinces and some cities nave a boiler safety law. Many underwriters require that their clients' boilers comply with these boiler safety laws. These safety laws call for action by the boiler manufacturer and action by the boiler owner/user. As a manufactur er. The Cleveland Range Company delivers steam generators built me ASME Boiler Code. Section IV. which have been inspected by a National Board Inspector. Also. each Cleveland Range Company boiler is built to comply with the boiler safety law of the state t o which it is sent
Safe and Effecient Boiler Operation Depends on Proper Installation Install the boiler in compliance with following regulations, where they apply:
— The National Fuel Gas Code. ANSI Z223.1-1984 —— installation Codes for Gas Burning Appliances and
Equipment B149.1 and B149.2
— The Cleveland Range Company Installation instruc-
tions
— The National Electrical Code ANSI/NFPA No.70-1984
The water for the boiler should be analyzed by a reputable boiler water specialist to see if the quality will permit safe and efficient boiler operation. Water treatment is becoming increasingly necessary because the quality of water sources is deteriorating. although treatment will not be required in every case. A boiler will not operate properly for very long if the water causes boiler corrosion or scale. Even water which 13 safe to drink may be detrimental to a boiler. Refer to Water quality Requirements page for details.
Safety Requires Periodic Inspection and Maintenance
Any leaks around the boiler's hand note plate must be Quickly stopped. Small leaks, it unchecked, cause corrosion and pitting on the boiler face around the hand hole gasket, making it unsealable.
Application of undue stress on the parts that are used to seal the boiler's hand hole opening, in an attempt to seal an unsealable opening, by sledging the handle of the wrench, by increasing the leverage of the wrench a length of pipe. or by other means, is dangerous because it may result the breakage of parts, or injury. No attempts should be made 10 tighten up the nut on the retaining stud beyond the recommended 15 foot pounds of torque.
When a repair affecting the safety of the boiler is necessary. call a National Board Inspector consultation and advice as to the best method of making the repair, so that the completed work will get his approval. Repairs to the boiler must conform to the applicable provisions in the ASME. Code or the National Board Rules for Repairs.
A boiler will last many years before it has to be retired from service. Periodic inspection will reveal the approaching
retirement time. It a better to schedule a convenient replacement time than to wait for the boiler to fail. When a boiler older man 10 years is replaced, the entire steam generator base assembly should be replaced for a number reasons:
Replacement parts become increasingly difficult to obtain for older controls. — Dependable performance of the new controls can be assured for a longer time. — The new steam generator, including controls, will comply with the latest industry and safety standards.
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHO 44110
— The local and municipal building code (plumbing ana
electrical — The state and city boiler laws — The recommendations of the owner/user's under-writers
Page 4
PRESSURE STEAMER OPERATING INSTRUCTIONS
NOTE: These instructions pertain to steamers equipped with self-contained steam generators (boilers). Forr steamers direct-connected to a remote (in -house) steam source, disregard those instructions which are directly and solely related to the self-contained steam generator. These instructions are to be retained by the owner/user for future reference.
1A Open the cabinet base door and close the drain valve if it is open.
B Make sure the hot and cold water supply valves are open
C For steamers equipped with a gas-fired steam generator (boiler) follow the lighting instructions noted on the instruction label displayed on
the unit before continuing to instruction in item 2.
2 Flip the t oggle switch on front of the cabinet console to "ON" The red console light should then glow and the boiler will automatically
begin filling with water (if it is not already full).
3 After approximately five minutes (after water appears in the sight gauge), depress the ""START" reset button on the console. This will
energize the electric heater elements or ignite the gas burners. This cannot be accomplished until the boiler is full of water.
4 in approximately 15 minutes you will notice the console's steam pressure gauge register 5 pounds. (10 pounds if the boiler is also supplying
steam to a kettle- The upper pressure gauge will register 5 pounds.) You can now preheat the cooking compartments.
5 Compartments should be preheated before use and should be kept hot between loads. If a Kettle and steamer are to be used at the same
time, always heat the kettle unit first. When kettle contents begin to simmer, preheat the steamer compartments- When pressure on the boiler gauge returns to 10 pounds, cooking may begin in the steamer
6 Close and latch door securely. Turn bar handle clockwise until the door gasket just touches the compartment face 7 Start steam supply by pulling steam valve handle out. If fined with automatic timer, set timer for 5 minutes. At the start, compartment
thermostatic traps should release air and wet steam tor about two minutes, then shut off.
8 Seal compartment door by turning bar handle clockwise just until steam leakage stops. DO NOT OVERTIGHTEN. 9 At the completion of the 5 minute preheatin g cycle, push steam valve slowly in, to avoid boilovers. This shuts off the steam supply and also
depressurizes and drains the compartment. If fitted with an automatic timer, the steam shuts off automatically and a bell rings when the timer reaches zero. Setting the timer to "Off" stops the bell.
10 To open compartment door, turn bar handle counter-clockwise and delatch. 11 Cooking can now begin by following the above operating steps #6 through #10, but setting the timer for the required cooking time- At the
end of a cooking cycle 40 minutes long or longer, or when defrosting frozen foods, wait at least two minutes for the compartments) to depressurize and drain before opening the compartment door.
CAUTION: After each cooking cycle, ensure that all water is draining, and not accumulating in the compartment. Should a drain become obstructed, it must be cleared before attempting to cook in that compartment.
12. At the end of each day's operation, flip the console toggle switch to the "Blowdown" position, open t he door in the cabinet base and open the boiler drain valve, (red handle). This "Blowdown" drains the boiler and helps to keep it dean. When the boiler is empty, flip the console toggle switch to the "OFF" position and dose the boiler drain valve
13. It is recommended that the boiler be refilled with water after the "Blowdown" is performed. This can be accomplished by flipping the toggle switch to the "ON" position for a period of five minutes and then returning the switch to the "OFF" position.
1. Blow down the steam generator daily.
2. A periodic boiler inspection must be performed by a qualified serviceman to prolong its life and to minimize service calls
3. At the end of each day's operation, wash the pan slides, drain screen covers, door gaskets, and compartment interiors with mild detergent and warm water- Thoroughly rinse with clean water. Rinse water should drain freely through the compartment drain openings. If it does not, the drain must be cleaned before using the steamer.
4. Once a week. flush each compartment drain with a food service equipment drain cleaner and a deliming solution 5 Once every three months, shut off the water supply (hot and cold), and clean the water line strainers.
6. Compartment thermostatic traps can be disassembled and cleaned, by hand or in a mechanical dishwasher. This procedure is recommended if the traps act sluggishly, as they may if contaminated by grease or other film. If cleaning fails to restore the trap's proper functioning, replace the trap. For more detailed thermostatic trap servicing instruc tions., refer to Data Sheet 260-LH.
TO PROLONG LIFE AND MINIMIZE SERVICE REQUIREMENTS
CLEVELAND RANGE. INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
1
Page 5
7. Shelves, drain screens, and pan slides arc stainless steel, and can be washed safely in a mechanical dishwasher.
8. Exterior Care: Allow steamer 10 cool before washing. Use the same cleaners and cleaning procedures as for other kitchen surfaces of stainless steel and aluminum. Mild soapy water, with a clear water rinse, ;s recommended. DC no: allow water to run into electncal controls- Always turn off equipment power before using water to wash equipment.
9. Compartment Door Care: a. When doors are closed tor preheating or cooking, turn bar handle just enough to stop steam leakage. Overtightening shortens gasket life. b. When doors are open or unlatched. Do not turn bar handle. c Always leave compartment doors ajar when not in use, to extend gasket life and to prevent gaskets from adhering to the steamer.
Unnecessary compression of a gasket shorten it s life.
d Keep bar handle screws clean. Lubricate frequently but not excessively. e. Door gaskets provide many months of service when care is taken to operate doors properly. When a gasket finally wears and does not
maintain an effective seal, it must be replaced. Door gaskets can be replaced easily without special tools or cement, and the steamer may be used immediately afterwards- Remove the old gasket and dean the channel. being careful not to damage the channel. The new gasket can then be pressed into place. Insert the gasket in the corners of the channel first, adjusting the slack evenly between the comers - Then work from the comers to the center. Ridges hold the gasket firmly. The gasket is designed to be oversize, so once it is compressed into the door's channel, it remains firmly in place.
PRESSURE STEAMER SAFETY
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Being the owner of a steamer carries with it the responsibility for Keeping it in as safe a condition as when it was shipped from the factory. Safe steamer operation dictates that every pressure steamer must have the following safety inspection at least every 12 months.
1. Steam Valve Linkages
Have a qualified serviceman examine the steam valve linkages which are attached to the inlet and exhaust valves' operating handles on the left side of the steamer. This pivoted linkage, which is attached to both the steam inlet valve and the steam exhaust valve, must prevent the door's latch from disengaging from its catch when the steamer compartment is pressurized. It is important that the linkage operates as described so that the steamer door cannot be opened when the compartment is pressurized.
It is also important that when the steam valve is closed, the exhaust valve should open. The proper operation of the steam inlet valve and the steam exhaust valve should be confirmed and observed while the steam is on.
2. Pressure Gauge Check each pressure gauge. Gauge pointer must return to zero when the steam generator is shut down. Look
for signs of water, rust, corrosion, or scale, inside the pressure gauge. A faulty pressure gauge should be replaced immediately.
a Door Gaskets
Inspect and replace compartment door gaskets once a year, or sooner if they are torn or hardened. The use of a hardened gasket produces undue stress in the parts which comprise the door enclosure and may result in breakage and injury.
4. Compartment Thermostatic Trap
Observe compartment thermostatic traps for proper operation. A good compartment trap, at start-up of a cooking cycle, is normally open and releases air and wet steam briskly for a few minutes. then holds steam within compartment. If brisk venting doesn't begin immediately at start-up, or if brisk venting continues without stopping, and the compartment trap is over a year old, it should be cleaned, or a new one installed- Refer to data sheet 260-LH for details
5 Compartment Steam Exhaust Valves and Drain Valves
Make sure that the compartment steam exhaust valves, and the drain lines attached to them, are free of food buildup internally and are venting freely to the atmosphere. If drain lines from other steam-consuming equipment have been connected to the drain line from the steamer, the other drain lines should be disconnected. Never operate a compartment without the drain screen cover in place.
6. Refer to separate data sheets for steam generator operation, maintenance, and safety procedures.
WARNING
Service of steam cooking equipment should only be performed by a trained and experienced service technician, thoroughly familiar with servicing steam equipment. No work should be performed on the steamer while it is pressurized or hot. Be sure all energy sources are shut off before the start of any work. When maintenance or repairs are required, contact a local food service equipment service agency, or call the factory. or a factory representative, for the name and address of one in your area.
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
2
Page 6
PRESSURE STEAMERS: THERMOSTATIC TRAP AND
COMPARTMENT DOOR GASKET REPLACEMENT
The thermostatic trap and door gasket on your steamer stop the escape of steam from the compartment during operation. Steam leakage from either source will cause loss of pressure. which will result in longer cooking time. wasted Steam and excessive condensation.
To keep your steamer operating at peak efficiency. thermostatic traps and compartment door gaskets require periodic replacement Frequency of replacement vanes from one piece of equipment to another depending on the amount of usage, and frequency and quality of maintenance.
A normal thermostatic trap at Startup releases air and wet steam briskly for the first few minutes, then holds steam within the compartment. During cooking, the trap will also release accumulated condensate ana a small amount of air
It brisk venting doesn't begin immediately at startup or if brisk venting continues for much longer than two minutes. and the compartment trap is over a year old, it should be cleaned, or removed and a new one installed.
A compartment trap less than a year old may act sluggishly only because it is contaminated by grease and other film. To remove a thermostatic trap. unscrew the union nut as shown on the sketch. To clean the trap. unscrew the threaded! diaphragm cover from the body and wash the entire assembly. A more thorough cleaning can be accomplished by removing and disassembling the trap. and washing the entire assembly in a mechanical dish washer. With proper tools, the threaded diaphragm cover can be unscrewed from the body. and the thermostatic diaphragm can be unscrewed from the diaphragm cover, if the trap does not work property after thorough cleaning. install a new one. If the steamer is used heavily for cooking foods contain ing large amounts of fat or starch. periodic cleaning is recommended as a routine procedure
Replace the gaskets on compartment doors once a year. or sooner if they are torn or hardened. Door gaskets can be replaced easily without special tools or cement, and the steamer may be used immediately afterwards.
Remove the old gasket and clean the channel, being careful not to damage the channel. The new gasket can then be pressed into place. insert the gasket in the corners of the channel first, adjusting the slack evenly between the comers. Then work from the comers to the center.
Ridges hold the gasket firmly. The gasket is designed to be oversize, so once it is compressed into the door's channel, it remains firmly in place.
COMPARTMENT THERMOSTATIC TRAP
COMPARTMENT DOOR GASKET REPLACEMENT
WARNING
Service of steam cooking equipment should only be performed by a trained and experienced service technician, thoroughly familiar with servicing steam equipment, No work should be performed on the steamer while it is pressurized or hot, Be sure all energy sources are shut off before the start of any work. When maintenance or repairs are required, contact a local food service equipment service agency, or call the factory, or a factory representative, for the name and address of one in your area.
CLEVELAND RANGE CO.. 1333 EAST 179th ST, CLEVELAND, OHIO 44110
Page 7
MODELS B, C, F, K PRESSURE STEAMERS DOOR
1 25303
Door Ann With Bushings
— Model B
&
C, Polished
25304
Door Arm With Bushings
— Model F
&
K. Polished
2
02568
Door Arm Hinge Bushing
(2
Req
uired) 3 41370
Standard Door Ann Screw With Ball
(1" x 8
thread)
41371
Oversize Door Ann Screw With Ball 1 3/32" x
8
thread)
4
081001
Screw Handle Bar, Polished
5
16305
Pin 6 15250
Oil Cup
7
122011
Door Ann Latch
— Model B, C.
&
F Chrome Plated
122021
Door Ann Latch
— Model K Chrome Plated
8
101018
Door Arm Latch Pin
— Model B, C, F,
&
K Brass
163101
Door Ann Latch Pin
— Model B, C, F,
&
K Chrome Plated
9
081031
Door Retainer
— Model B, C, F,
&
K Chrome Plated
10
19291
Screw
11
041631
Door
, Model B Polished
04164
Door, Model C Polished
04165
Door, Model F
&
K Polished
12
07132
Door Gasket
— Rubber, Model B
07134
Door Gasket
— Rubber, Model C, F, K
13
023001
Door Arm Hinge Post Bolt (Upper)
— Concentric Type
— 14
023061
Door Arm
Hinge Post Bolt (Lower)
— Eccentric Type
— 15
14643
Nut, For Lower Hinge Post Bolt
16
23181
Shim Washer
17
40547
60 Minute Bell Timer Assembly
18
08601
Timer Housing
— Model B
&
C Polished (Not Available)
08606
Timer Housing
— Model F Polished (Not
Available)
AND DOOR ARM ASSEMBLY
REFERENCE NUMBER
PART NUMBER DESCRIPTION
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 8
MODEL J DOOR AND DOOR ARM ASSEMBLY
1 253021
Door Arm W/Bushings, Polished
2 02568
Door Arm Hinge Bushing
(2
Required)
3
41370
Standard Door Arm Screw With Ball
(1" x 8
thread)
41371
Oversize Door Arm Screw W
ith Ball (1 3/32'' x
8
thread)
4
081001
Screw Handle Bar, Polished
5
16305
Pin 6 15250
Oil Cup
7
41360
Striker Plate and Pin
8
43723
Door Hanger w/Screws and Washers
(2
Required)
9
53035
Door Arm Insert, Stainless
10
04162
Polished Aluminum Door, Le
ss Gasket
11
07136
Door Gasket
— Rubber
12
68140
Retainer, Yoke Hanger
(2
Required)
13
19228
Screw
14
23182
Washer
15
122001
Door Arm Latch, Chrome Plated
16
163141
Door Arm Latch Pin, Chrome Plated
17
18306
Retainer Clip,
(2
Required)
18
023001
Door Arm Hinge Post Bolt (Upper)
— Concentric Type
— 19
023061
Door Arm Hinge Post Bolt (Lower)
— Eccentric Type
— 20
14643
Nut, For Lower Hinge Post Bolt
21
23181
Shim Washers
REFERENCE NUMBER
PART NUMBER DESCRIPTION
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 9
MECHANICAL COMPARTMENT CONTROLS
MODEL K PRESSURE STEAMERS-
DEC. 1977 THRU PRESENT
Page 10
MECHANICAL COMPARTMENT CONTROLS MODEL K PRESSURE
STEAMERS-DEC. 1977 THRU PRESENT
REFERENCE PART NUMBER NUMBER DESCRIPTION 1 40650 Pull Rod Handle 2 22130 Valve, Safely, 8 psi 3 70411 Tee, Special 3/4" 4 22140 Air Vent 5 42270 Inlet Manifold Ass'y.2-Compl.Mech. "K", Less Valves
42279 Inlet Manifold Ass'y.3-Compl.Mech. "K", Less Valves
6 07173 Gauge, Pressure, Rear Mount, 0 30 psi, 2 1/2"
07168 Gauge, Pressure, Rear Mount, 0-30 psi, 2"
7 42290 Exhaust Manifold Ass'y.—2-Compl., Model "K", Less Valves
42291 Exhaust Manifold Ass'y—3-Compl,, Model "K", Less Valves
8 02146 "Y" Bend 9 05263 Ell, 3/4" Radiator Union 10 20551 Thermostatic Trap—Plain End 11 05252 Ell, 1/2" Street 12 22212 Valve, 1/2 Ball, Inlet Steam 13 22213 Valve, 1" Bullerlly, Exhaust Steam 14 41100 Drain Cover Screen (Before 7/17/85)
69333 Drain Cover Screen (After 7/18/85) A 43765 Bushing Ass'y. B 40677 Linkage Ass'y., Model "K" C 42670 Conversion Kit, Inlet Valve—'K" Mech., Includes:
1/2" Inlet Steam Valve, 1/2" Street Elbow, 1/2 x 4" NIppIe, 1/2" x 2 1/4" Special Nipple, (2) Locknuts, (2) Sealing Washers
D 40710 Conversion Kit, Exhaust Valve, Includes:
1" Exhaust Steam Valve, (2) 1" x 3/4" Bushings, 3/4" Close Nipple, Drain Cover Screen
NOTE: FOR SAFETY PURPOSES, DRAIN SCREEN COVER MUST BE IN PLACE WHEN OPERATING EQUIPMENT.
Page 11
AUTOMATIC COMPARTMENT CONTROLS
MODEL K PRESSURE STEAMERS-
DEC. 1977 THRU PRESENT
Page 12
AUTOMATIC COMPARTMENT CONTROLS
MODEL K PRESSURE STEAMERS DEC. 1977 THROUGH PRESENT
1 40650
Pull Rod Handle
2 22130
Valve, Safety,
8
PSI 3 70411
Tee, Spe
cial 3/4" 4
22140
Air Vent
5
42298
Inlet Manifold Ass'y.
2-
Compl
Auto "K", Less Valves
42299
Inlet Manifold Ass'y.
3-
Compt.
Auto "K", Less Valves
6
22115
Valve, 1/2" Steam Inlet Solenoid
7
03278
Valve, Steam By
-
Pass 8 42290
Exhaust Manifold Ass'
y. 2-Compl,, Model "K", Less Valves
42291
Exhaust Manifold Ass'y
—3-
Compl., Model "K", Less Valves
9
43764
"Y" Bend
with 1/4" Tapped Hole
10
05263
Ell, 3/4" Radiator Union
11
20551
Thermostatic Trap
Plain End
12
22199
3/4
Solenoid Valve, Auto Exhaus
t,
115
Volt, For Use With
40518
Timer
22185
1/4" Solenoid Valve, Auto Exhaust,
115
Volt, For Use With
40540
Timer
13
07172
Gauge, Pressure, Bottom Mount,
0-30
PSI 14 40518
Timer,
60
Min, Mechanical (Mfg. # 70000)
15
19977
Switch
-
SPST 16 12
161 Signal Light,
1"
12169
Signal Light, 1
/2 17 07173
Pressure Gauge, Rear Mount,
0-30
psi, 2 1/2"
07168
Pressure Gauge, Rear Mount,
0-30
psi,
2" 18 41350
Buzzer
19
40540
Timer,
105
Min, (Mfg.
601) 20 22212
Valve, 1/2" Ball, Inlet Steam
21
22213
Valve,
1"
Butterlly, Exhaust Steam
22
41100
Drain Cover Screen (Before
7/17/85)
69333
Drain Cover Screen (After
7/18/85)
A
43765
Bushing Ass'y.,
B
40677
Linkage Ass'y., Model "K"
C
40711
Conversion Kit, Inlet Valve
-
"K" Auto, Includes:
1/2"
Inl
et Steam Valve,
3/8" Tube Ftng,
3/8"— 90°
Tube Ftng.,
(2)
1/2" Close Nipples,
1/2" x 2 1/4" Special Nipple 1/2 x
3/8" x 1/2 Tee,
3/8" x
6"
Tube,
(2)
Lock
-
nuts,
(2)
Sealing Washers.
D
40710
Conversion Kit, Exhaust Valve, Includes:
1" Exhaust
Steam Valve,
(2) 1"
x 3/4" Bushings, 3
/4
Close Nipple,
Drain Cover Screen.
REFERENCE NUMBER
PART NUMBER DESCRIPTION
NOTE: FOR SAFETY PURPOSES, DRAIN SCREEN COVER MUST BE IN PLACE WHEN OPERATING EQUIPMENT
Page 13
INTERMEDIATE DRAWOUT & LIFTOUT SHELF MODELS
1 • 19500
Angle Slide, Draw
-
Out Shelf, Model B, Right (Not Available)
• 19502
Angle Slide, Draw
-
Out Shelf Model B, Left (Not Availab
le) *19501
Angle Slide, Draw
-
Out Shelf, Model F, Right (Not Available)
19503
Angle Slide, Draw
-
Out Shelf, Model F, Left (Not Available)
2
42183
Draw-Out Intermediate Shelf, Model B
42814
Draw-Out Intermediate Shelf, Model F, J,
& K 3
43737
Fast
ener Assembly,
2
Per Slide, Includes
19216
Screw and
23109
Lockwasher
4
42180
Lift-Out Shelf, Model B
42181
Lift-Out Shelf, Model F
& K 5
08440
Lift-Out Shelf Hook,
4
Required Per Shelf
B, F, J, AND K PRESSURE STEAMERS
REFERENCE NUMBER
PART NUMBER DESCRIPTION
Substitute: 4 ea. — 08440 Hooks 1 ea. — 42181 Shelf
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 14
AUTO SHELF ASSEMBLY MODELS B & F
1 41445
Angle Slide Ass'y With Rollers, Models B
&
F, Includes
2
Weld Studs
19915
(Current, Since
1968)
(Shown)
41446
Angle Slide Ass'y With Rollers. Mod
els B & F, Includes
2
Hex Mount
ing Studs
19924
41447
Angle Slide Ass'y With Rollers, Models B
&
F, Includes Original Style
Body Mounting Bolt
&
Washers, etc.
2
01250
Angle Casting, Machined, Welded Stud, Models B
& F 01251
Angle Casting,
Machined. Hex Stud, Models B
& F 01252
Angle Casting, Machined. Bolted Stud, Models B
& P 3
14629
Lockout
4
19900
Roller Stud
5
23133
Washer
6
18720
Roller
7
19572
Roller Spring
8
43800
Shelf Arm
&
Connecting Rod Ass'y, Model B
43801
Shelf Ann
&
Connecting Rod Ass'y, Model F (Shown)
9
51002
Sliding Shelf Arm, Model B
51004
Sliding Shelf Arm, Model F (Shown)
10
42190
Connecting Rod, Model B
42191
Connecting Rod, Model F (Shown)
11
42185
Auto Sliding Shelf. Model B
42186
Auto Sliding
Shelf, Model F (Shown)
PRESSURE STEAMERS
REFERENCE NUMBER
PART NUMBER DESCRIPTION
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 15
MODELS J AND K PRESSURE STEAMER
SLIDE SETS
REFERENCE NUMBER 1 41440 Pan Support Slide Set, Model J Complete
2 41430 Right or Left Side Slide Rack, 2 Per Compt Req'd. Model J
3 41435 Center Slide Rack Model J, 1 Req'd Per Compt
4 19909 Replacement Top Studs (Screw-In) J or K (Set of 6)
PART NUMBER DESCRIPTION
41442 Pan Support Slide Set, Model K Complete
41432 Right or Left Side Slide Rack, 2 Per Compt Req'd. Mode) K
41437 Center Slide Rack Model K, 1 Req'd Per Compt
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 16
START-UP MAINTENANCE PROCEDURES STEAM GENERATOR
IMPORTANT: These instructions must be followed in order to prevent premature failure of the steam generator
START-UP:
1) Open the cabinet base door and close me drain valve if it is open (Red Handle lever marked "blowdown")
2) Flip the toggle switch on front of the cabinet console
to "ON" (up position). The red console light should then glow and wter will automatically begin filling the generator.
3) When the water level in the sight gauge galss (on the generator) reaches approximatley 2/3 full (afer approximately five minutes0. depress the "ON" reset button on the console. This will energize the electric heater elements or ignite the gas burner. If the sight gauge glass is completely filled, have the generator serviced.
4) In approximatley ten minutes you will notice the steam pressure gauge, on the console, register the steam pressure contained inside the generator.
5) Cooking may now begin. Refer to "Cooking" and "Opening Procedure" data sheets for specific instructions.
MAINTENANCE:
1) At the end of each day's operation, while the generator is pressurized, flip the console toggle switch to the "Blowdown" position, open the door in the cabinet base and open the generator's drain valve.(red handle). This "Blowdown" procedure drains the water out f the generator and helps to prevent lime scale formation. When the generator is empty, flip the console toggle seitch to the "OFF" position and close the generator's drain valve. It is recommended that the generator be refilled with water after the "Blowdown" is performed. This can be accomplished by flipping the toggle switch to the "ON" position for a period of five minutes and then returning the switch to the "OFF" position.
CAUTION:
Service on the generator should only be performed by a trained and experienced service technician, thoroughly familiar with servicing steam generators. No work should be done on the steam generator while it is pressurized or hot. Be sure all energy sources are shut off before the start of any work.
2) Even though the "Blowdown" is performed faithfully each day, it will still be necessary to periodically inspect the inside of the generator. The generator's hand hole plate should be removed at regular intervals so that it is removed. If the hand hole plate is chipped or cracked, or over three years old, install a new one. Replace the corrosion resistor if necessary, and chemically descale the the generator if it is coated with lime scale. A new hand hole gasket should always be installed.
3) It will be necessary to periodcally have scale accumulations removed from the inside of the steam generator by a qualified service tchnician. Generator descaling instructions are provided on a seperate data sheet. Failure to periodically remove scale from the inside of the generaotr will result in greatly reduced generator life.
4) Every steam generaotr is equipped with at least one corrosion and scaling. This corrosion resistor is sacrificial and must be replaced at regular intervals just before it is entirely consumed. In areas where the water is very hard, the feedwater must also be treated to remove the harmful mineral content.
Refer to seperate data sheets for corrosion resistor servicing instructions.,feedwater treatment information, and hand hole plate servicing instructions.
5) Check the safety valve once a week while steam generaotr is pressurized. Test by pulling safety valve extension wire. Valve must open freely and snap closed when released. If it does not or if it drips constantly, a new safety valve is needed.
6) If the steam generator is to be left idle for three months or mre, it should be drained and dried out and the hand hole plate left off.
7) Water level in the sight gauge normally should be about 2/3 full. This level is maintained automatically.
Refer to seperate data sheet for either mechanical or water fill servicing instructions.
8) If gas fired the lighting instructions are on the AGA rating plate. Pilot burner is lit through hole in panel at bottom of steam generator. This panel should never be left off as this will damage the controls. Burners will not light without water in the steam generator.
CLEVELAND RANGE CO, 1333 EAST 179th ST.. CLEVELAND, OHIO 44110
Manufacturer reserves right of desingn improvement or modification as warranted.
Page 17
WATER QUALITY REQUIREMENTS STEAM
GENERATOR PROTECTION AND MAINTENANCE A steam generator, or boiler unlike other types of water- using kitchen equipment, distills the water in order to make steam. Nearly all feed-water sources contain dissolved minerals in varying degrees of concentration. As this water is boiled, pure steam rises from it's surface, upward to the cooking compartments, leaving minerals behind, that can become harmful to the steam generator. If minerals are allowed to accumulate inside the steam generator, they will solidify as a scale. Then malfunctioning will occur, and serious equipment damage may result.
The use of good quality generator feed water is the responsibility of the owner/user. The use of poor quality feed water could void equipment warranties. The minimum treatment required in most areas is water softening, although local water conditions may require more intensive pretreatment than simply a water softener. Scale problems occur when feed water is high in hardness, total dissolved solids, silica, and alkalinity. Water softening will only reduce the water's hardness which is the presence of dissolved salts of magnesium and calcium. Water softening will not affect the multitude of other minerals, the best property to control, for generator feed water, is total dissolved solids, not just hardness. the recommended minimum water quality standards, whether untreated or pretreated, based upon 10hours of use per day, and a Daily Blowdown are as follows:
TOTAL DISSOLVED SOLIDS less than 60 parts per million TOTAL ALKALINITY less than 27 parts per million SILICA less than 13 parts per million pH FACTOR greater than 7.5
Consult a local water treatment specialist for an on the premises water analysis and for recommendations concerning steam generator and feed water treatment (if required) in order to remove or reduce harmful concentrations of minerals.
If the recommended water quality requirements are met without supplemental treatment or if treatment is applied resulting in feed water quality meeting the prescribed standards the steam generator will need to be blown down only once each day. In addition the inside of the generator requires an inspection (for excessive lime accumulation and consumed corrosion resistors) only once every six months. Replace the corrosion resistor and chemically descale the generator as required.
If a pre-treatment unit cannot be installed, and the recommended water quality requirements are not met, the following procedures should be followed in order to achieve maximum steam generator service life. The steam generator is heavily coated with scale, have it chemically descaled by a qualified service technician.
INSTRUCTIONS FOR CHEMICALLY DESCALING STEAM GENERATORS
Warning: Steam under pressure may cause serious injury and bodily harm when it is accidentally or carelessly released. Improper handling of acid could cause serious permanent injury. Therefore, service of the steam generator should only be performed by trained and experienced personnel, thoroughly familiar with servicing generators.
There are a number of commercial descaling chemicals available produced by various manufacturers. Those utilizing a sulfamic acid base, which can be identified by its powdered form are sage and compatable with our food preparation equipment. It is imperative that the acid used for descaling be FDA approved for use in food preparation equipment. Various manufacturers may include additional chemicals to increase potency and therefore, instructions are not provided with the deliming chemical you purchase the following general guidelines may be followed.
WARNING: Exercise care when handling acid. Avoid contact with skin, eyes, or clothing. Wear safety glasses or face shield along with rubber gloves and rubber apron. In case of exposure to clothing, remove clothing and flush with water. In case of exposure to skin or eyes, flush with water for 15 minutes and get immediate medical attention. Do not take internally. Keep out of the reach of children.
Be sure the generator has been drained, de-pressurized, and is cool. Open the hand hole access plate on the front of the generator and place approximately 8-10 pounds of sulfamic acid inside the generator. Put a new hand hole plate and replace the hand hole plate tightening the bar and nut assembly to a maximum of 15 foot pounds torque. The generator must be completely filled with hot water (fill the generator beyond its normal, automatic fill point to 2/3 up in the sight gauge.) On mechanical fill generators this can be accomplished by adding weight to the float or removing the float and regulating the fill level with a hand valve in the water supply plumbing. On electric fill generators (with probes) this can be accomplished by temporarily jumpering terminals #3 & #4 of the water control relay. Turn the main on-off toggle switch to the "ON" position then turn the switch to the "OFF" position when the generator is completely filled. Let the solution stand for several hours, then flush with water. Rinse with a solution of bicarbonate of sods to neutralize any acid residue and again flush with water.
CAUTION: Never tighten the hand hole plate nut when the steam generator is in use, hot, or otherwise pressurized. Never tighten nut over 15 foot pounds torque. Overtightening may cause uneven stress, which may result in the weakening and possible breakage of the plate.
CLEVELAND RANGE CO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Page 18
MAINTENANCE INSTRUCTIONS FOR STEAM GENERATORS
(EXCEPT THOSE EQUIPPED WITH TWO PROBES)
WARNING: Steam under pressure may cause serious injury and bodily harm when it is accidentally or carelessly released. Therefore, service of the steam generator should only be performed by trained and experienced personnel, thoroughly familiar with servicing steam generators.
CAUTION: Never work on the steam generator when
it is hot or pressurized.
Every steam generator shipped in equipped with at least one corrosion resistor (cathodic). The larger capacity steam generators will have two corrosion resistors.
The hand hole plate and gasket on your steam generator stops the escape of steam through the hand hole opening during operation.
1) Turn off all energy sources to steam generator. Drain steam generator.
2) Remove hand hole cover plate from steam generator.
3) Hang corrosion resistor from the right side of the front stay rod, away from the probes. Clean scale and rust off a portion of the stay rod so the hanger will rest on the bright, bare metal.
4) Re-install the hand hole plate, along with a new gasket.
The hand hole plate should be cleaned and examined every time it is removed. If the hand hole plate is chipped or cracked or over three years old, install a new one. Because continuous use and possible abuse cause metal fatigue which weakens the hand hole plate. a new one should be installed at least every three years.
CAUTION: Never tighten the hand hole plate nut when steam generator is in use, hot, or otherwise pressurized. Never tighten nut over 15 foot pounds torque. Overtightening may cause uneven stress, which may result in the weakening and possible breakage of the plate.
er
CLEVELANO RANGE CO, 1333 EAST 179th ST., CLEVELAND. OHIO 44110
Replace the gasket whenever the hand hole plate is removed or replaced. Keep a spare gasket on hand at all times. Replace the gasket at least once a year, or sooner if it is cracked, torn, or hardened.
Leakage of water past the hand hole plate should not be allowed to continue as this will cause pitting of the metal in contact with the gasket.
5) After re-installing the hand hole plate, close the steam generator drain valve. Turn on energy sources.
6)Start up and operate steam generator long enough to observe that it is operating properly.
The corrosion resistor is sacrificial and must be replaced at regular intervals just before it is entirely consumed. Frequency of replacement can only be established by a regular inspection for how much of the protector remains and whether scaling or pitting has begun. Scaling indicates a very hard water condition. In either case, more protectors or more frequent replacement of them in necessary. The best way to reduce servicing time and to assure long generator life is to provide feed water that is low in solids content and low n gas content. Water that is fit to drink can still be high in impurities that are highly detrimental to a steam generator. Consult a water treatment specialist in your area for recommendations concerning steam generator feed water treatment.
Under average conditions, the corrosion resistor provides about six months of service. An average condition would meet each of the following tests:
1. Less than 8 hours of steam generation a day.
2. One generator blowdown every day
3. Moderatley hard water. Less than 85 ppm.
4. Water containing less than 60 ppm Total Dissolved Solids.
Page 19
STEAM GENERATOR (BOILER) IDENTIFICATION
Service Note The above drawings showing the sight gauge location and method of mounting are for assisting in determining the proper part number for replacement generators. When ordering please provide both the proper part number and the equipment's serial number.
CLEVELAND RANGE CO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Page 20
SERVICING INSTRUCTIONS STEAM PRESSURE ADJUSTMENTS
WARNING: Adjustments must be made only by trained and experienced service personnel.
Normally there is no need to make pressure adjustments on a new steamer, because the proper settings are made at the factory.
In some cases however, the factory setting may shift due to shaking in transit, and resetting will be required after installation. The factory pressure settings shown on the accompanying chart should never be exceeded.
For Gas and Electric Steam Generator
Steam pressure is controlled with two pressure switches located toward the upper-front of the cabinet either to the extreme right.
The left switch is the operating pressure switch. This switch controls the pressure in the steam generator, which is the pressure indicated on the steam generator pressure gauge. The right switch is a high limit, pressure safety control. It breaks an electric circuit to shut off the energy source if the steam pressure rises above a safe level. Each switch has a screw on top of the case to permit the pressure set point to be adjusted without removing the cover. The correct settings are shown in the accompanying chart. The pressure switch indicator scale is for reference only. Actual pressure should be read on the pressure gauge and the pressure switch adjusted to produce the proper pressure gauge reading. Some models may also have a pressure reducing valve to control the pressure in the steam line to the steamer The adjustment of this discussed further on.
For Steam Coil Steam Generator
The steam supply to steam coil generators is controlled by one of two methods.
Steam generator pressure may be controlled by a pilot operated pressure regulating valve. The steam generator pressure can be adjusted by turning the adjusting collar, identified on the sketch. A steel rod is provided to turn the collar. The correct settings are shown in the accompanying chart.
On steam coil generators equipped with an electric solenoid valve to control the steam supply to the steam generator, one or two pressure switches control the steam generator pressure. To adjust the switch(es), turn the screw on the top of the case to achieve the pressure reading shown in the accompanying chart.
Pressure Reducing Valve-Adjustment and Care A screw at the top of the valve body, as shown on the sketch, permits the pressure set point to be adjusted. The locknut must be loosened before adjustment is made, and tightened after. Turning adjustment screw into housing raises pressure. If excessively high or low pressure
cant be corrected by adjustment, install a new valve. To eliminate erratic performance, the internal steam strainer should be cleaned periodically. The strainer can be reached by unscrewing the large hex head plug at the bottom of the valve
body.
(CONTINUED ON THE REVERSE SIDE)
CLEVELAND RANGE, INC, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification as warranted.
Page 21
Contained
Generator Only
Steam Generator Only
Super Steamcraft, or
GAUGE PRESSURE READING WITH NO STEAM FLOW (STATIC PRESSURE)
Self-Contained Steam Generator Gas or Electric
Self- Steam Coil Generator
Direct Connect ( To House Steam Supply)
Equipment Steam
5 PSI
Pressure Steamer N/A 5 psi 10 psi N/A 5 psi 5 psi N/A
Pressure Steamer With Any Kettles)
10 psi
Kettle Only-All N/A 10 psi 15 psi N/A N/A N/A 20 psi Convection Steamer,
"D" Series Defroster With or Without Kettles
Steamer's Pressure Reducing Valve
N/A 5 psi 10 psi N/A 5 psi N/A N/A
5 psi 10 psi 15 psi 5 psi 10 psi 5 psi 20 psi
N/A 10 psi 15 psi N/A 10 psi N/A N/A
N/A 10 psi 15 psi N/A 10psi 10 psi 20 psi
Operating
Pressure
Switch
High Limit Safety Pressure Switch
Steamer's Pressure Reducing Valve
Pressure Regulati ng Valve or Pressure Switch
Steamer's
Pressure
Reducing
Valve
Kettle's Pressure Reducing Valve
CLEVELAND RANGE, INC., 1333 EAST 179th ST.. CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification as warranted.
Page 22
SERVICING INSTRUCTIONS
PROBE SYSTEM: ELECTRIC WATER FILL AND ELECTRIC LOW WATER FUEL CUT OFF FOR STEAM GENERATOR 3 PROBE TYPE
WARNING: Service of the steam generator must be performed only by trained and
During operation of the steam generator. The water level is maintained automatically by unequal length probe extensions inside The probes and extensions must be kept clean and free of scale deposits in order to function properly
The probe extensions are sensors in a control system which monitors and maintains the water level between the end of the short probe extension
and the end of the intermediat e extension.
The long probe, called "Low Water." is a safety sensor which shuts off
experienced service technicians.
the fuel supply if there is insufficient water in the steam generator. Since the control system is all electric and these parts don't move or
wear, they can be expected to have a Ions life. If they do malfunction, it is generally because untreated hard feedwater is being used in the steam generator. This forms scale on the submerged ends of the probe extensions and on the top horizontal surfaces of the probes. After this scale is removed, the parts will function properly.
To eliminate the cause of scaling, refer to separate data sheets for feedwater treatment information and corrosion protector servicing instructions. Probes and probe extensions should be wiped clean each time the corrosion protector is replaced.
Erratic operation may result from loose connections on either end of the probe. The external end of the probe has a nut to hold the wiring terminal snugly to the probe. This nut, if loose, may be tightened, firmly but gently. Too much torque will turn the center peice of the probe and misalign the attached probe extension inside, causing the probe to become inoperative.
inside the steam generator, the screw which holds the probe extension to the probe may be loose, allowing the probe extension to swing or rest against some part of the steam generator. This can be corrected by removing the hand hole plate and reaching inside to align and hold the probe extensions vertically while tightening the screws.
To Service the Probes or the Probe Extensions
1) Turn off all utilities and fuel to steam generator. Drain Steam generator.
CAUTION: Never work on the steam generator when it is hot or pressurized.
2) Remove probe cover on outside of steam generator to expose probe terminals. Examine for loose wiring terminals.
3) Remove hand hole cover plate from steam generator. See separate data sheet for instructions.
4) Remove probe extensions from probes on inside of steam generator, clean off scale, and re-install Or. install new probe extensions if preferred.
5) Remove scale from the probe (see sketch above) Do not use an abrasive on the teflon insulator. If the old probe needs replacement, install a new one.
(CONTINUED ON THE REVERSE SIDE)
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 23
CONTINUES
SERVICING PROBE SYSTEM: ELECTRIC WATER FILL AND INSTRUCTIONS ELECTRIC LOW WATER FUEL CUT OFF FOR STEAM GENERATOR 3 PROBE TYPE
6 Assemble probe extensions to probes on inside of steam generator so they hang vertically, parallel to each other Malfunctioning
will occur if an extension touches any part of the steam generator or another probe extension
7) If insulation on electrical wires to the probe snows signs of being broken, cut or deteriorated, the wires should be replaced
8) Connect wire terminals on outside of steam generator to probe terminals as follows:
Red wire to the shortest probe. Turns water off. Black wire to the intermediate probe. Turns water on White wire to the longest probe- Shuts off fuel (low water safety fuel shut-off)
9) Re-install hand hole plate and install a new gasket. The hand hole plate should be cleaned and examined each time it is removed. If the plate is chipped or cracked it should be replaced
immediately. Because continuous use and possible abuse can cause metal fatigue which weakens the hand hole plate, a new one should be installed at least every three years. Replace the gasket at least once a year —or sooner if it is cracked or hardened.
10) Replace probe cover and check to make sure that the cover does not contact probes.
11) Close steam generator drain valve. Turn on utilities and fuel supply to steam generator.
12) Operate and observe steam generator long enough to insure that it is functioning properly. Low Water Fuel Cut Off Test
Proper operation of the "Low Water" probe extension should be checked periodically, by someone who is thoroughly familiar with the equipment.
To Test: Open the drain of the steam generator while fuel is on- When the water has drained below the "Low Water" probe, the fuel should shut off automatically- Indication of fuel shut off should occur just as the water level in the sight gauge drops from view. If it does. close the drain, allow the steam generator to refill, and resume normal operations. If the fuel does not shut off. immediately turn the on-off toggle switch to the "off position, and follow the steps outlined under "To Service the Probes or the Probe Extensions" as given on the reverse side of this sheet.
For specific information pertaining to the operation of the electric water fill controls, and electric low water safety fuel cut-off, refer to the following data sheets:
Electric Steam Generators Gas-Fired Steam Generators
Steam Coil (electric operated) Generators
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 24
STANDING PILOT-IGNITION TYPE GAS CONTROLS FOR GAS- FIRED STEAM GENERATORS
CAUTION: The following procedures, as well as other work on the gas controls, should be performed only by a trained and experienced service technician, thoroughly familiar with gas controls.
Built in gas controls assure safe and automatic operation of the pilot and main burners of the steam generator The controls consist of a pilot generator (thermocouple and a unit called the combination gas control This latter unit consists of a gas valve operator
and servo gas pressure regulator Generally, there is no need to make an adjustment to any portion of the gas system. The main burner orifices and the pilot burner orifice installed at the factory are correct for the kind of gas specified on the purchase order Also. the primary air supply to the main burner is properly adjusted for complete combustion.
Lighting and Shutdown Instructions Flip electrical switch on. Open water valve Open gas valve Slightly depress and turn control knob to "off" for 5
minutes before lighting gas. Turn control knob to "pilot." depress it completely, and light pilot burner. Continue to hold Knob in for about 60 seconds, then release. Pilot burner is lighted through hole in panel at bottom of steam generator Never leave panel off. as this will damage controls. Turn control knob to "on". Depress electrical switch. for main burner ignition Burners will not light without water in the steam generator. For main burner off. with pilot on control knob to pilot". For main and pilot burner off. slightly depress and turn control knob to "of" Flip electrical switch off
Occasionally due to regional differences in the gas supply the pilot burner flame may require adjustment.
A normal flame is mostly blue and steady, and envelops 3/8" to 1/2 of the tip of the pilot generator, as illustrated at right
The pilot gas adjusting screw can be found under a cover screw located near the gas control knob. illustrated below
To adjust the pilot flame:
1) Remove the pilot adjustment cover screw 2 Turn PILOT FLOW ADJUSTMENT SCREW clockwise-—to
decrease or counterclocKwise—to increase pilot flame.
3) WARNING: Be sure to replace cover screw after adjustment to prevent possible gas leakage
Electrical connections in the pilot generator circuit must be dean and secure. Because the pilot generator operates in a severe environment, it may eventually need a replacement. The time before replacement will vary from one piece of equipment to another, depending on the amount of usage. The pilot generator (thermocouple) should generate 450-750 MV in an open circuit condition. When a malfunction is traceable to the combination gas control unit. it is recommended that the entire unit be replaced with a new one. rather than attempting repairs to the old unit.
WARNING: To prevent the danger of possible gas leakage, the installer must be a trained and experienced service technician, thoroughly familiar with gas controls.
CLEVELAND RANGE CO.. 1333 EAST 179th ST.. CLEVELAND. OHIO 44110
Page 25
HOW THE ELECTRIC (WARRICK RELAY) WATER LEVEL CONTROLS OPERATE ON GAS FIRED STEAM GENERATORS (WITH 3 PROBES)
Inside Cleveland Range Co- boilers which have electric water level controls, there are three probe extensions vertically oriented above the water with their lower ends positioned at various levels
Water is admitted to the boiler and is shut oft in response to the water level sensed by the tips of the short and the medium length probe extensions The electrical conductance of the water is used in this system tor controlling its level. The third probe extension is a low water safety cutout sensor and
operates on the same principle. Operation Sequence Water Level Control
Assume an empty Boiler To fill. close Switch S for the following operations:
1) Solenoid SV, is energized allowing the boiler to fill with water at the same time the primary circuit of Transformer T, is also energized.
2; The boiler will continue to fill until the water level reaches the Water Off probe extension completing the T, secondary circuit, and energized Relay Coil RC.
3) When Relay Coil RC. is energized the normally closed contact opens, de -energizing Solenoid SV; stopping the water fill. The normally open contact is closed, complet ing the circuit to the Water On probe.
When the water boils away below the end of the Water On probe extension the following occurs:
1) The secondary circuit of Transformer T, is broken and the Relay Coil RC, is de-energized
2) When Relay Coil RC, is de-energized the normally open contact opens, breaking the circuit to the Water Off probe extension. And. the normally closed contact closes, energizing Solenoid SV; allowing the boiler to fill as in Step 2 above.
Operation — Low Water Safety Cutout
When Swit ch S is closed the following operations occur
1) The primary circuit of Transformer T2; is energized.
2) When the water level reaches the low water safety cutout probe extension and the momentary reset switch is manually closed. Relay Coil RC, is energized.
3) When Relay Coil RC; is energized the normally open contacts close, completing the low water safety circuit through Contacts 7 and 8 and completing the circuit through Contacts 3 and 4. completing the 750 millivolt pilot generator circuit and allowing the gas control package valve to operate.
If the water level drops below the Low Water Safety Cutout probe extension, the following occurs:
1) The secondary circuit of Transformer T2 is broken and the Relay Coil RC2 is de -energized- Contacts 7 and 8 and 3 and 4 open. breaking the 750 millivolt circuit
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted
which shuts off the flow of gas to the burners. The burners will not operate until water level in the boiler is normal and the reset switch is operated.
Operation-Boiler Drain Condenser
To activate the Boiler Drain Condenser System close switch S by placing toggle in the down position. To drain boiler, open boiler drain ball valve. The heat from the boiler drain water will close the normally open thermal switch TS and energize the condenser solenoid valve SV, . To de-activate the Boiler Drain Condenser System open switch S by moving toggle to center off position.
Page 26
HOW THE ELECTRIC (WARRICK RELAY) WATER LEVEL CONTROLS OPERATE ON ELECTRIC STEAM GENERATORS (WITH 3 PROBES)
inside Cleveland Range Co - boilers which have electric water level controls, there are three probe extensions vertically oriented above the water with their lower ends positioned at various levels.Water is admitted to the boiler and is shut off in response to the water level sensed by the tips of the short and the medium length probe extensions The electrical conductance of the water is used in this system for controlling its level. The third probe extension is a low water safety cutout sensor and operates on the same principle. Operation Sequence Water Level Control Assume an empty boiler. To fill. close Switch S tor the following operations:
1) Solenoid SV; is energized allowing the boiler to fill with water at the same time the primary circuit of Transformer T, is also energized.
2) The boiler will continue to fill until the water level reaches the Water Off probe extension completing the T, secondary circuit, and energizing Relay Coil RC,.
3) When Relay Coil RC, is energized the normally closed contact opens, de -energizing Solenoid SV2 stopping the water fill. The normally open contact is closed, completing the circuit to the Water On probe. When the water boils away below the end of the Water On probe extension the following occurs:
1)) The secondary Circuit of Transformer T, is broken and the Relay Coil RC, is de -energized.
2) When Relay Coil RC, is de -energized the normally open contact opens, breaking the circuit to the Water Off probe extension. And. the normally closed contact closes, energizing Solenoid SV2 allowing the boiler to fill as in Step 2 above.
Operation — Low Water Safety Cutout
When Switch S is closed the following operations occur
1) The primary circuit of Transformer T2 is energized.
2) When the water level reaches the low water safety cutout probe extension and the momentary reset switch is manually closed. Relay Coil RC2 is energized.
3) When Relay Coil RC2 is energized the normally open contacts dose, completing the low water safety circuit through Contacts 7 and 8, and completing the circuit through Contacts 3 and 4. energizing Contactor Coil C which closes the heater circuit
If the water level drops below the Low Water Safety Cutout probe extension, the following occurs:
1) The secondary circuit of Transformer T2, is broken and the Relay Coil RC2 is de -energized- Contacts 7 and 8 and 3 and 4 open. breaking the circuits to Contactor C., thereby turning off the heaters.
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
The Contactor C, will not operate until water level in the boiler is normal and the reset switch is operated.
Operation-Boiler Drain Condenser To activate the Boiler Drain Condenser System .close switch S by placing toggle in the down position. To drain boiler, open boiler drain ball valve. The heat from the boiler drain water will dose the normally open thermal switch TS and energize the condenser solenoid valve SV3,. To de-activate the Boiler Drain Condenser System open switch S by moving toggle to center off position.
Page 27
ELECTRIC STEAM GENERATOR (BOILER) ASSEMBLY - 3 PROBE TYPE
24KW, 36KW, & 48KW (2, 3, & 4 HEATER ELEMENTS) - 1968 to PRESENT
Page 28
ELECTRIC STEAM GENERATOR (BOILER) ASSEMBLY 3 PROBE TYPE
heater elements.
43938 Boiler shell
(43937)
above. also including two corrosion resistors, sight gauge. three probes and
extensions with cover box.
2
43895 Co
rrosion resistor. with hanger
3
40445 Water gauge set with glass.
07106 Fibre washer
(2
required)
23132 Gauge glass washer
(2
required).
4
07302 Glass only
6'
long. 5 40462 Probe with lock washer and screw
6
101467
Probe extension set
(3). 7 40421
Hand note plate ass
-
'y.. including bar. nut. and gasket
4374S Hand hole plate only.
8
07106 Hand note gasket, flat.
4- x
6"
oval 9 08165 Electric immersion heater. with gasket.
3"
flange.
12KW. 208/220
volt. 3 phase.
08166 Electric immersion hea
ler, with gasket.
3"
flange.
12KW. 230/240
volt, 3 phase.
08167 Electric immersion heater, with gasket.
3"
flange. 12KW. 440/480 volt.
3
phase.
08214 Electric immersion heater, with gasket.
3"
flange.
12KW, 208/220
volt 1 phase.
08215 Electric imm
ersion heater, with gasket.
3"
flange.
12KW. 230/240
volt, 1 phase.
08216 Electric immersion heater, with gasket.
3"
flange.
12KW.
440/480 volt.
1
phase.
08175 Electric immersion heater. with gasket.
2 1/2 "
flange,
12KW.
208/220 volt.
3
phase. 08176 Electric immersion heater with gasket. 2 1/2" flange,
12KW. 230/240
volt. 3 phase
08177 Electric immersion heater, with gasket. 2 1/2" flange,
12KW.
440/480 volt.
3
phase 10 07128 Heater gasket
square.
07115 Heater gasket
2 1/2" square.
11
53250 Probe cover.
12
03504 Water control relay,
115
volt (1D1DO).
13
03514 Low water cut
-
off relay.
115
volt. (1C1DO).
14
03276 1/4 " ball valve water supply shutoff.
15
22102 1/4" check valve.
16
44095 1/2" water teed solenoid valve
17
19870 1/4" "
line Strainer.
18
03509 Contactor
amp.
03506 Contactor
amp. 19 20533 Transformer 75VA (All, except Convection Steamers).
20
02193 Heavy duty terminal block
(125
amp
). 20A 02196 Heavy duty termina
l block
(250
amp size).
24KW.
220
volt single phase and 48KW.
208
. 220 & 240
volt. three phase.
21
20535 Transformer. 150VA, (Convection Steamers only).
22
03202 Circuit breaker for
20535.
23
19947 Pressure switch
(Models after
1-70) 24 22130 Safety valve
psi
22131 Safety valve
psi 25 19968 Reset switch.
26
19944 On-Off power switch.
115/220
volt DPST (before
1-78).
19967 On-Off power switch. 115 volt 3PDT (after 1
-
78) and all auto blowdown.
27 12161 Signal light. 115/220
volt. 1"
12169 Signal light.
115/220
volt. 1/2" (Pressure Steamers only).
28
07173 Steam pressure gauge, rear mount.
0-30
psi. 2 1/2".
07168 Steam pressure gauge, rear mount. 0
-
30 psi.
2"
(Pressure Steamers only)
29
03277 Generator drain valve
30
22140 Air vent.
31
40471 Control enclosure.
32
52558 Cover, control enclosure.
33
22122 3/4" pressure reducing valve.
3-15
psi output (optional).
34 19945 Float switch with gasket
only). 35 22104 1/4 ~ solenoid valve
36
19975 Thermal switch
37 22106 Valve, solenoid.
1/2" boiler auto blowdown.
115
volt (optional).
24KW, 36KW, & 48KW (2, 3, & 4 HEATER ELEMENTS) 1968 to PRESENT
REFERENCE PART NUMBER NUMBER
DESCRIPTION
SIZE
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 29
ELECTRIC STEAM GENERATOR (BOILER) ASSEMBLY
18KW, 27KW, and 36KW (3 ELEMENTS 6, 9, or 12KW EACH)
PRIOR TO 1968
Page 30
REFERENCE NUMBER PART NUMBER DESCRIPTION 1 40425 Hand Hole Plate Assembly
16650 Hand Hole Plate Only 2 07116 Hand Hole Gasket 3 40446 Water Gauge Set With Glass
07108 Fibre Washer (2 Required)
23132 Gauge Glass Washer (2 Required)
4 07301 Glass Only 10 1/2" Long 5 43720 Water Regulator Valve Assembly 6 06300 Float Only
7 43740 Float Arm and Block Assembly
8 02411 Float Pivot Bracket 9 23 130 Sealing Washer 10 43735 Float Plunger Assembly. 3 1/2" 11 16833 Plunger Disc 12 43724 Water Regulator Valve Sub-Assembly 13 43895 Corrosion Resistor 14 22130 Safety Valve — 8 psi
22131 Safety Valve — 15 psi
15 22140 Air Vent 16 16820 Pigtail.1/4" ips 17 19947 Pressure Switch 18 12161 Signal Light 115/220 Volt 19 19944 On-Off Power Switch. 115/220 Volt DPST 20 03503 Contactor tor Side Heater. 50 amp. 208/240 Volt Coil
03505 Contactor tor Side Heater. 75 amp. 208/240 Volt Coil 21 20532 Transformer — Optional (480/240/120 Volt Only) 22 08170
08171
08184
08172
08180 Electric Immersion Heater. Screw Type. 9KW. 240 Volt
08185 Electric Immersion Heater. Screw Type. 9KW. 480 Volt
08182 Electric Immersion Heater. Screw Type. 12KW. 208 Volt
08181
08183 23 08201 Heater. Screw Type. With Thermostat. 6KW. 208 Volt (Not Available)'
08200 Heater. Screw Type. With Thermostat. 6KW. 240 Volt
08204 Heater. Screw Type. With Thermostat 6KW. 480 Volt
08203 Heater. Screw Type. With Thermostat 9KW. 208 Volt (Net Available)*
08202 Heater. Screw Type. With Thermostat 9KW. 240 Volt (Not Available)'
08205 Heater. Screw Type. With Thermostat 9KW. 480 Volt (Not Available)' 24 19945 Float Switch With Gasket — Low Water Cut-off
Electnc Immersion Heater. Screw Type. 6KW. 208 Volt Electnc Immersion Heater. Screw Type. 6KW. 240 Volt Electric Immersion Heater. Screw Type. 6KW. 480 Volt Electric Immersion Heater. Screw Type. 9KW. 208 Volt
Electnc immersion Heater. Screw Type. 12KW. 240 Volt Electric Immersion Heater. Screw Type. 12KW. 480 Volt
• Consult factory tor conversion to a low water cut-off float switch type of safety circuit
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 31
WIRING DIAGRAM ELECTRIC STEAM
WIRING DIAGRAM FOR ELECTRIC STEAM GENERATORS
GENERATORS
WITH ELECTRICAL LOW-WATER HEATER CUTOFF, WITHOUT
MANUAL SAFETY RESET CIRCUIT PRIOR TO JANUARY, 1978
CLEVELAND RANGE CO, 1333 EAST 179th ST.. CLEVELAND. OHIO 44110
Page 32
CLEVELAND RANGE CO.. 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 33
GAS STEAM GENERATOR (BOILER) ASSEMBLY NO PROBES
100,000 BTU (2 BURNER) & 150,000 BTU (3 BURNER)
Page 34
GAS STEAM GENERATOR (BOILER) ASSEMBLY NO PROBES 100,000 BTU (2
1 40300 Boiler Shell Only, With Legs, Studs. Hand Hole Plate Assembly, and Top Flue Bracket.
1
1
3/4" Boiler Drain Valve
1/2" Combination Natural Gas Control Valve
2"
Combination LP Gas Control Valve
3/4" Pressure Reducing Valve.
3-15
psi Output (Optional)
BURNER) & 150,000 BTU (3 BURNER)
REFERENCE NUMBER
2 40425 Hand Hole Plate Assembly Including Bar, Nut. Gasket, and Hand Hole Plate 2A 16545 Hand Hole Plate Only 3 07116 Hand Hole Gasket 4 43895 Corrosion Resistor 5 40446 Water Gauge Set With Glass
6 07301 Glass Only—10 1/2" Long 7 43720 Water Regulator Valve Assembly 8 06300 Float Only 9 43740 Float Ann and Block Assembly 10 02411 Float Pivot Bracket
12 43735 Float Plunger Assembly, 3 1/2" 13 16833 Plunger Disc 14 43724 Water Regulator Valve Sub-Assembly 15 22112 Water Shut Off Angle Valve 16 22150 17 16621 Fusible Plug With Bushing 18 19945 Float Switch With Gasket—Low Water Cut-Off 19 02498 Main Gas Burner—24" Long
20 15453 Main Burner Orifice—Natural Gas 21 19632 Orifice Holder (After 7/76) 22 63150 Gas Manifold—100.000 BTU—2 Burner 23 22182 24 43651 Pilot Generator Assembly With 02505 Burner. 20410 Thermocouple. 52449 Bracket and 15460
25 20410 Pilot Thermocouple 26 02505 Pilot Burner—Natural Gas
27 15460 Pilot Burner Orifice—Natural Gas 28 52449 Pilot Bracket (After 7/76)
28A 52450 Pilot Bracket (Before 7/76) 29 07173 Pressure Gauge. Rear Mount—0 to 30 psi 30 19967 On-Off Power Switch. 115/220 Volt 3 PDT 31 19968 Reset Switch 32 12161 Signal Light. 115/220 Volt 33 19947 Pressure Switch 34 22140 Air Vent 35 22130 Safety Valve—8 psi
36 22122 37 69934 Rear Baffle and Burner Support—100,000 BTU—2 Burner
38 52171 Burner Compartment Front Baffle—100.000 BTU—2 Burner 39 70920 Twister
PART NUMBER
40307 Boiler Shell Only, With Clip Locks, Studs. Hand Hole Plate Assembly, and Top Flue Bracket 43826 Boiler Shell 40300 Above. Also Including One Corrosion Resistor. Sight Gauge. Low Water Cut-Off
43828 Boiler Shell 40307 Above. Also Including One Corrosion Resistor. Sight Gauge. Low Water Cut-Off
07108 Fibre Washers (2 Req'd.) 23132 Gauge Glass Washers (2 Req'd.)
23130 Sealing Washer
02499 Main Gas Burner—20" Long 02501 Main Gas Burner Used on Units Built Before 7/76 (not shown). Replace With Burner 02498 (24"
15450 Main Burner Orifice—LP Gas
19631 Orifice Holder (Before 7/76) 63151 Gas Manifold—150.000 BTU—3 Burner
22096
43653 Pilot Generator Assembly with 02523 Burner. 20410 Thermocouple. 52449 Bracket, and 15461
02523 Pilot Burner—LP Gas 15461 Pilot Burner Orifice—LP Gas
22131 Safety Valve—15 psi
69935 Rear Baffle and Burner Support—150.000 BTU—3 Burner 52172 Burner Compartment Front Baffle—150.000 BTU—3 Burner
DESCRIPTION
Switch, and Water Regulator. Switch, and Water Regulator.
Long) or 02499 (20" Long). 1963 Orifice Holder, and One 52450 Pilot Bracket (If Pilot's Burner is Replaced.)
1/
Orifice. Orifice.
CLEVELAND RANGE, INC., 1333 EA ST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 35
GAS STEAM GENERATOR (BOILER) ASSEMBLY 3 PROBE TYPE
210,000 BTU (5 BURNERS)
Page 36
GAS STEAM GENERATOR (BOILER) ASSEMBLY 3 PROBE TYPE
REFERENCE
NUMBER
PART
NUMBER
1 40302
Boiler Shell Only. With Legs, Studs. Hand Hole Plate Assembly, and Top Flue Bracket.
40309
Boiler Shell On
ly, With Angle Iron Mounting Bar, Studs. Hand Hole Plate Assembly, and
Top Flue Bracket.
43832
Boiler Shell
40302
Above, Also Including: Two Corrosion Resistors. Sight Gauge. Three
Probes and Extensions With Cover Box.
43833
Boiler Shell
40
309
Above, Also Including: Two Corrosion Resistors. Sight Gauge, Three
Probes and Extensions With Cover Box.
2
40425
Hand Hole Plate Assembly Including Bar, Nut. and Gasket
2A
16545
Hand Hole Plate Only
3
07116
Hand Hole Gasket
4
43895
Corrosion R
esistor
(2
Req'd.)
5
40446
Water Gauge Set With Glass
07108
Fibre Washers
(2
Req'd.)
23132
Gauge Glass Washers
(2
Req'd.)
6
07301
Glass Only, 10 1/2" Long
7
40462
Probe With Lockwasher and Screw
8
40455
Probe Extension Set
9
52350
Probe Cover
10 19870
1/4
" Line Strainer
11
44095
1/2" Water Feed Solenoid Valve
12
02499
Main Gas Burner
02500
Main Gas Burner Used on Units Built Before
7/76
(Not Shown). Replace With Burner
02498
24"
Long or
02499
20"
Long.
19632
Orifice Holder, and One
52450—
Pilot Bracket (If Pilot's Burner Is Replaced.)
13
15453
Main Burner Orifice
Natural Gas
15450
Main Burner Orifice
LP Gas
14
19632
Orifice Holder (After
7/76)
19631
Orifice Holder (Before
7/76)
15
63152
Gas Manifold
210,000 BTU
—5 Burner
16
22183
3/4" Combination Natural Gas Control Valve
16A 22189
3/4" Combination LP Gas Control Valve
17
43651
Pilot Generator Assembly With
02505
Burner,
20410
Thermocouple.
52449
Bracket, and
15460
Orifice.
43653
Pilot Generator Assembly With
02523
Burner,
20410
Thermocouple,
52449
Bracket, and
15461
Orifice.
18
20410
Pilot Thermocouple
19
02505
Pilot Burner
Natural Gas
02523
Pilot Burner
LP Gas
20
15460
Pilot Burner Orifice
Natural Gas
15461
Pilot Burner Orifice
LP Gas
21
52449
Pilot
Bracket (After
7/76)
21A 52450
Pilot Bracket (Before
7/76)
22
52177
Burner Compartment Front Baffle
23
69933
Burner Compartment Rear Baffle
24
07173
Pressure Gauge. Rear Mount
—0 to
30
psi 25 19941
On-
Off Power Switch,
115/220
Volt.
4
PDT 26 19968
Reset Switch
27
12161
Signal Light
115/220
Volt 28 19947
Pressure Switch
29
22140
Air Vent
30
22130
Safety Valve
—8 psi
22131
Safety Valve
—15 psi 31 22122
3/4" Pressure Reducing Valve.
3-15
psi Output (Optional)
32
19945
Float Switch With Gasket
Low
Water Cut
-
Off 33 03504
Water Control Relay,
115
Volt
(1
D1DO)
34
03514
Low Water
Cut-Off
Relay,
115
Volt (1C1DO)
35
22150
3/4" Boiler Drain Valve
36
16621
Fusible Plug With Bushing
37
70920
Twister
210,000 BTU (5 BURNERS)
DESCRIPTION
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 37
GAS STEAM GENERATOR (BOILER) ASSEMBLY 3 PROBE TYPE
160,000 BTU (3 BURNER) & 200,000 BTU (4 BURNER)
Page 38
GAS STEAM GENERATOR (BOILER) ASSEMBLY 3 PROBE TYPE 160,000 BTU
40298
Boiler shell
43872
above, also including two corrosion resistors, sight gauge, insulation panels, top flue
collector with insulation and cover plate, three probes and extensions with cover box.
2
40421
Hand hole plate assembly inc
luding bar. nut and gasket
2A
43748
Hand note plate only
3
07106
Hand hole gasket flat
4x6
oval. 4 43941
Left side insulating panel assembly
5
43943
Right side insulating panel assembly.
6
56320
Top flue collector.
7
40115
Top insulation baffle asse
mbly (flat).
40116
Top insulation baffle assembly (with flange).
8
42360
Internal flue riser assembly.
9
40462
Probe with lock washer and screw.
10
40455
Probe extension set
(3). 11 52350
Probe cover.
12
43895
Corrosion resistor.
13
40445
Water ga
uge set with glass.
07108
Fibre washer
(2
required).
23132
Gauge glass washer
(2
required).
14
07302
Glass only
long. 15 43851 3-
burner front baffle assembly
43855 3-
burner front baffle assembly
16
43852 4-
burner
front baffle assembly
43856 4-
burner front baffle assembly
17
41365 3-
burner rear burner support (after
7-76).
69952 3-
burner rear burner support (before
7-76). 18 41366 4-
burner rear burner support (after
7-76).
69953 4-
burner rear burner support (before
7-76). 19 19870
1/4" fine strainer.
20
44095
1/2" water feed solenoid valve.
21
22102
1/4 check valve.
22
03276
1/4" ball valve
-
off. 23 03277 Generator drain valve
24
02499
Main g
as burner.
25
15453
Main burner orifice
15450
Main burner orifice
- 26 40901 Gas manifold assembly
burner (after
7-76).
40905
Gas manifold assembly
burner (before
7-76). 27 40902
Gas manifold assembly
burner (af
ter 7-
76).
40906
Gas manifold assembly
burner (before
7-76) 28 19632
Orifice holder (after
7-76).
19631
Orifice holder (before
7-76). 29 43651
Pilot generator assembly with
02505
burner.
20410
thermocouple.
52449
bracket and
15460
orifice.
4
3653
Pilot generator assembly with
02523
burner.
20410
thermocouple.
52449
bracket and
15461
orifice.
30
20410
Pilot thermocouple.
31
02505
Pilot burner
02523
Pilot burner
32
52449
Pilot bracket
33
15460
Pilot burner orific
e —
Natural Gas.
15461
Pilot burner orifice
34
22182
1/2 combination gas control valve
35
22122 3/4" pressure reducing valve.
3-15
psi output (optional).
36
22130
Safe
ty valve
psi.
22131
Safety valve
—15 psi. 37 22140
Air vent
38
19947
Pressure switch.
39
03514
Low water cut
-
off relay.
115
volt (1C1DO).
40
03504
Water control relay.
115
volt.
(1D1
DO). 41 07173
Steam pressure gauge, rear mount
0-30
psi. 42 19
967
On-Off power switch.
115/220
volt 3 PDT. 43 19968
Reset switch.
44
12161
Signal light
115/220
volt 45 19945
Float switch with gasket
-
off (California only).
46
22104
1/4" solenoid valve
47
19979
Ther
mal switch
48
22106
Valve, solenoid.
1/2" boiler auto blowdown.
115
volt (optional).
49
05263
Radiator Ell.
3/4" union.
(3 BURNER) & 200,000 BTU (4 BURNER)
REFERENCE NUMBER
PART NUMBER DESCRIPTION
CLEVELAND RANGE CO., 1333 EAST 179th ST, CLEVELAND. OHIO 44110
Page 39
GAS STEAM GENERATOR (BOILER) ASSEMBLY 3 PROBE TYPE
250,000 BTU (5 BURNERS) ft 300,000 BTU (6 BURNERS)
Page 40
GAS STEAM GENERATOR (BOILER) ASSEMBLY 3 PROBE TYPE 250,000
NUMBER
NUMBER
2 40421 Hand Hole Plate Assembly including bar. nut and gasket
2A 43748 Hand hole plate only.
3
07106 Hand hole gasket fla
t
4x6
oval. 4 43942 Left side insulating panel assembly
5
43943 Right side insulating panel assembly
6
56321 Top flue collector
7
40117
Top insulation baffle assembly (flat)
48118 Top insulation
baffle assembly (with flange)
8 42361 Internal flue riser assembly
9
40462 Probe with lock washer and screw
10
40455 Probe extension set (3)
11
52350
Prove cover
12 43895
Corrosion resistor
13 40445 Water gauge set with glass
07108 Fibre washer (
2 required)
23132 Gauge glass washer (2 required)
14 07302 Glass only
-
6" long
15
43853 5 burner front baffle assembly
-
Natural Gas
43857 5
burner front baffle assembly
-
L.P. Gas
16
43854 6 burner front assembly
-
L.P Gas
6 burner front assembly
-L.P 17 41367 5
burner rear burner support (after 7
-
76)
5
burner rear burner support (before 7
-
76)
18 41368 6 burner rear burner support (after 7
-
76)
89955 6 burner rear burner support (before 7
-
76) 19 18870 1/4" line strainer
20
44095
1/2"water
feed solenoid valve
21 22102 1/4" check valve
22 03276
1/4"ball valve
-
water supply shut off
23
02499 Main gas burner
24 15453 Main burner orifice
-
Natural Gas
15450 Main burner orifice
-
LP Gas
25
19632 Orifice Holder (after 7
-
76)
19631 Orifice Hol
der (before 7
-
76) 26 03277
Generator drain valve
-
ball type
27 40903
Gas manifold assembly
-
5 burner (after 7
-
76)
40907
Gas manifold assembly
-
5 burner (before 7
-
76)
28 40804 Gas manifold assembly
-
6 burner (after 7
-
76)
40906
Gas manifold assembly
- 6 burner (before 7
-
76)
2S 43652 Pilot generator assembly with 02505 burner, 20411 thermocouple and 52449 bracket
30
2011
Pilot thermocouple
31 02505 Pilot burner
-
Natural Gas
02523 Pilot burner LP Gas
32
52449 Pilot bracket
33
22183
3/4 combination g
as control valve
-
Natural Gas
33A 22189
3/4 combination gas control vale
-
LP Gas
34 15480 3/4 combination orifice
-
Natural Gas
15481 3/4 combination orifice
-
LP Gas
35
22122
3/4 pressure reducing valve,3
-
15 psi output (optional)
36 22130 Safety valve
-
8 psi
22131 Safety valve
-
15 psi
37
22148 Air Vent
38 19947 Pressure switch
39
03514 Low water cutoff relay 115 volt (1C1DO)
40 03504 Water control relay, 115 volt (1D1DO)
41
07173
Steam pressure gauge, rear mount, 0
-
30 psi
42 1—87 On-Off power
switch, 115/220 volt 3 PDT
43 19968 Reset switch
44
12161 Signal light, 115/220 volt
45
19945 Float switch with gasket
-
low water cut off (California only)
46 22104
1/4 solenoid valve
-
boiler condensor water supply
47 19979 Thermal switch
-
boiler condens
or 48 22106 Valve solenoid 1/2" boiler auto blowdown, 115 volt (optional)
48 05263 Radiator Ell. 3/4 union
BTU (5 BURNERS) & 300,000 BTU (6 BURNERS)
Reference
1 43873 Boiler shell only, with legs, studs, hand hole plate assembly and top flue bracket.
40297
PART
DESCRIPTION
Boiler shell 43873 above, also including two corrosion resistors,sight gauge, insulation panels, top flue collector with insulation and cover plate three probes and extensions with cow box.
CLEVELAND RANGE, INC. 1333 EAST 179th SI., CLEVELAND, OHIO 44110
Page 41
WIRING DIAGRAM FOR 100,000 and 150,000 BTU STEAM GENERATORS, WITH PILOT IGNITION,
WITH AND WITHOUT SAFETY RESET CIRCUIT
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Page 42
WIRING DIAGRAM FOR 100,000 and 150,000 BTU STEAM GENERATORS, WITH PILOT IGNITION. WITH
MECHANICAL LOW-WATER FUEL CUTOFF, WITH AND WITHOUT SAFETY RESET CIRCUIT
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification as warranted.
Page 43
STEAM COIL WIRING DIAGRAM
HOW THE ELECTRIC LOW WATER SAFETY SHUT -OFF OPERATES ON
STEAM COIL (ELECTRIC OPERATED) STEAM GENERATORS
Operation — Low Water Safety Shut-Off When Switch S is closed the following operations occur
1. The primary circuit of Transformer T is energized.
2. When the water level reaches the low water safety cutout probe extension and the momentary reset switch is manually closed. Relay Coil RC is energized.
3. When Relay Coil RC is energized, the normally open contacts close, completing the low water safety circuit through Contacts 7 and 8, and completing the circuit through Contacts 3 and 4. energizing Solenoid SV2, allowing steam to flow into the boiler's steam coil.
If the water level drops below the Low Water Safety Cutout probe extension, the following occurs:
1. The secondary circuit of Transformer T is broken and the Relay Coil RC is de-energized. Contacts 7 and 8 and 3 and 4 open, breaking the circuits to Solenoid SV2. thereby shutting off the flow of steam to the boiler's steam coil.
The steam Solenoid SV2 will not operate until water level in the boiler is normal and the reset switch is operated.
Operation — Boiler Drain Condenser
To activate the Boiler Drain Condenser System close Switch S by placing toggle in the down position. To drain the boiler, open the boiler drain ball valve. The heat from the boiler drain water will close the normally open Thermal Switch TS and energize the condenser Solenoid Valve SV3. To deactivate the Boiler Drain Condenser System open Switch S by moving toggle to the center off position.
CLEVELAND/ALCO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 44
SERVICING INSTRUCTIONS MECHANICAL WATER FILL FOR STEAM
GENERATOR
The water level in the sight gauge should normally be about 2/3 full. If it is not, then (1) the water valve may be scaled up or (2) the water valve plunger disc is in need of replacement or (3) the adjusting screw at the top of the valve plunger is set incorrectly or (4) the float needs to be replaced.
WARNING: Steam under pressure may cause serious injury and bodily harm when It is accidentally or carelessly released. Therefore, service of the steam generator should only be performed by trained and experienced personnel, thoroughly familiar with servicing steam generators.
To service the water valve:
1. Turn off all utilities and fuel to steam generator. Drain steam generator.
CAUTION: Never work on the steam generator while It is hot or pressurized.
2. Remove hand hole plate from steam generator. Refer to separate data sheet for proper procedures and cautions.
3. (Inside the steam generator as shown on the diagram). Remove the float arm pivot screw. Disengage float arm assembly.
4. Lift out valve plunger disc and install new plunger disc.
5. Remove scale from valve seat and other internal valve surfaces.
6. Re-insert plunger in valve.
7. Install float arm assembly and check the adjustment. Float travel should be approximately 6 inches.
8. To increase the travel, turn adjusting screw clockwise. To decrease, reverse.
9. Re-install hand hole plate, never applying more than 15 ft./lbs- torque to the nut. The hand hole plate should be cleaned and examined every time it is removed. If the hand hole plate is chipped or cracked, or over three years old, install a new one. Because continuous use and possible abuse cause metal fatigue which weakens the hand hole plate, a new one should be installed at least every three years- Replace the gasket at least once a year — or sooner if it is cracked or hardened. Replace the hand hole gasket when re-installing the hand hole plate.
10. Close steam generator drain valve. Turn on utilities and fuel.
11. Check the water level. Proper level in the sight gauge is
about 2/3 full.
12. Start up and observe steam generator long enough to see
that it is operating properly.
13. After the valve plunger disc is installed, order more to have spares on hand at all times.
If hard water scale created the problem, the use of more corrosion resistors or more frequent replacement of them is required. Refer to separate data sheets for maintenance instructions pertaining to scale problems.
CLEVELAND/ALCO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 45
STEAM COIL GENERATOR (BOILER) ASSEMBLY WITH VARIOUS
CONTROL OPTIONS (INCLUDES BOILERS EQUIPPED WITH 0, 1, or 3
PROBES)
CLEVELAND/ALCO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Page 46
STEAM COIL GENERATOR (BOILER) ASSEMBLY WITH VARIOUS
3/
4
-
Ball valve
3/4" Steam control valve
3/4 "
Steam solenoid valve
3/4" Line strainer
1/4" Ball valve
1/4" Check valve
1/2" Water t
eed solenoid valve
1/4." Line strainer
19
020
**
*
CONTROL OPTIONS (INCLUDES BOILERS EQUIPPED WITH 0, 1, or 3
REFERENCE NUMBER
2 100636 Hand note plate assembly, incl. bar. nut. ana gasket
3 07116 Hand hole gasket 4 40401 Steam coil assembly 5 14612 1 1/4 Brass locknut 6 23135 3% " Square flat washer 7 14611 T'A " Steel tocknut 8 40446 Water gauge set with glass
9 07301 Glass only -10%" tong 10 43720 Water regulator valve assembly (used before
11
12 43740 Float arm and block assembly
13 100655 Float pivot bractet 14 23130 Sealing washer
15 43735 Float plunger assembly 16 16833 Plunge- disc
17 43724 Water regulator valve sub-assembly (seat) 18 40462 Probe with lockwasher and screw
PART NUMBER
43700 Steam coil broiler shell with legs. sight gauge.
43782 Steam coil boiler shell (43700) above, also in
439881 Steam coil boiler shell only. with legs and hand
43989 Steam coil boiler shell (43988) above, also
16545 Hand hole plate only
07106 Rbre Washer (2 required) 23132 Gauge Glass Washer (2 required)
06300 Float only
DESCRIPTION
water regulator. steam coil. one corrosion resistor, hand hole plate assembly. (For use with
mechanical pressure regulating valve tor controlling the steam supply.)
cluding one probe and extension with cover box, tor electric operation of the steam supply con trols (solenoid valve in lieu of the mechanical pressure regulating valve).
note plate assembly. (Equipped with 3 probe holes, for use with electrically controlled water and steam supplies).
including sight gauge, steam coil. 3 probes and extensions with cover box (for use with electrically controlled water ana steam supplies).
April. 1984)
PROBES)
REFERENCE PART NUMBER NUMBER
19 62453* Probe extension (tor use only with single probe 20 101468 Probe extension set (3) (for use only with three 2- 43895 Corrosion resistor (no: used with 3 probe 22 22200
23 07169 Pressure gauge, bottom mount 0-100-psi) 24 03277
25 22151 26 22193- 27 22140 Air vent 28 100075 Safety valve - 50 psi 29 22106 1/2 Solenoid valve, boiler auto blowdown, 115
30 22112 Water shut-off! angle valve 31 19872
32 20555 3/4 Bucket trap 33 03276 34 22102 35 44095— 36 19870 37 07173 Pressure gauge, rear mount. 0-30 psi. 2 1/2"
07168 Pressure gauge, rear mount. 030 psi. 2' (Pressure
38 19944*- On - off power switch. 115/220 volt. DPST 39 19968*- Reset switch 40 12161*
12169*-
41 19947- Pressure switch 42 03514- Low water cut-off relay. 115 volt (1C1DO)
43 03504" Water control relay. 115 volt (1D1DO) 44 45 19945*- Float switch with gasket - low water cut-off
DESCRIPTION
boilers) probe boilers) boilers)
3/4" Pressure reducing valve - 30 to 50 psi (optional)
volt (optional)
Steamers only)
Signal light. 115/220 volt 1- Signal light. 115/220 volt, 1/2' (Pressure Steamers
only)
3/4" Moisture separator (ball float trap) (California only)
*Required for electric steam control and electric low water cut-off safety circuit Through November 1982, these components were used
in lieu of the #22151 steam control valve as standard equipment on all 24" and 60" wide cabinets and all California units, but optional on 36" and 42" wide cabinets. After November 1982, the #22151 was not used and the electric controls became standard equipment on all steam coil generators.
**Required for electric (solenoid valve) water fill, used in lieu of the #43720 water regulator valve, beginning April 1984.
***Optional, if steam supply is wet.
CLEVELAND/ALCO, 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Loading...