CleaverBrooks Profile LNS1 Series, Profile S1 Series, Profile S1G, Profile S1L, Profile S1LG Installation, Operation, Service Parts

...
Profire S1/LNS1
Burner
Light Oil, Gas, or Combination
Installation
Operation
Service
Parts
Manual Part No. 750-208 07/2019
Monroe, Wisconsin
www.cleaverbrooks.com
S1/SERIES TABLE OF CONTENTS
SECTION 1:0
OPERATING PRECAUTIONS ................................................1
MODEL DESIGNATIONS, SIZES & INPUTS
CHAPTER 1. INTRODUCTION
A. GENERAL INFORMATION ................................................3
B. DESCRIPTION
C. OPERATING CONTROLS .................................................3
D. FLAME SAFEGUARD CONTROLS ...................................4
E. COMBUSTION AIR HANDLING SYSTEM ........................4
F. FIRING RATE CONTROLS................................................4
G. FIRING HEAD ....................................................................4
H. OIL SYSTEM AIR ATOMIZING ...................................... 4-5
I. GAS SYSTEM ................................................................ 6-7
CHAPTER 2. INSTALLATION
A. APPLICATION....................................................................8
B. INSTALLATION
C. PACKING PLASTIC REFRACTORY AROUND OVEN .....8
D. SEPARATE COMPRESSOR MODULE .............................8
E. TYPICAL OIL SUPPLY LOOP ............................................8
F. CIRCULATING OIL PUMP .................................................8
G. OIL PRESSURE REGULATOR..........................................8
H. GAS PIPING ......................................................................8
MOUNTING SKETCHES.
I. INSTALLATION CHECK LIST ..........................................10
OIL PIPING SCHEMATICS. GAS PIPING SCHEMATICS. GENERAL ARRANGEMENT MOTOR ROTATION CAUTION
.............................................................................15
...................................................................3
..................................................................8
................................................. 9-10
.................................................11
...............................................12
................................................13
.............................................................14
.........................2
CHAPTER 5. MAINTENANCE A. GENERAL. B. CONTROL SYSTEM.
C. PROGRAMMING CONTROL .......................................... 29
D. FIRING HEAD INSPECTION ........................................... 29
E. PILOT AND IGNITION ELECTRODE F. FLAME SCANNER.
G. OIL NOZZLE
H. DIFFUSER ....................................................................... 31
I. FIRING RATE CONTROLS J. BURNER MOUNTING INSPECTION.
K. FUEL OIL SYSTEM .........................................................32
L. GAS SYSTEM.
M. ELECTRICAL SYSTEM ...................................................33
N. EXTENDED SHUTDOWN. O. COMMON VENT LINE P. MAINTENANCE FLOW CHART
CHAPTER 6. TROUBLE SHOOTING A. AWARENESS. B. EMERGENCY SHUTDOWN. TROUBLE SHOOTING GUIDE.
....................................................................... 29
....................................................... 29
..............................29
.......................................................... 29
.................................................................... 31
............................................... 32
.............................. 32
................................................................. 32
.............................................. 33
....................................................33
....................................... 34
.................................................................. 35
........................................... 35
......................................36-38
SECTION 2:0
CHAPTER 7. LOW NOx SYSTEM A. F.G.R. SHUT-OFF VALVE
B. F.G.R. DAMPER ASSEMBLY ..........................................2-3
WARRANTY POLICY. START-UP / SERVICE REPORT. PRODUCT SATISFACTION SURVEY
.................................................. 1
.........................................................4-5
........................................... 6
...................................7
CHAPTER 3. OPERATION
A. PREPARATION FOR STARTING ....................................16
B. ELECTRICAL INTERFERENCE TEST
C. GAS PILOT FLAME ADJUSTMENT ................................17
D. START-UP SEQUENCE ..................................................17
E. AUTOMATIC SHUTDOWN ..............................................17
F. MANUAL SHUTDOWN ....................................................17
G. SAFETY SHUTDOWN .....................................................17
H. START-UP AND OPERATING. ........................................18
I. NORMAL OPERATION. J. SHUTDOWN.
CHAPTER 4. ADJUSTMENTS
A. GENERAL ....................................................................... 20
B. COMBUSTION ADJUSTMENT ON GAS AND OIL...... ...20
C. ELECTRICAL INTERFERENCE TEST.............................20
D. GAS SYSTEM.............................................................20-22
E. OIL SYSTEM...............................................................22-23
F. LINKAGE - MODULATING MOTOR............ .... ................23
G. FIRING RATE CONTROLS.............................. ................23
AIR DAMPER BOX ARRANGEMENT.................................
GAS LINKAGE ADJUSTMENTS.................................
OIL LINKAGE ADJUSTMENTS.................................
F.G.R. BLADE LINKAGE ADJUSTMENTS...........................
AIR DAMPER BLADE LINKAGE ADJUSTMENTS...............
....................................................................19
....................................................18
...................... 16-17
. 24
......... 25
........... 26
27 28
SECTION 3:0
PARTS SECTION FIRING HEAD ASSEMBLY HOUSING COMPONENTS
AIR DAMPER BOX................................................................. 8
AIR DAMPER BOX COMPONENTS MOD MOTOR MAXON VALVE GAS BUTTERFLY & LINKAGES OIL NOZZLE COMPONENTS OIL TRAIN AIR COMPRESSOR
....................................................................... 11
.................................................................... 12
............................................................................ 16
....................................................5
.................................................6-7
.................................9-10
..................................... 13-14
.............................................. 15
............................................................. 17
Monroe, Wisconsin
www.cleaverbrooks.com
OPERATING PRECAUTIONS
This operating manual presents information that will help to properly operate and care for the equipment. Study its contents carefully. The unit will provide good service and continued operation if proper operating and maintenance instructions are followed. No attempt should be made to operate the unit until the principles of operation and all of the components are thoroughly understood. Only trained and authorized personnel should be allowed to operate, adjust or repair this equipment.
If you are operating a burner(s), it is your responsibility to ensure that such operation is in full accordance with all applicable safety requirements and codes.
Placed on all CB Prore burners are warning or caution labels designed to inform the
operator of potential hazards and stress important information.
These symbols and their meanings are as follows:
WARNING
FAILURE TO INSTALL AND OPERATE THIS EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDED INSTRUCTIONS AND INDUSTRY STANDARDS AND PRACTICES CAN RESULT IN FIRE, EXPLOSION, PROPERTY DAMAGE AND/OR PER­SONAL INJURY !! READ THIS MANUAL IN IT’S ENTIRIETY PRIOR TO ANY ATTEMPT TO
COMMISSION THIS EQUIPMENT. INSTALLATION, STARTUP, OPERATION AND MAINTE­NANCE OF THIS EQUIPMENT MUST BE PERFORMED ONLY BY FACTORY AUTHORIZED, EXPERIENCED AND QUALIFIED PERSONEL.
WARNING
HAZ A RD OF EL E CT RI C S HO CK !! !
MORE THAN ONE DISCONNECT MAY BE REQUIRED TO DISCONNECT ALL POWER TO THIS PANEL. SERIOUS PERSONAL INJURY OR DEATH MAY RESULT.
WARNING
TO AVOID PERSONAL INJURY FROM MOV I N G PARTS, SH U T OFF ALL EL E C T R I C A L POWER BE F O R E SERVICING THIS EQUIPMENT.
CAUTION
ONLY FACTORY AUTHORIZED BURNER SE RV IC E PE RS ON NE L S HO UL D START UP, ADJUST, OR SERVICE THIS EQUIPMENT.
WARNING
READ PRODUCT MANUAL AND FULLY U N DE R S TA N D I T S C O N TE N T S BEFOREATTEMPTING TO OPERATE THIS EQUIPMENT. SERIOUS PERSONAL INJURY OR DEATH MAY RESULT.
CAUTION
PROVIDE SUPPORT FOR THIS PANEL TO PREVENT DAMAGE TO THE ELECTRICAL COMPONENTS.
CAUTION
AFTER FINAL FUEL INPUT ADJUSTMENTS ARE MADE, VERIFY FUEL INPUT BY METER IF POSSIBLE
Sec1:1
Further warning and caution references have been made in this manual and should be adhered to for smooth operation of the burner.
This symbol precedes information
WARNING
CAUTION
NOTE
Model designations are based on the type of fuel(s) to
be red and the amount of furnace pressure to be over­come. Burner size is based on ring rate (rated input in
BTU/HR).
which, if disregarded, may result in injury to the user of the burner or to others.
This symbol precedes information which, if disregarded, may result in damage to the burner.
This symbol precedes information which is vital to the operation or maintenance of the burner.
BURNER MAX.BURNER GAS INPUT
SIZE MBTU/HR.
462 46,200,000 504 50,400,000 546 54,600,000 588 58,800,000 630 63,000,000
Gas input based on natural gas at 1,000
Btu/cu.ft and 0.60 specic gravity
BURNER MAX.BURNER OIL INPUT
SIZE US G.P.H.
MODELS STANDARD FUEL - AIR ATOMIZATION
S1G GAS
S1L #2 OIL
S1LG #2 OIL and GAS
LNS1G LOW Nox < 30 ppm GAS
LNS1LG LOW NOx #2 OIL and GAS
THE INSTALLATION OF A BURNER SHALL BE IN ACCORDANCE WITH THE REGULATIONS OF AUTHORITIES HAVING JURISDICTION. THE EQUIPMENT MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE LOCAL, STATE OR PROVINCIAL INSTALLATION REQUIREMENTS INCLUDING THE NATIONAL ELECTRICAL CODE (NEC) AND ASSOCIATED INSURANCE UNDERWRITERS. WHERE APPLICABLE, THE CANADIAN GAS ASSOCIATION (CGA) B149 AND CANADIAN STANDARD ASSOCIATION (CSA) B140 AND B139 (FOR OIL BURNERS) CODES SHALL PREVAIL.
OIL AND GAS BURNING EQUIPMENT SHALL BE CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES, TO ASSURE SAFE AND PROPER OPERATION OF THE BURNER.
462 330 504 360 546 390 588 420 630 450
Oil input based on No.2 oil at 140,000Btu/gal
THE S1/SERIES BURNERS ARE DESIGNED TO BURN EITHER GAS OR LIGHT OIL No.1 OR 2 AS DEFINED BY ASTM D396-1978 SPECIFICATIONS, AND HEAVY OILS. DO NOT USE GASOLINE, CRANKASE OIL, OR ANY OIL CONTAINING GASOLINE.
Sec1:2
CHAPTER 1
INTRODUCTION
A. GENERAL INFORMATION
CB Prore S1/Series burners are assembled, wired and
tested at the factory. They are listed by the Underwriters Laboratory, CSD-1, NFPA-85, I.R.I., F.M., including the National Electrical Code (NEC) and associated insurance underwriters. Where applicable, the Canadian Gas As­sociation (CGA) B149 and Canadian Standards Association (CSA) B140 codes shall prevail. Other regulatory agency control options are available.
CAUTION
ONLY FACTORY AUTHORIZED BURNER SERVICE PERSONNEL SHOULD START-UP, ADJUST, OR SERVICE THIS EQUIPMENT
The operator must be familiar with the individual functioning of all controls to understand the operations and procedures described in the manual. Identify and locate each item in the illustrations as they are described in the following sections.
B. DESCRIPTION
The CB Prore S1/Series oil burners are of the low
pressure, air atomizing (nozzle) type. Gas burners are of the peripheral mix type. All burners feature ignition by
spark-ignited gas pilot ame. With either fuel, the burner
operates with full modulation. A switch permits changeover
from automatic fully modulated ring to manually set ring
at any desired rate between minimum and maximum. Ad­ditional safeguards assure that the burner always returns
to minimum ring position for ignition.
S1/Series burners are designed for automatic, unattended operation except for periodic inspection and maintenance. After selecting the proper overload settings for the starter, the rest of the control panel components require little at­tention except for occasional cleaning.
C. OPERATING CONTROLS The burner is supplied with a remote control panel and
with a burner mounted junction box.
CONTROL PANEL
The control panel contains a ame safeguard program-
ming control, motor starters, relays, time delays and termi­nal strips mounted internally on a panel sub-base. Lights,
switches, potentiometers, a control circuit breaker and ame
safeguard displays are mounted externally on the panel as indicated below.
1. ON-OFF BURNER SWITCH - (for gas or oil only)
2. FUEL SELECTOR SWITCH - Gas-Off-Oil (for combination gas-oil burners only)
Gas position: Selects gas as the ring fuel .
NOTE
WHEN CHANGING FROM OIL TO GAS FUEL, ALLOW PROGRAMMER TO COMPLETE POST PURGE AND SHUTDOWN BEFORE MOVING SELECTOR SWITCH TO GAS PO­SITION. THIS WILL ALLOW THE INTERLOCK CIRCUIT TO OIL-AIR PUMP OR COMPRES­SOR TO DE-ENERGIZE
Off position: Burner off.
Oil position: Selects oil as the ring fuel.
3. CONTROL CIRCUIT BREAKER - supplementary low overcurrent protection only. No larger than 15 amps.
4. AUTO-MANUAL
MODULATION SELECTOR SWITCH.
Auto Position: Selects boiler modulation control. Manual Position: Selects 135 ohm potentiometer for manual modulating control.
5. MANUAL MODULATING CONTROL 135 ohm
Increases or decreases the burner ring rate
manually.
6. SIGNAL LAMPS. a. POWER ON (white) illuminates when the control circuit is energized (powered).
b. IGNITION (amber) illuminates when the ignition transformer is powered, and gas pilot valve is energized (opened).
c. MAIN FUEL (green) illuminates when the main fuel valve or valves (gas or oil) are energized (open).
d. FLAME FAILURE (red) illuminates when the
ame safeguard system fails to detect pilot or main ame.
WARNING
READ THE FLAME SAFEGUARD MANUAL AND FULLY UNDERSTAND ITS CONTENTS BEFORE ATTEMPTING TO OPERATE THIS EQUIPMENT. SERIOUS PERSONAL INJURY OR DEATH MAY RESULT.
Sec1:3
D. FLAME SAFEGUARD CONTROLS
PRIMARY GAS BUTTERFLY VALVE
SECONDARY GAS BUTTERFLY VALVE
BURNER HEAD ASSEMBLY WITH DUAL GAS MANIFOLD
GASKET
REFRACTORY DRY OVEN
570-057
1-Dual gas manifold 2-Primary gas orifices 3-Secondary gas spuds 4-Diffuser 5-Scanner tube 6-Gas pilot line 7-Pilot 8-Oil Nozzles 9-Oil lines 10-Air atomizing line
1
2
3
4
5
6
7
8
9
10
021-0583
The ame safeguard programmer incorporates a ame
sensing cell (scanner) to shut down the burner in the event
of pilot ame or main ame failure. Other safety controls
shut down the burner based on sequence of operation as
shown in the manufacturers ame safeguard manual.
E. COMBUSTION AIR HANDLING SYSTEM
The combustion air handling system consists of two major
components:
1. DAMPER ASSEMBLY. A multi blade system regulates the combustion air volume and is positioned by a modulating motor. The dampers are
normally ALMOST CLOSED in the low-re position and opens as the burner drives toward a high-re position.
2. MOTOR DRIVEN IMPELLER. The diameter of the impeller determines available air pres­sure and the width determines air capacity in cubic feet per minute. Alternate motor-impeller combinations are available
for 50 cycle or 60 cycle power and for ring against either
moderate or high furnace pressure. For higher altitudes and higher furnace pressures, motor and impeller combinations are determined at the factory.
F. FIRING RATE CONTROLS
Regardless of the fuel used, burner input is fully modulated
between low re and high re on boiler demand. Firing rate
is controlled by the potentiometer-regulated modulating motor. Combustion air control damper, oil metering valve
and/or gas volume buttery valves are through variable
rate rod and lever linkages. The modulating motor rotates 90 degrees from low to high position. Flow rate through each component is adjusted by position­ing the control rods on the levers and the angular position of levers on shafts. Lever on the modulating motor shafts
actuate the high re position proving switch.
G. FIRING HEAD
Access to the ring head is provided by swinging open
the impeller housing. First, disconnect the damper linkage,
Figure 1-1
Sec1:4
Figure 1-2
release the housing latch and swing the housing to open position. An internal gas pilot is standard on all burners. Pilot gas pressure is adjusted at the pilot pressure regula­tor.
H. OIL SYSTEM AIR ATOMIZING
S1 Model burners use compressed air for atomization. Atomizing air is independent of combustion air. The system is supplied with a separate compressor module for mount­ing near the burner.
3-WAY SOLENOID VALVE.
Metered oil enters the common port of the 3-way solenoid valve. During shutdown, pre and post purge the valve is de-energized (N.C. port closed) and all metered fuel oil returns to the storage tank. When the valve is energized, metered oil is directed to the nozzle through the normally closed port.
NOZZLE ASSEMBLY.
The nozzle assembly consists of four main parts: body, compression spring, swirler, and tip. The swirler is held against the nozzle tip by the compression spring. The nozzle body has inlet ports for air and oil lines. Metered
fuel oil enters the nozzle body and ows through a tube to
the swirler. Oil is forced from the core of the swirler to the side ports where it meets with the atomizing air. Atomizing air enters and passes through the nozzle body to grooves in the swirler, where it mixes with fuel oil. Air/oil passes
through grooves and out of the nozzle orice in a cone of atomized oil. Proper velocity and angle of the ne spray
ensures good mixing with the combustion air, providing
quiet starts and excellent combustion efciency.
OIL STRAINER
VALVE, 1/2" MOTORIZED 3-WAY OIL
VALVE, MAXON FLOW CONTROL
SWITCH, HIGH OIL PRESSURE
VALVE, 1/2" HORIZONTAL CHECK
SWITCH, LOW OIL PRESSURE
GAUGE, 0-60 PSI
VALVE, 1/2" RELIEF
VALVE, 1/2" MOTORIZED 2-WAY
INLET
FROM SUPPLY
REFERENCE: GAS MANIFOLD ASSEMBLY
RETURN
TO SUPPLY
METERED OIL
TO NOZZLE
Prevents foreign matter from entering the burner oil system.
ATOMIZING AIR PROVING SWITCH
Pressure actuated switch contacts close when sufcient
atomizing air pressure is present.The oil valve will not open unless switch contacts are closed.
SEPARATE COMPRESSOR MODULE
All burners have a burner mounted oil metering unit and a separate compressor module. The system functions as follows:
AIR COMPRESSOR MODULE
Air is supplied by a positive displacement rotary vane compressor. This provides a constant volume of atom­izing air regardless of pressure. The compressor module
includes motor, air/oil reservoir tank, air lter and lube oil cooling coil. Air enters the compressor through the lter. The air ows from the compressor into the air-oil separating and reservoir tank. Filtering material and bafes separate
the lube oil from the compressed air. The tank air pres­sure forces lubricating oil from the tank to the compressor to lubricate bearings and vanes. A sight glass indicates the level of lubricating oil in the air/oil reservoir. Lubricat­ing oil must be visible in the gauge glass at all times. Air
compression heat is absorbed in part by the ow of lube
oil, creating a hot oil mist. The air/oil mist is cooled by a coil assembly. Lube oil is also cooled before entering the compressor.
OIL METERING
The oil metering unit is a MAXON Synchro ow control
valve. The multiple screw cam assembly provides mechani­cal adjustment capabilities to the fuel ratio at each valve position throughout the entire capacity range.
OPERATION
Fuel is delivered to the metering system at 50 to 70 psi. Metered oil is delivered to the common port of a 3-way solenoid valve for transfer to the burner nozzle through the normally closed port or back to the storage tank through the normally open port. During pre- and post purge, metered
oil is returned to the tank. During normal ring, all metered
oil is delivered to the nozzle. Air enters a rotary vane compressor through an air cleaner
where it is compressed to atomizing pressure. Air ows
from the compressor to an air/oil tank which serves the multiple purpose of dampening air pulsation, lube oil mist recovery, lube oil and atomizing air storage. Oil vapor is extracted by a mist eliminator in the upper section of the tank. Atomizing air from the upper tank section is delivered to the nozzle at a constant volume. Air pressure increases
as the burner ring rate increases. Atomizing pressure may
be adjusted by the valve located on the compressor air breather. The valve allows air to be bled from the tank to the compressor inlet. Delivery rate of the fuel oil metering is controlled by the modulating motor through adjustable linkage.
Figure 1-3
Sec1:5
I. GAS SYSTEM Gas is introduced into the combustion zone from a
circular manifold through multiple ports in the blast tube, and through a pre-mix zone. Firing rate is determined by the size and number of ports, by manifold pressure and by
combustion zone pressure. The ring rate is regulated by a rotary, buttery type throttling valve at the manifold inlet.
The valve is actuated by an adjustable linkage from the
modulating motor. Depending upon specic requirements,
one or two safety shutoff, motorized main gas valves are provided for installation in the gas train upstream of the
buttery valves. Safety shutoff gas valves are wired into
the programming control to automatically open and close at the proper time in the operating sequence.
MAIN GAS TRAIN COMPONENTS
Depending upon the requirements of the regulating au­thority, the gas control system and gas train may consist of some, or all, of the following items. A typical gas train is shown in Figure 1-4.
GAS VOLUME VALVE.
Two buttery type valves are positioned by linkage from the modulating motor and controls the rate of ow of gas.
MAIN GAS VALVES.
Electrically operated safety shutoff valve(s) that open to admit gas to the burner. Standard U.L. burners include: One motorized gas valve w/closure interlock and one standard motorized valve.
MAIN GAS REGULATOR
Regulates gas train pressure to specied pressure re­quired at inlet to gas train. Input is set by main gas pressure regulator adjustment.
MAIN GAS COCKS
For manual shutoff of the gas supply upstream of the pressure regulator. A second shutoff cock downstream of the main gas valve(s) provides a means of testing for leakage through the gas valve(s).
HIGH GAS PRESSURE SWITCH.
A pressure actuated switch that remains closed when gas pressure is below a pre-selected setting. Should the pressure rise above the setting, the switch contacts will open causing main gas valve(s) to close. This switch requires manual reset after being tripped.
LOW GAS PRESSURE SWITCH.
A pressure actuated switch that remains closed when gas pressure is above a pre-selected setting. Should the pressure drop below this setting, the switch contacts will open, causing main gas valve(s) to close. This switch requires manual reset after being tripped.
PILOT GAS TRAIN
GAS PILOT VALVE.
A solenoid valve that opens during the ignition period to admit fuel to the pilot. It closes after main ame is estab­lished.
GAS PRESSURE REGULATOR. Reduces gas pressure to that required by the pilot.
GAS PILOT SHUT-OFF COCK. For manually closing the pilot gas supply.
Sec1:6
Figure 1-4
OPERATION
Metered gas ows through the main gas shutoff cock,
through the pressure regulator to the automatic gas valves
and buttery valve to the gas manifold. The buttery gas valve modulates ow to burner input demand. The buttery valves are positioned through
mechanical linkage by the modulating motor. The air control damper is positioned simultaneously by the modulating motor. The automatic gas valve(s) cannot be energized unless the combustion air proving switch is closed. The low and high gas pressure switches must be closed to prove proper gas pressure. A normally open vent valve, if required, is located between the two automatic gas valves. This valve is shut when the automatic gas valves are open. When the automatic valves are closed, the vent valve is open for venting gas to the outside, should any be present.
Sec1:7
CHAPTER 2
INSTALLATION
A. APPLICATION
Electrical power available is usually 230/460 volt, 3 phase, 60 cycle, or 380 volt, 3 phase, 50 cycle. Control circuit is 115 volt, single phase, 60 cycle or 115 volt, single phase, 50 cycle. Refer to the electrical schematic diagram shipped with the burner. Power connections are made at the control panel. The burner is furnished with a burner mounted junction box and remote control panel. Wiring from the burner junction box to remote panel, panel to boiler controls, low water controls, remote compressor motor and remotely located fuel valves is furnished by the installer.
B. INSTALLATION
Locate the burner properly. The burner is designed for operation with the blast tube level. Do not tilt burner up or excessively downward. Installation of the refractory oven or combustion cone, shipped with the burner, is shown in Figures 2-1 and 2-2. Securely support the burner pedestal
on the oor or foundation. Allow enough clearance at the
rear of the burner to allow the housing to swing open for service and maintenance. The face of the boiler and burner
ange must be sealed with the gasket provided with the
burner. Carefully place the gasket over the dry oven bolts
before it is mounted onto the burner ange. The I.D. of
the dry oven and burner blast tube are concentric. Due to bolt hole tolerances, the dry oven may have to be shifted to accomplish this. After the dry oven nuts are properly tightened, the burner and dry oven assembly can then be mounted into the boiler.
C. PACKING PLASTIC REFRACTORY AROUND OVEN
The area between the outside circumference of the dry oven and existing refractory should be packed with Kaiser Refractory Mono T-9 Airset or equal within two hours after coating the dry oven with Trowleze. From inside the furnace, ram plastic refractory from the front to the rear parallel to outside surface of the dry oven.
supply entrance and pass through the return line and on to the tank. Metered oil is pumped (by the metering pump) to the common port of a 3-way valve. With the 3-way valve de-energized, the metered oil returns to the tank through the back pressure valve and return line. When the 3-way valve is energized, metered oil is passed on to the burner oil nozzle and atomized by air from the compressor. The proper strainers, check valves, vacuum and pressure gauges, etc. should be installed as indicated. All lines should be pressure tested after installation.
CAUTION
IT IS IMPORTANT THAT YOU PROVIDE S U P P O R T F O R T H E H O U S I N G WHEN IN THE OPEN POSITI O N TO PREVENT DAMAGE TO THE HINGES AN D SUBSEQUE NT COMPONE NTS.
F. CIRCULATING OIL PUMP A circulating oil pump is required to deliver fuel oil from
the storage tank to the burner at a minimum of 150% of
the maximum burner ring rate. The excess oil allows a
margin for piping error, viscosity changes in the fuel oil, and circulating pump wear. Correct pipe sizing is deter­mined by circulating rate , not burner capacity. Install the pump as close to the supply tanks as possible. Suction lift should be as low as possible. Maximum suction of 15" Hg vacuum is good practice for either light or heated heavy oil. The strainer should be installed in the suction line just ahead of the circulating pump to prevent foreign material from entering the pump. Locate the strainer so it may be easily cleaned.
G. OIL PRESSURE REGULATOR
An oil pressure regulator should be installed in the sup­ply line, close to the burner to regulate oil pressure. Oil pressure is 50 to 70 PSI to the metering valve.
D. SEPARATE COMPRESSOR MODULE
For oil burners supplied with the separate compressor module, piping to the burner is installed as shown in Figure 2-4. Copper tubing for the installation is not supplied with the burner.
E. TYPICAL OIL SUPPLY LOOP
Continuous oil circulation must be supplied to the burner
at a rate of 50 percent greater than the high-re burning
rate. The oil circulating pump should be located as close as possible to the storage tank to keep suction lines short and minimize suction loss. Note that the supply line is higher above the burner metering pump inlet to help eliminate air problems. The return line to the tank is connected at the discharge port of the 3-way valve. Note that the return line should be a minimum of 20 inches higher than the supply line. Since air rises to the highest point, it will rise from the
Sec1:8
H. GAS PIPING
Refer to Figures, 2-6 for typical gas piping schemat­ics. Gas service and house piping must supply the quantity of gas demanded by the unit at the pressure required at the burner gas train inlet. All piping must be in strict accor­dance with applicable codes, ordinances and regulations of the supplying utility. In the absence of other codes, piping should be in accordance with the following standards: "National Fuel Gas Code" NFPA No. 54, ANSI No. Z 223.1. (for Canada: the Canadian Gas Association (CGA) B149 and Canadian Standards Association (CSA) B140 codes shall prevail)
Gas train components upstream of the buttery valve
are shipped loose. These components should be mounted
by the installer as close to the buttery valve as practical.
Normally, the control train is ordered to suit a particular code
1
2
3
BOILER FRONT PLATE
BURNER MOUNTING FLANGE
(2) 1" INSULATING BLANKETS (KAO-WOOL, CERABLANKET OR DURABLANKET)
2" BLOCK INSULATION
COAT OUTER CIRCUMFERENCE OF DRY OVEN CONE WITH TROWLEZE
PACK WITH PLASTIC REFRACTORY KAISER MONO T-9 AIR SET OR EQUAL (RAM FROM FRONT TO REAR)
1" GASKET SUPPLIED WITH BURNER
STEEL WRAPPER ON CONE
DRY OVEN CONE SUPPLIED WITH BURNER
WRAP DRY OVEN CONE WITH KAO-WOOL (COAT BOTH SIDES WITH TROWLEZE)
REV DESCRIPTION RELEASE # DRAWN BY REVIEW BY
A
UPDATED TO CURRENT CAD SOFTWARE
-
GAS
07/30/08
JCS
07/30/08
45° MIN
FIREBRICK
1
2
3
BOILER FRONT PLATE
BURNER MOUNTING FLANGE
2.5" MINIMUM
TUBE
SHEET
(2) 1" INSULATING BLANKETS (KAO-WOOL, CERABLANKET OR DURABLANKET)
2" BLOCK INSULATION
COAT OUTER CIRCUMFERENCE OF DRY OVEN CONE WITH TROWLEZE
PACK WITH PLASTIC REFRACTORY KAISER MONO T-9 AIR SET OR EQUAL (RAM FROM FRONT TO REAR)
1" GASKET SUPPLIED WITH BURNER
STEEL WRAPPER ON CONE
DRY OVEN CONE SUPPLIED WITH BURNER
WRAP DRY OVEN CONE WITH KAO-WOOL (COAT BOTH SIDES WITH TROWLEZE)
45° MIN
7
REV DESCRIPTION RELEASE # DRAWN BY REVIEW BY
A
UPDATED TO CURRENT CAD SOFTWARE
-
GAS
07/30/08
JCS
07/30/08
NOTES:
1. LAY THE DRY OVEN ON THE FLOOR WITH THE STUDS UP. CAREFULLY PRESS THE GASKET OVER THE STUDS.
2. LIFT THE DRY OVEN ONTO THE BURNER FLANGE AND GENTLY TIGHTEN THE BOLTS.
3. MAKE SURE THE DRY OVEN IS CENTERED ON THE BURNER FLANGE SO THE SPACE IS EQUAL ALL AROUND THE BURNER BLAST TUBE
4. MAKE SURE THAT NONE OF THE GASKET IS PROTRUDING INTO THE AIR STREAM. TIGHTEN THE DRY OVEN NUTS.
5. WRAP THE DRY OVEN WITH TROWLEZE COATED KAO-WOOL AND LIFT THE BURNER ONTO THE BURNER STUDS AND BOLT SECURELY IN PLACE.
6. FINISH REFRACTORY WORK INSIDE FURNACE.
BURNER MOUNTING DETAILS FOR WATERTUBE BOILERS
Figure 2-1
NOTES:
1. LAY THE DRY OVEN ON THE FLOOR WITH THE STUDS UP. CAREFULLY PRESS THE GASKET OVER THE STUDS.
2. LIFT THE DRY OVEN ONTO THE BURNER FLANGE AND GENTLY TIGHTEN THE BOLTS.
3. MAKE SURE THE DRY OVEN IS CENTERED ON THE BURNER FLANGE SO THE SPACE IS EQUAL ALL AROUND THE BURNER BLAST TUBE
4. MAKE SURE THAT NONE OF THE GASKET IS PROTRUDING INTO THE AIR STREAM. TIGHTEN THE DRY OVEN NUTS.
5. WRAP THE DRY OVEN WITH TROWLEZE COATED KAO-WOOL AND LIFT THE BURNER ONTO THE BURNER STUDS AND BOLT SECURELY IN PLACE.
6. FINISH REFRACTORY WORK INSIDE FURNACE.
BURNER MOUNTING DETAILS FOR SCOTCH MARINE BOILERS
Sec1:9
Figure 2-2
570-071
ATOMIZING AIR TO NOZZLE
RADIATOR
R
ELECTRICAL JUNCTION BOX
COMPRESSOR BASE
BELT GUARD ASSY.
AIR BREATHER
SIGHT GLASS
OIL FILTER
MOTORCOMPRESSOR
OIL/AIR TANK
or insurance regulation - such as Underwriters Laboratories , Inc., CGA, Factory Mutual, or Industrial Risk Insurance. Arrange gas piping at the burner so that the burner is accessible for servicing without disassembly. The gas pilot supply line must be connected upstream of the main gas regulator. If a reducing bushing is required between the house piping and the burner piping, it should be close to the burner shut-off valve. The gas piping must be internally clean and free of foreign material. Before using in service, a leak test must be performed.
I. INSTALLATION CHECKLIST
All burners are carefully assembled and tested at the factory, but before being placed in service, all connectors should again be checked for looseness caused during shipment. Check:
1. Electrical terminals in the control panel and on all electrical components.
2. Pipe ttings and unions.
3. Tubing connections.
4. Nuts, bolts, screws.
Before operating pumps, metering heads and compres-
Figure 2-3
sors, make certain that reservoirs are properly lled with the specic lubricant. Open all necessary oil shut-off
valves. Do not run compressors, pumps, or metering units without oil. Before connecting electrical current to any component,
be sure the supply voltage is the same as that specied
on component nameplates. Before burner operation, be sure all motors are rotating in the correct direction. See Motor Rotation Reference on Sec1:13.
Before ring, make sure that the refractory ame cone is properly sealed to the burner mounting ange and the
boiler front plate. Make certain that the operator in charge is properly instructed in the operation and maintenance procedures.
CAUTION
THE BURNER REFRACTORY CONE IS AIR-CURED ONLY. HEAT-CURING MUST BE INITIATED AT INITIAL START-UP. RUN THE BURNER AT LOW FIRE FOR A PERIOD OF 6 TO 8 HOURS BEFORE STARTING TO GRADUALY INCREASE THE FIRING RATE. FAILURE TO DO SO WILL RESULT IN DAMAGE AND CRACKS IN THE REFRACTORY.
Sec1:10
570-070
PRESSURE REDUCING STATION
PRESSURE RELIEF VALVE
CHECK VALVE
2-WAY VALVE (ON BURNER)
H.O.P.S.
L.O.P.S.
NO. 2 OIL PIPING ARRANGEMENT
RETURN
SUCTION
CHECK VALVE
3-WAY VALVE (ON BURNER)
OIL METER (SUPPLIED WITH BURNER)
PRESSURE GAUGE & NEEDLE VALVE
CHECK VALVE
VACUUM GAUGE
STRAINER
GATE VALVE
GATE VALVE
GATE VALVE
PIPING BY OTHERS
PIPING BY CB PROFIRE
OIL CIRCULATING PUMP
OIL STORAGE TANK
TO DRAWER ASSEMBLY
570-072
1
3
4
PIPING LEGEND
ATOMIZING AIR INTERLOCK SWITCH
BURNER
FROM STORAGE TANK
RETURN TO STORAGE TANK
2
AIR/LUBE OIL
COMPRESSOR MODULE
1. ATOMIZING AIR PRESS. GAUGE (SUGGESTED LOCATION)
2. OIL-AIR TANK
3. OIL PIPING
4. BURNER NOZZLE ASSEMBLY
FUEL OIL
ATOMIZING AIR
LUBE OIL
Figure 2-4
Sec1:11
Figure 2-5
B
A
1) NORMALLY OPEN VENT VALVE LINE SHALL BE HALF OF THE MAIN GAS TRAIN PIPING SIZE. (3/4" MIN.)
1) FULL SIZE (1/4" OR LARGER) PIPE TO BE RUN FROM THE VENT OPENING TO OUTSIDE OF BUILDING.
2) NO TRAPS ALLOWED IN VENT LINE.
3) VENT LINE SHALL TERMINATE AWAY FROM ALL DOORS AND WINDOWS.
4) PROVISIONS SHALL BE MADE TO PREVENT FOREIGN OBJECTS FROM ENTERING VENT PIPING.
A
REGULATOR
SHUTOFF COCK
HIGH GAS PRESSURE SWITCH
A
Maxon
Maxon
570-0076
B
PILOT VALVE
PILOT SHUTOFF COCK
TEST OPENING TYPICAL
REGULATOR
N.O. VENT VALVE
MAIN GAS VALVE W/P.O.C.
MAIN GAS VALVE
SHUTOFF COCK
LOW GAS PRESSURE SWITCH
A
A
BURNER MOUNTING DETAILS FOR SCOTCH MARINE BOILERS
Sec1:12
Figure 2-6
S1-SERIES DIMENSION DIAGRAM
R
GENERAL DIMENSIONS
570-096
16-1/8
28
GAS TRAIN CONNECTION
FROM EITHER SIDE
16-3/4
OIL INLET
55-3/8
23-1/2
103-3/4 R
72-1/2
41-1/4
64-3/4
106-1/2
21-1/8
34
OIL INLET
16-1/4
(12) HOLES 3/4" DIA.
EQUALLY SPACED AS SHOWN
ON A 45" DIA. B.C.
NOTE: THESE DIMENSIONS ARE FOR REFERENCE ONLY. SPECIFICATIONS AND DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
AIR OUTLET 1" NPT
48
GAS PILOT INLET
6-1/4
10-5/8
3-7/8
OIL RETURN
MAIN GAS INLET
38-5/8
36-7/8
13-1/4
20-1/4
OIL INLET 1" NPT
23-7/8
21
11-3/4
35-1/237
OIL RETURN 1-1/4" NPT
23-1/8
40-5/8
22-1/2
7-3/8
4 3/8
ELECTRICAL
JUNCTION BOX
39-5/8
ADJUSTABLE BURNER SUPPORT
(5" WHEEL ASSEMBLY)
L
HINGE C
19-3/4
HINGE C
20
L
MAIN GAS INLET 4" NPT
GAS PILOT INLET 1/2" NPT
47
16-3/8 R
R
LNS1-SERIES DIMENSION DIAGRAM (BOTTOM ACCESS)
GENERAL DIMENSIONS
69
35
45-1/2
16-1/8
28
21-1/8
34
AIR OUTLET 1" NPT
48
570-097
16-3/8 R
47
GAS PILOT INLET 1/2" NPT
MAIN GAS INLET 4" NPT
L
20
HINGE C
19-3/4
HINGE C
L
ADJUSTABLE
BURNER SUPPORT
(5" WHEEL ASSEMBLY)
39-5/8
ELECTRICAL
JUNCTION BOX
4 3/8
7-3/8
22-1/2
40-5/8
23-1/8
OIL RETURN 1-1/4" NPT
37 35-1/2
11-3/4
21
23-7/8
OIL INLET 1" NPT
20-1/4
13-1/4
36-7/8
38-5/8
MAIN GAS INLET
OIL RETURN
3-7/8
10-5/8
6-1/4
GAS PILOT INLET
NOTE: THESE DIMENSIONS ARE FOR REFERENCE ONLY. SPECIFICATIONS AND DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
(12) HOLES 3/4" DIA.
EQUALLY SPACED AS SHOWN
ON A 45" DIA. B.C.
16-1/4
106-1/2
72-1/2
103-3/4 R
23-1/2
55-3/8
79-3/4
OIL INLET
36-1/2
F.G.R. INLET
CONNECTION
F.G.R. INLET
13-1/4" ID. x 21" OD.
(12) TAPPED HOLES 1/2-13 UNC.
EQUALLY SPACED AS SHOWN ON
A 18-3/4" DIA. B.C.
GAS TRAIN CONNECTION
FROM EITHER SIDE
OIL INLET
16-3/4
Figure 2-7
Sec1:13
Figure 2-8
Figure 2-9
R
LNS1-SERIES DIMENSION DIAGRAM (BOTTOM ACCESS)
GENERAL DIMENSIONS
69
35
45-1/2
16-1/8
28
21-1/8
34
AIR OUTLET 1" NPT
48
570-097
16-3/8 R
47
GAS PILOT INLET 1/2" NPT
MAIN GAS INLET 4" NPT
L
20
HINGE C
19-3/4
HINGE C
L
ADJUSTABLE
BURNER SUPPORT
(5" WHEEL ASSEMBLY)
39-5/8
ELECTRICAL
JUNCTION BOX
4 3/8
7-3/8
22-1/2
40-5/8
23-1/8
OIL RETURN 1-1/4" NPT
37 35-1/2
11-3/4
21
23-7/8
OIL INLET 1" NPT
20-1/4
13-1/4
36-7/8
38-5/8
MAIN GAS INLET
OIL RETURN
3-7/8
10-5/8
6-1/4
GAS PILOT INLET
NOTE: THESE DIMENSIONS ARE FOR REFERENCE ONLY. SPECIFICATIONS AND DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
(12) HOLES 3/4" DIA.
EQUALLY SPACED AS SHOWN
ON A 45" DIA. B.C.
16-1/4
106-1/2
72-1/2
103-3/4 R
23-1/2
55-3/8
79-3/4
OIL INLET
36-1/2
F.G.R. INLET
CONNECTION
F.G.R. INLET
13-1/4" ID. x 21" OD.
(12) TAPPED HOLES 1/2-13 UNC.
EQUALLY SPACED AS SHOWN ON
A 18-3/4" DIA. B.C.
GAS TRAIN CONNECTION
FROM EITHER SIDE
OIL INLET
16-3/4
BURNER AIR IMPELLER
AIR COMPRESSOR
MOTOR ROTATION, COUNTER CLOCKWISE REFERENCE
570-0075
ROTATION IS DETERMINED BY FACING THE REAR OF THE MOTOR
MOTOR ROTATION, COUNTER CLOCKWISE REFERENCE
ROTATION IS DETERMINED BY FACING THE REAR OF THE MOTOR
REAR
R
REAR
Sec1:14
Figure 2-10
CAUTION
CAUTION
BEFORE OPENING THE GAS SHUT-OFF VALVES, READ THE REGULATOR IN­STRUCTIONS CAREFULLY. OPEN SHUT­OFF VALVE SLOWLY TO ALLOW INLET PRESSURE TO BUILD-UP SLOWLY IN THE REGULATOR UNTIL IT IS FULLY PRESSUR­IZED. OPENING THE SHUT-OFF VALVE QUICKLY WILL DAMAGE THE REGULATOR. DO NOT EXCEED THE REGULATOR PRES­SURE RATINGS.
LUBRICATING OIL IS DRAINED FROM THE
AIR OIL TANK BEFORE SHIPMENT. BEFORE ATTEMPTING TO START THE BURNER, ADD OIL TO THE RECOM­MENDED LEVEL .
Sec1:15
CHAPTER 3
OPERATION
A. PREPARATIONS FOR STARTING
When the installation is complete and all electrical, fuel, water and vent stack connections are made, make certain said connections are tight. The operator should become familiar with the burner, boiler controls and components. To identify controls and components, refer to contents of Chapter 1. Adjustment procedures given in Chapter
4 should be reviewed prior to ring. The wiring diagram
should also be studied along with the operating sequence of burner programmer. Read and understand starting instructions before at­tempting to operate the burner. Before attempting to start the burner, the following checks must be made:
1. BOILER.
Check the boiler water level. Be sure all boiler valves are installed correctly and positioned properly. Set the high limit control sightly above the desired temperature. Set modulating controls at the desired temperature or pressure.
2. BURNER. Check the electrical power supply to the burner in ac­cordance with the nameplate voltage on all motors and the control circuit. Check the direction or rotation of the motors. Open the housing to check the electrode setting. Refer to Chapter 5, Figure 5-2, Sec1:30. Check the gas pilot pressure at the pilot gas regulator. Normal setting is 18" to 20" W.C.
For protection in shipment, the ame safeguard control
chassis is shipped unmounted. Check all screw connec-
tions before attaching ame safeguard chassis to base.
Screw must be secure to assure low resistance connec­tions. The relay chassis is mounted on the sub-base with a screw which, when tightened, completes the connection between the sub-base and chassis contacts. Press manual reset button to be sure safety switch contacts are closed. Check control linkage for proper movement of the air volume damper and fuel metering components. This can be done by loosening the linkage at the actuator level and manipulating by hand.
Check the air shutter and adjust low-re setting.
3. FIRING PREPARATIONS FOR OIL BURNERS.
Prior to initial ring, oil ow pressure and temperature should be veried.
Inspect the compressor lube oil sump level. Add oil to bring the oil level to the midpoint or slightly higher in the reservoir sight glass. Fill with non-detergent SAE30 oil. Make certain that the drive belts or couplings are aligned and properly adjusted.
To verify air ow and pressure, momentarily ip the switch
“ON” and immediately turn “OFF”. The programmer will continue through its cycle, however, without ignition or en­ergizing the fuel valves. Observe the air pressure gauge.
With compressor running and no oil ow, the pressure
should be approximately 10 psi. If the burner is a dual fuel model, make certain that the main gas shut off cock is closed and the fuel selector switch set to “OIL”.
OIL FLOW.
Open all valves in the oil suction and return line. The burner oil metering units are not capable of creating suction. Fuel oil must be supplied to the metering unit at a nominal 50 to 70 psi pressure by a circulating supply pump. A vacuum (or compound pressure-vacuum) gauge should be installed in the oil suction line, and its reading noted. This gauge indicates the tightness of the suction system.
4. OIL- AIR TANK (LUBE OIL). Check the lube oil level in the air-oil tank. Inspect oil level regularly. Loss of oil will damage the compressor. Fill the tank with non detergent SAE30 oil to a level midway up
the sight glass. Do not overll the tank.
For normal environment use SAE30 oil. For a 32 degree F. and below environment use SAE10 oil. Change oil every 2000 hours of operation.
5. FIRING PREPARATIONS FOR GAS BURNERS.
A representative of the gas utility should turn on the gas. Determine by a test gauge upstream of the burner regulator
that sufcient pressure exists at the entrance to the gas
train. The gas pressure regulator must be adjusted to the pressure required and the pressure setting recorded. On combination fuel models, set the selector switch to gas. On initial start-up, it is recommended that the main gas shutoff cock remain closed until the programmer has cycled through pre-purge and pilot sequences to determine that the main gas valve opens. Turn the burner switch "OFF"
and let programmer nish its cycle. Check to see that gas
valve closes tightly. Set the high and low gas pressure switches. Check for leaks and determine there is adequate gas pressure available at the burner for operating at full capacity. Check with the local utility if necessary. Check gas pres­sure at the pilot and the main burner. Close the manual gas valve.
B. ELECTRICAL INTERFERENCE TEST
Prior to putting the burner into service, conduct the fol­lowing test to ascertain that the ignition spark will not cause
the ame relay to pull in.
1. GAS FIRED.
Close the pilot and the main line manual gas valves. Start the burner and at time of pilot trail with just the
electrical ignition system energized, the ame relay
should not pull in (i.e. be energized). Upon completion of successful test, proceed with start-up proceedures.
Sec1:16
2. OIL FIRED
Disconnect the electrical power to the burner. Disconnect the electric oil safety shutoff valve. Reconnect electric power to the burner. Close the pilot line manual gas valve, if used. Start burner and at the time of pilot trial, with just the
electrical ignition system energized, the ame relay
should not pull in. Upon completion of successful test, disconnect power supply. Reconnect oil safety shutoff valve and turn on manual pilot gas valve. Reconnect power supply and proceed with start-up procedures.
C. GAS PILOT FLAME ADJUSTMENT
The gas pilot ame is regulated by adjusting the pres­sure setting of the pilot regulator. Normal setting is 18"
to 20" WC when the pilot is burning. The ame must be sufcient to be proven by the ame detector and ignite the main ame.
Although it is possible to visibly adjust the size of the
pilot ame, obtain a proper DC volt or microamp reading of the ame signal. The ame safeguard amplier has a meter jack for this
purpose. At initial start-up and during planned maintenance,
test the pilot ame signal, pilot turndown, and safety switch
lockout.
D. START-UP SEQUENCE
The programming control sequences the operation of all controls and components through the starting, ignition, r­ing, and shutdown cycle. The burner and control system are in starting condition when: a. The operating and high limit control (temperature or pressure) are below their cutoff setting; b. All power supply switches are closed; c. Power is present at the control panel. Refer to the manufacturers literature on programming controls and burner wiring diagrams for detailed informa­tion.
Begin starting sequence, with burner switch off, and 1. with all manual valves closed. Switch main power on. (Power On) light.
When ring oil, open the manual oil valves.2.
When ring on gas, open the main manual gas valve.3.
When ring on gas, manually reset the high and low 4.
gas pressure switches.
Place the gas / oil selector switch in position for 5. desired fuel. With all limit and operating controls calling for heat, the burner will follow the Flame Safeguard Sequence below.
When the burner motor starts, open the gas cock.6.
If ring on gas, when the main fuel lamp lights 7. indicating pilot ame proven open the the manual
leak test valve.
Time in Seconds External Operation
0 Provided the fuel valve is proven closed
the burner motor and ame safeguard
timer will start.
7 Air ow must be proven before ignition,
or the ame safeguard will lockout. If the interlock circuit opens during a ring
period, the burner will shut off and the
ame safeguard will lockout.
60 Firing on gas and providing the air ow
and low-re have been proven, the pilot
ignition transformer and ignition lamp are energized and the gas pilot valve opens to ignite the pilot.
70 Firing on oil, providing air ow and pilot
have been proven, the main fuel lamp lights. When on gas or oil, the main valve opens to ignite the burner at low
re.
80 The pilot ignition transformer is de-ener-
gized, and the main safety shut-off pilot
valve closes, scanner proves main ame
only. If the low/auto swtich is in the auto position, the following will occur:
On gas, the buttery valve and the burn­er air louvre moves to "low-re" position.
On oil, the metering pump and the burner
air louvre moves to "low-re" position.
100 "Normal run" position. Burner continues.
E. AUTOMATIC SHUTDOWN
Limit or operating controls open:
100 Fuel valves close. Main fuel lamp goes
off. Flame safeguard timer starts.
115 Flame safeguard timer and burner motor
stop. Burner is ready for start-up on the next call for heat.
F. MANUAL SHUTDOWN
1. Turn gas/oil selector switch off. Burner shuts down in Automatic Shutdown as above.
2. When burner motor stops, close all manual valves.
G. SAFETY SHUTDOWN
1. If at any time during the operating cycle a ame failure
occurs, the burner shuts down as in Automatic Shutdown,
with an additional post-purge, and the ame failure lamp
is energized.
A. The lockout switch on the ame safeguard control must be manually reset before the burner will re
again.
2. If a low water condition occurs, the burner shuts down as in Automatic Shutdown.
3. If a high or low gas pressure condition occurs while
ring on gas, the burner shuts down as in Automatic
Shutdown.
A. Condition must be corrected and the respective gas pressure switch manually reset before the burner
will re again on gas.
Sec1:17
Loading...
+ 50 hidden pages